Indian Oil Corporation Limited-IOCL has published Tender For Supply Installation, Testing And Commissioning Of Energecy Saving Is Standard Transfomer And Ht Panel At Lbp Trombay In The State Of Maharashra. Submission Date for this Tender is 26-11-2022. Transformer Supply Tenders in trombay Maharashtra. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | SUPPLY, INSTALLATION, TESTING & COMMISSIONING OF ENERGECY SAVING IS STANDARD TRANSFOMER AND HT PANEL AT LBP TROMBAY IN THE STATE OF MAHARASHRA |
2 | Supply of HT circuit breker- Supply of 11 KV, 630 A ,25 KA/3 sec HT VCB Panel with approved or reputed make. |
3 | Supply of 11KV, 3C, 400Sqmm Al Round Armoured XLPE Power Cable from Adani POWER POINT to IOCL Breaker (50Mtrs) |
4 | Supply of termination Kit -Supply of Indoor Boot Termination Kit for 11KV, 3C, 400Sqmm Al Round Armoured XLPE Power Cable between Adani Breaker & IOCL Breaker of approved or reputed make. |
5 | Supply of Indoor Boot Termination Kit for 11KV, 3C, 400Sqmm Al Round Armoured XLPE Power Cable between IOCL Breaker & new 1000KVA Transformer of approved or reputed make. |
6 | Earthing work -Supply of Chemical Earthing material for HT Breaker Earthing with 75mm dia CI Pipe, 50x6mm HDGI Flat & Earthing Chember of size 500x500 mm of approved or reputed make. |
7 | Dismentaling work -Dismentaling of old HT Circuit Breaker and keeping it at safe place assigned by location incharge of LBP Plant, IOCL Trombay. |
8 | Removal of old earthing of Breaker and keeping it at safe place assigned by location incharge of LBP Plant, IOCL Trombay. |
9 | Services for HT Circuit Breaker- Installation, testing & commissioning of 11 KV, 630 A ,25 KA/3 sec HT VCB Panel. |
10 | Services for Cable laying & Termination- Laying of 11KV, 3C, 400Sqmm Al Round Armoured XLPE Power Cable from Adani POWER POINT to IOCL Breaker (50Mtrs) & from IOCL Circuit Breaker to Transformer (50Mtrs)via underground Trench. |
11 | Termination of 11KV, 3C, 400Sqmm Al Round Armoured XLPE Power Cable from Adani POWER POINT to IOCL Circuit Breaker & Breaker outgoing through Indoor boot termination kit |
12 | Services for Earthing- The new earthing arrengements for new HT Breaker will be provided and the electrodes contact resistance for each earth pits will be measured and confirmed for less than 0.75 omhs and the record will be submitted to IOCL. |
13 | Civil Work- Making of HT Circuit Breaker Plinth upton height of 220mm for 11 KV, 630 A ,25 KA/3 sec HT VCB Panel |
14 | Designing & Liasoning Portion -Preparation of Drawings, Test Reports, MOM"s, General Arrangemet, work sequence sheet, etc |
15 | Central Electricity Authority (CEA) Inspections, Approvals, documentation, etc. |
16 | Outage Management, documentations, etc at Adani Power |
17 | Supply of 1000KVA, 11/0.415 KV, two wdg Transformer EEL2 confirming to IS1180 Part 1 2014, OUTDOOR TYPE, ONAN, on load tap changer, IS 1180 STANDARD ENERGY SAVING LEVEL 2, STAR RATING- 4 , BUCCHOLZRELAY, transformer oil confirming to IS335, bushings confirming to IS2099 & 3347 with approved or reputed make. |
18 | Supply of Cables- Supply of 11KV, 3C, 400Sqmm Al Round Armoured XLPE Power Cable from IOCL Breaker to Transformer (50Mtrs) of approved or reputed make.Make : M/s Polycab , M/s KEIIndustries, Mumbai, M/s KEC Cables, Mumbai |
19 | Supply of 440V, 3½ C, 400Sqmm Al Round Armoured XLPE Power Cable Four runs each of 37Mtrs from 1000KVA Transformer to Distribution Panel 1&2 of approved or reputed make. |
20 | Supply of 10C, 2.5sqmm Cu. Round Armoured Control Cable between Breaker & Transformer of approved or reputed make. |
21 | 3C, 2.5sqmm Cu. Round Armoured power cable between Breaker & Transformer of approved or reputed make. |
22 | Supply of Termination Kits- Supply of Outdoor Termination Kit for 11KV, 3C, 400Sqmm Al Round Armoured XLPE Power Cable at 1000KVA Transformer primary side of approved or reputed make. |
23 | Supply of Earthing Material- Supply of Chemical Earthing material for Transformer Neutral Earthing with 75mm dia CI Pipe, 50x4mm Cu Flat & Earthing Chember of size 500x500 mm of approved or reputed make. |
24 | Supply of Chemical Earthing material for Transformer Body Earthing with 75mm dia CI Pipe, 50x6mm HDGI Flat & Earthing Chember of size 500x500 mm of approved or reputed make. |
25 | Dismentaling work- Demolishing of Godown portion for access from road side along with removal of existing shed of the old 500KVA & 750KVA Transformer |
26 | Demolishing of existing 500KVA & 750KVA Transformer plinth. |
27 | Dismentaling of old 750KVA Transformer and keeping it at safe place assigned by location incharge of LBP Plant, IOCL Trombay. |
28 | Dismentaling of old 500KVA Transformer and keeping it at safe place assigned by location incharge of LBP Plant, IOCL Trombay. |
29 | Removal of old earthing of transformers & Breaker and keeping it at safe place assigned by location incharge of LBP Plant, IOCL Trombay. |
30 | Services for 1000KVA New Transformer- Installation, testing & commissioning of 100KVA, 11/0.415 KV Transformer. |
31 | Services for Cable laying & Termination-Laying of 440V, 3½ C, 400Sqmm Al Round Armoured XLPE Power Cable Four runs each of 37Mtrs from 1000KVA Transformer to Distribution Panel 1&2 via underground Trench |
32 | Laying of 10C, 2.5sqmm Cu. Round Armoured Control Cable between Breaker & Transformer & 3C, 2.5sqmm Cu. Round Armoured power cable between Breaker & Transformer via underground Trench |
33 | Termination of 11KV, 3C, 400Sqmm Al Round Armoured XLPE Power Cable at primary side of transformer through outdoor termination kit |
34 | Services for Earthing- The new earthing arrengements for new 1000KVA Transformer (Body & Neutral) will be provided and the electrodes contact resistance for each earth pits will be measured and confirmed for less than 0.75 omhs and the record will be submitted to IOCL. |
35 | Civil Work- Making of cable trench with chakkar Plate covers for power cables between HT Breaker & the 1000KVA Transformer via HT Breaker [300x300 mm]with combined lenth of 25 Mtrs |
36 | Making of Transformer"s RCC plinth for 1000KVA New Transformer upto height [Dimension of Plinth: 2200x2600x1800 mm] |
37 | Civil work for reconditioning of demolished Godown portion. |
38 | Making of Shed of appropriate size with chainlink Fensingupto height of 6 feet for the new transformer of 1000KVA near the Control panel room |
39 | Designing & Liasoning Portion- Preparation of Drawings, Test Reports, MOM"s, General Arrangemet, work sequence sheet, etc |
40 | Central Electricity Authority (CEA) Inspections, Approvals, documentation, etc. |
41 | Outage Management, documentations, etc at Adani Power |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy