Border Security Force-BSF has published Tender For Repair And Maintenance Of Course Attender Barracks And Staff Room At Ch Kadamtala _Sh Providing Ei And Ex_Fans. Submission Date for this Tender is 23-01-2023. Building Work Tenders in kadamtala West Bengal. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required. (Group -B) |
2 | Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.(a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire |
3 | Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required (a) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire |
4 | Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required (a) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire |
5 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/PVC conduit as required. (a) 3 x 1.5 sq. mm |
6 | Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel /PVC conduit as required. (a) 3 x 4 sq. mm |
7 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (a) 20 mm |
8 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. A) 5/6 Amp |
9 | Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required. (a) 3 pin 5/6 amp socket outlet |
10 | Supplying and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 amps socket outlet and 5/6 amps piano type switch, connection, painting etc. as required. (For light plugs to be used in non residential buildings). |
11 | Supplying and fixing metal box of 180 mm X 100 mm X 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 amps socket outlet and 15/16 amps piano type switch, connection, painting etc. as required. |
12 | Supplying and fixing PVC batten/ angle holder including connections etc. as required |
13 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) a) 8 Way, Double Door |
14 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. A) Single pole |
15 | Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. A) Single Pole and Neutral |
16 | Supplying and fixing stepped type electronic fan regulator on the existing switch box including connections but excluding modular plate etc. as required. |
17 | Supply and fixing of 18 watt Square LED surface/recessed mounted downlight with integrated electronic driver in ceiling/surface complete with all accessories including connections etc. as required. |
18 | Providing and fixing of 20 watt LED tube fitting indoor decorative PC housing extruded LED batten - integrated type complete with all accessories directly on wall/surface including connections with 1.5 Sqmm FRLS PVC insulated copper condutor, single core cable and earthing etc as requried. |
19 | Providing and fixing of380 mm sweep metal blade heavy duty exhaust fanincluding louvers/ shutters and making/drilling hole, connections with 1.5 sqmm copper wire etc. as required and directed by engg incharge. |
20 | Supplying, Installation, testing and commissioning of 1200 mm sweep ceiling fan, including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core able etc as required. |
21 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required, a) 3½ X 35 sq. mm (32mm) |
22 | Excavation for cable trenches of depth upto 1.2 m in soft soil including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metres. |
23 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. complete as required. a) 63 mm dia (OD-63 mm & ID-51 mm nominal) |
24 | Providing and laying one number of PVC Sheathed PVC insulated XLPE Power Conductor aluminium armourd cable 650/ 1100 V grade of following sizein the existing RCC/ HUME/ METAL pipe as required. The cable should conform to IS 7098 (Part1) 1988 with upt date amendents if any. a) 3½ X 35 sq. mm |
25 | Supplying and Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.. a) 3.5x35 sqmm(clamped with 1mm thick saddle) |
26 | Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. a) 3.5x35 sqmm |
27 | SITC of various sizes water protected outdoor type (water proof) hut type compartmentalized type double door cubical panel both side opening with 450 mm depth suitable for 415 V, 3 phases, 50 Hz made out of 2 mmthick CRCA sheet with required hardware duly painted with power coated. The panel having separatedetachable gland plateangle iron base frame made out of 50 mm x 50 mm x 5 mm angle iron of suitable size of the feeder pillar (minimum height 60 cm), hinged door, both side opening with locking arrangement, earth bar /stud, LED pilot light for phase indicator (R,Y,B) on top, 400A/415V 4 stripaluminum bus bar duly PVC sleeved, connection inter-connection with 25% extra current carrying capacity solid aluminium rod /solid copper conductor cable 10 sqmm/for incoming/Outgoing cables, links /heavy duty connectors/ terminals for three and single phase cable connections and for DP Isolators including marking of location for incoming and out going distribution i/c grouting the legs in existing floor with 1.3.6 cement concrete foundation and dismantinng the existing panel, incoming/outgoing cable connections etc asrequired. |
28 | Providing and fixing following rating and breaking capacity Triple pole 415 volt MCCB With Fixed Thermal Magnetic Trip Unit (TMD) with alluminume bus bar link in existing cubicle panel board ( in item no 27) including drilling holes in cubicle panel, making connections,i/c dismentling the existing switch gears alongwith electrical acessories etc as reqd. a) 125 Amp, 15-18 KA |
29 | Providing and fixing following rating and breaking capacity Triple pole 415 volt MCCB With Fixed Thermal Magnetic Trip Unit (TMD) with alluminume bus bar link in existing cubicle panel board ( in item no 27) including drilling holes in cubicle panel, making connections,i/c dismentling the existing switch gears alongwith electrical acessories etc as reqd. a) 63 Amp, 15-18 KA |