| 1 | Supply, Installation, testing and commissioning of copper wound Isolation transformer 250 KVA, LT 433/415 V, 3 phase, 50 hz, onan cooled oil immersed copper wound indoor type isolation transformer complete with first filling of IS: 335 ISI marked filtered & dehydrated transformer oil electrostatic shield between primary 415 V in delta connected & secondary 415V star connected complete & other standard fitting/ accessories and 5 position off circuit tap changer (tapping range +5% in steps of 2.5 % each) with vector group dyn-11. complete all as specified and directed.Make:- POWERWARE, INDIAN TRANSFORMERS & ELECTRICALS GURGAON, DIAMOND, HINDUSTAN TRANSFORMERS, M/s DAITRON POWER INFRASTRUCTURE LTD |
| 2 | Material and labour for Sub Main Wiring with two single core 4 Sqmm (nominal area) multi stranded copper conductor FRLS PVC insulated and unsheathed colour code cables, drawn in and including non-metalic rigid PVC conduit, heavy duty of 25 mm dia, including standard fittings such as Tees, junction, bands etc., conduit concealed in wall & fixed on ceiling with suitable clamps with and including one run of continuous multi stranded copper conductor 4 Sqmm (nominal area) FRLS PVC insulated and unsheathed colour code cable for earth continuity, 1100 volts grade , complete all as specified and directed. Note(s): (i) Two runs of 4 Sqmm main cable + one run of 4 Sqmm cable for earth continuity and PVC conduit shall be measured as one unit/one Running Metre.(ii)Rate quoted shall be deemed to include cutting chases for concealing conduit and making good in cement mortar (1:4) or PCC (1:2:4) as required. |
| 3 | Material and labour for Sub Main Wiring (in replacement) with two single core 6 Sqmm (nominal area) multi stranded copper conductor FRLS PVC insulated and unsheathed colour code cables, drawn in and including non-metalic rigid PVC conduit, heavy duty of 25 mm dia, including standard fittings such as Tees, junction, bands etc., conduit concealed in wall & fixed on ceiling with suitable clamps with and including one run of continuous multi stranded copper conductor 4 Sqmm (nominal area) FRLS PVC insulated and unsheathed colour code cable for earth continuity, 1100 volts grade , complete all as specified and directed. Note(s): (i) Two runs of 6 Sqmm main cable + one run of 4 Sqmm cable for earth continuity and PVC conduit shall be measured as one unit/one Running Metre.(ii)Rate quoted shall be deemed to include cutting chases for concealing conduit and making good in cement mortar (1:4) or PCC (1:2:4) as required. |
| 4 | Supply and fixing sheet metal enclosure, SPN, with a two pin socket and earth plug, with one MCB single pole, 240 Volts, 20 Amps, ‘B’ curve, 10 KA, complete all as specified and directed |
| 5 | Excavation in trenches in soft/loose soil not exceeding 1.50 meter wide and not exceeding 1.5 meter in depth; for laying/taking out cables and foundations of poles etcand getting out complete, all as specified. |
| 6 | Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm thick each as in soft/loose soil, complete all as specified.NOTE: For payment purposes volume of returning filling shall be considered after 10% deduction. |
| 7 | Removingof surplussoil / excavated material to a distancenot exceeding 50 metre and depositing where directed complete all as specified. |
| 8 | Clean dry sand laid in trenches/ducts for bedding andcushioning to cable, 8cm in depth before laying the cable and 15 cms (punned down to 10 cms thick) in depth after laying the cable including spreading, levelling and consolidation complete all as specified and directed.Note : Consolidated/punned thickness of 18 cm (overall) shall be measured for payment purpose. |
| 9 | Material and labour, locally available , sub class \"B\" bricks(old size) laid flat and dry in trenches over the cable for protection, perpendicular to the direction of cable adjacent to each other,complete all as specified and directed. |
| 10 | Supplying and laying,factory made unreinforced precast concrete cable cover HV type-1, flat, of size 300x180x40mm, laid flat and dryin trenches over the cable for protection, length perpendicular to the direction of cable adjacent to each other, complete all as specified and directed. |
| 11 | Supply and laying / fixing, GI pipe light grade 100 mm dia for cable protection fixed to pole/wall or laid under floor/ road/ pavement, including MS clamp/nuts & bolts etc complete all as specified and directed. |
| 12 | Supply and laying / fixing, GI pipe light grade 80 mm dia for cable protection fixed to pole/wall or laid under floor/ road/ pavement, including MS clamp/nuts & bolts etc complete all as specified and directed. |
| 13 | Supply and laying / fixing, GI pipe light grade 50 mm dia for cable protection fixed to pole/wall or laid under floor/ road/ pavement, including MS clamp/nuts & bolts etc complete all as specified and directed. |
| 14 | Supply and laying / fixing, GI pipe light grade 40 mm dia for cable protection fixed to pole/wall or laid under floor/ road/ pavement, including MS clamp/nuts & bolts etc complete all as specified and directed. |
| 15 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 300 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. |
| 16 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 240 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. |
| 17 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 185 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. |
| 18 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 120 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. |
| 19 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 70 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. |
| 20 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 50 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. |
| 21 | Supply, laying, jointing, testing and commissioning of Low Tension (LT)XLPEinsulated, galvanized steel strip armoured, heavy duty, electric power cable, cross sectional area 35 Sqmm 3.5 core aluminum conductor 1100 volts grade under ground cable including both side connection with cable lugs etc, laid in trenches, alongpolesorpassing through pipes or laid under floor or through walls etc, complete all as specified and as directed. Note : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. |
| 22 | Material and labour for vertical type sheet steel enclouser distribution boards, double door factory made3 phase 415 volts 4 way with 200 amps rating copper bus bar of suitable size and PVC insulatedcopper jumpers from the MCCB to the out going circuits (oneincoming MCCB and 12 outgoing MCBs circuits) comprising of 3 phase 4 wireof suitable rating includingMCCB 160 amps, 25 KA, TP, 415 volts, 50 Hz = 01 No. and 12 Nos MCBs 6-32 Amps, complete all as specified and directed. |
| 23 | Supply and fixing sheet metal enclosure for DBs (Single door type) when MCBs to be used single pole and neutral 8 ways including blanking plate as required with 200 Amps rated bus bar,240 volts fixed sunk/flush to the wall or niche complete all as specified and as directed including necessary brick work and plaster to match with the existing surface complete all as specified. |
| 24 | Supply and fixing amp rating 240V, 10KA \"C\" curve miniature circuit breaker (MCB) of SPN 32 Amps and current carrying capacity in the MCB DB complete with connection testing and commissioning,complete all as specified and as directed. |
| 25 | Supply and fixing amp rating 240V, 10KA \"C\" curve miniature circuit breaker (MCB) of SP 6 to 32 Amps and current carrying capacity in the MCB DB complete with connection testing and commissioning complete all as specified and as directed. |
| 26 | Supply, laying, jointing, testing and commissioning of High Tension (HT), 11000Volts (earthed) grade, XLPE insulated, screened, PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) with stranded aluminum conductor, cross sectional area 120 Sqmm, 3core under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and directed.Note : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately. |
| 27 | Supply and fixing Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrinktype joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm, Complete all as specified and directed. |
| 28 | Supply and fixing switch air break, triple pole, gang operated, outdoor type, mechanically operated, mounted on 12 insulators and steel channel frame with all fittings & accessorieslike channel, angle, nut, bolts and washer etc, with 25 mm bore GI pipe as operatig rod of suitable length for operating mechanism worked from ground level, including drop out fuse unit assembly 11 KV grade, for current rating upto 400 Amps suitable for 11000 volts grade, AC supply, including locking arrangement for opertaing handle incl all fixing arrangement complete all as specified and directed. |
| 29 | Material and labour for earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick burried directly in ground vertically (depth of pit not less than 2.25 m below normal ground level), with top edge of earth plate not less than 1.5m below normal ground level, earth plate surrounded from all sides by 15cm thick packed alternate layers of charcoal dust and common salt, electrode connections using galvanized iron wire 4mm dia (upto body of equipment) by means of nuts, bolts, check nuts & GI washers, connected to main switch board or main control board or test point, protected by galvanized iron pipe light grade 40mm dia bore, and watering pipe 20mm dia bore GI medium grade with funnel & wire meshincluding all necessary excavation & earth work,PCC chamber in PCC (1:2:4) type B-1 & RCC cover, all as shown in electrical plate No 3 of MES Schedule Part-I (2009), testing on completion, complete including dismantling of existing earthing all as specified and directed.Note(s) :-(i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm.(ii)PCC chamber shall be constructed 500 mm away from the edge of earth pit.(iii) Rate shall include GI strip and protection pipe of length 7.5m, excess beyond 7.5m length required at site shall be measured and paid separately.(iv)Earth resistance should be less than 3Ohm. In case the test results are not found below 3Ohm, complete earthing will be redone without any extra cost to Govt. |
| 30 | All as per the description of Srl item No. 29 here-in-before, but using galvanised iron strip 25×4 mm as earthing lead. |
| 31 | All as per the description of Srl item No. 29 here-in-before, but using galvanised iron strip 32X6mm as earth lead . |
| 32 | Material and labour for Shifting of Indoor type transformer300 KVA to a distance not more than 10Kms from power house/any other place to required place complete all as directed, including taking down all electric connections and refixing the same at site with necessary transportaion complete all as specified and directed. |
| 33 | Supply and installation in repairs, commissioning and testing Polycarbonate ASTA CPRI approved OEM made main LT Panel made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES including MCCBs and indicator lamps which shall be UV resistance in accordance with IEC 61439-1, clause 10.2.4: INCOMER:- 400 Amp, 4 pole MCCB, 36 KAAdj.Thermal & Magnetic Released - 01 No Digital Volt meter 0-500V with iinbuilt selector switch - 01 NoDigital Amp meter 0-400A with iinbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 01 NoCopper Bus Bar 630Amp TPN OUTGOINGS:250 Amp, MCCB TPN 36KA 415 V Adj.Thermal & Magnetic Released - 01 Nos 100 Amp, MCCB TPN 25KA 415 V Adj.Thermal & Fixed Magnetic Released - 02 Nos 63 Amp, MCCB TPN 16KA 415 V Adj.Thermal & Fixed Magnetic Released - 02 Nos |
| 34 | NOTE FOR SRL ITEM NO 33 : The panel shall be anti-acid & anti corrosive. Degree of protection against mechanical load shall be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of CPRI TEST REPORT IN POLYCARBONATE only also share panel assembled by OEM, channel partner or sister concern assembly will not be accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket shall be internally embedded made of polyurethane. The Panels made by aprroved enclosures in MES & they shall submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily - Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak & short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits. The board manufacturer shall submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel shall pass glow wire test 960 degrees Centigrade in accordance with 60695-2-11 [flame retardant and self-extinguishing].Make-SIEMENS, L&T, ABB, SCHNEIDER, LEGRAND, HENSEL, BHANDARI, INDO ASIAN, OSIAN, C&S ELECTRIC LTD, SHALABH, HAVELLS, HARTEK, STANDARD, JACKPOWER |
| 35 | All as per the description of Srl item No. 33 here-in-before, but LT Panel comprising of following:-INCOMER:250 Amp, 4 pole MCCB, 36 KA 415V Adj. Thermal & Adj. Magnetic Released - 01 No,Digital Volt meter 0-500V with inbuilt selector switch - 01 NoDigital Amp meter 0-250A with inbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 01 NoCopper Bus Bar 300Amp TPN OUTGOINGS: 100 Amp, MCCB TPN 25KA 415 V,Adj.Thermal & Fixed Magnetic Released - 03 Nos 63 Amp, MCCB TPN 16KA 415 V,Adj.Thermal & Fixed Magnetic Released - 01 Nos. |
| 36 | All as per the description of Srl item No. 33 here-in-before, but LT Panel comprising of following:-INCOMER:630 Amp, 4 pole MCCB, 36 KA 415V Adj. Thermal & Adj. Magnetic Released - 01 No,Digital Volt meter 0-500V with inbuilt selector switch - 01 NoDigital Amp meter 0-600A with inbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 01 NoCopper Bus Bar 800Amp TPN OUTGOINGS:400 Amp, MCCB TPN 36KA 415 V, Adj.Thermal & Magnetic Released - 01 Nos. 250 Amp, MCCB TPN 36KA 415 V, Adj.Thermal & Magnetic Released - 02 Nos. |
| 37 | All as per the description of Srl item No. 33 here-in-before, but LT Panel comprising of following:-INCOMER:250 Amp, 4 pole MCCB, 36 KA 415V Adj. Thermal & Adj. Magnetic Released -01 No,Digital Volt meter 0-500V with inbuilt selector switch - 01 NoDigital Amp meter 0-250A with inbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 01 NoCopper Bus Bar 300Amp TPN OUTGOINGS:100 Amp, MCCB TPN 25KA 415 V, Adj.Thermal & Fixed Magnetic Released - 01 Nos. 63 Amp, MCCB TPN 16KA 415 V,Adj.Thermal & Fixed Magnetic Released - 03 Nos. |
| 38 | All as per the description of Srl item No. 33 here-in-before, but LT Panel comprising of following:-INCOMER:- 160 Amp, 4 pole MCCB, 36 KAAdj.Thermal & Magnetic Released - 01 No Digital Volt meter 0-500V with iinbuilt selector switch - 01 No Digital Amp meter 0-400A with iinbuilt selector switch & CT Coils- 01 NoSet of LED type indicating lamps - 01 No Copper Bus Bar 630Amp TPN OUTGOINGS:63 Amp, MCCB TPN 16KA 415 V Adj.Thermal & Magnetic Released - 04 Nos |
| 39 | Demolition of cement concrete ( unreinforced) of any description and in any position not otherwise specially provided forincluding removal of debries out of defence land complete all as specified and directed |
| 40 | Material and labour for 100 mm thick plain cement concrete 1:4:8type D-2 using 40 mm graded crushed stone aggregate as in sub base of floors, complete all as specified and directed. |
| 41 | Material and labour for 50 mm thick plain cement concrete 1:3:6type C-2 using 40 mm graded crushed stone aggregate as in floors, finished the surface even and fair, complete all as specified and directed. |
| 42 | Note: The Total amount shall subject to adjustment of credit of Rs.91520.00 for old Materials as per Schedule of Credit |