Tender For Rate Contract For The Work Of Sitc Of Addressable Intelligent Fire Detection System, Novec 1230 Fire Suppression System And Vesda System For Phase Ix.2 Project At T.E. Mhs Bhavan Pune (Maharashtra) And T.E. Shahibaug Ahmedabad (Gujrat), pune-Maharashtra

Bharat Sanchar Nigam Limited-BSNL has published Tender For Rate Contract For The Work Of Sitc Of Addressable Intelligent Fire Detection System, Novec 1230 Fire Suppression System And Vesda System For Phase Ix.2 Project At T.E. Mhs Bhavan Pune (Maharashtra) And T.E. Shahibaug Ahmedabad (Gujrat). Submission Date for this Tender is 01-07-2023. Flame Detectors Tenders in pune Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

38235872
Corrigendum : Tender For Rate Contract For The Work Of Sitc Of Addressable Intelligent Fire Detection System, Novec 1230 Fire Suppression System And Vesda System For Phase Ix.2 Project At T.E. Mhs Bhavan Pune (Maharashtra) And T.E. Shahibaug Ahmedabad (Gujrat)
Open Tender
Indian
Maharashtra
pune
01-07-2023

Tender Details

Rate Contract For The Work Of Sitc Of Addressable Intelligent Fire Detection System, Novec 1230 Fire Suppression System And Vesda System For Phase Ix.2 Project At T.E. Mhs Bhavan Pune (Maharashtra) And T.E. Shahibaug Ahmedabad (Gujrat)

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 27-Jun-2023 Corrigendum Other 01-07-2023
2 28-Jun-2023 Corrigendum 2 Other 01-07-2023

Key Value

Document Fees
INR 1180 /-
EMD
INR 168604.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Rate Contract for the work of Supplying, Installation, Testing and Commissioning of Addressable Intelligent Fire Detection System, NOVEC 1230 Fire Suppression System and VESDA System for Phase IX.2 Project at T.E. MHS Bhavan Pune (Maharashtra) and T.E. Shahibaug Ahmedabad (Gujrat).
Sl. No. Item Description
1SH-I Addressable Intelligent Fire Detection system
2Supply, installation, testing and commissioning of UL 864 (10 EDITION) listed / FM approved Micro-processor based Intelligent Analogue Addressable Modular expandable networkable Panel having following loops with each loop having capacity of minimum 125 detectors and 125 modules in any combination with additional 20 % Spare capacity in each loop fire alarm/detection and Good Resolution LCD display. This panel can operate as a standalone or connect up to 8 panels in a network via Network Interface Card (NIC) for peer to peer networking. The panel must have minimum 5000 event history storage. The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON /OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, external printer to log all fire or fault events complete in all respects. The panel shall have a built in power supply and operate on 110 / 230 VAC +10% –15%. The panel shall have its own battery backup of a minium 24 hours in normal run and 5 minitues in the alarm condition. The battery shall be of sealed maintenance free type, housed inside the panel and with the charger support complete as required. The panel should have Ethernet Interfaces for central station communication,email, and diagnostics. The Panel should have provision to add within its cabinet an integrated analog/digital voice evacuation control card and shall be complete with all accessories required as per specifications. It should be compatible with loop powered sounder and sounder strobe. The panel shall have network card included inside the panel for RS-485 communication with other display devices like Graphic screen, repeater panel etc. Panel should also have provision for BMS/Third party interface. Note: It should be able to communicate and give command to Conventional Gas Release Panel at Item at Sl.No. 1 of SH:II. Note: All the items required for the complete functional requirement should be taken into consideration, while quoting the rate.
3Minimum 3 loop inbuilt (expandable upto 8 loops) for MHS Pune location.
4Minimum 2 loop inbuilt (expandable upto 5 loops) for Sahhibaug Ahmedabad location.
5Supply, installation, testing and commissioning of addressable type Repeater Panel with LCD Display etc. complewte as required. The repeater Panel CPU should have the same intelligence and capability of panel CPU. (UL Listed / FM approved).
6Supply, installation, testing and commissioning of analog addressable Control Module (IP-40) with built in fault isolator for activating the notification application devices complete as required for switching ON of smoke extraction fans / pressurisation fans etc. and switching OFF AHU"s etc. complete as required and as per specifications. (UL Listed / FM approved).
7Supply, installation, testing and commissioning of Addressable Monitor Module with builtin fault isolator for monitoring the field NO/NC devices, complete as required for monitoring flow switches/ interface with any third party devices etc. complete as required and as per specifications. (UL Listed / FM approved).
8Supply of Fault Isolator Module capable of monitoring short on SLC loop circuit also isolate wire-to-wire short circuits on an loop of type Class - A, IP-40 and automatically restore communications when shorted conditions are corrected. The fault isolator module and its mounting shall be as per technical specification.
9Supply, installation, testing and commissioning of Intelligent Addressable self decision making, Microprocessor based Multi-Sensor Heat Cum Smoke detector with ROR featues with builtin fault isolator to raise an alarm when the temperature reaches the defined value. Polarity free, smoke and Heat detector, optical type smoke obscuration with Bicolor (green/red) status LED for 360° visibility indicator on each detector. (UL 268 7th edition / FM approved).
10Supplying, installation, testing & commissioning of twin RED LED Response indicator having 360deg visibility, flush / ceiling wall mount, alarm Indication complete with MS box and suitable connections etc. as required.
11Supply of wall mount loop powered Sounder- Strobe with builtin isolator fixing box having minimum sound pressure level of 85dBA @1mtr, Flash intensity should be 15cd minimum Candela Low and High can be selected using DIP switch,flasher frequency 1HZ per second, shall have 7 different tone selection by using DIP 6-way DIP switch, Adjustable volume control, Sounder and strobe OFF facility.It shall be RED in colour. Complete with termination and testing as per requirement and as per specification.
12Supply, installation, testing and commissioning of conventional type Dual Tone Hooter with minimum sound level of 85 dB at distance of 1 mtr, ceiling/wall mounted arrangement etc as required.
13Supply, installation, testing and commissioning of analog Addressable Manual Pull Station with inbuilt fault isolator, with reset facility complete with termination and testing as per requirement and as per specification.
14Supplying, laying and fixing of following size one number PVC insulated and PVC sheathed FRLS multi stranded RED coloured Copper Conductor Armoured Cable of 1.1 KV grade on surface / recess complete as required.
152 x 1.5 sqmm
164 x 1.5 sqmm
17SITC of CO2 type fire extinguisher 4.5 Kgs. with mounting bracket on surface of wall etc. complete as required.
18SH-II NOVEC 1230 Fire Suppression System
19Supplying, installation, testing & commissioning of 2 zone UL listed / FM approved conventional Gas Release Panel for Single Hazard complete with power supply, battery, I/O circuits, LEDs, release / control heads, hardwired 4 nos. PFC (1st stage alarm zone 1, 1st stage alarm zone 2, 2nd stage alarm, gas discharged alarm) for interfacing with BMS etc.
20Designing, Supplying, installation, testing & commissioning of NOVEC 1230 Fire Suppression System, designed for the highest degree of protection and minimum extinguishing time for Server Room at uniform extinguishing concentration comprising of following components and related accessories, connections etc. as per specifications and approved makes as required.
21Supplying of 120 Kgs. Capacity CCOE / PESO approved NOVEC 1230 Seamless Cylinder complete with Cylinder Valve assembly, Supervisory switch, Pressure guage, safety bursts disc, safety cap etc. mounting bracket, cylinder strap, support etc, all fixing hardware complete as required as per manufacturer recommendation based on the estimated gas quantity.
22Supplying & filling of NOVEC 1230 Fre Suppression Clean Gas Agent in the existing cylinders.
23Supplying of Electrical Control Head (Solenoid and Manual Valve) operated either electrically or manually from from lockable/secure lever on the head.
24Supplying of Master Cylinder Kit along with accessories (consisting of Pressure gauge, Low pressure supervisory switch, electromagnetic actuator, manual / pneumatic actuator, Discharge Hose, warning signage -Novec 1230) etc. complete as required for proper fuctioning of fire suppression system.
25Supplying of Mid Slave Cylinder Kit along with accessories (consisting of Pressure Operated Control head, Actuation Hose, Branch Tee, Discharge Hose etc.) etc. complete as required for proper fuctioning of fire suppression system.
26Supplying of End Slave Cylinder Kit along with accessories (consisting of Pressure Operated Control head, Actuation Hose, Discharge Hose, Master cylinder adaptor Kit , Elbow etc.) etc. complete as required for proper fuctioning of fire suppression system.
27Supplying of Discharge Pressure Switch mounted on manifold.
28Supplying of NOVEC 1230 Discharge Brass Nozzle with pressure of at least 10 bar at nozzle tip during discharge.
29Supplying of Manifold Check Valve.
30Supplying of Manual Gas Release Unit.
31Supplying of Manual Abort Switch.
32Installation, Testing and Commissioning of complete fire suppression system. Note: All the items required for the complete functional requirement should be taken into consideration, while quoting the rate.
33Supplying and laying of suitable size M. S. Seamless Pipes as per ASTM 106 Gr. B, Schedule-40 as per below approximate length according to design consideration complete with necessary fittings including cutting, welding and clamping and shall be painted with two coats of primer and two coats of red enameled paint as per fire norms etc. complete as required. (Note :- The design based drawing of the entire system i/c piping etc should be submuitted before commencing the work)
34Approx. length is 50 Mtrs. for MHS Pune location which may vary as per actual site requirement.
35Approx. length is 35 Mtrs. for Shahibaug Ahmedabad location which may vary as per actual site requirement..
36SH : III VESDA SYSTEM
37Supply, installation, testing and commissioning of Laser- Based Absolute Smoke Detection VESDA System having coverage up to 500 Sq. Mtr., Single pipe inlet, Maximum pipe lengths : 1 x 50 Mtr. (Max. 30 holes), adjustable wide sensitivity range - 0.025 to 20% obs/m, 8 Nos. of threshold alarms, High efficiency aspirator, Clean air barrier optics protection for the maintenance free sealed autocleaning laser based detection chamber, Easy to replace dual stage filter, 3 Nos of inbuilt potential free relay outputs (Pre Alarm, Alarm & fault), Ultrasonic Airflow Sensing, Dual Stage Air Filtration, Instant Recognition Display, Event log minimum 5000 events, Multiple Event Logging in separate logs etc. etc complete as required. (UL listed / FM / VdS approved). (Make: M/s Honeywell / Siemens / Securiton)
38Supply, installation, testing and commissioning Power Supply Unit Input voltage of 110 / 230V AC either in built or in a suitable size enclosure along with sealed maintenance free battery backup for 24 hrs etc complete as required.
39Supply and installation of Sampling Pipe suitable for VESDA system etc. complete as required.
40Supplying and installation of Sampling Point on existing sampling pipe along with all accessories such as connector, union, elbow suitable for VESDA system etc. complete as required.