Tender For Special Repair To Central Ac Plant Serial Nos. 0000001 And 0000002 At Mh Bhopal Under Ge Bhopal, bhopal-Madhya Pradesh

Military Engineer Services-MES has published Tender For Special Repair To Central Ac Plant Serial Nos. 0000001 And 0000002 At Mh Bhopal Under Ge Bhopal. Submission Date for this Tender is 09-03-2023. HVAC Tenders in bhopal Madhya Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

35811692
Corrigendum : Tender For Special Repair To Central Ac Plant Serial Nos. 0000001 And 0000002 At Mh Bhopal Under Ge Bhopal
Open Tender
Indian
Madhya Pradesh
bhopal
09-03-2023

Tender Details

Special Repair To Central Ac Plant Serial Nos. 0000001 And 0000002 At Mh Bhopal Under Ge Bhopal

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 08-Feb-2023 Date Amendment Date 21-02-2023
2 15-Feb-2023 Date Amendment2 Date 25-02-2023
3 15-Feb-2023 RevisedBOQ BOQ 25-02-2023
4 25-Feb-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 04-03-2023
5 04-Mar-2023 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 09-03-2023

Key Value

Document Fees
INR 1000 /-
EMD
INR 112000.0 /-
Tender Value
INR 58 Lakhs /-

BOQ Items

Name of Work: SPECIAL REPAIR TO CENTRAL AC PLANT SERIAL NOS. – 0000001 AND 0000002 AT MH BHOPAL UNDER GE BHOPAL
Sl. No. Item Description
1Surveying, estimating, taking down, transporting, repairing, installing, testing and commissioning of compressor assembly of Chiller Nos 1 & 2, Sr No-0000001 & 0000002, Make: Voltas, Model No. ACEGWFXR2501MLS1, 3 x 250 TR chilled water type AC plant installed at MH Bhopal including inspection by specialist engineer for identification of defects, including replacing/ repairing of unserviceable parts, dehydration, welding works, brazing works, leakage testing with nitrogen gas, refrigerant recovery, leakage rectification, evacuation of both circuits, filling of compressor oil & refrigerant gas complete along with overhauling of components connected with condenser and chiller unit both side etc complete all as specified and as directed. Note: (a) Materials identified for replacement will be measured and paid separately under relevant items of the schedule as supply only. (b) Contractor shall inspect the site before quoting the tender. (c) The compressor shall be transported to the OEM (Voltas) workshop from MH Bhopal for repairing and again transported to the MH Bhopal from the workshop for installation. The exact location (anywhere in India) of the workshop shall be ascertained by the contractor before quoting. (d) The repair work shall be carried out by the contractor through authorised service agency/OEM. (e) Testing of AC plant shall be carried out in presence of the rep deputed by the Accepting Officer. (f) The rates quoted by the contractor shall be inclusive of all these aspects.
2Supply only compressor oil grade CP 120 and of specifications as existing at the site, Make- Solest
3Supply only Oil Return Filter 3/8 and of specifications as existing at the site, Make -Danfoss
4Supply only Slide Valve O Ring and of specifications as existing at the site
5Supply only Oil filter dryer core of both refrigerant circuit and of specifications as existing at the site
6Supply only Water Differential Switch and of specifications as existing at the site
7Supply only Contactor 3 TF51 and of specifications as existing at the site
8Supply only Single phase Preventer and of specifications as existing at the site
9Supply only MCS EVX Controller and of specifications as existing at the site
10Supply only Suction Pressure Transducer and of specifications as existing at the site
11Supply only Industrial type temperature sensor of evaporator entering, condenser entering and evaporation leaving discharge temp for chiller with complete "U" Shape pipe fittings of existing type and connected fittings and of specifications as existing at the site
12Supply only Unloading Plunger and of specifications as existing at the site
13Supply only Oil filter of both refrigerant circuit and of specifications as existing at the site
14M & L winding of compressor motor with copper wire of size and specifications as existing at the site compressor of Make: Voltas, Model No. VLX1130 VI 2.6 complete all as specified and as directed.
15Supply only bearing set for compressor Make: Voltas, Model No. VLX1130 VI 2.6 and of specifications as existing at the site.
16S & F mild steel ERW pipe of outside dia 219.1 mm, thickness 6.3 mm insulated with Class-O closed cell elastomeric nitrile rubber (of Make Aerocell) tubular sleeve sections of 19 mm thickness complete all as specified and as directed.
17S & F in repairs butterfly valve cast iron, PN 1.6, class 125, nominal size 65 mm as per IS 13095: 1991 complete all as specified and as directed.
18Supply and installation in repair of 200 mm cast iron Y-type strainer flange ends with fittings (GI Nut Bolts, gasket etc) etc. complete all as specified and as directed. Make: Zoloto/ AUDCO/ Kirloskar.
19Supply and of filling refrigerant gas R- 134A in sealed cylinders, complete NOTE ;- ( Empty gas Cylinders shall be returned to contractor after use.) Mafron/ Freon/ Fluron
20S & F in replacement microprocessor based computerised mother board PLC controller complete with software programming suitable for Central AC Plant 250 TR Panel of Make: VOLTAS (MCS MAGNUM) complete all as specified and as directed.
21S & F in repairs air relief valve, single air valve small orifice type (S1), scrwed ends, 15 mm nominal size as per IS 14845: 2000 complete all as specified and as directed.
22Supply & fix in repair contactor model - Code -13 100-250V or as per the site requirement AF265-40 (1SFC101066M0201), AC 415 V ,50 Hz , 3 phase, 4 pole for contractor of LT panel of AC plant complete all as specified and as directed. Make-L&T/Siemens/ABB.
23S & F Variable frequency drive (VFD) of 18.5 KW (25 HP) 50 Hz complete all as specified and directed. Make: ABB Model No -ACS310-03E-41A8-4 or equivalent in L&T SX2000, Crompton.
24Cleaning the cooling tower by cleaning chemical 1039XL,1031XL and applying wire brush, solvent by removing the deposited impurities such as silt, dust particles mud, sand inside the dome and around the fills, on wire mesh, main shaft etc and other connected items complete all as specified and directed.
25S & F in replacement sprinkler of cooling tower of central AC Plant of cap 2 X 250 TR of Make as per the site or as per approved complete all as specified and directed.
26S & F in repairs PVC fills in cooling tower, size 600 mm X 300 mm X 150 mm, honeycomb type, made of virgin PVC, to be installed in cooling tower for central AC Plant of capacity 3 X 250 TR of make as per site requirement or as per approved complete all as specified and directed. Make MM Aqua or equivalent
27S & F butterfly valve cast iron, PN 1.6, class 125, nominal size 200 mm as per IS 13095: 1991 complete all as specified and as directed.
28M & L for servicing of Humidifier 2/3/4 kW, 415 V AC, single step with following repairs all as directed by engineer in charge (a) descaling the storage tank, water level indicator, heating coil/element with descaling solution/agent and soft brush with non-metallic bristles without affecting thermal insulation/top cover gasket. (b) inspecting control wiring including replacement of unserviceable wiring, servicing of power contactors etc. (c) replacement of double tube air heater of 3 kW or as per the requirement at the site (d) inspecting/testing, servicing of relays, other safety valves
29M & L for servicing of chiller / condensing pump & remove the all dirt, rust of shaft impellor by machinery work etc of capacity 25 HP and gland packing, studs and nut bolts with bushes with two coats of paints after primer on angle on which motor fixed etc as required at site all as directed by Engr-in-Charge.
30M & L for servicing of Primary & secondary pump and remove all dirt, rust of shaft impellor by machinery work etc. of capacity 7.5 HP and gland packing, studs and nut bolts with bushes with two coats of paints after primer on angle on which motor fixed etc. as required at the site complete all as specified and directed.
31M & L for cleaning of condensing coil of AHU & valve with chemical solution by pressure pump with specific pressure for removal of dirt and scale deposited in pipe, solution to be recommended by OEM. Complete fittings of below given supply only parts in AHU and duct including supply and installation of Strip Heater 3 kW - 08 Nos with thermostat and make it functional from troubleshooting of humidity complete all as specified and directed.
32Supply of transformer 220 V AC to 24 V AC, AT140B1024 Class 2 PRI-1-COM, 2-208V,3-240V, 60 Hz, 0.22A SEC.-4-5 24VAC, 40 VA complete all as specified and directed. Make: - Honeywell - MPLS, MN
33Supply and fix of AHU actuator 24 V 50 Hz 6 VA Class 2 ML7420A8088-SBE065 Size DN 65 flow accuracy 4% 3/4 "" Stroke 1.0 min complete all as specified and directed. Make: Honeywell
34Supply of AHU thermostat Make: Honeywell T279812000
35Supply and fix in repairs pre-filter, anodised aluminium frame, filter media of non-woven Synthetic supported by aluminium expanded mesh on one side and finished with HDPE mesh on the other side, Efficiency: 99% down to 5 micron, water washable and air cleanable, size 610 mm X 610 mm X 50 mm complete all as specified. Make: Thermadyne, American air filter, Camfil air filter, Dyna Filters Pvt. Ltd.
36Supply and fix in repairs pre-filter, anodised aluminium frame, filter media of non-woven Synthetic supported by aluminium expanded mesh on one side and finished with HDPE mesh on the other side, Efficiency: 99% down to 5 micron, water washable and air cleanable, size 305 mm X 610 mm X 50 mm complete all as specified. Make: Thermadyne, American air filter, Camfil air filter, Dyna Filters Pvt. Ltd.
37Supply and fix in repairs pre-filter, anodised aluminium frame, filter media of non-woven Synthetic supported by aluminium expanded mesh on one side and finished with HDPE mesh on the other side, Efficiency: 99% down to 5 micron, water washable and air cleanable, size 305 mm X 305 mm X 50 mm complete all as specified. Make: Thermadyne, American air filter, Camfil air filter, Dyna Filters Pvt. Ltd.
38Supply and fix in repairs pre-filter, anodised aluminium frame, filter media of non-woven Synthetic supported by aluminium expanded mesh on one side and finished with HDPE mesh on the other side, Efficiency: 99% down to 5 micron, water washable and air cleanable, size 580 mm X 580 mm X 50 mm complete all as specified. Make: Thermadyne, American air filter, Camfil air filter, Dyna Filters Pvt. Ltd.
39Supply and fix in repairs high efficiency particulate air filter (HEPA), flange type, anodised aluminium frame, filter media of micro glass fiber having water repellent property, Efficiency: 99.97% down to 0.3 micron, temperature resistance upto 1200C, humidity resistance upto 100% RH, minimum 1000 CFM air flow, size 610 mm X 610 mm X 305 mm complete all as specified. Make: Thermadyne, American air filter, Camfil air filter, Dyna Filters Pvt. Ltd.
40Supply and fix in repairs high efficiency particulate air filter (HEPA), flange type, anodised aluminium frame, filter media of micro glass fiber having water repellent property, Efficiency: 99.97% down to 0.3 micron, temperature resistance upto 1200C, humidity resistance upto 100% RH, minimum 500 CFM air flow, size 305 mm X 610 mm X 305 mm complete all as specified. Make: Thermadyne, American air filter, Camfil air filter, Dyna Filters Pvt. Ltd.
41Supply and fix in repairs high efficiency particulate air filter (HEPA), mini pleat box type, anodised aluminium frame, filter media of micro glass fiber having water repellent property, Efficiency: 99.97% down to 0.3 micron, temperature resistance upto 1200C, humidity resistance upto 100% RH, minimum 1000 CFM air flow, size 610 mm X 1219 mm X 90 mm complete all as specified. Make: Thermadyne, American air filter, Camfil air filter, Dyna Filters Pvt. Ltd.
42Supply and fix in repairs high efficiency particulate air filter (HEPA), mini pleat box type, anodised aluminium frame, filter media of micro glass fiber having water repellent property, Efficiency: 99.97% down to 0.3 micron, temperature resistance upto 1200C, humidity resistance upto 100% RH, minimum 750 CFM air flow, size 610 mm X 915 mm X 69 mm complete all as specified. Make: Thermadyne, American air filter, Camfil air filter, Dyna Filters Pvt. Ltd.
43Supply and fix in repairs bag filter box type, anodised aluminium frame, filter media of non-woven Synthetic supported by aluminium expanded mesh on one side and finished with HDPE mesh on the other side, Efficiency: 99% down to 5 micron, water washable and air cleanable, size 610 mm X 610 mm X 300 mm complete all as specified. Make: Thermadyne, American air filter, Camfil air filter, Dyna Filters Pvt. Ltd.
44Supply and fix in repairs bag filter box type, anodised aluminium frame, filter media of non-woven Synthetic supported by aluminium expanded mesh on one side and finished with HDPE mesh on the other side, Efficiency: 99% down to 5 micron, water washable and air cleanable, size 305 mm X 610 mm X 300 mm complete all as specified. Make: Thermadyne, American air filter, Camfil air filter, Dyna Filters Pvt. Ltd.
45Supplying, fixing, testing and commissioning including designing water softener plant for flow rate of 20000 litre per hour with 650 litre ion exchange resin 225 Na and automatic sand filter with complete electrical connection to various parts of softener plant consisting of the following parameters: - (a) 1 HP Pump for recharging: Make- Crompton/Kirloskar (b) Vessel FRP Size (01 Nos): Height :72 inch / Dia:30 inch (c) Ion exchange resin quantity in litres:650 (d) Salt quantity in KG, each regeneration: 80 (e) Regeneration (250 PPM hardness) in after :150000 litre (f) Supporting Bed - Gravels & Media (g) Brine Tank Capacity (HDPE) :1000 Kg. (h) Multipurpose Valve: Automatic Designer valve (i) CPVC Pipeline for drain water to drain sump :30 RM (j) Multipurpose valve size & mounting50 NB/side mount (k) Minimum/ Maximum operating pressure (Min & Max):1.5 & 3.5 Kg/square cm (l) M.O.C of pipeline - CPVC (m) Type of valve on frontal pipeline - CPVC Butterfly (n) 50 mm dia Butterfly valves on frontal pipeline - 03 Nos (o) Sampling cock - 02 Nos (p) Pressure gauge - 02 Nos (q) Injection system with valves for brine dosing - 1 Lot (s) Quality of Raw water: Total hardness = 350 ppm (t) Quality of treated water: Total hardness = < 50 ppm (u) Size of CPVC Pipe for connection :50 MM (v) Type of media - Resin Ion exchange (225 Na) Automatic Sand Filter: (a) Vessel Dia: 24 inch, (b)Vessel height :72 inch, (c) Silex media (kgs): 250, (d) Coarse Sand media (Kgs) :100, (e)Activation media: Only Backwash, (f) Maximum Flow rate: 10000 LPH, (g)Multipurpose Valve: Automatic Designer Valve, (h) Maximum valve size & mounting: 50 NB side mount, (i)Minimum/ Maximum operating pressure (Min & Max):1.5 & 3.5 Kg/square cm (Note- (i) Rate quoted is deemed to be included for complete erection of plant as directed including necessary carried out as per the OEM design and all the filter media materials required to be fill inside the filtration plant to get the treated water as parameters mentioned here in before. (ii) All the water supply system fittings like pressure gauge, operating valves, gate valves, from oxidation chamber to output water line from the plant with complete painting as per the OEM design shall also deemed to be included in quoted rate).
46Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
47Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point
48M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.