Tender For Provision Of Certain Fire Fighting System, Integrated Automatic Fire Detection Cum Alarm System For Hangars At Porbandar And Electronic Fire Detection System At Okha Under Icgae Porbandar, porbandar-Goa

Military Engineer Services-MES has published Tender For Provision Of Certain Fire Fighting System, Integrated Automatic Fire Detection Cum Alarm System For Hangars At Porbandar And Electronic Fire Detection System At Okha Under Icgae Porbandar. Submission Date for this Tender is 14-07-2023. Flame Detectors Tenders in porbandar Goa. Bidders can get complete Tender details and download the document.




Tender Notice

38306124
Corrigendum : Tender For Provision Of Certain Fire Fighting System, Integrated Automatic Fire Detection Cum Alarm System For Hangars At Porbandar And Electronic Fire Detection System At Okha Under Icgae Porbandar
Open Tender
Indian
Goa
porbandar
14-07-2023

Tender Details

Provision Of Certain Fire Fighting System, Integrated Automatic Fire Detection Cum Alarm System For Hangars At Porbandar And Electronic Fire Detection System At Okha Under Icgae Porbandar

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 07-Jul-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 14-07-2023

Key Value

Document Fees
INR 2000 /-
EMD
INR 345000.0 /-
Tender Value
INR 2.70 Crore /-

BOQ Items

Name of Work: PROVISION OF CERTAIN FIRE FIGHTING SYSTEM, INTEGRATED AUTOMATIC FIRE DETECTION CUM ALARM SYSTEM FOR HANGARS AT PORBANDAR AND ELECTRONIC FIRE DETECTION SYSTEM AT OKHA UNDER ICGAE PORBANDAR
Sl. No. Item Description
1Site Clearance in soft loose soil complete all as specified and directed.
2Excavation in trenches not exc. 1.5m wide and not exc. 1.5m in depth for foundation etc or for shafts, wells, cesspits, manholes pier holes etc not exc. 10sqm on plan and not exc 1.5m in depth and getting out in hard/dense soil soil complete all as specified and directed.
3Returning filling in soil and including spreading leveling watering and well ramming in layers n.exc. 25 cm thick complete all as specified and directed.
4Removing excavated soil to a distance n.exc. 50 mtr and depositing where directed at a level n.exc. 1.5m above the starting points complete all specified and directed.
5Supply of Moorum/ red bajri Spreading and levelling in layers n exc. 25 cm thick and well ramming including watering as requiredcomplete all specified and directed.
6M/L for plain cement concrete (PCC) in foundation using 1:4:8 mix type D-2 using 40mm graded aggregate for foundation/ support complete all specified and directed.
7M&L for RCC Foundations, including rafts, footings, foundation beams; plinth beams; bases for columns, etc.; basement slabs, under-reamed piles and mass concrete in M20 grade (20mm graded aggregate) for foundation complete all specified and directed.
8S&F Stairs (framed) including stringers, treades, landing, balusters, hand rails etc. in cluding cleats, brackets, etc fixing complete using Fe-410-W (Gde E-250) quality A complete all as specified and directed.
9S&F Plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment etc fixing complete using Fe-410-W (Gde E-250) quality A complete all as specified and directed.
10S&F Mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, exc 10cm and n exc 15cm long with 16 to 20 mm dia of neckcomplete all as specified and directed.
11M&L preparation of new steel surfaces of any description, over 10cm in width or girth,one coat of red oxide and two coats of synthetic enamel paint complete all as specified and directed.
12Supply & Install Fire pump electrically driven horizontal end Suction, centrifugal type confirming to IS- 12469 :1988 with CI Casing , bronze impeller and Stainless steel shaft mounted on heavy duty bearings Suitable for continuous operation with "range of operation" 0 % to 150 % of rated capacity for 440 V , 3 Phase. 50 Hz 70m Head, 1620 LPM discharge complete all as specified and directed. NOTES: [i] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required [ii] Suitable cement concrete foundation duly plastered with antivibration pads. Make: Kirloskar, SPP Pumps, Precision Engineering Works [iii] The quoted rate shall include providing and fixing of vibration pad, common base plate, foundation bolts, grouting etc. [iv] Pump sets shall be as per NFPA-20. [v] Pump sets shall be installed as per IS 15301: 2003
13All as per item no 12.00 but 2850 LPM discharge complete all as specified and directed.
14Supply & install Fire pump diesel engine drivenhorizontal end suction, centrifugal type confirming to IS- 12469 1988 with CI casing , bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for continuous operation with "range of operation" 0 % to 150 % of rated capacity for 440 V , 3 phase, 50 Hz AC supply 70 m Head1620 LPM discharge complete all as specified and directed. “NOTES:” [i] Suitable HP, 1800 RPM diesel engine, water cooled with radiator, conforming to IS 10002: 1981, complete with auto starting mechanism, 12/24 V electric starting equipment, diesel tank, exhaust pipe extended up to 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour, etc. as required. [ii] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required. [iii] Suitable cement concrete foundation duly plastered with anti vibration pads. [iv] The pump shall be capable of furnishing not less than 150% rated capacity at a head of not less than 65% of the rated head. [v] The shut-off head shall not exceed 120% of rated head. [vi] The coupling guard shall be of zero access type. [vii] The quoted rate shall include providing and fixing of vibration pad, common base plate, foundation bolts, grouting etc. [viii] Pump sets shall be as per NFPA-20. [ix] Pump sets shall be installed as per IS 15301: 2003.
15All as per item no 14.00 but 2850 LPM discharge complete all as specified and directed.
16Supply & Fix Jockey pump horizontal end suction centrifugal type Confirming to IS- 12469: 1988 with CI casing , bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for automatic operation with non-over loading power characteristics for frequent start / stop operations for 440 V , 3 phase, 50 Hz 70 m head 180 LPM discharge complete all as specified and directed. Make: Kirloskar, SPP Pumps, Precision Engineering Works Notes: [i] Suitable HP squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on 3- Ph,415 V, 50 Hz AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class "F" insulation, conforming to IS 12615: 2018. [ii] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required. [iii] Suitable cement concrete foundation duly plastered with anti vibration pads. [iv] The pump shall be capable of furnishing not less than 150% rated capacity at a head of not less than 65% of the rated head. [v] The shut-off head shall not exceed 120% of rated head. [vi] The coupling guard shall be of zero access type. [vii] The quoted rate shall include providing and fixing of vibration pad, common base plate, foundation bolts, grouting etc [viii] Pump sets shall be as per NFPA-20 [ix] Pump sets shall be installed as per IS 15301: 2003 [x] The pumps shall be suitable for automatic operation.
17All as per item no 16.00 but 90 m head 180 LPM discharge complete all as specified and directed.
18M & L for MS ERW PIPE of following size
19200 mm dia
20150mm
21100 mm dia
2280 mm dia
2365 mm dia
2425 mm dia
25Supply and fix Valves, Sluice, flanged of class 1.6 PN , dia.
26200 mm
27150 mm
28100 mm
2980 mm
30Supply and fixing NRV of folowing size, dia
31200 mm
32150 mm
33100 mm
3480 mm
35Supply and fix Foot Valve conforming to IS 4038, of following dia .
36150 mm
37100 mm
38Supply and fix Foot Valve ball type, 150 mmdia flange type including S/S nut bolt washers etc complete as specified and directed.
39Supply and fix Air cushioning tank (Air vessel) 250mm dia x 1000mm high with dished top, made of minimum 6mm thick MS pipe /plate complete with 20mm dia. Brass air valve (ball type), 20mm dia stop valve, pressure gauge with brass stop cock, nipple tees elbows and all accessories complete as specified and directed.
40Supply and fix Mild Steel class "C" diesel pump exhaust pipe 150mm dia with one layer of 10mm thick asbestos rope insulation and including all fitting clamp/ structural steel supports complete as specified and directed.
41Supply and fix Gun metal fire brigade in let connection for connecting to external fire hydrant ring main consisting of two nos 63mm dia instantaneous type male coupling with built in check valves and 150mm dia, flanged outlet complete with all accessories as specified and directed.
42Supply and fix Pressure gauge 100 mm dia with ball valve of pressure 25 Kg/Sqcm complete all as specified and directed.
43Supply and fix Pressure gauge 100 mm dia with ball valve of pressure 0-106 Kg/Sqcm complete all as specified and directed.
44Supply and fix Cast Iron Air Valves with single air Outlets, conforming to IS 14845 of size 50 mm dia bore and fixing up in Cast Iron Water supply mains of size 50 mm dia complete all as specified and directed.
45Supply & fix fire hydrant landing valve type A (Single head outlet) of 63 mm dia conforming to IS 5290 complete all as specified and directed.
46Supply and fix fire hydrant stand post with provn of single outlet conforming to IS 908 complete all as specified and directed.
47Supply and fix fire hydrant Post / Stand Post 80mm dia GI / MS both flanged type 1.5m Height complete all as specified and directed.
48Supply and fix Hose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard complete all as specified and directed.
49Supply and fix 63 mm dia gun metal branch pipe with 12.5 mm nozzle conforming to IS 903 complete all as specified and directed.
50Supply and fix branch pipe with nozzle of 15 mm dia for hose reel conforming to IS 8090 complete all as specified and directed.
51Supply and fix 63 mm dia 15 meter long hose conforming to IS 636 complete with male and female coupling conforming to IS 903 complete all as specified and directed.
52Supply and fix 63 mm dia 30 meter long hose conforming to IS 636 complete with male and female coupling conforming to IS 903 complete all as specified and directed.
53Supply and fix 100 mm bore hand operated butterfly valve of pressure not less than 15 Kg / Sqcm with complete set complete all as specified and directed.
54Supply and fix 80mm bore hand operated butterfly valve of pressure not less than 15 Kg / Sqcm with complete set complete all as specified and directed.
55M & L for gate valve of following size
5625 mm dia
5750 mm dia
58Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor, cubical compartmental type "Motor Control Center"" (MCC) of suitable size, conforming to IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 54 protection made out of 2.00 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete as specified and directed. The MCC shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L+N) of copper busbar of rated capacity 630 A covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection [B] INCOMING [i] 400 A, 4P, 415 VATS (WCR = 35 kA for 3 cycles)-01 Nos. [ii] 400 A, 415 VI cw =I cw (1 sec)=50 1 sec)= 35kA ,50 l Hz VI ca =100% electrical draw-out type FP MCCB, conforming to IS/IEC 60947-2 & 3, having fully rated neutral with inbuilt protection, no derating up to 50° C, microprocessor based trip systems with thermal memory providing overload, short-circuit, instantaneous & earth- fault protection, zone selective interlocking, pre-trip alarm & individual fault indicating LEDs-01 Nos. [iii] CI 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Run hrs. On hrs & interrupts-01 Nos. [iv] LED phase indicators (Red, Yellow, Blue)- 01 Set
59[C] OUTGOING [i] 200 A, 415 V, Ics = 100% Icu= 25 KA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting ( 0.7 -1* ln) , adjustable short- circuit setting (5 - 10lr) , adjustable neutral protection (N, N/2, OFF) front indication LEDs (Ready, Overload and pre-alarm & Overload)-02 Nos. [for electric driven main fire pump] [ii] Fully automatic soft starter suitable for electric driven main pump having adaptive acceleration control, built-in RTD & thermistor inputs programmable auto start/stop, emergency run operation, fully programmable overload trip, etc. complete with contactors, push button, LED type indicators, auto/manual selector switch, current sensing type single phase preventer complete with all accessories and wiring etc.- 02 Nos. [for electric driven main fire pump] [iii] 32 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor-based trip unit, adjustable overload setting (0.71 X In), adjustable short- circuit setting (5-10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-02 Nos. [for jockey pump] [iv] Fully automatic DOL starter, suitable for the jockey pump, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc.- 02 Nos. [for jockey pump] [v] 40 A, 415 V, Ics = 100% Icu = 36 KA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.71 X In), adjustable short- circuit setting (5-10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-02 Nos. [for booster pump] [vi] Fully automatic DOL starter, suitable for the jockey pump, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc.- 02 Nos. [for booster pump] [vii] ISI marked 40 A, 300 mA, 415 V, 50 Hz, FP RCBO for AC applications, conforming to IS 12640 (Part-2)- 2016, having front face indication for earth leakage fault, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters-02 Nos. [for fire lift]
60[viii] Control for diesel engine comprising of automatic / manual selector switch & three attempts starting device, timers and relays as required, push buttons, start/stop in manual mode, indicating lamp for high/low lubrication oil pressure, high water temperature and engine on indication, battery charger suitable for 12 V/24 V DC with boost and trickle selector switch, 0-30 V DC voltmeter and 0-20 A DC ammeter complete with all standard relays and accessories for automatic operation of the diesel engine - 02 Nos. [for Diesel pump] [ix] 32 A, 10 kA, 230 V, 50 Hz, SPN MCB-03 Nos. [x] CI 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts-04 Nos. [xi] LED phase indicators (Red, Yellow, Blue)-04 Set NOTES: [i] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, GADs, etc. for approval of the Engineer-in-Charge. (ii) The control circuit for the main pump sets shall be designed for automatic operation ie whenever the pressure reduces in the system, the main pump shall automatically start. The stopping of the pump will be manual. (iii) The control circuit for the jockey pump set shall be designed that whenever pressure reduces the pump shall start automatically and when pressure reaches rated system pressure then it should automatically switch off. Make: Legrand/L&T(Ascent Engineers)/BCH/Siemens
61All as per item no 40.00 but 60 HP all as specified and directed. The MCC shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L+N) of copper busbar of rated capacity 500 A covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection [B] INCOMING [i] 315 A, 4P, 415 VATS (WCR = 35 kA for 3 cycles)-01 Nos. [ii] 315 A, 415 VI cw =I cw (1 sec)=50 1 sec)= 35kA ,50 l Hz VI ca =100% electrical draw-out type FP MCCB, conforming to IS/IEC 60947-2 & 3, having fully rated neutral with inbuilt protection, no derating up to 50° C, microprocessor based trip systems with thermal memory providing overload, short-circuit, instantaneous & earth- fault protection, zone selective interlocking, pre-trip alarm & individual fault indicating LEDs-01 Nos. [iii] CI 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Run hrs. On hrs & interrupts-01 Nos. [iv] LED phase indicators (Red, Yellow, Blue)- 01 Set [C] OUTGOING [i] 160 A, 415 V, Ics = 100% Icu= 25 KA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting ( 0.7 -1* ln) , adjustable short- circuit setting (5 - 10lr) , adjustable neutral protection (N, N/2, OFF)front indication LEDs (Ready, Overload and pre-alarm & Overload)-02 Nos. [for electric driven main fire pump] [ii] Fully automatic soft starter suitable for electric driven main pump having adaptive acceleration control, built-in RTD & thermistor inputs programmable auto start/stop, emergency run operation, fully programmable overload trip, etc. complete with contactors, push button, LED type indicators, auto/manual selector switch, current sensing type single phase preventer complete with all accessories and wiring etc.- 02 Nos. [for electric driven main fire pump]
62[iii] 32 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.71 X In), adjustable short- circuit setting (5-10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-02 Nos. [for jockey pump] [iv] Fully automatic DOL starter, suitable for the jockey pump, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc.- 02 Nos. [for jockey pump] [v] 40 A, 415 V, Ics = 100% Icu = 36 KA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.71 X In), adjustable short- circuit setting (5-10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload)-02 Nos. [for booster pump] [vi] Fully automatic DOL starter, suitable for the jockey pump, complete with contactors, push button, LED type indicators, auto/manual selector switch, overload protection, current sensing type single phase preventer complete with all accessories and wiring etc.- 02 Nos. [for booster pump] [vii] ISI marked 40 A, 300 mA, 415 V, 50 Hz, FP RCBO for AC applications, conforming to IS 12640 (Part-2)- 2016, having front face indication for earth leakage fault, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters-02 Nos. [for fire lift] [viii] Control for diesel engine comprising of automatic / manual selector switch & three attempts starting device, timers and relays as required, push buttons, start/stop in manual mode, indicating lamp for high/low lubrication oil pressure, high water temperature and engine on indication, battery charger suitable for 12 V/24 V DC with boost and trickle selector switch, 0-30 V DC voltmeter and 0-20 A DC ammeter complete with all standard relays and accessories for automatic operation of the diesel engine - 02 Nos. [for Diesel pump] [ix] 32 A, 10 kA, 230 V, 50 Hz, SPN MCB-03 Nos. [x] CI 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts-04 Nos. [xi] LED phase indicators (Red, Yellow, Blue)-04 Set
63NOTES: [i] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, GADs, etc. for approval of the Engineer-in-Charge. (ii) The control circuit for the main pump sets shall be designed for automatic operation ie whenever the pressure reduces in the system, the main pump shall automatically start. The stopping of the pump will be manual. (iii) The control circuit for the jockey pump set shall be designed that whenever pressure reduces the pump shall start automatically and when pressure reaches rated system pressure then it should automatically switch off Make: Legrand/L&T(Ascent Engineers)/BCH/Siemens
64M&L Earthing complete with Copper earth electrode 30 cm x 30 cm x 3.15 mm as earthing lead burried directly in ground vertically to a depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level connected to copper strip 20X3mm as earthing lead by means of bolts,nuts, check nuts and washer etc made of copper/brass including 40 mm bore GI pipe medium grade up to 7.5 metres long all as shown in electrcial plate No.3 of SSR Part I 2009 and as specified or indicated and testing on completion including excavation/ earth work in any type of strata, PCC (1:3:6) type C1 earthing chamber, precast RCC slab 50 mm thick in reinforced cement concrete (1:2:4) type B1 reinforced with welded steel wire fabric (XPM weight not less than 4 Kg/Sqm), cast iron frame, funnel with wire mesh, 20 mm bore medium grade GI watering pipe, lugs, 15 mm bore medium grade GI protection pipe, test point etc. complete all as specified and as directed. Note: (i) Item includes the cost of 7.5 metre GI pipe for protection of earth lead. Any aditional in length shall be adjusted through deviation order. (ii) Item includes trhe cost of 7.5 metre GI earth lead. Any additional in length shall be measured and paid under respective item of this Schdule.
65S&F Special foam making branch pipe MOC aluminium alloy having 63mm male instantaneous inlet 227 LPM foam water solution capacity at 7 kg/cm2 compl . With pickup tube complete all as specified and directed..
66Supply, fixing, testing ang commissioning Foam com water Monitor of 1750 LPM with swivel action and trolley mounted 200 Ltrs stanless steel 304 tank with 3% AFFF Foam (UL Listed). The monitor has welded carbon steel. (a) The monitor shall have 360 degree rotation. Parts in contact with foam shall be made of bronze, and hose not in contact with foam shall be hot dip galvanized complete all as specified and directed. NOTES: a) All steel parts are hot dip galvanized and epoxy painted. The vertical and horizontal rotation shall be through corrosion resistant bronze swiveling joint with double row of stainless steel ball bearing. b) The monitor shall have 360 degree rotation. Parts in contact with foam shall be made of bronze, and those not in contact shall be hott dip galvanised. Pick up tube shall be 3.0 M with brass dip pipe. Nozzle shall have AQUA Nozzle with pick up tube.
67S&F Mobile Wheeled Foam Unit with stainless steel tank of 220 Lts capacity with 3% AFFF Foam rated 7 bar pressure complete all as specified and directed. NOTES: a) Aluminium inductor, aluminium branch pipe and 1 no. 15 M x 63 mm dia hose complete with SS couplings.
68Supply and fixActive Fire Alarm Control Panel Repeater. Active Repeater should display the operational state of the control panel using 80 character LCD display and the 7 LED satus indicators. Repeater panel should have key operated "Access Enable" switch for control functions. Individual buttons should be provided for System Reset, Mute, Accept, Sound Alarms, Silence / Re-sound Alarms and Self test. Panel should connects to RS-485 peripheral bus. Repeater should be operated on 24 VDC power supply complete all as specified and directed.
69Supply, installation, testing and commissioning of microprocessor-based, true peer-to-peer networkable, double loop addressable Fire Alarm Control Panel (FACP) with its own microcontroller memory, communication module, fire device loop interface cards for intelligent initiating and indicating devices and peer-to- peer networkable with other addressable fire alarm panels with required accessories complete all as specified and directed by the engineer-in-charge. Make: Siemens/ABB/Honeywell [i] The FACP shall have one to ten isolated intelligent Signalling Line Circuits (SLCs) capable of connecting up to 99 detectors and 99 modules per loop. [ii] The FACP shall have a degrade mode and the loops shall work in degrade mode in case of the CPU failure [iii] The FACP shall have 640 character LCD backlit display/ Touch Screen display, full QWETRY program keypad. LED indicators viz. power, fire alarm; supervisory: system trouble; other event, signals silenced; point disabled; CPU failure; controls active; etc. membrane switch controls viz. acknowledge, signal silence, drill; system reset, lamp test, etc [iv] The FACP shall have four access levels, flash EPROM, 240 VAC power supply, automatic battery charger, 24 V sealed lead acid batteries, sufficient for 24 hrs normal working and 30 min in alarm condition.
70[v] The FACP shall have manual sensitivity adjustment up to nine levels, built-in alarm; trouble; security and supervisory relays, history file with 4000-event capacity in non-volatile memory plus separate 1000-event alarm-only file, keypad operation, LCD unit to indicate fire/fault signal of individual unit, in built printer to log all incoming data, etc. [vi] The FACP shall have integrated 8 channel digital voice evacuation system controller capable of broadcasting evacuation messages on the same peer-to-peer network, fire fighter"s telephone two-way communication system capable of supervising all the speaker circuits with adequate zone control and accessories etc. NOTES: [i] The FACP shall be servicable by any system integrator & shall not have dependency on specific system integrator. [ii] The FACP shall have feature to "ADD", "EDIT" & "DELETE" field devices like detectors & modules without dependency on PC/Software/Special tool/dongle
71All as per item no. 47.00 butcapacity from 99 detectors & 99 modules upto 200 detector complete all as specified and directed.
72Supply, installation, testing, commissioning ofmanual call point, resetting type with relay modules including all accessories like junction boxs, glands, terminating lugs etc complete all as specified and directed.
73Supply, laying & testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of size 1100 Volts grade for the following size : 3 Core 1.5 sqmm
746 Core 1.5 sqmm
75Supply and fixing MS conduit of 20 mm dia fixed under wall/slab with necessary clamps etc complete all as specified and directed.
76All as per item no 51.00 but25mm dia.
77M & L for pressure switch suitable for pressure range 0- 14 bar having die cast aluminium construction and SS sensing element with ball valve, fittings viz. unions, collars, reducers etc. for fire pump sets complete as specified and directed by the engineer- in-charge. Make: Danfoss/ Potter/ System Sensor
78M & L for flowswitch of following dia :
7980 mm (for Jocky Pump)
80100 mm dia
81Supply and install addressable control module complete all as specified and directed.
82Supply and install addressable monitormodule complete all as specified and directed.
83Supply and fix short circiut isolaters complete all as specified and directed.
84Supply and fix remote response indicators complete all as specified and directed.
85Supply ,installing,testing and commissioning of sounder cum strobe with control module complete all as specified and directed.
86Supply ,installing,testing and commissioning of mulispectrum infra-Red (Triple IR + Visible) detectors based on Quad Band technology complete all as specified and directed. Make:- Honeywell or equivalent
87Supply and fix Active Fire Alarm Control Panel Repeater. Active Repeater should display the operational state of the control panel using 80 character LCD display and the 7 LED status indicators. Repeater panel should have key operated "Access Enable" switch for control functions. Individual buttons should be provided for System Reset, Mute, Accept, Sound Alarms, Silence / Re-sound Alarms and Self test. Panel should connects to RS-485 peripheral bus. Repeater should be operated on 24 VDC power supply. Including Power supply unit should have capacity to operate on 230 volts AC mains input & shall provide 24 VDC, 3 Amp output, shall also support battery backup in case of AC mains failure & should have built in charging circuit for batterys. Power supply unit should have enclosure with lock & key included 12 VDC / 7 AH Battery-04 Nos. Make: Siemens/ABB/Honeywell
88Supply and fix Detectors Complying with and type certified to EN-45 Addressablemultisensor detector with heat and smoke combination intelligence as per IS: 11360 complete all as specified and directed.
89Supply and fix Detectors Complying with and type certified to EN-45 Addressable type heat detector with base with rate of rise cum fixed temperature as per IS: 2175 complete all as specified and directed.
90Supply and fix Pipe Support for all types of pipes including hangars / fastners / elbows/ supports / tees complete all as specified and directed.
91Supply, Installation,Testing & commissioning of MECHANICAL FOAM type fire extinguisher of 9 Ltrs confirm to IS : 15683, with ISI marked/TAC approved fitted with required accessories including wall suspension brackets complete all as specified and directed.
92Supply, Installation,Testing & commissioning of Trolley Mounted MECHANICAL FOAM type fire extinguisher of 50 Ltrs Kg confirm to IS : 15683, with ISI marked/TAC approved fitted with required accessories including wall suspension brackets complete all as specified and directed.
93Supply, Installation,Testing & commissioning of DRY CHEMICAL POWDER (ABC) stored pressure type fire extinguisher of 6 Kg confirm to IS : 15683, with ISI marked/TAC approved fitted with required accessories including wall suspension brackets complete all as specified and directed.
94Supply, Installation,Testing & commissioning of Trolley Mounted DRY CHEMICAL POWDER (ABC) stored pressure type fire extinguisher of 25 Kg confirm to IS : 16087, with ISI marked/TAC approved fitted with required accessories including wall suspension brackets.
95Supply, Installation,Testing & commissioning of Carbon Dioxide (Co2) type fire extinguisher of 4.5 Kg confirm to IS : 15683, with ISI marked/TAC approved fitted with required accessories including wall suspension bracketscomplete all as specified and as directed.
96Supply, Installation,Testing & commissioning of trolly mounted Carbon Dioxide (Co2) type fire extinguisher of 22.5 Kg confirm to IS : 15683, with ISI marked/TAC approved fitted with required accessories including wall suspension brackets complete all as specified and as directed.
97Supply, Installation,Testing & commissioning ofDRY CHEMICAL POWDER (ABC) stored pressure type fire extinguisher of 9 Kg confirm to IS : 15683, with ISI marked/TAC approved fitted with required accessories including wall suspension brackets complete all as specified and as directed.
98Supply and installation at approved locationapproved make Fire sand bucket of 24 gauge galvanized steel sheet, each set shall have 4 buckets with stand & Showel etc, complete all as specified and as directed.
99Supply, laying & testing cable XLPE insulated, armoured,heavy duty electriccables with aluminium conductor, 1100 volts grade, cross sectional area185 sqmm3.5 corecomplete all as specified and as directed.
100Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded Alumiium conductor of size 70sq mm 3.5 corecomplete all as specified and as directed.
101Taking down old unserviceable GI pipe of size 150 mm complete all as directed.
102Taking down old unserviceable Sluice valve and hydrant valve complete all as directed.
103Taking down old unserviceable Fire hydrant box with hose pipe and accessories complete all as directed.
104Taking downand old unserviceable centrifugal pump of 25 HP capacity incl dismanlting of suction pipe complete all as directed.
105S&F Existing escape light route indicator in case of fire complete all as specified and directed.
106Supply and lay Double Walled Corrugated (DWC) Pipes having corrugation on the outer wall and plain surface on the inner wall confirming to IS14930 (Part-II) for protection of UG cables size 110/95 mm outer dia laid in trenches/ road/ drain or fixed along wall, poles or laid under floor all as specified and as directed.
107Supply and fix Gun metal 4 way fire brigade in let connection four nos 63mm dia gun metal female connection in cast iron main unit complete with all accessories complete all as specified and directed.
108Supply and fix Gun metal fire brigade in let connection for connecting to external fire hydrant ring main consisting of two nos 63mm dia instantaneous type male coupling with built in check valves and 150mm dia, flanged outlet complete with all accessories complete all as specified and directed.
109Supply and fix hose reel of 20 mm dia and 30 meter length conforming to IS 5132 complete all as specified and directed.
110S&F wall mounted LED emergency Exit signage luminaire Light up using regular mains supply comes with a unique rechargeable Ni-Cd battery capable of emergency back up upto 02 hours complete all as specified and directed. (Cat No BESL 03 LED SSD WBBMake Bajaj or equivalent to Bajaj/havells)
111Supply and fix MS flanged pipe 150 mm NB heavy duty duly painted with 2 coats of synthetic enamel paint over coat of zinc chromate primer etc all as specified and directed.
112Supply and fix MS flanged pipe 100 mm NB heavy duty duly painted with 2 coats of synthetic enamel paint over coat of zinc chromate primer etc all as specified and directed.
113Supply and fix MS flanged pipe 65 mm NB heavy duty for multi storied building duly painted with 2 coats of synthetic enamel paint over coat of zinc chromate primer complete all as specified and directed.
114Supply and fix Fire Alarm sounders / Sirens electronic type horizontal single stage continuous normal operation for at least 50 minutes with sound level 65 DB to 120 DB measured at 1.5 meter with sound output variation of + 5 DB for 2 KM range complete all as specified and directed.
115S & F for Junction box, with cover and outlets for rigid steel ERW conduit of size 25 mm dia with complete all as specified and as directed.
116M & L for fabrication, supply and installation of MS pedastal type fire point made out of angle iron frame (50x5mm) free standing on ground/hard standing suitable for provision of hanging and including 4 Nos fire buckets 13 ltrs capacity each complete with painting with post office red colour including red oxide as perimer and writing letters FIRE on outer surafce of fire buckets, writing FIRE POINT on fire stand all as per IS specification complete all as specified and as directed.
117Supply, Installation,Testing & commissioning LT feeder Pillor Box indoor type with CRCA sheet mounting on angle iron frame with epoxy paintincluding Copper Bus Bar of capacity 315 Amp complete with labour charge including PCC work i) MCCBof capacity 200A, 4p,35KA, 415V, 50Hz- 01 Nos (Incomming) ii) MCCBs of capacity 40 A 415V, 50 Hz, 25 KA -02 Nos (outgoing) iii) MCCBs of capacity 63 A 415V, 50 Hz, 25 KA -02 Nos (outgoing) iv) Voltmeter 0- 500 v -01 Nos v) Ammeter of Capacity 200 A - 01 Nos vi)Phase indicator lamp RYB - 01 set of three
118Supply and Fix WideBand IR Infrared combined with Ultraviolet Flame Detector with Detection range greater than 60 m (200 feet) to 0.1 m (1 sq. ft.) heptane fire, Selectable detection sensitivities, Solar blind 90° cone-of-vision, Dual microprocessors, Real-time clock for accurate time of events, Built-in RS-485 ModBus communication, Built-in non-isolated 4-20 mA analog output, Alarm, Fault and Fire Verification relays, FM hazardous area, Ex d ATEX, CU-TR, NMETRO approved, Meets SIL 2 requirements, EN54-10:2002 Certified, Detector should be capable to detects hydrocarbon and non-hydrocarbon fuel fires complete all as specified and directed.
119M & L for point wiring using lSI marked 1.1 kV grade single core FR LSH flexible cable, conforming to IS: 694-1990, having multi-drawn thin strands of electrolytic copper conductors, conforming.to IS: 8130-1984 and insulation conforming to IS: 5831-1984, for phase, neutral and earth continuity conductor connecting to earth dolly, drawn in and including not less than 25 mm NB PVC medium grade concealed conduits,conforming to IS: 9537 (Part 3)- 1983, colour-coded as specified in IS: 11353-1985, including factory made sunken,galvanized, not less than 1.00 mm thick modular flush sheet metal enclosure having top, bottom, side and back-wall knockout for conduit entry from any direction,conforming to IS: 14772- 2000 and suitable for modular cover-plates complete all as specified in IS: 732-1989 and directed. NOTE: Circuit wire from DB to switch boards shall be included in the quoted rate.No additional payment will be paid to the contractor for the circuit submain. a) One light point controlled by one switch.
120One Ceiling Fan point controlled by one switch.
121One exhaust Fan point controlled by one switch.
122One 5amps Socket outlet on independent board controlled by one switch
123All as per Item No. 93 above but power point wiring with 2.5 sq.mm single core PVC insulated cable with stranded copper conductor for one switch socket outlet, 15 amps multipurpose on independent board including PVC unsheathed copper conductor of 2.5 sqmm as earth wire all as specifiedand directed.
124S & F Modular switch 1 way 6 A,1 module ISI marked complete all as specified and directed. Make :- Legrand (Arteor)/ Schneider (Zencelo)/ Hager (Berker)
125S & F Modular switch 1 way 16 A, 1 module ISI marked complete all as specified and directed. Make :- Legrand (Arteor)/ Schneider (Zencelo)/ Hager (Berker)
126S & F Socket, 6A-2/3 pin combined 2 module ISI marked complete all as specified and directed. Make :- Legrand (Arteor)/ Schneider (Zencelo)/ Hager (Berker)
127S & F Socket, 16A-6 pin combined 2 module ISI marked complete all as specified and directed Make :- Legrand (Arteor)/ Schneider (Zencelo)/ Hager (Berker)
128S & F Fan regulator 120W 2 module complete all as specified and directed. Make :- Legrand (Arteor)/ Schneider (Zencelo)/ Hager (Berker)
129S & F Ceiling rose, surface Bakelite, 65x50mm three terminal 230Volts, AC single phase complete all as specified and as directed.Make :- Legrand (Arteor)/ Schneider (Zencelo)/ Hager (Berker)
130Supply and fixing, connecting and testing MCB Single Pole (MCB SP) 220volts of capacity 6 to 40 Amps, 10Ka C curve complete all as specified and directed. Make :- Legrand (Arteor)/ Schneider (Zencelo)/ Hager (Berker)
131Supply and fixing, connecting and testing MCB Single Pole and neutral (MCB SPN) 220volts of capacity 6 to 40 Amps, 10Ka C curve complete all as specified and directed. Make :- Legrand (Arteor)/ Schneider (Zencelo)/ Hager (Berker)
132M&L for sub main wiring (concealed type) complete with four runs of 1100 volts grade heavy duty cable PVC insulated & unsheathed copper conductor, multi- stranded single core of 4 Sqmm including with one run of 4 Sqmm single core PVC insulated & unsheathed multistranded copper conductor cable as earth continuity conductor, drawn in rigid non-metallic PVC conduit of suitable dia, conduct fitting & accessories all as specified and directed.Note : 4 runs of cable, 1 run of earth wire and one run of conduit shall be measured as one length.
133M & L for Earthing complete with Galvanized steel earth plate electrode of size 600mmX600mm, 6.00 mm thick buried directly in ground vertically to a depth not less than 2.25 metres below the normal ground level with top edge of the plate not less than 1.5 m below normal GL and connected to galvanised earth lead strip 32x6 dia by means of bolts, nuts, checknuts and washers of galvanised ironor steel allall as shown in Electrical Plate No.3 onnecting to earthing test point, including necessary earth work in any type of soil, PCC earth chamber made in PCC 1:3:6 type C1 (using 20mm graded aggregate), common salt, charcoal, CI funnel, earth pit cover in RCC 1:2:4 type B1(using 20mm graded aggregates), with 8mm CTD bars @ 100mm c/c in both ways, including necessary form work complete including necessry test on completionall as specified and as directed. Note : The unit rate shall also include for excavation, earth work in hard/dense soil PCC (1:3:6) type C1 pit, RCC cover slab, GI funnel with 20 mm dia watering pipe, wire mesh, 40mm dia light grade GI protection pipe for earth lead etc., complete all as specified and as directed.
134Supply and fixing LED lights fitting 20W, 230V, with heavy duty driver having THD<10% with powder coated metallic housing and high quality poly carbonate diffuser connecting up with three core flexible copper conductor cable of suitable size from ceiling rose all complete as specified and directed. Make:Wipro (LL20-221-XXX-65N3/ Philips (BN108C LED 20S PSU NW WH)/Osram (LUXSMART LED BAT 22W 830)
135Supply and Fixing surface mounted LED batten 10W with extruded aluminum housing heavy duty integrated electronic driver, surge protection more than 2 KA and THD<10% all complete as specified and directed. Make:Wipro / Philips /Osram
136Supply and fixing LED security light fitting 25 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection all complete as specified and directed. Make:Wipro / Philips /Osram
137S & F energy efficient BLDC high-speed ceiling fan having 1200 mm blade sweep, air-flow not less than 210 CMM, operating voltage 220-240 V and frequency 50 Hz, including a down road of suitable size and electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fan complete all as specified and directed.. Make: Almonard/Havells/khaitan
138S & F energy efficient non-metallic fresh air fan having blade sweep 250 mm, air delivery not less than 860 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed. Make: Crompton Cat-Part No. VENTILUS 10" or equivalent model of Usha, Havells or BAJAJ.
139S & F single pole & neutral DB (double door) 240 V, 4 way , conforming to IEC 61439- 3, suitable for flush mounting with 100 A insulated & shrouded copper busbar for each phase, fully insulated & shrouded neutral bar, earth bar, wire set and cable ties for cable management, IP 43 & IK 09 protection with provision for MCB SPN as incomer and SP MCBs as outgoing, all complete as specified and directed. Make :Legrand (Arteor)/ Schneider (Zencelo)/ Hager Notes:- [I] MCBsshall be measured and paid in relevant items.
140Material and Labour for DI fittings and fixtures Bends (any type, radius and angle) tapers any type, (straight, bend, increasing, decreasing or double socket etc.) Tee pieces single branch. "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs upto 150mm bore complete as specified and directed..
141M & L for construction of RCC UG SUMP of 150000 ltr capacity for fire fighting with RCC framed structure (M-35 design mix) in permanent specification including all earth work and excavation complete all as shown on drawing and all specified and as directed.
142M & L for construction of PUMP HOUSE single storey building with RCC framed structure (M-30 design mix) in permanent specification (Height 3.6 m) complete all as shown on drawing and all specified and as directed.