Tender For Provn And Addn/Alt To Fire Hydrants, Fire Alarm, Fire Sprinkler And Allied Work At Af Stn Jaisalmer, jaisalmer-Rajasthan

Military Engineer Services-MES has published Tender For Provn And Addn/Alt To Fire Hydrants, Fire Alarm, Fire Sprinkler And Allied Work At Af Stn Jaisalmer. Submission Date for this Tender is 18-04-2023. Fire Sprinkler Systems Tenders in jaisalmer Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

36999681
Tender For Provn And Addn/Alt To Fire Hydrants, Fire Alarm, Fire Sprinkler And Allied Work At Af Stn Jaisalmer
Open Tender
Indian
Rajasthan
jaisalmer
18-04-2023

Tender Details

Provision And Additional / Alternation Of Fire Hydrants, Fire Alarm, Fire Sprinkler And Allied Work At Af Stn Jaisalmer

Key Value

Document Fees
INR 500 /-
EMD
INR 87400.0 /-
Tender Value
INR 43.70 Lakhs /-

BOQ Items

Name of Work : PROVN AND ADDN/ALT TO FIRE HYDRANTS,FIRE ALARM, FIRE SPRINKLER AND ALLIED WORKAT AF STN JAISALMER.
Sl. No. Item Description
1Motor control centre electrical driven hydrant / Sprinkler common main & Jockey Control Panel upto 90 HP including suitable size incomming and outgoing MCCBs, starters and sensors complete all as specified and directed. Note : Contractor shall produce the drawing of panel for approval before incorporating in the work.Cost of the same shall be included in the quoted rate.
2Electrial driven hydrant main, Sprinkler Standby & Jockey pump control panel. Up to 90 HP including suitable size incomming and outgoing MCCBs, starters, sensors and wiring complete all as specified and directed. Note : Contractor shall produce the drawing of panel for approval before incorporating in the work.
3Excavation in trenches, n exc 1.5m wide and n exc 1.5m in depth , for foundation, etc or for shafts, wells, cesspits, manholes, pier holes, laying of cables etc. n exc 10sqm on plan and n exc 1.5m in depth and getting out in any type ofsoil complete all as specified and as directed .
4Removing surplus soil to a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and as directed .
5Returning, filling in approved soft/loose soilincluding spreading, leveling, watering and well ramming in layers each n.exc 25cm complete all as specified and as directed .
6Mild steel ERW (Electric Resistance Welded) pipe water tubing heavy grade of 150mm bore with & including all fittings complete, laid in trenches, including taking up or down old unserviceable mild steel water tubing and connections complete all as specified and directed.
7Mild steel ERW (Electric Resistance Welded) pipe water tubing heavy grade of 100mm bore with & including all fittings complete, laid in trenches, including taking up or down old unserviceable mild steel water tubing and connections complete all as specified and directed.
8Mild steel ERW (Electric Resistance Welded) pipe water tubing heavy grade of 80mm bore with & including all fittings complete, laid in trenches, including taking up or down old unserviceable mild steel water tubing and connections complete all as specified and directed.
9Mild steel ERW (Electric Resistance Welded) pipe water tubing heavy grade of 40mm bore with & including all fittings complete, laid in trenches, including taking up or down old unserviceable mild steel water tubing and connections complete all as specified and directed.
10Mild steel ERW (Electric Resistance Welded) pipe water tubing heavy grade of 25mm bore with & including all fittings complete, laid in trenches, including taking up or down old unserviceable mild steel water tubing and connections complete all as specified and directed.
11Sprinkler quick / early response type as per IS:15105/TAC guidelines 68 degree temperature rating and testing on completion complete all as specified and directed.
12Cast iron body sluice valve heavy duty class ‘PN-1.6’, 150mm bore, ISI marked with confirming to IS-14846-2000, both flanged ends and drilled, high tensile brass spindle, Cast Iron gate with brass ring, non rising type, cast iron wheel handle, cast iron cap, complete with 3mm thick neoprene rubber gasket joint and nuts, bolts (high tensile), washers etc, and testing, including dismantling & taking out old unserviceable sluice valve, complete all as specified & directed.
13Cast Iron reflex valve/Non return butterfly valve (NRV) of size 150mm bore, cast iron body, (ISI marked) with confirming to IS 5312 (Part-1) : 2004, heavy duty, both ends flanged and drilled, including nuts, bolts, washer and neoprene rubber gasket joint including dismantling & taking out old unserviceable non return valve complete all as specified and as directed.
14Cast Iron reflex valve/Non return butterfly valve (NRV) of size 100mm bore, cast iron body, (ISI marked) with confirming to IS 5312 (Part-1) : 2004, heavy duty, both ends flanged and drilled, including nuts, bolts, washer and neoprene rubber gasket joint including dismantling & taking out old unserviceable non return valve complete all as specified and as directed.
15Fire brigade inlet connection 2 way including testing complete all as specified and directed.
16Hydrant valve size 63mm double headed including taking down old unserviceable valve complete all as specified and directed.
17Hose reel drum 36m including taking down old unserviceable complete all as specified and directed.
18Hose box made of 18 gauge MS sheet 800mm x 600mm x 250mm with double door with 4.00mm thick glasses and door frame made of 16 gauge Mild Steel Sheet painted fire red outside and brilliant white inside yard including taking down old unserviceable complete all as specified and directed.
19Foot valve conforming to IS 4038, of size 150 mm (6") dia including testing complete all as specified and directed.
20Yard hydrant Post / Stand Post 80mm Dia GI / MS both flanged type 1.5m Height including testing complete all as specified and directed.
21Single Loop Analogue Addressable Fire Alarm Control Panel, with a single loop driver card, loop current 500mA maximum per loop, dual flash based microprocessor, supports to connect 240 addressable devices one each loop via fully digital communication protocol, equipped with a white backlit display (240x64 pixel resolution) graphical LCD Display with atleast 6 lines of information, 200 fire zones (soft zones), fully programmable via alphanumeric keypad or configuration software, dedicated USB and RS-232 serial port for direct or PC connection. 5500 events storage, loop current 500 mA,panel shall be equipped with in-built multi-meter for live monitoring of loop current, earth voltage, loop voltage etc., installer"s logo application, can be networked to compatible addressable panels and repeater panels by adding a network card, features battery charger status and temperature, supports programmable cause / effect on outputs, panel housing meets IP30 ingress protection classification finished in RAL 7035, 1 Year Warranty, Independently certified as complying with requirements of BS EN 54 Part 2, 4, and 13. Approved by: British Standards Institute (BSI) and Vertrauen durch Sicherheit (VdS).complete all as specified and directed.
22Intelligent AnalogueMulti-Criteria (combination of smoke and heat) Detector with special algorithms to utilise information from both smoke and heat sensing elements to ensure high level of immunity to false alarms without compromising genuine alarm sensing performance, programmable multiple smoke senstivity level and 9 modes of operation, bi-directional in-built short circuit isolator to protect against cable faults, dual bi-colour LED"s with 360o view of status, auto- addressable/ electronically addressed, utilises fully digital communication addressable protocol with high noise rejection. Approved by LPCB for EN 54-5, EN 54-7, & EN 54-17 standard complete all as specified and directed.
23Standard Detector Base for mounting the compatible addressable detectorscomplete all as specified and directed.
24Network Card(Standard) enables to connect compatible addressable panels/ repeaters and network peripherals in the Network using standard two-core twisted pair cable, supports to connect maximum 32 panels/network nodes in single network, maximum total network cable length 1.5 Km complete all as specified and directed.
25Intelligent Analogue Manual Call Point with resettable operating element, with in-built bi-directional short circuit isolator. Bi-Colour LED for local indication of device status, single action operation, reset to normal condition using special reset key, clearly visible alarm flag in the activated state. Approved by LCPB for EN 54-11 standard complete all as specified and directed.
26Conventional Wall Sounder with Beacon for providing Audible and Visual Alarms in response to the output signal from the control panel, 32 selectable tone and adjustable sound level, maximum output volume@ 1M distance 100 dB(A), output tone frequency range 440 Hz to 2900 Hz,Visual alarm device output frequency 0.5 Hz, Approved by LPCB for EN 54-3 standard complete all as specified and directed.
27Intelligent Sounder Interface Module allows to connect conventional Sounder or Sounder Beacon to addressable loop, with in-built short circuit isolator, allows for two stage alarm capability, addressed through auto and manual options. Approved by LPCB for EN 54-17 & EN 54-18 standard complete all as specified and directed.
28Mounting Accessories like back box for detectors, devices & cable glands, etc complete all as specified and directed.
29Service cable 1.5 sqmm, twin core,1100 volts grade heavy duty cable PVC stranded insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathedincluding laying , fixing and testing etc as required complete all as specified and directed.
30Short circuit isolators including testing complete all as specified and directed.
31Remote response indicators including testing complete all as specified and directed.
32Rotational moulded polyethylene water storage tanks 2000 Litre capacity triple layer (cylindrical vertical with closed top) ISI marked, hoisted & fixed in position & making necessary arrangements for fixing inlet, outlet & over flow pipe & provision of wash out pipe etc. fixed with ball valve of high pressure of PTMT with epoxy coated aluminium rod and high density plastic ball and screwed for iron pipe 20mm bore complete all as specified and directed.
33Mild steel TMT bars upto 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.
34Mild steel TMT bars 6 to 8mm dia, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.
35Reinforced cement concrete M-25 (using 20mm graded stone aggregate) as in columns, pillers, piers, posts and struts complete all as specified and directed.
36Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of plate not less than 1.5 deep below normal ground level and connected to and including galvanized earth lead wire 4mm dia upto 7.5 metre by means of GI nuts, bolt, check nuts, washers thimbles, etc as shown in electrical plate No 03 SSR Part I and connection to main switch board or panel and testing on completion including excavation and earth work in any type to soil, returning fitting in and removal of surface spoil to a distance not exc 50 metre, PCC chamber (1:3:6) type C-2, charcoal and salt mixed layer 15cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe light grade 20mm bore for watering and 15mm bore meter long GI pipe light grade for earth wire protection fixed with poles with two clamps, made from MS flat 25mm x 3mm, bolts, nuts and washers 75mm thick RCC cover 1:2:4 type B-1 shall be provided on CI frame etc complete all as specified. Note - (i)PCC chamber shall be constructed at least 1.5m away from the earth electrode.The pipe for watering shall be provided in slanting manner.including the cost of 7.50m GI pipe for protection of earth wire/strip .(ii) Quoted amount deemed to include the cost of excavation /earthwork , PCC pit , funnel , coverGI medium grade protectiom pipe.
37MCCB, 4 Pole, 200 Amps rating, rupturing capacity 36 kA, 415 Volt grade, AC supply, 50 Hz, thermal Magnetic protection unit and making connections using suitable size copper lugs/thimbles and crimping tool,complete all as specified & directed.
38MCCB, 4 Pole, 160 Amps rating, rupturing capacity 16 kA, 415 Volt grade, AC supply, 50 Hz, thermal Magnetic protection unit and making connections using suitable size copper lugs/thimbles and crimping tool,complete all as specified & directed.
39MCCB, 4 Pole, 63 Amps rating, rupturing capacity 16 kA, 415 Volt grade, AC supply, 50 Hz, thermal Magnetic protection unit and making connections using suitable size copper lugs/thimbles and crimping tool, complete all as specified & directed.