| 1 | Supplying, installation, testing and commissioning of main fire pump(MFP /EP) suitable for water discharge of 2280 to 2850 LPM at 120 to 90 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 75kW etc. |
| 2 | Supplying, installation, testing and commissioning of jockey fire pump (JP) suitable for water discharge of 180 to 240 LPM at 90 to 70 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 9.3 kW or of suitable kW |
| 3 | Supplying, erecting, testing & commissioning of fire pump control panel (FCP) of cubical construction, floor mounted type, fabricated from minimum 2 mm thick CRCA sheet, suitable for satisfactory operation of main fire pump and jockey (pressurisation) pumps (1working+1standby) with necessary accessories, wiring &cabling along with allied accessories with following incoming and outgoings,suitable for automatic & manual operation on 415V, 3 phase, 50Hz ac supply as per specifications |
| 4 | Providing erecting and giving test and trial of FCMA fully Automatic, Starter with DOL Soft Starter complete with main Contactor, VAF meter , PLC and HMI , push buttons and indications,FCMA module with bypass contactor and its control circuitry etc complete.120HP |
| 5 | Supplying and erecting, assembled Fully Automatic Star Delta starter, in a provided cubical panel to operate squirrel cage induction motor working on 380- 440 Volt, 3 phase, 50 Hz with no volt coil, over load relay and ON-OFF push buttons, with necessary material and connected to supply, etc complete. |
| 6 | Supplying and erecting 200 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV (For Inlet Main Fire pump) |
| 7 | Supplying and erecting 200 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV (For Outlet Main Fire pump ) |
| 8 | Supplying and erecting 200 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV (For Outlet Main Fire pump) |
| 9 | Supplying and erecting 100 mm dia. cast iron double flange sluice valve complete with PN16 pressure rating, as per specification no. FF-VL/SV(For Inlet Jocky pump) |
| 10 | Supplying and erecting 100 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV (For Outlet Jocky pump) |
| 11 | Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV |
| 12 | Supplying and erecting 63mm dia, controlled percolation (C.P.) hose pipe,15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/CPH |
| 13 | Supplying and erecting 150 mm dia fire brigade header suitable for supplying water in fire tank complete as per specification no. FF-FA/FBC |
| 14 | Supplying and erecting fire brigade header ( Siamese connection )of 150 mm dia, for supplying water in fire tank complete as per specification no. FFFA/FMC |
| 15 | Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I.pipe, elbow etc. complete as per specification no. FF-FFA/PG |
| 16 | Supplying and erecting M.S./CRCA cabinet for housing Floor Hydrant valve, hose pipe, hose reel and branch pipe (size 1000 x 736 x 736 mm.) made from 16 SWG sheet and angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8\"x6\") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5) |
| 17 | Supplying and erecting gun metal branch pipe of 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specification no. FFFFA/NZ |
| 18 | Supplying and erecting 12/15 mm dia pressure switch with provided isolation valve, G.I. nipple, elbow, etc complete as per specification no. FF-FFA/PS |
| 19 | Supplying and erecting brass orifice plate having 6 mm. thickness, 140 mm outer dia with required diameter of inner hole at every single outlet hydrant valve as per specification no. FF-FFA/OP |
| 20 | Supplying and erecting 300 mm dia 1.5m in height air vessel / tank fabricated from min 5mm thick M.S. sheet complete as per specification no.FF-FFA/ACT |
| 21 | Supplying and erecting 200 mm dia Cast Iron end line strainer of T-Pot type flanged end pattern, PN16 pressure rating, screen of SS and end connection with flanged, for positive suction complete as per specification no. FF-VL/ELS |
| 22 | Supplying and erecting 100 mm dia Cast Iron end line strainer of T-Pot type flanged end pattern, PN16 pressure rating, screen of SS and end connection with flanged, for positive suction complete as per specification no. FF-VL/ELS |
| 23 | Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mm width & 100 mm height comprising all required stand. accessories. |
| 24 | Cable |
| 25 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armouredcable 1100 V, 3½ core 240 sq. mm. Al armoured conductoras per specification no. CB-LT/CU (Transformer to Pumphouse) |
| 26 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armouredcable 1100 V, 3½ core 35 sq. mm. Al armoured conductor Double run as per specification no. CB-LT/CU (Transformer to Pumphouse) |
| 27 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armouredcable 1100 V, 4 core 6 sq. mm. Al armoured conductor Double runcompleteas per specification no. CB-LT/CU (Premises) |
| 28 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armouredcable 1100 V, 4 core 10 sq. mm. Al armoured conductor Double runcompleteas per specification no. CB-LT/CU (Premises) |
| 29 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 50 sq. mm. copper conductor complete as per specification no. CB-LT/CU |
| 30 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 25 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 31 | Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3 core 25 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU |
| 32 | Dismentalling Joint. |
| 33 | 200 mm dia Joint |
| 34 | 100 mm dia Joint |
| 35 | Chain Pulley Block with Travelling Trolley-Providing, erecting triple spur gear type Chain Pulley Block suitable for capacity as below with 6 m lift complete with load chain and hand chain suitable for above lift, tested to 50% over load as per IS 3832 carrying ISI mark.with Travelling trolly 1 Tonn |
| 36 | Epoxy painting on both side of approved colour shade of provided iron work /MS / CRCA sheet steel work complete along with anti-rust treatment complete. |
| 37 | Painting identification number by indelible ink marker / enamel paint on fittings / equipment |
| 38 | Supplying and erecting GI sheet 1.6 mm (16 SWG) having zinc coating of 350 microns with galvanization process compliance to IS 2629:1985 to be used for fabrication of boxes panel boards etc. including cutting, bending, drilling,welding, riveting etc. and painting with one coat of red lead paint and 2 coats of enamel paint. |
| 39 | Supplying and erecting Level indicater |
| 40 | Supplying and erecting M.S.Pipes and specials |
| 41 | Providing fabicating and fixing MS Structural Steel work for necesaary Support of Panel Board, Sluice Valve, Reflux Valve, Delivery Line and Lifting arrangement etc complete per detailed specifications attached. |
| 42 | Dismentalling of old Machinery and plants etc. |