| 1 | Section: I) ADDRESSABLE FIRE ALARM SYSTEMFire Alarm Control Panel (FACP): Supplying installation testing and commissioning of Analogue addressable micro Processor - controlled, Standalone, Main Fire Alarm Control Panel 2 loop (1 Loop Card) (with minimum 125 detectors /125 devices capacity per loop card ) with LCD display, capable of being networked to the central monitoring System,to monitor and integrate other panels such asAccess control System and accessories like detectors, LCP\"s, hooters, control modules, monitor modules, Fault Isolation Modules, response indicators,fire/ fault indicators, audio-visualsignals, central processing units, complete with LCD display, zone indicating LEDs, having multiple access levels, event history file in non-volatile memory (EEPROM) as per the detailed specification, complete with PSU, Battery backup along with charger for 48 hours in non-alarm condition and 30 minutes in alarm condition etc. as required for each panel. The panel shall be UL listed fire alarm panel. |
| 2 | Addressable MultiSensor Detector: Supply of Addressable analogue MULTISENSOR / MULTICRITERIAtype, UL Listed photo cum thermal detectors with solid state design, indicating LED, mounting base, mounting bracket etc. base box, loop in and loop out gland as per requirement and detailed specification. As per following position:a) On Real Ceiling(Base Box is to be Used) /false flooring(Base Box with bracket is to be Used) |
| 3 | b) On False Ceiling |
| 4 | Addressable control modules: Supplying, installation, testing and commissioning of UL Listed Addressable control module complete with junction box etc. for control options for Hooters & for other control options like PA evacuation, Access Doors opening, the package Air Conditioners trip etc., in case of emergency, as required. |
| 5 | Addressable monitoring modules: Supplying, installation, testing and commissioning of UL Listed Addressable monitoring modules complete with junction box etc., to monitor status of other systems etc. as required. |
| 6 | Manual Call Point:Supplying installation testing and commissioning of UL Listed Manual call points with NO/ NC contacts slim type with Pull type/ break glass with Reset Lock & Key arrangement suitable for addressable function |
| 7 | Electronic Hooter Cum Strobe: Supplying, installation, testing and commissioning of Hooter having three distinct sounds with addressable relay module and strobe light with minimum 85 db from 1Mtr distance, UL listed etc. as required. |
| 8 | Fault Isolator Module: Supplying, installation, testing and commissioning of UL Listed Fault isolation module to electrically isolate different sections of detector loops (for every 20 detectors/ devices) as per detailed specifications.etc., as required. |
| 9 | Response Indicator: Supplying, installation, testing and commissioning of Response indicator having twin LEDs for mounting on false ceiling / wall at the entries of the cabin for indicating the operation of detectors in the above false ceiling / below false flooring detectors etc., as required. |
| 10 | Supplying and laying of 2 core x 1.5 sqmm armoured FRLS copper cable on surface/recess suitable for operation on 240V, 50Hz AC supplying including interconnections, testing etc., as reqd. |
| 11 | Section: II) FIRE SUPPRESSION SYSTEMDesigning and Supplying installation testing and commissioning of Vds/UL approved NOVEC 1230 fire suppression system, design for highest degree of protection and minimum extinguishing time for Server Room at uniform extinguishing concentration comprising of following components and related accessories, connections etc. asrequired.a) Supplying, installation, testing and commissioning of 120 Ltrs capacity seamless cylinder suitable for filling NOVEC 1230 complete with Cylinder Valve, Pressure gauge, safety outlet and port for low pressure switch connection and cylinder strap complete as required. Note: cylinder pressure, in compliance with Chief Controller of Explosive, Nagpur with electric & pressure operated control heads as per requirement complete with Master Actuation kit and other required accessories to make the cylinder completely operational etc complete as required. |
| 12 | b) Supplyingand charging of NOVEC 1230 Agent in the existing cylinders. |
| 13 | c) Supplying installation testing and commissioning of ElectricalActuator with local manual actuator |
| 14 | d) Supplying installation testing and commissioning ofPneumatic actuator with all accessories |
| 15 | e) Supplying, installation, testing and commissioning ofHigh pressure discharge flexible hose with fittings |
| 16 | f) Supplying, installation, testing and commissioning ofFlexible actuation hose |
| 17 | g) Supplying, installation, testing and commissioning ofManifold |
| 18 | h) Supplying, installation, testing and commissioning ofbracket for mounting the cyinders |
| 19 | i) Supplying, installation, testing and commissioning ofNOVEC 1230 discharge brass nozzle |
| 20 | j) Supplying, installation, testing and commissioning ofNon Return Valve |
| 21 | k) Supplying, installation, testing and commissioning ofmanual release switch (UL listed) |
| 22 | l) Supplying, installation, testing and commissioning ofmanual abort switch (UL listed) |
| 23 | Supplying, installation, testing and commissioning of suitable sizeM. S. Seamless pipes as per ASTM 106 Gr. B,Schedule-40according to design consideration complete with necessary fittings including cutting, welding and clamping and shall be painted with two coats of primer and two coats of red enamelled paint as per fire norms etc., complete as required for the following areas.a) Hyderabad (Area appox 375sqmtr) |
| 24 | b) Kokata (Area appox 265sqmtr) |
| 25 | c) Odisha (Area appox 240sqmtr) |
| 26 | Supplying, installation, testing and commissioning of Two Zone Addressable Gas Release Panel facility to connect the Manual Abort/Release switches. The Panel shall provide potential free contacts for first knock, second knock, trouble/fault status. The Panel shall be complete with red colour housing, power supply unit, battery charger, batter etc., as reqd. |
| 27 | Section: III) Aspirating Smoke Detection SystemAspirating Smoke Detector: Supply, installation, testing and commissining of Single channel Fire Alarm Aspiration system with coverage up to 500sqm and sensitivity range 0.00029% obs/ftto 6.25Obs/Ft, ultrasonic flow sensing and chamber air flow monitoring for presise system healthy information, dual source optical smoke detection technology, event log up to 18000 events, etc., as required as per the list of approved makes attached. |
| 28 | Aspirating Smoke Detector: Supply, installation, testing and commissining of Single channel Fire Alarm Aspiration system with coverage up to 250sqm and sensitivity range 0.00029% obs/ftto 6.25Obs/Ft, ultrasonic flow sensing and chamber air flow monitoring for presise system healthy information, dual source optical smoke detection technology, event log up to 18000 events, etc., as required as per the list of approved makes attached. |
| 29 | Supply, installation, testing and commissining of power supply unit (FM approved) 110/ 220V AC to 24V DC 2Amp complete as required. |
| 30 | Supply and laying ofISI marked CPVC pipe of 25mm dia for aspiration complete as per specifications,as required. |
| 31 | Supply, installation, testing and commissioning of capillary sampling point, as per specificationsas required. |
| 32 | Supply and fixing of END CAP for large bore 25mmetc., as required. |
| 33 | Electronic Hooter: Supplying installation testing and commissioning of Hooter having three distinct sounds with addressable relay module with minimum 85 db from 1Mtr distance etc. as required. |