Tender For Electrical Installation Works Of Five(5) Newly Procured Fume Exhaust System At West Bengal Public Health Laboratory, Kolkata-West Bengal

Public Works Department-PWD has published Tender For Electrical Installation Works Of Five(5) Newly Procured Fume Exhaust System At West Bengal Public Health Laboratory. Submission Date for this Tender is 16-05-2023. Bolts Tenders in Kolkata West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

37494454
Tender For Electrical Installation Works Of Five(5) Newly Procured Fume Exhaust System At West Bengal Public Health Laboratory
Open Tender
Indian
West Bengal
Kolkata
16-05-2023

Tender Details

Tender For Electrical Installation Works Of Five ( 5 ) Newly Procured Fume Exhaust System At West Bengal Public Health Laboratory- 1 Supplying And Drawing 1.1 Kv Single Core Stranded Fr Pvc Insulated & Unsheathed Single Core Stranded Copper Wire ( Brand Approved By Eic ) Of The Following Sizes In The Prelaid Polythene Pipe And By The Prelaid Gi Fish Wire And Making Necy. Connection As Required [ Ref : E-9 / 1 ] 2 A ) 4X80 / 0.4 ( 10 Sqmm ) + 2X84 / 0.3 ( 6 Sqmm ) As Ecc. 3 B ) 4X84 / 0.3 ( 6 Sqmm ) + 2X56 / 0.3 ( 4 Sqmm ) As Ecc. 4 Supplying And Fixing Pvc Rigid Conduit Fr [ Precision Make ] On Wall, Ceiling With Saddles And Other Accessories As Required And Mending Good Damages To Building Works. [ Ref : E-16 / 7 ] 5 A ) 25Mm Size. 6 Distribution Wiring In 1.1 Kv Single Core Stranded Fr Pvc Insulated & Unsheathed Copper Wire ( Brand Approved By Eic ) In 20Mm Size Pvc Rigid Conduit Fr ( Precision Make ) Incl. Necy. Fittings As Required [ Ref : E-14 ] 7 A ) 2 X 84 / 0.3 ( 6 Sqmm ) + 1 X 56 / 0.3 ( 4 Sqmm ) Ecc 8 B ) 2 X 56 / 0.3 ( 4 Sqmm ) + 1 X 36 / 0.3 ( 2.5 Sqmm ) Ecc 9 Finishing Of The Pvc Insulated Wire Ends By Socketting With Pin / Ring Type Copper Sockets And Insulated Tapes Etc., Including Supplying Sockets, Tapes. [ F-5, 9 ] 10 A ) 10Sqmm. 11 B ) 6 Sqmm 12 C ) 4 Sqmm 13 D ) 2.5Sqmm 14 Supplying And Fixing Mcb Ss Enclosure With Ip-20 / 30 Protection, Powder Coated Provision For Two / Four Pole Mcb, ( Make : Legrand / L & T ) Concealed In Wall After Cutting The Wall & Mending Good The Damages To Original Finish Incl. Painting, Connection & Provision For Earthing Attachment [ D-9 / 11 ] 15 A ) 4 Way. 16 B ) 2 Way. 17 Supplying And Fixing 240 / 415 V Mcb Isolator On Din Rail Of Existing Dbs And Necessary Connection. ( Make: Legrand / Schneider / L&T ) [ Ref : D-5 / 6 ] 18 A ) Fp, 63 A. 19 B ) Dp, 40 A. 20 Supplying And Fixing 240 / 415 V Mcb Of Breaking Capacity 10Ka & C Characteristics On Din Rail Of Existing Dbs And Necessary Connection ( Make: Legrand / Schneider / L&T ) ( D-6, 7 ) 21 A ) Sp 6-32A 22 Supplying And Fixing Double-Door Spn Mcb Distribution Board With Ip-42 / 43 Protection, Concealed In Wall After Cutting The Wall & Mending Good The Damages To Original Finish Incl. Inter Connection With Suitable Size Of Copper Wire And Neutral Link & Provision For Earthing Attachment. ( Make: Legrand / Schneider / L&T ) [ Ref : D-9, 13 ] 23 A ) 2+4 Way 24 Supply & Fixing 240 V, 3 Nos. 6 A, 1 No 16A, 3 Pin Modular Type Plug Socket With 3 Nos. 6A & 1No 16A, Modular Type Switch ( Brand Approved By Eic ) , Without Plug Top On 2 Row 12 Module Gi Modular Type Switch Board With 2 Row 12 Module Top Cover Plate Flushed In Wall Incl. S&F Switch Board And Cover Plate And Making Necy. Connections With Pvc Cu Wire And Earth Continuity Wire Etc [ Ref:E-17 ] ( Computer Board ) 25 Supply & Fixing 240 V, 3 Nos. 16 A, 5 Pin Modular Type Plug Socket With 3 Nos. 16A Modular Type Switch ( Brand Approved By Eic ) , 20A Modular Switch Type Sp Mcb ( C-Curve ) And Indicator Without Plug Top On 2 Row 12 Module Gi Modular Type Switch Board With 2 Row 12 Module Top Cover Plate Flushed In Wall Incl. S&F Switch Board And Cover Plate And Making Necy. Connections With Pvc Cu Wire And Earth Continuity Wire Etc. [ Ref : E-18 / 13 ] 26 S & F 20 / 25A Plug Top ( Brand Approved By Eic ) [ Ref : K-3 / 113 ] 27 S & F Of48 Sweep, 230V, 1-Phaseac Ceiling Fans Incl. All Accss., The Capacitor Of Fan Must Be P-2 Type Brust Proof & Must Have Safety Wire Directly Linked From Fan Hook To Stator Of Fan, Complete With Blades, Canopy, Fork, Rubber Bush Etc. Incl. S&F Connecting Wire For Down Rod Upto 30 Cm Incl. Painting The Rod With Approved Paint And Making Necessary Connection As Required By 2X1.5 Sqmm Flexible Copper Wire.. [ Make:Crompton-Hs / Riviera High Speed / Equivalent Model Of Orient ) --- Color-Brown ] [ Ref.: Non Schedule & Page No.-C-3, Sl. No.-21 ( A ) ] 28 Engraving The Deptt. Number With 10 Mm Lettering On The Body Of Fan Upto 10 Letters Incl. Hifen, Stroke Or Stop [ Ref: Schedule- C-3, 24 ] 29 Supplying & Fixing Ms Fan Clam Of Two Piece Type For Rc Ceiling As Per Approved Specification, Fabricated From 40 Mm X 9 Mm Ms Flat Including Making Good Damages To Building Roof With Satisfactory Finishing And Painting – ( As Per Drawing No. 475 Of Pwd Specification Book – May 1991 ) [ D14 / 29 ] 30 S&F Of 230V Grade 400 Mmsweep ( 18 ) Wall Mounting Bracket Fan ( Metal Body & Metal Blade ) On Wall Incl. S & F Of Ms Fastners And Nut & Bolts Etc. As Reqd. ( Make-- Epc ) [ Ref : N.S ] 31 3 Core 2.5 Sq.Mm Communication Cable [ Ref:N.S ] 32 Supply & Fixing 25 Mm Dia Pvc Flexible Conduit. [ Ref:N.S ] 33 S & F Of 120 / 240V Electronic Fan Regulator - Step Type Socket Size As Per Direction Of The E.I.C. Incl. Making Necy Conncetion. ( Make- Anchor ) . [ Ref:N.S ] 34 Add Works Contract Charge In Respect Of Gst @18% 35 Add Lwc @1% 36 Defect Liability Period : 1 Year

Key Value

Document Fees
Refer document
EMD
INR 3157.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: Electrical installationWorks of Five(5) newly procured fume exhaust system at West Bengal Public Health Laboratory.
Sl. No. Item Description
1Supplying and Drawing 1.1 KV single core stranded "FR" PVC insulated & unsheathed single core stranded copper wire (Brand approved by EIC) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required [Ref : E-9/1]
2a) 4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC.
3b) 4x84/0.3 (6 sqmm) + 2x56/0.3 (4 sqmm) as ECC.
4Supplying and fixing PVC Rigid Conduit "FR" [Precision Make] on wall, ceiling with saddles and other accessories as required and mending good damages to building works. [Ref : E-16/7]
5a) 25mm size.
6Distribution wiring in 1.1 KV single core stranded "FR" PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit "FR" (Precision make) incl. necy. fittings as required [Ref : E-14]
7a) 2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC
8b) 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC
9Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.[F-5,9]
10a) 10sqmm.
11b) 6 sqmm
12c) 4 sqmm
13d) 2.5sqmm
14Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, (Make : Legrand/L & T) concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment [D-9/11]
15a) 4 Way.
16b) 2 Way.
17Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection.(Make: Legrand/Schneider/L&T) [Ref : D-5/6]
18a) FP, 63 A.
19b) DP, 40 A.
20Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection(Make: Legrand/Schneider/L&T) (D-6,7)
21a) SP 6-32A
22Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.(Make: Legrand/Schneider/L&T) [Ref : D-9,13]
23a) 2+4 way
24Supply & Fixing 240 V, 3 nos. 6 A, 1 no 16A,3 pin Modular type plug socket with 3 nos. 6A & 1no 16A,Modular type switch (Brand approved by EIC), without plug top on 2 row 12 Module GI Modular type switch board with 2 row 12 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc [Ref:E-17] (computer board)
25Supply & Fixing 240 V, 3 nos. 16 A, 5 pin Modular type plug socket with 3 nos. 16A Modular type switch (Brand approved by EIC), 20A Modular switch type SP MCB (C-Curve) and Indicator without plug top on 2 row 12 Module GI Modular type switch board with 2 row 12 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [Ref : E-18/13]
26S & F 20/25A plug top (Brand approved by EIC) [Ref : K-3/113]
27S & F of48"" sweep, 230V, 1-phaseAC ceiling fans incl. all accss., the capacitor of fan must be P-2 type brust proof & must have safety wire directly linked from fan hook to stator of fan, complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.. [Make:Crompton-HS/Riviera High Speed/equivalent model of Orient) --- Color-Brown] [Ref.: Non Schedule & Page No.-C-3,Sl. No.-21(a)]
28Engraving the deptt. number with 10 mm lettering on the body of fan upto 10 letters incl. hifen, stroke or stop [Ref: Schedule- C-3, 24]
29Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991) [D14/29]
30S&F of 230V grade 400 mmsweep (18") wall mounting bracket fan (metal body & metal blade) on wall incl. S & F of MS fastners and nut & bolts etc. as reqd.(Make-- EPC) [Ref : N.S]
313 core 2.5 sq.mm communication cable[Ref:N.S]
32Supply & fixing 25 mm dia PVC flexible Conduit. [Ref:N.S]
33S & F of 120/240V Electronic Fan Regulator - Step type socket size as per direction of the E.I.C. incl. making necy conncetion. (Make- Anchor). [Ref:N.S]
34Add works contract charge in respect of GST @18%
35Add LWC @1%
36Defect Liability Period : 1 year
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail