Special Repair To Central Ac Plant Of Operation Theatre At Mh Under Ge(South) Pathankot, pathankot-Punjab

Military Engineer Services-MES has published Special Repair To Central Ac Plant Of Operation Theatre At Mh Under Ge(South) Pathankot. Submission Date for this Tender is 24-12-2022. HVAC Tenders in pathankot Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

34997705
Corrigendum : Special Repair To Central Ac Plant Of Operation Theatre At Mh Under Ge(South) Pathankot
Open Tender
Indian
Punjab
pathankot
24-12-2022

Tender Details

Special Repair To Central Ac Plant Of Operation Theatre At Mh Under Ge ( South ) Pathankot

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 17-Dec-2022 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 24-12-2022

Key Value

Document Fees
INR 500 /-
EMD
INR 68200.0 /-
Tender Value
INR 34.10 Lakhs /-

BOQ Items

Name of Work : SPECIAL REPAIR TO CENTRAL AC PLANT OF OPERATION THEATRE AT MH UNDER GE(SOUTH) PATHANKOT
Sl. No. Item Description
1Supply, installation,testing andcommissioning in replacement of unsv double -skin type horizontal, floor-mounted,top/side discharge cabinet capable of delivering 12000 CFM air at 125 static prsessure and having thermal break profilecomplete with air ttight casing using gaskets and self adhesive tapes and 0.6mm thick pre-coated outer skin and 0.6 mm thick GI inner skin,25+/- 2 mm thick double skin panel with pressure injected CFC & HCFC gree PUF having "k" value of 0.02 W/C/m & density 40kg/m, AMCA certified energy efficient plug fabs with backward curved impellers for high static pressure mounted on aluminium extruded siderail base frame with EU4 pre filter and EU7 fine filter(shall be mounted on a common frame )suitable high efficiency(IE3 ) TEFC squirrel cage induction motor, PVC/nylon hinges and handles,view port and marine lamp limit switch vibration isolators/rubber pads(minimum 1 " thick )inspection windows, Flexible connection made with airtight ASTM E84(Class I)polyester fire retardent cloth riveted on periphery of cloth with extruded aluminium "L" angle flange as per fan size at discharge duct/pienum, complete all as specified and directed.
2Supply, installation,testing and commissioning in replacement of unsv double -skin type horizontal, floor-mounted,top/side discharge cabinet capable of delivering 9000 CFM air at 125 static prsessure and having thermal break profile complete with air tight casing using gaskets and self adhesive tapes and 0.6mm thick pre-coated outer skin and 0.6 mm thick GI inner skin,25+/- 2 mm thick double skin panel with pressure injected CFC & HCFC gree PUF having "k" value of 0.02 W/C/m & density 40kg/m, AMCA certified energy efficient plug fabs with backward curved impellers for high static pressure mounted on aluminium extruded siderail base frame with EU4 pre filter and EU7 fine filter(shall be mounted on a common frame )suitable high efficiency(IE3 ) TEFC squirrel cage induction motor, PVC/nylon hinges and handles,view port and marine lamp limit switch vibration isolators/rubber pads(minimum 1 " thick )inspection windows, Flexible connection made with airtight ASTM E84(Class I)polyester fire retardent cloth riveted on periphery of cloth with extruded aluminium "L" angle flange as per fan size at discharge duct/pienum, complete all as specified and directed.
3Supply, installation, testing and commissioning in replacement of unsv 6 RD chiller water cooling coils & 2 RD Heating coil 12000 cfm section with 0.15 mm thick alfins and copper tubes tested on 21 kg /cm with SS sandwiched drain tray etc , complete all as specified and directed.
4Supply, installation, testing and commissioning in replacement of unsv 8 RD chiller water cooling coils & 2 RD Heating coil 5000 cfm section with 0.15 mm thick all fins and copper tubes tested on 21 kg /cm with SS sandwiched drain tray .etc , complete all as specified and directed.
5Supply, installation, testing & commissioning in replacement of unsv 3 way mixing/diverting valves of size 65mm, complete all as specified and directed.
6Supply, installation, testing & commissioning in replacement of unsv 3 way mixing/diverting valves of size 32mm, complete all as specified and directed.
7Supply, installation, testing & commissioning in replacement of unsv Butterfly valve of PN 1.6of size 80 mm, complete all as specified and directed.
8Supply, installation, testing & commissioning in replacement of unsv Butterfly valve of PN 1.6of size 65 mm, complete all as specified and directed.
9Supply, installation, testing & commissioning in replacement of unsv Butterfly valve of PN 1.6 of size 32 mm, complete all as specified and directed.
10Supply, installation, testing & commissioning in replacement of unsv Balancing valve (to control flow of water) of PN 1.6 of size 80 mm, complete all as specified and directed.
11Supply, installation, testing & commissioning in replacement of unsv Balancing valve (to control flow of water) of PN 1.6 of size 65 mm, complete all as specified and directed.
12Supply, installation, testing & commissioning in replacement of unsv Balancing valve (to control flow of water) of PN 1.6 of size 32mm, complete all as specified and directed.
13Supply, installation, testing & commissioning in replacement of unsv HEPA filter having filteration level 99.9% downto 0.03 Microns, complete all as specified and directed.
14Supply& installation in replacement of unsv AL plenum made of 20 Gaugefor HEPA filters as per existing size and shape, complete all as directed and specifed.
15Supply & installation in replacement of unsv Acountistic insulation with itrile Rubber open cell foam with density 140-180 kg/m3 and Class I Fire performance and with antimicrobial protection and should pass Fungi resistance as per ASTM G 21 and Bacterial Resistance as per ASTM E 21 using manufacturer"s recommended rubber based adhesive in ablend of solvents Thickness of insulation 10mm, complete all as specified and directed.
16Supply and installation in replacement of unsv canvas connection for cabinet and ducting as per existing size and shape, complete all as specified and directed.
17Supply, installation, testing and commissioning in replacement of unsv moitorized combination fire and smoke dampers in supply air main duct. The fire damper shall be monitorzed and spring return type so as to close the damper automatically in the event of power failure and open the damper whenpower is restored. The Fire and smoke damper shall be complete with electronic temperature sensor and electrically operated actautor and interconnecting wiring between AHU & dampers. The fire damper shall be located in the supply air ducts, complete all as specified and directed.
18Supply, installation, testing & commissioning in replacement of unsv scroll compressors of model No. XAC3S-036MAR2 of capacity 36 TR of make Blue star, complete all as specified and directed.
19Supply, installation, testing and commissioning in replacement of unsv air cooled copper condenserof model No.XAC3S-036MAR2 of capacity 36 TR of make Blue star, complete all as specified and directed.
20Supply, installation, testing and commissioning in replacement of unsv condensor fan motors of size 7 HP, 415V, 3 Phase 2900 RPM suitable for model No.XAC3S-036MAR2 of capacity 36 TR of make Blue star, complete all as specified and directed by Engr-in-Charge.
21Supply, installation, testing and commissioning in replacement of unsv evaporator duly insulation along with controls and expansion valves formodel No.XAC3S-036MAR2 of capacity 36 TR of make Blue star, Size as per existing at site, complete all as specified and directed.
22Supply, installation, testing and commissioning in replacement of unsv control panelalong with PCB, Aux, multimeter, contractor, relay etc and display of model No.XAC3S-036MAR2 of capacity 36 TR of make Blue star, complete all as specified and directed.
23Supply, installation, testing and commissioning in replacement of unsv control such as LP,HP and Anti-freezer for model No.XAC3S-036MAR2 of capacity 36 TR of make Blue star, complete all as specified and directed.
24Supply, installation, testing and commissioning in replacement of unsv pressure testing including vacuum & refrigerant charging R- 407 as required on the site for model No.XAC3S-036MAR2 of capacity 36 TR of make Blue star, complete all as specified and directed.
25Supply, installation, testing and commissioning in replacement of unsv Monoblock type chilled water pumpswith bronze impeller mechanical sealwith 7 LPS at 20 M head included with MS channel frame coupled with motor of 7.5 HP 3 Phase, 415 V, 1400 RPM, complete all as specified and directed.
26Supply, installation, testing and commissioning in replacement of unsv pressure gauge complete suitable for model No.XAC3S-036MAR2 of capacity 36 TR of make Blue star, complete all as specified and directed.
27Supply, installation, testing and commissioning in replacement of unsv water flow switch of type and size available at site, complete all as specified and directed.
28Supply, installation, testing and commissioning in replacement of unsv Motor actuator for fire damper complete as per exising size, complete all as specified and directed.
29Supply, installation, testing and commissioning in replacement of unsv control panelfor fire damper along with wire and smoke sensor with pre fitted circuit etc. complete all as directed and specified
30Supply, installation, testing and commissioning in replacement of unsv Humidistat & cooling & heating thermostat.
31Supply, installation, testing and commissioning in replacement of unsv MS heavy grade chilled water piping 80mm dia with insulation 50mm thick EPS pipe section final finished with AL sheet cladding and sand cement plaster.
32Supply, installation, testing and commissioning in replacement of unsv 65 MM MS piping class c heavy grade piping dully insulated with 50mm thick EPS pipe section final finished with 26 gauge AL sheet cladding and sand cement plaster make of pipe.
33Supply, installation, testing and commissioning in replacement of unsv 32 MM MS piping class c heavy grade piping dully insulated with 50mm thick EPS pipe section final finished with 26 Gauge AL sheet cladding/sand cement plaster make of pipe.
34Supply and fabrication in replacement of unsv AL ducting as per the SMACNA (Sheet metal and air conditioning contractors national association) standards fabrication at the site of suitable size
35Supply & installation in replacement of unsv nitrile closed cell insulation of 9mm thick FR class "O"
36Supply, installation, testing and commissioningin replacement of unsv starter panel 7.5 HP With control wiring limit switch, volt meter, amp meter, indicators withi pre wiredcircuit, complete all as specified and directed.
37Supply, laying, jointing & testing 50 Sq mm 3.5 Core LT XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, complete all as specified and directed.
38Supply, laying, jointing & testing 6 Sq mm 3 Core LT XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, complete all as specified and directed.
39Material and labour earthing with steelearth plate electrode ofsize 60x60cmx6mm thick buried directly in ground to a depth not less than 2.25mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full length of earth plate, GI medium grade pipe 40 mm bore protection pipe upto test point, 20mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and , complete all as specified and directed.orindicatedincludingtesting on completion.NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth strip upto 7.5 m long for connecting totest point etc. all as required at site for complete earthing).(AHU - 02 Sets, Chiller-01 Set, Pump -01 Set)
40Supply, installation, testing and commissioning of Electric Air vent as per the eixting size availabe at site, complete all as specified and directed.
41Supply, intalling and commissioning of Water Electric heater of 22KW suitable for existing system , complete all as specified and directed.
42Notes :The Schedule of Credit amount shall be deducted from the total of this schedule(BoQ)to arrive at Contract Sum.