| 1 | Supply, laying, jointing & testing in replacement XLPE insulated, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade cross sectional area 10 Sqmm 2 core laind in trenches or passing through pipe or fixed on poles complete all as specified and directed by Engr-in-Charge. |
| 2 | All all as per serial item No 1.00 here-in-before but of size 16 Sqmm 4 core complete all as specified and directed by Engr-in-Charge. |
| 3 | All all as per serial item No 1.00 here-in-before but of size 25 Sqmm 4 core omplete all as specified and directed by Engr-in-Charge. |
| 4 | All all as per serial item No 1.00 here-in-before but of size 35 Sqmm 3.5 core omplete all as specified and directed by Engr-in-Charge. |
| 5 | All all as per serial item No 1.00 here-in-before but of size 50 Sqmm 3.5 core omplete all as specified and directed by Engr-in-Charge. |
| 6 | All all as per serial item No 1.00 here-in-before but of size 70 Sqmm 3.5 core omplete all as specified and directed by Engr-in-Charge. |
| 7 | All all as per serial item No 1.00 here-in-before but of size 95 Sqmm 3.5 core omplete all as specified and directed by Engr-in-Charge. |
| 8 | All all as per serial item No 1.00 here-in-before but of size 120 Sqmm 3.5 core omplete all as specified and directed by Engr-in-Charge. |
| 9 | All all as per serial item No 1.00 here-in-before but of size 150 Sqmm 3.5 core omplete all as specified and directed by Engr-in-Charge. |
| 10 | All all as per serial item No 1.00 here-in-before but of size 240 Sqmm 3.5 core omplete all as specified and directed by Engr-in-Charge. |
| 11 | Taking down the unserviceable LT cable of any size from tranches/ walls /floor etc complete all as specified and as directed by Engr-in-Charge. |
| 12 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of cables, pipes foundations of poles/stays/pipes etc .not exc 10 Sqm area on plan and getting out in soft/loose soil complete all as specified and directed by Engr-in-Charge. |
| 13 | All as per serial item No 12.00 here-in-before but depth exceeding 1.5 mtr and not exceeding 3 mtr complete all as specified and directed by Engr-in-Charge. |
| 14 | Returning, filling in excavated soil in trenches including spreading, leveling, watering and well rammingin layers n. exc. 25 cm thick complete all as specified and directed by Engr-in-Charge. |
| 15 | Removing of excavated soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engr-in-Charge. |
| 16 | M&L for sand cushioning to UG cable laid in trenches with clean dry river sand8 cm below & 15 cm above the cable & punned down to 18 cm thickness complete all as specified and directed by Engr-in-Charge.Note: - For payment purpose 18 cm thickness shall measured. |
| 17 | Supply only burnt brick of size 230 x 115 x 75 mm sub class Bfor cable protection laid adjacent to each other perpendicular to the direction of cable in trenches complete all as specified and directed by Engr-in-Charge. |
| 18 | M&L for cement concreate 1:2:4 type B-2 (using 40 mm graded stone aggregate) as in coping etc including necessary form work and finishing the surface with cement mortar 1:4, 5mm thick finished to the portion of PCC muffs above ground level complete all as specified and directed by Engr-in-Charge. |
| 19 | M&L for PCC 1:4:8 type D-2 (using 40 mm grade stone aggregrate in foundation, mass concrate) as in foundation of poles & stay etc complete all as specified and directed by Engr-in-Charge. |
| 20 | Supply and Laying in replacement Galvanised iron steel tubes, ISI marked light grade of size 40 mm bore for cable protection along the poles under road under drains,laid in trenches/fixed on walls/poles with suitable clamps bolts nuts etcincluding taking down of old unserviceble pipe complete all as specified and directed by Engineer-in-Charge. |
| 21 | Supply and Laying in replacement Galvanised iron steel tubes, ISI marked light grade of size 80 mm bore for cable protection along the poles under road under drains,laid in trenches/fixed on walls/poles with suitable clamps bolts nuts etcincluding taking down of old unserviceble pipe, complete all as specified and directed by Engineer-in-Charge. |
| 22 | Dismantling of old unserviceable/ broken/jointed ACSR conductor or earth wire from poles and removing from site of work complete all as specefied and directed by Engr-in-Charge. |
| 23 | Taking down existing old cross arms of MS channel or angle sections etc all as specified and directed by Engr-in-Charge. |
| 24 | Taking down burnt and broken out insulators of any size from LT Poles complete all as specefied and directed by Engr-in-Charge. |
| 25 | Taking down old unserviceable cradle guard/earthing from LT Poles complete all as specefied and directed by Engr-in-Charge. |
| 26 | M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600mm x 6.0mm thick buried directly in ground ( earth pit not less than 2.25 mtr below normal ground level ) with top edge plate not less than 1.5 metre below normal ground level connected to galvanized earth strip of size 32 x 6mmas earthing lead by means of bolts, nuts, chuck nuts and washers of galvanized iron earth lead with 15 cm thick alternate layers of charcoal dust & common slat including PCC pit in PCC 1:2:4 type B-1, RCC covermade out of cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) reinforced with TMT steel bars 8 mm dia @150 mm c/c both ways with suitable handle andangle iron 40 x 40 x 5 mm frame, GI medium grade watering pipe 20 mm bore and funnel with wire mesh light grade protection pipe 40mm bore up to main board complete as shown on electrical plate No 3 of MES Sch 2009 (Part-I) and testing on completion complete all as specified and directed by the Engr-in-Charge. Note: - On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engr-in-Charge. |
| 27 | S&F in replacement earth continuity conductor on main earthing lead fixed to pole or buried in ground or at any other situation for loop earthing extra as required (beyond 7.5 M) of GI Strip 32 x 6 mm complete all as specified and directed by Engr-in-Charge. |
| 28 | M&L for switchyard gravelling of 15.0 cm (loose thickness) by broken stone of 40 mm size in and around two pole/ four pole structure/ substation complete all as specified and directed by Engr-in-Charge. |
| 29 | Taking out/dismantling any type of LT Panel by disconnecting the electric connection carefully after taking proper shutdown and removing from the site and stacking complete all as specefied and directed by Engr-in-Charge. |
| 30 | Supply, Installation , testing and commissioing in replacement of outdoor type, weather proof, cubicle panel board made out of 3.15 mm thick CRCA steel sheet mounted on 60 cm long legs made out of 40 x 40 x 6 mm equal angle, embedded in PCC 1:2:4 type B-1 blocks of size 15 x 15 x 15 cm front and back openable, double door openable up to minimum 150 degree & removable type having magnetic catche system, lockable/ openable by keys from both sides having chromium plated locks, louvers and air vent gaskets for natural air flow suitable foamed in PU gasket to make it dust/vermin proof, IP 54 protection, powder coated and prewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliset for short circuit current of 50 KA for one second and similar design and technology shall be adopted for fabrication of panel copy of CPRI test report shall be produced to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels complete suitable cable glands for cable entry. The panel shall accomodate the following equipments:-(a) Aluminium Bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 800 Amps for phases and neutral - 01 set. |
| 31 | (b) Digital multifunction meter of size 96x96mm to measure current, voltage, freequency and power factor with built in selector switch and programmable CT of appropriate ratio - 01 Nos.(c) Panel indicating lamp neon/LED type (Red, Yellow & Blue) with lamp holders - 03 Nos.(d) Panel instrumental wiring with FRLS suitable size but not less than 2.5 Sqmm copper wire single core - 01 Job. INCOMING(a) MCCB 4 Pole, Ics = 100% Icu, 50 KA, 415 Volts, 500 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos. OUT GOING(a) MCCB 4 Pole, Ics = 100% Icu, 35/36 KA, 415 Volts, 250 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos. (b) MCCB 4 Pole, Ics = 100% Icu,25/26KA, 415 Volts, 200 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 02 Nos. (c) MCCB 4 Pole, Ics = 100% Icu,25/26KA, 415 Volts, 100 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 02 Nos. |
| 32 | Supply, Installation , testing and commissioing in replacement of outdoor type, weather proof, cubicle panel board made out of 3.15 mm thick CRCA steel sheet mounted on 60 cm long legs made out of 40 x 40 x 6 mm equal angle, embedded in PCC 1:2:4 type B-1 blocks of size 15 x 15 x 15 cm front and back openable, double door openable up to minimum 150 degree & removable type having magnetic catche system, lockable/ openable by keys from both sides having chromium plated locks, louvers and air vent gaskets for natural air flow suitable foamed in PU gasket to make it dust/vermin proof, IP 54 protection, powder coated and prewired as per standard engineering practice, the panel manufacturer should have got any one of the panel tested at CPRI earliset for short circuit current of 50 KA for one second and similar design and technology shall be adopted for fabrication of panel copy of CPRI test report shall be produced to GE along with a certificate from manufacturer of the panel that the similar design and standard have followed in these panels complete suitable cable glands for cable entry. The panel shall accomodate the following equipments:-(a) Aluminium Bus bar of capacity duly covered with colour coded shrinkable sleeves not less than 800 Amps for phases and neutral - 01 set. |
| 33 | (b) Digital multifunction meter of size 96x96mm to measure current, voltage, freequency and power factor with built in selector switch and programmable CT of appropriate ratio - 01 Nos(c) Panel indicating lamp neon/LED type (Red, Yellow & Blue) with lamp holders - 03 Nos.(d) Panel instrumental wiring with FRLS suitable size but not less than 2.5 Sqmm copper wire single core - 01 Job. INCOMING(a) MCCB 4 Pole, Ics = 100% Icu, 50 KA, 415 Volts, 315 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos. OUT GOING(a)MCCB 4 Pole, Ics = 100% Icu,25/26KA, 415 Volts, 200 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 03 Nos. (b) MCCB 4 Pole, Ics = 100% Icu,25/26KA, 415 Volts, 100 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 02 Nos . |
| 34 | Supply, installation and commissioning in replacement LT Feeder pillar box of size 75x75x45 cm outdoor type factory made manufactured by a CPRI approved manufacturer, made out of 3.15 mm thick CRCA sheet and self supporting, built upon Rigid frame work suitable fo 440 volt 3 phase 4 wire system having front and rear hinger doors with neorprene rubber gasket epoxy powder coated with danger plate, earthing strip point and bottom detachable gland plate complete with suitable size zinc chromium plated nuts, bolts and washers etc having colour code aluminium bus bar interconnections for easy identification including incoming/outgoing cable holes at bottom, provision of six nos connectors and embedded with mild steel anglr iron frame of size 50x50x6 mm and 450 mm above normal ground level complete with PCC foundation in cement concrete (1:2:4) type B1 graded stone aggregate and testing after installation including taking down unserviceable Feeder Pillar box with connected acessories after disconnecting all incoming and outgoing cable etc complete all as specefied and comprising with the following:- |
| 35 | (a) Aluminium Bus-bar 400 Amp, supported with suitable size of Heavy Duty Porcelain Stand Lock with suitable size of Brass Nut, Bolts and Washer with Heat Shrinkable PVC Sleeving.The Bar shall be Colour Coded (Red, Yellow & Blue) for Three Phases and Black for Neutral. – 04 Nos(b) MCCB 4 Pole, Ics = 100% Icu, 35/36 KA, 415 Volts, 250 Amps, with thermal adjustable and fixed magnetic setting with extended terminals - 01 Nos (AS INCOMING) |
| 36 | M&L for road cuttig existing road for crossing of underground electric cable for laying of any size GI tubing including necessary excavation and earth work including repairing the same as per existing with pre mix bituminious carpet complete all as specefied and as directed by Engr-in-Charge.Note: - Width of trenchshall be 15 cm and depth shall be upto 30 cm . |
| 37 | Dismantling of unserviceable steel tubular pole swaged pole/PCC pole including PCC complete with acessories complete all as specified and directed by Engr-in-Charge. |
| 38 | S&F in replacement erecting steel tubular swaged poles erected to truly vertical or planted as strut complete with 6mm thick mild steel base plate(300mmx300mm), welded to pole, finial taper plug, bolts, nuts, and screws poles made out of ERW MS tubing conforming to IS-2713 Part-II Type 410 SP-31, 9mtr long including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bitumenous paintinternally and portion embedded in concrete, making five black & white bands at lower portion of pole each 300mm wide alternately upto the height and marking pole No. with black paint at suitable height including making two nos holes of suitable size in steel tubular pole by gas welding for passing PVC cable connection from junction box to security lights through pole where junction box to be fitted in pole complete all as specified and directed by Engr-in-Charge. Note: -Excavation and Earth Work, PCC in foundation shall be measuredand paid for separately. |
| 39 | Supply, Laying, jointing in replacement & testing 1100 Volts grade heavy duty cable PVC tape PVC sheathed 2.5Sqmm aluminium solid conductor 2 core nominal cross section laid in trenches/fixed to walls/ passing under the roads in existing pipes etc including takind down old UNSV cable complete all as specefied and directed by Engr-in-Charge. |
| 40 | S&F in replacement modular boxof size 333 x 233 x 120 mm made of FRP inpact resistance plastic & heat resistant materials including MCB SP 6 A, Connector terminal block 4 pole 16 A capacity and fixing to the street light or post top light pole with suitable sizes of clamps, nuts and bolts complete all as specefied and directed by Engr-in-Charge. |
| 41 | Cleaning the existing exposed surfaces of steel tubular pole of9.0 mtr long including cross arms, brackets, clamps etc and painting with two coats of synthetic enamel paint (Aluminium shade) marking five black & white bands at lower portion of pole, each 300 mm wide alternately and marking pole No. with yellow paint on black base at suitable height complete all as specefied and directed by Engr-in-Charge. |
| 42 | S&F in replacement modular boxof size 333 x 233 x 120 mm made of FRP inpact resistance plastic & heat resistant materials including MCB SP 6 A, Connector terminal block 4 pole 16 A capacity and fixing to the street light or post top light pole with suitable sizes of clamps, nuts and bolts complete all as specefied and directed by Engr-in-Charge. |
| 43 | S&F in replacement 60 Watt LED street light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED\"s must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 6000 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection,PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided.Luminarie should have top maintainable driver compartment for easy access to driver during maintenance.The driver used must be a constant current driver with efficiency of > 85%.The manufactures LOGO must be embossed/Engraved in the housing of the luminarie.Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specefied and directed by Engr-in-Charge. |
| 44 | S&F inLED flood lightwith lens 100 watt made uppressure diecast aluminium housing with toughned glass and high power leds and secondary lens with IP 66 protection system of efficasy >110/125LPW including 10 KV SPDincluding taking down old UNSV Streetlights complete all as specified and directed by Engr-in-Charge. |
| 45 | M&L for heat shrinkable type end termination joint kit indoor type suitable for XLPE insulated HT cable 11000 Volts grade of size 240 to 300 Sqmm 3 core complete with jointing material and acessories alongwith testing after jointing including taking out the old unserviceable joint kit complete all as specefied and directed by Engr-in-Charge. |
| 46 | M&L for heat shrinkable type end termination joint kit outdoor type suitable for XLPE insulated HT cable 11000 Volts grade of size 240 to 300 Sqmm 3 core complete with jointing material and acessories alongwith testing after jointing including taking out the old unserviceable joint kit complete all as specefied and directed by Engr-in-Charge. |
| 47 | M&L for heat shrinkable straight through joint kit suitable for XLPE insulated HT cable 11000 Volts grade of size 16 to 35 Sqmm 3 core complete with jointing material and acessories alongwith testing after jointing including taking out the old unserviceable joint kit complete all as specefied and directed by Engr-in-Charge. |
| 48 | All as per serial Item No 44.00 here-in-before but 50 sqmm to 95 sqmm complete all as specified and directed by Engr-in-Charge. |
| 49 | All as per serial Item No 44.00 here-in-before but 120 sqmm to 185 sqmm complete all as specified and directed by Engr-in-Charge. |
| 50 | All as per serial Item No 44.00 here-in-before but 240 sqmm to 400 sqmm complete all as specified and directed by Engr-in-Charge. |
| 51 | M&L for PCC 1:3:6 type C2 using 40mm graded aggregate in coping of size (0.65x0.55x0.45) Mtr for steel tubular/GI street light pole complete with 10mm thick cement plaster CM 1:4 on coping surface complete all as specified and directed by Engr-in-Charge. |
| 52 | Supply and fixing of High density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 of 20mm dia inclusive of all fitting accessories such as saddles, clamps etc for fixing on RCC/Steel tubular polesincluding dismantling existing unserviceable conduit pipe of any description complete all as specified and directed by Engr-in-Charge. |