Rural Development and Panchayat Raj Department has published Tender For Supply, Installation, Testing And Commissioning Of Fire Detection/ Alarm System In New Drug And Pharmacy Store Block At Skims. Submission Date for this Tender is 15-07-2023. Alarm Systems Tenders in soura Jammu And Kashmir. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 11-Jul-2023 | Date Extension | Date | 15-07-2023 |
Sl. No. | Item Description |
1 | Supply Installation Testing & Commissioning ofMicroprocessor based Intelligent Addressable Main Fire Alarm Control Panel with 2 Loop modules and each loop capable of supporting not less than 250 devices (detectors & modules should be in any combination) ; Loop length up to 1.5 km, 7"Color LCD touch screen display with bright colors to indicate alarms and events, 4 Nos of Integrated Ethernet Ports & 2 Nos of RS 485 for networking,programmable keyswith status indicators for individual triggering of NAC Outputs, evacuation speaker zones, AHU Modules, Damper switch, Smoke extraction Fans, Lifts.. etc. The Panel shall support 10000 history logs in the nonvolatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 24 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have seamless integration with EVAC certified Public Address System and shall be complete with all accessories. EN54 / Vds/UL Certification. |
2 | Supply, Installation, Testing and Commissioning of Active and networkable repeater panel withLCD display complete system function keys for programming and control like system reset, alarm acknowledgement, alarm silence, trouble acknowledgement etc. Shall be UL/EN/VDS Listed |
3 | SITC of Fire Graphics software with lifetime license for up to 4000 detection points to map, monitor (alarms & faults) & control all the detector and devices connected to all the Fire alarm panel. The fire Graphics software shall be loaded on the PC connected to the Fire alarm panel. The GUI based main network software shall network with other panels on True Peer-to-Peer network. It shall be capable of graphically representing each facility being monitored with floor plans and icons depicting the actual locations of the various systems, and / or sensors’ locations. It shall have the facility to change the sensitivity of any detector. The software shall have minimum 4000 DetectionPoints with option of future expansion |
4 | SITC of Addressable analogue type Heat Detectors with combination of fixed type and rate of rise of temperature feature. Detector should have inbuilt isolators as per NFPA 72 style 7 wiring requirements and have an option of both soft & hard addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/ VDs/ certification.(Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector) EN54 / Vds/UL Certification. |
5 | Supply, Installation, Testing and Commissioning of addressable multi-sensor smoke/Heat detector including mounting base with LED… etc. complete as required with 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements; Drift Compensation feature & Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values. Detector should have IP40 or better protection rating. EMC safety for detector shall be 50 V/m. Shall be UL/EN/VDS certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector |
6 | SITC of Loop Powered Sounder cum Strobe with inbuilt isolators as per NFPA 72 style 7 wiring requirements & with 32 different tone variants selection options & adjustable sound pressure by 5 levels, the sound pressure 92.1 dB(A), with flasher having Synchronized flash rate of 1 Hz and Light intensity > 2 cd, should be programmed from the panel. Shall be EN54 / Vds/UL |
7 | SITC of Addressable Manual Call Point break glass unit (Double action) with inbuilt isolators as per NFPA 72 style 7 wiring requirements, with flexible network structures & necessary fixing arrangements with key complete as required. Shall be EN 54 / Vds/UL Certification. |
8 | SITC of Addressable Control Relay Module with inbuilt isolators as per NFPA 72 style 7 wiring requirements. Relay Control module shall be used for emergency control functions including shutting down Fire dampers in AHU"s, tripping of AHU’s, Fresh air fans, Ventilation fans, tripping of Access control doors etc. Shall be EN54/ Vds Certification/UL. |
9 | SITC of Addressable Monitor Module with Inbuilt isolators for flow switches, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts or Line monitoring resistors.Shall be EN54 / Vds/UL Certification. |
10 | Response indicator for mounting on false ceiling at the entries of the cabin for indicating the operation for detectors in the above areas including Back box. |
11 | 2C 1.5 sq mm armored FRLS ZH Fire Retardant cables in ceiling with suitable clamps and screws (RED colour) |
12 | 25mm dia. MS conduit for laying of fire cable including necessary accessories like bend, junction box fixing of clamps etc., complete.The conduit shall be recessed in wall including chipping, roup plastering etc.(only for the Drops - MCPs) |