| 1 | Excavation for foundation in earth, soil of all types, sand, gravel and soft murum, including removing the excavated material up to a distance of 50 m. beyond the building area & stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 1.5 m.) By Mechanical Means |
| 2 | Excavation for foundation in earth, soils of all types, sand,gravel and soft murum, including removing the excavated material upto a distance of 50 metres beyond the building area and stacking and spreading as directed,dewatering,preparing the bed for the foundation and necessary back filling,ramming,watering including shoring and strutting etc.complete.(Lift from1.5m to 3.0m)By Mechanical Means |
| 3 | Providingsoling using80mm sizetrapmetalin15cm.layerincludingfilling voidswith Crushed sand/grit, ramming, watering etc. complete. |
| 4 | Providing PreconstructionalAntitermite Treatment as per I.S. 6313 (Part-II) by treating the bottom surface and sides for excavation clorophyriphoas / lendene at the rate of 5 liters of emusion concentrates of 0.5 % of Aldrin per square meter of surface |
| 5 | Providing preconstructional antitermite treatment as per I.S. 6313 (Part-II) treatment by treating the backfill in immediate contact with foundation at the rate of 5 litres of emulsion concentrate of 1.0 percent of clorophyrifos per square metre of vertic |
| 6 | Providing preconstructional antitermite treatment as per I.S. 6313 (Part-II) by treating the top surface of plinth filling at the rate of 5 litres of emulsion concentrate at 1.0 percent of clorophyrifos per square metre of surface area covering ten years |
| 7 | Filling in plinth and floors with approved excavated material in 15cm to 20cm layers including watering and compaction etc complete. |
| 8 | Filling in plinth and floors with contractor\"s approved material / murum / stone dustin 15cm to 20cm layers including watering and compaction etc complete. |
| 9 | Providing and filling in the foundation with sand of approved quality including watering,compacting etc. complete. (To be executed with prior approval of Superintending Engineer) |
| 10 | Providing and laying Cast in situ/Ready Mix cement concrete in M15 of trap/ granite/quartzite/gneiss metal for bed blocks, foundation blocks and such other items including bailing out water, Steel centering, formwork, laying/ pumping, compacting, rougheni |
| 11 | Providing and laying in situ cement concrete M-25 of trap / granite /quartzite/gneiss metal for R.C.C. work in foundations like raft, strip foundations, grillage and footings of R.C.C. columns and steel stanchions etc. including bailing out water, formwor |
| 12 | GROUND FLOOR - Building - 230.01 + C.W. - 48.77 = 278.78 Cum. |
| 13 | FIRST FLOOR |
| 14 | SECOND |
| 15 | THIRD FLOOR |
| 16 | Providing & casting in situ cement concrete M-25 of trap / granite /quartzite/ gneiss metal for R.C.C. beams and lintels as per detailed designs & drawings or as directed including centering, formwork, cover blocks compaction & roughening the surface if s |
| 17 | GROUND FLOOR - Building - 423.98 + C.W. - 50.84 = 474.82 Cum. |
| 18 | FIRST FLOOR |
| 19 | SECOND |
| 20 | THIRD FLOOR |
| 21 | Providing & casting in situ cement concrete M-25 of trap/ granite/ quartzite/ gneiss metal for R.C.C. chajja as per detailed design & drawings including centering, formwork, cover blocks compacting , curing , finishing & roughening the surface if special |
| 22 | GROUND FLOOR |
| 23 | FIRST FLOOR |
| 24 | SECOND |
| 25 | THIRD FLOOR |
| 26 | Providing and casting in situ cement concrete M-25 of trap/ granite / quartzite/gneiss metal for R.C.C. slabs and landings canopy as per detailed designs and drawings including centering, formwork, cover blocks compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).With fully automatic micro processor based PLC with SCADA enabled reversible drum type concrete mixer With natural sand. |
| 27 | GROUND FLOOR |
| 28 | FIRST FLOOR |
| 29 | SECOND |
| 30 | THIRD FLOOR |
| 31 | Providing and laying in situ / ready mix controlled grade of M-25 of trap /granite /quartzite /gneiss metal for RCC works in cut off walls / curtain walls including necessary scaffolding, centering, compacting by vibrator, finishing and curing etc. complete. (with fully automatic micro processor based PLC with SCADA enabled with reversible drum type mixer/ concrete batch mix plant (pan mixer)with natural/artifical sand, excluding reinforcement) |
| 32 | GROUND FLOOR |
| 33 | FIRST FLOOR |
| 34 | SECOND |
| 35 | THIRD FLOOR |
| 36 | Providing and laying Cast in situ/Ready Mix cement concrete in M-25 of trap / quartzite /granite /gneiss metal for R.C.C. Waist slab, and steps of staircases as per detailed design and drawings or as directed including steel centering, plywood/ steel formwork, steel props, laying/pumping, compaction, finishing uneven and honeycombed surface with C.M. 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement, including cover block).(Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc.) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With natural sand/V.S.I. quality Artificial Sand |
| 37 | GROUND FLOOR |
| 38 | FIRST FLOOR |
| 39 | SECOND |
| 40 | THIRD FLOOR |
| 41 | Providing expansion joints with 25mm thick Bituminous pad as per detailed drawings etc. complete. |
| 42 | GROUND FLOOR |
| 43 | FIRST FLOOR |
| 44 | SECOND |
| 45 | THIRD FLOOR |
| 46 | Providing and fixing in position TMT / HYSD steel bars reinforcement of various diameters for R.C.C. pile caps, footings, foundations, slabs, beams and columns, canopies, staircases, newels, chajjas, lintels, pardies, coping, fins, arches etc. as per detailed design and drawings and schedules including cutting, bending, hooking the bars, binding with wires or tack welding and supporting as required completed. |
| 47 | GROUND FLOOR - Building - 675.24 + C.W. - 18.10 = 693.34 Cum. |
| 48 | FIRST FLOOR |
| 49 | SECOND |
| 50 | THIRD FLOOR |
| 51 | Providing and fixing in position in R.C.C. slab during laying rectangular 2 mm thick M.S. Sheet iron box 180 mm x 100 mm and of required depth with holes or notches as required, bottom and top lids of 1.6 mm thick M.S. sheet fixed with 3.5 mm dia round head Screwed together with Fan dia.M.S. bar bent to shape with hooked ends (for fan hooks) as per standard design including painting to exposed portion complete. |
| 52 | GROUND FLOOR |
| 53 | FIRST FLOOR |
| 54 | SECOND |
| 55 | THIRD FLOOR |
| 56 | Providing Fly Ash Brick masonry with conventional/ I.S. type bricks in cement mortar 1:6 in foundations and plinth of inner walls / in plinth external walls including bailing out water manually , striking joints on unexposed faces, raking out joints on exposed faces and watering etc. Complete. |
| 57 | GROUND FLOOR - Building - 103.75 + C.W. - 152.52 = 256.27 Cum. |
| 58 | Providing fly ash brick masonry with conventional/ I.S. type bricks in cement mortar 1:6 in Superstructure including striking joints, raking out joints, watering and scaffolding etc. complete. |
| 59 | GROUND FLOOR |
| 60 | FIRST FLOOR |
| 61 | SECOND |
| 62 | THIRD FLOOR |
| 63 | Providing Second class fly ash brick masonry with conventional / I.S. type bricks in cement mortar 1:4 in half brick thick wall including mild steel longitudinal reinforcement of two bars of 6 mm diameter / two hoop iron strips 25 mm x 1.60 mm at every third course, properly bent and bounded at ends scaffolding raking out joints and watering etc. complete. |
| 64 | GROUND FLOOR |
| 65 | FIRST FLOOR |
| 66 | SECOND |
| 67 | THIRD FLOOR |
| 68 | Providing and laying Cast in situ/ReadyMix cement concrete in M-20 of trap/granite/quartzite/gneiss metal for R.C.C. coping to plinth or parapet and sill of doors and windows moulded a spe rdetailed drawings or chamfered as approved by the Engineer including steel centering,formwork,cover blocks, laying/pumping,compacting, curing,finishing and roughening the mifspecial finishis to be provided and curing complete.(Excluding reinforcement and structural steel).with fully automatic microprocessor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Panmixer) etc.complete.With fine aggregate(Crushed sand VSI Grade |
| 69 | GROUND FLOOR |
| 70 | FIRST FLOOR |
| 71 | SECOND |
| 72 | THIRD FLOOR |
| 73 | Providing and applying water proofing treatment using acrylic polymer modified cement based water proofing coat ing with fibre glass mesh mixing at the rate of powder to liquid (2:1) by weight cover ing 9 to 10 sqm / kg with two coat using Dr . Fixit or alike of chemicals for masonry and concrete surface by brush covering 7 years guarantee on Stamp Papers etc. complete. etc. complete. |
| 74 | GROUND FLOOR |
| 75 | FIRST FLOOR |
| 76 | SECOND |
| 77 | THIRD FLOOR |
| 78 | Providing water proof bedding for flooring of Bath and WC 25 mm thick in C.M. 1:3 including using approved water proofing compound in specified proportion as per manufacturers specifications for per bag of cement including leveling, curing and covering 10 years guarantee on court fee stamp paper of Rs.500/- including ponding test etc. complete. |
| 79 | GROUND FLOOR |
| 80 | FIRST FLOOR |
| 81 | SECOND |
| 82 | THIRD FLOOR |
| 83 | Providing waterproof plaster in W.C. and bath 20 mm thick for dado in cement mortar 1:3 with neat finishing, floating using waterproofing compound at the rate of 1 kg. per bag of cement of approved make and manufacturer and curing (and filling joints of Nahani trap and any outlet by properly) etc. complete. |
| 84 | GROUND FLOOR |
| 85 | FIRST FLOOR |
| 86 | SECOND |
| 87 | THIRD FLOOR |
| 88 | Providing internal cement plaster 12mm thick in single coat in cement mortar 1:4 without neeru finish to concrete or brick surfaces, in all positions including scaffolding and curing etc. complete. |
| 89 | GROUND FLOOR |
| 90 | FIRST FLOOR |
| 91 | SECOND |
| 92 | THIRD FLOOR |
| 93 | Providing internal cement plaster 20mm thick in two coats in cement mortar 1:4 without neeru finish, to concrete, brick surface, in all positions including scaffolding and curing etc.complete. |
| 94 | GROUND FLOOR - Building - 1883.82 + C.W. - 947.00 = 2830.82 Cum. |
| 95 | FIRST FLOOR |
| 96 | SECOND |
| 97 | THIRD FLOOR |
| 98 | Providing sand faced plaster externally in cement mortar using approved screened sand, in all positions including base coat of 15 mm thick in cement mortar 1:4 using waterproofing compound at 1 kg per cement bag curing the same for not less than 2 days and keeping the surface of the base coat rough to receive the sand faced treatment 6 to 8 mm thick in cement mortar 1:4 finishing the surface by taking out grains and curing for fourteen days scaffolding etc.complete. |
| 99 | GROUND FLOOR - Building - 2643.61 + C.W. - 840.00 = 3483.61 Cum. |
| 100 | FIRST FLOOR |
| 101 | SECOND |
| 102 | THIRD FLOOR |
| 103 | Providing fine cementfinish1.5 mm thick overgreen plastersurface including scaffolding curing etc. complete. |
| 104 | GROUND FLOOR - C.W. - 107.00 Sqm. |
| 105 | Providing and fixing in position DecorativeGypsum board false ceiling with 12.5 mmthick Gypsum boards, screwed /fixedto the under structure of suspended G.I. Grid constructed and suspended from the main ceiling consisting of ceiling sections of size 25 x 50 mm maximum center to center distance of 600 milimetre perimeter channel and intermediate channels at maximum center to center distance 1200 milimetre galvanized grid should be fixed to reinforced cement concrete slab. The gypsum board should be fixed to galvanized iron grid with necessary screws. The boards should be taped and filled from underside to give smooth, seamless ceiling. The rate should include necessary additional ceiling sections and intermediate channels. Additional intermediate channels should be fixed to strap hangers for additional support to prevent strapping at every 1200 milimetre item to be completed in all respect including necessary sleeves for ducts finishing of joints cut outs, painting including labour, material, lifts etc. all completeIncluding all vertical ,Horizontal ,patta |
| 106 | GROUND FLOOR |
| 107 | FIRST FLOOR |
| 108 | SECOND |
| 109 | THIRD FLOOR |
| 110 | Providing patti/ band 75mm wide on plastered surface 12 mm to 15 mm thick in C.M. 1:3 line and level including neat finishing scaffolding curing etc. complete. |
| 111 | GROUND FLOOR |
| 112 | FIRST FLOOR |
| 113 | SECOND |
| 114 | THIRD FLOOR |
| 115 | Providing patti/ band 100mm wide on plastered surface 12 mm to 15 mm thick in C.M. 1:3 line and level including neat finishing scaffolding curing etc. complete. |
| 116 | GROUND FLOOR - Building - 487.40 + C.W. - 368.41 = 855.81 Cum. |
| 117 | FIRST FLOOR |
| 118 | SECOND |
| 119 | THIRD FLOOR |
| 120 | Providing patti/ band 150mm wide on plastered surface 12 mm to 15 mm thick in C.M. 1:3 line and level including neat finishing scaffolding curing etc. complete. |
| 121 | GROUND FLOOR |
| 122 | FIRST FLOOR |
| 123 | SECOND |
| 124 | THIRD FLOOR |
| 125 | Providing and fixing chicken mesh of 22 gauge, with about 30 cm. width at the junction of R.C.C members and brick work, of approved quality including fixing mesh in position by necessary drilling in concrete /B.B.masonry and or tying by binding wire etc. complete. |
| 126 | GROUND FLOOR |
| 127 | FIRST FLOOR |
| 128 | SECOND |
| 129 | THIRD FLOOR |
| 130 | Providing Groove to required size at specified location as directed by Engineer, at junction of brick masonry wall and R.C.C beams or Column, at junction of composite masonry, including scaffolding, finishing, curing etc. complete. |
| 131 | GROUND FLOOR |
| 132 | FIRST FLOOR |
| 133 | SECOND |
| 134 | THIRD FLOOR |
| 135 | Supply, fixing and installation of 4mm thick Aluminium Composite Panel (ACP) of approved colour for external cladding in combination of solid and metallic colours, including all necessary Framework, support and complete weather sealing as per architectural drawing. The Aluminium Composite Panel (ACP) should be made out of thermoplastic core of low-density polyethylene LDPE (100% virgin mix), sandwiched between two aluminium sheets of ALLOY GRADE-5000 series, each not less than 0.50 mm thick, total thickness of aluminium composite panels not to be less than 4 mm, the exposed surface thereof shall have Stove lacquered finishing coat not less than (26 + - 2) micron (containing minimum 70% kynar 500 based PVDF) of colour and shade as per architectural design. The inside surface (facing the building exterior surface)shall have polyster based powder coating not less than 25 Micron with protective peel-off foil on the exterior face (peel off film will in no case leave any adhesive mark over the composite panel surface after it is peeled off). The supporting framework shall be made out of 50 mm X25mm X 3mm thick Aluminium section to be spaced horizontally and vertically for fixing |
| 136 | GROUND FLOOR |
| 137 | FIRST FLOOR |
| 138 | SECOND |
| 139 | THIRD FLOOR |
| 140 | Providing and laying vitrified mirror / glossy finish tiles decorative type RAK/ Kajaria/ Nitco/ Asian or equivalent make having size 590 mm to 605 mm x 590 mm to 605 mm of 8 to 10 mm thickness and confirming to IS. 15622- 2006 ( group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement mortar including neat cement float, filling joints, curing and clearing etc. complete. a) FlooringTiles |
| 141 | GROUND FLOOR |
| 142 | FIRST FLOOR |
| 143 | SECOND |
| 144 | THIRD FLOOR |
| 145 | Providing and laying vitrified mirror / glossy finish tiles having size 590 mm to 605 mm x 590 mm to 605 mm of 8 to 10 mm thickness and confirming to IS. 15622-2006 ( group Bla) of approved make, shade and pat tern for floor ing in required posi t ion laid on a bed of 1:4 cement mor tar including neat cement float , fi lling joints, cur ing and clear ing etc. complete.b) Skirting WALL TILES |
| 146 | GROUND FLOOR |
| 147 | FIRST FLOOR |
| 148 | SECOND |
| 149 | THIRD FLOOR |
| 150 | Providing and laying Antiskid Ceramic tiles of approved quality of size 30 cm x 30 cm and confirming to IS 15622-2006 (Group-B IIA) for antiskid flooring in required position laid on a bed of 1:4 cement mortar including cement float, filling joint with cement slurry cleaning curing etc. complete. |
| 151 | GROUND FLOOR |
| 152 | FIRST FLOOR |
| 153 | SECOND |
| 154 | THIRD FLOOR |
| 155 | Providing and laying ceramic tiles having size 30 cm. x 60 cm. confirming to cor responding I.S. for dado and skirting in required position with ready made adhesive mortar of approved quality on plaster of 1:2 cement mor tar including joint filling with white/ colour cement slurry cleaning curing etc. complete. |
| 156 | GROUND FLOOR |
| 157 | FIRST FLOOR |
| 158 | SECOND |
| 159 | THIRD FLOOR |
| 160 | Providing and laying in position flooring of telephone black / Amba White / Cat bary brown / Ruby red / Ocean Brown granite stone of approved shade and size 18 mm to 20 mm thick on bed 1:6 cementmortar including cement floats striking joints, pointing in C.M. 1:3 curing and cleaning etc. complete. |
| 161 | GROUND FLOOR |
| 162 | FIRST FLOOR |
| 163 | SECOND |
| 164 | THIRD FLOOR |
| 165 | Providing and fixing machine cut machine polished 18 mm to 20 mm thick telephone black / Amba White / Cat bary brown / RBI red / Ocean Brown granite stone for treads and risers of steps and staircases of approved colour and shade with full moulding and three grooved line for the treads on bed of 1:4 Cement mortar including float filling joints with neat cement slurry curing polishing and cleaningetc. complete. |
| 166 | GROUND FLOOR |
| 167 | FIRST FLOOR |
| 168 | SECOND |
| 169 | THIRD FLOOR |
| 170 | Providing and laying cement concrete flooring 50 mm thick with M15 cement concrete laid to proper level and slope in alternate bays including compaction filling joints, marking lines to give the appearance of tiles of 30cm x 30cm or other size laid diagonally/ square etc finishing smooth (with extra cement) in any colour as directed and curing etc. complete. With Natural Sand |
| 171 | GROUND FLOOR - Building - 562.83 + C.W. - 3.75 = 566.58 Cum. |
| 172 | FIRST FLOOR |
| 173 | SECOND |
| 174 | THIRD FLOOR |
| 175 | Providing 25 mm to 30 mm thick partition of polished black kadappa stone slab of approved quality including giving required size and shape etc. Fixing in cement mortar 1:3 curing and cement etc. complete. a)One side polish |
| 176 | a) Kadappa 25 mm to 30 mm thick |
| 177 | GROUND FLOOR |
| 178 | FIRST FLOOR |
| 179 | SECOND |
| 180 | THIRD FLOOR |
| 181 | Providing and constructing granite kitchen platform with fixingof stainless steel sink 600 mm x 450 mm size as per detailed drawing including vertical both side polished kadappah stone 25 to 30 mm thick supports with kadappah top 35 to 40 mm thick and polished granite 16 to 20 mm top with side strips of granite at front and both sides of platform raised with two vertical granite supports 15 cm height and top granite of 75 x 40 cm including cutting, opening for sink of required size in kadappah as well as granite etc. complete. (Platform top size 5.00 m x 0.60 m and height is 0.75 m) |
| 182 | GROUND FLOOR |
| 183 | FIRST FLOOR |
| 184 | SECOND |
| 185 | THIRD FLOOR |
| 186 | Providing and fixing heavy duty inter locking concrete Rubber mould glossy paving blocks of 80 mm thickness of having a strength of 400 kg/Sq.cm. of approved quality and shape on a bed of crushed sand of 25 to 30 mm thick including skirting joints and cleaning etc. complete. (using 100% crushed sand) |
| 187 | GROUND FLOOR |
| 188 | Providing and applying putty to new plastered surfaces in two coats to receive approved paint in all positions including all mater ials,labour scaffolding and curing etc. complete. |
| 189 | GROUND FLOOR |
| 190 | FIRST FLOOR |
| 191 | SECOND |
| 192 | THIRD FLOOR |
| 193 | Providing and applying priming coat on concrete/ masonary/ Asbestos Cement plastered surfaces including scaffolding if necessary, preparing the surface by thoroughly cleaning oil, grease, dirt and other foreign matter and sand papering as required etc. complete. |
| 194 | GROUND FLOOR |
| 195 | FIRST FLOOR |
| 196 | SECOND |
| 197 | THIRD FLOOR |
| 198 | Providing and applying plastic emulsion paint of approved quality, colour and shade to oldand new surface in two coats including scaffolding, preparing the surface. (excluding primer coat) etc.complete. |
| 199 | GROUND FLOOR |
| 200 | FIRST FLOOR |
| 201 | SECOND |
| 202 | THIRD FLOOR |
| 203 | Providing and applying two coats of exterior weather shield paint of approved manufacture and of approved colour to the plastered surfaces including cleaning ,preparing the plaster surface ,applying primer coat ,scaffolding if necessary, and watering the surface for two days etc complete.NOTE: For Item No. 15 to 18 prior approval of Superintending Engineer will be necessary |
| 204 | GROUND FLOOR - Building - 2643.61 + C.W. - 1787.00 = 4430.61 Cum. |
| 205 | FIRST FLOOR |
| 206 | SECOND |
| 207 | THIRD FLOOR |
| 208 | Providing and laying telephone black / Amba White / Cadburybrown / Ruby red / Ocean Brown granite stone of 18 to 20 mm thick for door frame/ dado/ window boxing etc. On C.M. 1:6 including filling joints with polymer base filler nosing the sharp edges wherever necessary, curing, etc. complete. |
| 209 | GROUND FLOOR |
| 210 | FIRST FLOOR |
| 211 | SECOND |
| 212 | THIRD FLOOR |
| 213 | Providing and laying glossy chequered colouredtiles of approved quali ty of size 30 cm x 30 cm, confirming to cor responding I.S. for floor ing in required posi t ion laid on a bed of 1:4 cement mor tar including cement float , filling joint wi th cement slur ry cleaning cur ing etc. complete. |
| 214 | GROUND FLOOR |
| 215 | Providing and fixing M40 grade thick vibrated pull cast or similar type concrete frame with chamfer conforming to I.S. 65241983 having 6 mm dia. bars 3 Nos. And stirrups @250 mm c/c and fixing in wall with 6 Nos of hold fast of 12 mm dia bars 500 mm long including primer and oil painting etc, complete) frame size 60 mm x 100 mm (Excluding the door frame) |
| 216 | GROUND FLOOR |
| 217 | FIRST FLOOR |
| 218 | SECOND |
| 219 | THIRD FLOOR |
| 220 | Providing and fixing collapsible steel gate in one / two leaves with hot rolled vertical channels of 18 x 9 x 3 mm minimum size, crossings of M.S. flats of size 18 x 5 mm T or E section for runner of minimum 40 x 6 mm size for flange, M.S. flat for top runner of minimum size 40 x 12 mm with roller wheels confirming to grade F.G. 150 fitted with snap headed rivets of minimum size 6 mm max. spacing of vertical channels be 100 mm enclosed gate position and clear space of 150 mm between two sets of crossings with hold fasts, stoppers, spaces, handles, locking arrangement and one coat of red lead primer & oil painting etc. complete. (I.S. 10521-1983). |
| 221 | GROUND FLOOR |
| 222 | Providing and fixing solid core flush door shutter in single leaf 32 mm thick decorative type of exterior grade as per detailed drawings approved face veneers 3 mm thick on both faces or as directed, all necessary beads, mouldings and lipping, wrought iron hold fasts, chromium plated fixtures and fastenings, with brass mortise lock, chromium plated handles on both sides, and finishing with French Polish etc. complete. |
| 223 | GROUND FLOOR |
| 224 | FIRST FLOOR |
| 225 | SECOND |
| 226 | THIRD FLOOR |
| 227 | Providing and fixing in position, Double shuttered aluminium extruded powder coated openable door of specified size with aluminium door frame of powder coated section 101.60 x 44.75mm , 3.18 mm thick and shutter comprising of powder coated section having bottom and lock rail of size 150 mm x 44.5 mm x 3.00 mm thick top rails 47.62 x 44.45 mm x 3.00 mm thick , vertical style 47.62 x 44.45 mm, 3.00 mm thick and for shutter plain glass panes 5 mm thick for top panels and 12mm thick both side laminated phenol bonded particle board panels for bottom panels etc. , I.S.I. mark , heavy duty, Hydraulic floor spring of 150 kg capacity , having heavy duty concealed lock, necessary beading, glazing clips, PVC gaskets, 250mm length aluminium tower bolts, 150mm dia. pad handle, etc. as per detailed design and drawing or as directed by engineer in charge including all materials , labours, and equipment etc.complete |
| 228 | GROUND FLOOR |
| 229 | FIRST FLOOR |
| 230 | SECOND |
| 231 | THIRD FLOOR |
| 232 | Providing and fixing in position extruded aluminium partitions having frame made out of extruded tubular section of size 65 mm x 40 mm with 12 mm thick three layered flat pressed teak wood particle board bonded with BWP type exterior grade phenol formaldehyde synthetic resin conforming to IS 129231990, laminated on both sides, Novateak or equivalent with aluminium glazing clips of size 12 mm x 12 mm (conical) as per drawing etc. complete. |
| 233 | GROUND FLOOR |
| 234 | FIRST FLOOR |
| 235 | SECOND |
| 236 | THIRD FLOOR |
| 237 | Providing and fixing fiber glass reinforced polyster door shutter 30 mm thick as per IS 14856 (2000) (Reaffirmed 2006) without ventilator including chromium plated fixtures and fastening with chromium plated handles onboth sides, etc complete. |
| 238 | GROUND FLOOR |
| 239 | FIRST FLOOR |
| 240 | SECOND |
| 241 | THIRD FLOOR |
| 242 | Providing and fixing in position (as per 1868/1982) Alluminium sliding window of three tracks with rectangular pipe 95x38.10x0.90 mm at weight 0.637kg/Rmt. with window frame bottom track section 92x31.75x1.30 mm at weight 1.070 kg/Rmt. Top and side track section 92x31.75x1.30 mm at weight 0.933 kg/Rmt. The shutter should be of bearing bottom 40x18x1.25 mm at weight 0.417 kg/Rmt.Inter locking section 40x18x1.10 mm at weight 0.469 kg/Rmt. and handle and top section 40x18x1.25 mm at weight o.417 kg/Rmt. As per detailed drawings and as directed by Engineer in charge with all necessary Aluminium sections fixtures and fastenings such as roller bearing innylon casting and self locking catch fitted in vertical section of shutter including 5 mm thick plain glass and aluminium mosquito net shutter with stainless steel jaili with all required screws and nuts etc,complete.With colour Anodising with box |
| 243 | GROUND FLOOR |
| 244 | FIRST FLOOR |
| 245 | SECOND |
| 246 | THIRD FLOOR |
| 247 | Providing and fixing in position powder coated aluminium louvered windows / ventilator of various sizes with powder coating as per detailed drawing and specifications including aluminium frames 80 x 38 mm x 1.22 mm box type, 5 mm thick sheet glass louvers, of approved quality etc. complete. |
| 248 | GROUND FLOOR |
| 249 | FIRST FLOOR |
| 250 | SECOND |
| 251 | THIRD FLOOR |
| 252 | Providing and fixing mild steel grill work for windows, ventilators etc. 20 kg/sqm as per drawing including fixtures, necessary welding & painting with one coats of anticorrosive paint & two coats of oil painting complete. |
| 253 | GROUND FLOOR |
| 254 | FIRST FLOOR |
| 255 | SECOND |
| 256 | THIRD FLOOR |
| 257 | Providing and fixing mild steel grill gate with angle iron frame 65mm x 65mm x 10mm with iron bars at 150mm C/C and diagonal flats as perthe detailed drawing including hinges, pivot block locking arrangement, welding riveting and oil painting of three coats of approved shade Weight of gate 35 Kg/Smt. |
| 258 | GROUND FLOOR - Building - 21.60 + C.W. - 14.75 = 36.35 Cum. |
| 259 | Providing and Fixing mat finish stainless steel (of 302 grade)railing with top pipe of 50 mm dia. and vertical pipe of 38 mm dia at 0.60 m c/c or as required and horizontal pipes of 25 mm dia in three rows, all pipes of 2 mm thick including buffing,fabricating fixtures and fastening including pipe base of appropriate diameter and ball base of 75 mm dia above newel post of 75 mm diameter etc. complete (Prior approval of sample and brand by Ex.Engineer is necessary before use) |
| 260 | GROUND FLOOR |
| 261 | FIRST FLOOR |
| 262 | SECOND |
| 263 | THIRD FLOOR |
| 264 | Providing and fixing 40 mm diameter and 1.5 mm thick Stainless steel hand railing in S.S.304 Grade including fabricating,fixtures,errecting,necessary welding,grinding,finishing,buffing to stainless steel pipe etc. complete |
| 265 | GROUND FLOOR |
| 266 | FIRST FLOOR |
| 267 | SECOND |
| 268 | THIRD FLOOR |
| 269 | Providing structural steel work in trusses,other similar trussed purlins and members with all bracing,gusset plates etc. as per detailed designs and drawings or as directed including cutting,fabricating, hoisting, erecting fixing in position, Making riveted/bolted/welded connection and one coat of anticorrosive paint and over it 2coats of oil painting approved quality and shade etc. complete. |
| 270 | GROUND FLOOR |
| 271 | Providing and fixing colour coated Zincalume(R) AZ150(min150 gms/sq.mt. total one achside) profiled sheets for roofing.The feed material is manufactured out of nominal 0.45mm Base Metal Thickness (BMT) (0.5 mm TCT), Hi-strength steel with min.550 MP a yield strength, metallic hotd ip coated with Aluminium -Zinc alloy (55% aluminium 43.4% zinc 1.6% silicon) with COLOR BOND (R) steel quality super durable polyester paint coat (with inorganic pigment). The paint shall have a total coating thick ness o fnominal 35 um, comprising of nominal 25 um exterior coat on top surface and nominal 10um reverse coat on back surface.Profile sheet shall have nom.950-1050 mm effective cover width and nominal 25-30 mm deep ribs with subtle square fluting in the five pan at nominal 180250 mm center-to-center. The end rib shall be designed for anti capillary groove.and returnleg. The feed material should have coil manufacturers product details marked are gularinterval.Including fasteners with min.fastened with min.25umZinc-Tinalloy coated, Hexhead,self-drilling screw etc.complete.(weight of profile 4.52 kg/sqm) |
| 272 | GROUND FLOOR |
| 273 | Providing and fixing of colour coated Zinc aluminium(R) AZ150 (min 150gms/sq.mt. total on each side) profiled sheets for roofing.The feed material is manufactured out of nominal 0.45 mm Base Metal Thickness (BMT) (0.5mm TCT), Hi-strength steel with min.550 MP a yield strength, metal lichotdip coated with Aluminium Zinc alloy (55% aluminiumm 43.4% zinc 1.6% silicon) with COLOR BOND(R) steel quality super durable polyster paint coat (with in organic pigment). The paint shall have a total coating thickness of nominal 35mm, comprising of nominal 25 mm exterior coat on top surface and nominal 10 umreverse coat on back surface. Profile sheet shall have nom.950-1050 mm effective cover width and nominal 2530 mm deep ribs with sublet square fluting in the five panat nominal 180-250 mm center-to-center. The end rib shall be designed for anticapacity groove.and return leg.The feed material should have coil manufacturers product details marked are gularinterval.including fasteners with min. fastened with min.25 um Zinc- Tin alloy coated, Hexhead,self-drilling screw etc.complete.(weight of profile 4.52 kg/sqm)600 mm girth (Surface Width). |
| 274 | GROUND FLOOR |
| 275 | Providing and fixing 90 cm. x 60 cm. Granite plate engraving 10cm. Height letter, figures including painting the lefters/figures with approved colour and shade complete. |
| 276 | GROUND FLOOR |
| 277 | Providing structural steel work in trusses,other similar trussed purlins and members with all bracing,gusset plates etc. as per detailed designs and drawings or as directed including cutting,fabricating, hoisting, erecting fixing in position, Making riveted/bolted/welded connection and one coat of anticorrosive paint and over it 2coats of oil painting approved quality and shade etc. complete. |
| 278 | C.W. |
| 279 | Providing and erecting Y type barbed wire fencing with seven rows of wire with 2.45 mm dia G.I. pipe ( Rezan/ concentiDeleted ire 0.75 mm dia ) with hot dip and G.I. coated hooks as per drawingsupportedonM.S.angle50x50x6mmat2.5mtr.c/cincludingfixingand fastening with wire, painting M.S. angles with one coat of red lead primer and two coat of oil paint etc. complete. |
| 280 | C.W. |
| 281 | Dismantling brick masonry in lime or cement mortar and stacking the materils as directed with all leads, lifts etc. |
| 282 | GROUND FLOOR |
| 283 | Dismantling stone masonry in lime or cement mortar including stacking the materils as directed with all leads, lifts etc. |
| 284 | GROUND FLOOR |
| 285 | Removing rich mix cement concrete including stacking the spoils as directed with all leads, lifts etc, complete. |
| 286 | GROUND FLOOR |
| 287 | Removing doors and windows with frames and stacking the materials as directed with all leads,lifts etc. complete. |
| 288 | GROUND FLOOR |
| 289 | Removing ventilators and small windows with frame and stacking the materials with all leads,lifts etc.complete. |
| 290 | GROUND FLOOR |
| 291 | Removing cement tiles,or marble or polished shahabad floor or dado without bed concrete including stacking the materials as directed with all leads, lifts etc. complete |
| 292 | GROUND FLOOR |
| 293 | Dismantling the R.C.C.Work 1:2:4 and sorting out the materials such as steel etc.as directed and stacking them with in the specified lead as directed etc. complete. |
| 294 | GROUND FLOOR |
| 295 | Removing urinal pans or wash hand basins with frame including disconnecting the sanitary and water supply connections,removing the same carefully and stacking the service able materials as and where directed including throwing the unserviceable materials outside etc complete |
| 296 | GROUND FLOOR |
| 297 | Removing W.C. pans including disconnecting the sanitary and watersupply connections,removing and breaking flooring and bed concrete around pan removing the same carefully and stacking the service able materials as and where directed including throwing the unserviceable mateiasls outside etc.carefully and throwing out the refusal outside etc. complete. |
| 298 | GROUND FLOOR |
| 299 | Providing and applying gypsum plaster ( with Gypsum material) with finishing with gypsum material in 10 to 13 millimeter thickness to previously plastered surface / or on newly brick surface ( Excluding rough cast plaster ) in all position including preparing and Finishing the surface scaffolding etc.complete. |
| 300 | GROUND FLOOR |
| 301 | FIRST FLOOR |
| 302 | SECOND |
| 303 | THIRD FLOOR |
| 304 | Providingandfixing75mmdiastabiliserpipe/P.V.C.soilvent/wastepipeandwith necessary fixtures andfitting such as bends, tees, single junctions, slotted vent, clamps etc. complete As directed by Engineer in charge |
| 305 | Providingandfixing100mmdiastabiliserpipe/P.V.C.soilvent/wastepipeandwith necessary fixtures andfitting such as bends, tees, single junctions, slotted vent, clamps etc. complete As directed by Engineer in charge |
| 306 | Providing and fixing 15 mm dia. Screw down bib / stop tap of brass including necessary socket union nut complete. |
| 307 | Providing and fixing on walls / ceiling / floors, 40 mm dia.heavy grade having embossed as ISI Mark galvanised iron pipes weight of 4.49 Kilogram / meter with necessary fittings and remaking good the demolished portion and applying primer of anti-corrosive oil paint 2 coats Including necessary scaffolding and removing existing pipeline if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete. |
| 308 | Providing and fixing on walls/ ceiling/ floor 15mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. (Prior approval of sample by Ex.Engineer is necessary before use) |
| 309 | Providing and fixing on walls/ ceiling/ floor 20mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. (Prior approval of sample by Ex.Engineer is necessary before use) |
| 310 | Providing and fixing on walls/ ceiling/ floor 25mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. (Prior approval of sample by Ex.Engineer is necessary before use) |
| 311 | Providing and fixing on walls/ ceiling/ floor 32mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. (Prior approval of sample by Ex.Engineer is necessary before use) |
| 312 | Providing and fixing on walls/ ceiling/ floor 40mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. (Prior approval of sample by Ex.Engineer is necessary before use) |
| 313 | Providing and fixing on walls/ ceiling/ floor 50mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. (Prior approval of sample by Ex.Engineer is necessary before use) |
| 314 | Providing and fixing 40 mm. dia Ball cock medium type with PVC float including sockets & necessary fittings and tested as per municipal requirements etc. complete. complete.(Prior approval of sample and brand by Ex.Engineer is necessary before use.) |
| 315 | Providing and fixing 450mm x 550mm size superior type Belgium mirror with 16mm dia. nickel plated towel rod etc complete. (Prior approval of sample and brand by Ex.Engineer is necessary before use.) |
| 316 | Providing and fixing Glass self 125 mm wide and 600 mm long with necessary chromium plated brackets providing T.W.gutties etc complete. (Prior approval of sample and brand by Ex.Engineer is necessary before use.) |
| 317 | Providing and fixing white european type wall hung,of size 360mm x 360mm x 575mm with flush valve of approved make including soil pipe,vent pipe upto outside faceofwall,100mm dia C.I.plug bend inlet pipe all fittings,cutting &making good walls,floors etc as directed by Engineer in charge. |
| 318 | Providing and fixing orissa type colour glazed earthenware 625x450mm. w.c. pan including trap,C.I.soil and vent pipe upto the outside face of wall including 100mm.dia.C.I.plug, bend,15mm. thick 10 litre PVC flushing cistern with all necessary pipe connection etc. complete. |
| 319 | Providing and fixing White Glazed Earthenware Squatting plate (Ladies Urinal) with P.V.C. flushing cistern of 5 liters capacity with fitting, inlet pipes and stoptap, brackets for fixing the cistern, 32 mm dia.P.V.C flush pipe with fittings and flushing arrangement including lead soilpipe,lead trap,soil pipe connection upto the outside face of the wall. |
| 320 | Providing and fixing C.P.pillar cock long neck with aerator of approed make including necessary sockets / union nut etc. complete. |
| 321 | Providing and fixing P.V.C. Rain water pipes of 110 mm outer diameter and having wall thickness of 2.2 to 2.7 mm confiRmt.ing toI.S.13592-1992 including proper rain water receiving recess with P.V.C. plug, bend, necessary fittings, such as, offsets, shoes, inluding fixing the pipe on wall using approved wooden cleats projecting 25 mm to 40 mm from face of wall afixing with clips of approved quality and number, filing the joint using rubber gasket with solvent cement and properly resting the shoe of pipes on C.C. or masonry blocks, including necessary scaffolding and maintenance for 3yrs for any leakages or dislocations of pipes. All the P.V.C.fittings and additional 2 piece socket clips shall be got approved from engineer in charge etc. complete. |
| 322 | RWH - Recharge Pit Providing and constructing recharge pit of 2.0 m deep and 1.0 m dia of pre-cast RCC rings with 6.5\" dia x 25 m deep bore well at the floor of recharge pit including installation of combination of solid / perforated PVC casing pipe wrapped around with netlon mesh including 300 mm thick side filling around outside of RCC rings (annular space) with 40 mm size boulders including filling of recharge pit upto 0.5 m depth with 25-75 mm clean washed gravels from bottom up followed by 0.5 m depth of 10-25 mm of clean washed stones followed by 0.5 m of washe driver fine aggregate (naturals and / crushed sand VSI grade finely washed etc.) including netlon mesh between each gravel / fine aggregate (naturals and / crushed sand VSI grade finely washed etc.) media layer including covering with RCCslab, manhole frame & cover,PVCrungs,PVC end-caps, fittings etc.including arrange mentforinlet & outlet pipe excavation & backfilling as shownin the drawing.The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, taxes, including all leads, lifts at all levels.All material should be of approved make.All works complete as per the drawing,technical specification and direction of the Engineer in charge. |
| 323 | Boring / drilling borewell of 300 mm dia forcasing / strainer pipe, by suitable method prescribed in IS:2800 (partI),including collecting samples from different strata, preparing and submitting strata chart / bore log, including hire & running charges of all equipments, tools, plants & machinery required for the job,all complete as per direction of Engineer incharge, upto 90m depth below ground level. |
| 324 | Supplying, assembling, lowering and fixing in vertical position in borewell,unplasticized PVC medium well-casing pipe of 150 mm dia,confoRmt.ing to IS:12818,including required hire and labour charges,fittings & accessories etc.all complete,for all depths,as per the direction of Engineer in charge. |
| 325 | Providing and fixing white wash basin with half pedestal of size 515mmX615mmX460mm including pillar cock auto-closing system CP angular stopcock long thread of approved make continental including S.S.bottletrap of necessary pipe connection upto the outside face of the wall. |
| 326 | Providing and fixing stainless steel sink of size 600x510x200mm incluidng coupling,outlet pipe, elbow and other necessary fitting, finishing etc. complete. |
| 327 | Providing and fixing C.P.Angular stop clock with wall flange of approved make continental including necessary sockets/union nut etc. complete. |
| 328 | Providing and fixing C.P.wall mixer with provision for overhead shower with 115mm long bend pipe and wall flange of approved make including necessary sockets/union nut etc.complete. |
| 329 | Providing and fixing Shower Head, with shower arm of approved make mixer of including all necessary pipe fittings and connections etc. complete as directed by Engineer in charge. |
| 330 | Providing and fixing white glazed urinal of series with Pressmatic auto closing valve of having 32mm diameter P.V.C.flush pipe with fitting and flushing of approved make and arrangement including lead soil pipe,lead trap & soil pipe connection upto the outside face of wall etc.complete as directed by Engineer in charge. |
| 331 | Providing and fixing C.P. 2-Way BIB cock with wall flange of approved make including necessary sockets / union nut etc. complete as directed by Engineer in charge. |
| 332 | Providing and fixing C.P. BIB cock with wall flange of approved make including necessary sockets / union nut etc. complete as directed by Engineer in charge. |
| 333 | Providing and fixing 10 cm PVC nahani trap with grating etc. complete. |
| 334 | Providing and fixing 15cm rigid PVC Nahani trap including PVC grating,bend,connecting piece of UPVC pipe upto the outside face of wall,making the good damaged surface and testing etc.complete. (Prior approval of sample and brand byEx.Engr.is necessary before use) |
| 335 | Providing,laying and fixing P.V.C.pipe of 20mm dia.with fittings such as bends,tees,reducers,clamps,etc.including necessary excavation,trench filling etc.complete.Including removing existing pipeline if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete. |
| 336 | Providing,laying and fixing P.V.C.pipe of 25mm dia.with fittings such as bends,tees,reducers,clamps,etc.including necessary excavation,trench filling etc.complete.Including removing existing pipeline if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete. |
| 337 | Providing,laying and fixing P.V.C.pipe of 32mm dia.with fittings such as bends,tees,reducers,clamps,etc.including necessary excavation,trench filling etc.complete.Including removing existing pipeline if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete. |
| 338 | Providing,laying and fixing P.V.C.pipe of 40mm dia.with fittings such as bends,tees,reducers,clamps,etc.including necessary excavation,trench filling etc.complete.Including removing existing pipeline if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete. |
| 339 | Providing,laying and fixing P.V.C.pipe of 50mm dia.with fittings such as bends,tees,reducers,clamps,etc.including necessary excavation,trench filling etc.complete.Including removing existing pipeline if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete. |
| 340 | Providing and laying concrete pipes of I.S.NP.class of 150 mm dia meter in proper line,level and slope including necessary collars, excavation, laying, fixing with collars in cement mortar 1:1 and refilling the trench complete. |
| 341 | Providing and laying concrete pipes of I.S.NP.class of 225 mm dia meter in proper line,level and slope including necessary collars, excavation, laying, fixing with collars in cement mortar 1:1 and refilling the trench complete. |
| 342 | Providing and laying concrete pipes of I.S.NP.class of 300 mm dia meter in proper line,level and slope including necessary collars, excavation, laying, fixing with collars in cement mortar 1:1 and refilling the trench complete. |
| 343 | Providing and fixing 15 cm x 10 cm salt glazed stoneware gully trap in cement concrete 1:4:8 outside the building including cast iron grating in the sink, connecting glazed stoneware pipe, brick masonry chamber with cast iron lid and cast iron grating for the gully trap. |
| 344 | Providing and constructing Brick Masonry Inspection Chamber 60 cm x 45 cm With R.C.C.raft in B.C. soil area including cost of reinforcement,1:2:4 cement concrete channels half round G.S.W. pipes, Brick Masonry, plastering from inside and airtight with 75 mm thick R.C.C. cover medium duty 140 Kilogrametc. complete. |
| 345 | Providing and constructing Brick Masonry Inspection Chamber 90 cm x 45 cm With R.C.C.raft in B.C. soil area including cost of reinforcement,1:2:4 cement concrete channels half round G.S.W. pipes, Brick Masonry, plastering from inside and airtight with 75 mm thick R.C.C. cover medium duty 140 Kilogrametc. complete. |
| 346 | Excavation for foundation in earth, soil of all types, sand, gravel and soft murum, including removingtheexcavatedmaterialuptoadistanceof50m.beyondthebuildingareaand stackingandspreadingasdirected,dewatering,preparingthebedforthefoundationand necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 0.00 to 1.50 m.) By Manual Means |
| 347 | GARDENSOIL:Supplying onsitegarden soil well sieved90% to pass throughLS. sieve ofIO mm sixefreefromstonesrubbishlikedriedgrassroots andothersuchmaterials.Thesoilshouldbefresh fromquarry. Thecolour ofthe soil generallybe red. The soilwill be measuredby measuringbox. (Farma) (Item includes Royalty charges., Transporting, loadingunloadingetc.)leadcharges for 30 k.m. is considered including all lead and lift etc Complete. |
| 348 | FARMYARDMANURE:Supplyingonsitewell decayed,welldried,wellpowdered,withoutclods and free fromstones,driedgrass andotherrubbish material. The colur of the manure generallybe black. Themanure will bemeasured bymeasuring box. (Farma) (Item includes Transporting, loading unloadingetc.)leadchargesfor30k.m.is considered including all lead and lift etc Complete. |
| 349 | Mixing garden soil/silt & manurethoroughlywell, wateringpreviousnight.Plantingrequiredplant species, lawn grass as directed etc. complete. (1/10 of semiskilledlabour) etc Complete. |
| 350 | Plantinglargeflowering/shadytrees:-(Minimum Heightto 1Mtr.)Digging pitwithsize0.9 mx0.9mx 0.9 m Removing & conveying unwanted stuff to a requireddistanceasdirected.Filling thepitwith approvedexcavatedmaterialup to a hight of 0.30 m. and remainingheightof0.60m with fresh garden soil & manure in 3:1 proportion. Mixing soil & manure thoroughly well, levelling as directed , watering previous night, planting one or two year old minimum 1 mtrs height , healthy trees sapling as per specifications. Maintaining till well established by watering, weeding, stirring of soil replacing of casualties including all lead and lift etc complete. |
| 351 | ROSE / COMMON BUDDED VARIETY |
| 352 | MOGRA / CREEPERS / CLIMBERS |
| 353 | Saplings of small & Medium Ornamental flowering plants, Thuja , Cupresus, Ornamental ficus , Mussanda including all lead and lift Etc complete. |
| 354 | Supply of self watering system Multi Stage Tree guard / Protctor 110 mm dia & total height of 1800 mm made up with HDPE. In tubular section, first stage will be 600mm long & second and forth stage 65% perforated casting in HDPE tubular section of 300mm long each tubular section & third and fifth stage of plain 300mm long each tubular section in 110mm dia. all sections fix with stagewise with leakproof fixing arrangement 2 no tubular rubber section of75mm dia, 1.5mm thick & length 350 mm (fix on both 65% perforated tubular section at top for increase the water holding capacity as per plant height). The specially designed rubber water holding device of size 90mm dia outerside & 12mm dia innerside of 1.5mm thick as per design fix on 40mm dia. 100mm long pvc pipe seperately.(for inserting the plants). 2 nos 40mm dia. treated bamboo of 2.00 mtr. height (buried 150 mm below the bottom of excavated pit & stand with tubular section) 2 nos rubber/pvc ties ( fix at bottom & top of plain tubular section with bamboo) 2 nos 5mm dia. fromate (fixing at bottom o tubular sectionfordeeprootirrigation system)2 nos600mm long HDPElateralpipe of5mm dia.withdeeproorirrigation system (insert in the gromate & pit, away form 200 mm from plant roots). 1200 mm long barbed |
| 355 | ROAD & DRAIN |
| 356 | Excavation for roadway in earth, soil of all sorts, sand, gravel or soft murum including dressing section to the required grade, camber and side slopes and conveying the excavated materials with all lifts upto a lead of 50m. and spreading for embankment o |
| 357 | Supplying hard murum/ kankar at the road site, including conveying and stacking complete. |
| 358 | Spreading hard murum/ soft murrum/ gravel or kankar for side width complete |
| 359 | Compacting the hard murum side widths including laying in layers on each side with vibratory roller including artificial watering etc. complete. |
| 360 | Providing granular sub base (drainage layer) by coarse graded materials confirming to grading-II of Table-400-2 of MORT & H in 50:30:20 proportion of 40 mm, 20 mm crusher broken metal and crusher sand respectively, spreading on prepared surface, mixing by |
| 361 | Providing and laying in situ / ready mix cement concrete of M-10 proportion with trap/ granite/ quartzite/ gneiss metal in foundation including necessary form work, compacting and curing etc. complete. (with reversible drum type mixer with SCADA with fine |
| 362 | Providing and laying in situ cement concrete M -30 with tremix treatment for 200 mm thickness for Concrete Road is including laying plastic sheet for 125 micron thickness with groove cutting of 4 mm wide and 20 mm deep with necessary refilling with polysu |
| 363 | Providing and fixing in position TMT FE 500, 25mm dia dowel bars precoated with anticorrosive epoxy paint of required Dia. 60 cms. Long and at 30.00 cm. C/C and wherever directedincluding handling, straightening, necessary cutting supported by TMT FE 50 |
| 364 | ProvidingandlayingCastinsitu/ReadyMixcementconcreteinM-10oftrap/granite/ quartzite/gneissmetalforfoundationandbeddingincludingbailingoutwater,Steel centering, formwork, laying/pumping, compacting, roughening |
| 365 | Providing cast in situ / ready mix M20 grade cement concrete for head walls of CD work / retaining walls etc. including necessary form work, compaction, finishing and curing etc. complete. (with reversible drum type mixer/ concrete batch mix plant (pan mi |
| 366 | Providing and fixing in position TMT - FE - 500 bar reinforcement of various diameters for R.C.C.pilecaps,footings,foundations,slabs,beamscolumns,canopies,staircase,newels, chajjas,lintelspardis,copings,fins,archesetc.as |
| 367 | Providing and fixing mild steel grill work for windows, ventilators, etc. 15 Kilogram/ One Square Metreasperdrawingincludingfixturesnecessaryweldingandpaintingwithonecoatof anticorrosive paint and two coats of oil painting comple |
| 368 | A) MEDICAL OXYGEN |
| 369 | SITC of Imported Oxygen Manifold (10+10size) : Oxygen Main Manifold (10+10). with 20nos. pig tail pipes & 20nos. of non return valves with middle frame complete. 20çylinder manifold bank as left side and 20cylinder manifold bank as right side complete with 40 nos.pig tailpipes and 40nos. non-return valves, all header racks and cylinder tailpipes should be 230 bar rated, with high pressure copper link pipes verified by technical files with the quality system. The cylinders shall not be included in the quoted price. It should comply and fully meets with the latest standard HTM02-01 and Cl 1. It should be duly CE marked with CE 0088 notified body as per medical devices directive. Certificate of Origin must be given. As per tender technical s cifications. |
| 370 | Supply. Erection, Installation,Testing & Commissioning of 1 X 12 cylindêrs (or combination thereof as specfied in specifications) (Indian Make- Aktiv) Emergency manifold convlete with 10 nos. pig tail pipes & 10 nos. of non return valves with middle frame complete in an aspect.Futly Complies and meets with HTM02-Ol/NFPA99/lSO 7396-1. Refer to specifications for details.The rate shall be inclusive of ali labour, material, wastage, scaffolding. transportation. import duties, transit insurances. including all leads and rts at al levels and shall be as directed by Engineer in charge, |
| 371 | SITC of Imported Oxygen Digital LCD Screen Fully Automatic Changeover Control Panèl of 1500/1700 fpm s: It should fully complies and meets with the reqt.frements of the UK DOH Health Technical Memorandum 02-01 (HTM 020 ) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, medical gas products are classified as Class 11b Medical Devices, The Automatic Changeover Manifolds shall be supplied pre-piped, pre-wired and fully tested and comply with the United Kingdom Department of Health (DOH) publication HTM 02-01 and NHS Model Engineering Specification Cl I. A test certificate shall be provided with each system detailing the results of the factory tests (*EMC Test passed, Adiabatic test passed: Copy of certificate must be submitted.) It should have halogèn polymers free, It ShOUtd have Digital 3.5\" colorful display. It should have Integrated & protected test \"point. Pre-wired for alarm connection to BMS outputs. Line pressure shall be contlnuoùsly monitored by an electronic pressure sensors;s mechanically actuated pressure 5+dtcheS are not acceptable. The manifold shall be capable of being fully isolated via a full now ball valve In order to Change any regulator withbut interruption of supply In the event of a low line pressure |
| 372 | SITC of Copper pipes of 28 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 373 | SITC of Copper pipes of 15 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 374 | SITC of Copper pipes of 12 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 375 | Supply, installation,Testing & Commissioning of 28 mm lockable line valves (lndian Make) Refer to specifiations for details.The rates shall be inclusive of all labour, material, wostcge. scaffolding. transportation. import duties, transit insurances, including all leads ond at 01 and shall be as directed by\" Engineer in charge. |
| 376 | Supply, installation,Testing & Commissioning of 15 mm lockable line valves (lndian Make) Refer to specifiations for details.The rates shall be inclusive of all labour, material, wostcge. scaffolding. transportation. import duties, transit insurances, including all leads ond at 01 and shall be as directed by\" Engineer in charge. |
| 377 | Supplying,lnstalling,Testing and commissioning of Medical Gas Terminal Units (Gas Outlet Points) for Oxygen with probe/adaptor complete in all aspects. Fully complies and meets with HTM02-O/NFPA99/ISO 7396-1 .. Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by the Engineer in charge |
| 378 | SITC of Imported Oxygen Flow Meter with Humidifier Bottle : It shall fully comply and meets with active medical device of class lla and in compliance with the EN ISO 15002: 2008 standard. It should be duly CE marked and comply with 93/42/EEC Medical Devices: General. It shall be CE marked with the notified body number specified. It shall be provided with a copy of the certificate of origin. Pressure compensated to prevent back pressure build UP on flow indicator, It should have cartridge knob, extremely reliable, easy-to-clean and ensuring an optimized adjustment. Perfect tightness of the knob thanks to its polyamide seat. The knob was tested under pressurized working conditions during more than 10,000 cycles without showing any leakage after closing. Expanded scale providing higher reading accuracy. Durable polycarbonate flow tube with cover. Monoblock scale cover made of polyamide fora higher sturdiness and a greater safety. The inopportune unscrewing of the monoblock scale cover is not possible. Body made of nickel-plated brass, very strong. Flowmeter should be MRI compatible. Flow. meter should be placed in the vertical position. It should be light weight of 275 g. The flow meters should be of 0-15 LPM range for oxygen and with inlet pressure 50-60psi. (4.5 bar). The closing of the knob should be without any leakage. Polysulphone 250cc Humidifier bottle should be unbreakable, reusable to disinfectants and complements. |
| 379 | B)COMPRESSED AIR (4BAR) |
| 380 | Supplying,Installing,Testing and commissioning of Imported Oil Free Scroll Air Compressor: Itshould be5 0Hz, 3Phase, 440 volts. 8Bar, 116Psig. 85 cfm at 8 Bar. 22Kw &30 Hp. The 85 cfm flow capacity for each compressor unit having suitable motor rating of scroll air cooled compressor. Compressors shall be oil free scroll compressors suitable for both continuous and frequent start/stop operation at a nominal outlet pressure of 800 kPa(8bar). Each compressor shall have atleast two individual scroll elements. Theair qualitys hall be 100%oil free, certified ISO 8573-1. The compressor shall have a sound insulating enclosure. |
| 381 | SITC of Indiginous Air Receiver Tank of 2000 Ltr Water capacity with pressure Gauge |
| 382 | SITC of Heatless Air Dryer - It should have air dryer desiccant type; each having full capacity of plant flow with a minimum accuracy in a range from -20. deg.C to -60 degC atmosphere dew point with a Set point of -45 c degree |
| 383 | SITC of 4 Bar Reducing Regulator |
| 384 | SITC of Imported coarse coalescing filter 3/4\" 85 SCFM Filter Housing Complete |
| 385 | SITC of Copper pipes of 28 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 386 | SITC of Copper pipes of 15 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 387 | SITC of Copper pipes of 12 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 388 | Providing & fixing 15mm Isolation Valve (Make IBP Convex or equivalent) including all materials, labour, transport, lead, lift, fitting, testing, taxes, commissioning to the satisfication of the engineer-in-charge and maintaining for defect libility period etc. complete and as derected by engineer in charge |
| 389 | Supplying,lnstalling,Testing and commissioning of Medical Gas Terminal Units (Gas Outlet Points) for Air with probe /adaptorcomplete in all aspects. Fully complies and meets with HTM02-O/NFPA99/ISO 7396-1 .. Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by the Engineer in charge |
| 390 | C)COMPRESSED AIR ( 8 BAR) |
| 391 | SITC of Copper pipes of 28 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 392 | SITC of Copper pipes of 15 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 393 | SITC of Copper pipes of 12 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 394 | Supply, installation,Testing & Commissioning of 28 mm lockable line valves (lndian Make) Refer to specifiations for details.The rates shall be inclusive of all labour, material, wostcge. scaffolding. transportation. import duties, transit insurances, including all leads ond at 01 and shall be as directed by\" Engineer in charge. |
| 395 | Supply, installation,Testing & Commissioning of 15 mm lockable line valves (lndian Make) Refer to specifiations for details.The rates shall be inclusive of all labour, material, wostcge. scaffolding. transportation. import duties, transit insurances, including all leads ond at 01 and shall be as directed by\" Engineer in charge. |
| 396 | Supplying,lnstalling,Testing and commissioning of Medical Gas Terminal Units (Gas Outlet Points) for Air with probe /adaptorcomplete in all aspects. Fully complies and meets with HTM02-O/NFPA99/ISO 7396-1 .. Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by the Engineer in charge |
| 397 | D) VACUUM |
| 398 | Supply, fixing, testing and commissioning of duplex Medical Vacuum Plant(lndian Make). Twin Vertical vacuum receiver tank and bacterial filter, 1 PCU control complete in all aspect. Fully Complies and meets with HTM02-Ol /NFPA99/lSO 7396-1. Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding,. transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by Engineer in charge |
| 399 | SITC of Indiginous Air Receiver Tank of 2000 Ltr Water capacity with pressure Gauge |
| 400 | SITC of Copper pipes of 28 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 401 | SITC of Copper pipes of 15 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 402 | SITC of Copper pipes of 12 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 403 | Supply, installation,Testing & Commissioning of 28 mm lockable line valves (lndian Make) Refer to specifiations for details.The rates shall be inclusive of all labour, material, wostcge. scaffolding. transportation. import duties, transit insurances, including all leads ond at 01 and shall be as directed by\" Engineer in charge. |
| 404 | Supply, installation,Testing & Commissioning of 15 mm lockable line valves (lndian Make) Refer to specifiations for details.The rates shall be inclusive of all labour, material, wostcge. scaffolding. transportation. import duties, transit insurances, including all leads ond at 01 and shall be as directed by\" Engineer in charge. |
| 405 | Supplying,lnstalling,Testing and commissioning of Medical Gas Terminal Units (Gas Outlet Points) for Vacuum with probe/adaptor complete in all aspects. Fully complies and meets with HTM02-O/NFPA99/ISO 7396-1 .. Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by the Engineer in charge |
| 406 | SITC bf Imported N20 Manifold (4+4size) : N20 Main Manifold (4+4) with 8nos. pig El pipes & 8 nos. of non return valves with middle frame complete. The cylinders shall not be included in the quoted price. It should comply and fully meets with the latest standard HTM02-01 and Cl l. It should be duly CE marked with CE 0088 notified body as per medical devices directive. Certificate of Origin must be given. As er tender technical specifications. |
| 407 | SITC of Copper pipes of 28 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 408 | SITC of Copper pipes of 15 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 409 | SITC of Copper pipes of 12 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 410 | Supply, installation,Testing & Commissioning of 15 mm lockable line valves (lndian Make) Refer to specifiations for details.The rates shall be inclusive of all labour, material, wostcge. scaffolding. transportation. import duties, transit insurances, including all leads ond at 01 and shall be as directed by\" Engineer in charge. |
| 411 | Supplying,lnstalling,Testing and commissioning of Medical Gas Terminal Units (Gas Outlet Points) for N2o with probe/adaptor complete in all aspects. Fully complies and meets with HTM02-O/NFPA99/ISO 7396-1 .. Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by the Engineer in charge |
| 412 | F) CARBON DIOXIDE |
| 413 | SITC of Imported C02 Manifold 12+2size) : C02 Main Manifold (2+2) with 4nos. pig tail pipes & 4nos. of non refurn valves with middle frame complete. The cylinders shall not be included in the quoted price. It should comply and fully meetS with the latest standard HTM02-01 and Cl 1. It should be duly CE marked with CE 0088 notified body as per medical devices directive. Certificate of Ori in must be iven. As er tender technical spcificatlons. |
| 414 | SITC of Copper pipes of 28 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 415 | SITC of Copper pipes of 15 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 416 | SITC of Copper pipes of 12 mm OD X 1.0 mm thick medical grade copper tube / pipes : It should be confirmed and meet with BS:EN:1412:1996 copper pipes. All medical grade degreased copper pipe must be inspected and duly third party certified by Lloyds registered Asia Medical Grade pipe manufacturers from phospherous , de-oxidised ,non arsenical copper to BS:EN 1412:1996grade CW 024A(Cu:DHP) manufactured to metric outside diameter and having mechanical properties in accordance with BS:EN:13348:2008 & 250 (Half Hard) Degreasing of pipe shall be such that their is less than 20 mg/m2 (0.002 mg/cm2) of hydrocarbon on degreased surface when tested by the meathod specified BS:EN:13348:2008 |
| 417 | Supply, installation,Testing & Commissioning of 15 mm lockable line valves (lndian Make) Refer to specifiations for details.The rates shall be inclusive of all labour, material, wostcge. scaffolding. transportation. import duties, transit insurances, including all leads ond at 01 and shall be as directed by\" Engineer in charge. |
| 418 | Supply, installation,Testing & Commissioning of 28 mm lockable line valves (lndian Make) Refer to specifiations for details.The rates shall be inclusive of all labour, material, wostcge. scaffolding. transportation. import duties, transit insurances, including all leads ond at 01 and shall be as directed by\" Engineer in charge. |
| 419 | SITC of Imported AGSS outlet hose assembly :lt should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (ffiM 02-01) stbhddrds It shall be duly CE marked to the Medical Device Directive; 93/42/EC under the atßplces of notified body no. and under this directive, med gas products are classified as Ciass 11b Medical Devices.. It Shall be provided with a copy of the certificate\" of origin from chamber of commerce. It conducts the waste gases to the fixed System outlet point and cmnprises a 4 metre length of reinforced clear tube (Colour coded yellow and bluè as per the standard . |
| 420 | SITC of Imported AGS Plastic Remote Indicator : It should fully complies and meets with the reqùements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class 11b Medical Devices. It shall be provided with a copy of the cefficate of origin from chamber of commerce. It should be flush mounted, 24 Volt pn/off rooi•n Indicating \"red\" ant failed \"amber\" d um failed and reen\" mains airflow on. |
| 421 | SITC of Imported AGSS Reservoir : It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class 11b Medical Devices. It shall be provided with a copy of the certificate of origin from chamber of commerce. The AGSS Receiver is the practical solution for waste anaesthetic gas discharges and is designed as an integral part of any waste anaesthetic gas system.. The receiver comes complete with a transfer system, outlet hose assembly, and user instructions. making it ready for immediate use.. It should have air break which prevents suction from the disposal system being transferred to the patient -flow indicator. Under normal operating conditions the indicator should be visible. -gauze filter built into the top of the vessel to prevent gown fluff and other solid material from reaching and blocking the fixed extraction system. |
| 422 | Supplying,lnstalling,Testing and commissioning of Medical Gas Terminal Units (Gas Outlet Points) for N2o with probe/adaptor complete in all aspects. Fully complies and meets with HTM02-O/NFPA99/ISO 7396-1 .. Refer to specifications for details. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, import duties, transit insurances, including all leads and lifts at all levels and shall be as directed by the Engineer in charge |
| 423 | G) AREA ALARM PANEL |
| 424 | SITC of Imported Antimicrobial Medical Gas Area Line Pressure Alarm : 5 Gas Oxygen, N20, MA4 Air, C02 & Vacuum. It should fully complies and meets with the requirements of the UK DOH Health Technical Memorandum 02-01 (HTM 02-01) standards only. It shall be duly CE marked to the Medical Device Directive 93/42/EEC under the auspices of notified body no. and under this directive, med gas products are classified as Class 11b Medical Devices, It shall be provided with a copy of the certificate of origin from chamber of commerce. It should have anti microbial coating labels for touch control. It should be capable of monitoring UP to 6 gas services by means of pressure sensors that detect deviations from the normal operating limits.. The cover, backbox and bezel shall be polyester powder. It should have antimicrobial coating. A single tamperproof fastener shall be used to gain access to the hinged door. The hinge shall operate through a minimum of 1200 to provide adequate access. It should have each gas service shall be displayed by coloured LED\"s to show \"Normal\" (green), \"Low\" and \"High\" pressure (red) conditibns. Medical vacuum systems shall be displayed in the \"Normal\" (green) and \"Low\" vacuum (red) conditions. Failure indicators shall be displayed by flashing lights and normal indications shall be steady. Each LED block indicator shall bela plug-in component with individual long life LED\"s connected in parallel in two banks to provide duplex circuits. An audible warning shall sound simultaneously with any failure indication and a mute facility shall be provided. Following a mute selection the audible will resound after approximately 15 minutes, or shall operate simultaneously should a firther alam condition occur. A \"Mute\" switch shall be provided inside the panel for useduñng any maintenance resulting in prolonged pipeline or plant shutdown. This facility shall automatically reset when the gas service returns to normal. The alarm panel shall have a \"Test\" facility to prove the integrity of the internal circuits, LED\"s and audible warning. The alarmi panel shall incorporate a volt free ndrmatly closed relay to allow for intercðnnection to either a medical gas Central alarm system or an event recording circuit of a building management systam. |
| 425 | Supplying, Installing, Testing and commissioning of Antimicrobial Medical Gas Area Line Pressure Alarm: 3 Gas Oxygen, M A4 Air & Vacuum. Fully complies and meets with HTM02-0/NFPA99/ISO7396-1.. Refer to specifications for details. The rateshall be inclusive of all labour, material, wastage, scaffolding, transportation, importduties, transit insurances, including all leads and lifts at all levels and shall be as directed by the Engineer in charge |
| 426 | Commissioning of BED HEAD WALL PANEL 1200MM with extra probe foc ventilator. AS PER TENDER TECHNICAL SPECIFICATIONS. Refer \"to specibeations for detoits. The rate shall be inclusive of all labour, material, wastage, tonspodation. impod duties, transit insurances, including all leads and lifts ot ord shon be as dirvcted by Engineer in charge. |
| 427 | MODULAR O.T. |
| 428 | WALL and CEILING PANEL - 50 MM THICK (SS/PPGI)Providing of PPGI Modular Double Skin Flush Partition/Cladding 50mm thick with using 0.9mm Sheet on both side. The Sheet filled with with PUF insulation with 40 kg density. Color Shade of Panel RAL – 9002 or |
| 429 | Rubber pads with concrete block |
| 430 | providing & carrying out 26 SWG aluminium cladding to cover insulated ducting to protect from heat rain and birds |
| 431 | Cleanroom Doors:Double Leaf Door designed to fit flush into the wall panel system on both sides and aresupplied in different dimensions. Doors are fabtricated from GI Powdered CoatedSheets. Shutter has sheet thickness of 0.8mm and the frame of 1.2mm |
| 432 | Cleanroom Doors:Single Leaf Door designed to fit flush into the wall panel system on both sides and aresupplied in different dimensions. Doors are fabtricated from GI Powdered CoatedSheets. Shutter has sheet thickness of 0.8mm and the frame of 1.2mm |
| 433 | Magnahelic gauges with SS box & S.S front cover plate |
| 434 | Antifungal,Antibectarial,Conductive Epoxy Flooring 5 mm thick. |
| 435 | Storage rack for Surgical Instruments. |
| 436 | FURNITURE |
| 437 | Executive\"sTable @ 1800Lx900Dx750HT Providing & Fixing of Table @ 1800Lx900Dx750HT - TOP & GABLE END to be made ofMembrane finish with soft water fall edges & curved panel & Decorated Anodized section MODESTY PANEL to be made of 18 mm thick Prelaminated particle board with PVC edge band as per drawing |
| 438 | Pedestal Unit @ 420Lx450Dx650HT Providing & Fixing of PEDESTAL @ 420Lx450Dx650HT :- To be made out of Complete Membrane consist of three Drawers as per drawing. |
| 439 | Free Standing Table @ 1500Lx600Dx750HTProviding and fixing Table of Size 1500 x 600 x 750 mm. Top: made from 25 mm Prelaminated Particle board.All edges are covered by 2 mm. Thk. PVC edge bands glued by hot melt glue applied by auto edge banding machine.Legs : C Shape made from CRCA Sheet with Powder Coat finish. Modesty panel : Made from 18mm both side prelaminated particle boards.All edges are covered by 0.8mm PVC edge bands glued by hot melt glue applied by auto edge banding machine.KEYBOARD TRAY ( WITHOUT MOUSE TRAY ) :-Metal Powder Coated - Black Color, CPU TROLLEY :-Metal Powder Coated - Black Color, 3 DRAWER PEDESTAL UNIT having overall size 392L x 450D x 680Ht. mm. with central lock and key. Drawers and body are complete metal with powder coat finish, facia in 18 mm prelaminated particle board, |
| 440 | Free Standing Table @ 1200Lx600Dx750HTProviding and fixing Table of Size 1200 x 600 x 750 mm. Top: made from 25 mm Prelaminated Particle board.All edges are covered by 2 mm. Thk. PVC edge bands glued by hot melt glue applied by auto edge banding machine.Legs : C Shape made from CRCA Sheet with Powder Coat finish. Modesty panel : Made from 18mm both side prelaminated particle boards.All edges are covered by 0.8mm PVC edge bands glued by hot melt glue applied by auto edge banding machine.KEYBOARD TRAY ( WITHOUT MOUSE TRAY ) :-Metal Powder Coated - Black Color, CPU TROLLEY :-Metal Powder Coated - Black Color, 3 DRAWER PEDESTAL UNIT having overall size 392L x 450D x 680Ht. mm. with central lock and key. Drawers and body are complete metal with powder coat finish, facia in 18 mm prelaminated particle board, |
| 441 | Conference Table @ 3600Lx1400Dx750HTProviding & Fixing of Main Table @ 3600Lx1400Dx750HT - made up of 18+18mm Thick MDF top with PVC Membrane finish and waterfall edge profile. Aluminium Anodizied finish beeding of 4mm thich is running all over the table top edge. Gable ends is Aerofoiled Shape with front edges in PVC Membrane finish and rest in Prelaminated MDF with batton structure. Gable ends should be hollow from inside for the provision of passing electrical and Data wiring. , MODESTY PANEL:- to be made of 18 mm thick Prelaminated particle board with PVC edge band Access Flap:- For Wire manager 2 Nos. |
| 442 | Low Height Openable Storage @ 900Lx450x750HT Providing and fixing Openable Steel Storage of 900 x 450 x 750Ht, with 2 adjustable shelves, Complete body & shutter made in0.8 mm thick & Top in 2 mm thick CRCA, 2 Shutter to be mounted with the help of cup hinges, and 4 adjustable levelers, enitre storage in powder coated finish with 60 to 80 microns. with 25 mm. thk additional Top on top of storage as as per drawing |
| 443 | Medium Height Steel Storage @ 750Lx450Dx1200HTProviding and fixing Openable Steel Storage of 750 x 450 x 1200Ht, with 2 adjustable shelves, Complete body & shutter made in0.8 mm thick & Top in 2 mm thick CRCA, 2 Shutter to be mounted with the help of cup hinges, and 4 adjustable levelers, enitre storage in powder coated finish with 60 to 80 microns. with 25 mm. thk. as per drawing. |
| 444 | Full Height Steel Storage @ 750Lx450Dx2100HTProviding and fixing Openable Steel Storage of 750 x 450 x 2100Ht, with 4 adjustable shelves, Complete body & shutter made in0.8 mm thick & Topin 2 mm thick CRCA, 4 Shutter to be mounted with the help of cup hinges, and 4 adjustable levelers, enitre storage in powder coated finish with 60 to 80 microns as as per drawing. |
| 445 | Providing & Arrangemnt of High Back, Synchronized Mechanism with Multiple Locking, Adjustable Armrest, Gaslift for Seat height adjustment, Standard 5-prong P/Nylon Basewith Leatherite Upholstery |
| 446 | Providing & Arrangemnt of MId Back, Normal SyncroMechanism , Fixed Armrest , Gaslift for Seat height adjustment, Standard 5-prong/Nylon Base with Leather Upholstery |
| 447 | Public Seating Chair. - 3 SeaterProviding and Fixing 3 seater Public seating chair made of complete metal with Legs in Crome finish and seates in silver powder coating finish. |
| 448 | Single Bed @ 2025LX 1000DX 650HProviding and fixing Single Bed of Size 2025Lx1000Dx650Hwith matress and pillow. Understructure: - The legs are made of Square tube of size 25 x 25mm made out of MS with a thickness of 1.2 mm. The legs should have corner brackets welded to it at two levels. The corner brackets are made of 2mm thick CRCA having a L shaped structure to join the side panels and headboard to the leg. Three nos. of Horizontal stiffeners are provided at equal intervals. The stiffeners are made of Square tube of size 25 x 25mm made out of MS with a thickness of 1.2mm. The middle Horizontal Stiffener has a leg attached to it to transfer the load to the ground and add to the strength and stability of the complete structure. This leg is also made of Square tube of size 25 x 25mm made out of MS with a thickness of 1.2mm. All Metal components to undergo 7 tank treatment process and should be powder coated to the thickness of minimum 50 Microns DFT.Side Panel: - The side panels are made up of 18mm thick Prelam Particle Board with both side decorative laminate. All exposed edges are sealed with 2mm thick PVC edge Banding. The overall width of the side panel is 150mm. The side panels have 18mm thick prelam particle board Baton running for required length to add rigidity to the structure. Head Board :- The head board is made up of 18mm thick Prelam Particle Board with both side decorative laminate. All exposed edges are sealed with 2mm thick PVC edge Banding. The head board size to be considered as 1000 x 650mm. Foot Board :- The foot board is made up of 18mm thick Prelam Particle Board with both side decorative laminate. All exposed edges are sealed with 2mm thick PVC edge Banding. The head board size to be considered as 1000 x 450mm.Bed Base: - The Bed Base is made up of 12mm thick Prelam Particle Board with both side White laminate. |
| 449 | Bed Side Table @ 400LX 400DX 415HProviding and Fixing Bed Side Table of size 400LX 400DX 415H The bed side unit is made up of 18mm thick Prelam Particle Board with both side decorative laminate. All exposed edges are sealed with 2mm thick PVC edge Banding. The bed side table has one drawer and one shelf. The shelf is made of 18mm thick Prelam Particle Board with both side decorative laminate. All exposed edges are sealed with 2mm thick PVC edge Banding |
| 450 | Kitchen TrolleyProviding and Fixing stainless steel kitchen trolley of overall 26 \" height and 22\" depth,supported on aluminium pipes ,trolley basket made out of 5 mm stainless steel rod fitted on telescopic channel of size 1.5 \" x 20 \" x 22 \" on both sides of trolley of 12 \" or above size, panel having 40Kilogramload bearing capacity of trolley made out of 20 mm PUC coated plywood and colour combination as directed by E-I-C.Inner side of panel covered by white mica ,100 mm s.s. decorative handle.(The width and height of individual compartments shall be kept as directed by Engineer-in-charge) |
| 451 | ELECTRICAL WORKS |
| 452 | Supplying and erecting HMS PVC conduit FRLS grade 20 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC. |
| 453 | Supplying and layingHMS PVC conduit FRLS grade 20 mm dia. with necessary accessories in RCC work/false ceiling/false flooring as per specification No.WG-MA/CC. |
| 454 | Supplying and erectingHMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No: WG-MA/CC. |
| 455 | Supplying and layingHMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC. |
| 456 | 1.2 PVC Flexible/Rigid Conduits/Casing-n-Capping/ Under Floor Trunking/ Raceways and Box Trunking |
| 457 | (WG-MA/CON) |
| 458 | Supplying and erecting 20mm dia. corrugated flexiblepolypropylene conduit |
| 459 | Supplying and erecting 25 mm dia. corrugated flexiblepolypropyleneconduit |
| 460 | Supplying anderectingPVCboxtrunking ofsize 75x50 mm. with accessorieson wall/ceiling as per specification No:WG-MA/BOX. |
| 461 | Supplying anderectingPVCboxtrunking ofsize 75x75 mm. with accessorieson wall/ceiling as per specification No:WG-MA/BOX. |
| 462 | 1.3 Bunch of Wires (WG-MA/BW) |
| 463 | Supplying and erecting mains with 3x2.5 sq.mm FRLSH copper PVC insulated wirelaid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 464 | Supplying and erecting mains with3x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 465 | Supplying and erecting mains with 3x6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 466 | 1.6 Modular switches and Accessories |
| 467 | Supplying and erecting ISI mark modular type switch6A / 10A duly erected on provided plate and box with wiring connections complete. |
| 468 | Supplying and erecting ISI mark modular type switch16A duly erected on provided plate and box with wiring connections complete. |
| 469 | Supplying and erectingmodular type bell-push 6A / 10A duly erected on provided plate and box with wiring connections complete. |
| 470 | Supplying and erectingmodular type D.P. switch 32A with indicator, duly erected on provided plate and box with wiring connections complete. |
| 471 | Supplying and erectingmodular type 3 pin 6Amultisocket with safety shutter,duly erected on provided plate and box with wiring connections complete. |
| 472 | Supplying and erectingmodular type 3 pin 6 / 16Amultisocket with safety shutter,duly erected on provided plate and box with wiring connections complete. |
| 473 | Supplying and erectingmodular type T.V. socket single outlet, duly erected on provided plate and box with wiring connections complete. |
| 474 | Supplying and erectingmodular type bell indicator, duly erected on provided plate and box with wiring connections complete. |
| 475 | Supplying and erectingmodulartype (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete. |
| 476 | Supplying and erecting modular type blanking plate one module, duly erected on provided plate & box. |
| 477 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 2 moduleduly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 478 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 4 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 479 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 6 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 480 | Supplying and erecting unbreakable concealed typemodular switch box with double mounting plate for8 moduleduly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 481 | Supplying and erecting 6 to 32 A, 10kA, SPMCB suitable to fix in1 moduleof modular switch in provided box complete & duly concealed with necessary material and connected. |
| 482 | Supplying and erecting 16 to 32 A, 10kA, DPMCB suitable to fix in2 moduleof modular switch in provided box complete & duly concealed with necessary material and connected. |
| 483 | Bed Head panels |
| 484 | Bed head panels with extruded Aluminium body, pre-treated matt satin finish, Epoxy-polyester powder coat in sky blue colour with following configuration; |
| 485 | Supplying and erecting ICU, surgical wards, isolation ward, pre-post operative ward, Dialysis ward Bed Head Panels, 1200 mm length x 210 mm height x 58 mm depth (+/- 2 mm Tolerance), with two numbers of 16A modular MCB, isolation wired, 2 Nos. 6/16 Amp electrical switch sockets, 3 Nos. 6A modular MCB, with 6A sockets. Provision for 3 numbers of electrical isolated medical gas outlets, slot for nurse call bed unit module, 6sqmm x 3 run, copper multi stranded, PVC insulated, FRLSH wiring factory harnessed and tested successfully |
| 486 | Supplying and erecting SS 304 rail for instrument mounting 2 feet in length per bed head panel |
| 487 | Point Wiring(PW) |
| 488 | 1.7 Point Wiring (WG-PW) |
| 489 | Point wiring forlight/bellhybrid type (Surface type under false ceiling and concealed type for drops & switch boards on walls)in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No:WG-PW/HW |
| 490 | Point wiring forceilingfan (Surface type under false ceiling and concealed type for drops & switch boards on walls)in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No:WG-PW/HW |
| 491 | Secondary point wiring foradditionallight/ bell point, concealed type in min 20 mm FRLS grade PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires with required accessories as per specification No: WG-PW/CW |
| 492 | Point wiring for Exhaust fan in 20 mm FRLS grade HMS PVCconduit with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthingand required accessories as per specification No: WG-PW/SW. |
| 493 | 1) For point wiring above 6 meters of length, add 10 % of overall rate of point wiring for every additional 1 meter length or part thereof. |
| 494 | 2)Point wiring starts from Main board/Intermediate switch board and suitable circuit mains are to be provided from D.B. to first board and between boards. |
| 495 | 2.1 Indoor Fittings (FG-IDF/LED) |
| 496 | Supplying and erectingLED square / circular Max. 18 W down lighter/ Panel Light having pressure die-cast aluminium housing,polystyrenediffuser having systemlumens output of Min. 2000 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%,THD<10%, p.f. >0.95, operating range of120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver,having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. |
| 497 | Supplying and erectingLEDPanel Light(600mm X 600mm) Max. 35 Whaving CRCA powder coated housing,polystyrenediffuser havingsystemlumensoutput of Min 4200 Lumens, min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%,THD<10%, p.f. >0.95, operating range of120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50including driver,having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. |
| 498 | Making suitable size recess in any type of false ceiling for erection of flush type down lighter and finishing the background to match the original surface upto 20W. |
| 499 | Making suitable size of recess in any type of false ceiling for erection of flush type LED panel light 600mm x 600mm/1200x300mm and finishing the background to match the original ceiling surface. |
| 500 | Supplying and erecting anodized aluminium corridor / passage / mirror light LED fitting (2 feet) Max. 12Wwith high transitivity diffuser with min. systemlumens output of 1200 lumens, min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple<5%,THD<10%,p.f. >0.95, operating range of200-270V, surge protection of 2 kV, Life class of 50,000 Hrs. at L70B50, including driver with end caps on provided PVC Block / wooden board with 3 years warranty. |
| 501 | Supplying and erecting anodized aluminium corridor / passage light LED fitting (4 feet) Max. 22Wwith high transitivity diffuser withsystem lumens output ofMin.2200 lumens , min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple<5%,THD<10%,p.f. >0.95, operating range of200-270V, surge protection of 2 kV, Life class of 50,000 Hrs. at L70B50, including driver, with end caps on provided PVC Block / wooden board with 3 years warranty. |
| 502 | 1) System efficacy shall not be less than 90 lumens/watt, |
| 503 | 2) CRI shall be more than 80. |
| 504 | 3) Total harmonic distortion voltage and current shall be less than 10% |
| 505 | 4) Operating voltage range shall be in range of 160V to 270V |
| 506 | 5) Power Factor of Luminaire shall be more than 0.95 |
| 507 | 6) Luminaire shall conform to respective IS. |
| 508 | 7) Luminaire shall withstand surge protection upto 2 kV |
| 509 | 8) Luminaire shall carry minimum three years warrantee. |
| 510 | 9) Correlated Colour Temperature (CCT) shall be required between 2700K-6500K. |
| 511 | 2.10 Fans (FG-FN) |
| 512 | Supplying and erecting exhaust fan medium duty230 V A.C. 50 cycles 225 mm. 1400 RPM with condenser complete erected in position with necessary materials. Fan motor with moisture proof treatment and ‘E’ class insulation. |
| 513 | Supplying and erectingenergy saving ceiling fan230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no.FG-FN/CF |
| 514 | 2.11 Accessories for Fans (FG-FN) |
| 515 | Supplying and erecting fan hook of 10 mm. M.S. round bar grouted in RCC slab with making the site as original. |
| 516 | Supplying and erecting‘B’ class G.I .pipe / M.S. pipe down rod duly painted for fan complete erected with PVC three core flexible cable 1 sq. mm copper PVC wire. |
| 517 | 2.4 Outdoor Fittings (FG-ODF/LED) |
| 518 | Supplying and erecting integrated LED street light fitting 23 to 25W IP65 & IK08 class having single piece pressure die-cast aluminium housing,havingsystem lumens output of Min. 2300 Lumens, min. efficacy of 100 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver complete with 3Years warranty as per specification NoFG-ODF/FLS2. |
| 519 | Supplying and erecting street light Wall bracket made from 40 mm. dia‘ G.I. pipe 1.2 m. in total length complete as per specification no. FG-BKT/WB |
| 520 | 3.7Online Uninterruptible Power Supply (UPS)(AP-UPS) |
| 521 | Supplying & erecting on line UPSpure sine wave of 80 kVA capacity complete with standard features, along with necessary SMF batteries for 30 mins battery backup,as per specification no.AP-UPS |
| 522 | 5.2 IC / MC Distribution Boards/ Mini Feeder Pillar/ Street Light Control Panel(SW-DB) |
| 523 | Supply, Installation, Testing and Commissioning of MainLV panel, cubicle type, made out of min 2 mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system with busbars extendable on both sides, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. |
| 524 | Supplying and erecting metal work in CRCA sheet including Iron work for supportswith fabrication ofboxes,panelboards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment andduly powder coated or paintedwith one coat of red lead paint and 2 coats of enamel paintcomplete. |
| 525 | M. S. Sheet 2 mm, Size of L.T. Panel 4 Mtr X 2 Mtr X 1 Mtr = 28 Sq. Mtr. @15.7 Kg/Sq.mtr=484 Kg outdoor installation Double door with canopy |
| 526 | Supplyinganderectingiron work, sheet metal workconsisting of CRCAsheets, varioussectionsofiron,plates, chequeredplates,rods,bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthepositionwith necessarymaterialsdulypaintedwith one coat of red oxide and two coats of enamelpaint to match the switchgears or as per directions by the authority. MS angle 50 * 50 * 6 mm = 22 meter @ 3.8 kg/meter |
| 527 | 1) Quantity of iron/sheet metal work shall be considered and worked out as per steel data table. |
| 528 | Supplying and erecting self-locking arrangement with keys in duplicate, made of brass of grade 1 compliance to IS 729-1979duly erected, flush with surface of panel / cupboard |
| 529 | Incomer |
| 530 | Supplying, installing, testing and commissioning air circuit breaker manual fixed type, non-drawout type, 650V, 800A, rated at 50º C without deration, 12kV Impulse, 4 pole (100% Neutral Protection), 50 kA (Ics=Icu=Icw for 1s), with standard accessories with ready to close, individual fault trip, alarm and trip indications, mechanical and electrical anti pumping, soft/ hard rating plug (including hard rating plug CT) with Micro-processer based LCD display release with LSIG and temperature rise protection & with 4 C/O contacts for On-Off-Trip indication, min. 5 event and trip history on breaker display on provided iron frame as per specification no. SW-SWR/ACB |
| 531 | Suitable electrical and mechanical interlock shall be provided between the DG and EB incomer. |
| 532 | Busbar |
| 533 | Supplying and erecting of any size electrolyte aluminium patti or bar in bus bar chamber / in panel or any other purpose, 500 V with require capacity99.9% aluminium purity with E91E Grade as per IS 5082 & Current Density 0.8 A per sq. mm.with fixing arrangement (like lug or bottle type lug) to both the end with high grade polyolefininsulation sleeve complete as per specification no. BCP-BB |
| 534 | 100mm x 10mm Aluminium Bus bar x 6 meters length x 4 Nos. |
| 535 | Instruments |
| 536 | Supplyinganderecting AC Three Phase Four wire Multifunction Energy Meter of Rating 10 - 60A, Class 1.0 with din rail / Panelmounting to measures and displayparameters with RS485 Modbus communication port. mounting whole current operated meter to measures and display V, I,kWh, KVAh, KW, KVA, P.F, THD, RS 485 Communication port. Electrical parameters shall be available on com port with their mapping address open for third party software |
| 537 | Supplying&erecting LED type indicating pilot lamp with LED colours red / yellow / green, 230 / 250Von providedbox / panelwith necessary material, wiring & connections etc. |
| 538 | Supplying&erecting LED type indicating pilot lamp with LED colour blue, 230 / 250 V on provided box / panel with necessary material, wiring & connections etc. |
| 539 | Outgoing. |
| 540 | Supplying, installing, testing and commissioning air circuit breaker manual fixed type,non-drawout type,650V,630A, rated at 50º C without deration, 12kV Impulse, 4 pole (100% Neutral Protection), 50 kA (Ics=Icu=Icw for 1s), with standard accessories with ready to close, individual fault trip, alarm and trip indications, mechanical and electrical anti pumping,soft/ hard rating plug (including hard rating plug CT) with Micro-processer based LCD display release with LSIG and temperature rise protection & with 4 C/O contacts for On-Off-Trip indication, min. 5 event and trip history on breaker displayon provided iron frame as per specification no. SW-SWR/ACB |
| 541 | Supplying, installing, testing and commissioning air circuit breaker manual fixed type, non-drawout type, 650V, 800A, rated at 50º C without deration, 12kV Impulse, 4 pole (100% Neutral Protection), 50 kA (Ics=Icu=Icw for 1s), with standard accessories with ready to close, individual fault trip, alarm and trip indications, mechanical and electrical anti pumping, soft/ hard rating plug (including hard rating plug CT) with Micro-processer based LCD display release with LSIG and temperature rise protection & with 4 C/O contacts for On-Off-Trip indication, min. 5 event and trip history on breaker display on provided iron frame as per specification no. SW-SWR/ACB |
| 542 | Providing & erecting3 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 543 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 544 | Providing & erecting 3 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA(Ics=100% of Icu),adjustablethermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW-SWR/MCCB |
| 545 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 546 | Providing & erecting 3 Pole MCCB 415V,630A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides,with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 547 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 548 | Supplying and erecting 150 kVAr,3 phase, 50 Hz., Power contactors Derated formicroprocessor APFC controller with MPP / APP type capacitor with 525 V and having minimum overcurrent capacity of 1.8 In,peak inrush current capacity 300 Inand minimum life 150000 hours with , consisting of suitable steps of MPP/APPtype capacitor units with detuned aluminium filter 7% reactors with circuit breaker as main incomer and MCCB for each branch protection, as per specification no CP-ED/APFC |
| 549 | Outgoing. |
| 550 | 1 Nos. 50kVAR MPP heavy duty capacitor with capacitor duty contactor & 7% detuned harmonic filter. |
| 551 | 2 Nos. 25kVAR MPP heavy duty capacitor with capacitor duty contactor & 7% detuned harmonic filter. |
| 552 | 4 Nos. 12.5kVAR MPP heavy duty capacitor with capacitor duty contactor & 7% detuned harmonic filter. |
| 553 | Supply, Installation, Testing and Commissioning of LIFT PANEL, cubicle type, made out of min 1.6 mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system with busbars extendable on both sides, including internal wiring with suitable size wires, rotary handle, spreaders, 2mm thick gland plate, hinged type door with neoprene / PU gasket etc. |
| 554 | Providing & erecting floor/wall mounting, MCCB panel board, with door, suitable for four pole incoming 250A,4 ways four pole outgoing, up to 100 A MCCBs on iron frame, as per specification no SW-SWR/MCCBPB. (Excluding MCCBs) |
| 555 | Incomer |
| 556 | Providing & erecting3 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 557 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 558 | Outgoing: |
| 559 | Providing & erecting 3 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact.MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 560 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 561 | Supply & Commissioning of Main UPS panel of 80kVA, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. |
| 562 | Providing & erecting floor/wall mounting, MCCB panel board, with door, suitable for four pole incoming 250A, 8 ways Four pole outgoing, up to 100 A MCCBs on iron frame, as per specification no SW-SWR/MCCBPB. (Excluding MCCBs) |
| 563 | Incomer |
| 564 | Providing & erecting3 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 565 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 566 | Instruments |
| 567 | Supplyinganderecting AC Three Phase Four wire Multifunction Energy Meter of Rating 10 - 60A, Class 1.0 with din rail / Panelmounting to measures and displayparameters with RS485 Modbus communication port. mounting whole current operated meter to measures and display V, I,kWh, KVAh, KW, KVA, P.F, THD, RS 485 Communication port. Electrical parameters shall be available on com port with their mapping address open for third party software |
| 568 | Supplying&erecting LED type indicating pilot lamp with LED colours red / yellow / green, 230 / 250Von providedbox / panelwith necessary material, wiring & connections etc. |
| 569 | Supplying&erecting LED type indicating pilot lamp with LED colour blue, 230 / 250 V on provided box / panel with necessary material, wiring & connections etc. |
| 570 | Outgoing. |
| 571 | Providing & erecting 3 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact.MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 572 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 573 | Supply, Installation, Testing and Commissioning of Fire panel, cubicle type, made out of min 2mm thick CRCA sheet (load bearing), totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system, including internal wiring with suitable size wires, rotary handle, spreaders, 3mm thick gland plate, hinged type door with neoprene / PU gasket etc. The panel shall include supply & installation of following switchgears, metering instruments and accessories as per specification. |
| 574 | Supplying, erecting, testing & commissioning of fire pump control panel (FCP) of cubical construction, floor mounted type, fabricated from minimum 2 mm thick CRCA sheet, compartmentalised with hinged lockable doors, with enclosure protection class IP54, duly powder coated or painted with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003), cable alley, interconnection with suitable size solid copper busbar strip of adequate size for all power connections having switchgears and accessories, mountings and internal wiring with adequate size copper conductor cable, earth terminals, numbering etc. complete in all respect, suitable for satisfactory operation of main fire pump and jockey (pressurisation) pumps (1working+1standby) with necessary accessories, wiring & cabling along with allied accessorieswith following incoming and outgoings, suitable for automatic & manual operation on 415V, 3 phase, 50Hz ac supply as per specifications |
| 575 | the capacity of electric motor driven pump are as follows |
| 576 | a. Main fire pump(MFP) having capacity of 22kW 1no (1 working) |
| 577 | b. Jockey pump(JP) capacity of suitable capacity 2 nos(1 working +1 standby, alternate run per start in auto mode) |
| 578 | comprises of the following features & switchgears: |
| 579 | 1. Main incomer FP SFU having rotary handle with HRC fuses of suitable rating. |
| 580 | 2. Electrolytic grade copper strips for busbar of suitable sizes for main incomer and branches to motor SFU\"s, starters & outgoing terminals with necessary accessories like stainless steel nut bolts with spring washers for connections, mounted on required no of epoxy or porcelain support insulators of suitable ratings etc. |
| 581 | 3. Individual pump TPN SFU having rotary handlewith HRC fuses of suitable rating.4. Digital voltmeter & ammeter & RYB indicating lamps & push buttons & SPP, O/L & phase reversal protection with emergency stop switch. |
| 582 | 5. TPN SPD 100kA Type 1 +2 tested. |
| 583 | 6. Required pressure transducer with pressure indication on panel with cabling required for monitoring & automatic operation of fire pumps. |
| 584 | 7. System controller to control operation of main electric fire pump, jockey (pressurization) pumps in sequence with interlocking for operation of pumps as per specification with automatic/manual operation with selector switch & alternate run of standby Pumps consisting of relays, timers. sensors, annunciation window for fault indication, complete as per specification. |
| 585 | 8.Suitable capacity electric motor starters for all individual pumps with necessary push buttons & indications. |
| 586 | 9. Siren of required capacity to be activated when main pump starts & allied accessories as per requirements of local CFO or as directed by engineer in charge. |
| 587 | 10. Danger board as per IS. |
| 588 | 11. Spare HRC fuses minimum 2nos of each individual rating with required bakelite fuse holder for main & jockey fire pumps MFP=(1working), JP = (1working+1standby, alternate run per start in auto mode) complete panel, asper specification no. FF-MFP/ECP |
| 589 | Add on |
| 590 | For addition of capacity of main electric motor driven fire pump MFP (1 working) for hydrant system is more than 22kW, add as follows in the basic cost of Item no 13-5-1 towards increased capacity switchgears and motor starters for main & jockey pumps along with necessary accessoriesfor main & jockey fire pumps MFP=(1working), JP = (1working + 1standby, alternate run per start in auto mode) |
| 591 | For main electric motor driven fire hydrant system pump of 55kW capacity & relevant capacity jockey pump add Rs… |
| 592 | For addition of fire sprinkler system to basic fire hydrant system control panel(FCP) which includes one main electric motor driven firepump MFP (1working) having __kW capacity& relevant capacity jockey pumps, add as follows in the basic cost of Item no 13-5-1 towards increased capacity switchgearsbusbar and additional motor starters for main & jockey pumps along with necessary accessories with software & hardware for main & jockey fire pumps additional Sprinkler system MFP=(1working)@22kW, JP = (1working+1standby, alternate run per start in auto mode) @relevant capacity |
| 593 | For main electric motor driven fire sprinkler system pump of 55kW capacity (1Working) & relevant capacity jockey pumps (1working+1standby, alternate run per start in auto mode,add Rs…. |
| 594 | For addition of standby main diesel engine driven fire pump (1 standby), add as follows in the basic cost of Item no 13-5-1 towards required 12/24 v battery charger and diesel engine starter along with necessary accessories, indicators etc. with necessary interlocking and updation of control logic with interlocking for operation of pumps MFP for main (1working+1standby mode)& jockey fire pumps (1working+1standby, alternate run per start in auto mode) , add Rs....... |
| 595 | The control for diesel engine comprises ofautomatic/manual selector switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode indicating lamp for high/ low Lub. oil pressure, high water temp and engine on indication battery charger suitable for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC voltmeter, and 0-20 A DC ammeter with all standard relays and accessories required for automatic operation of diesel engine with interlocking for operation of main fire pumps. |
| 596 | For addition of booster pump for fire hydrant/sprinkler, add as follows in the basic cost of item no 13-5-1 towards necessary accessories, indicators etc. with necessary interlocking and updation of control logic, add Rs....... |
| 597 | for 5.5/ 7.5 kW centrifugal type booster pump 1no(1working) , add Rs….... |
| 598 | 5.3 LT - MCBs/ MCB Change Over Switch(SW-MCB) |
| 599 | Supplying, erecting & marking SPMCB 6A to 32A, C-serieswithrated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 600 | Supplying, erecting & marking SPMCB 6A to 32A, B-series withrated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 601 | Supplying, erecting & marking FPMCB 6A to 32A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 602 | Supplying, erecting & marking FPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kAin provided distribution board as per specification no. SW-SWR/MCB |
| 603 | Supplying, erecting and markingfour pole isolators only switch version of miniature circuit breakers of 63Ain provided distribution board. |
| 604 | 1) For lighting load \"B\" series MCBs are to be provided and for motive/inductive power load \"C\" series MCB s are to be provided |
| 605 | 3) ROHS compliant MCB\"s, MCCB\"s, RCCB\"s, RCBO\"s and distribution boards shall be preferred. |
| 606 | 4) For use of MCB\"s with inbuilt short circuit indication on each pole add 10% in the cost of material component. |
| 607 | 5.4 LT - MCBDBs (SW-MCBDB) |
| 608 | Supplying&erecting triplepole and neutral distribution board (TPNDB), SPMCB of 8 ways / phase (24 poles),with door, 1.2mm thickness surface/ flushmounted, IP 43 Protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB |
| 609 | Supplying&erectingtriplepoleand neutral distribution board (TPNDB), SPMCB of 12 ways /phase (36 poles), with door,1.2mm thickness surface/flushmounted, IP 43 Protection on iron/GI frame (horizontal busbar type)as per specification no. SW-SWR/MCBDB |
| 610 | Supplyingand erectingsingle pole and neutral distributionboard (SPNDB), with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs,with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB |
| 611 | Supplying & erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBOcomplete erected on angle iron/GI frame. |
| 612 | 1) All MCB\"s shall have breaking capacity not less than 10 kA. |
| 613 | 2) Above rates are applicable only to factory made enclosures. |
| 614 | 3) Reduce overall rates by 5% if angle iron frame is not required. |
| 615 | 4) MCB\"s (double pole, four pole or triple pole & neutral) & isolators for single phase circuits shall not be incorporated for outgoing circuits of three phase distribution board. |
| 616 | 5) For more than 2 kW load RCCB shall invariably be provided & erected preferably on the same distribution board. (RCCB+MCB) or (RCCB+MCCB etc,) separate box for RCCB/ELCB is not permissible. |
| 617 | 6) Above rates are for branded DB\"s with provision of same brand interior switchgears |
| 618 | 7) The MCBDB is exclusive of incoming MCB/MCCB and outgoing SP/TP MCB\"s and the same should be preferably of the same make |
| 619 | 8) ROHS compliant MCB\"s, MCCB\"s, RCCB\"s, RCBO\"s and Distribution Boards shall be preferred. |
| 620 | 9) DB,s with IEC 61439 part 1 &3 and minimum IK 08 shall be preferred. |
| 621 | 5.5 LT -MCCBs(SW-MCCB) |
| 622 | Providing & erecting 4 Pole MCCB of 200A,415V capacity with short circuit rating 25 kA (Ics=100% of Icu)adjustablethermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frameas per specification no. SW-SWR/MCCB |
| 623 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 624 | 2) In case of specialised application, MCCB used at incomer level shall bemicroprocessor based with LSIG (overload, short circuit, instantaneous, earth fault) inbuilt protection and shall have door mounted display to ensure close door operation; increase the rate by 20%. |
| 625 | 3)MCCBs which are used as incomer in main panel shall be of four pole only to ensure neutral isolation. |
| 626 | 5.6RCCB / RCBO (SW-RCCB) |
| 627 | Providing, erecting and commissioning 2 poleRCCB only ofelectromagnetictype with 30/100/300 mA sensitivity and having capacity of 16/ 25A complete as per specification no. SW-RCCB/RCCB |
| 628 | Providing, erecting and commissioning 2 pole RCCBonly ofelectromagnetictype with 30/100/300 mA sensitivity and having capacity of 40A completeas per specification no. SW-RCCB/RCCB |
| 629 | Providing, erecting and commissioning 2 pole RCCBonly ofelectromagnetictype with 30/100/300 mA sensitivity and havingcapacity of63Acompleteas per specification no. SW-RCCB/RCCB |
| 630 | Providing, erecting and commissioning 4 pole RCCB only of electromagnetic type with 30/100/300 mA sensitivity and having capacity of 16/25A complete as per specification no. SW-RCCB/RCCB |
| 631 | Providing, erecting andcommissioning 4 pole RCCB of electromagnetic type with 30/100/300 mA sensitivity and having capacity of 63A complete as per specification no. SW-RCCB/RCCB |
| 632 | 1) For human safety RCCB with 30mA sensitivity shall be selected. |
| 633 | 2) ROHS compliant MCB\"s,MCCB\"s, RCCB\"s, RCBO\"s and Distribution Boards shall be preferred. |
| 634 | 3) Item no 5-6-23 to 5-6-25 shall be preferably used for lift applications to avoid nuisance tripping. |
| 635 | 4) For use of RCBO\"s with inbuilt short circuit indication on each pole and separate earth leakage tripping indication shall be preferably used. |
| 636 | 6.8 Sandwich Bus Bar Trunking System |
| 637 | Supplying, erecting ,Testing & commissioning Ceiling or wall Mounting type630A Capacity at 40oCambient temperature Sandwich type Aluminium Conductor tin plated at joints /Aluminium conductor Silverflashed copper bimetal contact having purity not less than 99.6% with suitable for (3L+ N)415V, 50 Hz A.C Supply with 100% Neutral+ enclosure as integral earth (PE)with IP 54/55 Protection,36/40KAshort circuit rating for 1sec, InsulationClass F (155 C) , casing made of minimum 1.5mm hotdipped / electroGalvanized /Epoxy powder coated steel sheetenclosurehavingMechanical strength certification up to IK10 with required shade of paint having overall cross sectional areanot more than0.0170 sq. Mtr., complete assembly must comply to seismic zone 4, with necessary accessories Like suspension bracket, wall bracket holder/ fixing accessories with Horizontal / Vertical G.I.Support at required interval with ExternalDouble run 50x5mm Aluminium earthingstrip or Internal Integral Earth completeconfirming to IEC 61439-6 as per specification |
| 638 | Supplying, installing, testing and commissioning ofFlange end with Adaptor box,as per site requirement suitable for Aluminium630A 3 phase 4 wire 415V, 50 Hz A.C ,36/40kAshort circuit rating for 1 sec Sandwich type Aluminium BBT. with necessary accessories complete |
| 639 | Providing & erecting 3 Pole MCCB 415V,630A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides,with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 640 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 641 | Supplying, installing, testing & commissioning of Tap off box with interlock arrangement on existing Air Insulated / Sandwich type bus trunking/ rising mains for 32A to 125A 3 phase 4 wire 415V, 50Hz AC Supplymade with High Grade Plastic enclosure with provision of MCB/ MCCBwithout (MCB/MCCB) complete as required confirming to IEC 61439-6 as per specification |
| 642 | Providing & erecting 3 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact.MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 643 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 644 | Supplying, installing, testing & commissioning of Tap off box with interlock arrangement on existing Air Insulated / Sandwich type bus trunking/ rising mains for 125A to 200A 3 phase 4 wire 415V, 50Hz AC Supplymade with 1.5 mm thick sheet metal enclosure (IP54/55) duly powder coated with provision of MCCB( without MCCB) complete as required confirming to IEC 61439-6 as per specification |
| 645 | Providing & erecting3 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 646 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 647 | Supplying, installing, testing & commissioning of Tap off box with interlock arrangement on existing Air Insulated / Sandwich type bus trunking/ rising mains for250Ato 400A 3 phase 4 wire 415V, 50Hz AC Supply made with 1.5mm thick sheet metal enclosure (IP54/55) duly powder coated with provision of MCCB( without MCCB) complete as required confirming to IEC 61439-6 as per specification |
| 648 | Providing & erecting 3 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA(Ics=100% of Icu),adjustablethermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW-SWR/MCCB |
| 649 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 650 | Supplying, installing & Commissioning of Plug in Points on provided Sandwich type Aluminium Compact bus trunking/ rising mains Suitable for630A, 3 Phase 4 Wire 415 V, 50 Hz AC Supply,,36/40KA short circuit rating for 1secMade of minimum 1.5mm Thick Galvanised sheet metal enclosure (IP54/55)duly powder coated with all necessary accessories complete. |
| 651 | 6.9 Air Insulated Bus Bar Trunking System |
| 652 | Supplying, erecting ,Testing & commissioning Ceiling or wall Mounting type400A Capacity at 40C ambient temperature Air Insulated type Bus Trunking Aluminium Conductorhaving purity not less than 99.6% with Tin plated at jointssuitable for (3L+N)415V, 50 Hz A.C Supply with 100% Neutral+ enclosures as integral earth (PE) BBT Shalltype tested as per IEC 61439-6 with IP 54 Protection, 25KA short circuit rating for 1sec, InsulationClass F (155 C), casing made of Galvanized / powder coated steel sheetenclosurehavingMechanical strength certification up to IK10, with required shade of paint & having cross sectional area notmore than 0.0270 Sq m, complete assembly must comply to seismic zone 4, with necessary accessories Like suspension bracket, wall bracket holder/ fixing accessories with , outlet cover , plug in hole as per site requirement withHorizontal / Vertical G.I.Support at required interval, with External Single Run 25x10mm Aluminium earthingstrip or Internal Integral Earthcomplete confirming to IEC 61439-6 as per specification |
| 653 | Supplying, installation, testing and commissioning of Flange end as per design requirement & site condition suitable for Aluminium 400A, 3 phase 4 wire 415V, 50 Hz A.C ,25kAshort circuit rating for 1 sec forAir Insulated type BBT. With necessary accessories completeconfirming to IEC 61439-6 as per specification |
| 654 | Providing & erecting 3 Pole MCCB 415V,630A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides,with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 655 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 656 | Supplying, installing, testing & commissioning of Tap off box with interlock arrangement on existing Air Insulated / Sandwich type bus trunking/ rising mains for 32A to 125A 3 phase 4 wire 415V, 50Hz AC Supplymade with High Grade Plastic enclosure with provision of MCB/ MCCBwithout (MCB/MCCB) complete as required confirming to IEC 61439-6 as per specification |
| 657 | Providing & erecting 3 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact.MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 658 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 659 | Supplying, installing, testing & commissioning of Tap off box with interlock arrangement on existing Air Insulated / Sandwich type bus trunking/ rising mains for 125A to 200A 3 phase 4 wire 415V, 50Hz AC Supplymade with 1.5 mm thick sheet metal enclosure (IP54/55) duly powder coated with provision of MCCB( without MCCB) complete as required confirming to IEC 61439-6 as per specification |
| 660 | Providing & erecting3 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 661 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 662 | Supplying, installing, testing & commissioning of Tap off box with interlock arrangement on existing Air Insulated / Sandwich type bus trunking/ rising mains for250Ato 400A 3 phase 4 wire 415V, 50Hz AC Supply made with 1.5mm thick sheet metal enclosure (IP54/55) duly powder coated with provision of MCCB( without MCCB) complete as required confirming to IEC 61439-6 as per specification |
| 663 | Providing & erecting 3 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA(Ics=100% of Icu),adjustablethermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW-SWR/MCCB |
| 664 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 665 | Supplying, installing & Commissioning of Plug in Points on provided Sandwich type Aluminium Compact bus trunking/ rising mains Suitable for630A, 3 Phase 4 Wire 415 V, 50 Hz AC Supply,,36/40KA short circuit rating for 1secMade of minimum 1.5mm Thick Galvanised sheet metal enclosure (IP54/55)duly powder coated with all necessary accessories complete. |
| 666 | 6.9 Air Insulated Bus Bar Trunking System |
| 667 | Supplying, erecting ,Testing & commissioning Ceiling or wall Mounting type400A Capacity at 40C ambient temperature Air Insulated type Bus Trunking Aluminium Conductorhaving purity not less than 99.6% with Tin plated at jointssuitable for (3L+N)415V, 50 Hz A.C Supply with 100% Neutral+ enclosures as integral earth (PE) BBT Shalltype tested as per IEC 61439-6 with IP 54 Protection, 25KA short circuit rating for 1sec, InsulationClass F (155 C), casing made of Galvanized / powder coated steel sheetenclosurehavingMechanical strength certification up to IK10, with required shade of paint & having cross sectional area notmore than 0.0270 Sq m, complete assembly must comply to seismic zone 4, with necessary accessories Like suspension bracket, wall bracket holder/ fixing accessories with , outlet cover , plug in hole as per site requirement withHorizontal / Vertical G.I.Support at required interval, with External Single Run 25x10mm Aluminium earthingstrip or Internal Integral Earthcomplete confirming to IEC 61439-6 as per specification |
| 668 | Supplying, installation, testing and commissioning of Flange end as per design requirement & site condition suitable for Aluminium 400A, 3 phase 4 wire 415V, 50 Hz A.C ,25kAshort circuit rating for 1 sec forAir Insulated type BBT. With necessary accessories completeconfirming to IEC 61439-6 as per specification |
| 669 | Supplying, erecting ,Testing & commissioning Ceiling or wall Mounting type 160A Capacity at 40oC ambient temperature Air Insulated type Bus Trunking Aluminium Conductorhaving purity not less than 99.6% with Tin plated at jointssuitable for (3L+N)415 V, 50 Hz A.C Supply with 100% Neutral+ enclosure as integral earth (PE) with IP 54 Protection,15KA short circuit rating for 0.1sec, InsulationClass F (155 C), casing made of Galvanised/powder coated steel sheetenclosurehavingMechanical strength certification up to IK10, with required shade of paint & having cross sectional area notmore than 0.0150 Sq m, complete assembly must comply to seismic zone 4, with necessary accessories Like suspension bracket, wall bracket holder/ fixing accessories with , outlet cover, plug in hole as per site requirement withHorizontal / Vertical GISupport at required interval with External Single Run 25x10mm Aluminium earthingstrip or Internal Integral Earth complete confirming to IEC 61439-6 as per specification |
| 670 | Supplying, installation, testing and commissioning of Flange endas per design requirement & site condition suitable for Aluminium 160A, 3 phase 4 wire 415V, 50 Hz A.C ,15kAshort circuit rating for 0.1 sec,forAir Insulated type BBT. With necessary accessories completeconfirming to IEC 61439-6 as per specification |
| 671 | Supplying, installing & CommissioningVertical or Horizontal 90 Degree/TeeElbowfor Air Insulated type bus trunking/ rising mainsof capacity 160A, 3 Phase 4 Wire 415 V, 50 Hz AC Supply,15kAshort circuit rating for 1 sec MadeGalvanised sheet metal enclosure (IP54)duly powder coated with all necessary accessories completeconfirming to IEC 61439-6 as per specification. |
| 672 | Providing & erecting3 Pole MCCB, 415V, 200A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB |
| 673 | 1)For use of 4 pole MCCBs in place of 3 pole MCCBs add 20% in rate of 3 pole MCCB. |
| 674 | 7.1 LT Cables (Aluminum) (CB-LT/AL) |
| 675 | Supplying, erecting & terminating HFFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core25 sq. mm.aluminium conductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 676 | Supplying, erecting & terminatingHFFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core35sq. mm.aluminium conductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 677 | Supplying, erecting & terminatingHFFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core50 sq. mm.aluminium conductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 678 | Supplying, erecting & terminating HFFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core70sq. mm.aluminium conductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 679 | Supplying, erecting & terminatingHFFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core185 sq. mm.aluminiumconductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 680 | Supplying, erecting & terminatingHFFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core300 sq. mm.aluminiumconductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 681 | Supplying, erecting & terminating HFFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core16sq. mm. aluminium conductor completeerected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipeas per specification no. CB-LT/AL |
| 682 | 7.2 LT Cables (Copper) (CB-LT/CU) |
| 683 | Supplying, erecting& terminatingHFFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core4sq. mm.copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU |
| 684 | 1) Add Rs. 5/- per metre for erection of cables on stone wall. |
| 685 | 2) Rate of all cables includes cost of lugs, glands, etc. required for erection and connection of cable. |
| 686 | 3) In case of next fault for same cable add Rs 4000/- per fault for fault detection. |
| 687 | 4)Add Rs 5000/- for high pressure testing charges of H.T. cable. |
| 688 | 5)Transportation charges of fault finding machine above 20 km Rs 12/- per km |
| 689 | 6) For round wire armouring increase rates by 27%. |
| 690 | 7) For use of XLPE insulation instead of FR-XLPE insulated armoured cable reduce rates by 5 % |
| 691 | 8) For use of FRLS-XLPE insulation instead of FR-XLPE insulated armoured cable increase rates by 5 % |
| 692 | 9) For use of XL-HFFR insulation instead of FR-XLPE insulated armoured cable increase rates by 14 % |
| 693 | 10) XL-HFFR insulated armoured cable are applicable for indoor use only. |
| 694 | 11) XL-HFFR insulated armoured cable shall be used for Hospital Buildings only. If used for other applications, prior permission from competent authority shall be taken. |
| 695 | 7.11Cable Tray (CB-CT) |
| 696 | Providing & erecting Hot dipped galvanized ladder type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 150 mm width & 100 mm height comprising all required standard accessories. |
| 697 | Providing & erecting Hot dipped galvanized ladder type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 300 mm width & 100 mm height comprising all required standard accessories. |
| 698 | Providing & erecting Hot dipped galvanized ladder type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 500 mm width & 100 mm height comprising all required standard accessories. |
| 699 | Providing & erecting Hot dippedgalvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner. |
| 700 | Providing & erecting Hot dippedgalvanized perforated type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware in approved manner. |
| 701 | 1) Standard accessories shall typically include : |
| 702 | a) \"Z\" section support -30 x 35 mm in size - 312 mm in length - 6 nos. support for one piece ladder of 2.5 m in length each. |
| 703 | b) Anchor fastener & nut bolts of adequate size - 16 nos. ( 2 nos. per support) |
| 704 | c) Coupler plates with hardware - 70 x 200 x 3 mm thick - 2 nos. for each piece of 2.5 m ladder complete with necessary accessories such as reducer, horizontal elbow & tee, up & down vertical elbow & bend, cross piece complete erected in approved manner. |
| 705 | 2) Provision for resting arrangement or support for perforated type cable tray shall be made separately as per iron work Item. |
| 706 | 3) Provision of cover for perforated type cable tray shall be made only where it is absolutely necessary and make sure for locking arrangement. |
| 707 | 4) Both type of cable trays shall be earthed properly. |
| 708 | Above items are conforming to relevant IS as mentioned below |
| 709 | 9.1 Plate, Pipe type Earthing (EA-EP) |
| 710 | Providing earthing with galvanizediron earth plate size 60 x 60 x 0.6 cm with funnel with a wire mesh for watering and brick masonry block C.l. covercomplete with all materials, testing & recording the results asper specification no. EA-EP |
| 711 | Providing earthing with copper earth plate size 60 x 60 x 0.315 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover with minimum 25 kg Carbonbased environment friendly back fill Ground Enhancing compoundcomplete with all materials, testing & recording the resultsas per specification no ESE -LA |
| 712 | Supplying and erecting copper strip of required size used for earthing on wall and/or any other purpose with necessarycopperclampsfixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no. EA-EP. Copper strip 25X3 mm = 0.7 kg/meter. Hence for 486 meters*0.7 = 340 kg |
| 713 | Supplying and erecting GI strip of required size used for earthing on wall and/or any other purpose with necessary GI clampsfixed on wall painted with bituminous paint in an approved manner with joints required. As per specification no EA-EP. GI strip 25X6 mm = 1.25kg/meter. Hence for 544 meters *1.25 = 680 kg |
| 714 | 1) Resistivity of the soil shall be checked and number ofback filling ground enhancing compound bags shall be used as per guidelines elaborated in specification. |
| 715 | 2) Additional G.I. pipe required from earth pit & GI/Copper wire / strip more than 8 m in length from earth pit to installation to be provided separately. |
| 716 | 3) Record entries for earthing work shall be maintained. |
| 717 | 4) Requirement of no of bags shall be decided with respect to soil resistivity. |
| 718 | 9.3 Lightning Conductor and Accessories |
| 719 | Supplying&erectingconventionalspike typeair termination suitable to carry lightning stroke made up of heavy gauge40 mm dia copper pipe of standard length with 5 Nos. copper spikes fixed on copper ball as air terminals duly threaded in copper pipeerected on provided foundation in an approved manner. |
| 720 | Providing and Back filling back filling ground enhancing compound 25 kg bag complete. |
| 721 | Above items are conforming to relevant IS as mentioned below |
| 722 | IS 3043-1987:-Earthing Indian Standard Code of practice of earthing |
| 723 | 4.7 Electric Vehicle Charger (ESD-EVC) |
| 724 | Supplying,erecting, testing and commissioning of10kW, 3 x 3.3 KW AC Electric Vehicle charger (suitable for 2/3/4 wheeler) havingminimum IK08/IP 54 Protection suitable for three phase, 415V AC, 50Hzincoming and 3 nos. output as per IEC 60309 industrial sockets having capacity of output current of 16A 240V ACat each socket with 3.5\"TFT touch screen for human interface & LED Light for status indication and metering for measurement of consumed energy having metering accuracy +/-1%, one hour battery backup for communication, emergency push stop button and having short circuit, over & under voltage, overload, over temperature, earth leakage protection and enclosure made of minimum 1.5mmduly RAL7035 Coated M.S, Erected oniron/GI frame on provided cement concrete foundation complete with one year on site warranty, confirming toIS 17017 Series as per specification. |
| 725 | Supplying,erecting, testing and commissioning of 30 kW DCElectric Vehicle Charger (suitable for 4 wheeler) having minimum IK08 & IP 54 Protection suitable for three phase, 415V AC, 50Hzincoming supply and 1 nos 30kW output charger interface CCS2 with 200-500VDC supply, Interlocking arrangement with minimum 4 meter charging cable length, 5\" LCD Touch Screen for human interface & LED Light for status indication and metering for measurement of consumed energy having metering accuracy +/-1%, One hour battery backup for communication, emergency push stop button. User interface by mobile application/QR Code/RIFD Card/Password Login with payment options and having short circuit, over & under voltage, input phase reversal, surge protection, earth leakage protection and enclosure made of minimum 1.5mm duly RAL7035 coated M.S, erected oniron/GI frame on provided cement concrete foundation complete with one year on site warranty, confirming toIS 17017 Series as per specification |
| 726 | Providing yearly subscription of payment gateway option for AC/DC EV Charger CMS (Charger management software) system for billing and payment gateway along with mobile application /android/IOS base app to facilitate charging, CMS should have ISO/IEC 27001:2003 certification. |
| 727 | Achalpur_Abstract_Street Lights |
| 728 | Supplying and erecting PVC insulated PVC round sheathed 2.5 sq.mm (50 no. x 0.25 mm dia.) 3 core flexible multi strandedcopper Industrial cable for voltage grade up to 1.1 kV |
| 729 | Supplying and erecting integrated LED street light fitting 60W IP65 & IK08 class having single piece pressure die-cast aluminium housing,havingsystem lumens output of Min.6600 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver complete with 3 Years warranty as per specification NoFG-ODF/FLS2. |
| 730 | Supplying and erecting integratedLED street light fitting 100-110W IP65 & IK08 class having single piece pressure die-cast aluminium housing,havingsystem lumens output of Min. 11000 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.95, operating range of140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50,including driver complete with 3 Years warranty as per specification NoFG-ODF/FLS2. |
| 731 | Supplying and erecting integrated LED flood light fitting Max. 155W IP65 & IK07 class having pressure die-cast aluminium housing,having system lumens output of Min. 18600 Lumens, min. efficacy of 120 lumen/W, CRI>70, CCT upto 6500K, THD<10%, p.f. >0.90, operating range of140-270V, inbuilt surge protection of 4 kV, Life class of 50,000 Hrs. at L70B50,including driver with U shaped bracket with 3 Years warranty as per specification NoFG-ODF/FLS2. |
| 732 | Supplying & erecting integral post top lantern fixtures (mushroom type) suitable forLED lamp upto 12 Wconsisting of clear acrylic top cover, cast aluminium pole cap complete with accessories on provided pole /bracket as per specification no. FG-ODF/PTL |
| 733 | Supplying and erecting Gate/garden light fitting with 300mm dia. glass bowl suitable for upto 12W LED Lamp on provided pipe as per specification No. FG-ODF/GLT |
| 734 | Supplying & erectingintegral post top lantern fixtures (globe type) suitable for LED lamp upto 12 W consisting of aesthetic round clear acrylic top cover, cast aluminium pole cap on provided pole /bracket as per specification no.FG-ODF/PTL |
| 735 | Supplying & erecting three phase, 415V, street light control panel up to the max load of 12kW, TPN MCB 63A,powder coated CRCA 14 SWG sheet, outdoor type, having IP54,IK10 protection, suitable rating contactor, 24 hrs. astronomical time switch with minimum 5 years battery back up,auto/manual selector switch, ON/OFF push buttons, indicator lamps, control wiring, metering device, etc. for automatic operation, with overcurrent, short circuit, earth fault protectionon provided iron frame / CC foundation. |
| 736 | Supplying, erecting & marking FPMCB 6A to 32A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB |
| 737 | Supplying & erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBOcomplete erected on angle iron/GI frame. |
| 738 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core6 sq. mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU |
| 739 | Supplying, erecting& terminatingFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core4sq. mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU |
| 740 | Supplying & erecting G.I. pipe‘A’ class 40 mmdia.erectedfor enclosingXLPEarmouredcable on wall/poleas per specification no. CB-CE |
| 741 | Supplying & erecting G.I. pipe‘A’ class 50 mmdia.erectedfor enclosingXLPEarmouredcable on wall/poleas per specification no. CB-CE |
| 742 | Supplying & laying (including excavation)reinforced cement concrete pipe of IS 458:2003 NP-2 class of 250 mm internal diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 743 | Supplying and laying (including excavation of suitable width & depth up to 90 cm) 75 mmoutside dia. double wall corrugatedpipes (DWC)ofHDPE for enclosing cable below ground/road surface, to required depth complete. |
| 744 | Supplying &erectingcast iron cable indicatorplate buried along with route of cable for PVC / XLPE armoured cableas per specification no. CB-CIP |
| 745 | Supplying & erectingFRP box of size 150 x 125 x 100 mm, 2.7 mmthickcomplete on pole/wallas per specification no. CB-SB |
| 746 | Supplying and erecting 12.5 m (clear height) motorized high-mast(Top -150mm, Bottom- 360mm) hot dipped galvanized material with average minimum thickness 65 micron, made from high tensile structure grade steel as per BSEN - 10025 S 355/E350 & 3mm thickness, with base plate 25 mm thick x OD 520 mm grade as per IS-2062, pole made in single section & submerge arc welded, with lowering & raising motorized unit, wire rope stainless steel 316 grade 2 nos., 7x19 construction 5mm, SG-DG U clamps, double drum with assembly 250 kg, 5x2.5 Sq.mm. flexible copper cable with lantern carriage assembly suitable for max. 12 nos. luminaires and its control gear box, lightning arrestor, arrangement for fixing aviation light, high-mast with serial number, factory inspection report/test report of high-mast should be provided as per specifications on provided foundation J type stud/bolts with necessary accessories complete as perspecification no.OH-PL/HM (excluding luminaries) |
| 747 | Providing & erecting 10 m high (clear height) galvanised octagonal pole with foundation bolts having bottom of 175 mm A/F, top 70 mm A/F on provided foundation as per specification no. OH-PL/OPL |
| 748 | Providing and erecting galvanised 1000mm single arm sword typebracket with FRP dome and ball as per specification no. OH-PL/PBKT |
| 749 | Providingpipetype earthing with 40mm. dia. G.l. pipe or 20 mm dia. G.l. Rodcomplete with all materials as per specification no. EA-EP |
| 750 | Making trench in soft soil having 0.75 m depth and minimum0.3 m widthfor laying providedcables up to voltage level of 1.1kV completeAs per specification No. CW-EXN-CTR |
| 751 | Excavating hard murum / stone metal roadby chiselling for preparing pit for poles stay or earth plates or for laying cables, pipes & clearing the site by removing debris & making the site as required complete. |
| 752 | Makingcement concrete foundationincluding excavation(60x 60x 150) cm deep in 1:3:6 cement concrete, (20 to 25) mm stone metalwith necessary curing and finishing complete.(for stay). |
| 753 | MakingM- 20 grade reinforced cement concretefoundationbyconsidering the safe soil bearing capacity at site as 10 T/sq.mat 1.5 m depth including supply of steel, concrete, excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete(for 9m & 10m high octagonal /conical GI pole). |
| 754 | MakingM- 20 cement concrete foundation by considering the safe soil bearing capacity at site as 10 T/sq. m at 2 m depth including excavation and fixing provided nut bolts with the help of template, duly plastered as per design complete(for 12.5 m raising lowering high mast). |
| 755 | Achalpur_Abstract_Networking |
| 756 | 1.8 Modular switches and Accessories |
| 757 | Supplying and layingHMS PVC conduit FRLS grade 20 mm dia. with necessary accessories in RCC work/false ceiling/false flooring as per specification No.WG-MA/CC. |
| 758 | Supplying and erectingmodular type telephone socket one gangwith safety shutter, duly erected on provided plate and box with wiring connections complete. |
| 759 | Supplying and erectingmodular type computer Jack RJ45 with safety shutter, duly erected on provided plate and box with wiring connections complete. |
| 760 | 1.10 Telephone,Audio and Video Wiring (WG-TW/TW) |
| 761 | Supplying & erecting2 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as perspecification No. WG-TW |
| 762 | Supplying & erecting 10 pair, 0.5 mm dia.jelly filled armoured telephonecopper cable with poly-al laminate moisture barrier, polythene sheathed, G.S.Tape armoured polythene jacketed havinglaid in provided trench as per specification No.WG-TW |
| 763 | Supplying & erecting 20 pair, 0.5 mm dia.jelly filled armoured telephonecopper cable with poly-al laminate moisture barrier, polythene sheathed, G.S.Tape armoured polythene jacketed havinglaid in provided trench as per specification No.WG-TW |
| 764 | Supplying & erecting 50 pair, 0.5 mm dia.jelly filled armoured telephonecopper cable with poly-al laminate moisture barrier, polythene sheathed, G.S.Tape armoured polythene jacketed havinglaid in provided trench as per specification No.WG-TW |
| 765 | Supplying & erecting 100 pair, 0.5 mm dia.jelly filled armoured telephonecopper cable with poly-al laminate moisture barrier, polythene sheathed, G.S.Tape armoured polythene jacketed havinglaid in provided trench as per specification No.WG-TW |
| 766 | Supplying & erecting co-axial copper cable low voltage grade tri-shielded RG-11 as per specification No.WG-TW |
| 767 | Supplying & erectingco-axial copper cable low voltage grade tri-shieldedRG-6as per specification No. WG-TW |
| 768 | Supplying and erecting 10mHDMI cord low voltage grademinimum 4k compliant to be laid in provided conduits with male/female 19 pin HDMI connectors complete. |
| 769 | Supplying and erecting 20mHDMI cord low voltage grademinimum 4k compliant to be laid in provided conduits with male/female 19 pin HDMI connectors complete. |
| 770 | Supplying & erectingHDMI ExtenderOver RJ45 Ethernet CableCat 6, 60m/200ft complete. |
| 771 | Supplying, installing, testing & commissioning of DVI to HDMI Convertor high-speed category,supporting full HD 1080p, 2K and 4K video up to 30 ft length, 3D having 24k gold-plated 19-pin Type-A connectors with high-flex CL3-rated jacket, RoHS compliant complete. |
| 772 | RG stands for Radio Grade. |
| 773 | VGA stands for Video Graphics Array. |
| 774 | HDMI stands for High Definition Multimedia Interface. |
| 775 | RJ stands for Registered jack. |
| 776 | DVI stands for Digital Visual Interface. |
| 777 | RoHS stands for Restriction of Hazardous Substances. |
| 778 | 1.9 Telephone Accessories (WG-TW/TA |
| 779 | Supplying, erecting & commissioningMDF Box 50x50 pairs made from min. 1.5mm thick MS sheet as per specification no.WG-TW |
| 780 | Supplying, erecting & commissioningMDF Box 100x100 pairs made from min. 1.5mm thick MS sheet as per specification no.WG-TW |
| 781 | Supplying, erecting & commissioning 10 pairsFRjunction box with moulded plastic enclosureas per specification no. WG-TW |
| 782 | Supplying, erecting & commissioning 50 pairsFRjunction box with moulded plastic enclosureas per specification no. WG-TW |
| 783 | Supplying, erecting & commissioning100 pairs M.S.junction box made from min. 1.5mm thick MS sheetas per specification no. WG-TW |
| 784 | Supplying, erecting &commissioning10 pair module for connection & disconnection of telephone cable as per specification no. WG-TW |
| 785 | Supplying & erecting over voltage protection magazine suitable for 10 pair as per specification no. WG-TW |
| 786 | Supplying and installing, testing & commissioning of digital (hybrid)type EPABX of6 x 32 extensions suitable upto 96 extensions complete. |
| 787 | Supplying, installing, testing & commissioning IP EPABX for 10 extensions complete. |
| 788 | Supplying, installing, testing & commissioningpush button telephone instrument desk top/wall mount unit as per specification complete |
| 789 | Supplying, installing, testing & commissioning IP telephone instrument as per specification complete. |
| 790 | Supplying & installing expansion cabinet for extension of digital hybrid EPABX to expand system by 32 ports with programming and configuration of extensions and direct lines with required accessories complete. |
| 791 | 4) Minimum one digital key telephone instrument is essential for commissioning digital type EPABX |
| 792 | 5) EPABX stands for Electronic Private Automatic Branch Exchange. |
| 793 | 1.12 ComputerCabling (WG-COC) |
| 794 | Supplying and installingcat-6 LSZH cable suitable for networking as per specification no. WG-COC/NC |
| 795 | Supplying and fixing 1 mUTP patch cordof Cat 6type in position as per specification No. WG-COC/PC |
| 796 | Supplying and fixing 3 m UTP patch cord of Cat 6type in position as per specification No. WG-COC/PC |
| 797 | Cat-6 stands for Category-6 cable. |
| 798 | LSZH stands for Low Smoke Zero Halogen. |
| 799 | UTP stands for Unshielded twisted pair. |
| 800 | FRLS stands for Flame Retardant Low Smoke. |
| 801 | LAN stands for Local Area Network. |
| 802 | WAN stands for Wide Area Network. |
| 803 | 1.11 Networking Components (WG- NWC) |
| 804 | Supplying, fixing, and configuring 24 ports with 4 (SFP+) port, ethernet managed switch with web view/CLI,6KV surge protection on ethernet port and console port for management in provided rack as per specification no.WG-NWC/GBS |
| 805 | Supplying, fixing, and configuring broadband ADSL router with all accessories, on provided rack or as directed as per specification No. WG-NWC/ADSL |
| 806 | Supplying, fixing, and configuring modularised multi-service router 802.11/a/n/ac unified Wave 2.5 GHz, with RJ-45 port, supporting1 to 13 channels for 2.4 GHz, with unified wireless access point complete. |
| 807 | CLI stands for Command Language Interpreter. |
| 808 | SFP stands for Small Form-factor Pluggable. |
| 809 | GBIC stands for Gigabit Interface Converter. |
| 810 | ADSL sands for Asymmetric digital subscriber line. |
| 811 | 1.12 Networking Accessories (WG-NAS) |
| 812 | Supplying, installing and testing UTP connector (RJ-45) asper specification No.WG-NAS/UTPC. |
| 813 | Supplying and fixingtool-less shutter keystone jack (RJ-45)in provided patch panel complete as per specification no. WG-NAS/KJ |
| 814 | Supplying and fixing24 port patch panel with tool-less keystone jacksin provided U Rack complete as per specification no.WG-NAS/PP |
| 815 | Supplying and fixing 9U wall mount rack (Dimension-DxWxH – 500x600x500 mm) as per specification No. WG-NAS/RAK |
| 816 | Supplying and fixing 12U wall mount rack (Dimension-DxWxH – 500x600x635 mm) as per specification No. WG-NAS/RAK |
| 817 | OM stands for Optical Mode. |
| 818 | IP stands for Ingress Protection. |
| 819 | PoE stands for Power over Ethernet. |
| 820 | APs stands for Access Points. |
| 821 | AWG stands for American Wire Gauge. |
| 822 | OS stands for Optical Singlemode. |
| 823 | Above items are conforming to relevant IS as mentioned below |
| 824 | IS 9537 (Part 1) :1980- Conduits for electrical installations-Part1 General requirements. |
| 825 | IS 9537 (Part 2) :1981 - Specification for conduits for electrical Installation Part-II Rigid Steel Conduit. |
| 826 | IS 9537 (Part-3) :1983- Specification for conduits for electrical installations Rigid plain conduit of insulating material |
| 827 | IS 14927 :2001 -Cable Trunking and ducting systems for electrical installations |
| 828 | IS 694 :2010 -PVC insulated cables for voltage upto including 1100V |
| 829 | IS 3854 :1997 - Switches for Domestic and similar purposes -specification. |
| 830 | IS 1293 :2005 - Plug and socket outlets of rated voltage upto and including 250 volt and rated upto and including 16 Amperes- Specification. |
| 831 | IS 371: 1999 - Ceiling Rose-Specification |
| 832 | IS 11037 :1984 -Specification for electronic type Fan Regulator |
| 833 | IS 14772 : 2000 - General requirements for enclosures for accessories for household and similar fixed electrical installations-Specification. |
| 834 | IS 732 :1989 - Code of practice forelectrical wiring installations |
| 835 | IS 4648:1968 - Guide for electrical layout in residential building |
| 836 | IS 2532 :1965 -Hard-drawn copper wire for telegraph and telephone purposes. |
| 837 | Achalpur_Abstract_CCTV |
| 838 | 14 CCTV System (FF-CCTV) |
| 839 | Supplying & laying HMS PVC conduit 25 mm dia FRLS grade with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC. |
| 840 | Supplying & erecting mains with 3x2.5 sq.mm FRLHS copper PVC insulated wirelaid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW |
| 841 | Supplying and erecting ISI mark modular type switch6A / 10A duly erected on provided plate and box with wiring connections complete. |
| 842 | Supplying and erecting ISI mark modular type 3 pin 6A multi sockets with safety shutter, duly erected on provided plate and box with wiring connections complete. |
| 843 | Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. |
| 844 | Supplying and installingcat-6 LSZH cable suitable for networking as per specification no. WG-COC/NC |
| 845 | Supplying, Erecting, Testing and Commissioning of Dome / Bullet Type IP Cameras Max 4 MP (2592x1520) resolution Built in2.8mmfixedlensMax25fps resolutions (H 265/H264) H 265 H264 MUPEG code C supported Multiple streaming Video Compression H265 H264 Image Sensor 1/3\" Progressive Scan CMOS Illumination 0.5 lux (20Meter) Image Setting: Compression colour brightness sharpness contrast white balance exposure control backlight compensation Security Password Protection IP Address filtering user access Log, Operating Conditions10 to 55C. Casing:Tamper Resistant for Indoor Environment IK08 Sensor 1/2.9 MP CMOS. 1) Pixels per sensor: 2000 (H) x 1121 (V) total. 1984 (H) x1105 (V)effective 2)scanning progressive3)Day/nightsetting:TrueDay&Night4)Backlight compensation (BLC):Off/On 4) WDR 120 dB 6)DigitalNoiseReduction(DNR):ON/Off.4Numberof multi-streaming profiles: 3 maximum a.) The 4 MP camera shallhaveonboardSDcardstorageMUPEGcode C supported Multiple Streaming. Motion detection, Tempering Defocus detection. Audio Mike Inbuilt MicroSD (128GB) memory slot POE/12V DC. IR viewable Length 20m. IP66 UK 10 LDC Support (Lens/Distortion Correction Certifications CE/UL. APPROVEDMAKE:- SONY/SAMSUNG(WiseNET) Warranty: 3 Years |
| 846 | S/I/T/C19\"RACKMOUNTABLENVR:SUPPORTS 32 CAMERAS ProfessionalSeries4K HD net work, Video recorder-/smart H265+/H265/Smart 264+ max 384 Mbps in coming Band width up to 12MP resolution for preview and play back-Bit rate 16 Kbps 20 Mbps per channel-2 HDMI/2 VGA simultaneous video out putto enhance the storage reliability when the network break downQuad coreembedded processor8 SATA III ports up to 6 YB for each HDD for 48 TB storage2 RJ 45 port( 10/100/100 Mbps) Independent of joint networking / Analytical futures likeANPRApeople countface detection / Missing / Abandoned objects Tripwire and intrusionalarmsmartFANtoachievenet work video recorderwith the ANR function automatically storevideodata. Approved Make: Honeywell, Sony, Samsung. Warranty For 3 Years |
| 847 | Supplying and erecting Supply &errecting 4TB enterprise hard disk 6gb /sec /128 MB cache /24x7x365 reliability similar to model no seagate ST2000NM0033 NON DSR Approved by SE Electrical Pune VideNCSR no 96/2019-20 Dated 04/09/2019 |
| 848 | Supplying and fixing single band POE 2x2 Mesh Router, 802.11 n/ac 2.4 GHz, standalone/software based access point complete. |
| 849 | Supplying, fixing, and configuring 8-ports managed gigabit, Layer-2 switch, 10/100/1000 base-T, POE smart switch plus 2 SFP erected in provided rack complete. |
| 850 | Supplying, installing and activating physical license packsoftware for multiple access point with management, configuration and trouble shooting for all access point in network complete. |
| 851 | Supplying, Installing, Testing & Commissioning of 40” Full HDCommercialLEDLCDSignageDisplaywithbuiltin CPUandEthernet/RS-232C,remotecontrolInputsof VGA,HDMI,DVI-D,andRS232Cbuilt-in LANcardto access thenetwork ,withSmart Signage software [ samsung, Sony,] WarrantyFor 3 Years |
| 852 | Achalpur_Abstract_Transformer and DG set |
| 853 | 5.9 HT SF6 Load Break Switch /VCB/RMU (SW-HTS) |
| 854 | Supplying, erecting, testing & commissioning 11 kV, 630A, 21kA/3sec, 3 way outdoor, extensible motorised SCADA compatible RMU, internal arc testedconsisting of 2 nos. feeder with 2 LBSand 1 no. feeder with 1 VCB.compliant to IEC 62271 -100, 200 and 102,as per specification no. SW-HTS/RMU SCADA |
| 855 | 3) Internal arc tested RMU (min equivalent to short circuit capacity) shall be preferred. |
| 856 | 4) LBS /RMU shall be IEC 62271 -100,200 and 102, compliance. |
| 857 | 6.4H. T. Metering |
| 858 | Supplying,erecting,testing and commissioning 11KV HT metering cubical (compact / vertical type) approved by MSEDCL / licensee fabricated with 2 mm (14 SWG) M.S. sheets with supporting angle, painted with powder coating / epoxy paintof required shade, copper bus bar size 25 x 6 mm, heavy duty mechanical lock, with counter meter for measuring no of times the opening of meter door, top side cover (CT, PT cover) interlock with meter door, epoxy casted 3 nos. CT having required ratio between 10/5A to 50/5A, VA10 or 15, Class 0.5S, epoxy casted 3 nos. PT having ratio 11000/V3/110/V3 VA 50, Class 0.5 suitable for provided trivector meter, andprovision for incoming and outgoing cables complete duly tested by licensee with necessary test certificatesand erected on provided plinth/ cc foundation. |
| 859 | 6.6Surge Protective Devices (CP-SPD) |
| 860 | Supplying, installation & marking of surge arrestor/ surge protection deviceat the sub main distribution board after the incoming breaker of type 2 testedfor Imax 15 kA for three phase and neutralwith compliance to IEC 61643-11 as per specification no. CP-SPD |
| 861 | The above items shall be used only in installation where delicate/ sensitive instruments are used or for installations that areprone to surges. |
| 862 | 7.3HT Cables (CB-HT) |
| 863 | Supplying , erecting & terminating XLPE insulated, galvanised steel formed wire armoured (wire armouring) cable11 kV(E), 3 x 185 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT |
| 864 | 7.5 Cable Joints & End Termination Kits (HT Cables)(CB-JT/HT) |
| 865 | Providing and erecting Heat shrinkable outdoor termination kit for 11 kV ( E ) XLPE HT cable 3x120 to 185 sq. mm. with necessary material as per specification no. CB-JT/HT |
| 866 | 1) Above rates are for Aluminium Lugs & Ferrules for Copper Lugs & Ferrules increase material rates by 15 % |
| 867 | 7.6 Cable Enclosures (CB-CE) |
| 868 | Supplying & laying (including excavation)reinforced cement concrete pipe of IS 458:2003 NP-2 class of 150 mm internal diameter in proper line, level and slope including providing and fixing collars in cement mortar 1:2 and curing etc. complete. |
| 869 | 1)For erection of G I pipe on stone wall add Rs.5/- per meter to the overall rate. |
| 870 | 2)All the GI pipes and DWC pipes shall be ISI marked. |
| 871 | 3) For running the cable across the field / along the road , it should be covered by half round Hume pipe only. |
| 872 | 10.1 Transformers |
| 873 | Supplying, installing, testing & commissioning3 phase, 11/0.433 kV, 50 Hz., 500 kVA,Mineraloil immersed and naturally cooledoutdoor type, Copper wound ,without gas cushioning ,hermetically Sealed transformer, delta/star connected with additional neutral brought out on load side, temperature rise shouldnot exceed 45? by thermometer in oil and 50? by the resistancemethodin winding at full load rating, using type A winding insulation (kraft paper)with HV tapping (with off load tap changer) off load +5 to -10 in steps of 2.5%,having 7 number of tap positions with standard accessories complete with test certificate with losses below 1510Watts at 50% load, 4300 Watts at 100% load as per IS:1180 (part 1) : 2014with necessary permissions of Electrical Inspector, as per specification no SS- TR-SL. |
| 874 | 10.6 Accessories |
| 875 | Supplying and erecting fencing of section having size 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete as per specification no SS-AS/FSG. Size of fencing: 8 meters+6 Meters = 14 meters x 2 = 28 meters - 1 gate of 1.2 meters = 26.8 meters / 1.2 meters width = 22.33 meters |
| 876 | Forsection less than 1200 mm width, reduce rate by Rs 200/- per 100 mm or part thereof for reduction in width of 1200 mm. |
| 877 | Supplying and erecting 50 x 50 x 6 mm angle iron as cornersupport 2m long fixed at the middle ofthefencing frame and the otherside inclined at 30 degree angle, in cement concrete foundation of 15 x 15 x 40 cm complete duly painted with one coat of red oxide and two coats aluminum paint complete. |
| 878 | Supplying and erecting double leaf hinged door each 1500 mm in width x 1850 mm in height using B class, GI pipe with angle iron supports, chain link wire mesh (jali) complete supported on channel iron, erected in foundation, and painted complete as per specification no SS-AS/DLD |
| 879 | Supplying & erecting barbed wire two ply with 12 SWG ply and 12 SWG barb with a gap between two bars of 75 mm. firmly fixed on provided angle supports with necessary materials complete. (6.044 meters/kg.). |
| 880 | Providing printed instruction chart for treating persons suffering from electric shock,printedinEnglish & Marathi and duly laminated complete. |
| 881 | Providingpair ofdulytestedrubber hand glovesas per IS :47705suitable forworking upto 22 kV supply complete. |
| 882 | Supplying standardfirst aid boxwith necessary antiseptic cream, medicine for use on wounds due burn, crepe bandage, gauge bandage, medicated ready to use bandage (Band-Aid) adhesive tape for medicinal use, scissors, anti-septic solution, etc. (All above contents shall be of standard makes) |
| 883 | Supplying and fixingPVC synthetic elastomerelectrically insulating matwith class C insulation conforming to IS: 15652 – 2006 tested having 3mm thickness up to 33 kV |
| 884 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete. |
| 885 | Above Items are conforming to relevant IS as mentioned below |
| 886 | IS 1180 (Part 2): 2016 :-Outdoor type three-phase distribution transformers up to and including 100 kVA 11 kV, Part 2: Sealed type |
| 887 | IS 2026 (Part 1): 2011 :-Power transformers, Part 1: General |
| 888 | IS 2026 (Part 2): 2010 :- Power transformers, Part 2: Temperature-rise |
| 889 | IS 2026 (Part 3): 2009 :- Power Transformers Part - 3 Insulation Levels, Dielectric Tests and External Clearances in Air |
| 890 | IS 2026 (Part 4): 1977 :- Power transformers, Part 4: Terminal marking, tappings and connections |
| 891 | IS 2026 (Part 5): 2011 :- Power Transformers, Part 5: Ability to Withstand Short Circuit |
| 892 | IS 2026 (Part 7): 2009 :- Power Transformers, Part 7: Loading Guide for Oil-Immersed Power Transformers |
| 893 | IS 2026 (Part 8): 2009 :- Power Transformers, Part 8: Applications guide |
| 894 | 11.1 Generators (GEN-GEN) |
| 895 | Supplying, erecting, testing and commissioning ofdiesel generating set with alternator of 500 kVA outputcontinuous rating, 3 Phase, 415 V, 50c/s 0.8 p. f. A.C supply, a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, along with standard accessories, self-excited, self-regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 %, with performance class G2 and maximum fuel consumption 81.90 Ltr/hr @75% loading. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite Acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet, sound absorbing material to restrict sound level up to 75 dB at 1.0 m, provided with first filling of oil, diesel not less than 690 Ltr etc. on provided M20 Grade CC Foundation and obtaining necessary approval from Electrical Inspectoras per specification no. GEN-DG |
| 896 | 1) DG Set rating for altitudes more than 150 m above mean sea level shall be de-rated at 3.5 % for every 300 m above 150 m mean sea level. |
| 897 | 2) In case of new DG set, if AMF/SYNC panel is to be used in lieu of standard panel, reduce rate by 10% of the cost of material of new AMF panel/SYNC panel. |
| 898 | 3) For all the Engines, the emission standards/norms shall meet applicable pollution control board norms as amended by Government. |
| 899 | 11.2 Auto Mains Failure Panels (AMF Panels) (GEN-AMF) |
| 900 | Supplying, erecting, testing and commissioning ofmicroprocessor based AMF panel suitable for diesel generating set of above 400 kVA up to 500 kVA capacity Three phase, 415 Volts, 50Hz A.C. with all standard features, safeties etc as per specification no. GEN-AMF. |
| 901 | 1) In case of new DG set, if AMF/SYNC panel is to be used in lieu of standard panel, reduce rate of Item No 11-2-1 to 11-2-23 by 10% ofrate of new AMF panel/SYNC panel. |
| 902 | Above Items are conforming to relevant IS & norms as mentioned below |
| 903 | IS 4722 : 2001- Rotating electrical machines (second revision) |
| 904 | Central Pollution Control Board (CPCB) norms II |
| 905 | Above Items are conforming to relevant IS as mentioned below |
| 906 | IS9079 : 2002 - Electric Monoset Pumps for Clear, Cold Water for Agricultural and Water Supply Purposes |
| 907 | IS 8034 : 2002- Submersible Pumpsets - Specification |
| 908 | 16.2 Masonry Work |
| 909 | Supplying and spreading stone metal 25 mm size for 100 mm depth above the ground level complete. |
| 910 | Supplying and erecting RCC chamber cover with frame 60cmx 45cm medium duty 100kgwith lifting arrangement including laying of angle iron frame of angle size as 50 x 50 x6 mm to be fixed / embedded on top of chamber complete. |
| 911 | 16.3 C.C. Foundation |
| 912 | Makingtransformer plinth (1.5 x 1.5 x 1.5) m in size with necessary excavation in ground with 150 mm. thick M- 10 PCC at the bottom and top and 250 mm. thick, burnt brick wall constructed at periphery and remaining hollow portion shall be filled with 40mm hard broken aggregate. External surface duly plastered by 12 mm thick including watering etc complete. |
| 913 | MSEDCL charges for HT connections: service connection charges for UG connection: Rs.2,53,000/-up to 1000kVA + supervision charges (@ 1.30% ) + Miscellaneous and general charges for HT service Rs.750/- + Application, Registration and processing charges: Rs. 2500/- + Net metering charges Rs. 1000/- (Supportive document attached) |
| 914 | MSEDCL security deposit |
| 915 | Achalpur_Abstract Solar PV |
| 916 | 4.6 Rooftop ON grid solar systems (ESD-RT-ONG) |
| 917 | Supplying, installing, testing and commissioning of10 kWp ON-GRID Solar PV System / Plant consisting Solar PV Poly Crystalline Panel (335 Wp X 30 Nos.) and Solar ON-GRID Inverter of similar capacity (THD<3%) with interconnectingwires / cables up to solar ON GRIDinverter, proper base plate, canopy box to house Inverter and necessary accessories i.e. ACDB/ DCDB , MCB etc. wiring up to solar Inverter in casing and capping, display board, sign board, two distinct earthing, lightning arrester, liaisoning charges, remote monitoring system with maintaining card/chip for 5 yearsincluding net charges for RMS System, complete up to net meter installation and export to the grid with 5 year ON-SITE warranty and fully comprehensive maintenance contract as per Specification no. ESD-RT-ONG |
| 918 | Space requirement: |
| 919 | 1kW of Sola PV requires 100sqft shadow free area on RCCslab |
| 920 | The size of 330Watt solar panel is 3.25ft x 6.42 ft |
| 921 | The surface area of 330watt solar panel is 21.50 sqft |
| 922 | For 11 kW solar PV, the panel requirement is 33 nos. |
| 923 | Area requirement of 33 panels is 33 x 21.50 = 710sqft |
| 924 | Available area is 25,000 sqft |
| 925 | Supplying, erecting & marking FPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kAin provided distribution board as per specification no. SW-SWR/MCB |
| 926 | Supplying & erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBOcomplete erected on angle iron/GI frame. |
| 927 | Supplyinganderecting three phase 10 to 60 A net meterDLMS compliance of accuracy class 1.0, 3 x 240V, 50 Hz,with backlitLCD display, optical port and RJ 232 port(measures import kWh, kVAh, export kWh, kVAh, Net kWh, kVAh, V, I, kW, 6 months history of energy)with wiring connections and mountinghardwareonprovidedpanelscompletewith calibration certificate from manufacturer. |
| 928 | Supplying, erecting& terminating HFFR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core10 sq. mm. copperconductorcompleteerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU |
| 929 | 9) For use of XL-HFFR insulation instead of FR-XLPE insulated armoured cable increase rates by 14 % |
| 930 | 10) XL-HFFR insulated armoured cable are applicable for indoor use only. |
| 931 | 11) XL-HFFR insulated armoured cable shall be used for Hospital Buildings only. If used for other applications, prior permission from competent authority shall be taken. |
| 932 | Achalpu_Abstract_Fire Alarm System |
| 933 | 13.10 Intelligent Addressable Fire Alarm System (FF-AFAS) |
| 934 | Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or UL Approvedwith 3 years equipment replacement warrantyFF-AFAS/SD . |
| 935 | Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area\"s etc. with 3 years equipment replacement warrantyIS : 2175 - 1988 reaffirmed 2000,IS 15908:2021 standards FF-AFAS/SD. |
| 936 | Supplying, installing, testing and commissioning of addressablemanual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with \"Break Glass\"massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listedwith 3 years equipment replacement warrantyFF-AFAS/MCP. |
| 937 | Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage rangeEN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH. |
| 938 | Supplying, installing, testing and commissioning of addressable fire monitor module complete as required. EN 54 or UL Listedwith 3 years equipment replacement warranty conforming toIS 5051Part 2 (Sec 1 to 3) : 1982 Reed relays FF-AFAS/MM |
| 939 | Supplying, installing, testingand commissioning HFFR, XLPE armouredcable 2 core1.5 sq.mm. copper conductorcomplete erected on wall/ ceiling complete asper specification no. CB-LT/CU |
| 940 | 9) For use of XL-HFFR insulation instead of FR-XLPE insulated armoured cable increase rates by 14 % |
| 941 | 10) XL-HFFR insulated armoured cable are applicable for indoor use only. |
| 942 | 11) XL-HFFR insulated armoured cable shall be used for Hospital Buildings only. If used for other applications, prior permission from competent authority shall be taken. |
| 943 | Supplying, installing, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 8 loop capacity and capable of supportingupto 250 devices and detectorsper loop,with on-board LCD display with min 16 lines of text,operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipmentvia a MODBUS/ OPC/ L-ONinterface etc. conforming to IS 15908:2021, IS 2189: 2008, EN 54 & VDS / FM/UL864 (10th edition)with 3 years replacement warranty FF-AFAS/CP |
| 944 | Supplying, installing, testing and commissioning ofrepeater panel with suitable battery backup of a minimum of 24 hours in normal condition and 30 min in alarm condition, 80 backlit alphanumeric LCD display with inbuilt buzzer to indicate fault/fire alarm, manual control keys for silence/mute and to reset the FACP from the repeater station. Panel size shall not more than175 x 275 x 65 mm conforming to EN 54 or UL approvedwith 3 years equipment replacement warranty FF-AFAS/RP |
| 945 | 13.11 P A System (FF-PAS) |
| 946 | Supplying, erecting,testing and commissioning 120 W amplifiersuitable to operate on 230VoltsA.C. / 12VoltsD.C. supply complete asper specification no.FF-PA/AFR |
| 947 | Supplying,erecting, testing and commissioning 15 to 30 Wattssoundcolumn or ceiling mounted complete asper specification no.FF-PA/SOC |
| 948 | Supplying,erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metreshielded cable and 3 Pin Professional XLR Connector, stereo jack complete asper specification no. FF-PA/MIC |
| 949 | Supplying,erecting, testing and commissioningrust freemicrophone floor standof chrome plating/powder coating or S.S. material , 500 mm to 1500 mmheight and sturdy mechanism ensuring trouble free movementcomplete. |
| 950 | Supplying,erecting, testing and commissioning of 2 core shielded cable complete asper specification no.FF-PA/MCC |
| 951 | Supplying,erecting, testing and commissioning of 1.5 sq. mm speaker wirecomplete. |
| 952 | Achalpur_ABSTRACT - FIRE Fighting SYSTEM |
| 953 | Providing Round bottom fire bucket of 9 Litres capacity as per IS : 2546 made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and red outside withFIREMark,onprovidedstand/wallhook complete.(10-2-24) |
| 954 | Providing Floor mounting stand for keeping 4 Nos. of FIRE buckets 1500mm in length, 900mm in height frame made out of 30x30x4 mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of silver paint complete.(10-2-25) |
| 955 | SupplyinganderectingD.C.P. type fire extinguisher 6 kg capacity cartridge type with gun metal cap 150 gram CO2 gas cartridge, powderandbrackets conforming to IS 2171-1985/ IS 15683 and complete erected with necessary clamps made from 50x6 mmM.S. flatwith nuts & bolts grouted in wall complete. |
| 956 | Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete. |
| 957 | Supplying and erecting ABC powder type fire extinguisher as per IS : 13849 /15683 of 6 kg capacity with necessary clamp for erection on wall.(10-2-36) |
| 958 | Supplying, installation, testing and commissioning ofmain fire pump (MFP / EP) suitable for water discharge of 2280 to 2850 LPM at 90 to 70 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 55kW or of suitable kWcapacityfor manual/automatic operation and consisting of following : |
| 959 | (a) Horizontal type, single stage, centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. |
| 960 | (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation onwith IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325. |
| 961 | (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. |
| 962 | (d) Erected on provided suitable size cement concretefoundation duly plastered with anti vibration pads with perfect aligning, properlevelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, asper specification no. FF-MFP/SSC/EP |
| 963 | Supplying, installation, testing and commissioning of jockey fire pump (JP)suitable for water discharge of 180 to 240 LPM at 140 to 110 m head driven by electric motor415 volts, 3 phase 50 Hz, AC supply of 15 kW or of suitable kW capacity for manual/automatic operation and consisting of following : |
| 964 | (a) Horizontal/vertical type, multi stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. |
| 965 | (b) Suitable kW Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-\"F\" insulation, conforming to IS-325. |
| 966 | (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. |
| 967 | (d) Erected on provided suitable size cement concretefoundation duly plastered with anti vibration pads with perfect aligning, properlevelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003)complete, asper specification no. FF-MFP/JP |
| 968 | Providing coating of bitumen paint & 4mm thick wrapping for underground 150 mm ring main of fire fighting system.(13-5-10) |
| 969 | Supplying and erectingG.I. pipe‘C’ class ERW25 mm dia with necessary fittings complete asper specification no. FF-PP |
| 970 | Supplying and erectingG.I. pipe‘C’ class ERW50 mm dia with necessary fittings complete asper specification no. FF-PP |
| 971 | Supplying and erectingG.I. pipe‘C’ class ERW65 mm dia with necessary fittings complete asper specification no. FF-PP |
| 972 | Supplying and erectingG.I. pipe‘C’ class ERW75/80 mm dia with necessary fittings complete asper specification no. FF-PP |
| 973 | Supplying and erectingG.I. pipe‘C’ class ERW100 mm dia with necessary fittings complete asper specification no. FF-PP |
| 974 | Supplying and erectingG.I. pipe‘C’ class ERW150 mm dia with necessary fittings complete asper specification no. FF-PP |
| 975 | Supplying and erectingG.I. pipe‘C’ class ERW200 mm dia with necessary fittings complete asper specification no. FF-PP |
| 976 | Providing coating of bitumen paint &4mm thick wrappingfor underground 100 mm ring mainof fire fighting system. |
| 977 | Providing coating of bitumen paint &4mm thick wrapping for underground 150 mm ring main of fire fighting system. |
| 978 | Providing coating of bitumen paint &4mm thick wrapping for underground 200 mm ring main of fire fighting system. |
| 979 | Supplying anderecting150 mm dia Cast Iron end line strainerof Y-type flanged end pattern, PN16 pressure rating, SSscreen,end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) forpositive suction complete asper specification no. FF-VL/ELS |
| 980 | Supplying and erecting 65 mm dia. cast iron double flangebutterfly valve of size complete with PN16 pressure rating, asper specification no.FF-VL/BFV |
| 981 | Supplying and erecting 75/80 mm dia. cast iron double flangebutterfly valve of size complete with PN16 pressure rating, asper specification no.FF-VL/BFV |
| 982 | Supplying and erecting 100 mm dia. cast iron double flangebutterfly valve of size complete with PN16 pressure rating, asper specification no.FF-VL/BFV |
| 983 | Supplying and erecting 150 mm dia. cast iron double flangebutterfly valve of size complete with PN16 pressure rating, asper specification no.FF-VL/BFV |
| 984 | Supplying and erecting 200 mm dia. cast iron double flangebutterfly valve of size complete with PN16 pressure rating, asper specification no.FF-VL/BFV |
| 985 | Supplying and erecting 75/80 mm diacast iron double flangeNRV complete with PN16 pressure rating, asper specification no. FF-VL/NRV |
| 986 | Supplying and erecting 100 mm diacast iron double flangeNRV complete with PN16 pressure rating, asper specification no. FF-VL/NRV |
| 987 | Supplying and erecting 150 mm diacast iron double flangeNRV complete with PN16 pressure rating, asper specification no. FF-VL/NRV |
| 988 | Supplying and erecting25 mmdiagunmetal gatevalvecomplete with PN16 pressure rating, asper specification no. FF-VL/GV |
| 989 | Supplying and erecting50 mmdiagunmetal gatevalvecomplete with PN16 pressure rating, asper specification no. FF-VL/GV |
| 990 | Supplying anderectingstainless steel single outlethydrantvalve fitted with necessary accessories complete asper specification no. FF-VL/HV |
| 991 | Supplying anderecting75/80 mm dia Cast Iron end line strainerof Y-type flanged end pattern, PN16 pressure rating, SS screen,end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) forpositive suction complete asper specification no. FF-VL/ELS |
| 992 | Supplying anderecting100 mm dia Cast Iron end line strainerof Y-type flanged end pattern, PN16 pressure rating, SSscreen, end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio)forpositive suction complete asper specification no. FF-VL/ELS |
| 993 | Supplying anderecting150 mm dia Cast Iron end line strainerof Y-type flanged end pattern, PN16 pressure rating, SSscreen,end connection with Flanged / Screwed / Socket Weld / Butt Weld End etc with standard OAR (open area Ratio) forpositive suction complete asper specification no. FF-VL/ELS |
| 994 | Supplying and installing wall mounting swinging hose reel drumfitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose)along with necessary accessories complete asper specification no. FF-FFA/HV |
| 995 | Supplying and erecting 63mm dia, reinforced rubber lined (R.R.L.) hose pipe,15m inlength, fitted with necessary accessories complete asper specification no. FF-FFA/RRL |
| 996 | Supplying and erecting gunmetal branch pipe of 63 mm diafitted with 20 mm dia detachable hexagonal nozzlecomplete asper specification no. FF-FFA/NZ |
| 997 | Supplying and erecting 150 mm diafire brigade header suitable for supplying water in fire tank complete asper specification no. FF-FA/FBC |
| 998 | Supplying and erecting fire brigade header ( Siamese connection )of 150 mm dia, for supplying water in fire tank complete asper specification no. FF-FA/FMC |
| 999 | Supplying and erecting300 mm dia 1.5min heightair vessel / tankfabricated from min 5mm thick M.S. sheetcomplete asper specification no. FF-FFA/ACT |
| 1000 | Supplying anderecting 20/25mm dia gun metal air release cock, with necessary G.I.coupling to be fitted on top of air vessel or on wet riser complete asper specification no.FF-FFA/ARV |
| 1001 | Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete asper specification no. FF-FFA/PG |
| 1002 | Supplying and erecting12/15 mm dia pressureswitch with provided isolationvalve,G.I. nipple, elbow, etc complete asper specification no. FF-FFA/PS |
| 1003 | Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP |
| 1004 | Supplying and erecting M.S./CRCA cabinet for housing single hydrant valveof size ( 400 x 400 x 400)mm or hose pipe boxof size (600 x 600 x 200)mm made from min. 1.5 mm thick CRCA sheet with angle iron work of min. of size (25 x 25 x 4) mmhaving front doors with viewing glass of size (200x150) mmandlockingarrangement with necessary fixingmaterialsuch as rubber biddingetc. dulypainted in post box red colour( Code 538 of IS 5) |
| 1005 | Supplying and erecting M.S./CRCA cabinet forhousingFireBrigade / SIEMESE connections (size 1250 x 400 x 300 mm.) made from 16 SWG sheet andangleiron 25 mm. x 25 mm. x 4 mm. having front doors with viewing glass (8\" x 6\") andlocking arrangement with necessaryfixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) |
| 1006 | Supplying and erecting M.S./CRCA cabinetfor housingFloorHydrant valve,hosepipe,hosereeland branch pipe (size 1000 x 736 x 736mm.)madefrom16SWG sheetandangle iron 25 x 25 x 4 mm. having front doors with viewingglass(8\"x6\") andlocking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) |
| 1007 | Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½\") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR. |
| 1008 | Supplying, erecting, testing and commissioning vane type water flow detector100 mm dia.with1) Visual switch activation 2) Rugged switch assembly 3) Heavy duty aluminium pipe saddles 4)Durable metal enclosure 5) Steel U bolts for secure mounting 6) Two SPDT ( Single pole double track ) synchronised switches 7) serviceable without draining pipes. |
| 1009 | Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM. |
| 1010 | For estimating purpose consider 1 bag of 20kg to cover 300mm x 400mm area 150mm thick or 0.018 m3 |
| 1011 | Making cement concrete foundationin 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) (for pumps). (Size of foundation: 1000 x 800 x 400mm x 5 pumps) |
| 1012 | Supplying, installation, testing and commissioning ofmain fire pump (MFP/DP) suitable for water discharge of 2280 to 2850 LPM at 90 to 60 m head driven by 76 HP or suitable HP capacity diesel engine at required working speedsuitable for manual/automatic operation and consisting of following : |
| 1013 | (a) Horizontal type, single stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft(SS410 grade), mechanical seal conforming to IS 1520. |
| 1014 | (b) Water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v, 50Hz AC supply, diesel tank of minimum 150ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine , exhaust pipe extended up to 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications etc. as required. |
| 1015 | (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. |
| 1016 | (d) Erected on provided suitable size cement concretefoundation duly plastered with anti vibration pads with perfect aligning, properlevelling complete pump set with engine assembly and accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/DP |
| 1017 | Supplyinganderectingself stick, self glow radium, Signagesfor Fire Fighting(NON CSR) |
| 1018 | Supply and installation of 150 mm Zone control valve as specified and shown on drawings and complete with: |
| 1019 | 1. Mains gate valve |
| 1020 | 2.Installation valve with retard chamber & motor gong. |
| 1021 | 3. Pressure gauges |
| 1022 | 4. Test connection with gate valve |
| 1023 | 5. All inter connected galvanised steel, piping, strainers, valves, drain piping etc. (NON CSR) |
| 1024 | Supply, Installation, testing & commissioning of UL listed / FM approved S S Braided flexible drops 25 mm dia capable to with stand maximum working pressure of 175 psi with all fittings for making connection to sprinklers and with the branches 1.2 Mtrs in length |
| 1025 | Supply & Installation of Stainless steel finish rosette plate of dia 75 mm for below false ceiling Supply & Installation of Stainless steel finish rosette plate of dia 75 mm for below false ceiling application as per specifications |
| 1026 | 150mm Flexible coupling(NON CSR) |
| 1027 | 65mm Flexible coupling (NON CSR) |
| 1028 | Achalpur_Abstract_Lifts |
| 1029 | 17 Lifts (LiFT) |
| 1030 | SITC of Electric Traction Passenger cum Stretcher/HospitalMRL Lift for G+2 floors of following description as per CSR and per floor ADD ON, as described below; |
| 1031 | • Rated capacity :- 15 Passenger/1020Kg |
| 1032 | • Travel :- 3 to 4.2 mtrs |
| 1033 | • Location of Lift Machine:- MR/MRL [applicable for Passenger Lift with MRL only & Stretcher/Hospital Lift with MR & MRL] |
| 1034 | • Rated speed :- 1.0mps VS |
| 1035 | • Doorstype :- COPO/TOPO Doors with frame having clear opening of 800/900/1000 mm wide x 2000mm highmade from SS 304 grade sheet of 1.5mm, thick in hairline finish for car and all landing doors with SS door architraves /frames |
| 1036 | • Lift car enclosure made from SS 304 grade sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. |
| 1037 | • COP with SS face plate having metallic push buttons with Braille Code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with/without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor |
| 1038 | • Clear Carsize of 1600 mm wide x 2400 mm deep x2200 mm high |
| 1039 | • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille Code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings |
| 1040 | • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port,control panel duly wired with proper size & strengthcopper wire forpower & control circuit, with provision for addition of floor/ control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class |
| 1041 | • ARD complete with necessary SMF VRLA batteries |
| 1042 | • Fireman controller having fireman switch at fire Landing, |
| 1043 | • CCTV surveillance system comprises of 2 Nos. minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC withHDR data backup for 60 days with 18\"FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. |
| 1044 | • Lift Machineof Gear less PMSM of suitable kWwith Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength |
| 1045 | • Other mechanical parts such as \"T\" section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. |
| 1046 | • Minor civil work for alteration if any and erection of door frames and accessories, erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails fixing of girders for mounting lift machine etc. complete as per specification no. LFT. |
| 1047 | • Lift shaft availablehaving clear size of 3000 mm wide x 3000 mm deep,1500 mm Pit depth, 4200 mm Overhead. |
| 1048 | Add On |
| 1049 | For Lift travelling up to six floors or at a speed of 1.0 mps, add as below, |
| 1050 | For Lift having 1000mm wide x 2000mm high clear entrance in 1.5mm thick SS 304 grade landing door [Two panel], this includes all necessary accessories like LOP\"s with UP/DN buttons-arrows-indicators, extension of guide rails, shaft wiring with trunking, travellingcables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete. |
| 1051 | For Full Collective control system, add as below. |
| 1052 | For Lift travellingabove First floor & up to Sixth floor |
| 1053 | Carrying out core cutting of size 3\" to 5\" dia x 15\" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original. |
| 1054 | Supplying and erectingbulk head LED fittingmax. 10Wwith high transitivity diffuser withsystem lumens output of min. 1100 lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg.,THD<10%,p.f. >0.95, operating range of140-260V, in built surge protection of 2.5 kV, Life class of50,000 Hrs. at L70B50, including driver, IP66, IK09 rated on provided PVC Block / wooden board with 3 years warranty. |
| 1055 | Supplying, erecting& terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core10 sq. mm. copperconductorcompleteerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU |
| 1056 | 6) For use of FRLS-XLPE insulation instead of FR-XLPE insulated armoured cable increase rate by 2% |
| 1057 | 1) General: - Job includes entire procedure of obtaining all necessary erection permissions & \"License to Work the Lift\" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. |
| 1058 | 2) Warrantee: - Job covers one years onsite warrantee for all the Lift parts with FCAMC as per the maintenance schedule. |
| 1059 | Achalpur_Abstract_HVAC |
| 1060 | Supplying, erecting, testing and commissioning 14 HP, VRF / VRV air conditioning system, out door unit (ODU) complying type-IV OEM standards working on HFC free refrigerant R410A or other required/suitable green equivalent refrigerant, for cooling capacity delivering 100% at 47 deg. celcius and non stop cooling even at 56 deg. celsius and coefficient of performance (COP) 3.00 to 4.00, modular type horizontal/vertical hot air discharge suitable for total piping length upto 1000 metre operation in cooling mode with inverter based VRF/VRV technology microprocessor based control compressor starter/control panel complete with scroll compressor, air cooled anti corrosive copper condenser coil of suitable shape for increasing maximum heat transfer area, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V ± 10%, 50 Hz, 3 phase power supply, internal copper refrigerant piping, internal wiring and first charge of refrigerant, etc. all housed in powder coated weather proof cabinet on provided angle iron frame or suitable foundation connected to the system in approved manner complete. |
| 1061 | Supplying, erecting, testing and commissioning 16 HP, VRF / VRV air conditioning system, out door unit (ODU) complying type-IV OEM standards working on HFC free refrigerant R410A or other required/suitable green equivalent refrigerant, for cooling capacity delivering 100% at 47 deg. celcius and non stop cooling even at 56 deg. celsius and coefficient of performance (COP) 3.00 to 4.00, modular type horizontal/vertical hot air discharge suitable for total piping length upto 1000 metre operation in cooling mode with inverter based VRF/VRV technology microprocessor based control compressor starter/control panel complete with scroll compressor, air cooled anti corrosive copper condenser coil of suitable shape for increasing maximum heat transfer area, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V ± 10%, 50 Hz, 3 phase power supply, internal copper refrigerant piping, internal wiring and first charge of refrigerant, etc. all housed in powder coated weather proof cabinet on provided angle iron frame or suitable foundation connected to the system in approved manner complete. |
| 1062 | Supplying, erecting, testing and commissioning 20 HP, VRF / VRV air conditioning system, out door unit (ODU) complying type-IV OEM standards working on HFC free refrigerant R410A or other required/suitable green equivalent refrigerant, for cooling capacity delivering 100% at 47 deg. celcius and non stop cooling even at 56 deg. celsius and coefficient of performance (COP) 3.00 to 4.00, modular type horizontal/vertical hot air discharge suitable for total piping length upto 1000 metre operation in cooling mode with inverter based VRF/VRV technology microprocessor based control compressor starter/control panel complete with scroll compressor, air cooled anti corrosive copper condenser coil of suitable shape for increasing maximum heat transfer area, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V ± 10%, 50 Hz, 3 phase power supply, internal copper refrigerant piping, internal wiring and first charge of refrigerant, etc. all housed in powder coated weather proof cabinet on provided angle iron frame or suitable foundation connected to the system in approved manner complete. |
| 1063 | Supplying, erecting, testing and commissioning 22 HP, VRF / VRV air conditioning system, out door unit (ODU) complying type-IV OEM standards working on HFC free refrigerant R410A or other required/suitable green equivalent refrigerant, for cooling capacity delivering 100% at 47 deg. celcius and non stop cooling even at 56 deg. celsius and coefficient of performance (COP) 3.00 to 4.00, modular type horizontal/vertical hot air discharge suitable for total piping length upto 1000 metre operation in cooling mode with inverter based VRF/VRV technology microprocessor based control compressor starter/control panel complete with scroll compressor, air cooled anti corrosive copper condenser coil of suitable shape for increasing maximum heat transfer area, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V ± 10%, 50 Hz, 3 phase power supply, internal copper refrigerant piping, internal wiring and first charge of refrigerant, etc. all housed in powder coated weather proof cabinet on provided angle iron frame or suitable foundation connected to the system in approved manner complete. |
| 1064 | Supplying, erecting, testing and commissioning 24 HP, VRF / VRV air conditioning system, out door unit (ODU) complying type-IV OEM standards working on HFC free refrigerant R410A or other required/suitable green equivalent refrigerant, for cooling capacity delivering 100% at 47 deg. celcius and non stop cooling even at 56 deg. celsius and coefficient of performance (COP) 3.00 to 4.00, modular type horizontal/vertical hot air discharge suitable for total piping length upto 1000 metre operation in cooling mode with inverter based VRF/VRV technology microprocessor based control compressor starter/control panel complete with scroll compressor, air cooled anti corrosive copper condenser coil of suitable shape for increasing maximum heat transfer area, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V ± 10%, 50 Hz, 3 phase power supply, internal copper refrigerant piping, internal wiring and first charge of refrigerant, etc. all housed in powder coated weather proof cabinet on provided angle iron frame or suitable foundation connected to the system in approved manner complete. |
| 1065 | Supply, installation, testing and commissioning of VRF/VRV based Hi-wall type indoor unit (IDU) of nominal cooling capacity 1.0TR (358 cfm) to 1.25TR (417 cfm) having EER as per BEE standards and specifications with multiple speed evaporator fan with motor, copper tube aluminium fin evaporator coil, washable air filter, insulated drain tray, expansion device, cordless remote control with necessary controls, with 3-core copper flexible cord of required length and electrical terminal to receive power supply, etc. IDU shall have anti-corrosive coating suitable for coastal area. Unit shall be suitable for indoor wall mounting, having an electronic control console, provided with suitable mounting brackets with any additional refrigerant and oil charge as per the requirement during installation, connected to the system complete. |
| 1066 | Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indor unit (IDU) compact / standard size of nominal cooling capacity 0.6TR ( 420 cfm ) / 0.8TR ( 441 cfm ) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. Indoor Units complete with in-built drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anticorrosive coating suitable for coastal area complete in all respects, to operate on 1-phase, 230V, 50Hz, AC input supply, consisting with any additional refrigerant and oil charge as per requirement during installation and connected to the system complete. |
| 1067 | Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indor unit (IDU) compact / standard size of nominal cooling capacity 1.0TR ( 441 cfm ) / 1.3TR ( 512 cfm ) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. Indoor Units complete with in-built drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anticorrosive coating suitable for coastal area complete in all respects, to operate on 1-phase, 230V, 50Hz, AC input supply, consisting with any additional refrigerant and oil charge as per requirement during installation and connected to the system complete. |
| 1068 | Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indor unit (IDU) compact / standard size of nominal cooling capacity 1.5TR ( 512 cfm ) / 1.8TR ( 618 cfm ) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. Indoor Units complete with in-built drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anticorrosive coating suitable for coastal area complete in all respects, to operate on 1-phase, 230V, 50Hz, AC input supply, consisting with any additional refrigerant and oil charge as per requirement during installation and connected to the system complete. |
| 1069 | Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indor unit (IDU) compact / standard size of nominal cooling capacity 2.0TR ( 618 cfm ) / 2.3TR ( 671 cfm ) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. Indoor Units complete with in-built drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anticorrosive coating suitable for coastal area complete in all respects, to operate on 1-phase, 230V, 50Hz, AC input supply, consisting with any additional refrigerant and oil charge as per requirement during installation and connected to the system complete. |
| 1070 | Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indor unit (IDU) compact / standard size of nominal cooling capacity 2.6TR ( 918 cfm ) to 2.8TR ( 1100 cfm ) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. Indoor Units complete with in-built drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anticorrosive coating suitable for coastal area complete in all respects, to operate on 1-phase, 230V, 50Hz, AC input supply, consisting with any additional refrigerant and oil charge as per requirement during installation and connected to the system complete. |
| 1071 | Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indor unit (IDU) compact / standard size of nominal cooling capacity 3.0TR ( 1100 cfm ) to 3.2TR ( 1165 cfm ) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. Indoor Units complete with in-built drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anticorrosive coating suitable for coastal area complete in all respects, to operate on 1-phase, 230V, 50Hz, AC input supply, consisting with any additional refrigerant and oil charge as per requirement during installation and connected to the system complete. |
| 1072 | Supply, installation, testing and commissioning of VRF/VRV based ceiling suspended 4 Way cassette indor unit (IDU) compact / standard size of nominal cooling capacity 3.3TR ( 1165 cfm ) to 4.0TR ( 1218 cfm ) having EER as per BEE standards and specifications, suitable as per site requirement with swing louvers and adjustable blades from sides. Indoor Units complete with in-built drainage arrangements, fan, refrigerant liquid and refrigerant piping, cordless remote control, and fresh air port etc. IDU shall have anticorrosive coating suitable for coastal area complete in all respects, to operate on 1-phase, 230V, 50Hz, AC input supply, consisting with any additional refrigerant and oil charge as per requirement during installation and connected to the system complete. |
| 1073 | Supplying, installing, testing & commissioning split type variable speed invertertechnology with minimum 3 to 1 convertible mode for compressor.room air conditioning unit1.7TR to 2.0TR capacity having ISEER minimum 5.0 suitable to operate on 250V, 50 Hz, A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerantR32 having copper condenser, minimum 2.5PM filter, self diagnosis feature, stabilizer free operation & temperature display on indoor unit, noise level maximum 50dBA at position in provided recess with wooden frame complete specification no. AP-AC/WAC |
| 1074 | Supplying, installing, testing & commissioningcassette type variable speedinverter technology with minimum 3 to 1 convertible mode for compressor room Air conditioning unit2.5TR to 2.7TR capacity havingISEER minimum 5.00 suitable to operate on 250V, 50 Hz, A.C. supply having 1 no of air handling unit hi-wall/floor mounting type complete with refrigerant R32/R410A having copper condenser, dust filter, self diagnosis feature, stabilizer free operation, noise level maximum 50dBA at position as per specification no. APAC/ WAC |
| 1075 | Supplying, installing, testing & commissioning cassette type room Air conditioning unit 4TR to 4.4TR capacity with refrigerantR32/410A 415V, 50 Hz, A.C. supply having 1 no of air handling unit (Mega split) mounting type complete withtemperature display on indoor unit, minimum dust filter, noise level maximum 50dBA at position as per specification no. APAC/ WAC |
| 1076 | Supplying & erectingseamless outside & inside, smooth, dry and clean copper pipe with ROHS compliant suitable for refrigeranthaving 22SWG thickness and inner dia/size 16mm complete. |
| 1077 | Supplying & erectingseamless outside & inside, smooth, dry and clean copper pipe with ROHS compliant suitable for refrigerant having 22SWG thickness and inner dia/size 35mm complete. |
| 1078 | Supplying, erecting, testing and commissioning centralised programmable remote contol panel (HMI)touch manager controls minimum 16 system of minimum 64 ODU\"s can be controlled and up to 992 IDU\"s can be individually mounted and controlled indoor units having minimum 200 mm size colour LCD touch panel, yearly schedule, power proportional distribution function, temperature limitation, history function complete erected on wall with an arrangement to integrate with provided fire alarm system. |
| 1079 | Supplying, laying / fixing, testing and commissioning ofappropriate nominal refrigerant copper pipe of 6.4 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system. |
| 1080 | Supplying, laying / fixing, testing and commissioning ofappropriate nominal refrigerant copper pipe of 9.5 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system. |
| 1081 | Supplying, laying / fixing, testing and commissioning ofappropriate nominal refrigerant copper pipe of 12.7 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system. |
| 1082 | Supplying, laying / fixing, testing and commissioning ofappropriate nominal refrigerant copper pipe of 15.9 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system. |
| 1083 | Supplying, laying / fixing, testing and commissioning ofappropriate nominal refrigerant copper pipe of 22.2 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system. |
| 1084 | Supplying, laying / fixing, testing and commissioning ofappropriate nominal refrigerant copper pipe of 19.1 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system. |
| 1085 | Supplying, laying / fixing, testing and commissioning ofappropriate nominal refrigerant copper pipe of 28.6 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system. |
| 1086 | Supplying, laying / fixing, testing and commissioning ofappropriate nominal refrigerant copper pipe of 34.9 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system. |
| 1087 | Supplying, laying / fixing, testing and commissioning ofappropriate nominal refrigerant copper pipe of 41.3 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system. |
| 1088 | Supplying and installation of high pressure grade required size copper connection Y or T- Joints / refnet for liquid and suction line complete erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV / VRF air conditioning system. |
| 1089 | Supply, installation, testing and commissioning of manually operated, opposed blade, duct mounted, flanged volume control dampers of required sizes in GI construction complete with operating mechanism, mounting arrangement, rubber refrigerant kits etc. complete. |
| 1090 | Supply, fabrication, installation an testing of flexible canvass connections constructed between ductable unit / dampers / ducting of required size with fire resist flexible double canvas sleeve complete. |
| 1091 | Providing adhesive thermal insulation for supply return air duct with 19mm nitrile rubber insulation having R-value as per the prevailing provisions in ECBC-2017. |
| 1092 | Supplying, erecting& terminatingFRLS XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core2.5sq. mm. copperconductor completeerected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipeas per specification no. CB-LT/CU |
| 1093 | 6) For use of FRLS-XLPE insulation instead of FR-XLPE insulated armoured cable increase rate by 2% |
| 1094 | Supplying and erecting HMSPVC conduit FRLS grade25 mm dia.with PVC accessories on wall /ceiling as per specification No: WG-MA/CON. |
| 1095 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware. |
| 1096 | Providing & erecting hot dipped galvanised ladder type cable traymanufactured from16 SWG (1.6 mm thick) GI sheet of 300 mm width & 75 mm height complete with necessary coupler plates & hardware. |
| 1097 | Providing & erecting Hot dipped galvanized cover suitable for perforated type cable tray manufactured from 18 swg (1.2 mm thick) GI sheet of 150 mm width & 20 mm height complete with necessary hardware in approved manner. |
| 1098 | Providing & erecting Hot dipped galvanized cover suitable for perforated type cable tray manufactured from 18 swg (1.2 mm thick) GI sheet of300 mm width & 20 mm heightcomplete with necessary hardware in approved manner. |
| 1099 | Supplying and erecting an air flow regulating valves / dampers in provided flexible or rigid duct / pipe of 100 mm size with an alteration for existing flexible pvc pipe duct and necessary joints, sealing, couplings complete at position. |
| 1100 | Supplying, erecting, testing& commissioning fresh air intake system, ductable circular inline fresh air fan inlet unit having 300 cfm capacity with maintaining the static pressure minimum 20 mm of Hg complete suitable to operate on 1ph, 230 V, 50Hz, A.C. supply. |
| 1101 | Supplyinganderectingiron, sheet metal workconsisting of CRCAsheets, varioussectionsofiron,plates, chequeredplates,rods,bars,MSpipes,etc. forpanel board or any other purpose with bending, cutting, drilling and welding completeerectedatthepositionwith necessarymaterialsdulypaintedwith one coat of red oxide and two coats of enamelpaint to match the switchgears or as per directions by the authority. |
| 1102 | Supply,Installation,Testing&CommissioningofCeiling SuspendedDoubleSkinAirHandlingUnitsmadeoutof Alu. Extruded Profile with Thermal Break Profile. The AHU panelsfabricatedoutof0.6mmthickPre-CoatedG.I. Sheet with 43 mm / 47 mm PUF InsulatedPanel. Blower Section shall consists of statically & dynamically balanced ForwardCurvedBlowercapableofdelivering4500CFM of air quantity at 50 mm total static pressure. The cooling coil shall be made out of not less than 27G thick 5/8\" dia. copperpipeof4row/6row deepwith12finsperinch. with SS 304 Drain Tray. Filter section consists of 10 & 20 micronfilterswithefficiencydownto90%.Theoutletof theAirHandlingUnitshallbeinstalledwithOpposed BaldeAerofoilshapeDamper&Firedamperof90Min Rating with Fusible Link. The Air Handling Unit Shall have necessary drive set. All the Motors shall be of three phase &EFFClass1.TheAirHandlingUnitshallbeprovided withElectricalStarterPanelwithVFD&Bypass Arrangement. The AHUs to be provided withthermal Breakprofile.VendortoreferdetailedAHUDataSheet attached seperately. |
| 1103 | Supply,Installation,Testing&CommissioningofCeiling SuspendedDoubleSkinAirHandlingUnitsmadeoutof Alu. Extruded Profile with Thermal Break Profile. The AHU panelsfabricatedoutof0.6mmthickPre-CoatedG.I. Sheet with 43 mm / 47 mm PUF InsulatedPanel. Blower Section shall consists of statically & dynamically balanced ForwardCurvedBlowercapableofdelivering5000CFM of air quantity at 50 mm total static pressure. The cooling coil shall be made out of not less than 27G thick 5/8\" dia. copperpipeof4row/6row deepwith12finsperinch. with SS 304 Drain Tray. Filter section consists of 10 & 20 micronfilterswithefficiencydownto90%.Theoutletof theAirHandlingUnitshallbeinstalledwithOpposed BaldeAerofoilshapeDamper&Firedamperof90Min Rating with Fusible Link. The Air Handling Unit Shall have necessary drive set. All the Motors shall be of three phase &EFFClass1.TheAirHandlingUnitshallbeprovided withElectricalStarterPanelwithVFD&Bypass Arrangement. The AHUs to be provided withthermal Breakprofile.VendortoreferdetailedAHUDataSheet attached seperately. |
| 1104 | Supply, Installation, Testing & commissioning of Fire dampers min 90 min rating,with fusible link & of GI Construction, as per the attached technical specifications. |
| 1105 | Supply, Installation, Testing & Commissioning of hi capacity drain pumps for Hi wall units. Maximum flow 10L/h, maximum sound level 23dB, insulated reservoir, suitable up to 8.75kW / 29850 BTU/h. |
| 1106 | SITC Pre insulated flexible duct with end clamps and Aluminium foil on both side as required in various sizes as below.TheductshallfireretardantULstandard approved.(100 mm Dia.) |
| 1107 | Supply, Installation, Testing & Commissioning of Terminal housingwithbottomremovableH-13(99.97%downto 0.1micron) HEPA filters, DOP testing ports shall be providedinadditiontoportsformeasuringdifferential pressureacrossHEPA filter, and volume controldamper on top alongwith SS 304 buff finished perforated sheet as perdetailedsketchforthefollowingsizeswithportsfor connectingmagnehelicgauge.Manufacturingonlyafter approval of Drawing from client, consultants. Housing Size 1200mmx 2400mm .Thishousingdrawingshouldbe approvedbeforeproduction.Peripheral100mmfromall side is considered for lighting with LED lights.(H1-610X610X298) |
| 1108 | Supply & Installation of flanged type 10 Micron filters (EU - 4) and SS304 buff finished perforated sheet to be fixed on risers provided in the room modular panels. (G.A.drawing to be approved by client before fabrication) |
| 1109 | Supply,Installation, Testing&Commissioning ofHard UPVCsupplywaterpipingusingplumbinggradeUPVC pipes. The pipingshall be properly clamped using saddle & pressure clamps. (50 mm Dia) |
| 1110 | Supply,Installation,Testing&Commissioning ofdrain piping using plumbing grade UPVC pipes The piping shall be properly clamped using saddle & pressure clamps (32 mm Dia.) |
| 1111 | Supply,Installation,Testing&Commissioning ofdrain piping using plumbing grade UPVC pipes The piping shall be properly clamped using saddle & pressure clamps (25 mm Dia.) |
| 1112 | Supply,Fabrication,Installation&TestingofGIDucting Factory Fabricated with T.D.Flange as per SMACNA Class-2withconventionalsupportsoffullThreadedGI rods of required size. All Plenums to be made out of 18 G Only. Use of 26G sheets for duct fabricationnot permitted). Ducts to be properly sealed along the Joints & Flanges with approved sealant from consultant, with Smokeleakagetest.Plenumstobefabricatedin18G only.No slip joints allowed.24 G |
| 1113 | Supply,Fabrication,Installation&TestingofGIDucting Factory Fabricated with T.D.Flange as per SMACNA Class-2 with neoprene rubber gasket splitter vanes conventional supports of full Threaded GI rods of required size.AllPlenumstobemadeoutof18GOnly.Useof 26G sheets for duct fabrication not permitted). Ducts to be properly sealed along the Joints & Flanges with approved sealantwith Smokeleakagetest.Plenumstobe fabricated in 18G only.No slip joints allowed.22 G |
| 1114 | Supply,Fabrication,Installation&TestingofGIDucting Factory Fabricated with T.D.Flange as per SMACNA Class-2 with neoprene rubber gasket splitter vanes conventional supports of full Threaded GI rods of required size.AllPlenumstobemadeoutof18GOnly.Useof 26G sheets for duct fabrication not permitted). Ducts to be properly sealed along the Joints & Flanges with approved sealantwith Smokeleakagetest.Plenumstobe fabricated in 18G only.No slip joints allowed.18 G |
| 1115 | Supply,Installation, Testing &Commissioning of AccousticInsulationofductwith15mmthickOpenCell Nitrile Rubber with Anti Microbial Tratement & of Class ’1’ stuck inside the duct using rubber adhesives.(F.M. Approved).Density of 140 - 180 Kg/m3. |
| 1116 | Supply,Installation, Testing &Commissioning of Underdeck Roof insulation with 19 mm thick Nitrile rubber insulation with Aluminium foil on one side. |
| 1117 | SupplyInstallationTestingandCommissiongof Exposed duct insulation with 19 mm thick nitrile rubber and externallycoveredwith26gaugealuminumcladdingfor all leads and lifts. |
| 1118 | Supply&TopofAdditionalRefrigerantR410AforVRV/ VRFSystem as per Manufacturer requirement. |
| 1119 | Supply,installation, testingandcommissioning of UV Coating For Exposed Pipes to Atmosphere . Piping insulation tobe covered with WovenGlass Cloth 100 gsm and finished in U/V Treatment. |
| 1120 | Achalpur_Abstract_Solar Hot Water System |
| 1121 | ENERGY SAVING DEVICES (ESD) |
| 1122 | 4.1 Solar hot water system (ESD-SHWS) |
| 1123 | Supplying, installing, testingand commissioning of ETC solar water heating system without heat exchanger type of 500 LPDcapacity with SS water tank of 0.5 mm thicknessconforming to IS1239 Part-I :2004 complete as per specification no. ESD-SHWS-ETC |
| 1124 | Calculations: Required solar HW capacity = 160 LPD per person x Number of persons (60% occupancy) |
| 1125 | Hence for 160 patient = 160*120 = 19200 LPD |
| 1126 | Calculations of space requirement AS PER MNRE GUIDELINES: 4 sqmtr for 100 LPD. Hence for 19200 LPD = 768 sqmtr. Available area: 976 sqmtr. |
| 1127 | Supplying and erecting 32/40 mm (ID/OD) Chlorinated polyvinyl chloride pipe (CPVC),thickness 3.8 mm conforming to IS 15778 (CTS Series) with necessary CPVC fittings and solvent cement for Solar Water Heater System as per specification No. ESD-HWP/CPVC |
| 1128 | Supplying and erecting 25/32 mm (ID/OD) Chlorinated polyvinyl chloride pipe (CPVC), thickness 3.2 mm conforming to IS 15778 (CTS Series)with necessary CPVC fittings and solvent cement for Solar Water Heater System as per specification No. ESD-HWP/CPVC |