| 1 | ERRECTION OF 22KV H.T LINEErection of pole.Digging of pit,(ii) Laying of RCC muff (iii) Drilling of holes in X-bracing set, X-arms (iv) Erection of pole (v) fixing of insulator,X-arm, X-bracing set, (vi) fixing of Barbed wire, Danger plate (vii) filling of pit & Ramming i/c painting of pole T/Pole str. (Complete in all respect). |
| 2 | Erection of pole.Digging of pit,(ii) Laying of RCC muff (iii) Drilling of holes in X-bracing set, X-arms (iv) Erection of pole (v) fixing of insulator,X-arm, X-bracing set, (vi) fixing of Barbed wire, Danger plate (vii) filling of pit & Ramming i/c painting of pole D/Pole str. (Complete in all respect). |
| 3 | ERRECTION OF STAY SET(i) Digging of pit (ii)fixing of stay rod (iii) Filling of pit (iv)Nozzeling & Tighting. |
| 4 | ERRECTION OF EARTHING(i) Digging of pit (ii) fixing of G.I wire to the earth system, filling of pit. |
| 5 | Sagging ofACSR Conductor 6/1/3.35mm (Single wire).Laying of conductor (i) stringing & sagging (ii) binding with insulator. |
| 6 | Sagging of G.I Wire for earth wire |
| 7 | MANNUAL CARRIAGE OF H.T LINE MATERIAL CONSIDERING AVERAGE DISTANCE 1.000 K.M. |
| 8 | MATERIAL TO BE SUPPLIED BY CONTRACTOR.Nut and Bolts off size. |
| 9 | Aluminium Paint |
| 10 | Support Clamp |
| 11 | Stay Clamp |
| 12 | X-Arms (MS Channel Iron (100*50*6mm), length 2800mm. (Made of only TATA/SAIL/Rastriya Ispat Steel.) |
| 13 | X-Bracing set MS Angle Iron : (50*50*6)length 2700+1500mm (Made of only TATA/SAIL/Rastriya Ispat Steel.) |
| 14 | Egg Isulator |
| 15 | Line Stapple |
| 16 | Bend Stapple |
| 17 | HT Stay Set |
| 18 | RCC Muff |
| 19 | Erection of 630KVA S/Stn. Digging of pit for pole and earthing, drilling of holes in x-arm, preparation of plate form, Str. MemberC.I A.I. X-arm, knee bracing set, erection of D-pole, c.c.muff, erection of plate form, erection of x-arm, dropout fuse unit, lightning arrester, MCCB switch, L.T box, energy meter, erection of transformer, G.O switch, stay set, jumper earthing 3 sets, L.T cables, paintingetc. (Complete in all respect). |
| 20 | C/O Transformer Bed ( 1.2*1.5*1.5M)(Civil Work) as per HPSR-2020. |
| 21 | Unloading & placing of Transformer to Bed through Hydra. |
| 22 | Mechanical Carriage of Transformer a/w complete accessories by private vehicle from Nichar to site of work. (Due to narrow road resulting Board\"s Truck could not run on that link road) |
| 23 | Providing Fencing around the Sub-station.Earth work in excation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and ramming of bottms, lift upto 1.5m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within lead of 50m(All kind of Soil). |
| 24 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, led up to 50m and lift upto 1.5 m. |
| 25 | Structural Steel work reveted, bolted or welded in built up sections, trussses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.Such as tees, angles, chanels and RS ioists,Flats exceeding 10mm in thickness,Mild Steel plates, Mild steel rivets etc. |
| 26 | P/L in position CC of specified grade excluding the cost of centering and shuttering-All work up to plinth level: 1:2:4(1Cement:2Coarse Sand:4Graded stone aggregate 20mm nominal size). |
| 27 | Centering and Shuttering including strutting, propping etc. and removal of form work for: Foundations, footings, bases for columns. |
| 28 | Providing and fixing G.I. (made of G.I. wire of 4mm) chain link fabric fencing of required width in mesh size 50X50mm including strengthening with 2mm dia wire or nuts, bolts and washers as required complete as per direction of Engineer-in-charge |
| 29 | MATERIAL TO BE SUPPLIED BY CONTRACTOR.Nut and Bolts off size. |
| 30 | Aluminium Paint |
| 31 | HT Stay Set |
| 32 | Egg Isulator |
| 33 | 22kV, GOABS(400Amps.), Triple pole,O/D Type. |
| 34 | Support Clamp |
| 35 | RCC Muff |