| 1 | INSTALLATION OF 3 NOS. OF NEW 250 KVA , 11/0.415 KV DISTRIBUTION TRANSFORMER FOR HOSTEL, SPORTS COMPLEX, APARTMENTS & RESIDENTIAL COMPLEX. |
| 2 | GI Steel tubular pole SP-35 |
| 3 | 250 KVA, 11/0,4 KV Transformer (CU Wound) raised RCC Plint/Platform mounted. Note the DTs shall be of 4 star and above ratings as per IPDS Specifications. |
| 4 | GIChannel 100x50x6 mm for X arm, switch D.O. etc. (2.2 Mtrs length weighing 20.24 Kg each)) |
| 5 | M.S. Angle 50x50x6 mm for DT LT Bus Bar (2.2 mtr weighing 10 Kg each) |
| 6 | Lightning arrestor, Distribution Class (9KV, 5KA, 1Ph). (Lamco/Oblum or other superior brands). |
| 7 | 11 KV GO air break switch complete 3-ph(heavy duty) (Yamuna/RPG/RM Electricals make) |
| 8 | 11 KV D.O. fuse with operating rod(heavy duty) (Yamuna/RPG/RM Electricals make) |
| 9 | GI Wire 6 SWG (5 mm dia) weighing 19.2 Kg per 100 metre Coil - for Pole Earthing |
| 10 | Earthing Materials for Transformer and LA |
| 11 | i) Copper Plate 2ft x2 ft, 3mm thick (weighing 11Kg each), for neutral and body - 2 nos |
| 12 | i) Copper Plate 1\"x1\", 3 mm thick (weighing 3Kg each) for LA |
| 13 | ii) Copper wire 5 SWG for Neutral (12 Mtrs ), Body (12 Mtrs) and LA (20 Mtrs), weighing 0.204Kg per mtr. |
| 14 | iii) Charcoal - (20kg/bag) |
| 15 | iv) salt - 50Kg |
| 16 | v) 2\" (25mm)GI Pipe 3 mtr (for water recharge/alternate electrode) |
| 17 | DTR Distribution Cubicle for 250 kVA DTRscomprising of following items and adequate cable ferrules/glands.i) Copper/Aluminium Bus Bar (4 nos), ii) MCCB 320 Amps(4 pole) for incomer conforming to L&T/Schneider make, iii) AMR , DLMS Complaint 3ph 4 wire trivector LTMeter, 5 Amp rated currentconforming to Secure/Genus/ L&T make, iv) 3 ph LTCT (4nos) 400/5 Aenclosed in metallic box with input and out put lugs terminals or butterfly type for fitting on LT bushing conforming to Secure or other superior make, v) 8 nos of 200 Amps Kit kat for 2 nos of outgoing feeders (Heay Duty) |
| 18 | ACSR WEASEL Conductor 6/2.59mm + 1/2.59 mm. |
| 19 | 11 KV polymer pin insulator complete with GI Pin (Yamuna/Denson/Compag/RPG make) |
| 20 | 11 kV Polymer Disc insulator 70 KN (Yamuna/Denson/Compag/RPG make) |
| 21 | H/W fittings for Disc insulator (E&S) 70 KN, Tension type |
| 22 | Tension clamp for ACSR Weasel |
| 23 | PG Clamp for Weasel |
| 24 | LT XLPE Single Core Aluminium ConductorPower Cable of KEI/Havells/Polycab make |
| 25 | i) 240 Sqmm (AL) for DTR LT Bushing to Bus Bar |
| 26 | ii) 185 Sqmm (AL) (for Bus to line 2 CKt) |
| 27 | iii). 150 Sqmm (AL) (for Neutral) |
| 28 | Copper Tubular Terminal ends/Lugs heavy duty (Dowells or other superior make) |
| 29 | i). 240 Sq. mm |
| 30 | ii) 185 Sqmm |
| 31 | iii). 150 Sq. mm |
| 32 | GI M. S. nuts and bolts with MS washer(Assorted) |
| 33 | Danger plate 11KV |
| 34 | Aluminium Tape |
| 35 | Pole double clamp of G.I flat 50x6 mm |
| 36 | Stay set 19 mm dia 1.6 mts. Length with stay rod, bow,plate |
| 37 | GI Stay Wire7/10 SWG weighing 43.4 Kg per 100 metres Coil |
| 38 | MS Rod Welded Mesh (15x2.44) for Fencing of Sub-station . |
| 39 | G. I Pipe 2\" for Fencing Post |
| 40 | INSTALLATION OF 1 NOS. OF NEW 500 KVA , 11/0.415 KV DISTRIBUTION TRANSFORMER FOR COLLEGE. |
| 41 | GI Steel tubular pole SP-35 |
| 42 | 500 KVA, 11/0,4 KV Transformer (CU Wound) raised RCC Plint/Platform mounted. Note the DTs shall be of 4 star and above ratings as per IPDS Specifications. |
| 43 | GIChannel 100x50x6 mm for X arm, switch D.O. etc. (2.2 Mtrs length weighing 20.24 Kg each)) |
| 44 | M.S. Angle 50x50x6 mm for DT LT Bus Bar (2.2 mtr weighing 10 Kg each) |
| 45 | Lightning arrestor, Distribution Class (9KV, 5KA, 1Ph). (Lamco/Oblum or other superior brands). |
| 46 | 11 KV GO air break switch complete 3-ph(heavy duty) (Yamuna/RPG/RM Electricals make) |
| 47 | 11 KV D.O. fuse with operating rod(heavy duty) (Yamuna/RPG/RM Electricals make) |
| 48 | GI Wire 6 SWG (5 mm dia) weighing 19.2 Kg per 100 metre Coil - for Earthing |
| 49 | Earthing Materials for Transformer and LA |
| 50 | i) Copper Plate 2ft x2 ft, 3mm thick (weighing 11Kg each), for neutral and body - 2 nos |
| 51 | i) Copper Plate 1\"x1\", 3 mm thick (weighing 3Kg each) for LA |
| 52 | ii) Copper wire 5 SWG for Neutral (12 Mtrs ), Body (12 Mtrs) and LA (20 Mtrs), weighing 0.204Kg per mtr. |
| 53 | iii) Charcoal - (20kg/bag) |
| 54 | iv) salt - 50Kg |
| 55 | v) 2\" (25mm)GI Pipe 3 mtr (for water recharge/alternate electrode) |
| 56 | DTR Distribution Cubicle for 500 kVA DTRscomprising of following items and adequate cable ferrules/glands, i) Copper/Aluminium Bus Bar (4 nos), ii) MCCB 320 Amps(4 pole) for incomer conforming to L&T/Schneider make, iii) AMR , DLMS Complaint 3ph 4 wire trivector LTMeter, 5 Amp rated currentconforming to Secure/Genus/ L&T make, iv) 3 ph LTCT (4nos) 400/5 Aenclosed in metallic box with input and out put lugs terminals or butterfly type for fitting on LT bushing conforming to Secure or other superior make, v) 8 nos of 200 Amps Kit kat for 2 nos of outgoing feeders (Heay Duty) |
| 57 | ACSR WEASEL Conductor 6/2.59mm + 1/2.59 mm. |
| 58 | 11 KV polymer pin insulator complete with GI Pin (Yamuna/Denson/Compag/RPG make) |
| 59 | 11 kV Polymer Disc insulator 70 KN (Yamuna/Denson/Compag/RPG make) |
| 60 | H/W fittings for Disc insulator (E&S) 70 KN, Tension type |
| 61 | Tension clamp for ACSR Weasel |
| 62 | PG Clamp for Weasel |
| 63 | LT XLPE Single Core Aluminium ConductorPower Cable of KEI/Havells/Polycab make |
| 64 | i) 400 Sqmm (AL) for DTR LT Bushing to Bus Bar |
| 65 | ii) 300 Sqmm (AL) (for Bus to line 2 CKt) |
| 66 | iii). 185 Sqmm (AL) (for Neutral) |
| 67 | Copper Tubular Terminal ends/Lugs heavy duty (Dowells or other superior make) |
| 68 | i). 400 Sq. mm |
| 69 | ii) 300 Sqmm |
| 70 | iii). 185 Sq. mm |
| 71 | GI M. S. nuts and bolts with MS washer(Assorted) |
| 72 | Danger plate 11KV |
| 73 | Aluminium Tape |
| 74 | Pole double clamp of G.I flat 50x6 mm |
| 75 | Stay set 19 mm dia 1.6 mts. Length with stay rod, bow,plate |
| 76 | GI Stay Wire7/10 SWG weighing 43.4 Kg per 100 metres Coil |
| 77 | MS Rod Welded Mesh (15x2.44) for Fencing of Sub-station . |
| 78 | G. I Pipe 2\" for Fencing Post |
| 79 | CONSTRUCTION OF 1.2 KM NEW 11KV OUTGOING FEEDERSFOR POWER DISTRIBUTION OF MEDICAL CAMPUS AND CONNECTING 6 NOS OF NEW DTS. ( 5DP and 5 SP line specificationof 100M span length each) |
| 80 | GI Steel Tubular Pole SP-45 |
| 81 | GI MS Channel 100x50x6mm for top Cross Arm- 2.2 M Long weighing 20.24 kg each |
| 82 | GI MS Angle 50X50X6mm - 2.5 M Long weighing 11.25Kg eachfor Guard Brackets DP 5 Nos and for SP 5 nos) |
| 83 | GI MS Angle 50X50X6mm - 5 M Long weighing 22.5Kg each. for DP Bracing |
| 84 | 11 kV Polymer Disc insulator 70 KN (DP-36Nos + 3 Spare). Yamuna/Denson/RPG/Compag make |
| 85 | H/W fittings for Disc insulator (E&S) 70 KN, Tension type |
| 86 | 11 KV polymer pin insulator(SP- 15 Nos + 3 Spare). Yamuna/Denson/RPG/Compag make |
| 87 | ASCR\"Weasel\" conductor |
| 88 | Tension clamp for ACSR Weasel |
| 89 | 3 inch C.I earthing pipe each of 3.0 meters conforming to relevant ISS |
| 90 | G. I. wire , 8 SWG for guarding (5.71 Kg per Span) - for 5 spans |
| 91 | G. I. wire , 6 SWG for earthing |
| 92 | HT stay set with 11 KV guy insulator |
| 93 | PG clamp, for ACSR Weasel |
| 94 | 11kV Danger plate |
| 95 | GI nuts and bolts withGI washer (Assorted) inlcuding 12\" through bolts for DP cross arms |
| 96 | Barbed wire |
| 97 | G.I Stay wire , 7/10 SWG |
| 98 | i) 115 mm dia (Top). -Double (jam) Clamp for DP cross armchannel support and Stay. |
| 99 | ii) 140 mm dia (Mid) - Single Clamp for Bracing support |
| 100 | i) 115 mm dia (Top). -Double (jam) Clampfor Stay |
| 101 | ii) 115 mm dia (Top)- Single Clamp for Cross Arm channelSupport |
| 102 | Sundries |
| 103 | CONSTRUCTION OF 2KM NEW LT 3Ph 5 WIRE LT DISTIBUTION LINE ASSOCAITED WITH 6 NEW DTS FOR ELECTRIFICATION OF MEDICAL CAMPUS ( 20 SP line specificationof 50 M span length each) |
| 104 | GI Steel Tubular Pole SP 35 |
| 105 | GI MS Angle 40x40x5mm for LT cross arm - 1.5 M Long weighing 5.25 Kg each |
| 106 | Pole clamp of GI flat 50x6 mm size for SP 35 SPStructure |
| 107 | i) 90 mm dia (Top) - Single Clamp for Cross Arm support |
| 108 | i) 90 mm dia (Top). -Double (jam) Clamp for Shackle Strap and Stay. |
| 109 | LT Pin Insulator (Porcelain) with G.I Pin. Aditya Birla/Rashtriya or superior brand |
| 110 | Shackel Insulator (Porcelain) (75x90)mm Aditya Birla/Rashtriya or superior brand |
| 111 | GI Shackle Straps (D Clamp) with bolts |
| 112 | AAC Asther conductor for Phases and Neutral |
| 113 | AAC Gnat Conductor for Street Light |
| 114 | GI Nuts & Bolts assorted with washer |
| 115 | LT Stay Set (Galvanised) |
| 116 | LT Guy insulator (porcelain) |
| 117 | GI 7/12 SWG Stay wire for LT stay set |
| 118 | LED Street Light (60W) Fixtures with Brackets, supports & Accessories & PVC wires (2.5 Sqmm) |
| 119 | CONSTRUCTION OF 1.5 KM NEW LT 1Ph 2 WIRE LT LINE for Compound Lighting ( 20 SP line specificationof 50 M span length each) |
| 120 | GI Steel Tubular Pole SP 28 |
| 121 | GI MS Angle 40x40x5mm for LT cross arm - 1.5 M Long weighing 5.25 Kg each |
| 122 | Pole clamp of GI flat 50x6 mm size for SP 28 SPStructure |
| 123 | i) 89 mm dia (Top) - Single Clamp for Cross Arm support |
| 124 | i) 89 mm dia (Top). -Double (jam) clamp for Shackle Strap and Stay. |
| 125 | LT Pin Insulator (Porcelain) with G.I Pin. Aditya Birla/Rashtriya or superior brand |
| 126 | Shackel Insulator (Porcelain) (75x90)mm Aditya Birla/Rashtriya or superior brand |
| 127 | GI Shackle Straps (D Clamp) with bolts |
| 128 | AAC Gnat Conductor for Phase and Neutral of Street Light |
| 129 | GI Nuts & Bolts assorted with washer |
| 130 | LT Stay Set (Galvanised) |
| 131 | LT Guy insulator (porcelain) |
| 132 | GI 7/12 SWG Stay wire for LT stay set |
| 133 | LED Street Light (60W) Fixtures with Brackets, supports & Accessories & PVC wires (2.5 Sqmm) |