Tender For Repairs To Lt Oh Line, Underground Cable, Lt Panels, Apfc Panels, Painting Of Poles And Connected Items And Repairs/Maint Of External Water Supply Installations, Cleaning Of Ug Reservoir, Oh Tank, Supply Of Chemicals For Water Treatment, tezpur-Assam

Military Engineer Services-MES has published Tender For Repairs To Lt Oh Line, Underground Cable, Lt Panels, Apfc Panels, Painting Of Poles And Connected Items And Repairs/Maint Of External Water Supply Installations, Cleaning Of Ug Reservoir, Oh Tank, Supply Of Chemicals For Water Treatment. Submission Date for this Tender is 15-04-2023. Chemical Supply Tenders in tezpur Assam. Bidders can get complete Tender details and download the document.




Tender Notice

36851432
Corrigendum : Tender For Repairs To Lt Oh Line, Underground Cable, Lt Panels, Apfc Panels, Painting Of Poles And Connected Items And Repairs/Maint Of External Water Supply Installations, Cleaning Of Ug Reservoir, Oh Tank, Supply Of Chemicals For Water Treatment
Open Tender
Indian
Assam
tezpur
15-04-2023

Tender Details

Repairs To Lt Oh Line, Underground Cable, Lt Panels, Apfc Panels, Painting Of Poles And Connected Items And Repairs / Maint Of External Water Supply Installations, Cleaning Of Ug Reservoir, Oh Tank, Supply Of Chemicals For Water Treatment At Misa Cam

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 28-Mar-2023 amdt BOQ 08-04-2023
2 08-Apr-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 15-04-2023

Key Value

Document Fees
INR 500 /-
EMD
INR 70000.0 /-
Tender Value
INR 35 Lakhs /-

BOQ Items

Name of Work: Repairs to LT OH line, underground cable, LT panels, APFC panels, painting of poles and connected items and Repairs/Maint of externalwater supply installations, cleaning of UGreservoir, OH Tank, supply of chemicals for water treatment at Misa Camp under GE (S) Tezpur
Sl. No. Item Description
1Excavation in trenches not exc 1.5 m in depth and not exc 1.5 m wide for taking out/laying XLPE cable/CI/GI pipes and getting out in soft/loose soil complete all as specified and directed.
2Removing excavation soil at a distance not exc 50 m and deposited where directed complete all as specified and directed.
3Returning, filling in including spreading, leveling, watering and well ramming in layers not exc 25 cm complete all directed.
4M & L for sand cushioning with clean dry sand for protection of under ground cable complete all as specified and directed. Note :- Punned thickness of sand layer shall be measured and paid to contractor all as specified and directed.
5M & L for Brick Sub Class "B" locally available best quality laid in trenches with width equal to length of the bricks, above sand cushioning for cable protection completeall as specified and directed.
6S&F in replacementsteel water tubing 50 mm dia of bore light grade galvanised with all fittings laid in trenches / fixing with surface of wall after drawn through electric cable by means of nuts bolt and washers all as specified and directed.
7S&F in replacementsteel water tubing 80 mm dia of bore light grade galvanised with all fittings laid in trenches / fixing with surface of wall after drawn through electric cable by means of nuts bolt and washers all as specified and directed.
8Supply and fix in replacement of MCCB 250 Amps, 4pole, 415volt, 36 KA breaking capacity with all the necessary electrical connections, all as specified and directed.
9Supply and fix in replacement of MCCB 200 Amps, 4pole, 415volt, 36 KA breaking capacity with all the necessary electrical connections, all as specified and directed.
10Supply and fix in replacement of MCCB 100 Amps, 4pole, 415volt, 30 KA breaking capacity with all the necessary electrical connections, all as specified and directed.
11Supply and fix in replacement of MCCB 63 Amps, 4pole, 415volt, 30 KA breaking capacity with all the necessary electrical connections, all as specified and directed.
12Supply, laying in repair in trenches of XLPE UG cable insulatedaluminum stranded conductor served with an inner sheathing or PVC tape heavy duty armored up to 1100volts (earthed) GI steel strip and overall PVC sheathed nominal cross sectional area 6 sqmm 2 core and testing complete all as specified and directed. (Make: Havells India Ltd/ Richa/ KEI Industries Ltd/Polycab/ASIAN Cable/Finolex).
13Supply, laying in repair in trenches of XLPE UG cable insulatedaluminum stranded conductor served with an inner sheathing or PVC tape heavy duty armored up to 1100volts (earthed) GI steel strip and overall PVC sheathed nominal cross sectional area 10 sqmm 2 core and testing complete all as specified and directed. (Make: Havells India Ltd/ Richa/ KEI Industries Ltd/Polycab/ASIAN Cable/Finolex).
14Supply, laying in repair in trenches of XLPE UG cable insulatedaluminum stranded conductor served with an inner sheathing or PVC tape heavy duty armored up to 1100 volts (earthed) GI steel strip and overall PVC sheathed nominal cross sectional area 16 sqmm 4 core and testing complete all as specified and directed. (Make: Havells India Ltd/ Richa/ KEI Industries Ltd/Polycab/ASIAN Cable/Finolex).
15Supply, laying in repair in trenches of XLPE UG cable insulatedaluminum stranded conductor served with an inner sheathing or PVC tape heavy duty armored up to 1100volts (earthed) GI steel strip and overall PVC sheathed nominal cross sectional area 25 sqmm 4 core and testing complete all as specified and directed. (Make: Havells India Ltd/ Richa/ KEI Industries Ltd/Polycab/ASIAN Cable/Finolex).
16Supply, laying in repair in trenches of XLPE UG cable insulatedaluminum stranded conductor served with an inner sheathing or PVC tape heavy duty armored up to 1100volts (earthed) GI steel strip and overall PVC sheathed nominal cross sectional area 35 sqmm 4 core and testing complete all as specified and directed. (Make: Havells India Ltd/ Richa/ KEI Industries Ltd/Polycab/ASIAN Cable/Finolex).
17Supply, laying in repair in trenches of XLPE UG cable insulatedaluminum stranded conductor served with an inner sheathing or PVC tape heavy duty armored up to 1100volts (earthed) GI steel strip and overall PVC sheathed nominal cross sectional area 50 sqmm 3.5 core and testing complete all as specified and directed. (Make: Havells India Ltd/ Richa/ KEI Industries Ltd/Polycab/ASIAN Cable/Finolex).
18Supply, laying in repair in trenches of XLPE UG cable insulatedaluminum stranded conductor served with an inner sheathing or PVC tape heavy duty armored up to 1100volts (earthed) GI steel strip and overall PVC sheathed nominal cross sectional area 70 sqmm 3.5 core and testing complete all as specified and directed. (Make: Havells India Ltd/ Richa/ KEI Industries Ltd/Polycab/ASIAN Cable/Finolex).
19Supply, laying in repair in trenches of XLPE UG cable insulatedaluminum stranded conductor served with an inner sheathing or PVC tape heavy duty armored up to 1100volts (earthed) GI steel strip and overall PVC sheathed nominal cross sectional area 95 sqmm 3.5 core and testing complete all as specified and directed. (Make: Havells India Ltd/ Richa/ KEI Industries Ltd/Polycab/ASIAN Cable/Finolex).
20Supply, laying in repair in trenches of XLPE UG cable insulatedaluminum stranded conductor served with an inner sheathing or PVC tape heavy duty armored up to 1100volts (earthed) GI steel strip and overall PVC sheathed nominal cross sectional area 150 sqmm 3.5 core and testing complete all as specified and directed. (Make: Havells India Ltd/ Richa/ KEI Industries Ltd/Polycab/ASIAN Cable/Finolex).
21Supply, laying in repair in trenches of XLPE UG cable insulatedaluminum stranded conductor served with an inner sheathing or PVC tape heavy duty armored up to 1100volts (earthed) GI steel strip and overall PVC sheathed nominal cross sectional area 185 sqmm 3.5 core and testing complete all as specified and directed. (Make: Havells India Ltd/ Richa/ KEI Industries Ltd/Polycab/ASIAN Cable/Finolex).
22M & L forBoring holes horizontally under Road without damaging the surface of Road (minimum 1.0 METRE below the Road Surface / footpath with the help of GI Tubing not exc. 80mm bore (dia) for passing of UG Cable, complete all as specified and directed NOTE: GI Pipe laid will be measured and paid separately under appropriate Item.
23Supply and fix in replacement of aluminum lug of size 16/25 Sqmm for connecting Aluminum XLPE cable all as specified and directed.
24Supply and fix in replacement of aluminum lug of size 35 Sqmm for connecting Aluminum XLPE cable all as specified and directed.
25Supply and fix in replacement of aluminum lug of size 50 Sqmm for connecting Aluminum XLPE cable all as specified and directed.
26Supply and fix in replacement of aluminum lug of size 70 Sqmm for connecting Aluminum XLPE cable all as specified and directed.
27Supply and fix in replacement of aluminum lug of size 95 Sqmm for connecting Aluminum XLPE cable all as specified and directed.
28Supply and fix in replacement of aluminum lug of size 120 Sqmm for connecting Aluminum XLPE cable all as specified and directed.
29Supply and fix in replacement of aluminum lug of size 150 Sqmm for connecting Aluminum XLPE cable all as specified and directed.
30Supply and fix in replacement of aluminum lug of size 185 Sqmm for connecting Aluminum XLPE cable all as specified and directed.
31M & L Cross-arms, Bracings, Supports, Clamps and Back Plates fabricated from Structural Steel Sections including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ directed and inclusive of one coat of Aluminum Primerone Under Coat and One Finishing Coat of Aluminum Paint, complete all as specified and directed.
32Supply and fixing Pin type porcelain, vitreous white brown or green insulators including one galvanised mild steel spindle, two galvanised iron washers, and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade complete all as specified and directed. Make: BHEL/Jaipuriya Brothers/Pactil/Southern Insulators
33Supply and fixing Shackle type, porcelain, vitreous, white brown or green insulators, including galvanised mild steel straps, washers, insulator bolts, washer and nut, 75 mm height, 90 mm dia, 3 Nos straps of size 31 x 3mm, dia of boltsfor 1100 volts grade complete all as specified and directed. Make: BHEL/Jaipuriya Brothers/Pactil/Southern Insulators
34S&F Loop Type Insulator Vitreous White, Brown or Green, large size with overall dimensions 90x65mm, clearance of hole 16mm dia, complete all as specified and directed.
35M & L Stay Assembly complete with Accessories as show in Electrical Plate No.1 of MES Schedule Part-I, diameter of Stay Rod 16mm, size of Plate 230x230x6mm complete all as specified and directed. NOTE: Earthwork, Cement Concrete, Mild Steel Stay Clamps with Bolts, Nuts, etc., Loop Insulator, etc. will be measured and paid under appropriate Items.
36Supply and fixing galvanised stay strand of size 7/3.15mm complete all as specified and directed.
37Supply, fixing, erecting in truly vertically position steel tubular swaged welded pole complete with cast iron base plate, finial taper plug, bolts, nuts, and screws as specified type 410 SP - 31 (9 mtr long) including one primer coat, one under coat, one finishing coat of aluminum paint, marking of pole numbers and making 3 Nos of black colour strip 15 cm wide on equal distance from coping including suitable size of PVC cable jointing box with nut bolts and MS clamps made out with 20 x 5 flat iron complete all as specified and directed.
38M & L for cement contrite 1:3:6 type C- 2 40 mm graded stone aggregate as in foundation of pole filling and mass concrete in complete all as specified and directed.
39M & L for cement concrete 1:2:4 type B-1 using 20 mm graded stone aggregate as in roof, curb or mud stops rounded or charged on edges ,coping etc complete all as specified and directed.
40Supply, fixing / stringing aluminum conductor steel reinforced (ACSR) in any type /size/ dia etc on existing poles including winding, jumpering with alkathine pipe and binding to insulators with aluminum binding wire as in over head conductors including stringing, tightening etc complete all as specified and directed.
41S & F in replacement of MCB TPN 415 Volts, 63 Amps, 50 Hz, breaking capacity 10KA, C series all as specified and directed
42Material and labour for painting to steel tubular pole 9.0 / 11.0 metre long with two coats of synthetic enamel paint up to 1.20 metre height from ground level in 15 cm alternative black and yellow strips and remaining portion with aluminum paintand MS frames like channel, clamps, angle, D-clamps etc with two coats of aluminum paint complete all as specified.
43Supply and fix in replacement on load change over switch AC-23A (side handle) with advance neutral switch in steel sheet metal enclosure 4 pole and 415 volts conforming to IS/IEC -60947-3 compact design of capacity 100 Amps complete all as specified and directed. Make: L&T/Legrand / ABB / Siemens / GE / Schneider / C&S Electric Ltd / Indo Asian
44Material & Labour for earthling with galvanised steel earth plate electrode of size 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead by means of bolts, nuts check nuts and washers of galvanised iron or steel using GI strip 32x6 mm as earthling lead as shown in electrical plate No. 3 of SSR Part-I connected to earthling test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregate pit, funnel, 20mm dia GI light grade watering pipe, 40mm dia GI light grade earth lead protection pipe, CI frame and cover, wire, copper lugs etc mesh, charcoal and common salt in alternate layer complete all as specified and directed.
45Supply, installation, testing and commissioning of factory made approved make as specified in PS,powder coatedoutdoor type, dust & vermin proof feeder pillar box made out of 3.15mm CRCA steel sheet of suitable size and angle iron 40 mm x 40mm x 6 mm , powder coated over one coat of red oxide primer suitably grouted in PCC-M10 using 20 mm graded stone aggregateincluding aluminum bus bar, internal wiring with PVC insulated single core cables of copper conductor of suitable size duly numbered with tags for the circuits with hinged double door shutters (front & rear), cubical type locking arrangement and slanted roof. The size of panel boards shall be suitable for housing the accessories given here under and also suitable for operation on AC 415 Volt, 3 phase, 50 Hz supply system. The panel board shall comprise of following items & all specified in SSR Part-I clause no 19.21 and all as shown on drawing all as specified and directed. INCOMING:- (i)MCCB 63 amps, 4 pole, breaking capacity 16 KA suitable for operation of 415 volts AC 50 HZ with adjustable type andallas specified in SSR Part -I and earth leakage module - 01 No, (ii) LED Type indicator lamp R-Y-B(1 Set), (iii) 4 strip aluminum coated copper bus bar of rating 1.5 times current carrying capacity of incoming switch gear or not less than 200 Amp whichever higher (iv) Voltmeter and ammeter (B) OUTGOING (i)MCB 6-32 Amp,2 Pole, 415 Volts, 10 KA, C Curve - 10 Nos (II) MCB TPN 63 Amp-02 Nos Note: Rate of PCC foundation for installation of panel shall be included in the quoted rate.
46M & L for earthling complete with GI earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25m deep below ground level ) with top edge of the plate not less than 1.5 m below normal ground level , connected to galvanised earth lead iron wire 4mm dia by means of GI bolts nuts and washers of galvanised iron or steel etc all as shown in electrical plate No.3 including earth work PCC pit and RCC pit cover, funnel with watering pipe ,wire mesh ,alternate layer of salt and charcoal, GI protection pipe light grade and testing on completion all as specified and directed
47Supply and fix in replacement on load change over switch AC-23 (side handle) with advance Neutral switch in steel sheet metal enclosure 4 pole By pass Switch and 415 volts conforming to IS/IEC -60947-3 compact design of capacity 63 Amps complete all as specified and directed. Make: L&T/Legrand / ABB / Siemens / GE / Schneider / C&S Electric Ltd / Indo Asian
48Excavating in trenches n exc 1.5m wide and n exc 1.5m deep and gettingout in soft / loose soil complete all as specified and directed.
49Returning, filling in including spreading, leveling, watering and well ramming in layers n. exc. 25 cm complete all as specified and directed
50Removing excavated materials n. exc. 50 mm and depositing where directed at a level n. exc.1.5 above the starting point complete all as specified and directed.
51Taking out 100 mm bore GI/CI Water mainfrom trenches and staking at site complete all as specified and directed.
52Supply, laying and testing ductile iron pressure pipe socket and spigot end, class K-7, confirming to IS-8329/2000 blast furnace slag cement with Portland cement properties suitable for Push - on- joint with inside cement mortar lining, internal metallic zinc coating and external black bitumen coating of size 100 mm dia duly ISI marked laid in trenches etc complete all as specified and directed.
53Taking out80 mm GI Water main from trenches/wall/ceilings/floor and staking at site complete all asdirected.
54Taking out63 mm PPR Water main from trenches/wall/ceilings/floor and staking at site complete all asdirected.
55Taking out50 mm GI Water main from trenches/wall/ceilings/floor and staking at site complete all asdirected.
56Taking out32 mm PPR/GI Water main from trenches/wall/ceilings/floor and staking at site complete all asdirected.
57Taking out25 mm PPR/GI Water main from trenches/wall/ceilings/floor and staking at site complete all asdirected.
58Taking out20 mm PPR/GI Water main from trenches/wall/ceilings/floor and staking at site complete all asdirected.
59Taking out15 mm GI Water main from trenches/wall/ceilings/floor and staking at site complete all asdirected.
60Supply and layingin repair of 3layered (outer green coloured UV stabilized, middle black coloured UV stabilized and inner most layer white coloured with antimicrobial properly) fusion welder PP-R (Poly propylene random Co-polymer) pipes laid in trenches incl plain PP-R and brass threaded PP-R fittings or flanged jointsincl connecting up with existingsystem of gradePN 10, SDR-11 of 63 mm outer dia size complete all as specified and directed.
61All as per Item No. 60 here in above but for size 32 mm outer dia.
62All as per Item No. 60 here in above but for size 25 mm outer dia.
63All as per Item No. 60 here in above but for size 20 mm outer dia.
64Supply and layingin repair of 3layered (outer green coloured UV stabilized, middle black coloured UV stabilized and inner most layer white coloured with antimicrobial properly) fusion welder PP-R (Poly propylene random Co-polymer) pipes laid wall/floors/ceiling incl plain PP-R and brass threaded PP-R fittings or flanged jointsincl connecting up with existingsystem of gradePN 7.4, SDR-11 of 32 mm outer dia size complete all as specified and directed.
65All as per Item No. 64 here in above but for size 25 mm outer dia.
66All as per Item No. 64 here in above but for size 20 mm outer dia.
67S&F in repair PP-R gate valve (Brass insert) as per requirement of site and fixed of63 mm bore including taking down all as specified and diretected.
68All as per Item No. 67 here in above but for size 32 mm bore
69All as per Item No. 67 here in above but for size 25 mm bore
70All as per Item No. 67 here in above but for size 20 mm bore
71S&F in repair of steel tubes medium grade galvanised 25 mm bore with all fittings and fixed complete to walls and ceilings and laid in floors complete all as specified and directed.
72S&F in repair of steel tubes medium grade galvanised 20 mm bore with all fittings and fixed complete to walls and ceilings and laid in floors complete all as specified and directed.
73S&F in repair of steel tubes medium grade galvanised 15 mm bore with all fittings and fixed complete to walls and ceilings and laid in floors complete all as specified and directed.
74S&F in repair of steel tubes medium grade galvanised 80 mm bore with all fittings laid in trenches complete all as specified and directed.
75S&F in repair of steel tubes medium grade galvanised 50 mm bore with all fittings laid in trenches complete all as specified and directed.
76S&F in repair of steel tubes medium grade galvanised 25 mm bore with all fittings laid in trenches complete all as specified and directed.
77S&F in repair of steel tubes medium grade galvanised 20 mm bore with all fittings laid in trenches complete all as specified and directed.
78S&F in repair of steel tubes medium grade galvanised 15 mm bore with all fittings laid in trenches complete all as specified and directed.
79S&F in repair of Straight plain brass ferrules 20 mm (or connecting screws) screwed both ends and fixed complete all as specified and directed
80S&F in repair of sluice valve (heavy duty) with SS spindle H/W conforming to IS 14846 both end flanged class PN 1.6 of size 150 mm dia incl necessary nuts, bolts washers and gasket including taking down all as specified and directed.
81S&F in repair of sluice valve (heavy duty) with SS spindle H/W conforming to IS 14846 both end flanged class PN 1.6 of size 100 mm dia incl necessary nuts, bolts washers and gasket including taking down all as specified and directed.
82Supply and Fix in repair of sluice valve of size 80 mm dia bore flanged ends drilled type with gun metal spindle incl nut and bolts washer and jointing material complete all as specified of class PN-I.6 ISI marked including taking down all as specified and directed.
83S&F in repair of Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed50 mm bore including taking down all as specified and directed.
84S&F in repair of Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed25 mm bore including taking down all as specified and directed.
85S&F in repair of Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed20 mm bore including taking down all as specified and directed.
86S&F in repair of Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed15 mm bore including taking down all as specified and directed.
87Supply and fix in repair of non return valve 100 mm dia screwed type ISI marked, including jointing materials and taking out the unserviceable valve complete all as specified and directed.
88Supply and Fix in repair of CI butterfly valve 150 mm dia without lugs, lever operated CI disc, EPDM rubber lining including taking down old u/s onecomplete all as specified and directed.
89Supply and Fix CI in repair of water type butterfly valve 100 mm dia without lugs, lever operated CI disc, EPDM rubber lining including taking down old u/s onecomplete all as specified and directed.
90M & L for DI fittings for spigot and socket pipes of size 100 mm to 350 mm bore such as bends(any type, radius and angle) tapers any type (straight, bend, increasing, decreasing or double socket etc)Tee pieces single branch, "Y"junction, double branch, cross(all sockets or socket and spigot) collars caps and plugs including taking down all as specified and directed.
91M & L for construction of valve pitof size 1.2 x 1.2 x 1.2 m (internal dimension)one brickthick wall including MS sheet covermade of MS sheet 3 mm thickand 50 x 50 x 6 mm thick MS angle iron frame and locking arrangement and painting with two coatsof synthetic enamel paint over a coat of red oxide primer after preparation of surfaces including demolition of existing brick masonry valve pit all as specified and directed.
92M & L for construction of valve pitof size 0.9 x 0.9 x 0.9 m (internal dimension)one brickthick wall including MS sheet covermade of MS sheet 3 mm thickand 50 x 50 x 6 mm thick MS angle iron frame and locking arrangement and painting with two coatsof synthetic enamel paint over a coat of red oxide primer after preparation of surfaces including demolition of existing brick masonry valve pit down all as specified and directed.
93M & L for construction of valve pitof size 0.6 x 0.6 x 0.6 m (internal dimension) one brickthick wall including MS sheet covermade of MS sheet 3 mm thickand 50 x 50 x 6 mm thick MS angle iron frame and locking arrangement and painting with two coatsof synthetic enamel paint over a coat of red oxide primer after preparation of surfaces including demolition of existing brick masonry valve pitall as specified and directed.
94Cleaning of overhead RCC tank at Pump House No. 05 of capacity 0.75 Lakh Gallon using following stages cleaning process including arrangement of necessary T&P, labour and Chemicals mechanize etc before starting process of cleaning complete all as specified and directed. (a) Mechanized Dewatering (b) Sludge Removal (c) High Pressure Cleaning (d) Vacuum cleaning (e) Antibacterial spray (f) UV radiation
95Cleaning of UG Sump at Pump House No. 07 and P-70 of capacity 0.28 Lakh Gallon using following stages cleaning process including arrangement of necessary T&P, labour and Chemicals mechanize etc before starting process of cleaning complete all as specified and directed. (a) Mechanized Dewatering (b) Sludge Removal (c) High Pressure Cleaning (d) Vacuum cleaning (e) Antibacterial spray (f) UV radiation
96Cleaning of PVC Sump at Pump House No. 07 of capacity 0.11 Lakh Gallon using following stages cleaning process including arrangement of necessary T&P, labour and Chemicals mechanize etc before starting process of cleaning complete all as specified and directed. (a) Mechanized Dewatering (b) Sludge Removal (c) High Pressure Cleaning (d) Vacuum cleaning (e) Antibacterial spray (f) UV radiation
97Cleaning of PVC overhead tank at ILP Location of capacity 0.11 Lakh Gallon using following stages cleaning process including arrangement of necessary T&P, labour and Chemicals mechanize etc before starting process of cleaning complete all as specified and directed. (a) Mechanized Dewatering (b) Sludge Removal (c) High Pressure Cleaning (d) Vacuum cleaning (e) Antibacterial spray (f) UV radiation
98M & L for re-winding of 22.5 HP Submersible motor afterlifting up of submersible pump set includingcolumn pipe from bore well, disconnecting motor from pump, taking out burnt winding wire of field coil and re-winding of field coil with suitable size of super enameled copper winding wire with necessary insulation materials including complete overhaulingand re-fixing motor, pump on frame with new nuts bolts etc and necessary connection to the terminal complete all as specified and directed.
99M & L for re-winding of 15 HP Submersible motor afterlifting up of submersible pump set includingcolumn pipe from bore well, disconnecting motor from pump, taking out burnt winding wire of field coil and re-winding of field coil with suitable size of super enameled copper winding wire with necessary insulation materials including complete overhaulingand re-fixing motor, pump on frame with new nuts bolts etc and necessary connection to the terminal complete all as specified and directed.
100M & L for re-winding of 15 HP induction motor disconnecting motor from pump, taking out burnt winding wire of field coil and re-winding of field coil with suitable size of super enameled copper winding wire with necessary insulation materials including complete overhaulingand re-fixing motor, pump on frame with new nuts bolts etc and necessary connection to the terminal complete all as specified and directed.
101M & L for complete servicing, greasing of the pump motor sets of capacity up to 15 HP by dismantling from the position, unscrewing nut bolt, bushes, cleaning, greasing and replacement of unsv bushes, gasket, gland packing/water seals, oil ring, nut bolts of suitable size including re-assembling the same in position and connect to the both end terminal circuit testing and commissioning complete all as specified and directed. (Note:- 1. Arrangement of necessary T&P items required for dismantling and reassembling pump motor set shall be deemed to be included in the quoted rate. 2. Cost of new bushes, gasket, gland packing nut bolts etc shall be deemed to be included in the quoted rate.)
102M & L for re-winding of 3 to 5 HP induction motorafter disconnecting motor from pump, taking out burnt winding wire of field coil and re-winding of field coil with suitable size of super enameled copper winding wire with necessary insulation materials including complete overhaulingand re-fixing motor, pump on frame with new nuts bolts etc and necessary connection to the terminal complete all as specified and directed.
103M & L for dismantling centrifugal pump of capacity 3 to 5 HP from motor and inlet outlet GI pipes and taking out for workshop for repair of impeller, casing water seal, shaft etc complete all as specified and directed.
104M & L for lifting of submersible non clogging pump set with 10/12.5 HP capacity motor from sewage well for repair/rewinding after taking out burnt winding wire and re-winding of same with suitable size of super enameled copper winding wire with necessary insulation and re-installing the same by proper assembling with connected pump set, testing commissioning complete all as specified and directed.
105M & L for dismantling of air compressor/blower for STP of 7.5 HP capacity after disconnecting the complete electrical connection and dismantling complete pipes and taking out for workshop for repair/rewinding of same with suitable size of super enameled copper winding wire with necessary insulation and filling suitable compressor oil and refixing on same place complete all as specified and directed.
106S&F in replacement of belt for air blower of suitable size complete all as specified and directed.
107M & L for Bacteriological/Chemical testing of Raw/treated water sample collected from different take over points at various water supply installations by therepresentation of natural testing laboratory (Govt Approved) and furnishing of detail report as per IS 10500 : 1991 indicating quality of water sample by provision of water quality parameters such as colour, odor, PH value, Chlorides, turbidity, total hardness (CaCO3), iron, dissolved solid, calcium, copper, lead, fluoride mercury, cyanide etc. complete all as specified and directed. Note: Payment to the contractor shall be made only after furnishing the report.
108S&F in repairBall valves high pressure of PTMT with epoxy coated Aluminumrod& high-density plastic ball screwed for iron pipe and fixed. (Minimum weight 15mm-142gms/ 20mm-210gms./ 25mm-455gms/ 40mm - 690 gms) for 25 mm bore pipe complete all as specified and directed.
109S&F in repairBall valves high pressure of PTMT with epoxy coated Aluminumrod& high-density plastic ball screwed for iron pipe and fixed.(Minimum weight 15mm-142gms/ 20mm-210gms./ 25mm-455gms/ 40mm - 690 gms) for 20 mm bore pipe complete all as specified and directed.
110Supply and fix cast iron foot valve 100 mm dia screwed type ISI marked, as per IS 4018, including necessary rubber gasket, nut bolt, and taking out the unserviceable foot valve complete all as specified and directed.
111M & L for re-winding of 5/7.5 HP induction motorafter disconnecting motor from pump, taking out burnt winding wire of field coil and re-winding of field coil with suitable size of super enameled copper winding wire with necessary insulation materials including complete overhaulingand re-fixing motor, pump on frame with new nuts bolts etc and necessary connection to the terminal complete all as specified and directed.
112S&F in repair fully automatic star delta starter 22.5 HP in sheet steel enclose type MN with single phase protection feature AC 3 Phase 415 Volt 50 Hz all as specified and directed.. Make L&T, CAT No. SS94364
113S&F in repair fully automatic star delta starter 15 HP in sheet steel enclose type MK with single phase protection feature AC 3 Phase 415 Volt 50 Hz all as specified and directed.. Make L&T, CAT No. SS96259
114S&F in repair fully automatic star delta starter 5 HP in sheet steel enclose type MN with single phase protection feature AC 3 Phase 415 Volt 50 Hz all as specified and directed.. Make L&T, CAT No. SS94351
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail