Tender For Comprehensive Maintenance Of Fire Alarm Panel Detector And Allied Works At Af Stn Kalalikunda Under Ge (Af) Kalaikunda, kalaikunda-West Bengal

Military Engineer Services-MES has published Tender For Comprehensive Maintenance Of Fire Alarm Panel Detector And Allied Works At Af Stn Kalalikunda Under Ge (Af) Kalaikunda. Submission Date for this Tender is 20-05-2023. Fire Alarm Systems Tenders in kalaikunda West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

37378266
Corrigendum : Tender For Comprehensive Maintenance Of Fire Alarm Panel Detector And Allied Works At Af Stn Kalalikunda Under Ge (Af) Kalaikunda
Open Tender
Indian
West Bengal
kalaikunda
20-05-2023

Tender Details

Comprehensive Maintenance Of Fire Alarm Panel Detector And Allied Works At Af Stn Kalalikunda Under Ge (Af) Kalaikunda Comprehensive Maintenance Of Fire Alarm Panel Detector And Allied Works

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 08-May-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 15-05-2023
2 15-May-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 20-05-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 44000.0 /-
Tender Value
INR 22 Lakhs /-

BOQ Items

Name of Work : COMPREHENSIVE MAINTENANCE OF FIRE ALARM PANEL DETECTOR AND ALLIED WORKS AT AF STN KALALIKUNDA UNDER GE (AF) KALAIKUNDA
Sl. No. Item Description
1Comprenesive maintenance and repair including renewal/replacement and installation of defective parts of all existing fire detection system complete consisting of addressable fire control panel 19 Nos., Conventional Fire Alarm Panel 11 Nos., Remote Terminal Unit panels 20 Nos., smoke/heat detector, response indicator, sounder, Manual call Point, Amlifier 20 Nos, Loud speaker, Loop isolator, Zone monitor module, Modem etc. located in technical and domestic area ,to make them 100 % serviceable incl checking of fire detector, checking the batteries and its connections, alarm system and itsfunctions, functionallity of fire controlpanel and indicating eqpt all to be checked by the operation of trigger device in each zone as described. The system installed in Fire station and at other locationsto be inspected and checked for its functionality and to make functional in all respect and if any defect observed to rectify it by visiting every monththrough Authorised Original Equipment Manufacturer"s Service Centre Engineersor through OEM Certified Agencies as approved by GE, complete all as specified and as directed. Note:- (i) Cost of new components shall be paid separately under relevant items. (ii) Contractor"s rep shall visit every month to check all fire panel and systemto check its functionility and to make them functional. if any defect observed. (iii) He shall take the serviceability certificate duly signed by the user and submit to the department. After obtaining / producing seviceability certificate of system payment will be made to contractor .(ii) The Contractor shall provide the following comprehensive services arising out of wear and tear of the normal runningincludes maintenance of all mechanical, electrical and electronic parts /sub-assemblies. Thepreventive maintenance report will be as per the Original Equipmentanufacturer"s instructions and Specification. The Contractor may claim payment on monthly basis.(iii) Breakdown Maintenance : The Authorised ServiceEngineer of OEM or OEM Certified Agencies will carry out all breakdown maintenance after receiving information (written or oral) from GE (AF kalaikunda)officials or their representatives, The OEM"s authorised service representative or OEM certified agencieswill carry out the required repairs of theunits and appraise GE,Engineer-in-Charge and JE the status of the break down repair at site. No payment shall be made on account of any breakdown service during maintenence period.
2(a) Station Fire section
3(b) WSA
4(c) Ration store
5(d) MT FSS
6(e) Logistics & Immols
7(f)ATC Building
8(g) Base Ops
9(h) Hawk Tech Flt (Hawk Tech Hanger)
10(j) Hawk Tech Flt FSS R1, R2, R3 (Hawk Tech Hanger)
11(k) OCU "B"
12(l) OCU "A"
13(m) MT POL Store AF
14(n) Logistics Aerolube Store
15(o) CEO Complex
16(p) BCR Buliding
17(q) GPU & Logs POL (MT Section)
18(r) HST & Compressor (MT Section)
19(s) CCR
20(t) 17 END ABH (17 ORP Hut)
21(u) 35 END ABH (35 ORP Hut)
22(v) HQ Signal Section
23(w) 771 SU Panel No.1
24(x) 771 SU Panel No.2
25(y) IT Cell Panel No.1
26(z) IT CellPanel No.2
27(aa) PAR Building
28(ab) MES MT POL store
29(ac) Main power House
30(ad) MES DG POL store
31(ae) 33 MRS
32(af) Hawk simulator
33(ag) DWR sites
34Servicing of allmultisensor detector with heat and smoke combination photoelectric after taking down from its position and refixing after servicing as per OEM instructionsthrough Authorised Original Equipment Manufacturer"s Service Centre Engineersor through OEM Certified Agencies as approved by GE , checking and testing its functionality,tracing and clearing any fault observed including cleaning detectors through air blower on site complete all as specified and directed. Note : Cleaning of detector shall be done in every three month.
35Testing offlamedectorsdevice, checking its functionality, rectifying any defects observed and testing themwithUVandIRdetectionat sitein hangers complete all as specified in OEM instructionsthrough Authorised Original Equipment Manufacturer"s Service Centre Engineersor through OEM Certified Agencies as approved by GE and directed by Engr-in-Charge. Note : Testing shall be done in every six month.
36Supply and fixingof GSM SIM card with validity ofSMS packs for 12 monthssuitable forexistingalarm control panelsto pass the signals from fire alarm panels located in different sectionsto Main fire alarm panel located in Fire Brigade section through Authorised Original Equipment Manufacturer"s Service Centre Engineersor through OEM Certified Agencies as approved by GE complete all as specified and directed by Engr-in-Charge. Note:- GSM service provider shall be choosen (as per network availability) by Engr-in-Charge.
37Supply only of 12 V, 100 AH batteryfor back up to all FACP and RTU panel as per OEM specification complete.
38Supply onlyof 12 V, 7 AH batteryfor back up to all FACP panel as per OEM specification complete.
39Supply only Indoor type detectors complying with and type certified to EN-54 Addressable type multisensor detector with heat and smoke combination photoelectric /optical with base with self built intelligence as per OEM specification complete all as specified and as directed.
40Supply onlyelectronically addressable intelligent resettable type manual call point with mounting base complying with EN 54 standard and LPCB approved with following specifications as under:- Power- 24V, = 0.6 mA (Standby Current) =1.8mA (Alarm Current),Class A , Initiating Mode - Pressing the action plate manually,Resuming Mode-Manually Resumed by a special Key , Ingress ProtectionIP-43 & Material-ABS all as per IS : 2189 / 1988 as per OEM specification complete.
41Supply onlyintelligent loop isolator with mounting base complying with EN 54 standard and LPCB approved with the specifications as appended below:- (a) Power- 24V, = 3 mA (Standby Current) =15mA (Action Current) (b) Class "A" , (c) Initiating Mode- Yellow flashes when polling, illuminates in action. (d) Ingress ProtectionIP-30 & Material-ABS or as per OEM specification complete.
42Supply only the announcing device Remote response indicator as per OEM specification complete.
43Supply only fire alarm sounder/sirens electronic type horizontal single stage continous normal operation for atleast 50 minutes with sound level 65db to 120db measured at 1.5 m with sound output variation of +5db 500m range as per OEM specification complete.
44Supply only Wireless modem suitable for GSM based communication system to be mounted in RTU enclosure shall be installed at all proposed buildings as per OEM specification complete.
45Supply onlyAmplifierssuitable 30-60Watts, 230VAC50Hzas per OEM specification complete.
46Supply onlyindoordetectorcomplyingwithandtypecertifiedtoEN -54AddressabletypeflamedectorswithUvandIRdetectioncapacity(addupcostofmoduleto beacompleteset,thetypeofmoduleshallberelaytypemodule)withselfbuiltintelligenceasperIS: 11360 as per OEM specification complete.
47Supply only Input Module for Fault and Alarm Monitoring, 24VDC required (Zone Monitor Module) as per OEM specification complete.
48Supply only wall mounted horn type loudspeaker 15 watt 230V AC ,50Hz of sturdy design weather proof type re-entrant horn type loudspeaker for operating under rough conditions as per OEM specification complete.
49Supply only 24 V DC Power Supply Unit of iRTU,as per OEM specification complete.
50Supply only 12/5 V DC Power Supply Unit of iRTU, as per OEM specification complete allasspecifiedanddirected.
51Supply onlyARM7 based CPU card with 3 nos. serial Port, 1 ethernet Port and SD card slot of RTU as per OEM specification complete allasspecifiedanddirected.
52Supply onlyAnalog and Digital I/O Card of RTU, as per OEM specification complete.
53Supply onlyDI/AI Termination PCB of RTU,as per OEM specification complete.
54Supply only Display and Keyboard of RTU,as per OEM specification complete.
55Supply only DO Termination PCB of RTU, as per OEM specification complete.
56Supply onlyMCB SP 6A, C curve , 10 KA as per OEM specification complete.
57Supply onlyLEDs (Red/Green) for RTU Panel.as per OEM specification complete.
58Supply onlyRelay card : 8 relay 1 c/o for RTU panel as per OEM specification complete.
59Supply only Isolation transformer 150 KVA for RTU panel as per OEM specification complete.
60Supply only Push Button withNO/NC contact (BLACK) as per OEM specification complete.
61Supply only GST200-2 Main Board F2.908.826a for FACP as per OEM specification complete.
62Supply onlyLCD Screen CGM12864 for FACPas per OEM specification complete allasspecifiedanddirected.
63Supply only GST200 Rubber Keypad F7.843.249for FACPas per OEM specification complete.
64Supply onlyGST200 Loop Interface Board F2.908.828 (RoHS)for FACP as per OEM specification complete.
65Supply onlyGST200 Power Supply Unit F2.932.069 (20100682)for FACPas per OEM specification complete.
66Supply onlyTransformer 220V/27V-100W-R for FACPas per OEM specification complete
67Supply only Sine Wave Inverter Capacity : 850 VAUPS as per OEM specification complete.
68Supply only copper conductor of size 1.5sqmm X 2 run FRLS flexible wire complete.
69Supply only Optical conventional smoke detector 300 series,LPCB as per OEM specification complete.
70Supply only RoR conventional Thermal detector 300 series,LPCB as per OEM specification complete.
71Supply only two wire Plug in detector base series 300 LPCB as per OEM specification complete.
72Supply only conventional MCP ,Red colour with LED 470 ohms, with back box andsurface mouting box red colour as per OEM specification complete.
73Supply only conventional Horn cum trobe, wall mounted,red colour as per OEM specification complete.
74Supply only conventional Remote response indicator ABS body with dual LEDas per OEM specification complete.
75Supply only step down transformer for convention fire alarm panel as per OEM specification complete.
76Supply only two zoneInterface card for fire panel of as per OEM specification complete.
77Supply only Display card for fire panel of as per OEM specification complete.
78Supply only Main Board (CPU) for fire panel as per OEM specification complete.
79Supply only Transistor with heat sinkfor fire panel as per OEM specification complete.
80Supply only 2 Zone conventional Fire Alarm Panel as per OEM specification complete.
81Supply only GSM Auto dialer as per OEM specification complete.
82Supply only Addressable Fire alarm Control Panel with 2 Loopas per OEM specification complete.
83Note: Schedule of cedit amount of Rs 52662.00 shall be deducted from the total quoted amount of BOQ.