Tender For Addition, Alteration And Change Of Facade In Mahatma Gandhi Government Senior Secondary School At Androth, Lakshadweep, androth-Lakshadweep

Public Works Department-PWD has published Tender For Addition, Alteration And Change Of Facade In Mahatma Gandhi Government Senior Secondary School At Androth, Lakshadweep. Submission Date for this Tender is 13-12-2022. Building Work Tenders in androth Lakshadweep. Bidders can get complete Tender details and download the document.




Tender Notice

34985327
Tender For Addition, Alteration And Change Of Facade In Mahatma Gandhi Government Senior Secondary School At Androth, Lakshadweep
Open Tender
Indian
Lakshadweep
androth
13-12-2022

Tender Details

Addition, Alteration And Change Of Facade In Mahatma Gandhi Government Senior Secondary School At Androth, Lakshadweep Addition, Alteration And Change Of Facade In Mahatma Gandhi Government Senior Secondary School At Androth, Lakshadweep ( Re E-Tender )

Key Value

Document Fees
INR 3000 /-
EMD
INR 3612311.0 /-
Tender Value
INR 26.21 Crore /-

BOQ Items

Name of Work: Addition, Alteration and Change of Facade including Pavilion of Mahatma Gandhi Govt. Senior Secondary School Androth, Lakshadweep
Sl. No. Item Description
1STRUCTURAL
2Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as wellas 10 sqm on plan including getting out and disposal of excavated earth upto 50 m and lift upto 1.5 m, as directed by Engineer-in- Charge:All kinds of soil
3Clearing jungle including uprooting of rank vegetation, grass, brush wood, trees and saplings of girth up to 30 cm measured at a height of 1 m above ground level and removal of rubbish up to a distance of 50 m outside the periphery of the area cleared.
4Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. All kinds of soil
5Felling trees of the girth (measured at a height of 1 m above ground level), including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material. Beyond 30 cm girth upto and including 60 cm girth
6Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. All kinds of soil
7Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
8Excavating, supplying and filling of local earth (including royalty) by mechanical transport upto a lead of 5km also including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete
9Disposal of earth work by mechanical transport including loading, transporting, unloading to approved municipal dumping ground for lead upto 5 km for all lifts, complete as per directions of Engineer-in-charge.
10Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth.
11Providing,diluting and injecting chemical emulsion to 12mm dia holes in Masonry/earth fiiling and plugging with cement mortar 1:2 to match the line and level of sorrounding area for PRE-CONSTRUCTIONAL anti-termite treatmentwith Imidacloprid (30.50% SC) or approved equivalent. Plinth area in plan at GF shall only be measured (for all below specified steps) and paid. A guarantee bond of 10 years shall be furnished. A) Bottom surface and the sides of the excavation made for masonry foundations at the rate of 5 liters/sqm (wherever applicable) B) Top surface of the plinth filling of 5 liter/sqm of internal plinth area etc. complete. C) At the rate of 5 liter/ sqm to the internalvertical surface from original Ground level to top of the earth filled in the plinth. D) At the rate of 5 liter/ sqm to the externalvertical surfacebelow finished Ground level to the full depth of the filling complete. The work includes all costfor chemical, drilling 12 mm diameter holes and plugging with cement mortar 1 :2 (1 cement : 2 Coarse sand) to match the existing finish etc all complete as per the direction of Engineer-In-Charge
12Providing and laying damp-proof course 50 mm thick with cement concrete 1:2:4(1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size).
13Providing & applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7kg per square metre on damp proof course after cleaning the surface with brushes and finally with apiece of cloth lightly soaked in kerosene oil.
14Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size)
15Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with :Cement mortar 1:6 (1 cement : 6 coarse sand)
16Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate /retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works upto plinth level. Concrete of M30 grade with minimum cement content of 350 kg /cum.
17Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate /retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works above plinth level upto floor V level. Concrete of M30 grade with minimum cement content of 350 kg /cum.
18Reinforced cement concrete work in arches, archribs, domes, vaults, shells, folded plate and roofs having slope more than 15° up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources).
19Centering and shuttering including strutting, propping etc. and removal of form for all heights : Foundations, footings, bases of columns, etc. for mass concrete
20Centering and shuttering including strutting, propping etc. and removal of form for all heights : Lintels, beams, plinth beams, girders, bressumers and cantilevers
21Centering and shuttering including strutting, propping etc. and removal of form for all heights : Columns, Pillars, Piers, Abutments, Posts and Struts
22Centering and shuttering including strutting, propping etc. and removal of form for all heights :Stairs, (excluding landings) except spiral-staircases
23Centering and shuttering including strutting, propping etc. and removal of form for all heights : Weather shade, Chajjas, corbels etc., including edges
24Centering and shuttering including strutting, propping etc. and removal of form for all heights : Suspended floors, roofs, landings, balconies and access platform
25Centering and shuttering including strutting, propping etc. and removal of form for all heights : Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
26Centering and shuttering including strutting, propping etc. and removal of form for all heights : Edges of slabs and breaks in floors and walls. Under 20 cm wide
27Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
28Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. Thermo-Mechanically Treated bars of grade Fe-500D or more.
29Providing and laying cement concrete in retaining walls, return walls, walls (any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts, buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor etc., up to floor five level, excluding the cost of centering, shuttering and finishing: 1:5:10 (1 cement : 5 coarse sand (zone-III) : 10 graded stone aggregate 40 mm nominal size).
30Cutting holes of required size in brick masonry wall for fixing of exhaust fan including providing and fixing 300 mm dia PVC pipe conforming BIS-12818 and making good the same etc. complete as per direction of Engineer-in-charge.
31Providing and fixing of expansion joint system related with floor location as per drawings and directionof Engineer-In-Charge. The joints system will be of extruded aluminum base members, self aligning / selfcentering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that itprovides floor to floor /floor to wall expansion control system for various vertical localtion in loadapplication areas that accommodates multi directional seismic movement without stress to it"scomponents. System shall consist of metal profiles with a universal aluminum base member designed toaccommodate various project conditions and finish floor treatments. The cover plate shall be designed ofwidth and thickness required to satisfy projects movement and loading requirements and secured tobase members by utilizing manufacturer’s pre-engineered self- centering arrangement that freely rotates /moves in all directions. The Self - centering arrangement shall exhibit circular sphere ends that lock andslide inside the corresponding aluminum extrusion cavity to allow freedom of movement and flexure inall directions including vertical displacement. Provision of Moisture Barrier Membrane in the JointSystem to have watertight joint is mandatory requirement all as per the manufactures design and asapproved by Engineer -in-Charge. (Material shall confirm to ASTM 6063). Floor Joint of 100 mm gap
32Providing and fixing of expansion joint system related with wall joint (internal/external) location as perdrawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminum base members,self aligning / centering arrangement and support plates as per ASTM B221- 02. The material shall besuch that it provides an Expansion Joints System suitable for vertical wall to wall/ wall to cornerapplication, both new and existing construction in office Buildings & complexes with no slipping downtendency amongst the components of the Joint System. The Joint System shall utilize light weightaluminum profiles exhibiting minimal exposed aluminum surfaces mechanically snap locking themulticellular to facilitate movement. (Material shall confirm to ASTM 6063) Wall Joint of 100 mm gap
33Providing and fixing of expansion joint system of approved make and manufactures for various rooflocations as per approved drawings and direction of Engineer-In-Charge. The joints shall be of extrudedaluminum base members with, self aligning and self centering arragement support plates asper ASTMB221-02. The system shall be such that it provides watertight roof to roof/roof to corner joint coverexpansion control system that is capable of accommodating multidirectional seismic movement withoutstress to its components. System shall consist of metal profile that incorporates a universal aluminumbase member designed to accommodate various project conditions and roof treatments. The cover plateshall be designed of width and thickness required to satisfy movement and loading requirements andsecured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement thatfreely rotates / moves in all directions. The Self centering arrangement shall exhibit circular sphere endsthat lock and slide inside the corresponding aluminum extrusion cavity to allow freedom of movementand flexure in all directions including vertical displacement. The Joint System shall resists damage ordeterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foottraffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to havewater tight joint is mandatory requirement. (Material shall confirm to ASTM 6063 Roof Joint of 100 mm gap
34Extra rates for quantities of earth works, executed: In or under water and/or liquid mud, including pumping out water as required .The extra percentage rate is applicable in respect of each item but limited to quantities of work executed in these difficult conditions. The unit, namely, metre depth, to be considered for payment, shall be the depth measured from the sub soil water level up to the centre of gravity of the qty executed in difficult conditions. The depth shall be reckoned correct to 0.10 m, 0.05 m or more shall be taken as 0.10 m and less than 0.05 m ignored
35Extra for laying concrete in or under water and/or liquid mud including cost of pumping or bailing out water and removing slush etc. completenThe quantity will be calculated by multiplying the depth measured from the sub-soil water level up to centre of gravity of concrete under sub-soil water level with quantity of concrete in cum executed under sub-soil water. The depth of centre of gravity shall be reckoned correct to 0.1m. 0.05m or more shall be taken as 0.1m and less than 0.05m ignored
36Extra for laying reinforced cement concrete in or under water and/ or liquid mud, including cost of pumping or bailing out water and removing slush etc., complete. The quantity will be calculated by multiplying the depth measured from the subsoil water level up to the centre of gravity of the R.C.C. under subsoil water with the quantity of R.C.C. in cubic metre executed under subsoil water. The depth of centre of gravity shall be reckoned correct to 0.1 m. 0.05 m or more shall be taken as 0.1 m and less than 0.05 m ignored. No extra payment shall be made for placing reinforcement or centering & shuttering under sub - soil water conditions.
37ARCHITECTURAL
38Providing and laying autoclaved aerated cement blocks masonry with 150mm/ 230mm/300 mm thick AAC blocks in super structure above plinth level up to floor V level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately).
39Providing and laying autoclaved aerated cement blocks masonry with 100 mm thick AAC blocks in super structure above plinth level up to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rate includes providing and placing in position 2 Nos 6 mm dia M.S. bars at every third course of masonry work.
40Providing and laying factory made well cured precast concrete solid blocks of 200 mm thickness from approved manufacturer in foundation and plinth in cement mortar 1:6 (1 cement : 6 coarse sand).The cost includes all neccessary scaffolding,arrangements for curing etcThe block samples must be approved for ensuring dimensions and quality prior to procurement.
41Providing and fixing stainless steel (Grade 316) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)
4212 mm cement plaster finished with a floating coat of neat cement of mix : 1:4 (1 cement: 4 fine sand)
4315 mm cement plaster on the rough side of single or half brick wall of mix : : 1:4 (1 cement: 4 fine sand)
446 mm cement plaster of mix : 1:3 (1 cement : 3 fine sand)
45Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.
46Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections.
47Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick
48Kota stoneflooring over 20 mm (average) thick base laid over and filling thejoints with artificial grass, including supply and fixing of grass andrubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick.
49Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete
50Providing edge moulding to 18-25 mm thick marble/granite/kota stone including machine polishing to edge to give high gloss finish etc. complete as per designapproved by Engineer-in-Charge.
51Extra for marble stone flooring in treads of steps and risers using single length up to 2.00 metre.
52Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
53Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete. Size of Tile 600x600 mm
54Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily.Glazed Vitrified tiles Matt/Antiskid finish of size.Size of Tile 600 x 600 mm.
55Providing and laying Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement: 3 coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joint with white cement & matching pigments etc. complete. Size of Tile 600x600 mm
56Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade. Area of slab over 0.50 sqm
57Providing and laying tactile tile (for vision impaired persons as per standards) of size 300x300x9.8mm having with water absorption less than 0.5% and conforming to IS:15622 of approved make in all colours and shades in for outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge.
58Extra for providing opening of required size & shape for wash basin/ kitchen sink in kitchen platform, vanity counter and similar location in marble/ Granite/ stone work, including necessary holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
59Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite work
6052 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer"s specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete.
61Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
62Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound ) content.With water thinnable cement primer on wall surface having VOC content less than 50 grams/litre
63Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. Two coats
64Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives. New work (Two or more coats applied @ 1.43 litre/ 10 sqm. Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm.
65Finishing walls with textured exterior paint of required shade : New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm
66Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to preparethe surface even and smooth complete.
67Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work
68Providing and laying M20 grade screed concrete conforming to IS 456 with coarse sand and graded hard stone aggregate 12.5mm/6 mm nominal size on the roof at any level in required slope and thickness as per the approved drawing and instruction of Engineer-In-Charge.The cost includes all material and labour for screeding,admitures/water prrofing comopunds, chamfering the conrners,making slope as per drawing towards down water pipes,finishing the top surface smooth,curing etc all complete
69Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : (a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours. (b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.
70Providing and applying fibre reinforced elastomeric liquid water proofing membrane with resilient acrylic polymers having Sun Reflectivity Index (SRI) of 105 on top of concrete roof in three coats @10.76 litre/ 10 sqm. One coat of self-priming of elastomeric waterproofing liquid (dilution with water in the ratio of 3:1) and two coats of undiluted elastomeric waterproofing liquid (dry film thickness of complete application/system not less than 500 microns). The operation shall be carried out after scrapping and properly cleaning the surface to remove loose particles with wire brushes, complete in all respect as per the direction of Engineer-in-Charge.
71Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineerin-charge. The product performance shall carry guarantee for 10 years against any leakage. For vertical surface two coats @0.70 kg per sqm
72Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservior, sewage & water treatment plant, tunnels / subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI-212-3R-2010 i.e by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the engineerin-charge. The product performance shall carry guarantee for 10 years against any leakage. For horizontal surface one coat @1.10 kg per sqm.
73Providing and Placing in position suitable PVC water stops conforming to IS:12200 for construction/ expansion joints between two RCC members and fixed to the reinforcement with binding wire before pouring concrete etc. complete : Serrated with central bulb (225 mm wide, 8-11 mm thick)
74Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :For fixed portion.Powder coated aluminium (minimum thickness of powder coating 50 micron)
75Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5 mm thickness (weight not less than 20 kg/sqm)
76Providing and fixing 6 mm thick toughened glass panel of approved brand and manufacture, including making necessary arrangements for fixing requiredfittings, all complete as per direction of Engineer-in-charge
77Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid door/window/Ceosetory windows & other Frames/Chowkhat comprising of virgin PVC polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) fabricated with miter joints after applying PVC solvent cement and screwed with full body threaded star headed SS screws having minimum frame density of 750 kg/cum, screw withdrawal strength of 2200 N (Face) & 1100 N (Edge), minimum compressive strength of 58 N/mm2, modulus of elasticity 900 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixed in position with M.S hold fast/lugs/SS dash fasteners of required dia and length complete as per direction of Engineer-In- Charge. (M.S hold fast/lugs or SS dash fasteners shall be paid for separately).Note: For WPC solid door/window frames, minus 5mm tolerance in dimensions i.e depth and width of profile shall be acceptable. Variation in profile dimensions on plus side shall be acceptable but no extra payment on this account shall be made.Frame size 65 x 100 mm
78Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid plain flush door shutter of required size comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) & 900 N (Edge), minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In- Charge. (Note: stainless steel butt hinges and necessary S.S screws shall be paid separately). 35 mm thick
79Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured):Rectangular or square
80Extra for providing frosted glass panes 4 mm thick instead of ordinary float glass panes 4 mm thick in doors, windows and clerestory window shutters. (Area of opening for glass panes excluding portion inside rebate shall be measured).
81Fly proof stainless steel grade 304 wire gauge with 0.5 mm dia. wire and 1.4mm wide aperture with matching wood beading
82Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c, including applying a coat of approved fire resistantprimer /powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per NBC 2016, IS 16231 (Part 3):2016 and asper direction of Engineer-in-charge with glass of required thickness having 120 minutes of fire resistance both integrity & radiation control (EW120) and minimum 20 minutes of insulation (EI20). The manufacturer have to give test report/certification of fire glass and the glass should have the stamp showing the value of E, EW & EI. The glass shall be tested in approved NABL accredited lab or by any other accreditation body which operates in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and calibration scopes shall be eligible. The maximum glazing size shall not be more than 1100x2200 mm (w x h) or 2.42 sqm.
83Providing and fixing fire resistant door frame of section 50 x 60 mm on horizontal side & 35 x 60 mm on vertical sides having built in rebate made out of 1.6 mm thick GI sheet ( Zinc coating not less than 120gm/m²) suitable for mounting 120 min Fire Rated Glazed Door Shutters. The frame shall be filled with Mineral wool Insulation having density min 96Kg/m³ . The frame will have a provision of G.I. Anchor fastners 14 nos ( 5 each on vertical style & 4 on horizontal style of size M10 x 80 ) suitable for fixing in the opening along with Factory made Template for SS Ball Bearing Hinges of Size 100x89x3mm for fixing of fire rated glazed shutter . The frame shall be finished with a approved fire resistant primer or Powder coating of not less than 30 micron in desired shade as per the directions of Engineer - in- charge . (Cost of SS ball bearing hinges is excluded).
84Providing and fixing panic bar / latch (Double point) fitted with a single body, Trim Latch & Lock on back side of the Panic Latch of reputed brand and manufacture to be approved by the Engineer- in- charge, all complete.
85Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with G.I. beading made out of 1.6 mm thick G.I. sheet (zinc coating not less than 120 gm/m²) of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c, including applying a coat of approved fire resistant primer/powder coating of not less than 30 micron on G.I. beading, & special ceramic tape of 5 x 20 mm size etc complete in all respect as per NBC 2016, IS 16231 (Part 3):2016 and asper direction of Engineer-in-charge with glass of required thickness having 120 minutes of fire resistance both integrity & radiation control (EW120) and minimum 20 minutes of insulation (EI20). The manufacturer have to give test report/certification of fire glass and the glass should have the stamp showing the value of E, EW & EI. The glass shall be tested in approved NABL accredited lab or by any other accreditation body which operates in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and calibration scopes shall be eligible. The maximum glazing size shall not be more than 1100x2200 mm (w x h) or 2.42 sqm
86Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISi, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width from 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
87Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.
88Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 300x10 mm
89Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete : 200x10 mm
90Providing and fixing bright finished brass 100 mm mortice latch and lock, ISI marked, with six levers and a pair of anodised (anodic coating not less than grade AC 10 as per IS : 1868) aluminium lever handles of approved quality with necessary screws etc. complete.
91Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embedding in cement concrete block 30x10x15cm 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size).
92Providing and fixing IS : 12817 marked stainless steel butt hinges with stainless steel screws etc. complete :100X58X1.90 mm
93Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.
94Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.
95Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer"s specifications including appropriate priming coat, preparation of surface, etc. complete. On steel work
96Providing & fixing Poly carbonate multi wall plain sheet 8 mm thick as approved by the Engineer in charge and should be supplied in a single length of 12 M or as decide by the Engineer in charge. The sheets shall be fixed using self drilling/ self tapping screw of size ( 5.5x55mm) with EPDM seal complete upto any pitch in horizontal /vertical / curved surface, but excluding the cost of purlins, rafters, trusses, and including cutting to size and shapes where ever required.
97Providing orange colour safety foot rest of minimum 6 mm thick plastic encapsulated as per IS : 10910, on 12 mm dia steel bar conforming to IS: 1786, having minimum cross section as 23 mmx25 mm and over all minimum length 263 mm and width as 165 mm with minimum 112 mm space between protruded legs having 2 mm tread on top surface by ribbing or chequering besides necessary and adequate anchoring projections on tail length on 138 mm as per standard drawing and suitable to with stand the bend test and chemical resistance test as per specifications and having manufacture"s permanent identification mark to be visible even after fixing, including fixing in manholes with 30x20x15 cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) complete as per design.
98Providing and Fixing ofBuilding signages 5-6 Sqm as per following specifications - Sign to be made shall be made of 3 mm aluminium / Acrylic Box Letters (100mm thick letters). Sign Face shall be in 3mm 0/40 Translucent Acrylic with Male / 10mm Water Proof Sun board Female Joint Adequate LED of Samsung Make shall be fitted with the required wiring & Waterproof Transformer to have the uniform Light. A provision for Weather Proof Box shall be made to keep the Transformers. The signages to be fixed on the structural ACP + MSframework with required sizes as per the design. The item includes design of supporting arrangement, fabrication, installation and commissioning the signages with structural framing including channels, angles, gusset plates and anchoring the frame by anchor fasteners to the Building. The structural framing should be painted with primer and enamel paints
99Room/Function identification holders signs made of imported clear acrylic The room location will be made 0.8mm raised computer cut with 16mm high. Signage will be painted with DuPont paint as per approved shade card.
100Room/Function identification holders signs made of3mm thk foam board with double sided tape.The room location will be made 0.8mm raised computer cut with 16mm high. Signage will be painted with DuPont paint as per approved shade card.
101Providing and fixing Toilet Cubicle (L-shape) of 1500mm x 1375mm x2100mm and door size of 800x 2090mm with clearence from floor 10 mm,made up of heat, water, chemical, scratch and anti bacterial resistant 12mm thick solid compact laminate panels test by national test house.Compact laminate including for doors, pilasters and intermediate panles should be confirming to IS 2046 and as per fire retardant BS-476/97 standard .Finish,shade and texture of all panles must be approved by the Architect prior to procurement. Providing and fixing necessary Stainless steel hardwares ( 316 grade) for cubicle including doors as per the manufacturer specifucation and architects"s instruction shall be inculded in the cost. All pilasters are supported by stainless steel bottom cladding with SS Shoe Box Plate and rectanglar SS top rail with a clearence of 50 mm in between the rail and door. The base of SS shoe box shall be anchored to the floor.
102Providing and fixing Toilet Cubicle (I-shape) of1375mm x2100mm and door size of 800x 2090mm with clearence from floor 10 mm,made up of heat, water, chemical, scratch and anti bacterial resistant 12mm thick solid compact laminate panels test by national test house.Compact laminate including for doors, pilasters and intermediate panles should be confirming to IS 2046 and as per fire retardant BS-476/97 standard .Finish,shade and texture of all panles must be approved by the Architect prior to procurement. Providing and fixing necessary Stainless steel hardwares ( 316 grade) for cubicle including doors as per the manufacturer specifucation and architects"s instruction shall be inculded in the cost. All pilasters are supported by stainless steel bottom cladding with SS Shoe Box Plate and rectanglar SS top rail with a clearence of 50 mm in between the rail and door. The base of SS shoe box shall be anchored to the floor.
103Providing and fixing of urinal partition of approved make in approximate size 1200mm x 500 mm made of 12mm compact laminates with anti- bacterial and anti- fungal protection with neccessary L-clamp of SS 316 grade. The design/shape and colour of divider must be approved by the Architect / Engineer in- charge.
104Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x0.90 mm M.S. laths with 0.90 mm thick top cover
105Extra for providing grilled rolling shutters manufactured out of 8 mm dia M.S. bar instead of laths as per design approved by Engineer-in- charge, (area of grill to be measured).
106Providing and fixing ball bearing for rolling shutters.
107Providing and fixing Gysum false ceiling (12.5 mm) at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound , jointing tapes , finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer"s specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with : 12.5 mm thick tapered edge gypsum plain board conforming to IS: 2095- (Part I) : 2011 (Board with BIS Certification marks)
108Providing & fixing 8 mm thick Calcium Silicate false ceilingat all height including providing & fixing of framework made of special section, power pressed from M.S. sheets and galvanised with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleat of size 25mm wide x 1.6mm thick with flanges of 27mm and 37mm, at 1200mm c/c, one flange fixed to the ceiling with dash fastener 12.5mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25 x10 x0.50mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I chanels 45 x15 x 0.90mm running at the spacing of 1200 mm c/c, to which the ceiling section 0.5mm thick bottom wedge of 80mm with tapered flanges of 26 mm each having lips of 10.5mm, at 450mm c/c, shall be fixed in a direction perpendicular to G.I intermediate channel with connecting clip made out of 2.64mm dia x 230mm long G.I wire at every junction, including fixing perimeter channels 0.50mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall/ partitions with the help of Rawl plugs at 450mm centre, with 25mm long dry wall screws @ 230mm interval, including fixing of Calcium Silicate Board to ceiling section and perimeter channels with the help of dry wall screws of size 3.5 x25mm at 230mm c/c, including jointing & finishing to a flush finish of tapered and square edges of the board with recommended jointing compounds, jointing tapes,finishing with jointing compounds in three layers covering up to 150mm on both sides of joints and two coats of primer suitable for boards, all as per manufacture"s specification and also including the cost of making opening for light fittings, grills, diffusers, cut outs made with frame of perimeter channels suitably fixed, all complete as per drawings, specificaton and direction of the Engineer in charge but excluding the cost of painting with: 8 mm thick Calcium Silicate Board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process.
109Supplying and installation of Black out roller blinds as per the detailed Technical specification and deatiled drawing. Including all fixing charges and necessary fittings. Base rate of fabric is Rs. 700/-
110Providing & supplying of Mirror fixing in toilet, above Toilet wash counter to provide 6mm edge polished mirrorfixed with mirror stud.
111Procuring healthy grass free from weeds and foreign materials and laying on the soil medium as turfing,the rate include for grass cost, transport to site, cost and application of manure, planting, labour, supervision and maintenance for 2 months after planting Pearl Grass
112Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Royal palm
113Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Foxtail palm
114Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Bismarkia palm
115Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Frangipani Tree
116Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Spider Plant
117Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Fishtail Palm
118Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Raphis Palm
119Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Ficus Reginold
120Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Peace Lilly
121Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Calatheas
122Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Nerium Oleander
123Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Tabernaemontana divaricata ( Crepe Jasmine)
124Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Ixora Coccinea (west indian jasmine)
125Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Delonix regia
126Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Portulaca Grandiflora
127Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Cassia Fistula
128Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Crinum Asiaticum
129Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Alamanda Schotti
130Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Bauhinia Variegata
131Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Bambusa Valgarus
132Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Syzygium Samarangenes
133Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Psidium Guajava
134Procuring and planting specified nursery grown trees, shrubs and other plants .Rates include plant cost,transport, cost of manure, planting, labour,supervision and maintenance for 2 months after planting. Azadirachta Indica ( Neem)
135Supplying of garden top soil with the mixture of red earth, compost, neem cake, bone meal and dried cow manure in proportion specified or directed,
136Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without groovesthickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge).
137Providing and laying factory made 50 mm thickBangalore stone of 600 mm x 600 mm of required strength, laid in required colour & pattern over 50mm thick compacted bed of 6mm aggregates, compacting and proper embedding/laying of blocks into the aggregate layer, filling the joints with cement mortar mixed with pigment to match the shade and , finishing and sweeping extra mortar,washing etc complete all as per direction of Engineer-inCharge.
138Providing and laying factory made 75 mm thickCobble stoneof 100 mm x 100 mm of required strength, laid in required colour & pattern over 50mm thick compacted bed of 6mm aggregates, compacting and proper embedding/laying of blocks into the aggregate layer, filling the joints with cement mortar mixed with pigment to match the shade and , finishing and sweeping extra mortar,washing etc complete all as per direction of Engineer-inCharge.
139Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-inCharge.80 mm thick C.C. paver block of M-30 grade with approved color design and pattern.
140Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge. With material conforming to Grade-II (size range 53 mm to 0.075 mm ) having CBR Value-25
141Supply and installation of 14mm (minimum) thickand 16mm (minimum) at high stress areas EPDM and PUR coated Sandwich Type Track OR Full PU system Track, colored, impermeable, full pour, spike and ultraviolet resistant self-leveling polyurethane Athletic Running Track system both fully certified and confirming the requirement of IAAF (International Association of Athletic Federation) to a total thickness of 14mm including game line marking all complete as per “IAAF” standard and specification. The cost includes all material and manpower for priming for SBR layer,installation of SBR layer,PU layer,EPDM and PU top coat,line marking,neccessary rubbing,cleaning etc all complete as per specifacations and drawings approved by the Architect.All works must be executed by authorised agency/vendor approved by the Engineer-In-Charge
142Extra for compaction of earth work in embankment under optimum moisture conditions to give at least 95% of the maximum dry density (proctor density)
143Cement concrete pavement with 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including finishing complete
144Providing and fixing pre-moulded joint filler in expansion joints of RCC roads / CC pavements after making the joints dust free with high pressure air jet cleaners, all complete as per direction of the Engineer-in-Charge. (Pre-moulded joint fillers shall be made of bitumen hot sealing compound impregnated fibre board having impregnation more than 35%, conforming to IS:1838 for fibre board and IS: 1834 for hot sealing bitumen compound grade A.)
145Providing and placing in position 100 mm thick factory made machine batched & machine mixed Precast RCC Rectangular Covers on drains of footpath of various sizes, of M-25 grade cement concrete for RCC work, including cost of centering, shuttering, reinforcement of 8 mm dia TMT bars of Fe 500 grade @ maximum 100mm c/c on both ways , neat cement punning on finished surface, properly encased on all edges with 1.6 mm thick , 100 mm wide MS sheet duly painted over priming coat , reinforcement to be welded at edges with MS sheet and providing 2 Nos. 12 mm dia bar for hooks etc i/c cost of cartage, all leads & lift, handling at site etc. all complete as per direction of Engineer-in-charge
146Constructing brick masonry chamber with inside dimensions 455x610 mm and 45 cm deep for single pipe line with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 for underground C.I. inspection chamber and bends with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg), R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 fine sand : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand), finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design.
147Construction of the layered gravel/stone base not less than 100 mm thick using varied size of stone aggredate sizes 40mm, 20mm,and 6mm finishing with proper compaction using roller for each layer seperately. Each layer shall be finished to the required compaction and slope as per the approved drawing without damaging the drain pipes as per the instruction of Engineer-In-Charge
148Supply and installation of 50mm quality proturf imported from FIFA quality manufactures with minimum 12 years warranty with proper infill (quarts sand as 2.5kg/sqft and crumbed rubber granules as 0.8kg/sqft) and standards as per FIFA.18000Dtex Density: 20172t/sqm, Gauge: 5/8 inch, Stitches: 280s/m. All filaments must have specially designed S curve structure. The cost includes all material and labour for supply,applying anti termite and weedicide, laying, infilling, polypropylene fibers Geotextile separation barrier of 200 GSM as per the standard procedure, line marking of ground material and two numbers of FIFA standard goal posts etc all complete as per the direction of Engineer-In-Charge.All works must be executed by authorised agency/vendor approved by the Engineer-In-Charge
149Constructing Volley ball court in international standards including all material and labour for levelling of ground, applying antitermite and weedicide, laying and compacting aggregate layer with 40mm size aggregate,100mm thick VDF concreting with M20 Ready Mix- M20 and plastering, crack removing Fabric net laying, laying synthetic 8-layer surface incluidng all game marking as per international rules,providing and fixing posts and nets of international standard with ITF Approved material of KDF, SMI, PACE or approved equivalent (One layer Primer,two layers of resurfacer, three layers of rubber cushion,two layers of color and marking in top coat). All the works has to be carried out by certified sports area manufactiures as per the approved design and direction of Engineer-In-Charge
150Constructing Badminton court in international standards including all material and labour for levelling of ground, applying antitermite and weedicide, laying and compacting aggregate layer with 40mm size aggregate,100mm thick VDF concreting with M20 Ready Mix- M20 and plastering, crack removing Fabric net laying, laying synthetic 8-layer surface incluidng all game marking as per international rules,providing and fixing posts and nets of international standard with ITF Approved material of KDF, SMI, PACE or approved equivalent (One layer Primer,two layers of resurfacer, three layers of rubber cushion,two layers of color and marking in top coat). All the works has to be carried out by certified sports area manufactiures as per the approved design and direction of Engineer-In-Charge.All works must be executed by authorised agency/vendor approved by the Engineer-In-Charge
151FURNITURE
152Providing and fixing Classroom Table with Bench of size 1200 x 970 x 750 mm for 2 persons consist of25 mm thick pre laminated particle board of approved make with2mm PVC Edge band on desk , bench and back.The end frames forunderstructure are made of 25 mm square x 1.6 mmthick ERW(Electrical Resistant Welding) tube and 5 no:s cross beams connecting end frame are made of 25 mm square x 1.6 mm thick ERW tube. For the foot rest 25 mm square x 1.6mm thick ERW tube will be at 180 mm high from floor level on front.Under Shelf is made of 0.8mm thick CRCA mounted below desk. All made of Knockdown Construction with all metal items are powder coated with 60+-10 microns. Sample furniture must be appoved by the Architect/Engineer-In-Charge prior to procurement.
153Providing and fixing chair with writing pad and upholstered with fabric cushion seat and back with arm rest and black powdercoated legs.Sample furniture must be appoved by the Architect/Engineer-In-Charge prior to procurement.
154Providing and fixing of Computertable of 1000mm x 700 mm x 750 mmhaving 18mm thick MDF Laminated Board table top of 1000mm x 700mm +18mm with Floor Mounted under Bench Storage Unit having CPU Box Front Open Type of320mm x 570mm x 720mm and Leg space/cross brace/foot rest/key board drawer/ cable manager/back panleand. and 450mm X 100 mm x 100 mmElectric TRunking Box having 6/16 Amp switch Socket and RJ45 Cat 6Data POint of approved make. Completely made of High zinc coated Galvanized Steel 1.0 mm thicknessprime export quality material with test certificate from galvanized steel manufacturer as per IS 277 standard. The shutter & drawer front should be of sandwich construction. Foam sheet filled in shutter gaps must required. The sound deadning Buffer to be used to minimize banging noise while closing the shutter.The shuttersare mounted to the modules by hinges which are openable to 90 degree & self closing on return. Lockable roller bearing to be usedso that the drawerwill not fall. The telescopic drawer slides which should be very sturdy &able to take load upto 30kg to 40Kg. Handle should be Aluminium Concealed Handle.All modulesto have lock and key arragement. Modules Completely finished with epoxy powdercoating. with minimum coatoing layer of 70-80 micron.Sample furniture must be appoved by the Architect/Engineer-In-Charge prior to procurement.
155Providing lab chairs withSW with PVC ringhandle, Gas Lift, Fiber stand with royal castor attached, 32 Density Foam for cushioningwithcompany press moulded ply, high quality craps cloth.Sample furniture must be appoved by the Architect/Engineer-In-Charge prior to procurement.
156Providing and fixing Centre Tableof size 1890 x 900 x 750 mm25 mm thick pre laminated particle board of approved make with Mahagony finish on top. All made of Knockdown Construction with all metal items are powder coated with 60+-10 microns. Sample furniture must be appoved by the Architect/Engineer-In-Charge prior to procurement.
157Providing and fixing High backadmin chair ofFP Invention with Multilock Mechanism ,Gaslift & Two Way AdjustableArms (Height & Swivel) with Chrome Base- Leatherette Seat & Back .Sample furniture must be appoved by the Architect/Engineer-In-Charge prior to procurement.
158Providing and fixing visitors chair with Chromeplated Sledge Base and fixed arm. The seat and back are made up ofLeatherette.Sample furniture must be appoved by the Architect/Engineer-In-Charge prior to procurement.
159Providing and fixing Storage unit of size 750x400x750 mm. Completely made of 25 mm thick pre laminated particle board of approved make. The shutters which are openable to 90 degree & self closing on return.Modules Completely finished with epoxy powdercoating. with minimum coatinglayer 60 micron.Sample furniture must be appoved by the Architect/Engineer-In-Charge prior to procurement.
160Providing and fixingfaculty Tableof size 1500 x 900 x 750 mm25 mm thick pre laminated particle board of approved make with Mahagony finish on top. All made of Knockdown Construction with all metal items are powder coated with 60+-10 microns. Sample furniture must be appoved by the Architect/Engineer-In-Charge prior to procurement.
161Providing and fixingfaculty chair of FP Invention with Multilock Mechanism ,Gaslift & Two Way AdjustableArms (Height & Swivel) with Chrome Base- Leatherette Seat & Back.Sample furniture must be appoved by the Architect/Engineer-In-Charge prior to procurement.
162Providing and fixing book shelves of size 1095 x370 x1950 mm with Upright - MS 40 x 40 x 1.6 Tube,Side Profile - MS Powder coated metal profile of 1.6mm with Acrylic pouch and band made of MS Powder coated metal 1.6mm. Shelves shall be made of MS powder coated metal 1.2mm supported with brackets,back panels made of MS Powder coated metal 0.8mm top panel , side panel & bottom panel made of 18mm thk plate.Sample furniture must be appoved by the Architect/Engineer-In-Charge prior to procurement.
163Providing and fixing of L shaped sitting tabel of 2700mm x 1200 mm x 750mm consists of 18mm -20 mm thick Jet BlackGranite Top with Edge moulding at the front and grove at the bottom to avoid by chemical spillage and is supported by rubber strip 6mm x 40 mm sheet of 2700 mm x 120mm +18mm with Table Top support frame of 2650 mm x 1150mm x 720mm andLeg space/Cross Brace /foot rest/key board drawer / Cable Manager / Back pane.Table top support frame of 2650mm x 1150mm x 720mm andMS Square tube frame with Epoxy Poder coating.Completely made of High zinc coated Galvanized Steel 1.0 mm thicknessprime export quality material with test certificate from galvanized steel manufacturer as per IS 277 standard. The shutter & drawer front should be of sandwich construction. Foam sheet filled in shutter gaps must required. The sound deadning Buffer to be used to minimize banging noise while closing the shutter.The shuttersare mounted to the modules by hinges which are openable to 90 degree & self closing on return. Lockable roller bearing to be usedso that the drawerwill not fall. The telescopic drawer slides which should be very sturdy &able to take load upto 30kg to 40Kg. All modulesto have lock and key arragement. Modules Completely finished with epoxy powdercoating. with minimum coating of 70-80 micron
164Providing and fixing reading chair,The seat and back are made of injection moulded high impact strenght polypropylene polymer compound with indoor grade UV Resistance.The tubular weled frame is made from Dia2.22 +/- 0.03cmx 0.12+/- 0.0128 cm and 3.5+/- 0.03 cm x 0.12+/-0.0128 cm stainless Steel 202 grade tube.The tube of green guard by ul certified chair shall be buffed polished to give shinyfinish. The Shoes are made of high impact strenght polypropylene polymer compond with indoor grad UV Resistance andpressed fitted with tubularfram.
165Providing and fixing Steel stools of SS 202 Grade and 16 Guage SS Pipe, Seating dia 12", Height: 20" and maximum 24"withmanual adjustable locking system .
166Providing and fixing Cupboard of 1000mmX450mmX1800mm with 2 horizontal compartment contain 2 adjustable shelfs in ecah compartment in which 1 is fixed and isCompletely made of 20 G High zinc coated Galvanized Steel 1.0 mm thicknessprime export quality material with test certificate from galvanized steel manufacturer as per IS 277 standard. The shutter & drawer front should be of sandwich construction. Foam sheet filled in shutter gaps must be required. The sound deadning Buffer to be used to minimize banging noise while closing the shutter.The shuttersare mounted to the modules by hinges which are openable to 90 degree & self closing on return. Lockable roller bearing to be provided for drawers. The telescopic drawer slides which should be very sturdy &able to take load upto 30kg to 40Kg. All modules should have lock and key arragement. Modules shall be completely finished with epoxy powdercoating with minimum coatinglayer 70 to 80 micron. Clear Glass Door shall be of 4 mm thick with lock and handle.
167Providing and fixing of tabel of 1225mm+3935mm x 610 mm x 750mm consists of 18mm -20 mm thick Jet BlackGranite Top with Edge moulding at the front and grove at the bottom to avoid by chemical spillage and is supported by rubber strip 6mm x 40 mm sheet of 1225mm +3935mmx 610mm +18mm with floor mounted under bench storage withdrawers unit of 1 drawer /2 shutter & 1 shelf unit of600mm x 500mm x 720mmand 3 drawer unit of 600mm x 500mm x 720 mm andLeg space/Cross Brace /foot rest/key board drawer / Cable Manager / Back pane.corner top support frame of 500mm x 500mm x 720mm and front gap covering panel of 580mm x 720 mm.Completely made of High zinc coated Galvanized Steel 1.0 mm thicknessprime export quality material with test certificate from galvanized steel manufacturer as per IS 277 standard. The shutter & drawer front should be of sandwich construction. Foam sheet filled in shutter gaps must required. The sound deadning Buffer to be used to minimize banging noise while closing the shutter.The shuttersare mounted to the modules by hinges which are openable to 90 degree & self closing on return. Lockable roller bearing to be usedso that the drawerwill not fall. The telescopic drawer slides which should be very sturdy &able to take load upto 30kg to 40Kg. All modulesto have lock and key arragement. Modules Completely finished with epoxy powdercoating. with minimum coating of 70-80 micron
168Providing and fixing of L shaped working table of 1075mm+1975mm x 610 mm x 900mm and 910mm x 910mm x 900mmconsists of 18mm -20 mm thick Jet BlackGranite Top with Edge moulding at the front and grove at the bottom to avoid by chemical spillage and is supported by rubber strip 6mm x 40 mm sheet of 1075mm +1975mmx 610mm +18mm and 910mm x 910 mm +18mm with floor mounted under bench storage withdrawers unit of 1 drawer /1shutter & 1 shelf unit of450mm x 500mm x 870mmand 1 drawer/ 2 shutter and 1 shelf unit of 600 mm x500mm x 870mm and 1 drawer/ 2 shutter and 1 shelf unit of 750mm x 500 mm x 870mm and 1 shutter & 1 shelf corner unit of 800+800mm x 500 mm x 870mm and electric Trunking of 1875mm+2490mm x 100mm x 100mm and 6/16 A switch socket of approved make andLeg space/Cross Brace /foot rest/key board 00 mmdrawer / Cable Manager / Back pane.Completely made of High zinc coated Galvanized Steel 1.0 mm thicknessprime export quality material with test certificate from galvanized steel manufacturer as per IS 277 standard. The shutter & drawer front should be of sandwich construction. Foam sheet filled in shutter gaps must required. The sound deadning Buffer to be used to minimize banging noise while closing the shutter.The shuttersare mounted to the modules by hinges which are openable to 90 degree & self closing on return. Lockable roller bearing to be usedso that the drawerwill not fall. The telescopic drawer slides which should be very sturdy &able to take load upto 30kg to 40Kg. All modulesto have lock and key arragement. Modules Completely finished with epoxy powdercoating. with minimum coating of 70-80 micron
169Providing and fixing of L shaped sitting table of 1375mm+3935mm x 610 mm x 750mm consists of 18mm -20 mm thick Jet BlackGranite Top with Edge moulding at the front and grove at the bottom to avoid by chemical spillage and is supported by rubber strip 6mm x 40 mm sheet of 1375mm +3935mmx 610mm +18mm with floor mounted under bench storage withdrawers unit of 1 drawer /2 shutter & 1 shelf unit of600mm x 500mm x 720mm and 1 drawer/2 shutter & 1 Shelf unit of 750mm x 500 mm x 720mm and adrawer unit of 600mm x 500mm x 720 mm andLeg space/Cross Brace /foot rest/key board drawer / Cable Manager / Back pane.corner top support frame of 500mm x 500mm x 720mm and front gap covering panel of 580mm x 720 mm.Completely made of High zinc coated Galvanized Steel 1.0 mm thicknessprime export quality material with test certificate from galvanized steel manufacturer as per IS 277 standard. The shutter & drawer front should be of sandwich construction. Foam sheet filled in shutter gaps must required. The sound deadning Buffer to be used to minimize banging noise while closing the shutter.The shuttersare mounted to the modules by hinges which are openable to 90 degree & self closing on return. Lockable roller bearing to be usedso that the drawerwill not fall. The telescopic drawer slides which should be very sturdy &able to take load upto 30kg to 40Kg. All modulesto have lock and key arragement. Modules Completely finished with epoxy powdercoating. with minimum coating of 70-80 micron
170WIRING
171Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C
172Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
173Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
1742 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
1752 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1762 X 4 sq. mm + 1 X 4 sq. mm earth wire
177Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
17820 mm
17925 mm
18032 mm
181Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
1825/6 A switch
1832 way 5/6 A switch
18415/16 A switch
1853 pin 5/6 A socket outlet
1866 pin 15/16 A socket outlet
187Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
188Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
189Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
1901 or 2 Module (75mmX75mm)
1913 Module (100mmX75mm)
1924 Module (125mmX75mm)
1936 Module (200mmX75mm)
1948 Module (125mmX125mm)
195MCCB, MCB & DB’S
196Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)8 way (4 + 24), Double door
197Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)4 way (4 + 12), Double door
198Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
199Single pole
200Triple pole
201Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
202Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
203Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
204Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
205CHAPTER-4-CABLE TRAYS
206Hot Dipped Galvanized Iron Cable Tray
207Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
208150 mm width X 50 mm depth X 1.6 mm thickness
209300 mm width X 50 mm depth X 1.6 mm thickness
210EARTHING
211Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
212Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
213Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
214Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
215Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
216Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
217Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
218Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
219CHAPTER 7-MV CABLE LAYING
220Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.
221Upto 35 sq. mm
222Above 185 sq. mm and upto 400 sq. mm
223Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
224Upto 35 sq. mm (clamped with 1mm thick saddle)
225Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
226Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required.
227Above 120 sq. mm and upto 400 sq. mm
228Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
2293½ X 400 sq. mm (82mm)
2303½ X 95 sq. mm (45mm)
2313½ X 50 sq. mm (35mm)
2323½ X 35 sq. mm (32mm)
2334 X 16 sq. mm (28mm)
2344 X 10 sq. mm (25mm)
235CHAPTER 10-HV CABLE JOINTING & END TERMINATION
236Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 300 sq. mm
237WIRING
238Wiring for light point/ fan point / exhaust fan point / call bell point with 1.5 sq.mm FRLS PVC insulated copperconductorsingle core cable in surface / recessedmedium class PVC conduit,with modular switch, modular plate,suitable GI box and earthing the point with 1.5sq.mm.FRLS PVCinsulatedcopper conductor single core cable etc. as required for;
239Two light controled by one switch.
240Three light controled by one switch.
241Four light controled by one switch.
242Five light controled by one switch.
243S" type M.S. fan hook fabricated from suitable dia. M.S. rod duly painted for fixing of ceiling fan. The "S" type hook shall be fixed to steel bar in RCC ceiling. The ceiling shall be replastered with sand, cement & neeru etc. The cost of labours for chipping out ceiling upto steel bar & fixing of "S" hook & resurfacing the ceiling is included in the cost of item
244MCCB, MCB & DB’S
245Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)12 way (4 + 36), Double door
246Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 100 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.25A
247Supplying and fixing following rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.25A, FP
248HT EQUIPMENTS
249RMU
25011KV Outdoor Metering Cubicle
251SITC of 11KV Outdoor Metering Cubiclecomprising of : 3 Nos. Current transformer (---/5A,15VA,class 0.2s) 1 No.Potential transformer(11KV /110V,100VA,class 0.2) Separate Compartment for CT/PT and TOD Meter with KSEB sealing facilityTTB with Fuse and CarrierProvision for incoming and outgoing XLPE 11 KV Cable and cable entry from bottom side withcable box suitable for 3 x 300 sqmm XLPE, 11KV Al: cable Enclosure-Powder coated CRCA sheet 2MM –IP 5411KV TOD Meter
252SITC of 11KV/ v3 / 110V/ v3 , Class 0.2S , 15VA HT TOD Meter suitable for mounting outdoortype with all standard accessories.11 KV KSEB metering cubicle, lead wires etc.complete Carrying CT/PT units with TOD meter for testing and calibrating at the KSEB Testing Lab and taking back the same to the site isincluded in the scope of the contractor.Statutory testing fees shallbe remitted and will be reimbursed against producing original receipt 11kV/433v, 160KVA USS
253HT Side comprising of : Incomer1 No. Indoor type 11kV, 630A, 26.3kA for 3 sec Horizontal Draw out LBS fittedwith Manual / Motor operated spring charging mechanism with 230V AC motor andmotor control switch, shunt trip coilof 24V DC, closing coil of 24V DC, Auxiliary Contact 6NO + 6NC, MechanicalON/OFF indicator,mechanical operation counter, master trip relay , auxilliary relay with multifunction meter, voltmeter with selectorswitch and 3 nos ammeter , necessary cast resin current transformer(45/5A , Cl:5P10,/ Cl: 1,15 VA-dual core),Potential transformer ( 11KV/110V , Cl:0.2 , 25VA ) Anti pumping feature, instantaneous IDMT relay withMicroprocessor based 3O/C + and 1E/F Protection relay, Strip Heater with thermostat , Power pack230V AC-24 V DC emergency OFF push button with Aluminium busbar and copper earthing strip Transformer comprising of :11kV/433V ,160KVA ,50Hz,3phase,Vector Dyn 11 Resin Cast Indoor Transformer with off circuit tapping+5% to -5% in steps of 2.5% with winding temperature indicator and hooter with allstandard accessories as per IS 2026/77 on HV side Rigid Bus Bar interonnection to the 11KV LBS Panel and on LT side cable boxsuitable for 3 x 3.5 x300 sq.mm XLPE Al ; cablewith all standard fittings and accessories.Painting shall be carried out as per IS 631, impedance ofthe transformer shall be as per relevant standards.
254HT CABLES
255Supply of 11KV stranded compact circular aluminium conductor,conductors insulation screened withextruded semi conducting compound in combination with copper tape (0.3 kA for 1 sec.),cores laid up, inner sheath of PVC tape,galvanized steel flat strip armoured,and overall PVC sheathed cable conforming to IS 7098/11/85 with latest amendments & confirming to the GTP of Group Aof following sizes.
2563C - 300 Sq.mm HT Cable
257GENERATORS
258SITC of D.G. set of following KVA 0.8 P.F.3 phase,50c/s,433V, comprising diesel engine, amf facilityfuel , tank, base plate,antivibration pad,battery, batterylead wire, battery charger self startingand self charging mechanism,and residential type silencer, control panel , in accoustic enclosure etc.with all standard accessoriesas per ElectricalInspectoratestandards and pollutioncontrol boardnorms.
25940 KVA
260NEUTRAL CTs
261Supply & Fixing of 1 No. Cast Resin Neutral CT fixed in a suitable M.S. box with viewglass. 63/5A, 10VA, Cl.5P10
262L.T.PANELS
263SITC of cubicle type mediumvoltage switch boards as per specificationsmentioned below, comprising ofACBs / MCCBs.,enclosed in 16 guage M.S.cubicle complete with angle iron frame work,panel doors , horizontal andvertical busbars and outgoing feeders,FRP separators, phase barriers,gaskets for door,feeders designations, etc.,Main Switch Board shall be capable of withstanding 50 KA fault level. The panelshall be suitable for erection on the floor using channel and fastners at regular intervals. All panels should have fire suppression system( Panel should confirm to BIS,IE rules,KSEI/ KSEB Standards)
264MAIN MV PANEL
265APFC PANEL - 50 KVAr
266POWER PANEL
267COMMON PANEL
268ESSENTIAL PANEL
269SUPPLY OF LT CABLE
270Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
2713½ X 400 sq. mm
2723½ X 95 sq. mm
2733½ X 50 sq. mm
2743½ X 35 sq. mm
2754 X 16 sq. mm
2764 X 10 sq. mm
277LIGHT FITTINGS / FANS
278SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans
279LED Downlight Recessed Fitting 12 W
280LED Linear Tube Light Fixture 40Watts 4ft
281Ceiling Fan -1200 mm
282Exhaust Fan- 250 mm
283Exhaust Fan- 450 mm
28450W Flood Light
2856M Pole& 35W LED Flood/Street Light with necessary arms for light fixtures (Civil works including)
286Bollard Lights
287LIGHTNING PROTECTION
288Air Terminal
289Providing and fixing Fully Solid Vertical Air terminals for wind stability as per IS/IEC -62305 part-3. For 1,2,3,4 meter air terminal 16mm rod tapered to 10 mm aluminium rodmeter rod: Meets the requirement (IS/IEC 62305). Semi-hard (E-AlMgSiO5) Suitable for high wind load. All air terminal must have Interception Tip at the Top of air terminal. System consist of Fang Fix with base and clamp on the top air terminal is erected. Air terminal Joining Clip Stainless Steel SS 304 clamp made of cable bracket, lightning tested for 100 KA 10/350 micro sec waveform. Stainless Steel Wall Clamp or 16 KG stone of 365 mm diameter, high level of stability.No. of stones/wall clamps depending on wind load. Quick and easy mounting of interception rod using anchors. Concrete, frost-resistant, can be stacked. Govt approved Indian labs test certificate required. Make: Cape/Dehn
2902meterairterminalwith Interception Tip mountedon Stainless Steel WallClamp mounting accessories.
291Parapet / Down Conductors
292Providing & fixing of 8mm solid aluminium round conductor with necessary holders @ required interval as specified below:Meets the requirement of (IS/IEC 62305) : semi-hard (E-AlMgSiO5 )with 50 sq.mm cross sectional area. Govt approved Indian labs test certificate required. Make: Cape/Dehn
293Conductor with Down Conductor Holder made of whether resistant plastic holder @ every 0.75 meters
294Conductor with Terrace Conductor Fibre Reinforce Concrete holder @ every 0.75 meters
295T-Connectors
296ProvidingandfixingofCrossConnector/TConnector/FoldingClamp/ClampingShoe/ Expansion Piece: to route vertical down conductor /mesh formation made ofAluminiumFerruleusingscrewfreejoints.FoldingClamp/ClampingShoeformetalpanels(upto 20mmthicknessofthemetalframe):Foldingclamp/clampingshoeformetalframe thicknessupto20mm,madeofstainlesssteelSS304/316grade, conformstothe requirements accordingto (IS/IEC 62305). Expansion piece with connector:Forequalising temperaturerelatedlengthchanges.Necessaryonconductorslengthat every 20 meters horizontally. Using round conductor 8mm aluminium conductor with straight Connector: usingAluminiumFerrule. Quick installation using crimp joints. Conforms to the requirements according to (IS/IEC62305).Makesurealljointsare strong and willbe inspectedatsite.GalvanisedIronjointsarenotpermittedtoavoidriskofcorrosion. Single bolt joints are not permitted to avoid risk of faulty loose joints and reduce risk of flash over. Govt approved Indian labs test certificate required. Make: Cape/Dehn
297Test Joints
298Providing and fixing of Stainless Steel Test Joint suitable with suitable Outdoor Enclosure: For 8mm dia solid round aluminium conductor & 10mmdiacopper coated solidsteel roundconductorhaving100micronsofcopperbonding.Conformstotherequirements according to(IS/IEC62305).Theenclosureshouldbeoutdoorglass-fibrereinforcedpolycarbonate opaque having minimum inner dimension of 75mm x 75 mm x 50 mm. Thetestlinkhastobestraightandneedsminimum4mountingscrewsforstrongjoints Inspection of bimetallic corrosion at site required. Seperation of 8mm Aluminium & 10mm Copper bonded steel is required for future inspection and contractor has to make sure both conductors permitted. Govt approved Indian labs test certificate required. Make: Cape/Dehn
299Ring Earthing
300Providingandlayingcoppercoatedsteelsolidroundconductor10mmdiameterfrom earth electrode directly in ground as required. copper coated steel, high corrosion resistant. Meets the requirement of (IS/IEC 62305) copper coating thickness of100microns Should be tested and use exclusively for lightning protection earthing system and ring equipotentialbonding.AftertestlinkneedstoberoutedinsideHeavydutyconduittoavoid touch potential till ground level. Govt approved Indian labs test certificate required.Make: Cape/Dehn
301Welded Joints
302Installation of Exothermic WeldJoints for 10mm round copper bonded steel conductor having 100 microns as per IS/IEC 62305.Each under ground joints has to be wrapped withpetrolatum- coatedchemicalfibrefabrichaving1.1mmthickandwidth 50mm. Govt approved Indian labs test certificate required. Make: Cape/Dehn
303Earth Pits
304Providingandfixingofmaintenance freeEarthingsystemcomprises ofmolecularly bonded copper of 99.9% purity on low carbon steel of min 3048mm length (10 feet), having a diameter of 20mm with copper bonding thickness of 250microns asper UL 467. The Rod has to be either continuous or with self-coupling peg & bore arrangement with fault current withstand capability of 30 KA rms value for 1 second and I peak of 76 KA The rod must be having corrosion test, peel off test for uniform coating, 180 degree bend testwith out peeloff of copper bonding. Exothermic welded Clamp for clamping as suggested as per NBC 2016.Ordinary Stainless steel/Copper alloy universal clamps are not recommended. For self coupling peg & bore arrangement rod needs Impactpoint onthe bottom rod for easy insertion. Earth enhancing mineral compound is used for improving the soil conductivity. The material shall be mineral inert to sub soil and shall not pollutethe environment and non corrosiveto earth rod. Thematerial shouldhave aresistivity less than0.2Om. It should be free from hazardous substances.The mineral compound is required to have minimum 17.5 Kg ofthe total composite.The compound should be chemically inert and needs to submitGovt approved Indian labs test certificate. Concrete Earth electrode inspection chamber with weight bearing capacity of 50KN. The dimension shall be 320mmx 320mmx 190mm. Govt approvedIndianlabstestcertificaterequired. Make: Cape/Dehn
305Solar PV
30640KWP Solar System - Essential Panel
307CCTV
308Supplying and fixing of 25 mm Medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
309Supply and drawing of UTP 4 pair Cat 6 LAN cable in the existing surface/recessed PVC conduit as required.
310one run
311Supplying and installing following size of perforated GI cable trays(galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with GI suspenders including bolts & nuts, required bends, tees, reducesetc as required.
312300 mm width X 50 mm depth X 1.6 mm thickness
313DATA
314Supplying and fixing of 25 mm Medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
315Supplying and fixing ofGI box of following size modules, alongwith modular base & cover plate for modular switches in recess etc as required.
3161 or 2 Module (75mmX75mm)
317Supply and drawing of UTP 4 pair Cat 6 LAN cable in the existing surface/recessed PVC conduit as required.
318one run
319Supplying and installing following size of perforated GI cable trays(galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with GI suspenders including bolts & nuts, required bends, tees, reducesetc as required.
320300 mm width X 50 mm depth X 1.6 mm thickness
321TELEPHONE
322Supplying and drawing 2 pair, 0.5 sq mm FR PVC insulated copper conductor, un armoured telephone cable in the existing surface/recessed steel/ PVC conduit.
323Supplying and fixing of 25 mm Medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
324Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc as required.
325Telephone socket
326Supplying and fixing ofGI box of following size modules, alongwith modular base & cover plate for modular switches in recess etc as required.
3271 or 2 module( 75 mmx75 mm)
328Supplying and installing following size of perforated GI cable trays(galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with GI suspenders including bolts & nuts, required bends, tees, reducesetc as required.
329150 mm width X 50 mm depth X 1.6 mm thickness
330CCTV
331Supply, installation, testing and commissioning ofIP based IRVarifocal dome Camera, 1/3" CMOS, 3 MP, 2.7–12 mm MFZ, night vision compatible,IR range of 40 mtrs PoE, inbuilt micro SD card,Ethernet port, H.264, IP 66, ONVIF, UL, FCC & CE certified. All mounting accessories shall be included
332Supply, installation, testing and commissioning ofIP based IRbullet Camera, 1/3" CMOS,3 MP,night vision compatible,IR range of 40 mtrs PoE,inbuilt micro SD card,Ethernet port, H.264, IP 66, ONVIF, UL, FCC & CE certified. All mounting accessories shall be included
333Supply, installation, testing and commissioning ofIP based IR PTZ camera, 1/3" CMOS, 2 Megapixel,30X zoom, WDR,IR range of 200 Meters, inbuilt micro SD card,,Ethernet port,TDN, PoE, DWDR, BLC, AGC, DNR, OSD,H.264 High Profile dual-stream, ONVIF, Wall/corner Mount, IP-66. CE, FCC, C-Tick certified. All mounting accessories and mounting arm suitable for the location shall be included
33432 Channel IP Cameras support, 4 SATA Ports ( Loaded with HDD for 60 days storage), Maximum users - 20 or higher, IR Range of 100 Mtr, Ptotocols - HTTP, HTTPS, TCP/IP, IPv4/IPv6, UPnP, RTSP, UDP, SMTP, NTP, DHCP, DNS, IP Filter, DDNS, FTP, SNMP, IP Search , ONVIF 2.4, SDK, CGI trigger Events - recording, PTZ, Tour, Alarm out, video Push, Email, FTP, Snapshot, Buzzer & Screen tips, recording Mode - manual, Schedule (Regular, Continuous), MD (video detection: motion detection, tampering, video Loss), Stop, Bandwidth - 200 Mbps, ONVIF 2.0
335Supply, installation, testing and commissioning of 20 100/1000 SFP ports + 4 Combo 10/100/1000BASE-T/SFP ports + 4 10G SFP+ ports, L2 Management Switch - Core Switch
336Supply, installation, testing and commissioning of 8 port- Edge PoE switch
337Supply, installation, testing and commissioning of 32 port- Edge PoE switch
338Supply, installation, testing and commissioning of Patch Panel  UTP Keystone- 32 Port- Fully loaded (Cat 5e,Cat 6 & Cat 6 A )
339Supply and installation of Cat 6 UTP patch cord, 1 mtr
340Supply, installation, testing and commissioning of Server PC, Intel i7 processor, 24 inch LED monitor, Gigabit LAN port, USB port, 8GB DDR3 RAM,1TB HDD,1GB dual graphic card, 100/1000 LAN ports, optical mouse, Keyboard, DVD Writer. Genuine Win 8.1 Pro - Down grade to Win 7 professional, 24 inch LED monitor
341Supply, installation, testing and commissioning of Professional Joystick designed for Surveillance application as compatible with the above mentioned system. UL+CE+FCC certification minimum.
342Supply, installation, testing and commissioning of Surveillance/ ESATA compatible Hard Disk of 4TB capacity to achieve the total storage for the NVR server
343Supply, Installation, Testing & Commissioning of 42 inch full HD LED monitor with resolution 1920X1080 pixel including wall mounting accessories (location: security room & central control room).Material shall be UL/CE listed
344Supply and installation of wall mounted 22U rackincluding cable manager, power supply units etc.to accommodate NVR, ethernet switch patch panel etc in control rooom
345PA SYSTEM
346Supply, installation, testing & commissioning of column speaker6 watts
347Supply, installation, testing & commissioning of 6 watts ceiling speakers
348Supply, installation, testing & commissioning of voice alarm call Station with all cables and accessories
349Supply, installation, testing & commissioning ofvoice alarm keypad - Extension to voice alarm call station with all cables and accessories
350Supply, installation, testing & commissioning of voice alarm controller with all cables and accessories
351Supply, installation, testing & commissioning of voice alarm router with all cables and accessories
352Supply, installation, testing & commissioning of 480 W Booster Amplifier with all cables and accessories
353Supply, installation, testing & commissioning of DVD/MP3Player for audio playback only
354Supply, Installation, Testing & Commissioning of Paging Microphone, goose neck type
355Supply, laying and termination ofShielded Cat6 cable with all necessary accessories
356Supply, laying and termination of2 Core x 1.5Sq.mm ArmouredAl.Mylar Screened FRLS Twin Twisted PVC Insulated cable along with all accessories. Accessories include cable glands, locknuts,saddle clips, cable tie & other hardwares to achieve cable termination and installation. Cable shall be terminated in speakers and amplifiers
357Supply, installation, testing & commissioning of standard AV rack with 600mm Width, 800 mm Outer Depthand 36U Height
358DATA SYSTEM
359Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc as required.
360RJ 45 socket
361Supply and installation of Cat-6 shuttered 24 port patch panel
362SITC of24 portunmanaged ethernet switch
363Supply and installation of 9U rack withFront glass door, Rear Perforated door with handle Lock & key. Front/Rear 19" mounting angles, top, bottom open, RAL 9005 with all other accessories
364TELEPHONE SYSTEM
365Supply,laying and termination of 10 pair telephone cable, 0.5mm copper PVC insulated,unarmoured telephone cable drawn in the existing cable tray
366Supply,laying and termination of 10 pair telephone terminal block housed in engineering plastic box with transparent hinged door
367Supply,installation,testring and commisioning of EPABX with the following specifications: 1.208 Analog Extensions with CLI Expandable to 512Ports 2. 08 Port Analog trunk with CLI and Power Failure Transfer and with Protection modules. 3. 02 PRI. 4. 02 nos Operator Console with 30 Direct selection Keys each. 5. 08 Port Voice Guidance to announce Extension Busy status, Wake up call announcement and other important telephone features,Auto Attendant facility for Welcome message announcement. 6. 02Nos -500 pair MDF(wall mountable) 7. 01 No. Call Billing and monitoring Software. 8. Charger/UPS with Batteries for backup of 1 hour.
368HVAC SYSTEM
369Supplying & installing M.S powder coated standard type stand mounting for outdoor unit of split A.C up to 2TR Capacity, erected with necessary hardware materials as irected. 1.75 kg for 1 set (8-3-3/151)
370Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
37122.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19mm thick insulation
372Providing and erecting 3 star and above rated approved make split air – conditioning unit consisting of condensing unit with fan motor, hermetically sealed rotary compressor with accessories etc. duly connected separately erected evaporating unit and blower motor with its accessories by means of proper insulated copper tubing up to 5 RMT suitable for (Cost includes M.S. Stand, Gas Charging & Internal Copper Wiring Remote Control).
373(B) For 1.5 ton capacity.
374(C) For 2 ton capacity.
375Remote control (b) Cordless remote control.
376SANITARY FIXTURES
377Providing & fixing White vitreous china water closet squatting pan (Indian type) along with "S" or "P" trap including dismantling of old WC seat and "S" or "P" trap at site complete with all operations including all necessary materials, labour and disposal of dismantled material i/c malba, all complete as per the direction of Engineer-in charge
378Orissa pattern W.C Pan of size 580x440 mm
379Providing and fixing white vitreous china extended wall mounting water closet of size 780x370x690 mm of approved shape including providing & fixing white vitreous china cistern with dual flush fitting, of flushing capacity 3 litre/ 6 litre (adjustable to 4 litre/ 8 litres), including seat cover, and cistern fittings, nuts, bolts and gasket etc complete.. Make: Jaquar, Kohler, Grohe, Cera high end series.
380Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- (a) White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer. Make:Jaquar, Kohler, Grohe, Cera high end series.
381Providing and fixing white vitreous china flat back half stall urinal of size 580x380x350 mm with white PVC automatic flushing cistern, with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P. brass, including painting of fittings and cutting and making good the walls and floors wherever required :Single half stall urinal with 5 litre P.V.C. automatic flushing cisternMake: Jaquar, Kohler, Grohe, Cera high end series.
382Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
383Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15 mm nominal bore.Make:Jaquar, Kohler, Grohe, Cera high end series.
384Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 15mm nominal bore Make: Jaquar, Kohler, Grohe, Cera high end series.
385WATER SUPPLY
386Providing and fixing Chlorinated Polyvinyl Chloride (CPVC SDR 11) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Internal work - Exposed on wall (Above ceiling and Ducts)
38720 mm nominal outer dia Pipes
38825 mm nominal outer dia Pipes
389Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. Make: Astral, Supreme, Finolex, Prince
39020 mm nominal outer dia Pipes
391ProvidingandsupplyingISImarkCID/FButterflyValvesasperIS:13095 (Latest Edition) of PN 10 and 50 mm diameter including all taxes, insurance, transportation,freightcharges,octroi,inspectioncharges,loading, unloading, conveyance to departmental stores, stacking etc. complete.
392ProvidingandsupplyingISImarkCID/FButterflyValvesasperIS:13095 (Latest Edition) of PN 10 and 40 mm diameter including all taxes, insurance, transportation,freightcharges,octroi,inspectioncharges,loading, unloading, conveyance to departmental stores, stacking etc. complete.
393Providing and fixing Gun metal check or non-return fullway wheel valve.(E) 40mm dia.
394A. SANITARY FIXTURES.
395Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required:- (a) White Vitreous China Wash basin counter top type 550x420mm with a 15 mm CP Brass single hole basin mixer. Make:Jaquar, Kohler, Grohe, Cera high end series.
396Providing, Fixing, Commissioning at site Urinal Partition with Curved shaped frosted glass fixing with brass screws,nuts , and washers complete including cutting and making good the walls and floors wherever requiredEtc complete. 900x450x10 mm tk. Make: Jaquar 1110uc/ equ.
397Providingandfixingofgrabbars300mmStainlesssteelinphysically disabledtoiletincludingallnecessaryfitting,SSScrews&Accessories etc.Complted in all manners and satisfied to of EIC. complete. Make: Jaquar, Kohler, Grohe, Hindware, Cera high end series.
398Providing and fixing of grab bars Vertical Swing 18-8 S, type-304, 18-gauge (1mm) stainless steel tubing with satin-finish. 1–1/4 (25mm) outside diameterwallmountedinphysicallydisabledtoiletincludingallnecessary fitting, SS Screws & Accessories etc.Complted in all manners and satisfied to of EIC.complete. Make: Jaquar, Kohler, Grohe, Hindware, Cera high end series.
399Providing, Fixing, Testing and Commissioning at site ablution Health Spray Faucet with wall hook and 1.2 mtr. Chrome plated PVC hose pipe, etc. complete in all respects. Queo - Addons/Kohler/Grohe/jaquar
400Providing and erecting water cooler having storage capacity 80Ltr. & cooling capacity 40 Ltr.per hour @ an ambient temp of 450C. The outlet temp. of the water should drop by 150 C within a hour, The water cooler should be comprisingof hermetically sealed compressor,fan motor,condensing unit, water tank surrounded by evaporating coil, thermostats, relay etc. complete withnecessaryinlet&outletconnection.Thebodyofwatercoolerwillbe made from Stainless Steel.
401Supplying&erecting5stagesinglereverseosmosiswaterpurification system with M.S.powdercoated frame,pre filterhousingwith "O"ringpre sediment filter GAC filter, carbon filter suitable buster DC pump capacity 80 psi,mentionwith40Osginlinetypepostcarbonfilterautolow&high pressureswitcheswithfollowingsizeofstoragetank&LPHcapacity& erectedasdirectedwith one year comprehensivemaintenance guarantee. [B] 25 Ltr / Hr with 30 Ltr. S.S. Pressure Tank
402B. SOIL, WASTE, VENT & RAIN WATER PIPES
40363 mm O.D( 4Kgf/cm2) Vent pipe in shaft
404Providing, Fixing, testing and commissioning at site in position uPVC pipe( IS : 4985 ) With Rubber Ring or Solvent Welded fittings with bosses where required e.g. tees, bends, coupling, etc. complete. (For Rain water pipes in shaft & Ceiling) Make: Astral/Supreme/Ajay
405110 mm O.D( 4Kgf/cm2)) Rain water pipe in shaft
406Supplying, Fixing, testing and commissioning at site in position u PVC pipe of 6Kgf/cm2including PVC fittings with bosses where required e.g. tees, bends,door TEE , Door Elboe where ever requiredcoupling and adapters and jointing with adhesive approved by fitting manufactures including cutting and making good the walls and floors or surface mounted with clamps as required at site universal clamps & anchor fasteners(8mm) , threaded rod(8mm),nuts ,washers, wherever required etc. complete.Make: Astral/Supreme/Ajay
40750 mm O.D. (6Kgf/cm2 (IS:4985)
40875 mm O.D. (6Kgf/cm2 (IS:4985)
409110mm O.D (6Kgf/cm2 (IS:4985)
410Supplying, Fixing, testing and commissioning at site in position Deep Seal UPvc fabricated Multi floor trap (4”), with suitable supporting on GI slotted rails (1.6mmthick) full threaded rod, anchor fasteners etc. Complete in all respects. 50/75 mm dia outlet (In Ceiling)Astral/Supreme/Ajay
411Supplying,Fixing, Testing and commissioning at site in position 150x150mm square C.P cast brass or stainless steel anti cockroach grating cover ss (304) of matching size of UPvc fabricated floor trap / multi inlet trap complete in all respects. Chilly/Eligna/
412Supplying,Fixing, Testing and commissioning at site in position 150x150mm square C.P cast brass or stainless steel sealed grating cover ss (304) of matching size of UPvc fabricated floor trap / multi inlet trap complete in all respects. Chilly/Eligna/ in common toilets
413Supplying,Fixing, testing at site in position 160mm dia square /circular grating Terrace rain water outlet(Cast Iron)(for 110mm dia pipe)
414Providing and fixing in position cowel went to pipes.(C) 100mm dia
415C. WATER SUPPLY (INTERNAL AND EXTERNAL)
416Supplying, Fixing, testing and commissioning at site Puddle Flangefabricated from Upvc ASTM Grade sch-40 pipes & uPVC sheet (600 mm long)
4172 ” (50mm) dia
418Supplying, Fixing, testing and commissioning at site Puddle Flangefabricated from 100 mm dia GI pipe with 6mm tk plate (600 mm long) for FIRE Tank
419D.EXTERNAL SEWERAGE
420Supplying and Laying of pipes and conveying to position; cleaning, laying and jointing to true lines and gradients,with proper bedding uPVC pipe of IS 4985(6kgf/cm2)including jointing the pipe as per specification, testing the pipe line after installation all per provisions of IS: 1742-1983 (Code of practice for building drainage) complete as directed by the Employer
421160 mm OD (6/kg/cm2)
422E.EXTERNAL STORM WATER DRAINAGE
423Providing and supplying of Class SN8Structured Wall polyethelene Piping systems (Pipe with online/offline coupler and elastomeric sealing ring) with non-smoothExternalAnnularCorrugatedandSmoothInternalSurfaces (Double Wall) for non-pressure underground Sewerage & Drainage application as per EN:13476-3 including all local and central taxes, transportation,freightcharges,octroi,inspectioncharges,loading, unloading, conveyance to the departmental stores etc. complete.(ID 150 mm diameter) Make: Astral, Supreme, Finolex, Prince
424160 mm OD (6/kg/cm2)
425200 mm OD (6/kg/cm2)
426Supply, installation, testing and commissioning of percolation well (Recharge well) including all work like drilling, compressor work, gravel packing, mud slurry disposal, clay packing and including of all materials like 300mm UPVC pipe, 300mm wire screens, 300mm collar joint, accessories, gravels, sand, sand filteration module etc. Site cleaning, mud pit, mud refilling for borewell must be in the contractor"sscope.Contractorhastomaintainthepercolationwellupto three years after installation.
427WATER TREATEMENT PLANT
42840 KLD Modular Membrane Bioreactor (MBR) based Sewage Treatment Plant, Design Flow KLD 40.0 LPH 2000.0 Type Fully-Automated, Design MLSS mg/L 6000.0 – 8000.0 Operating Hours h 24.0, Design Flexibility % 30 - 100 with transfer pumps, air blowers, medias, membrine, tube settlers and all connected pipe lnes and necessary power connections and cubicle control panel in all respect.
429Miscellaneous Works
430Excavation for foundation/utility services upto 1.5 m depth including sorting out and stackingofusefulmaterialsand disposingoffthe excavated stuff with all lead and lift.(E)HardRock
431Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20 cm. in depth consolidating each depositedlayer by ramming and watering. (Ramping by manual or mechanical means)
432Providing and fixing S.W. gully trap with C.I. grating brick masonry chamber and water tight C.I. cover with frame of 300mm x 300mm size (inside) with standardweight.(i)Squaremouthtraps.(B)150mmx100mmsizePorR type(make-Local )
433Construction of Manhole chambers(Inspection chambers) 600mm X 600 mm and depth 1.0 m in brickorbelastonemasonry,locallyavailableinC.M.1:6.Foundation concrete150 mm thick in C. C.1:4:8oftrap metalsize 25mm to40mm thick, inside cement plaster in C. M. 1:3 and cement pointing outside in C. M. 1:3 and top cover of precast RCC slab 100 mm thick (with key hole in two parts, each with handles or MS Bar etc. complete as given size) Upto 1 Mt. depth from G. L. to pipe invert level incl. complete civil works but excl. cost of excavation and refilling, with cast in situ RCC slab in one single piece with fixing of CI-MH Frame and cover (incl. cost of CI-MH Frame and cover) with 23 mm thick brick masonry wall in C.M.1:6.With precastslab in two parts 15mm.
434Extra over items above for every additional depth of 0.1M. of part thereof beyond 450mm depth for Brick masonry chamber.(i)
435ProvidingandfixingC.I.coverwithframe(Medium duty)450x450mm , total weight of cover and frame to be not less than 116 kgFOR SUMP TANKS
436ProvidingandfixingC.I.coverwithframe(Light duty)450x450mm , total weight of cover and frame to be not less than 38 kg for OHT
437F.PUMP AND ACCESSORIES
438Supply,Installation, Testing and commissioning of Clear water transfer open well submerssible pump of adiquate hp with discharge 3 lps at 20 mtr head, SS body, ss shaft with bronze impeller mounted on a single base platewith controll panel and auto level controller.
4391 working+ 1 stand by
440Fire Hydrant System
441Supply, installation, testing & commissioning of Single headed, S.S. ISI marked, ISO approved, oblique pattern hydrant landing valve with 80 mm dia flanged inlet and 63 mm dia instantaneous type female outlet complete with SSl cap and G.I. chain, twist release type plug and all accessories required for complete installation as per IS:5290(Type "A")Make: Safeguard, Minimax, New Age
442Supply, installation and testing of Controlled Percolating (CP) Fire Hose ISI marked (IS:8423) 63 mm dia x 15 m long complete with instantaneous type S.S. 63 mm dia, ISI marked Male & Female couplings (IS:903) bound and riveted to hose pipe with copper rivets and 1.5 mm copper wire including all accessories as required for complete installation. (For external hydrants) Make: Safeguard, Minimax, New Age
443Supply, installation and testing of S.S. 63mm dia short size, universal branch pipes with adjustable nozzles with 63mm instantaneous coupling ISI marked ISO approved including all accessories complete required for installation (IS: 903). And as per industrial standards Make: Safeguard, Safefire, Minimax, New Age
444Supply, installation, testing and commissioning of compact type first aid fire hose reel with wall mounting swinging-type drum complying to EN 671-1 standards with ISI marked, 19 MM x 30 M long thermoplastic hose. 560 MM Dia powder coated sheet metal frame, water ways made from Non-Ferrous aluminium Alloy metal, High quality semi-rigid marked (Type-1 or Type-2) flame resistant, kink and abrasion resistant,thermoplastic Hose. Rotary operated leak proof, hydraulically crimped with corrosion-free Stainless Steel Grade 304 fitting, shut-off nozzle with shut, spray & jet functions, etc. and tested to 1.2 MPA( 12 Bar pressure) installation brackets, complete in all respects including all accessories as required for complete installation. INLET PIPE CONNECTION FROM RISING MAINS TO HOSE REEL SHALL BE PROVIDED WITH GI HEAVY CLASS PIPES WITH UNIONS OR WITH READY MADE TYPE FLEXIBLE RUBBER HOSE IN STANDARD LENGTH, HYDRAULICALLY FITTED END CONNECTIONS ETC .Make: Monsher, Minimax, New Age
445Supply, installation, testing and commissioning of Gun-metal 4-way fire brigade inlet connection 63mm dia instantaneous type male coupling with built in check valves and 150mm dia flanged outlet complete with bolts, nuts and rubber insertions as per I.S:904 including all accessories as required for complete installation. Make: Safeguard, Safefire, Minimax, New Age
446Supply, installation, testing and commissioning of GI pipe (IS:1239 Part-I) Heavy duty Class "B" including cutting, welding etc. bends, elbows reducers, tees , clamps, hangers and all other accessories as required for complete installation etc. including cutting holes in brick or RCC walls/slabs and making good the same complete including painting with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade including all steel work. Note : Pipes up to and 50 mm dia shall be socket welded with DI fittings. For pipes inside the plant room
447100 mm dia
448Supply, installation, testing and commissioning of wafer types" iron , without lugs, lever operated Butterfly valves (PN 1.6) complete suitable with with bronze/gunmetal seat and all accessories required for complete installation. Make : Leader/ Audco/ Zoloto
449100 mm dia
450Supply, installation, testing and commissioning of horizontal lift swing check type reflux non-return valves (PN 1.6) complete with matching flanges, rubber insertion, nuts, bolts and washer etc. of following sizes complete with all accessories required for complete installation. Make : Leader/ Audco/ Zoloto
451100 mm dia
452Supply, installation, testing and commissioning of Brass Air release valve, size 25mm with threaded inlet & provided with ball type float complete with all accessories required for complete installation. Make : Leader/ Audco/ Zoloto
453Supply, installation, testing and commissioning of industrial type pressure switch having 1/4" BSP(F) connection IP:32 enclosure protection, phosphor bronze bellows as sensing element, SDPT contact system, switch rating 6A Inductive/lOA resistive 380 V AC, 0.2A Inductive/10A resistive 250V DC suit with ball valve etc. complete as required. Make: Infoss/
454FIRE PUMPS & ACCESSORIES
455Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump).
456a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520
457b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-"F" insulation, conforming to IS-325.
458c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.
459d) Suitable cement concrete foundation duly plastered and with anti vibration pads.
460900 lpm at 35 m Head
461Make : Kirloskar, Mather & Platt India Limited
462Fire Hydrant System
463Supply and installation of Weather proof Outdoor type hose cabinets fabricated from 14 SWG M.S. sheet with full glass door with locking arrangement (Water Proof), suitable to accommodate 2 nos.15 M long hose and 1 No branch pipe. Glass will be transparent Acrylic - 3mm thick. The cabinet shall be painted with coat of P O Red paint from outside and white paint from inside including all accessories as required for complete installation.(size shall be such that the above all items can be accommodated). (Double door type) as per industrial standards
464Supplying, laying, fitting and fixing , testing and commissioning of under ground GI heavy duty "C" class pipe confirming to IS 1239 The pipes shall have anti-corrosive wrapping coating and a wrapping treatment with pipe coat 4 mm thickness, after applying one or more coats of Asphalt primer. Rates shall include cutting, welding etc. bends, elbows reducers suitable for pipe joints, clamps and all other accessories including excavation of earth to sufficient depth to install the pipes, the pipes buried in ground excavation and refilling etc.as per the specification and as required complete as required for complete installation etc. including cutting holes in RCC walls/slabs and making good the same adequately supported on rigid supports duly painted as required complete in all respect including allup to building rising mains and for yard hydrants ,
465100 mm dia
466Supply & installation of Pressure Gauge with 0-300 psi (0-21Kg/Sq.CM) range white background, black graduation scale with dual reading in Kg/Sq.CM & PSI, 1/4" BSPT bottom entry 100 MM dial, PHOSPHOROUS BRONZE bourden tube, brass moving parts, polished stainless steel case with positive seal against weather, moisture & dust, hardened glass, glycerine filled type with syphon tube and isolation cock,Make: Fiebig / H guru
467Providing & fixing double flanged flexicon rubber expansion joint with unit control of standard length as per manufacturers specifications suitable for working pressure rated (PN16) and test pressure to be 150 % rated pressure ofincluding rubber gaskets, flanges, nuts, bolts and washers complete as required
468100 mm dia
469Extinguishers
470Supply and fixing Co2 type Fire Extinguisher of capacity 4.5 kg filled with Co2 Gas with control discharge mechanism ( squeeze grip type) fitted with Bend and Horn applicable on Class B and C class of fire. Manufactured and marked to IS 15683 with ISI marking and cylinders having the approval of Chief Controller of Explosives, and including all accessories as required for complete installation.
471Supply and fixing of dry chemical powder type (DCP) fire extinguishers (ABC Type) of 4 Kg capacity, Pressurized with nitrogen, mfg. to IS:15683 with ISI mark fitted with pressure gauge, GM cap nozzle complete with initial charges and installation brackets and screws with ISI marks etc. complete as approved and instructed by the engineer in charge including all accessories as required for complete installation..
472WIRING
473Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
474Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 32 mm
475MCCB, MCB & DB’S
476Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer ) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
4774 way (4 + 12), Double door
478Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
479Triple pole
480Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
481Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
482Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
483EARTHING
484Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
485Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
486Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
487Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
488CHAPTER 7-MV CABLE LAYING
489Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
490Upto 35 sq. mm
491Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.
492Upto 35 sq. mm
493Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
494Upto 35 sq. mm (clamped with 1mm thick saddle)
495CHAPTER 9-MV CABLE JOINTING & END TERMINATION
496Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
4974 X 10 sq. mm (25mm)
498L.T.PANELS
499SITC of cubicle type mediumvoltage switch boards as per specificationsmentioned below, comprising ofACBs / MCCBs.,enclosed in IP 65 Box, with pedestals Panel should confirm to BIS,IE rules,KSEI/ KSEB Standards)
500EXTERNAL LIGHTING DB
501SUPPLY OF LT CABLE
502Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
5034 X 10 sq. mm
5043X 4 sq. mm
505MV CABLE JOINTING & END TERMINATION
506Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
5073X 4 sq. mm
508LIGHT FITTINGS / FANS
509SITC of following Light Fixtures/Ceiling Fans / Exhaust Fans
51050W Flood Light
5116M Pole& 35W LED Flood/Street Light with necessary arms for light fixtures (Civil works including)
512Bollard Lights
51312M Meter High Mast with 6nos of 200W LED Lights including civil works
5146W Buried Uplighter
515CCTV
516Supplying and fixing of 25 mm Medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
517Supply and drawing of UTP 4 pair Cat 6 LAN cable in the existing surface/recessed PVC conduit as required.
518one run
519CCTV
520Supply, installation, testing and commissioning ofIP based IRbullet Camera, 1/3" CMOS,3 MP,night vision compatible,IR range of 40 mtrs PoE,inbuilt micro SD card,Ethernet port, H.264, IP 66, ONVIF, UL, FCC & CE certified. All mounting accessories shall be included
521Supply, installation, testing and commissioning ofIP based IR PTZ camera, 1/3" CMOS, 2 Megapixel,30X zoom, WDR,IR range of 200 Meters, inbuilt micro SD card,,Ethernet port,TDN, PoE, DWDR, BLC, AGC, DNR, OSD,H.264 High Profile dual-stream, ONVIF, Wall/corner Mount, IP-66. CE, FCC, C-Tick certified. All mounting accessories and mounting arm suitable for the location shall be included
52232 Channel IP Cameras support, 4 SATA Ports ( Loaded with HDD for 60 days storage), Maximum users - 20 or higher, IR Range of 100 Mtr, Ptotocols - HTTP, HTTPS, TCP/IP, IPv4/IPv6, UPnP, RTSP, UDP, SMTP, NTP, DHCP, DNS, IP Filter, DDNS, FTP, SNMP, IP Search , ONVIF 2.4, SDK, CGI trigger Events - recording, PTZ, Tour, Alarm out, video Push, Email, FTP, Snapshot, Buzzer & Screen tips, recording Mode - manual, Schedule (Regular, Continuous), MD (video detection: motion detection, tampering, video Loss), Stop, Bandwidth - 200 Mbps, ONVIF 2.0
523Supply, installation, testing and commissioning of 20 100/1000 SFP ports + 4 Combo 10/100/1000BASE-T/SFP ports + 4 10G SFP+ ports, L2 Management Switch - Core Switch
524Supply, installation, testing and commissioning of 8 port- Edge PoE switch
525Supply, installation, testing and commissioning of 32 port- Edge PoE switch
526Supply, installation, testing and commissioning of Patch Panel  UTP Keystone- 32 Port- Fully loaded (Cat 5e,Cat 6 & Cat 6 A )
527Supply and installation of Cat 6 UTP patch cord, 1 mtr
528Supply, installation, testing and commissioning of Professional Joystick designed for Surveillance application as compatible with the above mentioned system. UL+CE+FCC certification minimum.
529Supply, installation, testing and commissioning of Surveillance/ ESATA compatible Hard Disk of 4TB capacity to achieve the total storage for the NVR server
530Providing, Fixing, testing and commissioning at site in position uPVC pipe( IS : 4985 ) With Rubber Ring or Solvent Welded fittings with bosses where required e.g. tees, bends, coupling, etc. complete. Make: Astral/Supreme/Ajay
531110 mm O.D( 4Kgf/cm2)
532110 mm O.D( 6Kgf/cm2)) Perforated Drain Pipes
Disclaimer :