Ministry of Housing and Urban Affairs has published Tender For Data Centre Infrastructure Mse. Submission Date for this Tender is 27-01-2023. Sirens Tenders in Gandhinagar Gujarat. Bidders can get complete Tender details and download the document.
Sl. No. | Item Title | Item Description |
1 | IT Server Room - Rack | SITC of RACKS CTO CYBER RACK CY 42U 800W 1000D. With Front PRF and rear Dual Door, Side Panels with Earthing kit, 4 No. Castor Set. PDU 10 X 5or15 Amp With 32 Amp MCB 3 nos and 1 PDU set Universal. With mechanical Door Lock and Keboard and Monitor Tray Make- ValrackorAPWorVertive |
2 | IT Server Room - AC | Providing and erecting Inverter based approved make split air-conditioning unit - 2.2 ton - consisting of condensing unit with variable speed fan motor, inverter type hermetically sealed rotary compressor with accessories etc. duly connected separately erected evaporating unit and blower motor with its accessories by means ofextra supplied proper insulated copper tubing,drain PVC pipes suitable for -cost includes Eco Friendly green gas charging and 15A plug top and Remote Control and MS Stand, Cu pipe line - . Make- Mitsubisi or Daikin Heavy Duty 5 Star Invertor |
3 | IT Server Room - AC Operate | SITC of 2 Multiple AC cyclic designed with variable setting time systems to operate alternate AC with manual switch for maintenance. Suitable for 2 ton AC Make- Insu or Equivalent |
4 | IT Server Room - Fibre Cable | SITC of 6 Core Multi Mode Armoured metal free fibre cable with suitable sheath and glass roving. Cable laying in suitable metal pipe with clamping. Make- D Link, Legrand, Polycab |
5 | IT Server Room - PVC Pipe | Providing and fixing 25 mm. dia Pvcinsulated G.I corrugated flexible pipe with necessary socket, PVC or GI bushes Saddle. 25 mm Dia Make- Precision or Equivalent |
6 | IT Server Room - PVC Pipe | 16 mm dia |
7 | IT Server Room - raised Flooring | Supply and erecting server room raised flooring system with cable dressing and Laying. Floor panels are heavy grade high pressure laminate with Steel adjustable pedestal support system. Wight baring ability normal heavy grade to extra heavy garde. Height 230 to 300 mm as per suitable. |
8 | IT Server Room - UPS | Supply, Testing and Commissioning of ON LINE UPS system with SMF battery and 120 min back and with battery rack complete in all respect. 1 set. of 20KVA UPS Single Conversion Type UPS 3 ph in 3 ph out. Make- APC, Vertive |
9 | IT Server Room - Smoke Detector | Supply, Insta llation, TestingAndCommissioningof UL Listed AnalogaddressableSelf Acclimatising Multi Sensor smoke detector with mounting based LED, Address Switch from 01- 159, to programme the detectors, complete as perall requirements of technical specifications and contracts works. Approved Make- Notifieror Honeywell |
10 | IT Server Room - Temp. Detector | Supply, Insta llation, Testing And Commissioning of UL Listed, Fixed temperature cum rate of rate of rise heat detector, Address Switch from 01-159,to programme the detectors, as per all requirements of technical specifications and contracts works. Approved Make- Notifieror Honeywell |
11 | IT Server Room - copper cable | Supply and laying of 2 Core X 1.5 sq.mm. FRLS Armoured PVC Insulated Fire Alaram copper cable. Approved Make- KEIorPolycaborFinolexorRR Kabel |
12 | IT Server Room - manual call point | Supply, Installation, Testing And Commissioning of UL listed, Flush or surface mounted Manual CallPoint in manufacturers prescribed matching red enamel outletbox complete with key operated test-reset lock. The word FIRE shall appear in front of station as per all requirements of technical specifications and contracts works. Approved Make- NotifierorAgnior Honeywell |
13 | IT Server Room - Siren | SITC of Siren with inbuilt Flash Make- Notifieror Honeywell |
14 | IT Server Room - Fire alarm panel | Supply,Insta llation,Testing And Commissioning of Microprocessor based 1 loop capacity panel should be capable of expanding upto 8 loop,Networkable analogue addressable type fire alarm control panel with 640 characterLCDdisplay,each loop shall have a minimum capacity of 90 detectors and 90 devices analog in one loop. The Panel Shall have High-Speed Network Communications Module fiber-optic cable interface. The panel shall have integrated QWERTY Keypad, 4000 History logging event, Four access levels, capable of taking Flash Scan devices, flash EPROM,sufficientnumbers of programmable relay controls for controlling AHUs, pressurization fans, ventilation fans at fire pump room, monitoring of fire sprinkler and fire hydrant pump, 240 volts AC power supply, automatic supervised battery charger, 24 volts sealed lead acid batteries sufficientfor 24 hours normal working and then be capable of operating the system for 120 Minutes in emergency conditions as required. Integrated8channel DigitalVoice Evacuation and 2 way Communication Fire Alaram System capable tosupervision ofall the speaker circuits with zone selection, and accessories required to complete the system.The DVC should be fully integrated with Fire alarm Panel and in single Enclosure. Approved Make- NotifierorHoneywell |
15 | IT Server Room - Rodent control system | SITC of Rodent Control Systeam standalone control 400 Sq. Ft. in floor area and 300 Sr. Ft in False Ceiling and Flase FLooring area |
16 | IT Server Room - MCB | Providing and erecting Sheet Steel powder coated MCB distribution board - flush or surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 and 3, IEC 61439-1 and 3 without MCB to house appropriate nos. of MCBs.- The DBs should be used of same company of MCB to be used - suitable for - B - three phase incoming and single phase horizontal type outgoingPer phase isolation type - PPI - 8Way Double Door, 63A FP MCB -1, 40A DP ELCB 30 mA, SP MCB 6 -32A C Curve - 24 Nos Make- LandT, Legrand, CandS, Havells |
17 | IT Server Room - FP APCCL Switch | SITC of 32 Amp FP ACCL Switch for DB |
18 | IT Server Room - pipe | Providing and erecting XLPE- IS-7098 -- I --88 ISI armoured cable multistrand or SolidCopperconductor for1.1 KV. to be laidon wall with necessary clamps or in existingtrenchor pipe at road crossing or floorof followingsize of cables. - C - 4 core 6 Sq. mm |
19 | pipearmoured cable | Providing and erecting XLPE- IS-7098 -- I --88 ISI armoured cable multistrand Copperconductor for1.1 KV. to be laidon wall with necessary clamps or in existingtrenchor pipe at road crossing or floorof following size of cables. - A - 3 1or2core 25 Sq. mm -10 Sq. mm 1or2 core - Make- RRorPolycabor KEI |
20 | IT Server Room - pipe | C - 3 1or2core 50 Sq. mm -25 Sq. mm1or2 core - |
21 | IT Server Room - copper wire | providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in or on wall or ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size. - b - 2 wire 6 sq. mm with Rigid PVC Pipe |
22 | IT Server Room - copper wire | Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipeto be erected concealed in orflushed on wallorceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size - b - 2 wire 2.5 sq. mm with Rigid PVC Pipe |
23 | IT Server Room - earthpit | Supplying and erecting in earthpit of minimum bore dia. 225mm sizeapproved make Safe Earthing Electrode consisting Pipe-in-Pipe Technology as per IS 3043-1987 made of corrosion free hot dipped G.I.Pipeshaving Outer pipedia of 80 mm having 80-200 Micron galvanising, Inner pipe dia of 40 mm having 200-250 Micron galvanising, connection terminal dia of 14 mm with constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for following type of applicationswith chamber and heavy duty cover.- approvedmake OEM has to submit test certificate including value of earth resistane of installation. - C - For Electrical Installation covering Transformer Neutrals, Lightningarrester Earthing, A.C.Plant and SensitiveComputer System- likeAutomation,SCADA -i.e. independent Earthinglocated in other than normal soil i.e. Soft Rock,Marshy Soil etc.. -Length of Pipe - 3 Mtrs.-Back filling Compound -2 nosBags of 25 Kg. |
24 | IT Server Room - wire | providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed copper conductor with heat resistant PVC insulated conforms to IS 694, IEC - 227 erected in existing pipe offollowing size - Specifically for control panel, relays, power switchgears, motor starters and control wiring - with required size of copper lugs, nuts and bolts if required. - f -One wire 10.00 sq. mm |
25 | IT Server Room - wire | - e - One wire 6.00 sq. mm |
26 | IT Server Room - pipe | Providing and erecting ISI mark Medium class RIGID PVC PIPES of following size complete to be erected onorin wall or ceilingerected with necessary PVC fittings and Junction boxes fixed with adhesive solution and Clamps with following dia of pipes, in approved manner as directed - a -20 mm |
27 | IT Server Room - pipe | - b - 25 mm |
28 | IT Server Room - Voltage Protection | SITC of FP Volage Surge Protection System Type 1 and 2 -Protectin against Direct and Indirect Light surage - Maximu Protection 100kA. Make - LandT, Schinder, Legrand |
29 | IT Server Room - LIU | Supply, Installation, Testing and Commissioning of 6 F LIU with FDMS, 1U, LC SM OM2, Loaded Pigtails, Splice tray, adapter and splice with FDMS. protectors.Dressing existing and New CableApproved Make- Polycabor D Link or Legrabd |
30 | IT Server Room - Fibre patch cord | Supply, Insta llation, Testing and Commissioning of Duplex LC To LC MM Fiber Patch Cord 3 mtr. Approved Make- Polycabor D Link or Legrabd |
31 | IT Server Room - camera | Supply, Installation, Testing and Commissioining of 4 MP, progressive scan, CMOS image sencor, Fixed Color IR, IP Dome Camera, 1080P resolution, POE, 2.8 or 3.6 mm, SIP enabled for indoor, wall or ceiling mounted. Approved Makes- Matrix, Bosch, Honeywell |
32 | IT Server Room - NVR | Supply, Installation, Testing and Commissioning of 8 Channel NVR with 1 SATA, with 1080p Realtime Live View H.265orH.264 MJPEG dual codec decoding Up to 12 MP resolution preview and playback Max 320 Mbps incoming bandwidth support 4 SATA HDDs up to 16 TB, Supports fisheye videode-warping in local and web user interface,Supportsvisual or auditory notifications- a flashing light, bell,or siren - ONVIF compliant, UL, CE, FCC and and RoHS compliant. Including 4 TB SATA HDD with minimum 30 days backup. Approved Makes-Matrix, Bosch, Honeywell |
33 | IT Server Room - POE Switch | Supply, Insta llation, Testing And Commissioning of Gigabit POE switch with 8 Port 10or100or1000BaseT ports with 2 Gigabit SFP Port. Approved Make- DLINK or JVJor Zyxel Vendor Authorized OEM Certificate required |
34 | IT Server Room - Door access | SITC Door Acess Control Systeam with Fingering, Bar card and Keypad Password Access user capacity 100 including Software. Approved Make- Matrix or Honeywell or Bosch Vendor Authorized OEM Certificate required |
35 | IT Server Room - LAN Cable | Supplying and erecting approved make LAN cable of following size in existing pipe as per direction D - CAT - 6 eApproved Make- Dlink or Vendor Authorized OEM Certificate required |
36 | IT Server Room - POE Switch | Supply, Insta llation, Testing And Commissioning ofGigabit POE switch with 24 Port 10or100or1000BaseT ports with 2 Gigabit SFP Port. Approved Make- HPor Cisco Vendor Authorized OEM Certificate required |
37 | IT Server Room - UPVC Cable | Supplying and laying UPVC cable trunking system comprising unplasticised polyvinyl, chloride rigid material with ignition free and flame proof confirming BS with necessary end caps Internal and external bend, flat bends, coupler, tee etc..All necessary accessories and measuring of following sizes - 2 - 100 mm x 50 mm trunking |
38 | IT Server Room - Pt. wiring | Point wiring for Light or Bell with2-1.5 sq.mmand earth wire of 1.5 sq.mm - Green - both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length , in below type of pipe erectedwith 6A Modular type switch or bell push and accessories and earth continuityof following type, erected on PVC or MetallicorWooden box, single mounting base framecovered with texturedormetallicorwhite front plate modules erected on orin wall or ceiling as per pipe erected, with necessary Lamp holderorceiling rose or H.D.Connector as directed. Cat. III |
39 | IT Server Room - Plug | Point wiring for Individual Plug withand earth wire of 1.5 sq.mm - Green - both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erectedcomplete with Modular type switch and 5 pin Plugerected on PVC or MetallicorWooden box covered with appropriate front plate modules erected on or in wall or ceiling as per pipe erected with following type of accessories. - I - For 6A Plug and 6 a switchwith 2-1.5 sq.mm Cu. Wire from nearby switchboardormcb db board |
40 | IT Server Room - Plug | - II - For 16A Plug and 16 amp switchwith 2-2.5 sq.mm Cu. Wire from mcb db board. |
41 | IT Server Room - Switch board | Providingand erecting Switchboard for Computer or electric apparatus consisting offollowing modular type accessories mounted withPVCor Metallic concealedoropen box with single mounting base frame covered with texturedormetallic orwhite front plate,modules erected with necessary connections as directed 1 no. 6Aor16A universal plug-switchcombined. 3 nos. 6A Switch 3 nos. 6A 5 pin Plug |
42 | IT Server Room - UPS Shift | Remove 10 KVA UPS with batteries shifting, minor repair and charged battery and re installed at given location as per instruction. |
43 | IT Server Room - POP Cut | POP Cut Out and Fixing and Painting at various location as required. |
44 | IT Server Room - civil work | Wooden and Glass Partion remove, fixing and reparing with minor civil work |