Tender For Proposed Construction Of State Command Control Center At Ranchi, ranchi-Jharkhand

Building Construction Department-BCD has published Tender For Proposed Construction Of State Command Control Center At Ranchi. Submission Date for this Tender is 31-05-2023. Building Work Tenders in ranchi Jharkhand. Bidders can get complete Tender details and download the document.




Tender Notice

37396550
Corrigendum : Tender For Proposed Construction Of State Command Control Center At Ranchi
Open Tender
Indian
Jharkhand
ranchi
31-05-2023

Tender Details

Proposed Construction Of State Command Control Center At Ranchi

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 23-May-2023 Corrigendum Date 31-05-2023

Key Value

Document Fees
INR 10000 /-
EMD
INR 7810000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work:-Proposed Constructionof State Command Control Center at Ranchi
Sl. No. Item Description
1Earth work in excavation in foundation trenches in ordinary soil ( vide classification of soil itemA) and disposal of excavated earth as obtained to a distance upto 50M including all lifts leveling ramming the foundation treanches, removing roots of trees, and shrubs all complete as per approved design, building specification and direction of E/I.
2Extra for earthwork in hard soil as per specification and direction of E/I. ( vide classification of soil item-B)
3Earth filling infoundaion trenches and plinth in layers not exceding 150 mm thick well watered, rammed, fully compacted and fine dressed with earthobtainedfrom excavation offoundation trenches within a lead of 50 M and lift of 1.5 M all complete as per building specification and direction of E/I.(mode of measurement compacted volume)
4ProvidIng coarse clean sand In filling in foundation trenches or In plinth including ramming and watering in layers not exceeding 150mm thick with all leads and lifts including cost of all materials, labour. royalty and taxes all complete as per building specification and direction of Ell ( Mode of measurement compacted volume).
5Filling in foundation trenches and plinth in layers. Not exceeding 150 mm thick well watered, rammed fully compacted and fine dressed with earth obtained after cutting within a lead of 50 M and lift of 1.5 M all complete as per building specification and direction of E/I (Mode of measurement compacted volume)
6Supplying chemical emulsion in sealed containers including delivery as specified.
7Chlorpyriphos/ Lindane emulsifiable concentrate of 20%
8Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) :
9Along the external wall below concrete or masonry apron using chemical emulsion @ 2.25 litres per linear metre including drilling and plugging holes etc.:
10With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration
11Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing floor:
12With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
13Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
141:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size)
151:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size)
16Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts,buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills,fillets etc. upto floor five level, excluding the cost of centring, shuttering and finishing :
171:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
18Providing and laying cement concrete in kerbs, steps and the like at or near ground level excluding the cost of centering, shuttering and finishing. 1:1½:3 (1 Cement: 1½ coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size)
19Providing and fixing at or near ground level precast cement concrete in kerbs, edgings etc. as per approved pattern and setting in position with cement mortar 1:3 (1 Cement : 3 coarse sand), including the cost of required centering, shuttering complete. 1:1½:3 (1 Cement: 1½ coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size).
20Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm bed by dry brick ballast 40mm nominal size well rammed and consolidated and grouted with fine sand includingfinishing the top smooth.
21Centering and shuttering including strutting, propping etc. and removal of form for all heights
22Foundations, footings, bases of columns, etc. for mass concrete.
23Walls (any thickness) including attached pilasters, butteresses, plinth and string course etc
24Suspended floors, roofs, landings, balconies and access platform.
25Shelves ( Cast in situ )
26Lintels, beams, plinth beams, girders, bressumers and cantilevers.
27Columns, Pillars, Piers, Abutments, Posts and Struts.
28Extra for shuttering in circular work (20% of respective centering and shuttering items)
29beams
30Columns,
31Stairs, (excluding landings) except spiral-staircases.
32Small lintels not exceeding 1.5m clear span, moulding as in cornices, window sills, string courses, bands, copings, bed plates, anchor blocks and the like.
33Edges of slabs and breaks in floors and walls.
34Under 20 cm wide
35Weather shade, Chajjas, corbels etc., including edges.
36Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured).
37Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)
38providing Tor steel reinforcement of 8mm dia rods as per approved design and drawing exclusive carriage of M.S. bars to work site, cutting, bending and binding with annealed wire with cost of the wire, removal of rust, placing the rods in position all complete as per building specification and direction of E/I. TMT Fe 500 (only valid for SAIL & TATA STEEL)
39providing Tor steel reinforcement of 10mm,12mm,& 16mm. dia bars as per approved design and drawing inclusive carriage of M.S. bars to work site, cutting, bending and binding with annealed wire with cost of the wire, removal of rust, placing the rods in position all complete as per building specification and direction of E/I.
40a) 10 mm / 28/32 mm dia (TMT coiI Fe 500) {Only valid for Tata (Tiscon), SAIL, JSPL,Electrosteel steels Ltd. Bokaro and Vizag (RINL)}
41c) 12 mm / 16 mm / 20/25 mm dia (TMT coiI Fe 500) {Only valid for Tata (Tiscon), SAIL, JSPL,Electrosteel steels Ltd. Bokaro and Vizag (RINL)}
42Providing Tor steel, reinforcement of 20mm, 25mm, 28mm, 32mm dia bars as per approved design and drawing-do- -do-
43Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.
44Footpaths and Separators (Construction of footpath/separator by providing a 150 mm compacted granular sub base as per clause 401 and 25 mm thick cement concrete grade M15, over laid with precast concrete tiles in cement mortar 1:3 including provision of all drainage arrangements but excluding kerb channel.)
45Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge.“(Note :- Cement content considered in this item is @ 330 kg/cum.“Excess/ less cement used as per design mix is payable/recoverable separately).
46All works upto plinth level
47All works From Plinth Level & upto floor V level.
48Concrete of M30 grade with minimum cement content of 350 kg /cum
49Add for using extra cement in the items of design mix over and above the specified cement content therein.
50Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for each four floors or part thereof.
51B R I C KW O R K(A)
52Providing designation 75 A brick work in C.M. (1:6) in foundation and plinth with approved quality of clean coarse sand of F.M. 2 to 2.5 Including providing 10 mm thick mortar joints. cost of screentng materials raking out joints to 15mm depth, curing, taxes and royalty all complete as per building specification and direction of E/l.
53Providing designation 75 A brick work in C.M. (1:6) in superstructure with approved quality of clean coarse sand of F.M. 2 to 2.5 Including providing 10 mm thick mortar joints. cost of screentng materials sacffolding, raking out joints to 15mm depth, curing, taxes and royalty all complete as per building specification and direction of E/l.
54Providing designation 100 A brick work with fly ash lime brick (FLAG) confirming to IS 12894-1990 (9"x4.5"x3") in C.M (1:6) in foundation and plinth with approved quality of clean coarse sand of F.M 2 to 2.5 including providing 10 mm thick mortar joints, cost of screening matenals, raking out joints to 15mm depth, curing, taxes and royalty all complete as per building specification and direction of E/I
55Extra for brick work / AAC block masonry / Tile brick masonryin superstructure above floor V level, for each four floors or part thereof by mechanical means.
56Providing designation 100 A brick Work with fly ash lime brick (FLAG) confirming to IS 12894-1990 (9"x4.5"x3") in C.M. (1:6) in super structure with approved quality of clean coarse sand of F.M. 2 to 2.5 including providing 10 mm thick mortar joints, cost of screening materials, raking out joints to 15mm depth. curing, taxes and royalty all complete as per building specification and direction of E/I.
57Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:3:6(1Cement:3coarsesand(zone-III):6gradedstoneaggregate40mm nominal size)
58Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.
59Cement mortar 1:4 (1 cement :4 coarse sand)
60Extra for half brick masonry in superstructure, above floor V level for every four floors or part thereof by mechanical means.
61Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars atevery third course of half brick masonry.
62Providing and laying autoclaved aerated cement blocks masonry with 100 mm thick AAC blocks in super structure above plinth level up to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rate includes providing and placing in position 2 Nos 6 mm dia M.S. bars at every third course of masonry work.
63Half brick masonry with non modular fly ash bricks of class designation 10, conforming to IS : 12894, in super structure above plinth and upto floor V level.
64Cement mortar 1 : 4 (1 cement : 4 coarse sand)
65Providing and laying autoclaved aerated cement blocks masonry with 150mm/230mm/300 mm thick AAC blocks in super structure above plinth level up to floor V level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately).
66Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.
67Granite of any colour and shade
68Area of slab up to 0.50 sqm.
69Area of slab over 0.50 sqm.
70Extra for fixing marble /granite stone over and above corresponding basic item, in facia and drops of width upto 150 mm with epoxy resin based adhesive including cleaning etc. complete.
71Extra for providing opening of required size & shape for wash basins/ kitchen sink in kitchen platform, vanity counters and similar location in marble/Granite/stone workincluding necessaryholesfor pillar taps etc. including rubbing and polishing of cut edges etc. complete.
72Stone work (machine cut edges) for wall lining etc. (veneer work) upto 10 metre height, backing filled with a grout of average 12 mm thick cement mortar 1:3 (1 cement : 3 coarse sand) including pointing in white cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of pigment matching the stone shade : (To be secured to the backing and the sides by means of cramps and pins which shall be paid for separately) :
73White sand stone - exposed face fine dressed with rough backing .
7430 mm thick
75Providing and fixing stainless steel cramps of required size and shape for anchoring stone wall lining to the backing or securing adjacent stones in stone wall lining in cement mortar 1:2 (1 cement : 2 coarse sand), including making the necessary chases in stone and holes in walls wherever required.
76Supplying, fitting and fixing 35mm thick solid core type non-decorative single leaf flush door shutter in doors and windows with black board core bended with high quality phenol formal dehydes synthetic resin both side commercial veneered of standard make with oxidized iron fittings such as hinges, tower bolts, handle, cleast and sand blocks and taxes all complete as per building specification and direction of E/I.
77Float glass panes
784 mm thick glass pane (weight not less than 10kg/sqm).
795.0 mm thick glass panes (weight not less than 12.5 kg per sqm)
80Extra for providing lipping with 2ndclass teak wood battens 25 mm minimum depth on all edges of shutters (over all area of door shutter to be measured) Over item no. 9.20 and 9.21.
81Providing and fixing aluminium sliding door bolts, ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868), transparent or dyed to required colour or shade, with nuts and screws etc. complete :
82300x16 mm
83250x16 mm
84Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :
85300x10 mm
86150x10 mm
87100x10mm
88Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete :
89125 mm
90100mm
9175 mm
92Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.
93Single rubber stopper
94Twin rubber stopper
95Supplying, fitting and fixing 35mm thick solid core type decorative single leaf flush door shutterwith both sides decorative veneered with black boardcore bended with high quality phenol formal dehydes synthetic resin of standard make with aluminium fittiings such as hinges, tower bolts, handle, cleast and sand blocks and taxes all complete as per building specification and direction of E/I.
96Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt/ suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality.
971.0 mm thick
98Providing and fixing bright finished brass 100 mm mortice latch and lock, ISI marked, with six levers and a pair of anodised (anodic coating not less than grade AC 10 as per IS : 1868) aluminium lever handles of approved quality with necessary screws etc. complete.
99Providing and fixing factory made uPVC white colour sliding glazed window upto 1.50 m in height dimension comprising of uPVC multi-chambered frame with in-built roller track and sash extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), appropriate dimension of uPVC extruded glazing beads and uPVC extruded interlocks, EPDM gasket, wool pile, zinc alloy (white powder coated) touch locks with hook, zinc alloy body with single nylon rollers (weight bearing capacity to be 40 kg), G.I fasteners 100 x 8 mm size for fixing frame to finished wall and necessary stainless steel screws etc. Profile of frame & sash shall be mitred cut and fusion welded at all corners, including drilling of holes for fixing hardware"s and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealent over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes, wire mesh and silicon sealant shall be paid separately)
100Note: For uPVC frame and sash extruded profiles minus 5% tolerance in dimension i.e. in depth & width of profile shall be acceptable.
101Three track three panels sliding window with fly proof SS wire mesh (Two nos. glazed & one no. wire mesh panels) made of (small series) frame 92 x 44 mm & sash 32 x 60 mm both having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension (Area of window upto 1.75 sqm).
102Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer. Using M.S. angels 40x40x6 mm for diagonal braces
103Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 part 1 and M.S. top cover of required thickness for rolling shutters.
10480x1.25 mm M.S. laths with 1.25 mm thick top cover
105Providing and fixing ball bearing for rolling shutters.
106Extra for providing mechanical device chain and crank operation for operating rolling shutters.
107Exceeding 10.00 sqm and upto 16.80 sqm in the area
108Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge:
109Profile B
110Fixing with adjustable lugs with split end tail to each jamb
111Providing and fixing M.S. fan clamp type I or II of 16 mm dia M.S. bar, bent to shape with hooked ends in R.C.C. slabs or beams during laying, including painting the exposed portion of loop, all as per standard design complete.
112Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing.
113Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.
114In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete
115In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works.
116Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approved steel primer.
117M.S. tube
118Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm dia double threaded 6.8 grade (yield strength 480 N/mm2), counter sunk head, comprising of 10 mm dia polyamide PA 6 grade sleeve, including drilling of hole in frame , concrete/ masonry, etc. as per direction of Engineer-in-charge.
11910 x 120 mm
120Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).
121Light shade pigment using white cement
122Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
12362 mm thick cement concrete flooring with concrete hardener topping,under layer 50 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) and top layer 12mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate, 6mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacture’s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete.
124Chequered terrazo tiles 22 mm thick with graded marble chips of size up to 6 mm in floors, jointed with neat cement slurry mixed with pigment to match the shade of the tiles, including rubbing and polishing complete, on 20 mm thick bed of cement mortar 1:4 (1 cement :4 coarse sand) : Light shade pigment using white cement
125Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in colours White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement: 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete.
126Providing and laying Double Charge Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS:15622/ ISO 13006, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement :4 coarse sand ), jointing with grey cement slurray @ 3.3 k.g / sqm including grouting the joints with white cement and matching pigments etc., complete size of tile 600 x 600 mm .
127Size of Tile 600x600 mm
128Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately).
129Size of Tile 600x600 mm
130Providing and laying 25mm thick kotah stone slab flooring of approved size, texture and colour over 19mm. thick base of lime morter (1:1:1) (lime putty:surkhi:coarse sand) laid over and Jointed with grey cement slurry mixed with pigment to match the shade of slab including rubbing and polishing to granolithic finish with approved quality of carborandium stone including cost of curing, taxes and royalty all complete as per building speclflcationand direction of Ell.
131iv) 600X600 mm Size
132Providing and laying 25mm thick kotah stone tiles In risers of steps, skirting, and pillars of approved size, texture and colour laid over 12mm. thick cement mortar (1:3) and joined with grey cement slurry mixed with pigment to match the shade of the slab including rubbing to granolilthic finish with approved quality -do-
133Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge :
134Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
135Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge.
136Polished Granite stone slab colour of Black, Cherry/Ruby Red or equivalent
137Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering process and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-incharge. (The panel shuttering work shall be paid for separately). (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately).
138Providing & fixing in position Phenol bonded Bamboowood flooring with planks of sizes 14mm thick, minimum 1800mm length and minimum 100 mm wide, in approved colour, texture and finish, having Performance Appraisal Certificate (PAC) issued by Building Materials & Technology Promotion Council (BMTPC). The flooring shall be fixed with tongue and groove interlocking system, with underlayment of 4mm thick expanded polyethylene foam sheets having density 40kg/cum, over prepared surface with necessary quarter round planks of size 1900mm x 18mm and door reducer of size 1900mm x 44mmwherever required. The bamboowood planks shall have minimum density of 1000 Kg/cum & minimum Hardness 1000 Kgf. with Eco friendly UV coating, all complete as per direction of the Engineer in-charge.
139Providing & fixing in position Phenol bonded Bamboo wood in wall skirting with planks of sizes 14mm thick, 1900mm length (minimum) and 85mm wide(minimum), in approved colour, texture and finish, having Performance Appraisal Certificate (PAC) issued by Building Materials & Technology Promotion Council (BMTPC). The skirting shall be fixed with SS screws & rawl plugs, over underlayment of 4mm thick, expanded polyethylene foam sheets having 40kg/cum density over prepared surface. The bamboowood planks shall have minimum density of 1000Kg/cum & minimum Hardness 1000 Kgf. with Eco friendly UV coating, all complete as per direction of the Engineer in-charge.
140Providing and fixing 10x10x7.50 cm Granite stone block hand cut and chisel dressed on top, for paving in floors, drains etc. laid over 20mm thick base mortar 1:4 (1 cement : 4 coarse sand) with joints 10mm wide filled with same mortar including ruled pointing etc. complete as per direction of engineer-in-charge.
141Marble stone flooring with 18 mm thick marble stone, as per sample of marble approved by Engineer-in-charge, over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with grey cement slurry, including rubbing and polishing complete with :
142Marble chips skirting up to 30 cm height, rubbed and polished to granolithic finish, top layer 6 mm thick with white, black, chocolate, grey, yellow or green marble chips of sizes from smallest to 4 mm nominal size, laid in cement marble powder mix 3:1 (3 cement : 1 marble powder) by weight in proportion of 4:7 (4 cement marble powder mix : 7 marble chips) by volume
14318 mm thick with under layer 12 mm thick in cement plaster 1:3 (1 cement : 3 coarse sand) :
144Light shade pigment with white cement
145Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on 20 mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand).
146Light shade pigment using white cement
147Providing and fixing removable raised/false access flooring with system and its components of approved make for different plenum height with possible height adjustment upto 50 mm, comprising of modular load bearing floor panels supported on G.I. rectangular stinger frame work and G.I. Pedestal etc. all complete, as per the architectural drawings, as specified and as directed by Engineer-in-charge consisting of: (a) Providing at required spacing to form modular framework, pedestals made out of GI tube of thickness minimum 2 mm and 25 mm outer diameter, fully welded on to the G.I. Base plate of size 100mm x 100mm x 3mm at the bottom of the pedestal tube, G.I. pedestal head of size 75mmx75mmx3.5 mm welded with GI fully threaded stud 16mm outer diameter with two GI Check nuts screwed on the stud for level adjustment upto 50mm, locking and stabilizing the pedestal head in position at the required level. The pedestals shall be fixed to the subfloor (base) through base plate using epoxy based adhesive of approved make or the machine screw with rawl plug.
148(b) Stringers system in all steel construction hot dipped galvanized of rectangular size 570x20x30x0.80mm thick having holes at both ends for securing the stringers on to the pedestal head using fully threaded screws ensuring maximum lateral stability in all directions, the grid formed by the pedestal and stringer assembly shall receive the floor panel, this system shall provide adequate solid, rigid support for access floor panel, the system shall provide a minimum clear uninterrupted clearance between the bottom of the floor for electrical conduits and wiring etc. all complete as per the architectural drawings, as specified and as directed by the Engineer-in-charge.
149(c) Providing and fixing Access Floor panel of 600x600x32 mm medium grade Filled Steel anti static high pressure Lamination of 800H grade (FS800H). Access Floor panel shall be steel welded construction with an enclosed bottom pan with uniform pattern of 64 hemispherical cones. The top and bottom plates of Steel Gauges: top 0.6 mm and bottom 0.7 mm fused spot welded together (minimum 64 welds in each dome and 20 welds along each flange). The panel should be Corroresist epoxy coated for lifetime rust protection and cavity formed by the top and bottom plate is filled with Pyrogrip noncombustible Portland cementitious core mixed with lightweight foaming compound. The access floor shall be factory finished with Anti-static High Pressure laminate with Non Warp technology upto 1mm thickness for superior adhesion and Surface flatness within 0.75mm.The panel is to withstand a Concentrated Load of 363 kgs applied on area 25mm x 25mm without collapse in the centre of the panel which is placed on four steel blocks. The panel will withstand and Uniformly Distributed Load (UDL) minimum 1250 kg/sqm and an impact load of 50kg all complete as per the approved manufacturers specification and as per the direction of Engineer-in-charge. All specification must be printed on the side of the panel to ensure the quality of the product.
150300 mm Finished Floor Height (FFH)
151Extra for pre finished nosing in treads of steps of Kota stone/ sand stone slab.
152Extra for Kota stone/ sand stone in treads of steps and risers usingsingle length up to 1.05 metre.
153Extra for pre finished nosing to treads of steps of marble/ granite stone.
154Extra for marble/ granite stone flooring in treads of steps and risers using single length up to 2.00 metre.
155Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes.
156Providing & Fixing 110mm PVC Pipe For Weep Holes
157Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main ‘T’ runner suitably spaced at joints to get required length and of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced between main’T’ at 600 mm centre to centre to form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screws @ 230 mm interval and laying 15 mm thick densified edges calicum silicate ceiling tiles of approved texture in the grid, including, cutting/ making opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main ‘T’ runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main ‘T’, bottom exposed with 24 mm of all Tsections shall be pre-painted with polyster baked paint, for all heights, as per specifications, drawings and as directed by Engineer-in-Charge.
158Note :- Only calcium silicate false ceiling area will be measured from wall to wall. No deduction shall be made for exposed frames/opening (cut outs) having area less than 0.30 sqm.The calcium silicate ceiling tile shall have NRC value of 0.50 (Minimum), light reflection > 85%, non- combustible as per B.S. 476 part IV, 100% humidity resistance and also having thermal conductivity <0.043 w/mK.
159Providing and fixing Gl Clip in Metal Ceiling System of 600x600 mm module which includes providing and fixing "C" wall angle of size 20x30x20 mm made of 0.5 mm thick pre painted steel along the perimeter of the room with help of nylon sleeves and wooden screws at 300 mm center to centre, suspending the main C carrier of size 10x38x10 mm made of G.I steel 0.7 mm thick from the soffit with help of soffit cleat 37x27x25x1.6 mm, rawl plugs of size 38x12 mm and C carrier suspension clip and main carrier bracket at 1000 mm c/c. Inverted triangle shaped Spring Tee having height of 24 mm and width of 34 mm made of Gl steel 0.45 mm thick is then fixed to the main C carrier and in direction perpendicular to it at 600 mm centers with help of suspension brackets. Wherever the main C carrier and spring T have to join, C carrier and spring T connectors have to be used. All sections to be galvanized @ 120 gms/sqm (both side inclusive), fixing with clip in tiles into spring T with :
160GI Metal Ceiling Clip in plain Beveled edge global white color tiles of size 600x600 and 0.5 mm thick with 25 mm height, made of G I sheet having galvanizing of 100 gms/ sqm (both sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum), including factory painted after bending.
161Providing and fixing tiled false ceiling of specifiedmaterials of size 595x595 mm in true horizontal level, suspended on interlocking metal grid of hot dipped galvanized steel sections ( galvanized @ 120 grams/ sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200 mm center to center and cross "T" of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanized butterfly level clips of size 85 x 30 x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer-in-charge.
1628 mm thick fully perforated calcium silicate board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process to give stable crystalline structure with minimum compressive strength 225 kg/ sq. cm, bending strength 100 kg/sq. cm , of size 595x595 mm, having perforation of dia. 10 mm with minimum perforated area 18 % with non woven tissue on the back side, having an NRC ( Noise Reduction Coefficient) of 0.85, with 50 mm thick rockwool of 48 kg /cum backing.
163Providing 12mm thick cement plaster (1:6) with clean coarse sand of F.M. 1.5 including screening, curing with all leads and lifts of water, scaffolding taxes and royalty all complete as per building specification and direction of E/I.
164Providing and applying 12 mm thick water proof cement plaster (1:3) with clean coarse sand of F.M 1.5 with 5% cico or any other approved water proofing compound.-do
165Providing 6mm thick cement plaster (1:4) in ceiling with clean of F.M. 1.5 including screening, curing with all leads and lifts of water, scaffolding taxes and royalty all complete as per building specification and direction of E/I.
166Extra for plaster work over exterior surface for each consecutive floor above first floor including cost of scaffolding etc. all complete as per direction of E/I.
167Making 6x6mm grooves in plaster surface over walls truly horizontal of vertical as specified at regular intervals, at all heights including cleaning, finishing, scaffolding and curing with all leads and lifts of water all complete as per building specification and direction of E/I.
168Providing two coats of plastic emulsion paint of approved shade and make over a coat of cement primer over new surface including preparing plastered surface by rubbing smooth with pumice stone of fine sand paper, applying putty wherever required, scaffolding washing of floor and taxes all complete as per building specification and direction of E/I
169providing two coat of oil bound distemper of approved shade and make over a coat of cement primer over new surface including preparing the plastered surface by rubbing smooth with pumice stone or fine sand paper applying putty whwerever required scaff folding washing of floors and texes all complete as per building specification and dircetion of E/I
170Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
171Providing two coat of synthetic enamel paint of approved shade and make over new wooden surface do/-
172Finishing walls with Acrylic Smooth exterior paint of required shade :
173New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm)
174Providing and fixing 10x10x7.50 cm Granite stone block hand cut and chisel dressed on top, for paving in floors, drains etc. laid over 20mm thick base mortar 1:4 (1 cement : 4 coarse sand) with joints 10mm wide filled with same mortar including ruled pointing etc. complete as per direction of engineer-in-charge.
175Providing and fixing of façade at all heights with extruded hollow Clay / Terracotta ventilated rainscreen tiles of height 250/ 300/ 400mm and length of 595 mm of approved texture,design and pattern having Flexural Strength/ Modulus of Rupture of ? 14 N/m² and maximum water absorption of 10% tested as per ISO 10545-4:2004(E) and ISO 10545-3:1995 respectively in true level fixed to a supporting aluminium framework(Alloy 6063 T5/T6) consisting of vertical "T" (for intermediates)/ "L"(for ends/ termination)/ Tubular sections (at corners)of size 80x60x2mm/ 40x60x2mm/ 40x40x2mm respectively, spaced at maximum spacing of 600mm c/c matching to the tile vertical grid, and horizontal aluminium "C"-clamps of size 56x25x2mm thickness of length 150mm at junction of tiles and of length 75mm at wall ends/ corners fixed on top of the vertical sections at spacing of 250/ 300/ 400mm c/c matching to the tile horizontal grid with two numbers of self-drilling / self-tapping SS screws of size 5.5x25 mm with EPDM washers.The vertical "T"/"L/ Tubular" sections shall be fixed to the wall using HDG (hot-dip-galvanized) steel L-brackets (galvanizing thickness of minimum 80 microns)of size 110x80x6 mm at intermediate vertical aluminium profiles and of size 220x110x12 mm at outer corners and stainless steel grade 304,M10 full threaded anchor fasteners with nylon sleeve 100mm long (for brick work) and M8 expansion anchor fasteners 75mm long for concrete surface, spacing of brackets to be based on a structural/ static calculation.
176The brackets shall be of length 175mm at junction of two vertical aluminium profiles and of length 100mm at intermediate points of vertical profiles and shall be fixed to the vertical aluminium T / L / Tubular profiles using two numbers self-drilling/ self-tapping SS screws of size 5.5x25mm with EPDM washers. EPDM gaskets to be fixed in between brackets and vertical profiles. The tiles shall be mounted on the ‘C’ clamps such that the tiles are supported at top and bottom at both ends. The tiles shall be additionally secured to the horizontal ‘C’ clamps using special SS clips of required size which shall be inserted and pressed into position on the ‘C’ clamps holding the tiles and the cut-tiles shall be glued at points to thehorizontal ‘C’ clamps by using MS Polymer sealant adhesive. Thevertical joint open groove between two adjacent tiles shall be 5mm. The tiles and system shall be designed to resist wind load as per IS 875 (Part 3) according to different zones. The tiles shall be installed using the ventilated rain screen principle with provision for natural ventilation of the space between the façade tiles and the structural wall. The work shall be carried out as per specification, drawing and as per direction of the Engineer-in-Charge. Note : Scaffolding wherever required to be paid separately.
177With 16mm thickness (+/- 10%) terracotta tiles of other than grey colors
178ALUMINIUM WORK
179Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing,aneling and dash fasteners to be paid for separately) :
180For fixed portion
181Powder coated aluminium (minimum thickness of powder coating 50 micron)
182For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately)
183Powder coated aluminium (minimum thickness of powder coating 50 micron)
184Providing and fixing anodised aluminium grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only weight of grill to be measured for payment).
185Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineerin- charge.
186Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side
187Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge.
188With stainless steel cover plate minimum 1.25 mmthickness
189Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):
190With float glass panes of 5 mm thickness (weight not less than 12.50 kg/sqm)
191Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete.
192Providing and fixing anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868. Minimum anodic coating of grade AC 15) sub frame work for windows and ventilators with extruded built up standard tubular sections of approved make conforming to IS: 733 and IS: 1285, fixed with dash fastener of required dia and size (Dash fastener to be paid for separately).
193WATER PROOFING
194Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying a) First layer of slurry of cement @ 0.488 kg/sum mixed with water proofing cement compound @ 0.253 kg/sum.This layer will be allowed to air cure for 4 hours.b) Second layer of slurry of cement @ 0.242 kg/sum mixed with water proofing cement compound @ 0.126 kg/sum.This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours.The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.
195(b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.
196Water proofing for Old and New Roof Slab:- Providing and laying water proofing treatment on roof slab by applying two Component, factory designed, ready to use, acrylic modified flexible material applied with, brush, roller or spray for water proofing coating as per manufacturer specifications with following steps: (a surface preparation-Providing and cleaning of concrete surface to remove dust, oil, greaseincluding removal of existing loose paint / coating, and cement laitance by cleaning with compressed air & water jet including all materials, labour, tools complete. Ponding test to be done after plugging all outlets and to be checked from soffit to identify seepage, leakage. On identification of seepage, cement grouting to be done with non shrink expanding admixture of Sika India Pvt Ltd /MYK Schomberg/Dr Fixit/Fosroc or equivallent Providing and reparing of all comers and joints such as those between the parapet wall and the roof slab etc shall be chamfered with 150 mm X 150 mm fillet of mortar (Cement: sand-1:4) admixed with acrylic polymer of Sika Fosroc/MYK Schomberg Fixit or equivalent. Before chamfering a prime coat shall be given with the slurry ofacrylic polymer. Repairing surface irregularities, damaged concrete in base slab, dead cracks if any, with an acrylic polymer modified repair mortar including a coat of bonding agent of the same with cement slurry including all material, labour, tools complete. (b)1st Coat Apply 1st coat of two component acrylic modified, ready to use, flexible cementitious material on surface saturated dry roof and inside wall of Parapet wall upto 600 mm by brush or roiler After 1st coat of application, 45 gsm of Fibre glass cloth to lay when the first layer is still green. 1st coat should be applied @1.50 kg / Samt/coat. For the purpose of measurement the entire treated surface will be measured." (c) 2nd Coat-To apply the 2nd coat of two component acrylic modified, ready to use, flexible cementitious material right angle to the 1st coat over the glass fibre laid surface 2nd coat should be applied @0.7 kg/Samticoat For the purpose of measurement the entire treated surface will be measured After three days of drying the 2nd coat, the rail water outlets to be plugged and ponding test to be done for 48 hours to identify seepage, leakage from soffit and if found necessary rectification to be done as per satisfaction of EIC. The waterproof coating to be protected from damage before screed over it. Waterproofing Brand- Sika Topseal 109hi/Fosroc Brushbond RFX/Dr Foxit Pidiffin 2K/MYK Aquafin TG Product Performance - Chemical Base Part A Acrylic copolymer, Part B Specially graded cementitious powder- Density 1.6 kg/l (mixed density) at +27°C Tensile Strength -2 Nimm2 after 28 days (with Fibre cloth) (According to ASTM D 2370) Pullout Bond Strength -2 N/mm2 (concrete failure) (According to ISO 4624) Slant-Shear Bond Strength -4 N/mm2 (According to FIP 5.15) Elongation at Break -35% without Fibre Cloth and 20% with Fibre Cloth (According to ASTM D 2370) (d) Protection of treated surface with PCC-The treated surface should be covered with 25mm/ 50mm PCC of M-20 grade(1:1.5:3) with proper slope (1:120) towards the rain outlets in alternate panels of 2 mt x 2mt keeping 6 mm gap between the panel joint. Integral water proofing admixture conforming to IS 2645 @of 100 ml per bag of of cement to be added in the screed concrete(paid separately for this items) All corners shall be chamfered with 150mm x 150 mm fillet. The rain water outlets shall be just leveled with the screed concrete to ensure smooth discharge of water the peripheral gaps between pvc pipe outlet and concrete surface should be packed property with rich concrete and the peripheral mouth to be sealed with moisture insensitive epoxy putty of Sika India Pvt. Ltd. /MYK Schomberg/Dr Fixt/Fosroc For the purpose of measurement the entire treated surface will be measured." (e)Groove of PCC surface should be filled with Polysulphide Sealant (Paid Separately). Brand- Sika India Pvt Ltd./MYK Schomberg/Dr Foxit/Fosroc Warranty for five years.
197Covering of treated surface with PCC:- Providing 50 mm thick Cement Concrete M20(1:1.5:3) maintaining slope inalternate 2 mt x 2 mt panels with aaproved quality of stone chips of 20 mm to 6 mm size graded and cleaned sand of F.M 2.5 to 3 including screening,shuttering and mixing cement concrete in mixer withadmixture of integral water proofing and placing in position,striking curing,taxexand royality all complete as per building specifiction and direction of Ell.Panels thathas been left should be casted next day.There should be 6 mm gap between Panels .Brand-Sika­ P\astocrate plus, MYK proof WP 1O,Fosroc-Conplast X4211 C,Dr.fixit Pidiproof LW+ or Equivalent .
1985.12.8. Providing and filling of 6 mm thickGroove between 25 mm PCC Panels with Polysulphide Sealant (Poring Grade)as per drawings and technical specifications and direction of E in Charge.(with 18% GST).Brand:-Sika-Polysulphide, Fosroc-Thioflex 600,Dr. Fixit Pidiseal PS(42P),MYK Seal PS or Euivalent
199SUB HEAD - STRUCTURAL GLAZING AND ALUMINIUM COMPOSITE PANEL
200Providing and supplying aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawings , the aluminium quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. ( The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account). The weight of aluminium extruded section shall be taken for purpose of payment.
201Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including:
202Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)-cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including:
203Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers.
204Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment, including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass.
205Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight.
206Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer- in-Charge.
207Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this subhead. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves) on the external face shall be measured in sqm. up to two decimal places.
208Note:-2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately.
209The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NABL accredited lab or by any other accreditation body which operates in accordance with ISO / IEC 17011 and accredits labs as per ISO/ IEC 17025.
210Performance Laboratory Test for Air Leakage Test (-50pa to - 300pa) & (+50pa to +300pa) as per ASTM E-283-04 testing method for a range of testing limit 1 to 200 mVhr
211Static Water Penetration Test. (50pa to 1500p) as per ASTME- 331-09 testing method for a range up to 2000 ml.
212Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01- 05 testing method for a range upto 2000 ml
213Structural Performance Deflection and deformation by static air pressure test (1.5 times design wind pressure without any failure) as per ASTME-330-10 testing method for a range upto 50 mm
214Seismic Movement Test (upto 30 mm) as per AAMA 501.4- 09 testing method for Qualitative test, Tests to be conducted on site.
215Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000 ml
216Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as required and specified, comprising of an outer heat strengthened float glass 6mm thick, of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an inner Heat strengthned clear float glass 6mm thick, spacer tube 12mm wide, dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor. (Payment for fixing of IGU Panels in the curtain glazing is included in cost of item No.25.2) For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm.
217(i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement.
218Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.
219Fixed to steel windows by welding
22015 mm cement plaster on rough side of single or half brick wall of mix:
2211:6 (1 cement: 6 coarse sand)
22218 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster 1:3 (1 cement : 3 coarse sand) finished rough with sponge.
223Distempering with 1st quality acrylic distemper, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture, including applying additional coats wherever required, to achieve even shade and colour.
224Two coats
225Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :
226Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture
227Neat cement punning.
228Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers.
229Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content.
230With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre
231"Providing and laying design mix cement concrete of M-30 grade, in roads/ taxi tracks/ runways, using cement content as per design mix, using coarse sand and graded stone aggregate of 40 mm nominal size in appropriate proportions as per approved & specified design criteria, providing dowel bars with sleeve/ tie bars wherever required, laying at site, spreading and compacting mechanically by using needle and surface vibrators, levelling to required slope/ camber, finishing with required texture, including steel form work with sturdy M.S. channel sections, curing, making provision for contraction/ expansion, construction & longitudinal joints ( 10 mm wide x 50 mm deep) by groove cutting machine, providing and filling joints with approved joint filler and sealants, complete all as per direction of Engineer-in-charge (Item of joint fillers, sealants, dowel bars with sleeve/ tie bars to be paid separately).
232Note:- Cement content considered in M-30 is @ 340 kg/cum. Excess/ less cement used as per design mix is payable/ recoverable separately.
233Cement concrete prepared with batch mixing machine
234Providing and placing in position 100 mm thick factory made machine batched & machine mixed Precast RCC Rectangular Covers on drains of footpath of various sizes, of M-25 grade cement concrete for RCC work, including cost of centering, shuttering, reinforcement of 8 mm dia TMT bars of Fe 500 grade @ maximum 100mm c/c on both ways , neat cement punning on finished surface, properly encased on all edges with 1.6 mm thick , 100 mm wide MS sheet duly painted over priming coat , reinforcement to be welded at edges with MS sheet and providing 2 Nos. 12 mm dia bar for hooks etc i/c cost of cartage, all leads & lift, handling at site etc. all complete as per direction of Engineer-in-Charge.
235Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of engineer-in-charge.
236Pre-laminated particle board with decorative lamination on both sides.
237Filling the gap in between aluminium frame & adjacent RCC/ Brick/ Stone work by providing weather silicon sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete.
238Upto 5mm depth and 5 mm width
239Providing and fixing aluminium casement windows fastener of required length for aluminium windows with necessary screws etc. complete.
240Powder coated minimum thickness 50 micron aluminium
241Providing and laying integral cement based treatment for water proofing on horizontal surface at all depth below ground level for under ground structures as directed by Engineer-in-Charge and consisting of :
242(i) Ist layer of 22 mm to 25 mm thick approved and specified rough stone slab over a 25 mm thick base of cement mortar 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound conforming to IS:2645 in the recommended proportion over the leveling course (leveling course to be paid separately). Joints sealed and grouted with cement slurry mixed with water proofing compound. (ii) 2nd layer of 25 mm thick cement mortar 1:3 (1 cement: 3 coarse sand) mixed with water proofing compound in recommended proportions. (iii) Finishing top with stone aggregate of 10 mm to 12 mm nominal size spreading @ 8 cudm/sqm thoroughly embedded in the 2nd layer.
243Using rough kota stone.
244Providing and laying integral cement based treatment for water proofing on the vertical surface by fixing specified stone slab 22 mm to 25 mm thick with cement slurry mixed with water proofing compound conforming to IS:2645 in recommended proportions with a gap of 20 mm (minimum) between stone slabs and the receiving surfaces and filling the gaps with neat cement slurry mixed with water proofing compound and finishing the exterior of stone slab with cement mortar 1:3 (1 cement : 3 coarse sand) 20 mm thick with neat cement punning mixed with water proofing compound in recommended proportion complete at all levels and as directed by Engineer-in-charge :
245Using rough kota stone.
246Embankment Construction with Material Obtained from Borrow Pits (Construction of embankmentwithapprovedmaterialobtainedfromborrowpitswithallliftsandleads, transporting to site, spreading, grading to required slope and compacting to meet requirement of table 300-2)
247Rolling with vibratory roller
248Filling in foundation trenches and plinth in layers. Not exceeding 150 mm thick well watered, rammed fully compacted and fine dressed with earth obtained after cutting within a lead of 50 M and lift of 1.5 M all complete as per building specification and direction of E/I (Mode of measurement compacted volume)
249Granular Sub-base with Close Graded Material (Table:- 400-1)
250PlantMixMethod(Constructionofgranularsub-basebyprovidingclosegraded Material,mixing in a mechanicalmix plant at OMC, carriageof mixed Materialto work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401 )
251for grading- IMaterial
252for grading- IIMaterial
253for grading-IIIMaterial
254Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver in sub- base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density.
255Dry Lean CementConcreteSub- base (Constructionof dry lean cementconcreteSub- baseoverapreparedsub-gradewithcoarseandfineaggregateconformingtoIS: 383, the size of coarseaggregatenot exceeding25 mm, aggregatecementratio not to exceed15:1, aggregategradationafter blendingto be as per table 600-1,cement content not to be less than 150 kg/ cum, optimummoisturecontent to be determined duringtriallengthconstruction,concretestrengthnottobelessthan10Mpaat7 days, mixedin a batchingplant, transportedto site, laid with a paverwith electronic sensor, compactingwith 8-10 tonnes vibratory roller, finishing and curing.)
256Cast in Situ Cement Concrete M20 kerb (Construction of cement concrete kerb with top and bottom width 115 and 165 mm respectively, 250 mm high in M 20 grade PCC on M-10 grade foundation 150 mm thick, foundation having 50 mm projection beyond kerb stone, kerb stone laid with kerb laying machine, foundation concrete laid manually, all complete as per clause 408)
257Using Concrete Batching and Mixing Plant
258Retro-reflectorisedTrafficsigns(Providingandfixingofretro-reflectorisedcautionary, mandatoryandinformatorysignasperIRC:67madeofencapsulatedlenstypereflective sheeting vide clause 801.3, fixed over aluminium sheeting, 1.5 mm thick supported on a mild steel angle iron post 75 mm x 75 mm x 6 mm firmly fixed to the ground by means of properly designed foundation with M15 grade cement concrete 45 cm x 45 cm x 60 cm, 60 cm below ground level as per approved drawing)
25990 cm equilateral triangle
26060 cm equilateral triangle
26160 cm circular
26280 mm x 60 mm rectangular
26360 cm x 45 cm rectangular
26460 cm x 60 cm square
26590 cm high octagon
266DirectionandPlaceIdentificationsignsupto0.9sqmsizeboard.(Providinganderecting direction and place identification retro-reflectorised sign asper IRC:67madeof encapsulated lens type reflective sheeting vide clause 801.3, fixed over aluminium sheeting, 2 mm thick with area not exceeding 0.9 sqm supported on a mild steel single angle iron post 75 x 75 x 6 mm firmly fixed to the ground by means of properly designed foundation with M15 grade cement concrete 45 x 45 x 60 cm, 60 cm below ground level as per approved drawing)
267Direction and Place Identification signs with size more than 0.9 sqm size board. (Providing and erecting direction and place identification retro- reflectorised sign asper IRC :67 made of encapsulated lens type reflective sheeting vide clause 801.3, fixed over aluminium sheeting, 2 mm thick with area exceeding 0.9 sqm supported on a mild steel angle iron post 75 mm x 75 mm x 6 mm, 2 Nos. firmly fixed to the ground by means of properly designed foundation with M15gradecementconcrete45cmx45cmx60cm,60cmbelowgroundlevelasper approved drawing)
268Overhead Signs (Providing and erecting overhead signs with a corrosion resistant aluminium alloy sheet reflectorised with high intensity retro-reflective sheeting of encapsulated lense type with vertical and lateral clearance given in clause 802.2 and 802.3 and installed as per clause 802.7overadesignedsupportsystemofaluminiumalloyorgalvanisedsteeltrestlesand trusses of sections and type as per structural design requirements and approved plans)
269Truss and Vertical Support
270Aluminium alloy plate for over head sign
271Painting Two Coats on New Concrete Surfaces (Painting two coats after filling the surface with synthetic enamel paint in all shades on new plastered concrete surfaces)
272Painting on Steel Surfaces (Providing and applying two coats of ready mix paint of approved brand on steel surface after through cleaning of surface to give an even shade)
273Road Markingwith Hot Applied ThermoplasticCompound with Reflectorising Glass Beads on Bituminous Surface (Providing and laying of hot applied thermoplastic compound 2.5 mm thick including reflectorising glass beads @ 250 gms per sqm area, thickness of 2.5 mm is exclusive of surface applied glass beads as per IRC:35 .The finished surface to be level, uniform and free from streaks and holes.)
274Kilo Metre Stone (Reinforced cement concrete M15grade kilometre stone of standard design as per IRC:8-1980, fixing in position including painting and printing etc)
275Ordinary Kilometer stone (Precast)
276RoadDelineators(Supplyingandinstallationofdelineators(roadwayindicators,hazard markers, object markers), 80-100 cm high above ground level, painted black and white in 15 cm wide stripes, fitted with 80 x 100 mm rectangular or 75 mm dia circular reflectorised panels at the top, buried or pressed into the ground and confirming toIRC-79 and the drawings.)
277Reinforced Cement Concrete Crash Barrier (Provision of an Reinforced cement concrete crash barrier at the edges of the road, approaches to bridge structures and medians, constructed with M-20 grade concrete with HYSD reinforcement conforming to IRC:21 and dowel bars 25 mm dia, 450 mm long at expansion joints filled with pre-moulded asphalt filler board, keyed to the structure on which it is built and installed as per design given in the enclosure to MOST circular No.RW/NH-33022/1/94-DOIIIdated24June1994asperdimensionsintheapproved drawing and at locations directed by the Engineer, all as specified)
278M 20 grade concrete
279Metal Beam Crash Barrier
280Type - A, "W" : Metal Beam Crash Barrier (Providing and erecting a "W" metal beam crash barrier comprising of 3 mm thick corrugated sheet metal beam rail, 70 cm above road/ground level, fixed on ISMC series channel vertical post, 150 x 75 x 5 mm spaced 2 m centre to centre, 1.8 m high, 1.1 m below ground/road level, all steel parts and fitments to be galvanised by hot dip process, all fittings to conform to IS:1367 and IS:1364, metal beam rail to be fixed on the vertical post with a spacer of channel section 150 x 75 x 5 mm, 330 mm long complete as per clause 810)
281Type - B, "THRIE" : Metal Beam Crash Barrier (Providing and erecting a "Thrie" metal beam crashbarriercomprisingof3mmthickcorrugatedsheetmetalbeamrail,85cmabove road/ground level, fixed on ISMC series channel vertical post, 150 x 75 x 5 mm spaced 2 m centre to centre, 2 m high with 1.15 m below ground level, all steel parts and fitments to be galvanised by hot dip process, all fittings to conform to IS:1367 and IS:1364, metal beam rail to be fixed on the vertical post with a space of channel section 150 x 75 x 5 mm, 546 mm long complete as per clause 810)
282FlexibleCrashBarrier,WireRopeSafetyBarrier(Providinganderectingawireropesafety barrier with vertical posts of medium weight RS Joist (ISMB series) 100 mm x 75 mm (11.50 kg/m), 1.50 m long 0.85 m above ground and 0.65 m below ground level, split at the bottom for better grip, embedded in M 15 grade cement concrete 450 x 450 x 450 mm, 1.50 m center to center and with 4 horizontal steel wire rope 40 mm dia and anchored at terminal posts 15 m apart. Terminal post to be embedded in M 15 gradecementconcretefoundation2400 x 450 x 900 mm (depth), strengthened by a strut of RS joist 100 x 75 mm, 2 m long at 450 inclination and a tie100x8mm,1.50mlongatthebottom,allembeddedinfoundationconcreteasper approved design and drawing, rate excluding excavation and cement concrete.)
283SpreadingofSludgeFarmYardManureor/andgoodEarth(Spreadingofsludgefarmyard manure or/ and good earth in required thickness (cost of sludge, farm- yard manure or/and good earth to be paid for separately))
284Grassing with " Doobs" Grass (Grassing with "Doobs" grass including watering and maintenance of the lawn for 30 days or more till the grass forms a thick lawn free from weeds and fit for moving including supplying good earth if needed)
285In rows 15 cm apart in either direction
286In rows 7.5 cm apart in either direction
287Making Lawns including Ploughing and Dragging with "Swagha" Breaking of Clod (Making lawns including ploughing and breaking of clod,removal of rubbish,dressing and supplying doobs grassrootsandplantingat15cmapart, includingsupplyingandspreadingoffarmyard manure at rate of 0.18 cum per 100 sqm)
288Maintenance of Lawns or Turfing of Slopes (Maintenance of lawns or Turfing of slopes (rough grassing) for a period of one year including watering etc)
289TurfingLawnswithFineGrassingincludingPloughing, Dressing(Turfinglawnswithfine grassingincludingploughing,dressingincludingbreakingofclods,removalofrubbish, dressing and supplying doobs grass roots at 10 cm apart,including supplying and spreading of farm yard manure at rate of0.6 cum per 100 sqm)
290Maintenance of Lawns with Fine Grassing for the First Year
291a) PlantingPermanentHedgesincludingDiggingofTrenches(Plantingpermanent hedges including digging of trenches,60 cm wide and 45 cm deep,refilling the excavated earth mixed with farmyard manure, supplied at the rate of 4.65 cum per 100 metres and supplying and planting hedge plants at 30 cm apart)
292Maintenance of Hedge for one year
293a)Planting Flowering Plants and Shrubs in Central Verge
294Maintenance of Flowering Plants and Shrubs in Central Verge for one Year
295PlantingofTreesandtheirMaintenanceforoneYear (Plantingoftreesbytheroadside (Avenue trees) in 0.60 m dia holes,1 m deep dug in the ground,mixing the soil with decayed farm yard/sludge mannure,planting the saplings,backfilling the trench,watering,fixing the tree guard and maintaining the plants for one year)
296Renovation Lawns including, Weeding, Forking the Ground, TopDressing with Forked Soil (Renovationlawnsincluding, weeding, forkingtheground, topdressingwithforkedsoil, watering and maintenance the lawns,for 30 days or more,till the grass forms a thick lawn, free from weeds,and fit for moving and disposal of rubbish as directed,including supplying good earth,if needed but excluding the cost of well decayed farm yard manure)
297Supply at Site Well Decayed Farm Yard Manure (Supply at site of work well decayed farm yard manure,from any available source, approved by the engineer in charge including screening and stacking)
298Wrought Iron and Mild Steel Welded Work (Wrought iron and mild steel welded work) (using angles, square bars,tees and channel grills, grating frames, gates and tree guards of any size and design etc. including cost of screens and welding rods or bolts and nuts complete fixed inpositionbutwithoutthecostofexcavationandconcreteforfixingwhichwillbepaid separately)
299Tree Guard with MS Angle Iron and Steel Wire (Providing and fixing tree guard 0.60 metre square,2.00 metre high fabricated with MS angle iron 30 x 30 x 3 mm,MS iron 25 x 3 mm and steel wire3 mm dia welded and fabricated as per design in two halves bolted together)
300Water proofing for Old and New Roof Slab:- Providing and laying water proofing treatment on roof slab by applying two Component, factory designed, ready to use, acrylic modified flexible material applied with, brush, roller or spray for water proofing coating as per manufacturer specifications with following steps: (a surface preparation-Providing and cleaning of concrete surface to remove dust, oil, greaseincluding removal of existing loose paint / coating, and cement laitance by cleaning with compressed air & water jet including all materials, labour, tools complete. Ponding test to be done after plugging all outlets and to be checked from soffit to identify seepage, leakage. On identification of seepage, cement grouting to be done with non shrink expanding admixture of Sika India Pvt Ltd /MYK Schomberg/Dr Fixit/Fosroc or equivallent Providing and reparing of all comers and joints such as those between the parapet wall and the roof slab etc shall be chamfered with 150 mm X 150 mm fillet of mortar (Cement: sand-1:4) admixed with acrylic polymer of Sika Fosroc/MYK Schomberg Fixit or equivalent. Before chamfering a prime coat shall be given with the slurry ofacrylic polymer. Repairing surface irregularities, damaged concrete in base slab, dead cracks if any, with an acrylic polymer modified repair mortar including a coat of bonding agent of the same with cement slurry including all material, labour, tools complete. (b)1st Coat Apply 1st coat of two component acrylic modified, ready to use, flexible cementitious material on surface saturated dry roof and inside wall of Parapet wall upto 600 mm by brush or roiler After 1st coat of application, 45 gsm of Fibre glass cloth to lay when the first layer is still green. 1st coat should be applied @1.50 kg / Samt/coat. For the purpose of measurement the entire treated surface will be measured." (c) 2nd Coat-To apply the 2nd coat of two component acrylic modified, ready to use, flexible cementitious material right angle to the 1st coat over the glass fibre laid surface 2nd coat should be applied @0.7 kg/Samticoat For the purpose of measurement the entire treated surface will be measured After three days of drying the 2nd coat, the rail water outlets to be plugged and ponding test to be done for 48 hours to identify seepage, leakage from soffit and if found necessary rectification to be done as per satisfaction of EIC. The waterproof coating to be protected from damage before screed over it. Waterproofing Brand- Sika Topseal 109hi/Fosroc Brushbond RFX/Dr Foxit Pidiffin 2K/MYK Aquafin TG Product Performance - Chemical Base Part A Acrylic copolymer, Part B Specially graded cementitious powder- Density 1.6 kg/l (mixed density) at +27°C Tensile Strength -2 Nimm2 after 28 days (with Fibre cloth) (According to ASTM D 2370) Pullout Bond Strength -2 N/mm2 (concrete failure) (According to ISO 4624) Slant-Shear Bond Strength -4 N/mm2 (According to FIP 5.15) Elongation at Break -35% without Fibre Cloth and 20% with Fibre Cloth (According to ASTM D 2370) (d) Protection of treated surface with PCC-The treated surface should be covered with 25mm/ 50mm PCC of M-20 grade(1:1.5:3) with proper slope (1:120) towards the rain outlets in alternate panels of 2 mt x 2mt keeping 6 mm gap between the panel joint. Integral water proofing admixture conforming to IS 2645 @of 100 ml per bag of of cement to be added in the screed concrete(paid separately for this items) All corners shall be chamfered with 150mm x 150 mm fillet. The rain water outlets shall be just leveled with the screed concrete to ensure smooth discharge of water the peripheral gaps between pvc pipe outlet and concrete surface should be packed property with rich concrete and the peripheral mouth to be sealed with moisture insensitive epoxy putty of Sika India Pvt. Ltd. /MYK Schomberg/Dr Fixt/Fosroc For the purpose of measurement the entire treated surface will be measured." (e)Groove of PCC surface should be filled with Polysulphide Sealant (Paid Separately). Brand- Sika India Pvt Ltd./MYK Schomberg/Dr Foxit/Fosroc Warranty for five years.
301Providing and fixing at all height false ceiling of 4mm thick phenol bonded Bamboo Mat board (595x595mm) conforming to IS:139581994 including providing and fixing of frame work made of GI angle 25x25x0.4 mm thick all around suitably fixed to wall with the help of dash fastener and hanger frame (600x600 c/c) made GI slotted Tee having powder coating on bottom side (30x25x0.3 mm thick for main member & 25x25x0.3 mm for cross member) connected to ceiling with 2.64mm GI wire and anchor fastener at every junction and also including cost of making openings for light fittings, grills, diffusers, cut outs made with frame of perimeter channels suitably fixed all complete as per direction of Engineer-in-charge.
302Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid door/window/Ceosetory windows & other Frames/Chowkhat comprising of virgin PVC polymer of K value 5860 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms)fabricated with miter joints after applying PVC solvent cement and screwed with full body threadedstar headed SS screws having minimum frame density of 750 kg/ cum, screw withdrawal strength of 2200 N (Face) & 1100 N (Edge), minimum compressive strength of 58 N/mm2, modulus of elasticity 900 N/mm2 and resistance to spread offlame of Class Acategory with property of being termite/borer proof, water/moisture proof and fire retardant and fixed in position with M.S hold fast/lugs/SS dash fasteners of required dia and lengthcomplete as per direction of Engineer-In- Charge. (M.S hold fast/lugs or SS dash fasteners shall be paid for separately).
303Note: For WPC solid door/window frames, minus 5mm tolerance in dimensions i.edepth and width of profile shall be acceptable. Variation in profile dimensions on plus side shall be acceptable but no extra payment on this account shall be made.
304Frame size 50 x 100 mm
305Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid plain flush door shutter of required size comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium carbonate andnatural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) & 900 N (Edge), minimumcompressive strength50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread offlame of Class Acategory with property of being termite/ borer proof, water/moisture proof and fire retardant and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In- Charge. (Note: stainless steel butt hinges and necessary S.S screws shall be paid separately)
30635 mm thick
307CARRIAGE OF MATERIAL
308Stone Chipps /stone aggregate (20 km )
309Coarse Sand ( 20 km)
310Brick (8 km) (1 K + 7 P)
311Fly Ash Brick (8 km )
312Earth( 5 km)
313PLUMBING WORK
314SUB HEAD -I : SANITARY FIXTURES & FITTINGS
315Supplying, fitting and fixing vitreous white glazed earthen ware I.W.C. Of parry Hindustan or any other I.S.S. Approved make with 100mm H.C.I. "P" trap 15liters C.I. Pull and let go flushing cistern of names or other I.S.S. Equipment make, complete with all fittings, C.I. or C.C. brackets 32mm alkathene/P.V.C. telescopic flush, pipe about 2 M long with one brass coupling and clamps G.I. chain and pull including supplying and fixing a pert of vitreous white glazed earthenwere were footrest to be fixed in floor 15mm C.I. body brass spindle stope cock of weight not less than 50grms, 15mm P.V.C. connection pipe 450mm long and the exposed pipe and cistern with two coats of approved paint over a coat of red oxide primer etc. all complete as per specification and direction of Engineer - in - charge .
316580 mm Long
317With 15.0 litre High Level CI Cistern
318Supplying fitting and fixing 40mm high vitreous white glazed earthen E.W.C. With "P" trap of parry hindustan or any other approved I.S.S. Make including supplying and fixing 15 litres C.I. Mosquito proof low down flushing cistern of approved make with complete fittings With C.I. handle and R.S. or bracket with telescope flush pipe with brass coupling and plumbers joints spindle stop cock of approved uality weight not less than 450grams 15mm P.V.C. alkathene pipe 45cm long with brass coupling at both ends and white/ black plastic solid state seal and lead of commander/cuckoo or other I.S.S. make with hinges or screws etc. painting pipe and cistern etc. with 2 coats of approved pain over a coat of red oxide priming all complete as per specification and direction of Engineer - in - charge .
319With P Trap
32012.5 Litre Low level CI Cistern
321Supplying fitting and fixing vitreous white glazed earthen ware wash hand basin of parry or Hindustan or any other I.S.S. Approved make supported on painted C.I. Or R.S. Bracket 32mm C.I. Brass waste, 15 mm dia C.I. Body brass spindle stop cock of approved quality of weight not less than 350 grams, 32mm P.V.C. waste pipe 750mm long with brass coupling at one end and making plunber joints etc. all complete as per specification and direction of E/I.
322Providing and placing on terrace ( at all floor levels ) polythylene water storagetank of approved brand and manufacture with cover and suitable locking system in double layer Conforming to IS : 12701 -1996 with Latest Revisionand making necessary holes for inlet,out let and over flow pipes but without fitting and the base support for tank .
323Providing and fixing Stainless Steel AISI 304 (18/8) kitchen sink as per IS: 13983 with C.I. brackets and stainless steel plug 40 mm, including painting offittings and brackets,cuttingandmakinggoodthe walls wherever required
324Kitchen sink with drain board
325510x1040 mm bowl depth 250 mm
326Providing and Fixing White Viterous China battery based infraredsensor operated urinal of approx. size 610 x 390 x 370 mm having pre and post flushing with water ( 250 ml and 500 ml consumption ) , having water inlet from back side , including fixing to wall with suitable brackets all as per manufacturer specification and direction of engineer - in - charge .
327Providing and Fixing stone slab with table rubbed , edges rounded and polished of size 75 x 50 cm deep and 1.8 cm thick , fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 ( 1 Cement : 2 Coarse Sand : 4 Graded stone finished smooth aggregate 6 mm nominal sizes ) as per direction of engineer - in - charge .
328Granite Stone of approved shade
329Providing and Fixing CP brass 32 mm size Bottle Trap of approved quality and make as per the direction of Engineer - in- charge .
330Providing & fixing ofWaste pipe forSinks including pvc waste fittings complete.
331Flexible Pipe
33240 mm dia
333Providing & fixingtoilet paper holder:
334C.P.brass
335Providing & fixing PTMT liquid soap container 109mm wide,125mm high and 112mm distance from wall of standard shape with bracket of the same materialswith snap fittings of approved quality and colour. weighing not less than 105 gms.
336Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour,weighing not less than 88 gms.
337Providing & fixing PTMT towel rail complete with brackets fixed to wooden cleats with C.P brass screws with concealed fitting arangement of approved quality and colour.
338600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190 gram.
339Providing and fixing C.P. brass bib cock of approved qualityconforming to IS : 8931 .
34015 mm nominal bore
341Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.
34215 mm nominal bore
343Providing and fixing unplasticised P.V.C. connection pipe with PTMT Nuts, collar and bush of approved quality and colour.
34415 mm nominal bore with 45cm length
345Providing and fixing 600x450 mm beveled edge mirror of superior glass ( of approved quality ) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P brass screws and washers complete .
346Providing and fixing C.P. Brass Angle Valve for basin mixer and geyser points of approved quality conforming to IS : 8931
34715 mm nominal bore
348Providing & fixing PTMT soap dish Holder having length of 138mm,breadth 102mm, height of 75mm with concealed fittingarrangements.Weighing not less than 106gms.
349Providing and fixing CP brass shower rose with 15 or 20 mm inlet
350100 mm diameter
351Providing & Fixing CP brass single lever telephonic wall mixer of quality and make as approved by engineer - in - charge .
35215 mm nominal dia
353SOIL , WASTE VENT AND RAIN WATER PIPE
354Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement:2 coarse sand:4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 mx1 mx400 micron, finished 12 mm cement plaster 1:3 (1 cement:3 coarse sand) and a coat of neat cement rounding the edges and making and finishing the outlet complete .
355Providing and Fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams .
356Providing and Fixing 100 mm diameter and 60 cm long rain water spout in cement mortar 1:4 ( 1 Cement : 4 Fine Sand )
357Stone ware Spout
358INTERNAL WATER SUPPLY
359Providing and fixing 3 layer PP-R (Poly propylene Random copolymer) pipes confirming to IS 15801, UV stabilized & anti - microbial fusion welded, having thermal stability for hot & cold water supply, including all PP - R plain & brass threaded polypropylene random fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes testing of joints complete as per direction of Engineer-in-Charge. Internal Exposed on walls
360PN - 16 Pipe, 20mm OD (SDR-7.4)
361PN - 16 Pipe, 25mm OD (SDR-7.4)
362PN - 16 Pipe, 32mm OD (SDR-7.4)
363PN - 16 Pipe,40mm OD (SDR-7.4)
364PN - 16 Pipe,50mm OD (SDR-7.4)
365Providing and fixing 3 layer PP-R (Poly propylene Random copolymer) pipes confirming to IS:15801, UV stabilized & anti - microbial fusion welded, having thermal stability for hot & cold water supply, including all PP - R plain & brass threaded polypropylene random fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work,including cutting chases and making good the wall etc. Concealed work, including cutting chases and making good the walls etc.
366PN - 16 Pipe, 20mm OD (SDR-7.4)
367PN - 16 Pipe, 25mm OD (SDR-7.4)
368PN - 16 Pipe, 32mm OD (SDR-7.4)
369Providing and fixing G.I. Pipes complete with G.I. fittingsand clamps,including cutting and making good the walls etc Internal work - Exposed on wall
37040 mm dia nominal bore
37150 mm dia nominal bore
372Painting G.I. pipes and fittings with synthetic enamel white paint with two coats over a ready mixed priming coat, both of approved quality for new work :
37340 mm dia nominal bore
37450 mm dia nominal bore
375EXTERNALWATER SUPPLY
376Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. (external work)
37740mm dia nominal bore
37850mm dia nominal bore
37965mm dia nominal bore
38080mm dia nominal bore
381Providing and fixing gunmetal gate valve with CI wheel of approved quality (screwed end).
38225 mm dia nominal bore
38332 mm dia nominal bore
38440 mm dia nominal bore
38550 mm dia nominal bore
38665 mm dia nominal bore
38780 mm dia nominal bore
388Providing and fixing C.I. sluice valves (with cap) complete with bolts, nuts, rubber insertions etc. (the tail pieces if required will be paid separately):
389100 mm diameterClass II
390150 mm diameterClass II
391Constructing brick masonry chamber 30x30x50cms inside with 1st class brick work in cement mortar 1:5 (1 cement : 5 fine sand) for stop cock withCI surface box 100x100x75mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1cement : 2 coarse sand :4 graded stone aggregate 20mm nominal size)necessary excavation foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size) and inside plastering with cement mortar 1:3 (1 cement 3 coarse sand) 12mm thick finished with a floating coat of neat cement complete as per standard design.
392With common burnt clay F.P.S.(non modular) bricks of class designation 100A
393Constructing masonry Chamber 90X90X100 cm, inside with 75 class designation brick work in cement mortar 1:4 (1 cement: 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with channel lid and RCC top slab 1:2:4 mix (1 cement: 2 coarse sand: 4 graded stone sggregate 20 mm nominal size) necessary excavation foundation concrete 1:5:10 (1 cement : 5 fine sand: 10 graded stone aggregate 40 mm nominal size) and inside plastering with cement mortar 1:3 (1 cement: 3 coarse sand) 12 mm thick finished with a floating coat of neat cement complete as per standard design:
394With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
395Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality.
39640mm dia nominal bore
39750mm dia nominal bore
39865mm dia nominal bore
39980mm dia nominal bore
400Providing & fixing enclosed type water meter ( bulk type ) conforming to IS : 2373 and tested by municipal board complete with nuts , bolts , rubber insertion etc . ( The tail piece if required will be paid saperately )
40180 mm dia nominal bore
402Providing & Laying D.I specials of class K-12 suitable for push on jointing as per IS : 9523 .
403up to 600 mm dia
404Providing and laying S&S centrifugally cast (spun) / Ductile iron pipes conforming to IS :8329
405100 mm dia Ductile iron class K-9 pipes
406150 mm dia Ductile iron class K-9 pipes
407Providing push on joints to centrifugally cast (spun ) iron pipes or Ductile iron pipes including testing of joints and the cost of rubber gasket
408100 mm diameter pipe
409150 mm diameter pipe
410Constructing masonry Chamber 60x60x75 cm inside, in brick work in cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I. surface box 100x100 x75 mm (inside) with hinged cover fixed in cement concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), i/c necessary excavation, foundation concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate 40mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat cement complete as per standard design :
411With common burnt clay F.P.S.(non modular) bricks of class designation 100A
412EXTERNAL SEWERAGE & DRAINAGE SYSTEM
413Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand :10 graded stone aggregate 40 mm nominal size) up to haunches of S.W.pipes including bed concrete as per standard design :
414150 mm dia
415200 mm dia
416250 mm dia
417300 mm dia
418Providing and fixing square-mouth S.W. gully trap grade "A" complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300x300 mm size ( inside ) the weightof cover to be not less than 4.50 kg and frame to be not less than 2.70 Kgas per standard design :
419180x150 mm size P type With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
420Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) :
421With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
422Inside size 120x90 cm and 90 cm deep including C.I. cover with frame (medium duty) 500 mm internal diameter, total weight of cover and frame to be not less than 116 kg (weight of cover 58 kg and weight of frame 58 kg) :
423With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
424ExtraDepth For Manhole Size 90x80 cm With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
425ExtraDepth For Manhole Size 90x120 cm With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
426Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910, on 12 mm dia steel bar conforming to IS:1786, having minimum cross section as 23 mmx25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequeringesides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per pecifications and having manufacture’s permanent identification mark to be visible even after fixing,including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design.
427Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand ) with precast R.C.C. vertical grating complete as per standard design : With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
428Excavating trenches of required width for pipes cables etc including excavation for sockets, and dressing of sides, ramming of bottoms, depth upto 1.5 m ncluding getting out the excavated soil , and then returning the soil as required , in layers not exceeding 20 cm in depth including consolidating each deposited layer by ramming, watering, etc. and disposing of surplus excavated soil as directed , within a lead of 50 m. All kind of soil
429Pipes, cables etc. exceeding 80 mm dia . But not exceeding 300mm dia.
430Pipes, cables etc. exceeding 300 mm dia . But not exceeding 600mm dia.
431"Extra for excavating trenches for pipes, cables etc.in all kinds of soil for depth exceeding 1.5 m , but not exceeding 3 m.(Rate is over corresponding basic item for depth upto 1.5 meter.) All kind of soil
432Pipes, cables etc. exceeding 80 mm dia . But not exceeding 300mm dia.
433Pipes, cables etc. exceeding 300 mm dia . But not exceeding 600mm dia.
434HYDT of drilling 200 mm x 165 mm x 125 meter deep bore well in all kinds of soil and rock in rural area for installation of pump set with hydraulic DTHRig Machine , all complete including Supplying all material , tools , drilling rig , Air Compressor and equipments , as well as fuel , lubricants and cost of transportation of Rig machine and other Vehicles up to the site ( Basic rate )
435(a) From 0.00 M to 50.00 M below G.L.
436(b) From 51.0 M to125.00 M
437(c) From126.0 M to150.00 M
438Supply of 200 mm dia x 3.0 m Long UPVC Casing Pipe Conforming to IS : 12818 : 2016 ( CML No. 5543459 ) Latest Revision including carriage ( basic rate )
439Supplying All Tools , Equipments , Labour and doing washing , flushing and development of drilled tubewell to give clean and clear water all complete as per direction of Engineer - in - charge . ( Basic Rate )
440Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of: 200 mm dia
441Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete. 200 mm clamp
442Supplying 100mm dis submersible pump sets confirming to 8034 and motor confirming to IS 9283 pump shall be suitable for various delivery head and discharge with stainless steel pump shaft and polypropylene/noryl impeller. Motor suitable for working on 415 + 10, 3HP, 50 Hz, AC supply with cable guard, thurst carbon/fiber bearing to withstand entire hydraulic thurst, water proof winding shall be provided. The pump set shall be suitable for diret coupling Pump shall have suitable outlet as per manufacturers design. Anti thurst stream lined non return valve shall be provided with pump, 3 meter submersible copper conductor cable in single/double run shall be provided with each pump.Submersible pump set 100mm dia (with Polypropylene/Noryl Impeller) up to 20 stages 2 HP
443Supplying Fully automatic star delta starter to operate induction motor working on 415 Volts , 3 Phase 50 HZ with no volt coil , over load element , ON / OFF push button with necessary materials and connected to supply etc complete starter with original sheet encloser FASD Starter
44410 HP
445Supplying fitting and fixing 3 crore 4 sqmm Flat copper submersible cable FINOLEX / HEVELS make including all taxes ,royalty etcall complete job as per direction of E/I.
446Supplying all tools equipments and labour lowering 32 mm dia medium quality GI Pipe in drilled tubewell in 3 mtr length all complete as per direction of engineer - in - charge including carriage of materials ( Basic Rate )
447Providing 1.5mm cement punning including curing carriage of water with all leads and lifts as per building specification and direction of E/I.
448Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.19.6.2-150 mm dia
449Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge 100 mm nominal size dia
450Supplying, filling, spreading & leveling stone boulders of size range5 cm to 20 cm, in recharge pit, in the required thickness, for allleads & lifts, all complete as per direction of Engineer-in-charge 22 /7(10.0x10.0)/4=78.571 total
451Supplying, filling, spreading & leveling gravels of size range 5 mm to10 mm, in the recharge pit, over the existing layer of boulders, inrequired thickness, for all leads & lifts, all complete as per directionof Engineer-in-charge22 /7(10.0x10.0)/4=78.571 total
452Supplying, filling, spreading & leveling coarse sand of size range 1.5 mmto 2 mm in recharge pit, in required thickness over gravel layer, for all leads& lifts, all complete as per direction of Engineer -in-charge 22 /7(10.0x10.0)/4=78.571 total
453DT : Basic rates for 125/115mm dia drilled Tube-well for drilling in all kinds of soil and rock for installation of hand pump with DTH rig Machine all complete including supplying all materials, labours, tools, drilling, rigs, air compressor and equipments as well as fuel lubricant, for making 125/115 mm dia boring etc. and cost of transporting rig machine and other vehicle up to site of work as per specification and direction of E/I.. (Basic Rates) Drilling upto 30 mtr. Depth below G.L. in Rural Areatotal
454Carriage of material
455Stone metal lead = 22 km
456ELECTRICAL
457Items
458Wiring for light point/ fan ponit/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, with modular switch, modular plate, suitable size Gl box etc.as required.
459Group C
460Wiring for circuit/ submain wiring along with earth wire with the following sizes PVC insulated copper conductor, single core cable in surface / recessed PVC conduit as required.
4612 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
4622 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
4632 x 10 sq. mm + 1 x 6 sq.mm earth wire
4642 x 16 sq. mm + 1 x 6 sq.mm earth wire
4654 X 6 sq. mm + 2 X 6 sq. mm earth wire
4664 X 10 sq. mm + 2 X 6 sq. mm earth wire
4674 X 16 sq. mm + 2 X 6 sq. mm earth wire
468Supplying and drawing following size of FR PVC insulated copper conductor, single core cable in the existing surface / recessed PVC conduit as required.
4696 x 1.5 sq. mm (4 X 1.5 sq.mm + 2 X 1.5 sq. mm)
4709 x 1.5 sq. mm (6 X 1.5 sq.mm + 3 X 1.5 sq. mm)
471Wiring for light/ power plug with 2 X 4 sq.mm FR PVC insulated copper conductor single core cable in surface/ recesed PVC conduit along with 1 No. 4 sq. mm FR PVC insulated copper conductor single core cable for loop earthing as required.
472Wiring for light/ power plug with 4 X 4 sq.mm FR PVC insulated copper conductor single core cable in surface/ recessed PVC conduit along with 2 Nos. 4 sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required
473Supplying and fixing following size/modules G.I. box along with modular base & cover plate for modular switches in recess etc as required. 1 or 2 Module (75mmX75mm) (for Telephone, Television, Fan reguletor)
474Supplying and drawing following pair, 0.5 sq.mm FR PVC insulated copper conductor, unarmoured telephone cable in the existing surface / recessed PVC conduit as required. 2 Pair
475Supplying and drawing co-axial cable RG-6 grade copper conductor, PE insulated with PVC sheath in the existing surface/recessed PVC conduit as required.
476Supplying and fixing of following sizes of PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required.
47725 mm ( for TV, Telephone, & circuit wiring)
47832 mm ( for TV, Telephone, & circuit wiring)
479Supplying and fixing suitable size G.I. box with modular plate and cover in front on surface or in recess including providing and fixing 5 pin, 5/6 amps modular socket outlet and 5/6 amps modular type switch connection, painting etc, as required.
480Supplying and fixing suitable size of GI box with modular plate and cover in front on surface or in recess including poviding and fixing 6 pin, 15/16 amps modular socket outlet and 15 / 16 amps modular switch. connection, painting etc, as required.
481Supplying & fixing suitable size GI box wih modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required. For AC
482Supplying and fixing following modular type switch/ socket on the existing modular plate and switch box including connection but excluding modular plate etc. as required.
483Telephone socket outlet
484TV antenna socket outlet
485Supply, installation, testing & commissioning of Bulk Head Luminare delivering an initial system lumen of 700 lumens & the luminaire shall be with system efficacy = 70 lm / W. Housing: Die Cast Aluminium. IP65 , Diffuser : OPAL Polycarbonate. The operating CCT shall be 5700K with CRI of =70. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD = 20% & PF = 0.95, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79& LM80 issued by LED manufacture along with Photo Biological Safety Standard. (cat no.LW07-141-XXX-57-XX)
486Supply, installation, testing & commissioning of 18W Surface mounted Round LED Downlighter delivering an initial system lumen of 1527 lumens & the luminaire shall be with system efficacy = 84 lm / W. Housing: Die Cast Aluminium. IP20 , Optics:PMMA LGP/Polysterene Diffuser. The operating CCT shall be 6000K with CRI of =80. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD = 20% & PF = 0.95, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79& LM80 issued by LED manufacture along with Photo Biological Safety Standard. (cat no.LD80-171-XXX-60-SM)
487Supply, installation, testing & commissioning of 20/22 W LED Tube Light 4ftLinear LED luminaire delivering an initial system lumen of 4000 lumens & the luminaire shall be with system efficacy = 100 lm / W. The luminaire Housing shall be made of extruded Aluminium & the diffuser shall be of polycarbonate/PMMA. The operating CCT shall be 6500K with CRI of =80. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD = 20% & PF = 0.95 , 50,000 Hrs LED Life with L70 Criteria, IP20. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79& LM80 issued by LED manufacture along with Photo Biological Safety Standard.(cat no.LL22-511-XXX-65-XX)
488Supply, installation, testing & commissioning of 36W Surface/ Suspended 500mm RoundLed Fixture delivering an initial system lumen of 3230 lumens & the luminaire shall be with system efficacy = 95 lm / W. Housing: CRCA. IP20 , Optics:HET Diffuser. The operating CCT shall be 5700K with CRI of =80. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD = 10% & PF = 0.95, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79& LM80 issued by LED manufacture along with Photo Biological Safety Standard.(cat no.LM71-441-XXX-57-XX)
489Supply, Installation, testing and commissioning of 5W LED mirror light shall be 6500K. Housing shall be synthetic chrome/Engineering plastic with IP20 protection having lumen output of min 900 lumes having minimum system efficacy of 90lm/w & THD<25%. . complying to above specifications. . Wipro Make LL20-111-XXX-65NE3or equivalent as specified in the approved list of make.)
490Supply, installation, testing & commissioning of 15W Surface mounted Square Led Downlighter delivering an initial system lumen of 1350 lumens & the luminaire shall be with system efficacy = 90 lm / W. Housing: Die Cast Aluminium. IP20 , Optics:PMMA LGP/Polysterene Diffuser. The operating CCT shall be 5000K with CRI of =80. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD = 20% & PF = 0.95, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79& LM80 issued by LED manufacture along with Photo Biological Safety Standard.
491Supply, installation, testing & commissioning of 12W Surface mounted Round Led Downlighter delivering an initial system lumen of 1527 lumens & the luminaire shall be with system efficacy = 84 lm / W. Housing: Die Cast Aluminium. IP20 , Optics:PMMA LGP/Polysterene Diffuser. The operating CCT shall be 6000K with CRI of =80. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD = 20% & PF = 0.95, 50,000 Hrs LED Life with L70 Criteria. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79& LM80 issued by LED manufacture along with Photo Biological Safety Standard. (cat no.LD80-171-XXX-60-SM)
492SITC of following items Power Saver A.C. electric Ceiling fans, capacitor type with double ball bearing complete with 300 mm down rod, canopies, shackles, blades, but without regulator suitable for operation on 230 / 240 Volts, 50 Hz, single phase, A.C. supply etc. as reqd.
4931200mm fan ( BLDC )
494Supplying of 300 mm dia Exhaust fan (Ventilating Fans), complete with louvers mounting rings frame as reqd.
495Supplying and fixing of Stepped type electronic fan regulator on the existing modular plate & switch box including connections but excluding modular plate etc. as reqd.
496Installation, testing and commissioning of pre-wired, fluorecent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. direct on ceiling/ wall, including connection with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable and earthing etc. as required.
497Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm ) with 1.5 sq.mm FR PVC insulated, copper conductor, single core cable etc. as required.
498Installation of exhaust fan upto 450 mm. sweep in the existing opening, including making the hole to suit the size of the above fan, making good the damange, connection, testing, commissioning etc as required.
499Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
5008 way, double door
50112 way, double door
502Supplying and fixing following way, three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess complete with tinned copper busbar, neutral busbar, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted including earthing etc. as required. (But without MCB/ RCCB/ Isolator)
5036 way (4 + 18), Double door
5048 way (4 + 24), Double door
505Supplying and fixing following way TP&N MCB distribution board of 415 volts on surface/ recess complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted including earthing etc. as required.(But without MCB/ RCCB/ Isolator)
50612 Way , Double Door,Horizontal Type
507Supplying and fixing following rating, DP 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
50840 amps
509Supplying and fixing following rating, four pole,415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
51040 amps
51163 amps
512Supplying and fixing following rating, double pole,(Single phaseand neutral), 240volts residual current circuit breaker (RCCB), having a sensitivity current 30mA in the existing MCB DB complete with connection, testing and commissioning ets. As required.
51340 amps
51463 amps
515Supplying and fixing following rating, double pole, 240 volts, "C" series, miniature circuit breaker suitable for inductive loads in the existing MCB DB complete with connections, testing and commissioning etc. as required.
5166/32 amps, single pole
517Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
518EARTHING
519Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. as required. (but withoutcharcoal or coke and salt)
520Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode, as required.
521Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along as required.
522Providing and fixing MV Danger Notice Plate of 200 mm x 150 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides and with inscription in single red colour on front side as required.
523Providing and fixing HT danger notice plate of 250 mm x 200 mm, made of mild steel, at least 2 mm thick, and vitreous enamelled white on both sides and with inscription in single red colour on front side as required.
524Design, manufacture, supply, erection, testing & commissioning of following rating of DG Sets in Accoustic Enclosure, having self excited & self regulated 415 V, 3 Phase, 4-Wire, 50 Hz, 0.8 p.f. Alternator coupled with multi-cylinder, turbo-charged/ turbo-charged after cooled as called for, Diesel Engine capable to generate the power not less than the required BHP to achieve the alternator capacity as given below, with radiator Cooled, hospital type silencers and Electronic governer (G3 Governing System), DG set controller suitable for Auto Synchronization & Auto Load Sharing with microprocessor based Synchronization relay like Woodward/Dief/ Deepsea or equivalentincluding providing of Engine control panel, 24V batteries of suitable rating, battery-charger with battery leads, inbuilt oil fuel tank of capacity as per OEM standards and complete with all standard accessories & protection as required and as per specifications, including first filling of lube oil, fuel tank, providing common base plate, anti vibration pads, drip trays, foundation bolts, nuts, bolts, cable termination/adopter box sutiable to terminate upto 5 nos. of 3.5Cx300 sq.mm. XLPE cables as required for a complete installation including RCC/PCC foundation for DG set as per the structural detail for Dynamic Load submitted by the Vendor and approve by the Client. DG set should comply relevant Indian standards. DG shall have Remote Monitoring System.
525500 KVA (With Acoustic Enclosure)
526Supply, installation, Testing and commissioning of the following rating UPS as per specifications and complete in all respects. 80 KVAUPS3 phase (415 V + 15%) Volts input & 3 phase output (415 V + 1%), 50 Hz, IGBT based technology, Input harmonic Current THD <=3% typical at 100% load, ,<=6% maximum at 100% loadwith inbuilt Isolation Transformer and 30 minbattery backup for each UPS along with battery cabinet, Parallel card, BMS Port & communication card complete in all respect including supporting steel structure for UPS and Battery as required.Quotedprice shall be inclusiveofrequired rating single core copper conductor cable including terminations,connections ofUPS to batteries etc complete in all respect and as per direction of Engineer in Charge.
527MS Battery rack suitable for 40 to 50 UPS battery installation
52812V 150Ah sealed maintenance free (SMF) battery with 24 mounth replacement guaranty IS : 1652:1991
529laying of one number PVC Insulated and PVC shethed /XLPE power Cables of 1.1 KV grade of following size direct in ground including excavation,sand cushioningand protecting covering and refilling the trench etc as required.
530Up to 35 sqmm.
531Above35 sq mm and up to 95 sqmm.
532Above95 sq mm and up to 185 sqmm.
533Above185 sq mm and up to 400 sqmm.
534Laying and fixing of one no PVC insulated and PVC sheathed /XLPE power cable of 1.1 kV grade offollowing size on Cable tray as required.
535Up to 35 sqmm. (Clambed with 1mm thick saddle)
536Above35 sq mm and up to 95 sqmm. (Clambed with 25 x 3 mm thick MS Flat Clamp)
537Above 95 sq. mm and upto 185 sq. mm (clamped with 25/ 40x3mm MS flat clamp)
538Above185 sq mm and up to 400 sq mm.(Clambed with 25/40 x 3 mm thick MS Flat Clamp)
539Supply of following sizes of XLPE insulatedAluminum conductor strip/ wire Armoured, overall PVC sheathed 1.1 KV grade cables conforming to relevant IS-7098 Code and technical specifications.
5403 x 2.5 sq. mm
5413 x 4 sq. mm
5424 x 4 sq. mm
5434 x 6 sq. mm
5444 x 10 sq. mm
5454 x 16 sq. mm
5464 x 25 sq. mm
5473½ x 35 sq. mm
5483½ x 50 sq. mm
5493½ x 70 sq. mm
5503½ x 95 sq. mm
5513½ x 120 sq. mm
5523½ x 150 sq. mm
5533½ x 185 sq. mm
5543½ x 240 sq. mm
5553½ x 300 sq. mm
556Providing and fixing 25 mm X 5 mm Copper strip in 40 mm dia G.I. pipe from earth electrode, as required.
557Providing and fixing 25 mm X 5 mm Copper strip on surface or in recess for connections etc. as required.
558Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
559Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing etc. as required.
560Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. as required. (but withcharcoal or coke and salt)
561Earthing with Copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. as required. (but withcharcoal or coke and salt)
562Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
563Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
564Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For horizontal run)
565Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required.(For vertical run)
566Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
567Providing and laying G.I. tape 32 mm X 6 mm from earth electrode directly in ground as required.
568Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.
569Above 6.5 metre and upto 8.0 metre
570Above 8.0 metre and upto 11.0 metre
571S.I.T.C of floowing rating LED Flood lighting luminarie with pressure die cast housing and toughened glass cover (IP 66 protection) in existing pole/pipe for supply voltage 1C[.Z70Y AC,50Hz. Luminarie shall be confirm tolS:,1,0322part-5/section-5 and shall be complete with all neccssary accessories as required
572200W LED Flood light
573S.I.T.C of floowing rating LED Flood lighting luminarie with pressure die cast housing and toughened glass cover (IP 66 protection) in existing pole/pipe for supply voltage 1C[.Z70Y AC,50Hz. Luminarie shall be confirm tolS:,1,0322part-5/section-5 and shall be complete with all neccssary accessories as required
57490/100W LED Flood light
575S.I.T.C of following rating approved make LED Bollard fitting with cylinder shape of height 600 to 850mm power input-8/9watt with die cast aluminium housing opel wtth PC diffuser, lP:65/54 protectiory conferming to IS:10322 part 5 etc all complete as required. (excluding plinth charge)
576S.I.T.C of following rating LED Post top lamp made in die cast aluminium housing with decorative clear/opal acrylic diffuser on existing pipe including connection with 1.5sq.mm. copper conductor etc all complete as required
57740/45W LED Post top lamp clear
578Extra for fixing the louvers shutters complete with frame for a exhaust fan of all sizes.
579Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required
580S/ F powder coated of approved shade MS Cable Trays Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required..
581150 mm width X 50 mm depth X 1.6 mm thickness
582300 mm width X 50 mm depth X 1.6 mm thickness
583450 mm width X 62.5 mm depth X 2.0 mm thickness
584600 mm width X 62.5 mm depth X 2.0 mm thickness
585S/ F powder coated of approved shade MS Cable Tray Bends Supplying and installing following size of perforated powder coated of approved shade M.S. cable tray bends with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
586150 mm width X 50 mm depth X 1.6 mm thickness
587300 mm width X 50 mm depth X 1.6 mm thickness
588450 mm width X 62.5 mm depth X 2.0 mm thickness
589S/ F powder coated of approved shade MS Cable Tray Tee"s Supplying and installing following size of perforated powder coated of approved shade M.S. cable tray tee"s with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
590150 mm width X 50 mm depth X 1.6 mm thickness
591S/ F powder coated of approved shade MS Cable Tray Cross Members Supplying and installing following size of perforated powder coated of approved shade M.S. cable tray cross members with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
592300 mm width X 50 mm depth X 1.6 mm thickness
593Laying of one number XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
594Above 120 sq. mm and upto 400 sq. mm.
595supplying and making indoor cable end termination with heatshrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
596240 sq. mm
597Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
598240 sq. mm
599P/ F RCC Hume Pipe Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required.
600150 mm dia ID
601300 mm dia ID
602Supplying & making of end terminations with brass compression gland and Al. lugs for following sizes of PVC insulated and PVC sheathed/ XLPE Al. conductor cable of 1.1 KV grade as required.
6034 x 10 sq. mm
6044 x 16 sq. mm
6054 x 25 sq. mm
6063½ x 35 sq. mm
6073½ x 50 sq. mm
6083½ x 70 sq. mm
6093½ x 95 sq. mm
6103½ x 120 sq. mm
6113½ x 150 sq. mm
6123½ x 185 sq. mm
6133½ x 240 sq. mm
6143½ x 300 sq. mm
615ELV WORK
616CCTV SYSTEM
617Supplying and drawing of UTP 4 pair CAT6 LAN cable in the existing surface /recessed steel /PVC conduit as required (1 run of cable).
6181 run of cable
6192 run of cable
6203 run of cable
621Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
62225 mm
62332 mm
624Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System)and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications.
6252 Loop Panel
62610 Loop Panel
627Supplying, installation, testing & commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required.
628Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED,metallic cover complete with all connections etc as required.
629Supplying, installation, testing & commissioning of fault isolator complete with base as required.
630Supplying, installation, testing & commissioning of addressable fire control module complete as required.
631Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
632Supplying, installation, testing & commissioning of addressable manual call point complete as required.
633Supplying, installation, testing & commissioning of fire fighter telephone handset complete as required.
634Supplying, installation, testing & commissioning of fire fighter phone jack complete as required.
635Supplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required.
636Supplying, installation, testing & commissioning of digital audio amplifier 75 Watt, 25V rms operating at 240 Volt AC Supply complete as required.
637Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
638FIREFIGHTING WORK
639PUMPS & EQUIPMENTS
640Supplying , Installation , Testing and Commissioning of Electric Driven Main Fire Pump Suitable for Automatic operation and Consisting of Following Complete in all Respect as Required Horizontal Type Multistage , Centrifugal , Split Casing , Pump of Cast Iron Body and Bronze Impeller with Stainless Steel Shaft Mechanical Seal Conforming to IS : 1520 "Suitable HP Squirrel cage Induction motor , TEFC , synchronous speed 1500 RPM , Suitable for operation on 415 Volts 3 Phase 50 Hz AC Supply with IP 68 protection for enclosure Horizontal Foot Mounted type with class F insulation Conforming to IS : 325 with Energy Efficiency class IE-3 MS Fabricated Common Base Plate Coupling , Coupling Guard Foundation bolts etc as Required Suitable Cement Concrete Foundation duly Plastered with anti vibration Pads The Head of the Pump is Selected in a manner so as to give a minimum 3.5 kg/sqcm pressure at the highest / farthest point
6412280 Lpm at 88 m Head
642Supplying , Installation , Testing and Commissioning of Diesel Engine Driven Main Fire Pump Suitable for Automatic operation and Consisting of Following Complete in all Respect as Required ( Diesel Engine Driven Fire Pump ) Horizontal Type Multistage , Centrifugal Pump of Cast Iron Body and Bronze Impeller with Stainless Steel Shaft Mechanical Seal Conforming to IS : 1520 Suitable HP 1500 RPM Water Cooled with radiator diesel engine conforming to relevant IS standard complete with auto starting mechanism 12/24 Volts electric starting equipment diesel tank exhaust pipe extended up to 10 m outside pump house duly insulated with 50 mm thick glass wool with 1 mm thick aluminium sheet cladding residential silencer instruments and protection as per standard specification stop solenoid for auto stop in the event of fault with audio indications painted with post office red colour etc as required . MS Fabricated Common Base Plate Coupling , Coupling Guard Foundation bolts etc as Required Suitable Cement Concrete Foundation duly Plastered with anti vibration Pads The Head of the Pump is Selected in a manner so as to give a minimum 3.5 kg/sqcm pressure at the highest / farthest point
6432280 Lpm at 88 m Head
644Supplying , Installation , Testing and Commissioning of Electric Driven Pressurisation Pump Suitable for Automatic operation and Consisting of Following Complete in all Respect as Required ( Jockey Pump ) Horizontal Type Multistage , Centrifugal Pump of Cast Iron Body and Bronze Impeller with Stainless Steel Shaft Mechanical Seal Conforming to IS : 1520 Suitable HP Squirrel cage Induction motor , TEFC , synchronous speed 1500 RPM , Suitable for operation on 415 Volts 3 Phase 50 Hz AC Supply with IP 68 protection for enclosure Horizontal Foot Mounted type with class F insulation Conforming to IS : 325with Energy Efficiency class IE-3 MS Fabricated Common Base Plate Coupling , Coupling Guard Foundation bolts etc as Required Suitable Cement Concrete Foundation duly Plastered with anti vibration Pads The Head of the Pump is Selected in a manner so as to give a minimum 3.5 kg/sqcm pressure at the highest / farthest point
645180 Lpm at 88 m Head
646Supplying , Installation , Testing and Commissioning of Electric Driven Pressurisation Pump Suitable for Automatic operation and Consisting of Following Complete in all Respect as Required ( Water Curtain Pump ) Horizontal Type Multistage , Centrifugal Pump of Cast Iron Body and Bronze Impeller with Stainless Steel Shaft Mechanical Seal Conforming to IS : 1520 Suitable HP Squirrel cage Induction motor , TEFC , synchronous speed 1500 RPM , Suitable for operation on 415 Volts 3 Phase 50 Hz AC Supply with IP 68 protection for enclosure Horizontal Foot Mounted type with class F insulation Conforming to IS : 325with Energy Efficiency class IE-3 MS Fabricated Common Base Plate Coupling , Coupling Guard Foundation bolts etc as Required Suitable Cement Concrete Foundation duly Plastered with anti vibration Pads The Head of the Pump is Selected in a manner so as to give a minimum 3.5 kg/sqcm pressure at the highest / farthest point
6471620 Lpm at 88 m Head
648Supplying , Installation , Testing and Commissioning of Electric Driven Terrace Pump Suitable for Automatic operation and Consisting of Following Complete in all Respect as Required ( Terrace Fire Pump ) Horizontal Type Multistage , Centrifugal Pump of Cast Iron Body and Bronze Impeller with Stainless Steel Shaft Mechanical Seal Conforming to IS : 1520 Suitable HP Squirrel cage Induction motor , TEFC , synchronous speed 1500 RPM , Suitable for operation on 415 Volts 3 Phase 50 Hz AC Supply with IP 68 protection for enclosure Horizontal Foot Mounted type with class F insulation Conforming to IS : 325with Energy Efficiency class IE-3 MS Fabricated Common Base Plate Coupling , Coupling Guard Foundation bolts etc as Required Suitable Cement Concrete Foundation duly Plastered with anti vibration Pads The Head of the Pump is Selected in a manner so as to give a minimum 3.5 kg/sqcm pressure at the highest / farthest point
649900 Lpm at 35 m Head
650Supplying and Fixing Air Vessel made of 450 mm dia 8 mm thick ms sheet 2000 mm in height with air release valve on top and flanged connection to riser drain arrangement with 25 mm dia gunmetal wheel valve with required accessories pressure gauge and painting with synthetic enamel paint of approved shade as required
651PIPING, HYDRANT , SPRINKLERAND ACCESSORIES SYSTEM
652Providing Laying Testing and Commissioning of C class Heavy dutyMS Pipe Conforming to IS : 1239 / 3589 including Fittings like elbows , tees , flanges , tapers , nuts , bolts , gaskets etc in ground including welding excavation and Providing cement concrete blocks as supports anticorrosive treatment with coaltar / asphalts tape as per IS :10221 refilling the trench etc of following sizes complete as required .
653150 mm dia
654100 mm dia
65580 mm dia
656Providing Laying Testing and Commissioning of C class Heavy dutyMS Pipe Conforming to IS : 1239 / 3589 including Fittings like elbows , tees , flanges , tapers , nuts , bolts , gaskets etc and fixing the pipe on the wall / ceiling with suitable clamp / support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required .
65725 mm dia
65832 mm dia
65940 mm dia
66050 mm dia
66165 mm dia
66280 mm dia
663100 mm dia
664150 mm dia
665200 mm dia ( Wall Thickness 6.3 mm )
666250 mm dia ( Wall Thickness 6.3 mm )
667Supplying Fixing Testing and Commissioning of butterfly valve of PN 1.6 Rating with Bronze Gunmetal Sheet duly ISI marked complete with nuts , bolts , washers , gaskets conforming to IS : 13095 of following sizes as required .
66850 mm dia
66965 mm dia
67080 mm dia
671100 mm dia
672150 mm dia
673200 mm dia
674Supplying Fixing Testing and Commissioning of double flanged sluice valve of Rating PN 1.6 with non rising spindle bronze gunmetal seats ISI marked complete with nuts , bolts , washers , gaskets and conforming to IS : 14846 of following sizes complete as required .
67580 mm dia
676100 mm dia
677150 mm dia
678200 mm dia
679Providing Installation Testing and Commissioning of Non Return Valve of following sizes conforming to IS : 5312 complete with rubber gasket , GI Bolts , Nuts , washers etc as required .
68080 mm dia
681100 mm dia
682150 mm dia
683200 mm dia
684Providing Installation Testing and Commissioning of Stainless Steel Y Strainer fabricated out of 1.6 mm thick stainless steel , Grade 304 , Sheet with 3 mm dia holes with stainless steel flange .
685100 mm dia
686150 mm dia
687200 mm dia
688Supplying and Fixing Single Headed Internal Hydrant Valve with instantaneous gunmetal material coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS : 5290 ( Type A ) with blank Gunmetal material cap and chain as required .
689Single Headed Gunmetal Material
690Supplying and Fixing Single Headed External Yard Hydrant Valve with 1 Nos 63 mm dia Instantaneous Female Gunmetal Material Coupling and Cast Iron Wheel , ISI marked , Conforming to IS : 5290 ( type A ) with blank gunmetal material cap and chain as required .
691Single Headed Gunmetal Material
692Supplying and Fixing orifice plate made out of 6 mm thick stainless steel ( Grade 304 ) with orifice of required size to be fitted between flange and landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg / sqcm complete as required .
693Supplying and Fixing 63 mm dia 15 m Long RRL Hose pipe with 63 mm dia male and female coupling duly bound with GI wire , rivet etc . Conforming to IS : 636 ( Type A ) as Required .
694Gunmetal Material
695Supplying and Fixing First aid hose reel with MS Construction Spray painted in Post office red conforming to IS : 884 complete with the following as required 20 mm nominal internal dia water hose thermoplastic ( Textile Reinforced ) Type - 2 as per IS : 12585 20 mm nominal internal dia gunmetal globe valve and nozzle Drum and Brackets for fixing the equipments on wall Connections from Riser with 25 mm dia stop gunmetal valve and MS Pipe and socket
69636.5Metre Length
697Supplying and Fixing 63 mm dia Gunmetal Short Branch Pipe with 20 mm nominal internal diameter size nozzle conforming to IS : 903 suitable for instantaneous connection to interconnect hose pipe coupling as required .
698Gunmetal Material
699Supplying and Fixing of Fire brigade connection of Cast iron body with gunmetal male intantaneous inlet coupling complete with cap and chain as required for suitable dia ms pipe connection conforming to IS : 904 as required
7002 Way - 100 mm dia MS Pipe
7014 Way - 150 mm dia MS Pipe
702Supplying and Fixing Air Vessel made of 250 mm dia 8 mm thick ms sheet 1200 mm in height with air release valve on top and flanged connection to riser drain arrangement with 25 mm dia gunmetal wheel valve with required accessories pressure gauge and painting with synthetic enamel paint of approved shade as required
703Providing and Fixing of Pressure Switch in MS Pipe Line including connection etc as required
704Providing , Installation , Testing and Commissioning of adjustable rosette plate for 15 mm dia in white finish UL Listed or FM approved complete as required .
705Providing and Fixing flow switch in following sizes MS Pipe including connection etc as required .
706100 mm dia
707150 mm dia
708Providing , Fixing , Testing and Commissioning of 15 mm dia Quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories .
709Pendent Sprinkler / Upright Sprinkler
710Horizontal Side Wall Sprinkler
711Concealed Sprinkler
712Providing , Fixing , Testing and Commissioning of Installation Control Valve of Cast Iron body and brass / bronze working parts comprising of water motor alarm , bronze seat clapper and clapper arm and hydraulically driven mechanical gong bell to sound countinuous alarm when the wet riser and sprinkler system activates , pressure gauges , emergency release , strainer , pressure switch , cock valve complete with drain valve and bypass , test control box , ball valves , ms pipe of required sizes flanges , orifice plate , gaskets etc of following sizes as required .
713150 mm dia
714Supply , installation , Testing and Commissioning of sprinkler flexible pipe ( UL Listed ) of Stainless Steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI ( burst ) with branch line( inlet )25 mm NPT male thread to sprinkler head ( outlet ) 15 mm NPT female thread with reducer , nipple , 2 sides brackets , center bracket , stockbar of following sizes complete as required .
715700 mm Length
7161000 mm Length
7171200 mm Length
7181500 mm Length
719Supplying , Installation , Testing and Commissioning of deluge valve ( to be used for water curtains ) UL Listed with wet pilot basic trim assembly for DVA with test and alarm , drip and drain valve with water motor gong complete as required .
720150 mm dia
721Providing , Installation , Testing and Commissioning of water curtain nozzle 15 mm dia nickel chrome plated brass , BSPT , K - factor as per design consideration complete as required .
722Providing , Installation , Testing and Commissioning of electric release trim assembly for deluge valve with two way solenoid valve , weather proofoperation on 24 volts DC supply complete as required .
723HVAC WORK
724HVAC : SECTION - A (DSR ITEMS)
725OUTDOOR UNITS
726Supply Installation,Testing&Commissioning of modular type Variable RefrigerantFlow / Variable Refrigerant Volume aircooled Outdoor units suitable for cooling and heating,having all hermetically sealed inverter type Scroll Compressor(s),minimum two compressors for above 14HP modules, micro processor based Controller,top discharge type condensing unit(s), with R410A Refrigerant,vibration isolators,with suitable foundation etc.complete as required.The unitshall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping.The unit shall be suitable towork on 400V+/10%,3Phase,50HzACpowersupply.Theunit shall be filled with first charge of the refrigerant and ready for useas required.The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 . (Considering conversion factor IHP= 0.83TR)
727Outdoor capacity in HP Please note : The oudoor unit configuration will be as per26 HP + 34 HP + 18HP + 28HP for Ground Floor18 HP + 10 HP + 24HP +24HP for FirstFloor 22 HP + 46 HP + 24HPfor SecondFloor
728Items
729Indoor unit- Ductable type Supply, installation, testing and commissioning of following minimumcapacityandexternalstaticpressureVRF/VRVceiling mounted ductable type Indoor unit equipped with washable syntheticmediapre-filter,fansectionwithlownoise fan/dynamicallybalancedblower,multispeedmotor,coilsection withDXcoppercoil,electronicexpansionvalve,cordedremote control, outer cabinet, vibration isolators, drain pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in case of fire on receiveing signal from BMS System.The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature.
730Low static ductable units (minimum 25 pascal external static pressure) 1TR
7311.6TR
732Mid Static Ductable units (minimum 45 pascal external static pressure) 2.6TR
7334 TR
734Items
735REFRIGERANT PIPING Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required
7366.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
7379.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
73812.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
73915.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
74019 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
74122.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
74228.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
74334.9 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
74441.27 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
745Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
7460.63 MM (24 gauge) Galvanized Sheet Steel Ducting
7470.80 MM (22 gauge) Galvanized Sheet Steel Ducting
7481.00 MM (20 gauge) Galvanized Sheet Steel Ducting
7491.25 MM (18 gauge) Galvanized Sheet Steel Ducting
750Supply, installation, balancing and commissioning offabricated at siteGSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
7510.63 MM (24 gauge) Galvanized Sheet Steel Ducting
7520.80 MM (22 gauge) Galvanized Sheet Steel Ducting
7531.00 MM (20 gauge) Galvanized Sheet Steel Ducting
7541.25 MM (18 gauge) Galvanized Sheet Steel Ducting
755Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.
756SUPPLY / RETURN AIR DIFFUSERS Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
757Supplying, fixing testing commissioning of Return air/ Exhaust diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.
758SUPPLY / RETURN AIR GRILLES Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
759Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers as per specifications.
760FIRE DAMPERS Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications.
761Fire damper
762Actuator
763INSULATION Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (class“O”) insulation on existing duct after applying Suitable adhesive for nitrile rubber. The joints shall sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.
76419 mm thick (In Condition Space)
76525 mm thick (In Non - Condition Space)
766Supplying, fixing acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 Kg/M3, with 25 mm x 25 mm GI section of 1.25 mm thick at 600 mm centre to centre covering with rienforced plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound complete as required and as per specification.
767Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with 50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction fixed in 610mm x 610 mm frame work made of25X50X50X50X25 mm made out of 0.6mm thick GI sheet U shapedchannel and covered with reinforced fiber glass tissue and finishedwith 0.80 mm perforated aluminium sheet etc. complete as required and as per specifications.
768NON SCHEDULE ITEMS
769Providing and laying full body matt finishedvitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption"s less than 0.08% and conforming to IS : 15622 of approved make in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand) including grouting the joints with matching grout recommended by the tile manufacturer and matching pigments etc., complete.
770Size of Tile 600x600 mm
771Providing and layingLeather granite Flooring in required design and patterns, in linear as well as curvilinear portions of the building, all complete as per the architectural drawings, with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand), laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade, including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge.
772Leather granite FlooringCherry red, cat eye, Elite brown
773Providing and layingLeather granite in required design and patterns, in linear as well as curvilinear portions of the building, all complete as per the architectural drawings, with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand), laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade in skirting, riser of steps, dados, including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge.
774Leather granite , Cherry red, elite brown , cat eye, Jet black
775Providing and fixing of fully insulated55 mm thick wooden fire / smoke check door shutter using 31mm thick FR insulation with internal facia of 9mm thick calcium silicate board having density not less then950 Kg/cum on both sides and faced with 4mm thick commercial ply facing including 15X55 mm size hardwood beading with fire and smoke seal of size 10 X4 mm fitted along vertical and horizontal edges of the shutter .The complete door system should be capable to achieve Two hour fire rating in accordance with BS:476 Part 20and IS:3614 part II.Rate to include 150x75mm Hardwood door frame duly embedded with Promseal Intumscent Smoke Strip as per manufacturer"s specification all complete . The door shutter shall also have a vision panel 6mm thk, 200mm x 300mm / 300mm x 300mm fire rated glass ( to be paid saperately), surrounded with fire proof treated teakwood beading, all around complete in all respects as per manufactures specifications and direction of the Engineer-In-Charge.
776Providing & Fixing following fire rated fittings as permanufactures specifications and direction of the Engineer-In-Charge.
777Door Locks
778Glass ( Wired) Vision Panel Of Size 200mm X 300mm
779Door closer
780SS Door Handles
781SS Tower Bolts
782Panic bar for S/L door
783External trim for panic bars
784Granite work gang saw cut(polished and machine cut) of thickness 18mm for wall lining,skirting and dado (veneer work) in cementmortar 1:3 (1 cement : 3 coarse sand) including pointing with white cement mortar 1:2 (1 white cement : 2 marble dust) with an admixture of pigment to match the marble shade: (To be secured to the backing by means of cramps, which shall be paid for separately).
785Providing & Fixing 50 mmprecast glass reinforced concrete jali as per the architectural design includingfixing throughout in cement mortar 1:3 (1 cement : 3 coarse sand), including pointing in white cement mortar 1:2 (1 white cement : 2 stone dust) with an admixture of pigment, matching the stone shade, jali slab without any chamfers etc.complete as per the direction of Engineer-in-charge.
786Supply and installation of polycarbonate multi-layered system, a complete assembly of extruded multilayer UV protected polycarbonate panels incorporated into a complete system. Co-extruded UV protected polycarbonate panel system of 25 mm thick. Panels shall be manufactured with vertical standing seam at both sides of the panels. Panels shall be fixed on Purlin with snap on connectors with grip lock locking mechanism and will be secured on MS structure (will be paid Separately) with 3 numbers self-drilling screws & trapezoid SS fasteners holding the base of the standing seam offering best stability having a pull-out load of min. 7000N (7KN) tested as per ISO 6892:1998 and IS 1608: 2005. Panel of 1200 mm (min.) width with angular day lighting concept in a complete system. All fixing accessories to ensure best performance for wind uplift, vibration, oil canning and visual appearance Panels must satisfy Dart drop impact test as per IS 14443-97 shall show no sign of breakage on Polycarbonate sheets which have been exposed to UV for a min. of 500 Hours as per ASTM G 155.Panels shall have minimum seven layers with opaque and translucent louvers integrated within clear body combination as per required lux level with truss bridge design commonly called as X Structure of the cells for better strength and stability. Panels must satisfy Dart drop impact test as per IS 14443-97 shall show no sign of breakage on Polycarbonate sheets which have been exposed to UV for a min of 500 Hours as per ASTM G 155. Panels shall not have Yellowness Index as per ASTM D 1925 of 15 units when tested on a sample exposed to UV for 500 Hours as per ASTM G 155. U value shall not be more than 1.6 W/m2K as per EN ISO 10077-2:2018 .Panel shall be with additional End cap/Aluminium U/F profile/ Glazing Bar for ends as required. Panel shall be fixed over MS structural steel/MS purlin (paid separately) conforming to the detail technical specifications as per approved architectural drawings. Fixing shall be done by the specialized agency onlyas per drawing & direction of the engineering in charge.
787Providing and applying special pure acrylic base resin stone texture paint ( finish thickness 1.2mm to 1.5 mm) Marmoplast of Ultratech make or equivalent . One coat of acrylicPrimer Mixed with wall sealer in the ratio of 1:1 is applied with brush and roller. Repairs to be done with interior grade putty post primer application . OneCoatofstonecrushed texture to be applied as pittedfinish applied with special tool (added with inorganic pigments from 0.01- 3.00%) after the final texture coatone coat of pure acrylic emulsion followed by final coat of siloxane base protection coat to be applied which make the product completely water repellent / dust resistant / antifungal which ensures with a warranty of 08 years on shades and sustainability ,whereas grooves are to be crafted in plaster as design approved by engineering in charge.
788Providing &fixingSS wire gaugeof average width of aperture 1.4 mm with wire of dia 0.63 mm for aluminium doors/window fixed with nessecary screw / washercomplete in all respectsas per direction of Engineer-In- Charge.
789Providing and fixing 36 mm EPDM Rubber flooring of approved make comprising of 30 mmRubber crump and 6 mm granuesls of EPDMin classification of ASTM standard D-1418 all complete as per drawing , specification and direction of the Engineer in Charge.
790Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double action hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-incharge (Door handle, lock and stopper etc.to be paid separately).
791HALL CEILING: Providing & fixing micro perforated of square perforation size 3mmx3mm Gypsum false ceiling having system NRC 0.75 as marked in the drawings, consisting of GI perimeter channels of size 0.55mm thick (having one flange of 20mm and another flange of 30mm and a web of 27mm) along with perimeter of ceiling, screw fixed to brick wall/ partitionwith the help of nylon sleeves and screws, at 610mm c/c. Then suspending GI intermediate channels of size 45mm (0.9mm thick with 2 flanges of 15mm each) from the soffit at 1220mm c/c with ceiling angles of width 25mm x 10mm x 0.55mm thick fixed to soffit with GI cleats and steel expansion fasteners. Ceiling section of 0.55mm thickness having knurled web of 51.5mm and two flanges of 26mm each with lips of 10.5mm are then fixed to the intermediate channel with the help of connecting clips and in a direction perpendicular to the intermediate channel at 300mm c/c. Finished in 12.5mm thick micro-perforated gypsum board, 1200mm x 2400mm in combination with 12mm thick plain gypsum board. The board shall have an overlay of 50mm thick, 1000 GSM polyester wadding. The ceiling to be finished with 2 or more coats of mat type plastic emulsion paint after proper jointing & making surface smooth.
792Stage suspension Grid: Providing & fixingMS suspension grid system over stage for hanging stage services made of 2 nos 40x40x5mm MS angles welded back to back with 50x12x12mm thk studs as MS spacers sandwiched between the MS angles so as to maintain 12mm gap between MS angles, the welded angles to be placed @ 1200mm c/c in one direction and 40x5mm thick MS Tee @ 600mm c/c in other direction. The MS grid to be suspended from the roof structure by means of MS flat suspender of 50x6mm thick MS flats @ 1200mm c/c in both directions. All MS members to be painted with a coat of red oxide primer & 2 or more coats of black enamel paint.
793Woodwool fibril acoustical tiles in stage ceiling: Providing and fixing Fibril Wood Wool black acoustical tilesof size 1200x600x25 mm, to be installed on existing MS suspension grid. Which will comprise of NRC 0.70.
794Wooden Slit Perforated Acoustic Wallpaneling on Rear & Side Walls Lower Level:- Providing and fixing Wood melamine finish HDF basedpanels with slit perforations of size 8/10 x 40/80/100 mm to be fixed on walls.The panels shall bewith melamine laminate finish of size 1200mm x 600mm x 16mm thick having density of 800kg/m3 having system NRC 0.83. The back of the panels are with a nonwoven fabric covering of 0.2mm for providing Sound absorption via the acoustic impedence method. Panel is to be fixed on 50mm GI framework with screw. Framework consisting of 48x36x34x0.5mm thick GI Studs wall channels & 50x35x35x0.5mm floor channels which comes @ 600mm c/c horizontal / vertical on wall as recommended by the manufacturer or engineer in-charge. The cavity of framework should be inserted with 50mm thick, 1000 GSM polyester wadding for better insulation.
795PLUMBING
796Providing and fixing C.P. brass Doublecoat hooks fixed in Toilet wallwith C.P brass wall flanges & C.P. brass screws and other required accessories complete in all respect as per direction of engineer - in - charge .
797Providing and fixing health faucetwith 1 m CP brass flexibletube and swivel hook with CPbrass wall flange including cutting & making good the walls wherever requiredcomplete in all respect as per direction of engineer in charge .
798Providing and fixing stainless steel 600 mm long Grab Bar with 2 nos CP brass wall flange including cutting & making good the walls wherever required complete in all respect as per direction of engineer - in - charge .
799Providing & fixing C.P. brass Central hole wall mounted / table mounted sink mixer with aerator connecting legs & 2 nos CP brass wall flange and 2 nos CP brass stop cock including cutting & making good the walls wherever required complete in all respect as per direction of engineer - in - charge .
800Providing and fixing vertical or horizontal storage type hot water heater fixed to wall with anchor bolts & nuts, 15mm CP brass angle stop cock and 15mm CP brass non-return valve complete including making connections with 15mm dia CP connecting pipes on inlet and outlet, suitable length of power cable and 15 amps plug .
80115 Litre Capacity
80225 Litre Capacity
803Providing & Fixing water purifier cum water cooler made of stainless steel having storage capacity of 80 liter & cooling capacity 60 liter / hour with Reverse osmosis system & ultra voilet membrane TDS reduction 90% having automatic back wash system with filteration unit & all other required accessories complete in all respect as per direction of the engineer in charge .
804Providing and fixing sound insulated Polyproplene piping system as per ON EN 1451-Part 1-6 & EN 12056 Part 1-5 with 3 layer pipe made of PP-C + PP-MV + PP-C in Blue Ral 5014 (halogen and calcium free) colour, push-fit type, food safe, having high impact and stiffness, offering sound levels of not more than 20 dBA as per DIN EN 1451 , DIN EN 752 , DIN 1986 -100 at a flow rate of 4 l/s and having pipe ring stiffness as per 1S0/DIS 9969 and tightness as per EN 1277/B and C and DIN 19560, density of pipe not more than 1.25gms/m3, elongation = 0.05mm/m0K and tensile strength > 24 N/mm2,with all necessary fittings in blue colour, fitted with factory fitted lip ring.
80575 mm dia
806110 mm dia
807Providing and fixing sound insulated Polyproplene piping system as per ON EN 1451-Part 1-6 & EN 12056 Part 1-5 with 3 layer pipe made of PP-C + PP-MV + PP-C in Blue Ral 5014 (halogen and calcium free) colour, push-fit type, food safe, having high impact and stiffness, offering sound levels of not more than 20 dBA as per DIN EN 1451 , DIN EN 752 , DIN 1986 -100 at a flow rate of 4 l/s and having pipe ring stiffness as per 1S0/DIS 9969 and tightness as per EN 1277/B and C and DIN 19560, density of pipe not more than 1.25gms/m3, elongation = 0.05mm/m0K and tensile strength > 24 N/mm2,with all necessary fittings in blue colour, fitted with factory fitted lip ring.
80832 mm dia
80940 mm dia
81050 mm dia
811Providing and fixing PP white Trap with minimum 50mm water seal with rubber seal on inlet to push fit hopper for indirect waste connections (Mcalpine, UK).
812110 mm inlet and 110 mm outlet
813Providing & fixing in position Poloplast materialfloor drainincluding cost of cutting and making good the walls and floors whereverrequired.
814110 mm inlet and 63 mm outlet
815Providing and fixing Poloplast material Inlet fitting / Multi Floor Trap with maximum 3 inlets 32,40 or 50 mm size fabricated from 110 mm dia PP pipes and fixed to PPsockets,fixed to Poloplast floor trap with chemical sealentjoint and set in cement concrete as per standard drawing complete.
816Providing and fixing Poloplast material cleanout plug( Ceiling or Floor) with suitable insert keys for opening, male threaded joint with Poloplast socketfixed to Poloplast Pipe complete in all respects.
817110 mm dia
818Providing and fixing Stainless Steel Grade (304) grating with ring and Stainless steel anti cockroach basket and two SS screw including fixing to the floor with cement mortar.
819Providing and fixing MS holder bat clamps / PVC Material pipe clip of approved design to pipe embedded in and Including cement concrete blocks 10 x10 x10cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size) including cost of cutting holes and making good the walls etc.
82075 mm dia
821110 mm dia
822Providing and fixing Terminal Guard / Vent Cowl of Standard PP Material including fixing the Vent Cowl on the top ofVent / Soil and Waste Stack and Rain Water Pipes .
82375 mm dia
824110 mm dia
825Providing and fixing Tee / Elbowof 90 degree angle fittings of Standard PP Material including fixing the Tee on suitable Location ofVent / Soil and Waste Stack and Rain Water Pipes .
82675 mm dia
827110 mm dia
828Providing and fixing Tee / Elbowof 45 degree angle fittings of Standard PP Material including fixing the Tee on suitable Location ofVent / Soil and Waste Stack and Rain Water Pipes .
82975 mm dia
830110 mm dia
831Providing and fixing Single / Double Socket of Standard PP Material including fixing the Bend on the Bottom ofVent / Soil and Waste Stack and Rain Water Pipes .
83275 mm dia
833110 mm dia
834Providing and fixing Shoe Plain of Standard PP Material including fixing the Shoe on the Bottom ofVent / Soil and Waste Stack and Rain Water Pipes .
83575 mm dia
836110 mm dia
837Providing and installing Air Admittance valves with required air flow rate, including submission of design data(Mcalpine )
838Air flow Capacity up to 32 Litre per Second ( Maxi Vent )
839Air flow Capacity up to 7.5 Litre per Second ( Mini Vent )
840Providing and Fixing Maxi Filtra with Active Carbon Filters( Studor )
841100 mm Inlet and 110 mm Outlet
842Providing and fixing Thermoflex or Careflex thermal insulation tubing, a elastomeric flexible material having hermetic blister closed cell structure of expanded synthetic rubber over pipes of following nominal bores and thickness including all required accessories complete as per specification.
8439 mm thick ( Pipes in Chases)
844For 15 mm dia Pipe
845For 20 mm dia Pipe
846For 25 mm dia Pipe
847Providing and Fixing full way lever operated forged brass ball valve of brass body with forged brass hard chromeplated steel ball tested to a pressure not less than 15 kg/sqcm with threaded / flanged joints complete with nuts, bolts, gaskets, washers etc.
84815 mm dia nominal bore
84920 mm dia nominal bore
85025 mm dia nominal bore
85132 mm dia nominal bore
85240 mm dia nominal bore
85350 mm dia nominal bore
854Providing and fixing C.I.butterfly valves Lever operated PN-1.6 complete with bolts, nuts, 1.5 mmthick compressed asbestos gasket and two nos flanges as per Table “E”complete.
85565 mm dia nominal bore
85680 mm dia nominal bore
857100 mm dia nominal bore
858Providing, fixing, testing and commissioning of motorised butterfly valve of following dia for filling of overhead water tank complete with high and low level control switches to control tanks. The level controllers shall be installed in overhead tanks. The level switch will close the valve when water level is high in overhead tank and open the valve when overhead water tank level is low. The system should be complete in all respects with accessories 220 V AC / 2 V DC, IP67 electrical water level control unit, copper control wiring in whether proof casing etc.
85940 mm dia nominal bore
86050 mm dia nominal bore
861Providing and fixing C.I.butterfly valves Lever operated PN-1.6 complete with bolts, nuts, 1.5 mmthick compressed asbestos gasket and two nos flanges as per Table “E”complete.
86265 mm dia
86380 mm dia
864100 mm dia
865150 mm dia
866Providing & fixing cast iron swing seal dual type non-return valves (PN1.6) complete with matching flanges, rubber insertion, nuts, bolts and washercompleteas required.etc. of followingsizes.
86780 mm dia
868100 mm dia
869Providing and Laying of UPVC Pipes Confirming to IS: 4985Class V (10 kg/cm2) including all fittings wherever required e.g., tees, bends of any degree, Couplings, Adapters, Plugs, Unions etc. and Jointing as Manufacturer Recommondation etc. including Necessary Excavation and Refilling Complete in All Respects. (For Garden Hydrant System )
87032 mm outer dia
87140 mm outer dia
87250 mm outer dia
87363 mm outer dia
87475 mm outer dia
87590 mm outer dia
876110 mm outer dia
877Constructing 2x1x1 mtr (effective Depth). inernal dimension brick masonry oil and grease trap with Ist class bricks in cement mortar 1:4 (1 cement : 4 coarsesand) RCC top slab with 1:2:4 mix (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) foundation concrete 1:4:8 mix (1 cement: 4 coarse sand: 8 gradedstone aggregate40 mm nominal size) inside and outside plastering 12 mm thick with cement mortar 1:3 (1 cement: 3 coarse sand) finished with afloating coat of neat cement inside and rough plaster on outside, 2 Nos. 150 mm dia S W Tees, 3 Nos. 600x600 mm size SFRC manhole cover with frame, necessary baffle walls, 100 mm dia 2100 mm high SCI vent pipe with cowl, complete as per drawing,including excavation refilling and disposal of surplus earth.
878Providing and Laying of HDPE pipes confirming to IS: 14333 type PE-80 (6 kg/cm2) PN -6including all fittings wherever required e.g., tees, bends of any degree, couplings, adapters, plugs, unions etc. and butt welding joints as permanufacturer recommondation etc. including necessary excavation and refilling complete in all respects.
879160 mm outer dia
880200 mm outer dia
881250 mm outer dia
882315 mm outer dia
883450 mm outer dia
884TOTAL OF SUB HEAD - II
885WATER SUPPLY PUMPS AND WATER TREATMENT EQUIPMENTS
886Supply, installation, testing & commissioning of vertical inline multistage pumping set (Imported) with Stainless steel-304 body, Stainless steel-304 impeller, Stainless steel-304 casing, shaft of Stainless steel-316 and C.I. base & head with mechanical seal, connected to a TEFC inductionmotor with class IE -3 efficiency and IP 68 Protection and class F insulationsuitable for 415+/- 10%volts, 3phase50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock,including suction and delivery headers of G.I "C" class pipe of required dia, isolation valves, NRV of PN-16 grade,required valve and strainer & vibration eliminators on both suction & delivery side of pumps, vibration eliminatingpadsunder foundations, 80x40 mm I section base plate bolted to cement concrete foundations complete.Vendor to submit performance curves and technical catalogue of the proposed model for review and information.
887Filter Feed Pump ( In UGT / Plant Room )
888Set of Two pumps (1 Working + 1 Standby)
889Capacity- 100 LPM
890Head - 30.0 Mtr.
891Eff. - Class IE-3-1 Set
892STP Make up Pump ( In UGT / Plant Room )
893Set of Two pumps (1 Working + 1 Standby)
894Capacity- 100 LPM
895Head - 60.0 Mtr.
896Eff. - Class IE-3-1 Set
897Supply, installation, testing & commissioning of variable speed hydropneumatic system mounted on a common base plate comprising ofvertical inline multistage pumping set with Stainless steel-304 body, Stainless steel-304 impeller, Stainless steel-304 casing, shaft of Stainless steel-316 and C.I. base & head with mechanical seal, shaft directly coupled to a TEFC induction motor with class IE -3 efficiency and IP 68 Protection and class F insulation suitable for 400/440 volts, 3 phase, 50cycles AC supply with 150mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation,one No. microprocessor based controller,two Nos. variable frequency drives, one No.remote sensors, transmitters, sequence running cotroller, dry running Protection,motor control centre, necessary power and control cabling from MCC to pumps including required rating of MCB, two Nos. required capacity M.S diaphragam tank with interchangeable butyl rubber membrane,complete in all respects including suction and delivery headers of G.I "C" class pipe of required dia, isolation valves, NRV of PN-16 grade & vibration eliminators on both suction & delivery side of pumps, power box, equipped with fuses/ isolators/circuit breakers as required.
898No. and capacity of Pressure Vessel - 01 Nos. x 200 litres min. (Or as per Manufacturer Calculations)
899The system shall also comprise the following:-
900Control Panel with Programmable Logic Controller (PLC) with in-built PID controller with 16 inputs and 12 outputs, digital display with fluorescent screen with 2 lines of 20 character each equipped with 8 function keys and 9 service keys, 3 Phase, 415 V I/P, 4 KW, AC variable speed drive with in-built EN55011 Class A RFI Filters, having standard function of BI Loop , energy saving, catching a spinning load with speed search, auto hunting jog, preset speeds, controlled stop on loss of supply power loss side through, D.C. injection braking, fast stop. Drive should have selectable, rated input frequency 50/60 Hz and output frequency range of 0.5-32 HZ, contractors, overlead relays and MCBs should confirm to IEC-898-1995 standards Ammeter, voltmeter. All strip indication should blink in case of trip and panel should only be accessible through an access code.
901Type 8202 pressure transducer with SS pressuresensor and control electronic board. Output 4-20m A on two wires conforming BS-6134 standards and IP 68 protection class.
902Domestic Water Supply Pump ( In UGT / Plant Room )
903Set of Two pumps ( 1 Working + 1 Standby)
904Capacity- 100 LPM
905Head - 80.0 Mtr.
906Eff. - Class IE-3-1 Set
907Supply, installing, testing and commissining of submersible single stage single entry pumps with C.I.bodyand C.I. two vane enclosed type impeller connected to TEFC submersible motor with class IE-3 efficiency and IP 68 Protectionand class F insulation for 415 + 10% volts, 3 phase, 50 cycles A.C. power supply withmechanical seal, pump connector unitwith rubber diaphram and bend, vertical discharge pipe, guide pipe and chain in built level controller, sequence running controller, dry running Protection with gunmetal isolation cock,including suction and delivery headers of G.I "C" class pipe of required dia, isolation valves, NRV of PN-16 grade,required valve and strainer & vibration eliminators on both suction & delivery side of pumps complete in all respects.
908(Pumps shall be installed in a set of two pumps One working and One standby , Pump shall be automatic ON / OFF on Cyclic Pattern )
909Drainage Sump Pumps
910(Pumps to be suitable to handle solids upto 28 mm size)
911Capacity - 250 LPM (Each)
912Head- 15 M
913Eff. - Class IE-3-3 Set
914Supply, installation, testing & commissioning of vertical self supportingfiltration unit fabricated from MS sheet as per IS: 2825, (minimum thickness of shell 6mm and dished end 8mm) pressure gauges, sample cock, GI class "C" face piping, CI butterfly valvesand all accessories , with initial charge of filter media including anthracite, 600 mm depth of graded sand gravel and 600 mm depth of anthracite painting inside with epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint, testingand commissioning complete.
915Dual Media Filter
916Capacity-6000 lph
917Filtration rate - 15000 lph/sqm
918Filter dia approx. - 800 mm
919Working pressure : 3.0 Kg/sqcm.
920Test pressure :4. 5 Kg/sq cm-1 Set
921Supply, installation, testing & commissioning of vertical self supportingfiltration unit fabricated from MS sheet as per IS: 2825, (minimum thickness of shell 6mm and dished end 8mm) pressure gauges, sample cock, GI class "C" face piping, CI butterfly valvesand all accessories , with initial charge of filter media including anthracite, 600 mm depth of graded sand gravel and 600 mm depth of anthracite painting inside with epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint, testingand commissioning complete.
922Activated Carbon Filter
923Capacity-6000 lph
924Filtration rate - 12000lph/sqm
925Filter dia approx. - 800 mm
926Working pressure : 3.0 Kg/sqcm.
927Test pressure :4. 5 Kg/sq cm-1 Set
928Supply, installation, testing & commissioning of metering pump type chemical doser with motorize ajector, shaft & blade SS 304 material with 100 lits. PVC/HDPE solution tank, injection fitting assembly, suction and delivery hose upto the point of injection, capacity 0-6 lph, complete in all respects. -1 Set
929Supply, installation, testing & commissioning of annunciation and indication panel with interlocking arrangement complete in accordance to specification with level controller ( In Tubewells , Fire Water , Raw Water , Domestic Water Tank : High / Low Level Controller ) etc with control cabling from field to MCC as required .-1 Set
930The System shall be complete to ensure automatic operation of pump in accordance to water Level in respective tanks .
931Providing and Fixing Level Controllers for water pumps to start / stop the pumps at set level including wiring , cabling from pump to panel and all other accessories as required to operate the system automatically .-6 Set
932Providing and Fixing Pressure Switch for Water Pumps to start / stop the pumps at set pressure including wiring , cabling from pump to panel and all other accessories as required to operate the system automatically .-6 Set
933Providing and fixing GI pipes complete (IS:1239 Heavy Class) with GI fittings conforming to IS : 1879and clamps including MS pipe supports, painting with two or more coats of synthetic enamel paint including one coat of primeras per specification cutting and making good the walls etc. complete.
93425 mm dia-20 Metre
93532 mm dia-20 Metre
93640 mm dia-40 Metre
93750 mm dia-40 Metre
93865 mm dia-20 Metre
93980 mm dia-20 Metre
940100 mm dia-20 Metre
941150 mm dia-20 Metre
942Providing and fixing forged brass ball valve suitable for pressure 25 Kg/Cm2ofthefollowingsizeincluding providing necessary union/flange.
94332 mm dia-6 Each
94440 mm dia-6 Each
945Providing & fixing of C.I. butterfly valve suitableforpressure 16 Kg/Sqcm. with flanges, nut bolts&gasketscomplete required.
94650 mm dia-6 Each
94765 mm dia-2 Each
94880 mm dia-2 Each
949100 mm dia-2 Each
950150 mm dia-2 Each
951Providing & fixing cast iron Single Plate Check valves suitable for pressure 16 kg / sqcm complete with matching flanges, rubber insertion, nuts, bolts and washercompleteas required etc. of followingsizes.
95232 mm dia-2 Each
95340 mm dia-6 Each
95450 mm dia-6 Each
95565 mm dia-2 Each
95680 mm dia-2 Each
957Providing & fixing double flanged flexicon rubber expansion joint with unit control of standard length as per maufacturers specs. Tested to a pressure of 16 Kg/Sqcm including rubber gaskets, flanges, nuts, bolts and washers complete as required.
95832 mm dia-6 Each
95940 mm dia-6 Each
96050 mm dia-6 Each
96165 mm dia-4 Each
96280 mm dia-4 Each
963ProvidingandfixingC.I. "POT" strainer with bronzeperforatedsheetbasket testedtoapressureof 16 Kg/sqcm includingrubber gasket, flanges, nuts, bolts and washers, complete as required.
96440 mm dia-4 Each
96550 mm dia-4 Each
96665 mm dia-4 Each
96780 mm dia-2 Each
968100 mm dia-2 Each
969150 mm dia-2 Each
970Complete Set including all Items as described above
971SEWERAGETREATMENT PLANT
972Sewage Treatment Plant Capacity : 60 KLD.
973Preliminary Works
974Shop Drawings.
975Detailed GA drawing, flow diagram, equipment list, power load requirement
976Design, calculations of all elements of the plant, electrical and mechanical work to satisfy adequacy of design
977Submission of detailed GOOD FOR CONSTRUCTION" stage architectural, structural, construction, electrical, mechanical and piping drawing for approval.
978Sewage Treatment Plant 60 KLD
979Design, Supplying, Installing, Testing & Commissioning of Sewage Treatment Plant capacity 60 KLD. The plant proposed shall be 60 KLD with a main pump room. The plant is proposed to be installed in the Under-groundfrom the pump room itself for future maintenance. Opening shall be provided on above for this purpose, for the following :
980Nature of effluent-Domestic Sewage fromToilet use and kitchen waste,washing waste water etc .
981Daily average flow - 60 Cum / Day
982PH - 6.5 - 8.5
983BOD 5 - upto250-450 Mg/L
984S. Solids - 250 - 400 Mg/L
985COD - upto450-600 Mg/L
986Oil & Grease - 50 Mg / L
987Effluent discharge standard after treatment
988PH - 6.5 - 8.5
989BOD 5 - Less than 30 Mg/L
990S. Solids - Less than 10 Mg/L
991COD - Less than100 Mg/L
992Oil & Grease - Nil
993Sewage treatment plant shall include the following items:
994Bar Screen Chamber
995oil & grease trap
996Sewage equalization tank
997drainage sump
998MBBR Tanks
999Tube Settler Tanks
1000Clear Water tank
1001Treated Water tank
1002Sludge Holding Tank
1003Filter Feed Pumps
1004Irrigation water pump
1005Flushingwater pump
1006Plant Room Sump Pump
1007Multigrade Sand Filter
1008Activated Carbon Filter
1009Chemical Doser
1010UV System
1011Electromagnetic / Turbine type water Flow Meter
1012Air Blowers
1013Pumps & equipment
1014Centrifuge
1015Piping, valves etc
1016Electrical Panel & Cabling
1017Common plant room adjacent to STP.
1018All piping, valves & level indicator/controller etc. within plant room.
1019Supply, installation, testing & commissioning of 2 Nos Stainless Steel 304 PerforatedScreen with suitable lifting arrangement (size 600 mm wide x 1200 mm high approx)-2 Set
1020Supply, installation, testing & commissioning of electronic type level indicator and controller for automatic operation of the system with high/low level alarm complete with auxiliary NO/NC contacts.
1021Contractor shall ensure submission of detailed GA drawings (Plan & Section), P & I diagram, schematic diagram for the above mentioned components and additional components such as inserts, puddle flanges, vent pipes etc.if so required for the complete work.-2 Set
1022Supply of MBBR media consisting of Virgin PE carrier modules with Surface not less than 500 M2/M3 of suitable capacity and as per manufacturer"s recommendation for Reactor tanks alongwith suitable sludge removal arrangement either by pumps or air lifting pumps.-20 Cum
1023Supply of PVC Tube deck media consisting of Virgin PE carrier modules with Surface not less than 500 M2/M3 of suitable capacity and as per manufacturer"s recommendation for Tube Settler tanks alongwith suitable sludge removal arrangement either by pumps or air lifting pumps.-10 Cum
1024Supply installation, testing and commissioning of Electromagnetic Type Sewage / Water Flow meter with 2 nos matching flanges and nuts , rubber , gasket etc . Water Meter shall be applicable with BMS Compitable .-10 Set
1025Supply, installation, testing & commissioning of non clogging type pumps,having SS -304Casing & SS -304impeller and SS -316 Shaftcomplete withall accessories, TEFC Induction motor with class IE-3 efficiency and IP 68 Protectionof required capacity. Delivery header with isolation valve, pressure gauge on delivery line with isolation cock level controller with wiring to control the level of sump automatically. Pump shall have following duty.
1026Submersible Transfer Pumps (2 Nos. - One working & One stand by)
1027(Minimum Solid handling Cap. 46 mm)
1028Flow rate (each)=6 m3 / hr
1029Head =12 Mtr-1 Set
1030Plant Room Sump Pump 2 Nos (1 working + 1 standby) .
1031(Minimum Solid handling Cap. 46 mm)
1032Flow rate= 15 cum/hr
1033Head =15 Mtr-1 Set
1034Mono block centrifugal Sludge Recirculation /Sludge Transfer Pumps ( 2 Nos. - One working & one stand by )
1035(Minimum Solid handling Cap. 46 mm)
1036Flow rate (each)= 3 m3 / hr
1037Head =8-10 Mtr-1 Set
1038Provision of guide ropes to guide submersible pump from upper levelto operational level in sump basin with channels / angle section of MSEP shall be made by the STP contractor.
1039Providing, installation, testing & commissioning of screw Sludge disposal pump for the disposal of sludge to Centrifuge . The pumps shall have SS -304casing, SS -304Impeller & SS -316shaft & sleeve with mechanical rotary shaft seal connected by a flexible tier type coupling to TEFC induction motor with class IE-3 efficiency and IP 68 Protection mounted on a common channel base-plate with coupling guard, 150 mm dia pressure gauge with GM isolation cock, suitable vibration eliminator pads of approved design. Motor to be suitable for including all necessary piping, valves and other accessories and concrete foundation complete as required.
1040Sludge Disposal Pumps (2 Nos. - One working & One stand by)
1041Capacity-3 m 3 / hr
1042Head =40Mtr-1 Set
1043Air diffusionsystemshall include the following:
1044Twin type rotaryair blowers(one working& one standby) capable ofdelivering 60 cum/hr (each) of free air at 0.5 kg/cm2 driven through “V” belt or directly coupled through flexible coupling to a TEFC Induction motor with class IE-3 efficiency and IP 68 Protection of suitable HP Suitable for 415 ± 10% volts, 3 phase, 50 cycles a/c supply .-1 Set
1045Air piping shall comprise of pipesdroppers/ laterals withM S (epoxy coated) Header complete with all fittingssuch as tees,crosses, plugs, sockets, elbows, reducers, supports&clamps,puddle flanges etc cutting chases& making good. -1 Lot
1046Non clog type airdispersion systemcapable of handling 3-5cfm of airwithoxygen transferefficiency of3-4% per/meterwaterdepth.Air dispersion gridshall be assembled in modular formso thatthey canbe replaced / repaired .
1047Fine bubble diffusers
1048For equalization tank -1 Nos.-1 Lot
1049For sludge holding tank - 1 No.-1 Lot
1050For MBBR tank - 2 No.-1 Lot
1051Air dispersion system shall be provided for Equalization Tank, Sludge holding Tank and MBBR Tank.
1052Providing and fixing all piping (as described below) and isolation control valves for making the system complete.
1053MS Epoxy:Submerged air piping
1054MS Epoxy: Air piping
1055PVC piping:Pumped effluent & tank overflow pipe line-1 Lot
1056Supply, installation, testing and commissioning of Bowl type Centrifuge 2-3m3/hr Make Hiller withscrew feed pumps with TEFC Induction motor with class IE-3 efficiency and IP 68 Protection for required capacity head 10-12 m (1Working+1Standby), with interconnecting piping and poly dosing system all complete.-1 Set
1057Supply, installation, testing & commissioning of vertical inline multistage pumping set (Imported) with Stainless steel-304 body, Stainless steel-304 impeller, Stainless steel-304 casing, shaft of Stainless steel-316 and C.I. base & head with mechanical seal, connected to a TEFC inductionmotor with class IE-3 efficiency and IP 68 Protection and class F insulation suitable for 415+/- 10%volts, 3phase50 cycles A.C. supply with 150 mm dia pressure gauge with gunmetal isolation cock,including suction and delivery headers of G.I "C" class pipe of required dia, isolation valves, NRV of PN-16 grade,required valve and strainer & vibration eliminators on both suction & delivery side of pumps, vibration eliminatingpadsunder foundations, 80x40 mm I section base plate bolted to cement concrete foundations complete.Vendor to submit performance curves and technical catalogue of the proposed model for review and information.
1058Filter Feed Pump ( In STP Plant Room )
1059Set of Two pumps ( 1 Working + 1 Standby)
1060Capacity- 100 LPM
1061Head - 30 Mtr.
1062Eff. - Class IE-3-1 Set
1063Irrigation Water Pump ( In STP Plant Room )
1064Set of Two pumps ( 1 Working + 1 Standby)
1065Capacity/Flow Rate-100 LPM
1066Head-60 m
1067Eff. - Class IE-3-1 Set
1068Supply, installation, testing & commissioning of variable speed hydropneumatic system mounted on a common base plate comprising ofvertical inline multistage pumping set with Stainless steel-304 body, Stainless steel-304 impeller, Stainless steel-304 casing, shaft of Stainless steel-316 and C.I. base & head with mechanical seal, shaft directly coupled to a TEFC induction motor with class IE -3 efficiency and IP 68 Protection and class F insulation suitable for 400/440 volts, 3 phase, 50cycles AC supply with 150mm dia pressure gauge with gunmetal isolation cock, vibration eliminating pads under foundation,one No. microprocessor based controller,two Nos. variable frequency drives, one No.remote sensors, transmitters, sequence running cotroller, dry running Protection,motor control centre, necessary power and control cabling from MCC to pumps including required rating of MCB, two Nos. required capacity M.S diaphragam tank with interchangeable butyl rubber membrane,complete in all respects including suction and delivery headers of G.I "C" class pipe of required dia, isolation valves, NRV of PN-16 grade & vibration eliminators on both suction & delivery side of pumps, power box, equipped with fuses/ isolators/circuit breakers as required.
1069No. and capacity of Pressure Vessel - 01 Nos. x 200 litres min. (Or as per Manufacturer Calculations)
1070The system shall also comprise the following:-
1071Control Panel with Programmable Logic Controller (PLC) with in-built PID controller with 16 inputs and 12 outputs, digital display with fluorescent screen with 2 lines of 20 character each equipped with 8 function keys and 9 service keys, 3 Phase, 415 V I/P, 4 KW, AC variable speed drive with in-built EN55011 Class A RFI Filters, having standard function of BI Loop , energy saving, catching a spinning load with speed search, auto hunting jog, preset speeds, controlled stop on loss of supply power loss side through, D.C. injection braking, fast stop. Drive should have selectable, rated input frequency 50/60 Hz and output frequency range of 0.5-32 HZ, contractors, overlead relays and MCBs should confirm to IEC-898-1995 standards Ammeter, voltmeter. All strip indication should blink in case of trip and panel should only be accessible through an access code.
1072Type 8202 pressure transducer with SS pressuresensor and control electronic board. Output 4-20m A on two wires conforming BS-6134 standards and IP 68 protection class.
1073Flushing Water Supply Pump ( In STP Plant Room )
1074Set of Two pumps ( 1 Working + 1 Standby)
1075Capacity- 100 LPM
1076Head - 80.0 Mtr.
1077Eff. - Class IE-3-1 Set
1078Supply, installation, testing & commissioning of vertical self supportingfiltration unit fabricated from MS sheet as per IS: 2825, (minimum thickness of shell 6mm and dished end 8mm) pressure gauges, sample cock, GI class "C" face piping, CI butterfly valvesand all accessories , with initial charge of filter media including anthracite, 600 mm depth of graded sand gravel and 600 mm depth of anthracite painting inside with epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint, testingand commissioning complete.
1079Dual Media Filter
1080Capacity-6000 lph
1081Filtration rate - 15000lph/sqm
1082Filter dia approx. - 800mm
1083Working pressure : 3.0 Kg/sqcm.
1084Test pressure :4. 5 Kg/sq cm-1 Set
1085Supply, installation, testing & commissioning of vertical self supportingfiltration unit fabricated from MS sheet as per IS: 2825, (minimum thickness of shell 6mm and dished end 8mm) pressure gauges, sample cock, GI class "C" face piping, CI butterfly valvesand all accessories , with initial charge of filter media including anthracite, 600 mm depth of graded sand gravel and 600 mm depth of anthracite painting inside with epoxy paint and outside with two coat of red oxide primer and two or more coat of synthetic enamel paint, testingand commissioning complete.
1086Activated Carbon Filter
1087Capacity-6000lph
1088Filtration rate - 12000lph/sqm
1089Filter dia approx. - 800 mm
1090Working pressure : 3.0 Kg/sqcm.
1091Test pressure :4. 5 Kg/sq cm-1 Set
1092Supply, installation, testing & commissioning of metering pump type chemical doser with motorize ajector, shaft & blade SS 304 material with 100 lits. PVC/HDPE solution tank, injection fitting assembly, suction and delivery hose upto the point of injection, capacity 0-6 lph, complete in all respects. -1 Set
1093Supply installation, testing and commissioning UV System cap. 6 cum / hour with required no of UV Lamp and other required accessoriescomplete in all respect.-1 Set
1094Supply, installation, testing & commissioning of annunciation and indication panel with interlocking arrangement complete in accordance to specification with level controller ( In Tubewells , Fire Water , Raw Water , Domestic Water Tank : High / Low Level Controller ) etc with control cabling from field to MCC as required .-1 Set
1095The System shall be complete to ensure automatic operation of pump in accordance to water Level in respective tanks .
1096Providing and Fixing Level Controllers for water pumps to start / stop the pumps at set level including wiring , cabling from pump to panel and all other accessories as required to operate the system automatically .-6 Set
1097Providing and Fixing Pressure Switch for Water Pumps to start / stop the pumps at set pressure including wiring , cabling from pump to panel and all other accessories as required to operate the system automatically .-6 Set
1098Providing and fixing GI pipes complete (IS:1239 Heavy Class) with GI fittings conforming to IS : 1879and clamps including MS pipe supports, painting with two or more coats of synthetic enamel paint including one coat of primeras per specification cutting and making good the walls etc. complete.
109925 mm dia-20 Metre
110032 mm dia-20 Metre
110140 mm dia-40 Metre
110250 mm dia-40 Metre
110365 mm dia-40 Metre
110480 mm dia-20 Metre
1105100 mm dia-20 Metre
1106150 mm dia-20 Metre
1107Providing and fixing forged brass ball valve suitable for pressure 15 Kg/Cm2ofthefollowingsizeincluding providing necessary union/flange.
110832 mm dia-6 Each
110940 mm dia-6 Each
1110Providing & fixing of C.I. butterfly valve suitableforpressure 16 Kg/Sqcm. with flanges, nut bolts&gasketscomplete required.
111150 mm dia-8 Each
111265 mm dia-6 Each
111380 mm dia-4 Each
1114100 mm dia-2 Each
1115150 mm dia-2 Each
1116Providing & fixing cast iron Single Plate Check valves suitable for pressure 16 kg / sqcm complete with matching flanges, rubber insertion, nuts, bolts and washercompleteas required etc. of followingsizes.
111732 mm dia-6 Each
111840 mm dia-6 Each
111950 mm dia-4 Each
112065 mm dia-4 Each
112180 mm dia-4 Each
1122Providing & fixing double flanged flexicon rubber expansion joint with unit control of standard length as per maufacturers specs. Tested to a pressure of 16 Kg/Sqcm including rubber gaskets, flanges, nuts, bolts and washers complete as required.
112332 mm dia-8 Each
112440 mm dia-8 Each
112550 mm dia-6 Each
112665 mm dia-6 Each
112780 mm dia-6 Each
1128ProvidingandfixingC.I. "POT" strainer with bronzeperforatedsheetbasket testedtoapressureof 16 Kg/sqcm includingrubber gasket, flanges, nuts, bolts and washers, complete as required.
112940 mm dia-4 Each
113050 mm dia-6 Each
113165 mm dia-6 Each
113280 mm dia-6 Each
1133100 mm dia-2 Each
1134150 mm dia-2 Each
1135Complete Set including all Items as described above
1136SOLAR HOT WATER GENERATION SYSTEM
1137FOR CONTROL ROOM BUILDING
1138Supply, installation, testing & commissioning of Solar Water Heating System of 4 NOS ISI Marked Solar Flat Plate Collectors of size 2080mm X 1070mm X 100mm, Laser welded . with necessary Stands, Support etc. with 400 Ltrs capacity SS -304 hot water storage tank of thickness 4 mm duly insulated with 50 mm thick PUFF insulation & 24 SWG Aluminium Cladding, with Heat Exchanger of suitable surface area, with necessary makeup tank, with 4 KWH Electrical backup for cloudy / foggy days, with necessary piping with solar panels & solar hot water tank, with one No. temperature Gauge, with 01 Nos. Ball valves, to produced hot water up to 60 degreeC on clear sunny days.(MNRE Approved)
1139Supply, installation, testing & commissioning of Solar Water Heating System of 8 NOS ISI Marked Solar Flat Plate Collectors of size 2080mm X 1070mm X 100mm, Laser welded . with necessary Stands, Support etc. with 800 Ltrs capacity SS -304 hot water storage tank of thickness 4 mm duly insulated with 50 mm thick PUFF insulation & 24 SWG Aluminium Cladding, with Heat Exchanger of suitable surface area, with necessary makeup tank, with 8 KWH Electrical backup for cloudy / foggy days, with necessary piping with solar panels & solar hot water tank, with one No. temperature Gauge, with 01 Nos. Ball valves, to produced hot water up to 60 degreeC on clear sunny days.(MNRE Approved)
1140ELECTRICAL
1141Supply, installation, testing & commissioning of 65 W Recessed Mounted LED luminaire delivering an initial system lumen of 6500 lumens & the luminaire shall be with system efficacy = 90 lm / W. The luminaire Housing shall be made of PC & the diffuser shall be of polycarbonate/PMMA. The operating CCT shall be 6500K with CRI of =80. The luminaire shall be with BIS Registered electronic driver with input voltage range of 150 to 270V , THD = 20% & PF = 0.95 , 50,000 Hrs LED Life with L70 Criteria, IP20. The LED Driver shall be easily avaiable in India for repair and service. The LED shall be SMD type. Luminaire shall have minimum surge protection of 2KV.The luminaire shall be with following certifications: LM79& LM80 issued by LED manufacture along with Photo Biological Safety Standard.
1142Same as item above but Secondary point. i.e. Points to be looped with Primary pointwith 1.5 sqmm wire and Point wiring
1143Supply, installation, testing and commissioning of following krone type tag blocks enclosed in MS enclosure of suitable size with lockable cover.
114410 pair Tag block
114530 pair Tag block
114611 KV HT DP STRUCTURE
1147Supply, Installation, testing and commissioning of 11 KV DP structure as per CEI & HPSEB norms & comprising of the following, but not limited to it for completion of works
1148RSJ pole of 9.15 mt length of size 175 x 90 mm complete with suitable M.S. base plate welded at bottombase plate - 2 Nos.
1149MS Channel of size 100 x 50 mm, length 4 mts (approx)
115011 KV AB switch - 1 set
115111 KV Horn Gap fuse Unit - 1 set
115211 KV Lightning Arrestor
115311 KV Disc insulator
115411 KV Pin insulator
11556 SWG copper wire for jumpering
1156Supply and erection of Stay set complete with necessary foundation, excavation and refilling of earth etc. as required.
1157Concrete foundation for RSJ poles burrioed upto a depth of 1830 mm in ground in a pit of size 450X450 mm in CC 1:3:6 along with 200 mm copping above ground inclusive of earth work.
1158Necessary Nut, Bolts, clamps, operating handle for AB switch, clamping welding etc. complete as required.
1159Painting the RSJ poles complete with two coat of Red Oxide and two coats of GI enamel paints complete as required.
1160Transportation of all materials and accessories at site
1161Complete erection, testing and commissioning.
116211KV H.T. METERING PANEL (INDOOR TYPE):
1163Supply, Receiving, Unloading, Storing, Shifting, Installation, Testing & Commissioning of indoor type floor mounted, dust, damp and vermin proof, cubicle HT. Metering Panel made out of 14 gauge CRCA sheet steel complete with 5 Amp electronic trivector meter, C.T."s of80/5 Amp, 0.5 Class, 10 VA Burden, and P.T"s of 11 KV / v3, 110V /v3, 100 VA conforming to relevant IS Standards and complete as required.H.T. Metering cubicle along with C.T."s, P.T."s and trivector meter shall be got tested and approved from local electricity supply authority. The GA drawing shall be got approved by HPSEB/ local statutory authorities before fabrication.
116411 KV HT SWITCHBOARD ( SINGLE PANEL) - INDOOR DUTY (TO BE LOCATED NEAR THE MAIN ENTRANCE)
1165Design, Manufacture, Supply, delivery, erection, testing and commissioning of a single enclosed 2 mm thick sheet steel clad floor mounting, vermin proof, fully interlocked vertical isolation, extensible, horizontal draw out, air insulated, metal clad switchboard having double isolation features complete with circuits as detailed below.The switchboard shall be complete with necessary PVC insulated copper busbars, small wiring, labels, cable eyes, cable termination to receive XLPE cables, foundation bolts and suitable for operation on 11 kV 3 phase, 50 cycle, earthed system with a rupturing capacity of 350 MVA at 11 kV Panel shall be equipped with following accessoriesand as per specifications and schematic drawing.
11661No. - Metal Clad housing with having 630A Vaccum circuit breaker with Electric operated mechanism (spring charged motor - 230V AC)
11671Set- Tripping coil & closing Coil 24V DC
11681 - Set of isolating plug and receptacle
11691 - Set of Automatic safety shutter
11701- Set of breaker control switch (TNC)
11711 set - Dual Core Cast Resin Current transformers of ratio 80/40/5A Class 5P10 and Class 0.5, 15 VA burden for protection & metering.
11721set of 11/ v3KV / 110/v3 Volt, 100 VA burden & accuracy class 1, 3 nos. single phase construction, dry type cast resin PT
11731 - Set of ON/OFF/Trip/ Spring Charged & Trip circuit healthy and phase indicating lamps.
11741 No.- H.T. Cable joint box for 3C x 240 Sq.mm aluminium conductor XLPE cable,11 KV(E)
11751- set of IDMT relay with 2 element of O/C protection(50%-200%) & 1 element of E/F protection (20%-80%).
11761 no. Anti Pumping Relay
11771 Set of Power Pack 220 Volt A.C. / 24 Volt D.C. complete as required.
1178Supplying,Installation,Testing & Commissioning Rate for 33 kV HT Panel as described above
117911 KV HT SWITCHBOARD ( SINGLE PANEL) - INDOOR DUTY (TO BE LOCATED NEAR THE MAIN ENTRANCE)
1180Design, Manufacture, Supply, delivery, erection, testing and commissioning of a single enclosed 2 mm thick sheet steel clad floor mounting, vermin proof, fully interlocked vertical isolation, extensible, horizontal draw out, air insulated, metal clad switchboard having double isolation features complete with circuits as detailed below.The switchboard shall be complete with necessary PVC insulated copper busbars, small wiring, labels, cable eyes, cable termination to receive XLPE cables, foundation bolts and suitable for operation on 11 kV 3 phase, 50 cycle, earthed system with a rupturing capacity of 350 MVA at 11 kV Panel shall be equipped with following accessoriesand as per specifications and schematic drawing.
1181One Incoming panel equipped with :
11821- Air insulated metal clad housing
11831- set of 3 phase PVC insulated copper busbars 630 amps rating
11846- single pole cluster type isolating contacts i.e. plug and switches
11851- Triple pole draw out truck mounted 11kV, 350 MVA, 630 Amps Vacuum Circuit Breaker fitted with arc control devices.
11866 NO/NC contacts for remote ON/OFF/TRIP status at BMS
11871- Trip free 230 V AC, motor charged spring release closing mechanism complete with necessary auxiliary switches, emergency hand trip device and mechanical "OFF" & "ON" indicator.
11881 - 24 Volt DC shunt trip coil
11891 set-Dual Core Cast Resin Current transformers of ratio 80/40/5A Class 5P10 and Class 0.5, 15 VA burden for protection & metering.
11901- 3 Phase cast resin horizontal draw out line potential transformer ratio 11 KV/v3:110/v3 Volt, class 0.5, 200VA connectedwith H.V. and L.V. connections, H.V.fuses and LV MPCB of adequate rating to withstand fault level in PT circuit, isolating plugs for H.V. and L.V. connection.
11911- Strip heater to prevent absorption of moisture
1192The instrument and relay panel fitted with :
11931- Square voltmeter of 96 x 96 mm scaled 0-15000 volt with 3 way and OFF selector switch.
11941- Square Ammeter of 96 x 96 mm scaled 0-200 amps with 3 way and OFF selector switch.
11951 no. energy analyser to measure voltage, current, power factor,frequency,kW/kVA, kWh, kVArh, kVAh,Real time,date with communication module.
11961 - no. circuit breaker control switch for electrical (T/N/C)
11971- Triple pole numerical I.D.M.T. overcurrent & earth fault relay with two outer elements connected for overcurrent protection and the middle element for earth fault protection overcurrent setting 50% - 200% Earth fault setting 20% - 80% (51 and 51N)
11981 - Electro mechanical Master trip relay (86)
11991 - Electro mechanical Anti pumping relay (94)
12001 - Trip Circuit supervision relay.
12011- set of Red/Green indicating lamps for close and open position
12021- Amber indicating lamp for auto trip
12031- clear indicating lamp for trip circuit healthy
12041- set of white indicating lamps one per phase
12051 - blue indicating lamp for spring charged
12061 - push button on front door for emergency trip
12071-Four window annunciation display to indicate fault trip of incoming and outgoing feeders including audio alarm hooter with accept push button, internal wiring,protection fuses etc. complete.
12081- cable box suitable for cable termination to receive 11 KV XLPE Cable 3 Core 240 sqmm.
12091 Set of Power Pack 220 Volt A.C. / 24 Volt D.C. complete& suitable as requiredfor th complete item.
1210TWO NOS OUTGOINGS- Two Nos. for Transformers Feeder equiped with:
12111- Air insulated metal clad housing
12121- set of 3 phase PVC insulated copper busbars 630 amps
12136- Single pole cluster type isolating contacts; i.e. plug and switches
12141- Triple pole drawout truck mounted 11 kV 350 MVA, 630 amps Vacuum circuit breaker fitted with arc control devices.
12151- Trip free 230 V AC, motor charged spring releaseclosing mechanism complete with necessary auxiliary switches emergency hand trip device and mechanical "OFF" and "ON" indicator.
12166 NO/NC contacts for remote ON/OFF/TRIP status at BMS
12171 - 24 volts DC shunt trip coil
12183 - Dual Core Cast resin Current transformers of ratio 40/5 Class 5P10 and Class 0.5, 15 VA burden for protection & metering.
12191- Strip heater to prevent absorption of moisture
1220The instrument and relay panel fitted with
12211- Square Ammeter 96 mm x 96 mm scaled 0-35 amps with 3 way and OFF selector switch
12221- Triple pole numerical I.D.M.T. over current and earth fault relay, with two outer elements connected for over current and the middle element for earth fault protection over current setting 50% - 200% Earth fault setting 20% -80% and with instantaneous element on all 3 pole settings 500-2000% on over current and 200-800% on earth fault (51, 50, 51N & 50N)
12231 - Electro mechanical Master trip relay (86)
12241 - Electro mechanical Anti pumping relay (94)
12251 - Trip Circuit supervision relay.
12261 - set of electro mechanical auxiliary relay for OLTC
12271- set Electro mechanical auxiliary relay for transformer fault ALARM for winding temperature conditions
12281- set Electro mechanical auxiliary relay for transformer fault TRIP for winding temperature conditions
12291 - no. circuit breaker control switch for electrical (T/N/C)
12301- set of Red/Green indicating lamps for close and open position
12311- Amber indicating lamp for auto trip
12321- clear indicating lamp for trip circuit healthy
12331- set of white indicating lamps one per phase
12341 - blue indicating lamp for spring charged
12351- cable termination suitable for cable joint to receive 11 KV XLPE cable 3 core 240 sqmm.
1236The switchboard shall be complete with all interconnections, label wiring, etc as required and as per direction
1237Supplying,Installation,Testing & Commissioning Rate for 11 kV HT Panel as described above
1238Supply, erection, testing and commissioning of 230V, single phase 2 wireAC to24V DC Batteries charger with semiconductor/IGBT fullwave rectifier with auto /manual float cum boost facility complete with 24V DC, 120 AH sealed maintenance free batteries including one no. distribution board having 63 Amps DP MCCB as incomer and 12 Nos. 20/16ADP MCB"s (D.C. duty) as outgoing complete as required and as directed by Engineer Incharge.
1239DISTRIBUTION TRANSFORMERS Supply, installation, testing and commissioning of 500 kVA 11000/433 volts Deta/Star, vector group DY11, outdoor mounting, oil cooled, ONAN transformer with ON Load Tap Changer (OLTC) AVS relay and RTCC for automatic sensing of incoming voltage, automatic operation of OLTC and facility for remote manual operation of On Load Tap changer, suitable for incoming voltage variation of +5% to - 15% in steps of 1.25% 17 steps to give a constant secondary voltage. The transformer shall be provided with fittings, accessories, protection, first filing of oil etc. including Buchholz oil temperature alarm/trip protection and space for mounting differential protection CT"s in LV chamber complete as per specifications and as required. The transformer shall be provided with arrangement to terminate XLPE cable on HT side and to connect XLPE Cable on LT side, complete as required and conforming to IS:1180 EEL II (Revised in July 2017), IEC 60726 & IS 2026, ECBC-2017, ANSI, NEMA standards& as per specification complete in all respects as required at site.
1240Transformer described as above.
1241Supplyingoffollowing size of aluminum conductor, XLPE insulated armoured and over all PVC sheathed, 11 KV (E) grade earthed cable as per relevant IS code and technical specifications
12423C x 240 sq.mm. XLPE insulated Aluminium. Armored. Cable
1243Supply of fire buckets 4 No. in each set duly filled with fine sand and fixed on an angle iron frame as per requirement of local authorities. Fire buckets shall be painted red from outside and white from inside with additional handle at the bottom and suitable for outdoor installation.
1244Supply and fixing on position the approved Single Line Diagram framed in 1000 x 800 mm size glass frame and installed in main switch room as directed by Engineer Incharge
1245Supply of First Aid box as directed by Engineer Incharge
1246Supply of tool kit with 1 pair 11 KV rubber hand gloves as directed by Engineer Incharge.
1247Supplying & fixing standard shock treatment charts in English & Hindi duly framed and covered with glass as directed by Engineer Incharge.
1248Providing Safety mat made of elastomeric polymers Material (Class B) 1.2 M wide with thickness 2.5 mm to withstand35KV dielectric strength AS PER relevant IS Code
1249Providing a mat made of elastomeric polymers Material (Class A )1.2 M wide with 2 mm thickness to withstand 1.1 KV dielectric strength AS PER relevant IS Code
1250EXHAUST PIPE & CHIMNEY Supply, installation, testing and commissioning of exhaust pipe fabricated out of 6 mm thick MS pipe Class C Heavy duty conforming to IS:3589 with all fixing accessories and hardwares.The work include necessary cladding of exhaust pipe work using 50 mm thick Loosely bound resin (LBR) mattress/ mineral wool/ Rockwool, density not less than 120 kg/m3 and aluminium cladding (0.6 mm thick) for the complete portion. The exhaust pipe work includes necessary supports, foundation etc. to avoid any load & stress on turbo charger / exhaust piping.The exhaust pipe shall be run along the existing wall of the building duly clamped/supported on independent structure for which, the design and Drawing for such structure shall be got approved from the Engineer-in-charge.
1251200 mm dia
1252Design, supply, fabrication and erection of steel structure from channel /angle iron of suitable sizes to support the chimney /exhaust MS pipe duly taking into consideration of the wind load/pressure at the site etc.includingthe cost of civil foundations as required to support a maximum of 2 nos exhaust chimneys on the overhead platform complete as required. The structure shall be givenprimer coatandtwo coats of enamel painting.
1253SS Flexible Bellow 200 mm dia
1254Aluminium cladding for the residential silencers
1255Supply & Fixing of Y Bend for Exhaust pipe
1256MAIN LT PANEL Design, fabrication, assembly, wiring and supply of front operated dead front cubicle type compartmentalised as per Form 3B, rear access free standing, dust and vermin proof (IP 42 ingress protection) main switchboards suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system suitable for a symmetrical fault level of 55 kA at 415 volts, fabricated from 2 mm thick CRCA MS sheets with hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement with suitable angle/channel/T/flat sections including 3 mm thick gland plates on top and bottom and including lifting hooks with sleeved TPN Aluminum Bus bars and GI earth strip of required size with 2 nos earthing terminals and including powder coated paint finish of approved shade (RAL 7032) over metal surface cleaned and treated with seven tank process complete with interconnections etc as per specifications, as required and as below. This main panel must be extendable for future requirement in such a manner not to disrupt ongoing services at the point of use during extension. All LT Panel shall conform to latest IS/IEC -61439 code. All Panel shall be complete with power & control wiring, danger & inscription plate, Lifting hooks etc.
1257Each incoming / outgoing breaker shall have microprocessor release with adjustable over current, short circuit & earth fault protection with instantaneous as mentioned in specification. The Panel will be made as per detailed specifications & drawings forming part of this document. Fault level of panel shall be 50 KA.
1258All the MCCB with adustable overload, short circuit & earth fault protection and above shall have microprocessor. The panel shall be manufactured as per BOQ, tech specification and drawing.
1259(Note:The contractor may select the next higher fault rating of ACB/ MCCB if it is not readily available ,without any extra cost ,as the figure indicated within the bracket are required maxmum fault level of the panel.)
1260NOTE: PANEL MUST BE AS PER IEC 61439 TYPE TESTED FROM ANY INDIA BASED TEST LABORATORY (CPRI/ERDA ETC) FOR ROTECTION AGAINST SHORT CIRCUIT/TEMPERATURE RISE/INTERNAL ARC/DEGREE OF PROTECTION) (PTTA PANEL UPTO 630A & TTA PANEL ABOVE 630A)
1261MAIN LT PANEL
1262INCOMER FROMTRANSFORMER 1 (2 Nos. 500 KVA)
12632 Nos. of800 A 4P electrically operated Drawout type ACB with Ics=Icu=Icw 50KA having Mircroprocessor based releases for O/L, S/C & E/F.
12642 Sets - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT"s
12652 Sets - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
12662 nos. indicating LED lamps for ACB On/Off/ Trip with protective SP MCB"s.
12672 Sets of CTs of the ratio 800/5A for APFC Relay, burden 15 VA
12682 Sets of CTs of the ratio 800/5A with class 0.5 Accuracy for Metering, burden 15 VA
12692 Nos. 800/5A , 15 VA, 5P10 CT"s for Protection
12702 Nos. Under Voltage relay (59)
12712 Nos. Over voltage relay(27)
1272Negative Phase protection Relay, reverse power relay
1273INCOMER FROMDG SETS(2 Nos. 500 KVA)
12742 Nos. of800 A 4P electrically operated Drawout type ACB with Ics=Icu=Icw 50KA having Mircroprocessor based releases for O/L, S/C & E/F.
12752 Sets - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT"s
12762 Sets - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
12772 nos. indicating LED lamps for ACB On/Off/ Trip with protective SP MCB"s.
12782 Sets of CTs of the ratio 800/5A for APFC Relay, burden 15 VA
12792 Sets of CTs of the ratio 800/5A with class 0.5 Accuracy for Metering, burden 15 VA
12802 Nos. 800/5A , 15 VA, 5P10 CT"s for Protection
12812 Nos. Under Voltage relay (59)
12822 Nos. Over voltage relay(27)
1283Negative Phase protection Relay, reverse power relay
1284BUS COUPLER:-
12851 No. of 800A 4P electrically operated Drawout type ACB with Ics=Ics=50KA having Mircroprocessor based releases for O/L, S/C & E/F protection.
12863 Set of Breaker ON-OFF-TRIP, Spring charged indication Lamps as required.
1287Breaker Accessories
128824 V DC Shunt trip Coil-1 Set
1289240 V AC under Voltage release-1 set
1290Auto - manual/ test selector switch-1 set
1291Breaker control switch-1 set
1292Auxilliary contacts required for necessary interlocking of breakers.
1293BUS BARS
12942 Sets of 1000A TPN Aluminum bus bars with colour coded heat shrinkable PVC sleeves.
1295Auto - manual selector switch for individual breaker & PLC
1296Incomer terminal/Adapter box for bus duct & cable connection.
1297OUTGOINGS
12981 Nos. 630 A TP MCCB, 35 kA breaking capacity with thermal release and adjustable setting and with rotary handle. with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along withControl SP MCB
12994 No. 400 A TPN MCCB, 35 kA breaking capacity with thermal release and adjustable setting and with rotary handle. with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along withControl SP MCB
13003 No. 250 A TPN MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle. with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along withControl SP MCB
13013 No. 160 A TPN MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle. with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along withControl SP MCB
13023 No. 125 A TPN MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle. with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along withControl SP MCB
13033 No. 100 A TPN MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle. with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along withControl SP MCB
1304Wiring and Supplying , installation of space heater, humidistat and control MCB"s shall be provided all vertical sections.
1305All Bus bar section/ backside panels have pad locking facility and hinged type door
13065 W LED Lamp, switch shall be provided in each vertical section
1307Supplying,Receiving, fixing, testing & commissioning of Main LT Panel asdescribed above
1308Note: Incomers for Transformer & Bus couplers shall be electrically& mechanically interlocked.
1309Note:The Main LT Panelshall also include the following:
1310(i) Necessary control and firing card with proper control wiring and lugs of the required rating to be provided.
1311(ii) Heavy duty exhaust fans to be provided for cooling
1312(iii) Each Incommer shall have Surge Protection Device.
1313(iv) All outgoing feeders of Main LT Panel shall have BMS compatible Electronic Energy Meter and ON/OFF/TRIP indication Lamps
1314DG SYNCHRONIZATIONPANEL Supply, Installation, Testing and Commissioning of Auto- Synchronizing Panel for 1X500 KVA DG set’s (2 Nos.) inparallel mode of operation, with Auto/Manual Test selector switch, DC Ammeter Voltmeter , Reverse power relays, hooters, annunciator,Indoor floor mounted, sectionalised, compartmentalized MV cubical panel having 31 MVA breaking capacity of suitable size fabricated from cold rolled sheet steel of 2 mm thick for frame work, enclosure and doors, 3mm thick for gland plates with stiffeners wherever required, having vibration free structure chemically treated with seven tank process before painting free structure chemically treated with seven tank process before painting for surface treatment and powder coated, with suitable electrolytic grade high conductivity aluminiumbusbar extensible type, DMC/SMC busbar supports, suitable for 3 phase 415 V 50 HZ AC supply i/c providing and fixing the following switchgear mounted thereon complete with gaskits and interconnections, connections as per specifications complete as required. (The board shall be dust & vermin proof with degree of protection of IP 42 as per IS :13947, free standing type, mounted on base channel of MS Section not less than 100mmx50mmx5mm) and as per the Single Line Diagram and provided with suitable size of Heat Shrinkable Sleeved Coupler extensible bus bars capacity.
1315PLC based auto syncronizing shall be provided complete with analog double voltmeter and frequency meter, syncronoscope, dark lamp, speed and voltage raise/lower selector switch, 2 KVA UPS with battery and battery charger and other essential equipments for complete monitoring and controling accessories.
1316INCOMER
13172 Nos. 800A TPN ACB, 50 kA breaking capacity with microprocessor release and rotatry handle with ON/OFF/TRIP indication Lamps, MFM with BMS Communication Facility along with Control SP MCB
13182 Sets - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT"s
13192 Sets - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
13202 nos. indicating LED lamps for ACB On/Off/ Trip with protective SP MCB"s.
13212 Sets of CTs of the ratio 800/5A for APFC Relay, burden 15 VA
13222 Sets of CTs of the ratio 800/5A with class 0.5 Accuracy for Metering, burden 15 VA
13234 Nos. 800/5A , 15 VA, 5P10 CT"s for Protection
13244 Nos. Under Voltage relay (59)
13254 Nos. Over voltage relay(27)
1326Negative Phase protection Relay, reverse power relay
1327BUS BARS
13282 Sets of 1000A TPN Aluminum bus bars with colour coded heat shrinkable PVC sleeves.
1329Auto - manual selector switch for individual breaker & PLC
1330Incomer terminal/Adapter box for bus duct & cable connection.
1331OUTGOINGS
13322 Nos. 800A TPN ACB, 50 kA breaking capacity with microprocessor release and rotatry handle with ON/OFF/TRIP indication Lamps, MFM with BMS Communication Facility along with Control SP MCB
13331 Sets - digital multifunction meter (showing harmonics along with all other electrical parameters such as voltage current, Hz, KW, KWHr, PF.) with RS 485 port with matching cast resin CT"s
13342 Sets - 0-500V 96 sqmm Voltmeter with selector switch, 3 No. phase indicating LED lamp to show the incoming power with control SP MCB.
13352 nos. indicating LED lamps for ACB On/Off/ Trip with protective SP MCB"s.
13362 Sets of CTs of the ratio 800/5A with class 0.5 Accuracy for Metering, burden 15 VA
13372 Nos. 800/5A , 15 VA, 5P10 CT"s for Protection
13382 Nos. Under Voltage relay (59)
13392 Nos. Over voltage relay(27)
1340Negative Phase protection Relay, reverse power relay
1341Supplying,Receiving, fixing, testing & commissioning ofDG SYNCHRONIZATIONPANELasdescribed above
1342Capacitor Panel -1 ( 125KVAR)
1343INCOMER
13441 No. 250 A TPN MCCB, 35 kA breaking capacity with thermal release and adjustable setting and with rotary handle. with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along withControl SP MCB
1345METERING & INDICATION
13461 set of phase indicating lamps
13471 No. 12 stage Microprocessor APFC controller/Relay shall continuously monitor all three phases and LCD displays for various Electrical Parameters like voltage, input current, capacitive current, KVA demand,KW, Power Factor, self diagnostic error code indication with printout facility of the above with RS 232 C port.Controller should mounted on the front side of the panel. Panel shall be suitable for Auto/Manual operation and shall be provided as per technical specifications.
1348BUS-BAR
13491 Set of 300A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1350OUTGOINGS
13512 Nos.of 80A TP MCCBwith suitable Capacitor dutycontactor
13526 Nos.of 40A TP MCCBwith suitable Capacitor dutycontactor
13533 Nos.of 20A TP MCCBwith suitable Capacitor dutycontactor
13542 Nos. 25 KVAR capacitor Bank each with 7%harmonic & discharge resistorsuitable capacity to carry expected current continuosly. with suitable size capacitor duty contactor, start/stop Push buttons, ON/OFF indication Lamps, Auto/ manual switch complete with wiring in all respects.
13556 Nos. 10 KVAR capacitor Bank each with 7%harmonic & discharge resistorsuitable capacity to carry expected current continuosly. with suitable size capacitor duty contactor, start/stop Push buttons, ON/OFF indication Lamps, Auto/ manual switch complete with wiring in all respects.
13563 Nos. 5 KVAR capacitor Bank each with 7%harmonic & discharge resistorsuitable capacity to carry expected current continuosly. with suitable size capacitor duty contactor, start/stop Push buttons, ON/OFF indication Lamps, Auto/ manual switch complete with wiring in all respects.
1357Supplying,Receiving, fixing, testing & commissioning ofCapacitor Panel asdescribed above
1358Note: The capacitos shall also stipulate the following
1359(i) All the capacitors shall be suitable for 525 V
1360(ii) Necessary control and fixing card with proper wiring and lugs of the required rating to be provided.
1361(iii) Suitable exhaust fans, ventilation louvers to be provided for cooling.
1362(iv) LED indication lamps for number of capacito banks " ON & Power Factor lagging or leading.
1363(v) The APFC shall be protected from following
1364* Over- voltage& Voltage unbalance
1365* Over temperature-system should be in standby mode and automatically restart after above condition restored.
1366*Total harmonic Distortion
1367MDB UPS Input Panel
1368INCOMER
13691 No. 400A 4P MCCB ,25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1370METERING & INDICATION
13711 set of R,Y,B phase indicating lamps
13721 set of ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1373BUS-BAR
13741 Set of 500A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1375OUTGOINGS
13762 Nos. 200A TPN MCCB, 25 kA breaking capacity withmicroprocessor release and adjustable setting and with rotary handle.
1377Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1378MDB UPS Output Panel
1379INCOMER
13802 Nos. 200A 4P MCCB ,36 kA breaking capacity with microprocessor release and adjustable setting and with rotary handle.with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1381METERING & INDICATION
13823 sets of R,Y,B phase indicating lamps
13833 sets of ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1384BUS-BAR
13851 Set of 250A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1386OUTGOINGS
13876 Nos. 63A TPN MCB ,10 kA breaking capacity
13886 Nos. 40A TPN MCB ,10 kA breaking capacity
13893 Nos. 40A SPN MCB ,10 kA breaking capacity
1390Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1391SDB Lift Panel -1 & 2
1392INCOMER
13931 No. 160A 4P MCCB ,36 kA breaking capacity with microprocessor release and adjustable setting and with rotary handle.with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1394METERING & INDICATION
13951 set of R,Y,B phase indicating lamps
13961 set of ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1397BUS-BAR
13981 Set of 200A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1399OUTGOINGS
14003 Nos. 63A TPN MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.
14013 Nos. 40A SPN MCB ,10 kA breaking capacity
1402Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1403MDB Lift Panel
1404INCOMER
14051 No. 250A 4P MCCB ,36 kA breaking capacity with microprocessor release and adjustable setting and with rotary handle.with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1406METERING & INDICATION
14071 set of R,Y,B phase indicating lamps
14081 set of ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1409BUS-BAR
14101 Set of 300A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1411OUTGOINGS
14123 Nos. 160A TPN MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.
14132 Nos. 40A SPN MCB ,10 kA breaking capacity
1414Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1415MDB Ventilation Panel -1
1416INCOMER
14171 No. 100A 4P MCCB ,25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1418METERING & INDICATION
14191 set of R,Y,B phase indicating lamps
14201 set of ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1421BUS-BAR
14221 Set of 150A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1423OUTGOINGS
14244 Nos.63A TPN MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle
14251 No. 63A TPN MCB
1426NOTE :- All starters shall have ON & OFF push button &suitable rating of contractor and overload relays
1427Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1428Pressurization Panel
1429INCOMER
14301 No. 40A 4P MCCB ,25 kA breaking capacity with thermal release and adjustable setting and with rotary handle with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1431METERING & INDICATION
14321 set of R,Y,B phase indicating lamps
14331 set of ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1434BUS-BAR
14351 Set of 100A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1436OUTGOINGS
14372 No. 3 KW DOL Starter with 16A TP MCB (Lift Well Pressurization-3)
14381 No. 16A TP MCB
1439NOTE :- All starters shall have ON & OFF push button &suitable rating of contractor and overload relays
1440Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1441Plumbing Panel (Pump Room)
1442INCOMER
14431 No. 160A 4P MCCB ,25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1444METERING & INDICATION
14451 set of R,Y,B phase indicating lamps
14461 set of ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1447BUS-BAR
14481 Set of 200A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1449OUTGOINGS
14505 Nos. 10 HP Star Delta Starter with 40A TP MCB (Borewell Pumps-1,2,3,4 &5)
14512 Nos. 6 HP DOL Starter with 16A TP MCB (Filter Feed Pump- 1W+1S)
14522 Nos. 3 HP DOL Starter with 10A TP MCB (STP Make Up Pump- 1W+1S)
14532 Nos. 10 HP Star Delta Starter with 40A TP MCB (Domestic Water Supply Pump- 1W+1S)
14542 Nos. 2HP DOL Starter with 10A TP MCB (Drainage Sump Pump- 2W+2S)
14551 Nos 0.5HP DOL Starter with 16A SPN MCB (Chemical Doser- 1W)
14562 Nos. 2HP DOL Starter with 10A TP MCB (Softner Feed Pump- 1W+1S)
14572 Nos. 2HP DOL Starter with 10A TP MCB (Softner Transfer Pump- 1W+1S)
14582 No. 40A TPN MCB
14591 No. 16A TPN MCB
14602 Nos. 10A TPN MCB
14611 No. 16A SPN MCB
1462NOTE :- All starters shall have ON & OFF push button &suitable rating of contractor and overload relays
1463Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1464Fire Fighting Panel
1465INCOMER
14661 No. 400A 4P MCCB ,25 kA breaking capacity withmicroprocessor release and adjustable setting and with rotary handle.with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1467METERING & INDICATION
14681 set of R,Y,B phase indicating lamps
14691 set of ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1470BUS-BAR
14711 Set of 500A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1472OUTGOINGS
14732 No. 200 amps TP+N MCCB outgoing feeders with required capacity (80 H.P Approx. or as required) S/D starters out going feeders to Hydrant / Sprinkler pump motor. The compartment shall contain CT operated ammeter of 0-125 amps range with selector switch auto / manual selector switch and indicating lamp with MCBs for `ON"/OFF`TRIP" status of motor.
14742 Nos. 40 amps TP+N MCCB,with required capacity (12 H.P Approx. or as required) Direct online starter with single phase preventer and outgoing feeder to jockey pump and Terrace Pump. The compartment shall contain CT operated ammeter of 0-40 amps and indicating lamps with MCBs for `ON"/OFF`TRIP" status of pump motors.
14751 No. space for S/D starter with self illuminated Push button for ON & OFF. 1 No. space for DOL starter with self illuminated Push button for ON & OFF. AMF Control & Starter for 100 HP or as reqd. Diesel Engine complete with Contactors, Fuses, MCBs & relays of suitable rating, as required. Connector Block/Strip of suitable no.of pairs complete with wiring upto all Starters, for parallel operation from control desk.
1476Facility for mode selection ie auto or manual test & local/remote.
1477Contractor shall include in his rates for providing level controllers, switches, wiring, cabling from level controller to panel etc. complete as required to operate the system automatic/manual and pump shall be protected against running dry.
1478Electrical hooter with ON/OFF switch for the above pumps running indication Wiring from pressure switch to starter -1 Lot for above pumps
1479Suitable rating TPNMCCB for Diesel Engine Control panel
1480Set of control system to make the system automatic /BMS compatible as per functionl as requirements.
1481Control Panel for Diesel Engine comprising Auto/Manual selector switch & 3 attempt starting device, timers and relays as required, push buttons, start/stop in manual mode.
1482Indication lamp for High/Low Lub.oil pressure, High Water Temp. and Engine ON Indication.
1483Battery charger suitable for 24V DC with boost and trickle selector switch, with digital panel meter for AC, DC voltage and Ammeter for battery charging current
1484Necessary potential free contact for indication of diesel engine driven fire pump running/fault in the addressable fire alarm panel/BMS Panel.
1485All standard relays and accessories for automatic operation of diesel engine.The diesel engine driven fire pump shall start automatically in the event of pressure drop beyond preset limit or mains failure or failure of electrical driven pumps to start
1486Following provisions to be made in the fire panel:
1487Protection failure & control cabling. Panel shall be interlocked in such a way when fire pump startson pressure drop in the header, supply to working air conditioningpanels is disconnected.Neccessory Control wiring upto A/c panels , relevant relays& contactors etc. as required complete in all respect shall be in the scope the Fire contractor (Control wire shall be paid separately under relevant item). Remote indication of ON/OFF/TRIP shall be provided through potential free contact. Provision of remote starting/stopping (manuals) of the engine shall be made. All pumps operation shallbe controled by pressure switches.
1488MDB PANEL -2
1489INCOMER
14901No. 160 A FP MCCB, 36 kA breaking capacity with Thermal release and rotatry handle.
1491METERING & INDICATION
14921 set of R,Y,B phase indicating lamps
14931 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
14941 No. (0-160A) Ammeter with ASSwith 3 nos. 160/5A CT"s
1495BUS-BAR
14961 Set of 150 A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1497OUTGOINGS
14983 Nos. 63A TPN MCB, 15 kA breaking capacity .
14992 Nos. 40A TPN MCB, 10kA breaking capacity .
15002 Nos. 40A SPN MCB, 10 kA breaking capacity.
15012 Nos. 25A SPN MCB, 10 kA breaking capacity.
1502Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1503STP Panel
1504INCOMER
15051 No. 100A 4P MCCB ,25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1506METERING & INDICATION
15071 set of R,Y,B phase indicating lamps
15081 set of ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1509BUS-BAR
15101 Set of 125A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1511OUTGOINGS
15122 Nos. 2 HP DOL Starter with 10A TP MCB (Raw Sewage Relift Pumps- 1W+1S)
15132 Nos. 1.5 HP DOL Starter with 10A TP MCB (Sludge Recirculation Pumps- 1W+1S)
15142 Nos. 1.5 HP DOL Starter with 10A TP MCB (Plant Room Sump Pumps- 1W+1S)
15152 Nos. 2 HP DOL Starter with 10A TP MCB (Sludge Loading Pumps- 1W+1S)
15162 Nos. 3 HP DOL Starter with 10A TP MCB (Air Blowers- 1W+1S)
15171 No. 3 HP DOL Starter with 10A TP MCB (Centrifugal Pump)
15182 Nos. 2 HP DOL Starter with 16A TP MCB (Filter Feed Pumps- 1W+1S)
15192 Nos. 2 HP DOL Starter with 16A TP MCB (Softner Feed Pumps- 1W+1S)
15202 Nos. 10 HP Star Delta Starter with 40A TP MCB (Flushing Water Transfer Pump- 1W+1S)
15212 Nos. 4 HP DOL Starter with 16A TP MCB (Irrigation Water Pumps- 1W+1S)
15221 No. 0.5 HP DOL Starter with 16A DP MCB (Chemical Dozer- 1W)
15231 No. 3 HP DOL Starter with 10A TP MCB (UV System)
15241 No. 40A TPN MCB
15251 No. 16A TPN MCB
15264 Nos. 10A TPN MCB
15271 No. 16A SPN MCB
1528NOTE :- All starters shall have ON & OFF push button &suitable rating of contractor and overload relays
1529Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1530EXTERNAL LIGHTING FEEDER PILLAR-1 (Outdoor Type weather proof, double door with canopy IP-65)
1531INCOMER
15321No. 63A FP MCB(10 KA)
15331No. 63A FP Contactor, AOM switch & Astronomical Watch Timers for 24 Hrs. setting
1534Metering & Indication
15351 set of RYB phase indicating lamps
1536Surge Protection Device Type2 Class C 4 Mode Imax 15KA Per Pole With Necessary Protection .
1537BUS-BAR
15381 Set of 100A TPN Copper Bus Bar with colour coded PVC Sleeves
1539OUTGOINGS
15404 Nos. 20A FP MCB
15414 Nos. 20A DP MCB
1542Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1543HVAC Panel (Terrace)
1544INCOMER
15451 No. 800A 4P MCCB ,25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.with ON/OFF/TRIP indication Lamps, MFM with Communication Facility along with control SP MCB
1546METERING & INDICATION
15471 set of R,Y,B phase indicating lamps
15481 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
15491 No. (0-800A) Ammeter with ASSwith 3 nos. 800/A CT"s
1550Surge protection device , Type 2, MOV type for 8/20 us wave, 3 Nos phase to neutral, one No neutral to earth ,(minimum 3+1 mode) with minimum discharge capacity 40KA along with necessary fuses - Model AG 415-40 T2 (Argos) or equivalent
1551BUS-BAR
15521 Set of 1000A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1553OUTGOINGS
15543 Nos. 250 Amp TPN MCCB, 25 kAbreaking capacity with microprocessor release and rotatry handle (for Chiller-1,2 & 3 )
15553 Nos. 7.5 KW S/D Starter with 40A TPN MCCB
15563 Nos. 3.2 KW S/D Starter with 25A TPN MCCB
15571 No. 250 Amp TPN MCCB, 25 kAbreaking capacity with microprocessor release and rotatry handle (Spare )
15582 No. 40 Amp TPN MCCB, 25 kAbreaking capacity with Thermal release and rotatry handle.
15592 Nos. compartment for DOL Starter.
1560NOTE :- All starters shall have ON & OFF push button &suitable rating of contractor and overload relays
1561Supply, Receiving, fixing, testing & commissioning of HVAC Panel (3rd Basement) as described above
1562MDB VENTILLATION PANEL (1ST BASEMENT)
1563INCOMER
15641 No 100 Amp FP MCCB, 25 kA breaking capacity with microprocessor release and adjustable setting and with rotary handle.
1565METERING & INDICATION
15661 set of R,Y,B phase indicating lamps
15671 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
15681 No. (0-100A) Ammeter with ASSwith 3 nos. 100/5A CT"s
1569Surge protection device , Type 2, MOV type for 8/20 us wave, 3 Nos phase to neutral, one No neutral to earth ,(minimum 3+1 mode) with minimum discharge capacity 40KA along with necessary fuses - Model AG 415-40 T2 (Argos) or equivalent
1570BUS-BAR
15711 Set of 150A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1572OUTGOINGS
15732 Nos. 6.5 KW Star Delta Starter with 63A TPN MCCB for Fresh Air Fan (In Case of Fire & In Case of Nornal)
15742 Nos. 6.5 KW Star Delta Starter with 63A TPN MCCB for Smoke & Normal Exhaust Fan
15752 Nos. 63A TPN MCCB,25 KA.
15761 Nos. 20A TPN MCB,10 KA.
15772 Nos. compartment for Star Delta Starter.
1578Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1579MDB VENTILLATION PANEL ( TERRACE )
1580INCOMER
15811 No 100 Amp FP MCCB, 25 kA breaking capacity with microprocessor release and adjustable setting and with rotary handle.
1582METERING & INDICATION
15831 set of R,Y,B phase indicating lamps
15841 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
15851 No. (0-100A) Ammeter with ASSwith 3 nos. 100/5A CT"s
1586Surge protection device , Type 2, MOV type for 8/20 us wave, 3 Nos phase to neutral, one No neutral to earth ,(minimum 3+1 mode) with minimum discharge capacity 40KA along with necessary fuses - Model AG 415-40 T2 (Argos) or equivalent
1587BUS-BAR
15881 Set of 150A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1589OUTGOINGS
15902 Nos. 7.5 KW Star Delta Starter with 63A TPN MCCB for Fresh Air Fan (In Case of Fire & In Case of Nornal)
15915 Nos. 4.5 KW Star Delta Starter with 40A TPN MCCB for Smoke & Normal Exhaust Fan
15921 Nos. 3.5 KW Star Delta Starter with 25A TPN MCCB for Smoke & Normal Exhaust Fan
15932 Nos. 63A TPN MCCB,25 KA.
15942 Nos. 40A TPN MCB,10 KA.
15952 Nos. compartment for Star Delta Starter.
1596Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1597AHU SDB panel-1 (For Ground Floor)
1598INCOMER
15991 Nos. 80A TPN MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.
1600METERING & INDICATION
16011 set of R,Y,B phase indicating lamps
16021 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
16031 No. (0-80A) Ammeter with ASSwith 3 nos. 80/5A CT"s
1604BUS-BAR
16051 Set of 100A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1606OUTGOINGS
16072 Nos. 4.5 KW DOL Starter with 40A TPN MPCB.
16082 Nos. 3.5 KW DOL Starter with 25A TPN MPCB.
16091 Nos. 40A TPN MCB (Spare).
16101 Nos. 25A TPN MCB (Spare).
1611Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1612AHU SDB panel-1 (For First Floor)
1613INCOMER
16141 Nos. 80A TPN MCCB, 25 kA breaking capacity with thermal release and adjustable setting and with rotary handle.
1615METERING & INDICATION
16161 set of R,Y,B phase indicating lamps
16171 No. (0-500V) Voltmeter with Built-in VSS with 3 nos. 2A SP MCB
16181 No. (0-80A) Ammeter with ASSwith 3 nos. 80/5A CT"s
1619BUS-BAR
16201 Set of 100A TPN Aluminium Bus Bar with colour coded PVC Sleeves
1621OUTGOINGS
16222 Nos. 5.0 KW DOL Starter with 40A TPN MPCB.
16232 Nos. 4.5 KW DOL Starter with 40A TPN MPCB.
16241 Nos. 3.5 KW DOL Starter with 25A TPN MPCB.
16252 Nos. 40A TPN MCB (Spare).
16261 Nos. 25A TPN MCB (Spare).
1627Supplying,Receiving, fixing, testing & commissioning ofabove described Panel
1628XLPE Insulated Copper Armoured Cables
16293C x 6 Sq.mm.
16303C x 4 Sq.mm.
16317 C x 1.5 Sq.mm.
163212 C x 2.5 Sq.mm.
16331C X 150 sqmm Cu flexible(Unarmoured) cable
1634Supply and making End termination with brass Single/ Double compression gland including providing and crimping of aluminum/copper solderless lugs/ferrules for XLPE/PVC insulated armoured power aluminum/copper conductor cables 1.1 KV grade of following sizes:
1635SINGLE COMPRESSION GLAND FOR AI. AR. CABLE
16364C/3C x 6/4 sq.mm.
1637Single Compression Gland for Cu. Cable
16384C/3C/2C x 4/6/2.5 sq.mm.
16397C x 1.5 Sq.mm.
164012C x 2.5 Sq.mm.
1641Supplying, fixing, testing and commissioning of following bare Copper/ GI flat including all necessary fixing accessories and effecting connections.
164250 mm x 6 mm thick Cu flat
164350 mm x 6 m thick GI flat
1644Supply and laying medium class GI pipe under road/paved areas/wall crossing etc. including earth excavations refilling, ramming and making good as approved.
1645150 mm dia GI pipe Class B
1646Supplying, fixing, testing and commissioning of following size PVC sleeve for bare Copper/GI tapes including all necessary fixing accessories and effecting connections.
1647For 50 mm x 6 mm thick Cu. tape.
1648Supply of Lightnig counter - LCD screen shows the number of lightning strikes, hour and date of lightning eventsButtons enable TIME/DATE setting and log viewing. Replaceable battery, working life minimum five years, meet the requirements for IS/IEC 62305 and IEC 62561-2.Tested for Electrical ,Mechanical and Chemical as per IEC 62561.
1649Items
1650Supply,Installation,Testing and Commissioning of on grid Solar Photo voltaic Power Plant conforming to MNRE specifications as amended,consisting of Mono/Poly Crystalline silicon solar cells,net metering facility,necessary protections,earthing, mounted on Aluminium/GI structure of suitable strength with following components complete etc as reqd:-
1651Solar Photovoltaic Module of capacity 330W por above,manufacture din India, conforming to IS14286 / IEC61215, IS/IEC61730-Part-1,IS/IEC61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than16.5%.PV modules used in solar power plants/systems must be warranted for their output peak watt capacity,which should not be less than 90% attheend of 10 years and 80% attheend of 25 years.
1652Power Conditioning Unit (PCU) of 350 800 VDC Input voltage range and 400VAC,three phase,4wire,50Hz+/-2.5Hz,output voltage suitable to generate AC Power with efficiency not less than 97%,total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degreeC.The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency.
1653Data Monitoring System complete with accessories.
1654Fixing of Arrayjunction box & Main junction box with IP65 protection and termination arrangement for in coming and out going cable along with glands,lugsand other accessories etc. as required.
1655Lightning and surge voltage protection.
1656Connections & Inter connections by supplying & fixing required size XLPE insulated copper conductor1.1kVgrade armoured power and control cables between solarmodules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/ conduit lugs and other accessoriesetc.asrequired. Note: The rate of this item includes the rate of structure and related civil works in complete respect for erection and installation of Solar power plant and necessary items required for its proper working, the work will be carried out on different locations in same campus, nothing extra shall be paid in this account.
1657Supplying, installation, testing and commissioning of Spyke light fitting suitable for 8 watt IP 65LED having system lumen output of minimum 750 lumenscomplete with all accessories and lamp. Wipro Cat No.: LF05-600-036-27-XX
1658Supplying, installation, testing and commissioning of 90W LEDSolar Street Light On 9 Meter GI octagonal Pole having Compact, Aesthetic, Eco friendly & modern integrated Solar street light in extruted Aluminum construction with high efficiency monocrystalline silicon photo voltaic panel, high efficacy SMD LED 6500K having secondary lens optics for street lighting distribution, high performance lithium battery, MPPT charge controller & Intelligent control module/sensor with higher reliability, long service life, suitable for easy & quick installatio. Wipro Cat No.: LR 14-132-XXX-65-XX.
1659Supply of 20mtr. High mast in two section Construction 5355 grade as per BIEN 10 025 Top Dia 150mm, bottom dia 410mm, plate thickness 3mm,2Oside polygon, galvanisation as per BS EN ISO 146L, base plate dia 570mm, base plate thickness 25mm, GI single spike lighting protection, maximum wind speed 47 m/swith 8 nos foundation bolts of PCD 490mm TS 600/ 30mm dia/850 mm long. Luminaries carriage : Material for 50 NB ERW Class B - M.S. Pipe, dia of carriage ring 535mm (ID) with 6 arm, welded,2 sections having carrying capacity upto 12 luminaries. Trailing Cable : 5 core 4sq.mm. PVC flexible copPer conductor Winch/Power Tool : Double drum, SWL 750 kg with 1HP 6 pole single speed integral motor Rope : Grade A13131"6,7 /19 construction, dia 6mm, BLC 2350 x 2 having 2 nos of continues roPe. Aviation obstmction light: twin dome aviation obstruction lights LED Itype as required. (But excluding Feeder Pillar) For 20 mtr. High mast: ITC of the high mast and light fixture with the help of suitable tools and plans, wiring of luminaries with all Hi"g material like PVC insulate[Pvc sheathed flexible cable of suitlblb copper conductor lugs, MCB and all labour & construction of shallow foundation with M25 grade concrete for the high mast considering safe soil bearing capacity of 10T / mhs sq. for 20 M High mast.
1660Providing, installation of 200 x 150 x 125 mm polycarbonate weather proof (IP-55) junction box and SP MCB’s and terminal block. Supplying and laying cable through GI pipe upto junction box including excavation and back filling, wiring with 2 x 2.5 sq.mm PVC insulated 1100 volts grade copper conductor wires from junction box to lighting fixturecomplete.
1661ELV WORK
1662Supply, installation, testing and commissioning of 3 MP Dome Camera , ONVIF profile S & G ,UL , CE , FCC Certified , 1/2.8" CMOS sensor ,3.6 mm fixed focal , triple stream ,Min Illumination :0.01 Lux @ (F1.2, AGC ON), 0.028 Lux @(F2.0, AGC ON), 0 Lux with IR , Shutter Speed : 1/5 ? 1/100,000 s ,Edge analytics : line crossing , perimeter intrusion , stationary object ,Video Compression : H.265 ,H.264, frame rate 30 fps @ 3MP , Edge analytics : line crossing , perimeter intrusion ,Face detection , cross counting , stationary object ,Inbuilt IR LED , IR distance upto 30 mtrs ,IP 66 , POE .
1663Supply, installation, testing and commissioning of UL Listed 3 MP Bullet Camera , ONVIF profile S & G ,UL , CE ,FCC Certified , 1/2.8" CMOS sensor ,3.6 mm fixed focal , triple stream , Min Illumination :0.05 Lux @ (F1.2, AGC ON), 0 Lux with IR , Shutter Speed : 1/5 ? 1/100,000 s , Video Compression : H.265 , H.264 , frame rate 30 fps @ 3MP , Edge analytics : line crossing , perimeter intrusion ,Face detection , cross counting , stationary object ,Inbuilt IR LED , IR distance upto 30 mtrs ,IP 66 , POE .
1664Supply, installation, testing and commissioning of ONVIF profile S & G ,UL certified16 Channel NVR , 4 SATA ports , each SATA capacity of upto 8 TB, Recording Bandwidth 320 Mbps , 1 X HDMI , 1 X VGA , Alarm : 16ch in / 1ch out , 1 X RJ45 port , 1x3.0 USB for backup / upgrade, 2x 2.0 USB for mouse , Smart Phone support : iOS, Android
1665Supplying ,Installation, Testing and commissioning of 8TB HDD for Storage.
1666Supply, Installation, Testing & Commissioning of 8 port 10/100/1000+ 2 X gigabit SFP , managed L-2Switch withSFP moduleswitching capacity 216 gbps, Complete as per side required.
1667Supply, installation, testing and commissioning of Client workstation with Min-intel i7 orbetter , 8 GB RAM , 4 GB dedicated graphic card , 1TB HDD , 1 x HDMI Port.
1668Supplying ,Installation, Testing and commissioning of 42” Full HD LED Display Unit - Wall Mount.
1669Supplying ,Installation, Testing and commissioning of HDMI Cable- 3Mtr
1670Supply, Installation, Testing and commissioning of 32U Rack - Outdoor with PDU,FAN and Cable Manager(Wallmount).
1671FIRE ALARM SYSTEM
1672Supplying, installation, testing & commissioning of Addressable monitor module, 100% soft addressed from panel, integral short circuit isolators, capable of monitoring NO contacts, Option to choose operation mode as supervision of 20Sec or activation immediatee to connect NO/NC contacts such as pressure switch, flow switches, fire pump contacts etc Module shall be supplied with mounting plate from OEM for ease of installation & maintenance.
1673Intelligent and electronically addressable photoelectric smoke detector with microprocessor in head and includingmounting base with LED etc. complete as per specification (Above False ceiling)
1674Intelligent and electronically addressable photoelectric smoke detector with microprocessor in head and includingmounting base with LED etc. complete as per specification(Below False ceiling)
1675DATA NETWORKING (STRUCTURE CABLING SYSTEM PASSIVE)
1676Supply , Installtion , Testing and comissioningof armoured 6 coreSinglemode OFC cable for interfloor switch connectivity.
1677Supply , Installtion , Testing and comissioningof 12 port loaded LIU with adaptor plates , pigtel cables for connections.
1678Supply , Installtion , Testing and comissioningof LC-LC singlemodefiber patch cord.
1679Supply , Installtion , Testing and comissioning of CAT6 information outlet (I/O) for Data, Voice, CCTV & Wi-Firack.
1680Supply , Installtion , Testing and comissioning of loaded 12 port CAT6jack panel for CAT6 cable termination.
1681Supply , Installtion , Testing and comissioning of CAT6 patch cord 3 feet for rack side switch termination for user End.
1682Supply , Installtion , Testing and comissioningof CAT6 patch cord 7 feet for user termination to information outlet Rack End.
1683Supply , Installtion , Testing and comissioningof 12 U Wall mount rack with fans , 2 Nos of hardware pkts.
1684Supply, installation, testing and commissioning of Single Mode 1G SFP Module compatible with above switches.
1685TELEPHONE NETWORKING SYSTEM Supplying and drawing following pair, 0.5 sq.mm FR PVC insulated copper conductor, unarmoured telephone cable in the existing surface/recessed PVC conduit as required.
168610 Pair Cable As per
1687100 Pair Cable As per
1688SITC of Analog telephone instrument with CLI facilities, flash, redial .
1689Supply, installation, testing and commissioning of following krone type tag blocks enclosed in MS enclosure of suitable size with lockable cover.
169010 Pair MDF.
169150 Pair MDF.
1692ACCESS CONTROL SYSTEM
1693Supply, Installation, Testing and Commissiong of4 Door 4 reader access control panel with onboard 32 Bit RISC ARM CPU, 8MB flash memory, shall support up to 100000 card user, 400000 event transactions, TCP/IP, the panel should have inbuilt 4 GB SD memory card to take mirror image of device configuration. data shall support standard Wiegand readers, Access Control panel should have MODBUS connectivity to integrate the panel with BMS (Building Management System), with metal enclosure & inbuilt power supply, facility of din-rail mounting should available. capable to integrate with IP/CCTV & NVR for access event alerts, Inbuilt door interlocking facility, SNMP alerts facility, Low battery and AC fail alert facility & reader Tamper detection alert facility should available.
1694Supply, Installation, Testing and Commissiong of Cloud Compatible enterprise level Web based Modular Access Management and Time Attendance software with SQL Database and support up to desired number of users. Single GUI Plateform with complete modular software with provision to integrate with different application ie; Access Control, VMS, Alarm Management, etc. Employee Self Service - login module for Employee/HOD/MANAGER where they can view their attendance; they can apply for leave/manual punch/tour entry/outdoor entry though internet with their login ID & password. Same way manager can online approve all application sent by employee. Comprehensive Email and SMS module for to send various SMS & Email on the base of different events in Access Control & Time Attendance system. It should support Multi company, multi location, multi department, multi login with different rights, muti hierarchy of employee, Should support maker & checker facility - the local administrator should able to add the users but he should not able to authenticate/approve the User, Approval right of the added user should be with main Administrator. Dedicated output reports for Payroll integration, Duress Authentications, Email & SMS can be sent on every configured event ie; Leave Application/approval, Manaual Punch Application/Approval,Outdoor Application/Approval, Tour Application/Approval, Condone Application/Approval . Holiday restriction (Reader Wise), Device Configuration – Push/Pull, Dual Authentications, Easy Employee tracking as outdoor Employee Attendance should marked with their GPS Location, Employee can mark Offline attendance (If No Network) through Android Mobile App.
1695Supply, Installation, Testing and Commissiong ofMifare smart Card Reader Technical Specs.
1696Read Range -4-9 cms
1697Data Read CSN/Sector
1698Type Smart Card (Mifare Classic)
1699Transmit Frequency 13.56 MHz
1700Card (Transponder ) Mifare® Series (ISO14443-A)
1701Card Read Time 0.1 Sec
1702Output Interface Wiegand Format (32 Bits)
1703LED Indicator Bi Color LED
1704Power supply 12V DC @ 100mA
1705Material Abs Plastic
1706Card should be read in1 sec
1707A Wiegand output that easily interfaces with most existing Wiegand protocol access control panels.
1708Compact and Elegant. Easily installed on walls and doors.
1709Supply, Installation, Testing and Commissiong of Mifare Smart Card Contactless transmission of data and supply energy (No battery needed), Operating Distance: Upto 100mm (Depending on Antenna Geometry), Operating Frequency: 13.56 MHZ. Fast Data Transfer: 106 Kbit/s High Data Integrity: 16 Bit CRC, parity, bit coding, bit counting. 1 Kbyte, organized in 16 sectors with 4 blocks of 16bytes each (one block consists of 16 byte), User definable access conditions for each memory block. Data retention of 10 years. Mutual three pass authentication (ISO/IEC DIS9798-2), Data encryption on RF-Channel with replay attack protection. Individual set of two keys per sector (per application) to support multi-application with key hierarchy. Unique serial number for each device. Transport key protects access to EEPROM on chip delivery.
1710Supply, Installation, Testing and Commissiong of Electromagnetic Lock 600 lbs, Single leaf, LED Status Display.
1711Supply, Installation, Testing and Commissiong Electromagnetic Lock 1200 lbs, double leaf, LED Status Display.
1712Supply, Installation, Testing and Commissiong of 8 Core x 1.0 sq mm multi strand, copper, unarmoured shieldedCable as per specification (between the every card readers & the access controllers).
1713Supply, Installation, Testing and Commissiong of U/L Clamp made of aluminium anodised for EM Lock.
1714Supply, Installation, Testing and Commissiong of Exit push button as required.
1715Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
17162 x 1.5 sq. mm
1717Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
171825 mm dia.
1719Providing and fixing of Fire Hose Cabinet size not less than2.1 x 1.2 x 0.90 mtr made out of M.S. sheet not less than 1.5 mm thick having central opening and 4 mm thick glazed glass doors (Two nos.)suitably markedon the outside "with the letters "FIRE HOSE" including necessary lockingarrangement and painting inPO red coloursuitableto accommodate, internal hydrant valve, 2 nos15 mtrlongHose pipe, branch pipe, nozzle and fire man"s axe. It shall be fixed inside the FHC Cabinet Complete as required .
1720Providing and fixing weather proof Fire Hose Cabinet of size not less than0.75 x 0.6 x 0.25 mtr made out of M.S. sheet not less than 1.5 mm thick having central opening and 4 mm thick glazed glass doors (Two nos.)suitably markedon the outside "with the letters "FIRE HOSE" including necessary lockingarrangement and painting in PO red coloursuitableto accommodate, externalyard hydrant valve, 2 nos15 mtrlongHose pipe, branch pipe, nozzle and fire man"s axe. It shall be mounted on boundary wall complete as required.
1721Providing & fixing Controlled Percolating (CP) Hose ISI marked (IS:8423) 63 mm dia x 15 m long complete with instantaneous type Stainless steel63 mm dia ISI marked Male & Female couplings (IS:903) bound and riveted to hose pipe with copper rivets and 1.5 mm copper wire.brusting pressurenot lessthan22Kg/Sqcm. ( Two nos. for eachhydrant-valve)
1722Providing & fixing GM fire Brigade Suction hose coupling (Draw out Connection) with nut for female coupling as per IS:902-1974 complete with 150 mm dia. 1 No C.I Foot valve flanged (to be connected to static water tank)
1723Providingandfixing standard firemans axe with heavy rubber handle.
1724Providing and fixing 25 mm dia inspection & testing assembly with Stainless steel valve sight glass, valve & connected to drain line.
1725Providingand fixing dial type pressure gauge withisolationcockand copper pipe on main header Dial diameter 100 mm celebration 0-16 / sq. cm.
1726Providing & fixing double flanged flexicon rubber expansion joint with unit control of standard length as per maufacturers specs. Tested to a pressure of 20 Kg/Sqcm including rubber gaskets, flanges, nuts, bolts and washers complete as required.
172780 mm dia
1728100 mm dia
1729150 mm dia
1730200 mm dia
1731Providing and fixingFire Extinguishers (CO2 type powder ) 4.5 Kg Capacitycompletewith all accessories aspermanufacturers specifications.
1732Providing and fixingFire Extinguishers (A, B, C type powder ) 6 Kg Capacity completewith all accessories aspermanufacturers specifications.
1733Providing and fixingFire Extinguishers (A, B, C type powder ) 9 Kg Capacity completewith all accessories aspermanufacturers specifications.
1734Providing and Fixing ISI marked (IS:2878) Fire and wall suspension bracket, Extinguisher, Trolley mounted carbon-dioxide type capacity 45 Kg. Flat base including valve, discharge hose of not less than 10mm dia 1m long complete in all respects including wheeled trolley, carrying handle and initial fill with CO2 gas as per IS: 307-1996 filled to a filling ratio of not more than 0.667.
1735Providing and Fixing ISI marked ( IS : 13386 )fire extinguisher Mech. Foam type capacity 50 litres with gunmetal cap and nozzle, trolly mounted and complete in all respects including initial fill.
1736GAS FLOODING SYSTEM Novec 1230, CCOE Approved 120.0 Ltrs. Cylinder working at 34.5 bar pressure with Valve Assembly and arrangement for Supervisory Switch connection for monitoring cylinder pressure, a pressure gauge with a safety burst disc and safety cap
1737Novec 1230 manufactured by 3M, with Zero Ozone Depeltion Potential and Very Low Global Warming Potential of 1 with 20 Years Blue Sky Warantee against any regulatory Bans and Restrictions.
1738Master Cylinder Kit complete comprises of Electric Control Head operated electrically from the detection and control system or locally with a manual actuator, complete with cylinder supervisory switch.
1739Manual Actuator Assembly complete with liverto activate the system manually.
1740Wire Braided Flexible Rubber Hose with Elbow and connectors complete assembly to Connect Novec 1230 Cylinder Assembly Discharge outlet with Discharge Pipe or Discharge Manifold.
1741Primary Pressure Operated Slave Control Head Complete Kit with Pneumatic Actuating ValveOperated Pneumatically from the Master Cylinder Discharge Pressure, Flexible Interconnincting Hose. Complete with Cylinder Supervisory Switch.
1742Supply of manifold check valvefor non return arrangement of Novel 1230 gasafter discharge back into cylinder.
1743Warning Signs and Plates for Inside Room and Outside Room application.
1744Discharge Nozzles to Discharge Novec 1230 Gas in the Hazard Area as perhydraulic calculation and flow rate required in 180 Deg/360 Deg Discharge Pattern.
1745Cylinder Bracket for 120 ltr Capacity Cylinder
1746FIRE DETECTION SYSTEM
1747Supply , Installation , Testing & Commisioning of2 Zone Fire Detection Panel with Cross Zone Gas Release Module with Battery back up
1748Supply , Installation , Testing & Commisioning ofSmoke/Heat /Multi Detector
1749Supply , Installation , Testing & Commisioning of Manual Release Switch
1750Supply , Installation , Testing & Commisioning of Abort Switch
1751Supply , Installation , Testing & Commisioning ofHooter cum Sounder
1752Supply , Installation , Testing & Commisioning of Response Indicator
1753Supplying, laying, testing and commissioning offollowing sizes ofLow Smoke Zero Halogen Silicon Insulated Fire Survival Cable with Drain Wire, solid copper conducter cable approved by LPCB as per BSEN 50200:2015 PH 120 (Fire, Mech Shock & Water 120 Minutes @ 830 deg Celcius, Fire & Mech Shock every 5 Min for 2 Hours- Both test conducted on same sample) and BS-6387 CWZ The cable shall sustain 950 deg. C. For 3 hours approved along with accessories/ termination glands and all necessary materials to complete. The cable shall be approved for. The cable shall be BS EN 60332-1-2:2004 for Bunched Flame Retardancy (installed as a single or bunched cable self extinguishes leaving the upper cable sheath unaffected showing the cable does not propagate fire). Cable shall be guaranteed for 10 years from the date of manufacture marked on the cable. Size :-2C X 1.5sqmm
1754Piping and Installation
1755Discharge Pipe with Support and Fittings, CS Seamless to ASTM A-106 Schedule 40.
1756HVAC WORK
1757AIR HANDLING UNIT (connected To vrv unit) The AHUshall be of double skin construction complete with filter, cooling coil and constant volume supply air fan sections.The unit shall be of uniform cross section throughout and free standing type.Construction shall be prefabricated individual framed sections bolted together with neoprene gaskets between to make a complete unit. All AHU"s shall be ceiling suspended type. The AHU casing to have a "Penta-Post" perimeter frame with wholly be easily removable.Formed from galvanised sheet externally powder coated, rigidly reinforced with 50mm thick foam or fibreglass insulation. The outer skin of casing panels shall be of minimum 1.0mm thick galvanised steel sheet and the internal skin shall be of minimum 0.8mm thick galvanised steel sheet. All air handling units shall include thermal breaks on casing framework,and wherever required to prevent condensation on the casing.Thermal breaks shall be in the form of profiled rubber inserts between internal and external surfaces.AHU Shall be complete with DIDW Centrifugal fan (plugfan/belt driven),straters , with display type thermostat, Squirrel cage induction motor, cooling coil (Copper tubes and Aluminium fins) (DX coil to be seletecd to maitain the desired temperature required)
1758(Ground Floor), 8000 CFM (FM) AHU, 23.0 TR, 4 Row deep DX cooling coil, 45 mm Static Pressure withwith Required H.P 3 Phase motor
1759(Ground Floor), 10000 CFM (FM) AHU, 27.0 TR, 4 Row deep DX cooling coil, 45 mm Static Pressure withwith Required H.P 3 Phase motor
17606500 CFM (FM) AHU, 20.0 TR, 4 Row deep DX cooling coil, 45 mm Static Pressure withwith Required H.P 3 Phase motor
1761(First Floor), 3000 CFM (CS) AHU, 7.5 TR, 4 Row deep DX cooling coil, 30 mm Static Pressure withwith Required H.P 3 Phase motor
1762(Second Floor), 15000 CFM (CS) AHU, 37.5 TR,, 4 Row deep DX cooling coil, 45 mm Static Pressure withwith Required H.P 3 Phase motor
1763CONTROL & TRANSMISSION WIRING
1764Supply, installation, testing and commissioning of2 Core x 1.5 mm2 copper wire in PVC conduit as per specifications for transmission
1765Supply, installation, testing and commissioning of2 Core x 1.5 mm2 copper wire in PVC conduit as per specifications for remotes
1766REFNET(Y-JOINT )
1767Supply,installation,testing and commissioning of Y - Joints with necessary fittings as per specification.
1768AXIAL FLOW FANS
1769"Supply, installation, testing and commissioning of direct driven Axial Flow Fans as shown in drawings and as per specifications.Each fan shall be complete with totally enclosed fan cooled motor IE-3 (IP:55), Starters, metering, power and control wiring between Control panel and Motor etc., motor mount and vibration isolators. Fan motor shall be suitable for 3 Phase, 415 +/- 10% V, 50 HzAC supply.(Motor speed shall not exceed 900 rpm).The Smoke Extraction Fan and its casing shall be suitable for smoke exhaust application and fan shall be AMCA certified. Motor shall be thermally rated (class H) for 250°C for 2 hours as per [BS-7346 Part-2 : 1990] Class-B. Axial Flow Fans with DOL starter below 7.5 HP & Star Delta for 7.5 HPand above"
1770Duty : STP Exhaust
1771Air Quantity: 10,000CFM
1772Static Pressure : 40 mm wg
1773Motor Rating : 7.5 HP (Suggested) or as per requirement
1774Duty : STP Fresh Air
1775Air Quantity: 8,000CFM
1776Static Pressure : 40 mm wg
1777Motor Rating : 5.0 HP (Suggested) or as per requirement
1778Duty : Pump Room Exhaust
1779Air Quantity: 6,000CFM
1780Static Pressure : 40 mm wg
1781Motor Rating : 5.0 HP (Suggested) or as per requirement
1782Duty : Pump Room Fresh Air
1783Air Quantity: 4,000CFM
1784Static Pressure : 40 mm wg
1785Motor Rating : 5.0 HP (Suggested) or as per requirement
1786Duty : Normal & Smoke Exhaust (basment)
1787Air Quantity: 15,000CFM
1788Static Pressure : 40 mm wg
1789Motor Rating : 5.0 HP (Suggested) or as per requirement (Class H Insulation)
1790Duty : LT PANEL Room (Exhaust Air)
1791Air Quantity: 3,500CFM
1792Static Pressure : 40 mm wg
1793Motor Rating : 5.0 HP (Suggested) or as per requirement
1794Duty : LT PANEL Room (Fresh Air)
1795Air Quantity: 3,000CFM
1796Static Pressure : 40 mm wg
1797Motor Rating : 5.0 HP (Suggested) or as per requirement
1798Supply, Installation, Testing and commissioning of single skin Fan Section as shownin drawing and as per specifications. Each unit shall be complete with casing (16G) DIDW centrifugal fan, belt drive, motor(EFF 1 class), Starters, metering, power and control wiring between Control panel and Motor etc, louvers etc. Fan motor shall be suitable for 3 Phase, 415 ± 10% V, 50 HzAC supply.
1799Duty: Lift WellPressurisation
1800Air Quantity : 24,000 CFM
1801Static Pressure: 40 mm wg
1802Motor Rating: 17.5 HP or as per requirement
1803Duty: Lift WellPressurisation
1804Air Quantity : 12,000 CFM
1805Static Pressure: 40 mm wg
1806Motor Rating: 15.0 HP or as per requirement
1807Duty: Lift lobbyPressurisation
1808Air Quantity : 13,500 CFM
1809Static Pressure: 40 mm wg
1810Motor Rating: 7.5 HP
1811Duty: StaircasePressurisation
1812Air Quantity : 13,000 CFM
1813Static Pressure: 40 mm wg
1814Motor Rating: 7.5 HP
1815INLINE FANS
1816Supply, installation, testing and commissioning of inline ducted Fans as shown in drawings. Fan motor shall be suitable for single phase, 50 Hz AC supply. The capacity of the fan given as under:-
1817Air Quantity: 3000 CFM
1818Static Pressure : 25 mm wg
1819Motor rating:As Required
1820Duty : Exhaust
1821Air Quantity: 500 CFM
1822Static Pressure : 15 mm wg
1823Motor rating:As Required
1824Duty : Exhaust
1825Air Quantity: 400 CFM
1826Static Pressure : 15 mm wg
1827Motor rating:As Required
1828Duty : Exhaust
1829GI Propeller Fans
1830Supplying, installing, testing and commissioning of direct driven propeller .Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate with light weight type GI impellers with aerofoil contours for high efficiency & low noise & gravity louvers for weather protection as required. fan suitable for 220 ± 5% volts 50 cycles, 1 phase AC supply.Fan selection arrangement and Electrical characteristics shall be as follows :
1831Air Quantity : 500 CFM , 3 mm St. Pr., 900 RPM or as per OEM, fan suitable for 220 ± 5% volts 50 cycles, 1 phase AC supply.
1832Power : As Required
1833Duty : Exhaust
1834Plastic Propeller Fans
1835Supplying, installing, testing and commissioning of direct driven PROPELLER FANS. Each fan shall be complete with PVC impellers with aerofoil contours for high efficiency & low noise & gravity louvers for weather protection as required. Fan selection arrangement and Electrical characteristics shall be as follows :
1836Air Quantity : 100/150 CFM,5 mm St. Pr., 900 RPM or as per OEM, fan suitable for 220 ± 5% volts 50 cycles, 1 phase AC supply.
1837Power : As Required
1838Duty : Exhaust
1839Air Quantity : 200 CFM,5 mm St. Pr., 900 RPM or as per OEM, fan suitable for 220 ± 5% volts 50 cycles, 1 phase AC supply.
1840Power : As Required
1841Duty : Exhaust
1842Air Quantity : 250 CFM,5 mm St. Pr., 900 RPM or as per OEM, fan suitable for 220 ± 5% volts 50 cycles, 1 phase AC supply.
1843Power : As Required
1844Duty : Exhaust
1845DRAIN PIPING Supply,installation, testing and commissioning of rigid heavy duty PVC piping complete with fittings, support as per drawing and insulated with 6 mm closed cell elastomeric insulation.
184625 mm dia
184732 mm dia
184840 mm dia
1849Supply, installation and balancing of extruded aluminium powder coated air louvers complete with aluminium wire mesh birdscreen & volume conrtol dampers as per specifications.
1850Fresh air louvers
1851Exhaust air louvers(without volume control dampers)
1852HI WALL SPLIT UNITS - INVERTER DRIVEN Supply, Installation, testing and commissioning of Air-cooled Hi-wall split air conditioners each comprising anoutdoorunit(s)consisting of inverter driven compressor, air cooledcondenser,condenser fan along with Cooling thermostats etc. with outer casingand indoor fan coil unit consisting of centrifugal fans,fan motor, DX cooling / Heating coil, outer casing, filter, control and power panel with remote etc. entire cabling and wiring from indoor to outdoor, insulation and with full charge of refrigerant gas and oil, supports, canvas connection etc. complete as per drawings. The indoor and outdoor units shall be with structural steel supports, angles, rods etc. The quoted price shall also include 24 G soft copper refrigerant piping with 13mm "O" class factory backed nitrile rubber with aluminium foil from outdoor unit to indoor unit complete with insulation, refrigerant charging,PVC drain piping with 6mm thick nitrile rubber insulation, supports, clamps, fittings, connections, sleeves, supports, MCB, stabilizer etc from main panel to the unit. The refrigerant used shall CFC Free R-410 A. (Unit will include complete piping/wiring/stand/drain piping or any other acessories required to run the machine etc.)
18531.5 TR Unit
18542 TR Unit
1855LIFT WORK
185620 PASSENGER / 1360 KG LIFT (Main Block)
1857Supply, installation, testing & commissioning of 20 PASSENGER / 1360 KG lift having contract speed of 1.5 MPS serving different floors in the lift shaft. Lift will be complete with combined luminous hall button with seven segment digital hall position indicator at all floor, car operating panel with luminous buttons, seven segment digital car position indicator combined with direction arrows, overload warning indicator, battery operated alarm bell and emergency light, fireman"s switch at main lobby enclosed and as under:-
18581) DESIGN OF LIFTS - PASSENGER TYPE
18592) CAPACITY - 20 PASSENGER / 1360 KG
18603) SPEED - 1.5 m/s
18614) DRIVE - V3F
18625) WITH MACHINE ROOM
18636)TRAVEL - 16.8 Mtr. (Approximate)
18647) FLOORS - B+G+3
18658) NO. OF STOPS - 5 Stops
18669) REQUIRED WELL SIZE - as per Drawing
186710) POWER SUPPLY - 415 V - 3 Phase 50 HZ AC
186811) AUXILIARY - Single Phase 220 V AC
186912) CAR SIZE - Suitable for 20 Passengers
187013) CAR ENCLOSURE
1871a) CAR CEILING - SS HAIRLINE FINISH
1872b) CAR PANELS - SS HAIRLINE FINISH
1873c) ILLUMINATION - LED LIGHT
1874d) CAR FLOORING - 20 MM RECESS (FLOORING BY CUSTOMER)
187514) NO. OF ENTRANCE - ONE LOCATION FRONT
187615) CAR ENTRANCE - AUTOMATIC COPD DOORS IN SS HAIRLINE FINISH
187716) DOOR SAFETY - FULL HEIGHT INFRARED LIGHT CURTAIN
187817) LANDING ENTRANCE - AUTOMATIC COPD DOORS IN SS HAIRLINE FINISH
187918) CONTROL - SELECTIVE COLLECTIVE SIMPLEX
188019) ARD-TO BE PROVIDED
1881Goods Cum, Stretcher Cum16 Passenger / 1088 KG LIFT (Main Block)
1882Supply, installation, testing & commissioning of 16 PASSENGER / 1088 KG lift having contract speed of 1.5 MPS serving different floors in the lift shaft. Lift will be complete with combined luminous hall button with seven segment digital hall position indicator at all floor, car operating panel with luminous buttons, seven segment digital car position indicator combined with direction arrows, overload warning indicator, battery operated alarm bell and emergency light, fireman"s switch at main lobby enclosed and as under:-
18831) DESIGN OF LIFTS - PASSENGER TYPE
18842) CAPACITY - 16 PASSENGER / 1088 KG
18853) SPEED - 1.5 m/s
18864) DRIVE - V3F
18875) WITH MACHINE ROOM
18886)TRAVEL - 16.8 Mtr. (Approximate)
18897) FLOORS - B+G+3
18908) NO. OF STOPS - 5 Stops
18919) REQUIRED WELL SIZE - as per Drawing
189210) POWER SUPPLY - 415 V - 3 Phase 50 HZ AC
189311) AUXILIARY - Single Phase 220 V AC
189412) CAR SIZE - Suitable for 16 Passengers
189513) CAR ENCLOSURE
1896a) CAR CEILING - SS HAIRLINE FINISH
1897b) CAR PANELS - SS HAIRLINE FINISH
1898c) ILLUMINATION - LED LIGHT
1899d) CAR FLOORING - 20 MM RECESS (FLOORING BY CUSTOMER)
190014) NO. OF ENTRANCE - ONE LOCATION FRONT
190115) CAR ENTRANCE - AUTOMATIC COPD DOORS IN SS HAIRLINE FINISH
190216) DOOR SAFETY - FULL HEIGHT INFRARED LIGHT CURTAIN
190317) LANDING ENTRANCE - AUTOMATIC COPD DOORS IN SS HAIRLINE FINISH
190418) CONTROL - SELECTIVE COLLECTIVE SIMPLEX
190519) ARD-TO BE PROVIDED
19068 PASSENGER / 544 KG LIFT (Main Block)
1907Supply, installation, testing & commissioning of 8 PASSENGER / 544 KG lift having contract speed of 1.0 MPS serving different floors in the lift shaft. Lift will be complete with combined luminous hall button with seven segment digital hall position indicator at all floor, car operating panel with luminous buttons, seven segment digital car position indicator combined with direction arrows, overload warning indicator, battery operated alarm bell and emergency light, fireman"s switch at main lobby enclosed and as under:-
19081) DESIGN OF LIFTS - PASSENGER TYPE
19092) CAPACITY - 8 PASSENGER / 544 KG
19103) SPEED - 1.0 m/s
19114) DRIVE - V3F
19125) WITH MACHINE ROOM
19136)TRAVEL - 13.2 Mtr. (Approximate)
19147) FLOORS - G+4
19158) NO. OF STOPS - 5 Stops
19169) REQUIRED WELL SIZE - as per Drawing
191710) POWER SUPPLY - 415 V - 3 Phase 50 HZ AC
191811) AUXILIARY - Single Phase 220 V AC
191912) CAR SIZE - Suitable for 8 Passengers
192013) CAR ENCLOSURE
1921a) CAR CEILING - SS HAIRLINE FINISH
1922b) CAR PANELS - SS HAIRLINE FINISH
1923c) ILLUMINATION - LED LIGHT
1924d) CAR FLOORING - 20 MM RECESS (FLOORING BY CUSTOMER)
192514) NO. OF ENTRANCE - ONE LOCATION FRONT
192615) CAR ENTRANCE - AUTOMATIC COPD DOORS IN SS HAIRLINE FINISH
192716) DOOR SAFETY - FULL HEIGHT INFRARED LIGHT CURTAIN
192817) LANDING ENTRANCE - AUTOMATIC COPD DOORS IN SS HAIRLINE FINISH
192918) CONTROL - SELECTIVE COLLECTIVE SIMPLEX
193019) ARD-TO BE PROVIDED
1931Audio Visual Works
1932Supply, Installation, Testing and Commissioning of 1-chip DLP LASER Phosphor Multimedia Projection system having, 7000 Lumens 20000 hours lamp life,1920 x 1200 WUXGA Native Resolution, Inbuilt blending and warping with automatic caliberation software, 3D ready, 1200000:1 Contrast Ratio, inputs: HDBaseT,HDMI2.0, DVI-D, Active 3D, Motorised zoom and focus, alongwith 1.25-2.0 lens & projector mountin bracket etc. complete with installation as per the site requirement.
1933Supply, Installation, Testing & Commissioning of Retractable Motorised Micro Ceiling Lift Voltage: 220V 50Hx or 110V 60Hx, Projector Size : 500×450×200mm (L×W×H), Bottom Panel Dimension: 50cmx50cm, Loading Capacity: 20KG, Travel Length:100cm with all require accessories etc. all complete.
1934Supply, Installation,Testing & Commissioning ofTab Tensioned 170" diagonal motorized projection screen with an aspect ratio of 16:10. Screen fabric should in accordance with DIN 4102-1 Class B2 materials. Screen should Sustain temperature of 23 ± 2 °C, and a relative humidity of 50 ± 6 %. Should equipped with RS 232/485 Relay Connectivity. Screen Should have Anti Heat Cut off Option to avoid any Calamity at site. Heavy Dowel to maintain Flatness. Screen Fabric should meet the requirements of Class B2 of building materials. Should be supplied with complete standard accessories as required.
1935Supply, Installation, Testing and Commissioning of 65" LCD panel with 3840 X 2160 resolution or better, USB playback,bluetooth and meracast connectivity,4X HDMI 2.0,DP1.2, HDR10,500 nits or better, Video wall mode should be available, contrast ratio : 1200:1, OPS slot,should have 178 degrees viewing angle complete with mounting and accessories.
1936Supply, Installation, Testing and Commissioning of Retractable Cable manager with 2 AC power outlet, retractors for 1 HDMI, & 1x LAN connection and 1x USB C. Should Provide Convenient and Easy–to–Use Connecting — Pull the cable to extend up to 1.8m (5.9ft) from the installation site. The cable automatically locks in position to the desired length. When finished, pull the cable again to retract it into the housing. Should have High–speed HDMI with Ethernet Cable Retractor with HDMI connector,1x USB-C Cable Retractor and 1x CAT 6 Cable Retractor with RJ–45 connector complete with standard accessories as required.
1937Supply, Installation, Testing and Commissioning of 4K60 18G HDMI & USB-C auto switcher with USB 3.0 switching hub, audio de-embed and display control, 1 HDMI input, 1 USB-C input and 1 HDMI output; USB 3.0 hub built in, Built-in EDID management, Supports HDMI 2.0 and HDCP 2.2, complete with standard accessories as required.
1938Supply, lnstallatian, Testing & Commissioning of 8x8, 4K60 4:4:4 / HDR 18G HDMI Matrix switcher with audio de-embed, IR, RS232, & TCP/IP control. All HDMI I/O should support full 18G 4K@60Hz 4:4:4 HDCP 2.2 and 4K HDR. Shall support Third party IR, RS232 and IP control. Shall have Manual DIP switch for EDID management. Shall have Analog and digital de-embedded audio outputs for each output.
1939Supply„lnstallatian, Testing & Commissioning of Wireless Presentation Solution, Enables wireless presentation of 4K Wireless Display, App-free, Wireless Touch, Extended Screen support, shall offer Enterprise Management features, up to four Shared screens simultaneously, and annotate in Office 365 apps and share notes to devices or the front-of-room display, Supports display resolutions up to 4K and FUII HD 1080P and UXGA/WUXGA, Provides HDMI / VGA / mini DisplayPort, and analog audio outputs etc. all compJete.
1940Supply, lnstallatian, Testing & Commissioning of 4x1 HDMI 2.0 Super Slim Auto-switcher, 4K60 4:4:4 / HDR 18G Matrix switcher with audio de-embed, ARC, IR, & RS232 control,shall support auto switching between connected source, shall Support resolutions up to 4k@60Hz, 4:4:4. 8 bit deep color, shall support HDR formats, and should be HDCP 2.2 compliant. Shall support CEC pass through control of source / display.
1941Supply, lnstallatian, Testing & Commissioning of 4K60 4:4:4 / HDR 18G 100m HDMI extender set with IR, RS232, Ethernet Pass Through,Complete set includes TX, RX, power supply, and IR flasher/emitter Extend HDMI 2.0 signals up to 4K@60Hz / 4:4:4 up to 100m (4K 70m / 1080P 100m). Extends bi-directional IR, RS232 and ethernet pass through. Should Support HDR10 and should be HDCP 2.2 compitable.
1942Supply, lnstallatian, Testing & Commissioning of 4K @ 30fps & Full HD 1080p @ 60fps PTZ Camera with minimum 30X Optical Zoom, min 100 Presets, Ethernet Out, HDMI Out, 3G-SDI Out, Audio In, RS232/422 Controls, -170° ~ +170° Panning angle, -30° ~ +90° Tilting angle , Should support PoE
1943Supply, lnstallatian, Testing & Commissioning of Recording, Streaming & Webcasting Hardware simultaneously, Built-in 4 Inputs (HDMI /IP/3G-SDI/DVI) HDMI Out, Can record upto any three inputs simultaneously in a single frame and as well as individual sources simultaneously, Should have minimum 1TB inbuilt storage, Should be able to support minimum 3 unicast streams
1944Supply ,installation ,testing and commissioning of Full HD 1080p60 Hardware based VC endpoint. should support Line input and Line output for audio. . In future should be upgradable to add 2 more microphones. The video conference system shall support both H.323 and SIP. The video conference system should work behind a DHCP network without any NAT, Static IP or Public IP provisioning, • The video codec shall support a minimum 1920x1080 resolution With Progressive Scan @ 30 frames per second.• The video conference system must have automatic noise reduction, automatic gain control and echo cancellation. • The video conference system must support full duplex audio for natural conversations. • The video codec shall support recording of video, audio and presentation to an external appliance. The codec should support either MPEG4 or H.264 video standards. When recording using MPEG4, the recording appliance should not be seen to be a participant in the call, but shall provide a simple recording notification on screen for all participants during the call. • The video conference system shall support NAT/firewall traversal (H.460/SIP), • The video conference system must support SNMP, • The video conference system must have backup and restore functionality. • The video codec should support the following audio and video standards: H.263, H.263+, H.264, G.711, G.722, G.722.1c, MPEG4-AAC-LC. • The video codec should support secure calling with 128b AES encryption using H.235 or SRTP/TLS, including strict compliance. • The video conference system must support Do Not Disturb mode prior to a call and in-call modes. The Video Conference system should be able to join Microsoft Teams connecting Laptop/PC through USB.
1945Supply, lnstallatian, Testing & Commissioning of Joystick for PAN/Tilt/Zoom and Focusing, IP & RS232C/RS455 Communication Interfaces, High Brightness OLED Display, Auto Backlit Keys, Should be able to control minimum 100 Cameras on IP & 10 Cameras through RS232/422, Should support PoE.
1946Supply, lnstallatian, Testing & Commissioning of Multi-View with Streaming Solution for Video Conference. HDMI inputs and outputs with 18Gbps (600MHz) 4K UHD support. Seamless switching (no loss of sync to display) when switching sources in 4x2 matrix mode. Supports the ability to store a multi-window arrangement as a preset that can be recalled later. EDID management. Supports easy adjustment of window size, position and settings in the PiP windowing mode via the WebGUI. Controllable via front panel buttons, WebGUI, Telnet, RS-232. Automatically scales 4K sources to 1080p for USB capture. Supports video timing stabilization to help ensure a reliable and stable USB capture stream. Capturing over USB 3.0 allows uncompressed video and audio data capture(1080p, LPCM 2.0). Capturing over USB 2.0 applies minimal MJPEG compression to the video and audio data (1080p, LPCM 2.0). Supports capturing 2 channel digital audio from either HDMI (LPCM 2.0) or the 3.5mm analog audio input (selectable via capture software). Compliance with the UAC (USB Audio Class) and UVC (USB Video Class) standards, allows the unit to support most common capture and video streaming software’s.
1947Supply, lnstallatian, Testing & Commissioning of 1x4 HDMI Distribution Amplifier / Splitter with 4K60 4:4:4 / HDR 18G capable 2 InputA/splitter with analog and digital audio de-embedding and auto down scaling for max display compatibility. Shall have 2 switchable HDMI inputs and 4 HDMI outputs, Front panel button, RS232, or TCP/IP control for input selection, should be HDCP2.2 compliant. Auto down scaling for maximum compatibility with mixed resolution displays.
1948Supply, Installation, Testing and Commissioning of4K HDMI & USB-C to HDMI Scaler. 18G 4K HDMI to HDMI Digital Scaler with HDMI and USB–C Inputs & HDMI Scaled output up to 4K @ 60 Hz (4:4:4). 2x1 AV switcher, unit up or down scales the selected video signal to 4K @ 60 Hz (4:4:4), Minimum data rate 18 Gbps, HDCP 2.2 and 1.4 compliant, supports CEC, OSD menu, features Input Auto–Switching, Constant Sync on the output even if the input video signal is lost or interrupted, Contact Closure Switches: On a 3–pin terminal block, USB: On a USB–A connector for firmware upgrade, Certification: CE, ISO 9001, ISO 14001, OHSAS 18001. Should be supplied with standard accessories as required.
1949Supply, Installation, Testing and Commissioning of USB 2.0 High Speed High Performance Twisted Pair Extender Set, USB 2.0 100m extension set with type B on Host and Type A on client w/ isochronous data support. Supplies 500mA to USB devices, Complete with standard accessories as required.
1950Supply, Installation, Testing and Commissioning of Digital Graphics Engine for Live Annotation. Provides a high-performance graphics engine for thethird-party touch screen displays. Supports advanced Smart Graphics® technology with dual-window video from HDMI®, DM®, and streaming sources. Its low-profile, surface-mountable design fits virtually anywhere. features a 4K UHD capable HDMI® output for connection to the display device, and includes a USB HID port for touch, mouse, and/or keyboard input. Additional control ports are provided to enable control of the display device and other equipment. Kinetic effects to enhance the feeling of realism, with lists and toolbars that scroll with momentum at the flick of a fingertip. Drag-and-drop objects that snap into place, offering an easy way to switch sources. Dashboard widgets to personalize the touch screen with clocks, weather, news, and other information.
1951Supply, Installation, Testing and Commissioning of 21.5" Retractable monitor. The Smart retractable monitor with a professional electrically retractable 21.5” widescreen monitor to be integrated in furniture. With a 20° automatic tilt, the monitor has a powder coated steel housing and an up-table cover plate in brushed stainless steel. Should include DVI-I and DVI-D inputs which are HDCP compliant. The Smart monitor integrates a patented single motor system activated through push buttons placed on the cover plate. The monitor works with the AHnet protocol (RS422) through CAT5 loop-through cable, individual addressing and termination switch complete with standard accessories as required.
1952Supply, Installation, Testing and Commissioning of Control system have minimum 8 bidirectional RS232, 8 IR, 8 Relays and 8 GP/IO and 1 Ethernet port to control all the devices in the room. Should have inbuilt or external IR sensor/learner to learn IR commandsThe compatible relay controller to control the Projector screen up down should be supplied as a package (may be from same OEM of controller or different).Should have inbuilt processing power and internal storage to store and process the control program.Should be compatible with any (IOS/Android) wireless or wired Touch screen of any size.Additional ports if required can be added with minimum hassle.Should have the flexibility to add as many user interfaces as required. Should have embedded webpage for control port settings. Should have Status LED to check for Control/Connection status. It should have minimum 5 license each included for both iOS & Android application Certification: CE, ISO 9001, ISO 14001, OHSAS 18001. Extra component or equipment maybe added to match the complete specs. Should be supplied with standard accessories as required.
1953Supply, Installation, Testing and Commissioning ofWall & Table Mount PoE Touch Panel have 7” or more IPS color screen.Should have minimum 1280 x 800 resolution, brightness 4000cd/m2, contrast ratio 800:1, 16:10 aspect ratio Should have inbuilt Wi-Fi, 802.11 b/g/n/ac, Bluetooth 4.0 Should have capacitive touch technology. Should support Multitouch. CPU performance: 1.6GHz Quad Core, GPU, 2GB RAM, 16GB flash. Should be able to decode video format HEVC/H.265, H.264, H.263, MPEG–1/2/4, VC–1, VP6/8, RV8/9/10, AVS, MVC, Sorenson Spark, M–JPEG Should be able to encode/stream video format H.264, MVC, VP8, M–JPEG Should have front 2MP camera, HD 720p. Should have Ethernet port 10/100/1000Mbps PoE LAN. Should have inbuilt mic and speaker. Should be provided with table mount & wall mount kit. Secured Operation - Highly secured operation of applications using password protection, hidden control buttons and more. Red LED alert when camera is active. should be possible with Customized GUI using same OEM GUI Software. should support native integration of same OEM enterprise management software. Certification: CE, FCC, ROHS, REACH, ISO 9001, ISO 14001, OHSAS 18001. Extra component or equipment may be added to match the complete specs. Should be supplied with standard accessories as required.
1954Supply, Installation, testing and commissioning of Wireless 10" touch Panel. Should support Wi-Fi (802.11a/b/g/n/ac); dual band (2.4GHz and 5GHz); HT80 with MIMO, Bluetooth 4.2 technology, 500 nits brightness. shall be supplied with Customized GUI software as required to control the AV system.
1955Supply, Installation, Testing and commissioning of Central Conferenec Engine with recording capabilities including software for voting ,room layout , agenda, should have have 4 nos Conference Ports or better, Integrated dynamics processor with programmable threshold, ratio, attack and release of noise gate, AGC and limiter functions, Must have internal Recording capacity of over 100 hours of audio with Single push button to start or stop recordings, ON/OFF Power,System Volume,Recording Indicator LED etc, DLP switch to enable and disable power to the conference ports, Web Server with User-friendly Interface, 1 no. balanced input and 1 no. Blanaced output. 2 Unbalanced Cinch audio inputsand 2 Unbalanced Cinch audio outputs, Audio Routing, Network Monitoring, built-in Diagnostics application and camera control, Loop cabling for redundance in case of failure of unit. It shall have flexibility to attach wireless conference units as well if required in future, Should also support Voting & Interpretaion feature by addiing additional license if required in future.Option to add DANTE network card for Audio over IP in case required for future seamless integartion.USB port for expandable memory to record longer meetings (volumes up to 500 GB), Conference Network Ports shall have minimum speed of 1000 Mbps or better for both upstream and downstream, Control Port Ethernet, Power Supply Included, It shall be complete with Meeting Management Software and license with features like setting up the meeting room and control the settings of the Conference system,add new roles for meeting, the use of meeting template with delegate information, speakers and request lists, view the reports and meeting history,the room layout, and voting results during or after a voting session etc. 19" Rack Mountable, Certification: CE. Country of origin should not be China Approved Make: Televic/Audio-Technica/Sennheiser
1956Supply, Installation, Testing and commissioning of power supply for Audio conference controller. Rated Input Voltage : 100Vac-240Vac, nput Voltage Range :90Vac to 264Vac, Input Frequency Range: 47Hz to 63Hz ( ±1Hz ), Input Current at:100Vac, 240Vac / 5.62A load: = 3.5A, Input Current Harmonic : IEC61000-3-2 Class D, Certification: CB, TUV, UL,
1957Supply, Installation, Testing and commissioning of Programmable touch enabled tabletop conference unit for Delegate/chairman, Multifunctional button for delegate, chairman, Chaiman unit should support below functioanlity › Start / stop recording › Meeting state control › Agenda control, Button for request-to-speak and priority functionality when unit is configured as chairperson, Interactive display showing meeting information such as agenda topic, who is speaking, position in request list, speech timers, Built-in high-quality loudspeaker, Speaker shall automatically muted when the microphone is active, to prevent acoustic feedback, Screw lock or Plugin type microphone connector, 5.2" or better capacitive touch screen with light sensor for automatic luminance adjustmen, Unit should have Guiding dots also make it accessible for visually impaired users, Tactile reference, Haptic feedback on touchscreen, Anti-fingerprint coating, Dual Headphone connector, RJ 45 connectors for loop through cabling, Unit should support Voting, language Selection, Bluetooth, badge identification on Chairman/Delegate units, Conferenec Delegate/Chairman unit should be supplied with 400mm Goosenck with Cardioid/Unidirection Pickup Pattern, Microphone Max SPL @ 1 kHz : 110 dB SPL (1% THD+N), Microphone Signal to noise ratio> 67 dB(A), Microphone should be GSM immune, Bi-colour led ring indication (red / green), Windscreen should be included with gooseneck microphone, Complete with necessary cable and connector, Unit should be CE Certified and should not be manufactured in China.
1958Supply, Installation, Testing and commissioning of Digital beam-steering line array column loudspeaker with onboard DSP and 600 watts (12 x 50 W) of amplification with Twelve (12) x 2.25-inch full-range transducers with 58 Hz – 18 kHz frequency range also Dante digital audio network interface and line-level analog input with Articulated Array configuration which allows wide, 160° horizontal coverage and Modular design allows building vertical arrays using 1-3 units. The system should also have multiple algorithms for beam steering control that designers can optimise consistency of coverage, tonal balance, and maximum SPL per job; Maximum SPL @ 1 m 112 dB SPL (118 dB SPL peak). Should be supplied with standard accessories as required.
1959Supply , installation , testing and commissioning of Ceiling Flush Music/PA Loudspeaker, Free field Frequency range (-10dB) of 84Hz to 19kHz; Power handling of 64 Watt peak; Nominal dispersion of 140° Conical; Free field Sensitivity of 86 dB SPL and Max SPL of 104 dB SPL peak; Nominal Impedance 16 Ohms; Integral multi-tap Transformer with tap settings of 2/4/8/16 W @ 100V. with Powder-coated steel grille; Shall include necessary standard hardware for ceiling install.
1960Supply, Installation, testing and commissioning of intregrated high impedence Class D Dual zone amplifier with output power of upto 2x120W @ 70/100V. frequency response of 55 Hz - 20 kHz (+0/–3 dB, @ 1 W reference 1 kHz); THD <0.3% at rated power. Channel Separation = –60 dBV (below rated power, 1 kHz), Dynamic range > 88 dB.
1961Supply, Installation, Testing and commissioning of AEC capable Digital Audio Conferencing Processor with at least 12 AEC Mic/Line inputs & 8 analog outputs, 24 Bit A-D and D-A Convertors; Sampling Rate : 48 kHz;THD : < 0.002 % ; Channel Separation (Crosstalk) : < 108 dB ; Frequency Response 20 Hz - 20 kHz ; Signal-to-Noise Ratio 90 dB ;Dynamic Range > 115 dB; 5 Control Inputs and Outputs; RS-232 and Ethernet Port for third party Control and Monitoring; 64x64 Bidirectional DANTE Audio Networking ports, Shall include standard Connectivity features like VOIP, POTS, USB Audio etc. inbuilt DSP features like Conference room Routers,Input Equalizers, Router, Band Pass filter, Output Equalizer, Delay, Limiters, gates , Source selectors etc. Shall Support at least 15 remote Zone controllers complete with standard accessories as required.
1962Supply, installation, testing and Commissioning of Wireless Handheld Microphone System, Wireless Microphone system with MHZ carrier frequency band , Up to 16 pre-programmed frequencies within the same frequency band, Audio bandwidth 35 - 20,000 Hz THD at 1 kHz: <0.3%(Receiver) , Signal-to-noise: 120 dB(A)( Receiver), Wideband FM Modulation, Up to 48 Simultaneous channels , Upto 14 hours operation with one single AA battery or better, Pilot Tone, transmission to know the transmitter battery status, Receiver should have microphone level and line level output, Transmitter should have display to show the battery and LED to show the Muted /Unmuted status Sensitivity 6.3 dB V / -100 dBm, Should have Microprocessor-controlled diversity, T.H.D.: 0.7 % (Transmitter), Infrared programmable, RF output power: 10 or 50 mW
1963Supply, installation, testing and Commissioning of Wireless Lavalier Microphone System, Wireless Microphone system with MHZ carrier frequency band , Up to 16 pre-programmed frequencies within the same frequency band, Audio bandwidth 35 - 20,000 Hz THD at 1 kHz: <0.3%(Receiver), Signal-to-noise: 120 dB(A)( Receiver), Wideband FM Modulation Up to 48 Simultaneous channels, Upto 14 hours operation with one single AA battery or better, Pilot Tone transmission to know the transmitter battery status, Receivershould have microphone level and line level output, Transmitter should have display to show the battery and LED to show the Muted /Unmuted status, Sensitivity 6.3 dB V / -100 dBm, Should have Microprocessor-controlled diversity, T.H.D. 0.7 % (Transmitter), Infrared programmable, RF output power: 10 or 50 mW
1964Supply, installation, testing and Commissioning of Wide-band UHF active Antenna and Power Splitter that can feed up to 4 receivers with the RF signal coming from one pair of antennas and also supplied with power to all connected receivers via BNC cables. Splitter should be operate in an extended frequency range of 470 to 952 MHz. It shall be having 2 BNC socket for RF Inputs and having 10nos BNC Socket for RF outputs. Shall include Active Omnidirectional Antenna shall be from the same OEM of Antenna Power Splitter.
1965Supply, Installation, Testing and Commissioning of 24-port 1000base-T Gigabit PoE+ Smart Managed Switch. . Should have Network Protocol and Standards Compatibility IEEE 802.3 Ethernet. IEEE 802.3i 10BASE-T.IEEE 802.1x. Access Control Lists (ACLs) L2 / L3 / L4 complete with standard accessories as required.
1966Supply, Installation, Testing and Commissioning of Wi-Fi router/Access point for wireless meeting collaboration complete with standard accessories as required.
1967Supply, Installation, Testing and Commissioning of 6 ft Premium High Speed HDMI Cables with Ethernet, Full 18 Gig HDMI 2.0 4K@60Hz and HDR Certified by HDMI ATC. Should Support Ethernet, ARC, CEC, and all HDMI Audio formats. NEC CM, CEC CMG FT4, RoHS/REACH Compliant, Complete with standard accessories as required.
1968Supply, Installation, Testing and Commissioning of 10 ft Premium High Speed HDMI Cables with Ethernet, Full 18 Gig HDMI 2.0 4K@60Hz and HDR Certified by HDMI ATC. Should Support Ethernet, ARC, CEC, and all HDMI Audio formats. NEC CM, CEC CMG FT4, RoHS/REACH Compliant, Complete with standard accessories as required.
1969Supply, Installation, Testing and Commissioning of 15 ft Premium High Speed HDMI Cables with Ethernet, Full 18 Gig HDMI 2.0 4K@60Hz and HDR Certified by HDMI ATC. Should Support Ethernet, ARC, CEC, and all HDMI Audio formats. NEC CM, CEC CMG FT4, RoHS/REACH Compliant, Complete with standard accessories as required.
1970Supply, Installation, Testing and Commissioning of 6" Molded USB 2.0 A male to A male. In-Line format, no panel mount option, Molded PVC connector housings. USB 2.0 Hi Speed, Complete with standard accessories as required.
1971Supply, Installation, Testing and Commissioning of Category 6A F/UTP EN Series 23 AWG 4 Pair Shielded Cable. Solid annealed bare copper conductors, High density polyethylene insulation, 4 pairs twisted in varying lays and cabled, Overall aluminum/poly foil shield with drain, Flame rated PVC jacket, TIA/EIA-568-C Category 6A, NEC CMR, CEC CMR FT4, RoHS compliant.
1972Supply, Installation, Testing and Commissioning ofSpeaker Cable – 1.5 Sqmm (48/0.20mm) x 2 core cable ATC copper conductor PVC insulated, core twisted, outer jacketed with Vasiform Type PVC Sheath.
1973Supply, Installation, Testing and Commissioning of 18 AWG microphone cable (24/0.20mm) x 2 core ATC copper conductor, PE insulated, core twisted in a circular form, Inner sheathed with moisture Proof Polymer, braid shielded (80%) with ATC copper, outer Jacketed with Matt finish Rugged Flexible PVC.
1974Supply, installation, testing and Commissioning of Co-axal Cable for Antenna. Should be SDI Coax, RG-6, 18 AWG, Solid BC, Foil + 95% TC Braid, PVC Jkt, CMR complete with standard accessories as required.
1975Supply , installation , testing and commissioning ofWorkstation with i-7 Configuration. Server: Intel Core i7, such as Intel Core i7-4770 Quad-Core 3.4Ghz 8 GB DDR3-1600 RAM 1 Gbit/s Network Hard drive SATA 6 Gbit/s 7200 RPM Enterprise Class – Up to 48 Mbps per drive for optimal performance. Client: Intel Core i7, such as Intel Core i7-4770 Quad Core 3.4Ghz 8 GB DDR3-1600 RAM , Bandwidth supported - Up to 256 Mbit/s video data. Should include Keyboard and Mouse and 21.5" FHD Monitor. Should Include AV Control software with customized GUI,. Audio Conference Management Software andWindow 10.or its equivalent in specifications
1976Supply, Installation, Testing and Commissioning of bulk connectors XLR, RJ-45, Speakon, Phono, Stereo Jack etc as required.
1977Supply, Installation,Testing & Commissioning of 32 U Equipment rack to house all rack mountable equipment, with internal wiring, front glass door,heat dissipation fans,power distribution units etc.complete with standard accessories as required.
1978Supply, Installation, Testing and Commissioning of 1-chip DLP LASER Phosphor Multimedia Projection system having, 7000 Lumens 20000 hours lamp life,1920 x 1200 WUXGA Native Resolution, Inbuilt blending and warping with automatic caliberation software, 3D ready, 1200000:1 Contrast Ratio, inputs: HDBaseT,HDMI2.0, DVI-D, Active 3D, Motorised zoom and focus, alongwith 1.25-2.0 lens & projector mountin bracket etc. complete with installation as per the site requirement.
1979Supply, Installation, Testing & Commissioning of projector mount bracket for above projector complete with standard as required.
1980Supply, Installation,Testing & Commissioning ofTab Tensioned 170" diagonal motorized projection screen with an aspect ratio of 16:10. Screen fabric should in accordance with DIN 4102-1 Class B2 materials. Screen should Sustain temperature of 23 ± 2 °C, and a relative humidity of 50 ± 6 %. Should equipped with RS 232/485 Relay Connectivity. Screen Should have Anti Heat Cut off Option to avoid any Calamity at site. Heavy Dowel to maintain Flatness. Screen Fabric should meet the requirements of Class B2 of building materials. Should be supplied with complete standard accessories as required.
1981Supply, lnstallatian, Testing & Commissioning of 4x1 HDMI 2.0 Super Slim Auto-switcher, 4K60 4:4:4 / HDR 18G Matrix switcher with audio de-embed, ARC, IR, & RS232 control,shall support auto switching between connected source, shall Support resolutions up to 4k@60Hz, 4:4:4. 8 bit deep color, shall support HDR formats, and should be HDCP 2.2 compliant. Shall support CEC pass through control of source / display.
1982Supply„lnstallatian, Testing & Commissioning of Wireless Presentation Solution, Enables wireless presentation of 4K Wireless Display, App-free, Wireless Touch, Extended Screen support, shall offer Enterprise Management features, up to four Shared screens simultaneously, and annotate in Office 365 apps and share notes to devices or the front-of-room display, Supports display resolutions up to 4K and FUII HD 1080P and UXGA/WUXGA, Provides HDMI / VGA / mini DisplayPort, and analog audio outputs etc. all compJete.
1983Supply, Installation,Testing & Commissioning ofHDMI & VGA HDBaseT Wall Plate Extension Set with USB. 4K 10.2G 100M 2 HDMI, VGA, & USB2.0 High Speed Wall Plate extender set with audio pass-through / de-embedding and automated display control. Complete set includes Wall plate TX, RX, Power supply, cover plate, Simple programmable display control using CEC or RS232 protocols to power on/off display automatically or by front panel button on wall plate, Support HDMI input video resolutions up to 4K@60HZ 4:2:0 8 bit deep color. Should be HDCP 2.2 Compitable complete with standard as required.
1984Supply, lnstallatian, Testing & Commissioning of 4K60 4:4:4 / HDR 18G 100m HDMI extender set with IR, RS232, Ethernet Pass Through,Complete set includes TX, RX, power supply, and IR flasher/emitter Extend HDMI 2.0 signals up to 4K@60Hz / 4:4:4 up to 100m (4K 70m / 1080P 100m). Extends bi-directional IR, RS232 and ethernet pass through. Should Support HDR10 and should be HDCP 2.2 compitable.
1985Supply, Installation, Testing and Commissioning of Control System.Controller with Minimum 4 bidirectional RS232, 4 IR, 4 Relays and 4 GP/IO and 1 Ethernet port to control all the devices in the room.Should have inbuilt or external IR sensor/learner to learn IR commands. The compatible relay controller to control the Projector screen up down should be supplied as a package (may be from same OEM of controller or different).Should have inbuilt processing power and internal storage to store and process the control program.Should be compatible with any (IOS/Android) wireless or wired Touch screen of any size.Additional ports if required can be added with minimum hassle.Should have the flexibility to add as many user interfaces as required. Should have embedded webpage for control port settings. Should have Status LED to check for Control/Connection status. It should support PoE. It should have minimum 5 license each included for both iOS & Android application. Certification: CE, ISO 9001, ISO 14001, OHSAS 18001. Extra component or equipment maybe added to match the complete specs.
1986Supply, Installation, Testing and Commissioning ofWall & Table Mount PoE Touch Panel have 7” or more IPS color screen.Should have minimum 1280 x 800 resolution, brightness 4000cd/m2, contrast ratio 800:1, 16:10 aspect ratio Should have inbuilt Wi-Fi, 802.11 b/g/n/ac, Bluetooth 4.0 Should have capacitive touch technology. Should support Multitouch. CPU performance: 1.6GHz Quad Core, GPU, 2GB RAM, 16GB flash. Should be able to decode video format HEVC/H.265, H.264, H.263, MPEG–1/2/4, VC–1, VP6/8, RV8/9/10, AVS, MVC, Sorenson Spark, M–JPEG Should be able to encode/stream video format H.264, MVC, VP8, M–JPEG Should have front 2MP camera, HD 720p. Should have Ethernet port 10/100/1000Mbps PoE LAN. Should have inbuilt mic and speaker. Should be provided with table mount & wall mount kit. Secured Operation - Highly secured operation of applications using password protection, hidden control buttons and more. Red LED alert when camera is active. should be possible with Customized GUI using same OEM GUI Software. should support native integration of same OEM enterprise management software. Certification: CE, FCC, ROHS, REACH, ISO 9001, ISO 14001, OHSAS 18001. Extra component or equipment may be added to match the complete specs. Should be supplied with standard accessories as required.
1987Supply, Installation, testing and commissioning of stackable Wall Mount multi driver (8 or better) Vocal range Column Array loudspeaker with free field frequency range (-10dB) of 100Hz to 16kHz; RMS continuous power handling of 300W better; Nominal dispersion of 120 H X 20 V; full range Sensitivity of 88 Db SPL; Max SPL of 113 dB SPL (119dB peak); Nominal Impedance of 8 ohms; Rugged enclosure with powder coated steel grille. Optional 70/100V OEM transformer module with tap settings of 150/75 W shall be available.Shall be supplied with wall mount bracket complete with standard as required. Approved Makes: Bose / L acoustics / d&b audiotechnik
1988Supply , installation , testing and commissioning of Ceiling Flush Music/PA Loudspeaker, Free field Frequency range (-10dB) of 84Hz to 19kHz; Power handling of 64 Watt peak; Nominal dispersion of 140° Conical; Free field Sensitivity of 86 dB SPL and Max SPL of 104 dB SPL peak; Nominal Impedance 16 Ohms; Integral multi-tap Transformer with tap settings of 2/4/8/16 W @ 100V. with Powder-coated steel grille; Shall include necessary standard hardware for ceiling install.
1989Supply, installation, testing & Comissioning of class D Power amplifier with a Max Output Power of 4x 300W@4-8 ohms as well 70/100V or bridged mode output power of 2x 600W @ 2/4 ohms and 70/100V. Frequency Response of 20Hz - 20 KHz(+/- 1 dB @ 1 W),THD+N <0.04%; Senstivity: -10dBV to +14dBu; A/D and D/A conveters: 24-bit/48KHz; should have built-in DSP functions including SmartBass processing, routing, level control, delays, limiters, Bose loudspeaker EQs, plus input and area EQs Should have 4 outputs with dynamic power >100 dBA, Input impedance 10KO complete with standard accessories as required. Should have Opti-voice paging for smoothtransition between music & announcements; Shall have protection over , high temperature, output short, extra high frequency (EHF), excessively low or high AC line voltage offer & optional Network audio connectivity through RJ-45 port for expansion.
1990Supply, installation, testing and Commissioning of Wireless Handheld Microphone System, Wireless Microphone system with MHZ carrier frequency band , Up to 16 pre-programmed frequencies within the same frequency band, Audio bandwidth 35 - 20,000 Hz THD at 1 kHz: <0.3%(Receiver) , Signal-to-noise: 120 dB(A)( Receiver), Wideband FM Modulation, Up to 48 Simultaneous channels , Upto 14 hours operation with one single AA battery or better, Pilot Tone, transmission to know the transmitter battery status, Receiver should have microphone level and line level output, Transmitter should have display to show the battery and LED to show the Muted /Unmuted status Sensitivity 6.3 dB V / -100 dBm, Should have Microprocessor-controlled diversity, T.H.D.: 0.7 % (Transmitter), Infrared programmable, RF output power: 10 or 50 mW
1991Supply, installation, testing and Commissioning of Wireless Lavalier Microphone System, Wireless Microphone system with MHZ carrier frequency band , Up to 16 pre-programmed frequencies within the same frequency band, Audio bandwidth 35 - 20,000 Hz THD at 1 kHz: <0.3%(Receiver), Signal-to-noise: 120 dB(A)( Receiver), Wideband FM Modulation Up to 48 Simultaneous channels, Upto 14 hours operation with one single AA battery or better, Pilot Tone transmission to know the transmitter battery status, Receivershould have microphone level and line level output, Transmitter should have display to show the battery and LED to show the Muted /Unmuted status, Sensitivity 6.3 dB V / -100 dBm, Should have Microprocessor-controlled diversity, T.H.D. 0.7 % (Transmitter), Infrared programmable, RF output power: 10 or 50 mW
1992Supply, installation, testing and Commissioning of Wired Gooseneck Microphone with Desktop base unit and on/off switch for Podium, Desktop gooseneck Mic, Audio frequency bandwidth =70 - 18000 Hz, Signal to Noise:64 dB-A, Length =500 mm, Voltage =9 to 52 V Power Interface
1993Supply, installation, testing and Commissioning of Small-format Analog Mixing Console with USB I/O andEffects , shall have Input (Mic) - Mic/Line Combo Inputs - 4 , Shall have Input (Mic) - Gain 4 , Shall have Input (Mic) - Inputs with Hi-Z 2 , Shall have Input (Mic) - Peak Light 4 , Shall have Input (Mic) - EQ High 4 , Shall have Input (Mic) - EQ Mid 4 , Shall have Input (Mic) - EQ Low 4 , Shall have Input (Mic) - Pan 4 , Shall have Input (Mic) - Level 4 , Shall have Input (Line) - 1/4" Stereo Line Inputs w/Trim 2 , Shall have Input (Line) - RCA Stereo Line Inputs 1 , Shall have Input (Line) - 1/4" Stereo Line External FX Return 1 , Shall have Input (Line) - Aux/FX 3 , Shall have Input (Line) - Balance 4,Input (USB) - USB Return 2, summed with RCA, to channel 9/10 , Shall have Output - Master Stereo Out 1,Output - Monitor Stereo Out 1 , Shall have Output - Aux Out 1 , Shall have effect Processing -reverb/Chorus/Delay 1 , Effect Processing - Tap Tempo 1 , Shall have Output Control - Master Level Fader 1 , Shall have Output Control - Monitor/Phones Level 1 , Shall have Output Control - Output Meters 4x LED
1994Supply, Installation, Testing and Commissioning of 8-port 1000base-T Gigabit PoE+ Smart Managed Switch. . Should have Network Protocol and Standards Compatibility IEEE 802.3 Ethernet. IEEE 802.3i 10BASE-T.IEEE 802.1x. Access Control Lists (ACLs) L2 / L3 / L4 complete with standard accessories as required.
1995Supply, Installation, Testing and Commissioning of Wi-Fi router/Access point for wireless meeting collaboration complete with standard accessories as required.
1996Supply, Installation, Testing and Commissioning of 6 ft Premium High Speed HDMI Cables with Ethernet, Full 18 Gig HDMI 2.0 4K@60Hz and HDR Certified by HDMI ATC. Should Support Ethernet, ARC, CEC, and all HDMI Audio formats. NEC CM, CEC CMG FT4, RoHS/REACH Compliant, Complete with standard accessories as required.
1997Supply, Installation, Testing and Commissioning of 15 ft Premium High Speed HDMI Cables with Ethernet, Full 18 Gig HDMI 2.0 4K@60Hz and HDR Certified by HDMI ATC. Should Support Ethernet, ARC, CEC, and all HDMI Audio formats. NEC CM, CEC CMG FT4, RoHS/REACH Compliant, Complete with standard accessories as required.
1998Supply, installation , testing and Commissioning of VGA with Audio cable (15 feet). High-performance cable with male 15-pin HD and 3.5mm stereo audio connectors at each end. Should have Gold Plated pins. Should have conductor 26 AWG 7/34 tinned copper All pins should be connected for DDC2 and EDID support. Should be maximum 0.35 inch in diameter. Outer Jacket should be HD polyethylene, Dielectric: Foam polyethylene. Compliance: UL: CL2, CSA: C(UL) CL2
1999Supply, Installation, Testing and Commissioning of Category 6A F/UTP EN Series 23 AWG 4 Pair Shielded Cable. Solid annealed bare copper conductors, High density polyethylene insulation, 4 pairs twisted in varying lays and cabled, Overall aluminum/poly foil shield with drain, Flame rated PVC jacket, TIA/EIA-568-C Category 6A, NEC CMR, CEC CMR FT4, RoHS compliant.
2000Supply, Installation, Testing and Commissioning ofSpeaker Cable – 1.5 Sqmm (48/0.20mm) x 2 core cable ATC copper conductor PVC insulated, core twisted, outer jacketed with Vasiform Type PVC Sheath.
2001Supply, Installation, Testing and Commissioning of 18 AWG microphone cable (24/0.20mm) x 2 core ATC copper conductor, PE insulated, core twisted in a circular form, Inner sheathed with moisture Proof Polymer, braid shielded (80%) with ATC copper, outer Jacketed with Matt finish Rugged Flexible PVC.
2002Supply, Installation, Testing and Commissioning of bulk connectors XLR, RJ-45, Speakon, Phono, Stereo Jack etc as required.
2003Supply, Installation,Testing & Commissioning of 12 U Equipment rack to house all rack mountable equipment, with internal wiring, front glass door,heat dissipation fans,power distribution units etc.complete with standard accessories as required.
2004Supply, Installation, Testing and Commissioning of Video wall with 55" extreme narrow bezel HD resolution panels in 6x2 Matix, brightness should be 500 nits or better, contrast ratio 1200:1 or better, combined bezel size should not exceed 0.88 mm, 4k@60Hz built-in video wall scaling, HDMI 2.0, DP1.2,OPS slot, daisy chain upto 25 panels, inbuilt PiP and PbP and bezel compensation, TAA complied, video wall scaling upto 10X10 panels, viewing angle must be 178 degrees or better. It should be complete with mounting bracket etc. complete with installation as per the site requirement.
2005Supply, Installation,Testing & Commissioning ofVideo wall controller network Based videowall controller with Single Xeon(4core)+800WRPSU + 32GB RAM + 2 x 240GB SSD + Windows 10, 08 X HDMI Inputs 12 X 4K@60Hz HDMI Outputs, 09X 4K video splitter with PSU complete with installation as per the site requirement.
2006Supply, Installation,Testing & Commissioning of Uncompressed 4K AV over IP Transceiver w/ Video wall and Multi-view ability. Should be fully Routable zero latency HDMI 2.0 signals up to 4K60 4:4:4 over standard 10GbE Network, Supports 10Gbps Ethernet networking standards, can extend full 4K60 18Gbps resolutions and capability up to 100 meters using CAT6A cable, Transceiver modes; encoder, decoder or transceiver. Transceiver can act as an encoder and a decoder at the same time, perfect for remote sources. Should support HDR10, should be HDCP 1.4/2.2 Compliant. Should be fully interoperable with other products using SDVoE technology tec, complete with standard accessories as required.
2007Supply, Installation,Testing & Commissioning of AVoIP Management Device.Should include device management software which configures, manages and controls AVoIP devices on a Network. UI Creator control system license allows you build unlimited user interfaces to control the IP video system as well as other components via Ethernet, IR and Serialcomplete with standard accessories as required.
2008Supply, Installation, Testing and Commissioning of Stackable Managed L2/L3 Switch with 24 Ports SFP+. Voice VLAN with SIP, H323 and SCCP protocols detection and LLDP-MED IP phones automatic QoS and VLAN configuration. Comprehensive IPv4/IPv6 static and dynamic routing including Proxy ARP, OSPF, Policy-based routing and automatic 6-to-4 tunneling. Scalable Pro AV deployments L2 multicast. PoE+ (30 watts per port) with hot swap, redundant power supplies and full provisioning. Advanced IPv4/IPv6 security implementation including malicious code detection, DHCP Snooping, IP Source Guard protection and DoS attacks mitigation. Should be Zero Touch AV-over-IP with pre-configured L2 Multicast (SDVoE-ready), Advanced Layer 2, Layer 3 and Layer 4 feature set - no license required - including Policy Based Routing, RIP, VRRP, OSPF and PIM.
2009Supply, Installation, Testing and Commissioning of Category 6A Shielded Patch cords -1 Mtrs. The work area equipment cords shall, be comply with TIA/EIA- 568-B.2-10CommercialBuilding CablingStandards TransmissionPerformanceSpecificationsfor4 pairCategory 6A Cabling.
2010Supply, Installation, Testing and Commissioning of Cat6A jack Panel 24 port Loaded Shielded. It must be made of cold rolled steel, in 24 port configurations. Should come with 24 jack, Each jack for the jack panel must provide a Cap or Shutter to avoid dust and contaminates entering the jack & for 100% dust free environment.
2011Items
2012Supply, Installation, Testing and Commissioning of bulk connectorsetc as required.
2013Supply, Installation,Testing & Commissioning of 15 U Equipment rack to house all rack mountable equipment, with internal wiring, front glass door,heat dissipation fans,power distribution units etc.complete with standard accessories as required.
2014FURNITURE WORK
2015Providing and Placing Cabin Table "STELLAR" of HNI Make . Table Dimensions as mentioned below. Main Table and Side Table made of 36 mm thick Pre Laminated Particle Board with matching 2 mm thick edge Banding. Modesty panels are in 18mm thk Postlaminated finish. The Table tops should have metal inserts on underside for modularity. The screw used should be blunt headed and not sharp headed for metal to metal coupling . Table supports are combination of Metal poles and Gable ends. Access Flap with Cable tray and switch mounting plate is provided on side table for wire management. Side table has a 3 drawer pedestal unit. 3 drawer pedestal unit has castors and pedestal unit has size400mm L x 450mm D x 680mm Ht made up of 18mm thk. Prelaminated Particle Board Caracass having central locking system . 2 Drawers are with roller slide mechanism and Filing Unit is with Ball bearingslides. Back storage is made of 18mm thick pre laminated partical Board conforming to IS : 12823 and ishinged door unit. The back of the unit is made from 18mm prelaminated board. All the exposed edges are with 2mm PVC egde Imported banding & sealed edges are with 0.8mm thick PVC Imported edge banding. The top, side and hinged shutters are sealed with 2mm thick PVC edge banding. BackThe units are assembled by knock down fittings such as Minifix & Dowels. All the hardware and Hinges are from Hettich/Ebco.Warranty 5 years . DY. SP. Control Room & Magistrate Office
2016Main Table :- W2400xD750xH750mm
2017Return :- W1200xD450xH750mm
2018Back Storage :- W2400xD450xH750mm
2019Verta HB with HeadrestChair Leatherite Upholstered Weight activated synchronize Tilt Mechanism with Seat Depth Adjustment. Seat Foam is Moulded PU and has Plastic Inner and Outer cover under it. No wood or ply is used in seat .4D Adjustable Arm withBlack PU Cover on arms.Chair is With Lumbar Support Adjustment and has Black Back Frame Black Y Support Polished Aluminium Base with Twin wheel castors. WARRANTY: 10 Years from the date of invoice
2020Main Chair
2021Providing and supplying HNI Model Quip Medium Back Chair .This is a Mediumback chair with Mesh Back with back tilt tension adjustable . The chair mesh is available in 6 different colours ( Green / Ruby / Cinnamon / Magenta / Indigo / Black ) with matching or contrast seat fabric according to the choice of the client . The chair has Adjustable Lumber Support . The Chair has Nylon base with 60 mm twin wheel castors .Chair comes with1-D adjustable armrests with PU Pads . Seat size is 490 mm W x 435 mm D and the Chair Height 975 mm - 1070 mm . Overall size of the chair is 630mm W x 550 mm D x (975 mm- 1070mm) H. The chair has Pneumatic Gas Liftwith Stroke=85 mm . Chair carries a warranty of 5 years.
2022Assistant Chair
2023Libro MB Back Height - Medium Back Back Finish - Mesh with adjustable lumbar support Back Frame - Black Color Seat Finish - Fabric - Black Seat Height Adjustment - Pneumatic Mechanism - Synchronized Tilt Back Tilt Lock - Upright Position Back Tilt Tension - Adjustable Armrests Type - 1D Height Adjustable Armpads Type - Metal Base Type - 5-Star in Nylone Base Warranty : 3 years from the date of invoice
2024Visitor Chair/ Workstation Chair / VIP Monitoring Room & CCTV Superviellance Chair / Meeting Room Chair / Conference Room Other Chair
2025Providing & Fixing of sofa . the inside frame is made of seasoned wood and has antitermite treatment. The seat and back are made of foam and is finished in leatherite upholestry. The structure is supported on Polished Solid Wood Legs. Leatherite colour and type as per directions of Engineer in Charge. The above furniture should be as per specification and sample approved by client.
20263 Seater Sofa
2027Supply and placing centre table in position with sizes 900mm(W)x500 - 600mm(D)x400mm(H)with top made of 10mm thick glass top supported on SS Studs on understructure ofPrelaminated Particle Board. The Table shall have another shelf at lower level The work shall be carried out as per the instructions received from engineer-incharge.
2028Centre Table :- W900xD500xH400mm
2029Providing & Fixing of Table having dimension 500mm Lx 500mm W x 400mm Ht made of 18mm thick prelaminated particle board .The top is 10mm thick Glass supported on 4 nos. SS Studswith verticals also made of 18mm Particle board.The table has a shelf of 450mm L x 450mm W under the main top. All edges are sealed with 2 mm thick PVC Lipping. The above furniture should be as per specification and sample approved by client.
2030Corner Table :- W500xD500xH400mm
2031Providing and placing HNI make "Pinnacle Table ", Main Table .......mm L x .......mm W x750mm D, made up of 25mm thk. Prelaminated particle Board with 2mm PVC Edge Banding supported on Gable ends made out of 25mm thk prelam particle boards with 2mm thk PVC edge banding. The Worktops should have metal inserts on underside for modularity. The screw used should be blunt headed and not sharp headed for metal to metal coupling. Modesty panels is in 18mm thk Prelaminated finish. Separate provision for mounting switches on the wall adjoining the tables shall be made by customer as the tables do not come with switch mounting facility. Wire routing / wire management groumets shall be provided on main Table. Side Table of size ......mm L x 500mm D x 750mm Ht made up of 25mm thick Prelaminated particle Board with 2mm PVC Edge Banding supportedon Gable ends made out of 25mm thk prelam particle boards with 2mm thk PVC edge banding. Modesty panels are in 18mm thk Prelaminated Particle finish.Side Table hasPedestal unit of size 400mm L x 450mm D x 680mm made up of 18mm thk. Prelam particle board conforming to IS : 12823 Interior Grade with 3 Drawer ( 2 Drawer + 1 Filing ) with roller slide mechanism for 2 Drawers and Ball bearing slide for 1 Filng Unit. Back storage is made of 18mm thick pre laminated partical Board conforming to IS : 12823 and ishinged door unit. The back of the unit is made from 18mm prelaminated board. All the exposed edges are with 2mm PVC egde Imported banding & sealed edges are with 0.8mm thick PVC Imported edge banding. The top, side and hinged shutters are sealed with 2mm thick PVC edge banding. BackThe units are assembled by knock down fittings such as Minifix & Dowels. All the hardware and Hinges are from Hettich/Ebco.Warranty 5 years . Senior Officer Cabin / Admin Office
2032Main Table Type - 01 :- W2100xD750xH750mm
2033Main Table Type - 02 :- W2550xD1200xH750m
2034Return Type - 01 :- W1050xD500xH750mm
2035Return Type - 02 :- W1350xD500xH750mm
2036Back Storage :- W1950xD450xH750mm
2037Providing and supplying HNI Model Ativo High Back Chair with head rest .This is a Highback chair with Mesh Back with back tilt tension adjustable . The chair has Adjustable Lumber Support . The Chair has Nylon base with 60 mm twin wheel castors .Chair has 1-D adjustable armrests with PU Pads . Seat size is 500 mm W x 515 mm D and the Chair Height 1135mm - 1225mm . Overall size of the chair is 640mm W x 665mm D x (985 mm- 1220mm) H . The PU foam used for chair seat is fire retardant. The chair has Pneumatic Gas Liftwith Stroke=85 mm . Chair carries a warranty of 5 years.
2038Main Chair
2039Providing and supplying HNI Model Certo Medium Back Chair .This is a Mediumback chair with Mesh Back with back tilt tension adjustable .The chair has AnchoredLumber Support . The Chair has Nylon base with 50 mm twin wheel castors .Chair comes with1-D adjustable PP armrests . Seat size is 500 mm W x 520 mm D and the Chair Height 985 mm - 1080 mm . Overall size of the chair is 635mm W x 605 mm D x (985 mm- 1080mm) H . The PU foam used for chair seat is fire retardant. The chair has Pneumatic Gas Liftwith Stroke=85 mm . WARRANTY: 3 Years from the date of invoice .
2040Visitor Chair / Reception Chair
2041Providing & Fixing of sofa . The inside frame is made of seasoned wood and has antitermite treatment. The seat and back are made of foam and is finished in leatherite upholestry. The Frame base has Webbing for Supporting the Cushions. The Complete Sofa Body has Polyurethane Foam in desired shape. The Sofa is supported on Metal Chrome Plated Legs. Leatherite colour and type as per directions of Engineer in Charge.
20422 Seater Sofa
2043Providing and Supplying HNI Make Office Table having Dimension 1200mm L x 600mm W x 750mm Ht. Worktop is made of 25mmthick PLPB of Grade II, Type IIconforming to IS:12823: 1990 and having 2mm thick pvc edge lipping, Understructure is made of 18mm thick PLPB of Grade II, Type IIconforming to IS:12823: 1990 and having 2mm thick pvc edge lipping .Three no Drawer is built into the table.The Drawers have lock and each drawer is provided with Pull out Handle.5 Year Warranty. Staff Cabin
2044Main Table :- W1500xD750xH750mm
2045ATIVO MB Back Height - Medium Back Back Finish - Mesh with adjustable lumbar support Back Frame - Black Color Seat Finish - Fabric ( Black) Seat Height Adjustment - Pneumatic Mechanism - Synchronized Tilt Back Tilt Lock - Upright Position Back Tilt Tension - Adjustable Armrests Type - 1D Height Adjustable Armpads Type - Polyurethane Base Type - 5-Star in Black nylon WARRANTY: 5 Years from the date of invoice
2046Main Chair
20471. Leatherette Upholstered Seat & Back 2. Seat Size-530 mm W X470 mm D 3. Back Size – 530 mm W X460 mm HT 4. Base - Powder Coated fixed Base 5. Overall Chair Size - 618 mm W X 615 mm D X 815 mm H
2048Visitor Chair /Training Chair
2049Providing and placing HNI make "Connect"Curvilinear Workstation.Frame is 50 mm thick and made ofverticalAluminium Extrusions of 1.9 mm to 2mm thickness. Horizontal Member of frame are CRCA 0.8mm Thick. The System is complete hollow system with space for wire reticulation . All the frames will be duly powder coated . All the frames are fastened together by means of M6 NUTS & BOLTS .All the frames are fitted with M10 leveling bolts.board.Raceway :-The raceway cover are sliding type and are integrally fitting inside frame andare made out of 0.8mm - 1mm thick CRCA steel & powder coated.The electrical raceway can be provided below worktop or above worktop.The partition hasintegrated raceway provided one at skirting level thereby making 2 Raceways.Corner and End Post are made of 1.6mm Thick Aluminium Extrusion , Vertical Trims are made of 1.3mm Thick Aluminium and Horizontal Trims are made of 1.1mm thick Aluminium and are duly powder coated. The free space available within raceway accommodates power, data and communication cables. The cable can be taken into the Frame from the floor from the bottom. Tiles: Fabric Tile: Constructed out of 4mm thick Medium Density Fiber Board (MDF) and covered with Fabric of choice.Laminate Tile: Made out of 5mm -6 mm thick Pre-laminated Medium Density Fiber Board (MDF). Bottom Row of Steel Tile: Constructed out of 0.7mm CRCA sheet and finished in epoxy powder coating. Can be given with plain / perforations / embossed finishes. Magnetic tile: Constructed out of 0.7mm Galvanized sheet and covered with fabric of choice. Pin up tile is made of 4.5mm Bubble Guard Sheet + Fabric wrapped. Whiteboard marker tiles: Made out of 4mm MDF with 1mm glossy highly wear resistant face laminate . Total thickness is 5mm.Table tops and Gable ends are of 25mm thk Pre-laminated particleboards conforming to IS : 12823 Interior Grade. All Worktops to have Metal Insets for fixing screws. Powder coated M.S. brackets having 2mm thickness fixed to the partition frame support the tabletops. Gable ends are of 25mm thk. both side laminate (BSL) with 2mm PVC edge banding on front side. Gable Ends are fixed with 2mm thick MS brackets to Frame and with 2mm thick Brackets to Worktops. Sealed edge in table top and gable ends are with2mm thick PVC edge banding on Working side and 0.8mm thick edge banding on non working side. WARRANTY: 10 Years from the date of invoice
2050Workstation :- W1500x1500xD600xH1200mm
2051Laminate pedestal unit having Dimension 400mm W x 450mm D x 621mm Ht and shall consist of One pencil tray, 2 drawers and one filing box.It is made of 18mm prelaminated particle board . It shall be provided with 2 lockable and two free twin wheeled castors.The pedestals shall have central locking mechanism.It has roller slide mechanism for 2 Drawers and Ball bearing slide for 1 Filng Unit.The pencil tray shall be made of2mm moulded HIPS and shall be fitted inside the first drawer.It should freely slide in horizontal direction.The pencil tray shall have necessary compartments (Miniumum 3 compartments) for keeping stationary items.
2052Pedestal :- W400xD450xH621mm
2053Providing and placing HNI MakeTablecompletely made up of Prelaminated particle board conforming to IS : 12823 Interior Grade with PVC edge banding. Top are with 25mm thk boards.The Worktops should have metal inserts on underside for modularity. The screw used should be blunt headed and not sharp headed for metal to metal coupling . Table top issupported on 18mm thick Gable ends and 18mm thk Modesty panels. exposed edges are in 2mm thk PVC edge banding & sealed edges are in 0.8mm thk PVC edge banding. Separate provision for mounting switches on the wall adjoining the tables shall be made by customer as the tables do not come with switch mounting facility.Main table hasPedestal unit of size 400mm L x 450mm D x 680mm made up of 18mm thk. Prelam particle board conforming to IS : 12823 Interior Grade with 3 Drawer ( 2 Drawer + 1 Filing ) with roller slide mechanism for 2 Drawers and Ball bearing slide for 1 Filng Unit. Side storage is made of 18mm thick pre laminated partical Board conforming to IS : 12823 and ishinged door unit. The back of the unit is made from 18mm prelaminated board. All the exposed edges are with 2mm PVC egde Imported banding & sealed edges are with 0.8mm thick PVC Imported edge banding. The top, side and hinged shutters are sealed with 2mm thick PVC edge banding. BackThe units are assembled by knock down fittings such as Minifix & Dowels. All the hardware and Hinges are from Hettich/Ebco.Warranty 5 years . Cabin & Technical Staff
2054Main Table :- W1500xD750xH750mm
2055Return :- W900xD450xH750mm
2056Providing and supplying HNI Model Quip High Back Chair with head rest .This is a Highback chair with Mesh Back with back tilt tension adjustable . The chair mesh is available in 6 different colours ( Green / Ruby / Cinnamon / Magenta / Indigo / Black ) with matching or contrast seat fabric according to the choice of the client..The chair has Adjustable Lumber Support . The Chair has Nylon base with 60 mm twin wheel castors .Chair has 1-D adjustable armrests with PU Pads . Seat size is 490 mm W x 435 mm D and the Chair Height 1135mm - 1225mm . Overall size of the chair is 640mm W x 665mm D x (985 mm- 1220mm) H.The chair has Pneumatic Gas Liftwith Stroke=85 mm . Chair carries a warranty of 5 years.
2057Main Chair
2058Providing and placing HNI Trent Prelaminated Particle Board storage with openable doors of 1200mm(ht), made up of 18mm thick prelaminated particle board with PVC edge banding and locking arrangement.Storage body is made of 18mm thick pre laminated partical Board conforming to IS : 12823 Interior Grade.The back of the unit is made from 18mm prelaminated board. All the exposed edges are with 2mm PVC egde Imported banding & sealed edges are with 0.8mm thick PVC Imported edge banding. The top, side and hinged shutters are sealed with 2mm thick PVC edge banding. Storage has adjustable shelves inside and cam lock, tower bolt and locking strips.The units are assembled by knock down fittings such as Minifix & Dowels. All the hardware and Hinges are from Hettich/Ebco. Storage has Brushed SS finish handles and lock .Prelam storage unit of 1200mm ht and 450mm depth ( SQFT) RO
2059Storage :- W900xD450xH1200mm
2060Providing & Supplying HNI Make Tablewith dimensions as mentioned above. For main table orktop is made owf 25mm thick Prelaminated particle board with 2 mm thick PVC Lipping on the edges. The worktop is supported on loop shaped Metal Legs 50mm x 50mm , powder coated understructure with Laminate / metal Modesty panel. The Metal legs are connected by Metal Beams for stability and . The Table tops should have metal inserts on underside for modularity. The screw used should be blunt headed and not sharp headed for metal to metal coupling . Colour as per direction of Engineer in Charge. Warranty 5 years . VIP Monitoring Room & CCTV Superviellance
2061VIP Monitoring Room & CCTV Superviellance Table :- W2850xD600xH750mm
2062Providing & Supplying HNI Make Tablewith dimensions as mentioned above. For main table and side tableWorktop is made of 25mm thick Prelaminated particle board with 2 mm thick PVC Lipping on the edges. The worktop is supported on inclinedMetal Legs 50mm x 50mm , powder coated understructure with Laminate / metal Modesty panel. The Metal legs are connected by Metal Beams for stability and . The Table tops should have metal inserts on underside for modularity. The screw used should be blunt headed and not sharp headed for metal to metal coupling . Colour as per direction of Engineer in Charge. Warranty 5 years . Briefing Hall Training Centre & Call Taker Agent / Supervisor Hall / Staff Command & Control Center
2063Main Table :- W3750xD750xH750mm
2064Providing and Supplying HNI make Model AlfaTable having Dimension 1500mm L x 750mm W x 750mm Ht. Understructure is made of Powder coated CRCA Leg with 25 mm thick PLPB with 2mm PVC Lipping.The The rectengular worksurface shall be made ofprelaminated particle board of 25mm thickness of Grade II, Type IIconforming to IS:12823: 1990 and having 2mm thick pvc edge lipping. All the worktops should have metal inserts on the underside of worktops for coupling with metal screws for complete modularity. The understructure has metal CRCA legs of702(ht)mm duly powder coated to 40-60 micron thickness. C-Legs is made up of Foot & vertical member. Foot is bended in triangular shape in 2mm CRCA sheet and vertical structure (1mm thick CRCA x213mmx676mmx30mm) is bended in single sheet.The legs have ABS plastic end caps and levellers. Modesty Panel is Perforated Steel Panel duly powder coated and made of 0.8mm Thick CRCA Steel.
2065Training Table :- W1500xD750xH750mm
2066Libro MB Back Height - Medium Back Back Finish - Mesh with adjustable lumbar support Back Frame - Black Color Seat Finish - Fabric - Black Seat Height Adjustment - Pneumatic Mechanism - Synchronized Tilt Back Tilt Lock - Upright Position Back Tilt Tension - Adjustable Armrests Type - 1D Height Adjustable Armpads Type - Metal Base Type - 5-Star in Nylone Base Warranty : 3 years from the date of invoice
2067Workstation Chair
2068Providing and placing HNI Trent Prelaminated Particle Board storage with openable doors of 1200mm(ht), made up of 18mm thick prelaminated particle board with PVC edge banding and locking arrangement.Storage body is made of 18mm thick pre laminated partical Board conforming to IS : 12823 Interior Grade.The back of the unit is made from 18mm prelaminated board. All the exposed edges are with 2mm PVC egde Imported banding & sealed edges are with 0.8mm thick PVC Imported edge banding. The top, side and hinged shutters are sealed with 2mm thick PVC edge banding. Storage has adjustable shelves inside and cam lock, tower bolt and locking strips.The units are assembled by knock down fittings such as Minifix & Dowels. All the hardware and Hinges are from Hettich/Ebco. Storage has Brushed SS finish handles and lock .Prelam storage unit of 1200mm ht and 450mm depth ( SQFT) RO
2069Storage :- W95--750xD450xH1200mm
2070Storage :- W900xD450xH1200mm
2071Storage :- W2550xD450xH1200mm
2072Storage :- W3900xD450xH1200mm
2073Providing and Supplying HNI Make Office Table having Dimension 1200mm L x 600mm W x 750mm Ht. Worktop is made of 25mmthick PLPB of Grade II, Type IIconforming to IS:12823: 1990 and having 2mm thick pvc edge lipping, Understructure is made of 18mm thick PLPB of Grade II, Type IIconforming to IS:12823: 1990 and having 2mm thick pvc edge lipping .Three no Drawer is built into the table.The Drawers have lock and each drawer is provided with Pull out Handle.5 Year Warranty. Record Room
2074Main Table :- W1200xD750xH750mm
2075Providing and placing HNI Trent Prelaminated Particle Board storage with openable doors of 1200mm(ht), made up of 18mm thick prelaminated particle board with PVC edge banding and locking arrangement.Storage body is made of 18mm thick pre laminated partical Board conforming to IS : 12823 Interior Grade.The back of the unit is made from 18mm prelaminated board. All the exposed edges are with 2mm PVC egde Imported banding & sealed edges are with 0.8mm thick PVC Imported edge banding. The top, side and hinged shutters are sealed with 2mm thick PVC edge banding. Storage has adjustable shelves inside and cam lock, tower bolt and locking strips.The units are assembled by knock down fittings such as Minifix & Dowels. All the hardware and Hinges are from Hettich/Ebco. Storage has Brushed SS finish handles and lock .Prelam storage unit of 1200mm ht and 450mm depth ( SQFT) RO
2076Storage :- W900xD450xH1200mm
2077Providing & Fixing of HNI "Ensemble " Confetrence table of Size 4650mm x 1200mm. the Worktop shall be made of 25mm Prelamparticle Board of Grade II , Type-II as per IS:12823 and backing laminate of 0.6mm All the exposed edges are finished with 2mm thick PVC lippingmachine pressed. The Table tops should have metal inserts on underside for modularity. The screw used should be blunt headed and not sharp headed for metal to metal coupling .Legs are made of Aluminum Extrusion of 1.6mm thickness with aesthically designed elliptical Cover sections . Legs are designed to facilitate wire management . Cross Member are in CRCA steel and the Beam is made of MS and has size 75x50 mm of 1.5mm thickness in powder coated finish of 50 microns thickness and is connected with legs to allow for traversing of wires horizontally. The beam raceway provided with slots for fixing data and electrical switches and sockets for each user under the table. The above furniture should be as per specification and sample approved by client. Meeting Room
2078Meeting Room Table :- W4650xD1200xH750mm
2079Providing and placing Meeting Room table in "U" Shape. Table Tops – Available in standard modules 1500mm L x 600mm D / 1350mm L x 600mm D / 1200mm L x 600mm D / 1050mm L x 600mm D / 900mm L x 600mm D /750mm L x 600mm D, made of 25mm thick Prelaminated Partlice Board. The Table tops should have metal inserts on underside for modularity. The screw used should be blunt headed and not sharp headed for metal to metal coupling .Understructure – Legs made of 18mm thick Prelaminated Particle Board panels interconnected with 18mm thick pre-laminated modesty panels, with height adjustable levelers to take care of uneven floors. Wire Management – Concealed wire management to take care of basic wiring requirements both horizontally & vertically.Cable Tray is mounted on the inner side of modesty panel for horizontal wire carrying. Vertical wire management is through flexible vertical wire manager at one place . Slots for Mounting Data and Electric Switches and Sockets are provided on Cover Section of Cable Tray.Standard table top height – 750mm.Designed for Flexibility through modular Construction, Provision for easy wire management, Upgradeable / reconfigurable for future needs. Corners are Provided in 25mm thickness . Corners are supported on 63.5mm Painted Metal Pole with Leveller for Height Adjustment. Conference Rooom
2080U - Shape Conference Table :- W15000xD3000x900xH750mm
2081Providing & Placing Bed of size 2000 mm x 900mm The top of the bed is 18 mm thick ISI marked Pre-laminated Board,grade conforming to IS:12406 fixed on 19mm x19mm cross stiffeners frame. The 3 sides of the bed to be in 50x25mm MS Tubes and cladded with 18 mm thickPre-laminatedboard , conforming toIS:12406 . The head & Foot rest to be as per drawing in 18mm Pre-laminatedboardconforming to IS:12406 to achieve shape and design. The bed has four legs made out of 50x25x1.6mm thk MS tubes.All Metal Parts is Duly Powder Coated with 45 microns.(Without Matress) Rest Room
2082Single Bed
2083Providing and Supplying Bed Side Table made of 18mm thick PLPB with PVC Edge Banding. Each Bed Side Table has 2 Nos Pull Out Drawers. The Table Dimension is 500 mm Ht x 450mm D x 400mm Width. Each Bed side Table has Levellers on Underside.
2084Bed Side Table
2085Providing & Fixing of sofa . The inside frame is made of seasoned wood and has antitermite treatment. The seat and back are made of foam and is finished in leatherite upholestry. The Frame base has Webbing for Supporting the Cushions. The Complete Sofa Body has Polyurethane Foam in desired shape. The Sofa is supported on Metal Chrome Plated Legs. Leatherite colour and type as per directions of Engineer in Charge.
20861 Seater Sofa
2087Providing and placing HNI make round centre table with 600mm dia . Table top is made of 25 mm thick prelaminated particle board .All the exposed edges are with 2mm PVC egde Imported banding & sealed edges are with 0.8mm thick PVC Imported edge banding . Understructure is made of ss with 475mm dia . Table height is 400mm . Warranty 5 years .
2088Round Corner Table :- W600mm Dia.
2089Providing & Fixing of HNI Make table of Size 1050mm x 1050mm. The Worktop shall be made of 25mm Prelamparticle Board of Grade II , Type-II as per IS:12823 and backing laminate of 0.6mm All the exposed edges are finished with 2mm thick PVC lippingmachine pressed. Legs are made of powdered coated steel 50mmx 50mm Section.Cross Member are in CRCA steel and the Beam is made of MSof 1.5mm thickness in powder coated finish of 50 microns thickness . The above furniture should be as per specification and sample approved by client. Cafeteria
2090Café Table :- W1050xD1050xH750mm
2091Model no: MANTO •Back Finish - Plastic Shell (Red , Orange and Blue colour) •Seat Finish - Plastic Shell (Red , Orange and Blue colour) •Base Type -Sledge base, powder-coated in Silver color •Stackability - up to 6- high on the floor.Seat size - 446 W X 430 D , back height (From Seat to Top of Back Frame) is 410mm . The chair comes with sledge base of size500 W x 490 D
2092Café Chair
2093Providing and supplying Reception Desk having Dimension 1200mm L x 600mm x 1185mm Height . It has 25mm thick Worktop and Gable Ends made of pre Laminated Particle Board sealed with PVC Edge Banding. Front and Modesty Panel are 18mm thick Pre Laminated ParticleBoard Sealed with PVC EdgeBanding.. The Counter Top is 25 mm Thick Postformed ParticleBoard.Unit has One Pull out drawer with Lock and Handle. Reception / Waiting Lobby / Anti Space
2094Reception Table :- W1200xD600xH1185mm
2095Providing and supplying Reception Desk having Dimension ............mm L x 600mm x 1185mm Height . It has 25mm thick Worktop and Gable Ends made of pre Laminated Particle Board sealed with PVC Edge Banding. Front and Modesty Panel are 18mm thick Pre Laminated ParticleBoard Sealed with PVC EdgeBanding.. The Counter Top is 25 mm Thick Postformed ParticleBoard.Unit has One Pull out drawer with Lock and Handle.
2096Reception Table :- W4350xD600xH1185mm
2097Providing and placingstorage. Storage body is made of 18mm thick pre laminated partical Board conforming to IS : 12823. The back of the unit is made from 18mm prelaminated board. All the exposed edges are with 2mm PVC egde Imported banding & sealed edges are with 0.8mm thick PVC Imported edge banding. The top, side and hinged shutters are sealed with 2mm thick PVC edge banding.Storage has adjustable shelves inside and cam lock, tower bolt and locking strips. The units are assembled by knock down fittings such as Minifix & Dowels. All the hardware and Hinges are from Hettich/Ebco.
2098Back Storage :- W4350xD450xH750mm
2099HNI make centre table in position with sizes 900 mm L x 500mm D x 400mm H with completely made of 25mm thick prelaminated particle. The Table have one pull out drawer and another shelf at lower level. 25mm thick particle board Top with edges sealed with PVC lipping. 25mm thick particle board Gable ends with edges sealed with PVClipping. 18mm thick particle board Modesty panel with edges sealed with PVC lipping. 0-20mm adjustable levelers. 1 Drawer.
2100Centre Table :- W900xD500xH400mm
2101HNI Make Corner Table having dimension 500mm L x 500mm W x 400mm H with completely made of 25mm thick prelaminated particle board . Verticals also made of 25mm Particle board. All edges are sealed with 2 mm thick PVC Lipping. 25mm thick particle board Top with edges sealed with PVC lipping. 25mm thick particle board Gable ends with edges sealed with PVC lipping. 18mm thick particle board Modesty panel with edges sealed withPVC lipping. 0-20mm adjustable levelers.
2102Corner Table :- W500xD500xH400mm
2103Add 18 % GST
2104Add 1% Labour Cess