| 1 | Supply installation, testing and commissioning of Booster pump of 900 LPM at average 35mtr head, each giving a pressure of not less than 3.5 kg/cm2 at the top most hydrant outlet of the Downcomer shall be provided at terrace level of the building. |
| 2 | Supply, installation, testing and commissioning of Fire Pump Control Panel(MCC) . The control part should have logic such that, in the event of any Hose reel or landing valve is opened, then the pressure in the line drops and the pressure switches installed on the pump manifold give the indication for the pump to start. |
| 3 | Supplying & Installing of cast iron, double flange, butterfly valve of P.N.16 Rating. of size |
| 4 | 100 NB |
| 5 | Supplying & Installing of cast iron, double flange, Y- strainer of P.N.16 Rating. of size |
| 6 | 100 NB |
| 7 | Supplying and installing of double flange NRV of P.N.16 Rating. of size |
| 8 | 100 mm dia. |
| 9 | Supplying and installing pressure gauge of 100 mm dia., 0-300 PSI or 0-21 kg/sq.cm fitted with 12/15 mm dia. pad cock valve, and G.I. pipe, elbow, etc. as per requirement in an approved manner. |
| 10 | Supplying and installing pressure switch with 12/15 mm dia. Isolation valve, G.I. nipple, elbow, etc. in an approved manner. |
| 11 | Supplying and installing pressure switch with 12/15 mm dia. Isolation valve, G.I. nipple, elbow, etc. in an approved manner. |
| 12 | Landing valve, Hose Reel, etc. |
| 13 | Supplying, erecting and commissioning of Single headed hydrant valve conforming to IS 5290, made of gunmetal with 63 mm dia instantaneous outletof 80 mm dia fanged inelt, Blank caps , chain and CI hand wheels etc complete. |
| 14 | Supply, Installation & Testing of 15 M long, 63mm dia Reinforced Rubber Lined (RRL) hose conforming to IS 363 Type A with gun metal instantaneous couplings conforming to IS 903 and Hoses shall be stored in side the hose cabinet. |
| 15 | M.S. Hose cabinet stand mounted type fabricated out of M.S. sheet of 16 swg. with glass fronted (4mm thick glass with rubber beeding) door and size of the cabinet shall be 750mm x 600 mm x 250 mm Quoted rate shall be includes suitable stand for mounting, all fasteners etc, and cabinet shall be red painted finish both inside and out side. |
| 16 | Supply, Installation & Testing of First aid Hose reel conforming to IS 884 completes with 19 mm dia bore reinforced braided rubber hose of 30 mtrs length fitted with 6.35mm dia shut off Nozzle, 25 mm dia ball valve etc. The hosereel shall be manual 180 deg. swining type with reel drum hose shall be provided with coupling. |
| 17 | Supplying and fixing of approved make of 25mm dia (PN 1.6) gun metal spring loaded automatic air release valve screwed end type with unions etc. complete. |
| 18 | Supplying, installing, testing and commissioning of Gun metal chrome finished Ball valves of 25mm dia (PN 1.6) with fittings of screwed end type. |
| 19 | Supplying S.S . branch pipe of 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle. Make: ISI marked. |
| 20 | Supply, installation , testing and commissioning of Two way Breaching inlet valve with male instantaneous inlet with cap & chain with 100 mm Butterfy Valve. |
| 21 | Piping |
| 22 | Supplying, installing, testing and commissioningof Above groundGalv Steel ERW Pipes confirming to IS 1239 Part - I for pipes upto 150 NBHeavy grade Class \"C with two coat of BP Zinc Yellow (or equivalent) for primer coating over GI pipes and two coat of synthetic enamel painting, suitable type of MS supports, anchor fasteners, bolts nuts (Galvanised), clamps, \"U\" bolts, malleable specials such as Reducers,Tees, elbows, flanges. Including cutting, welding, joining, laying on pedestals and fixing in / on walls, ceiling by using suitable supports etc, complete. The quoted rate shall include the weldable / socketfittings. The fittings with 65mm dia and above shall be butt weldable, 50mm dia and below shall be socket fittings.All pipes after welding &installation shall be tested for 1.5 times the working pressure for at least 24 hrs.above ground |
| 23 | 100mm dia |
| 24 | Electrical work-cable,cable tray,Earthing |
| 25 | Supplying and laying of 2C x 1.5 mm2,Armoured,single strand, outer sheathed, XLPE, PVC insulated copper conductor FRLS cable confirming to specified IS standards (RED COLOUR) |
| 26 | Cable TraySupplying and fixing of perforated G.I.sheet cable tray with necessary angle iron suspension supports, anchor fasteners etc. complete.Size of the tray shall be suitable for laying the above mentioned cables necessary bends,joints, Tee, Reducers etc., (Main Tray shall be 300mm, Drop trays shall be 150mm) |
| 27 | 300 mm x 50 mm |
| 28 | 150 mm x 50 mm |
| 29 | Providing and fixing 25mm X 5mm G.I strip on surface/cable tray for fire pump & panel with earth connections, etc.as required. |
| 30 | Fire Detection &Alarm System |
| 31 | Supplying, installing, testing and commissioning of Addressable type smoke detectors |
| 32 | Supplying, installing, testing and commissioning of Addressable Manual Call Point with back box. |
| 33 | Supplying, installing, testing and commissioning ofAddressable Loop powered Sounder with strobe light |
| 34 | Supply, Installation, Programming& Commissioning of Single-Loop Capacity Addressable Fire Alarm Control panel with Loop cards, operating modules, network cards, battery charger, 48 hours battery back-up and build-in printer etc. The panel shall consist of 80 character LCD display and RS 485 for networking. The panel shall be UL Listed / FM Approved make. |
| 35 | Automatic fire detection and fire fightingsystem for LT panel consisting of 1. Cylinder with HFC 27 clean agent gas fitted with DLV, pressure gauge, pressure switch, control panel for indications suitable to work automaticallywith 40 m sensitive polymer base tube. Assuem gas charge of 6 kg . |
| 36 | Fire Extinguishers |
| 37 | Supplying and erecting ABC powder fire extinguisher as per IS : 13849 of 4 kg capacity with necessary clamp for erection on wall. Make: ISI |
| 38 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. Capacity, conforming to IS 2878 Complete with, necessary clamp made front 50mm x 6mm. M.S. flat with nut & bolts grouted in wall complete.Make: ISI |
| 39 | Passive Fire protection |
| 40 | 120 Minutes Fire rated Door System for Electrical Room 1.5x2 mtr conforming of BS 476 part (20& 22), tested at CBRI. Fire door shall befitted with appropriate fir resistant fittings, such as frame and door for panel room.valve |
| 41 | Signages |
| 42 | Providing & Fixing Self luminating signages for following items of (size 4\" x 12\") |
| 43 | Exit signage (shall be electric + battery operated ) |
| 44 | Fire extinguisher signage |
| 45 | Hose reel Hose Signage |
| 46 | Assmbly point signage |
| 47 | Fire Alarm Signage |
| 48 | Electrical roomsignage |