Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | CIVIL WORKEarthwork in excavation in hard soil for site leveling, foundation, pits, trenchesand other civil works upto and including 1.5metre lift and stacking the soil upto a lead of 100 metre and including dewatering, removing slush, shoring and strutting (as required), complete as per specification and as directed by the Engineer-In-Charge. |
| 2 | Filling in foundation trenches and plinth, with excavated earth including laying the earth in layers not exceeding 23.5 cm thick ramming & watering with all leads & lifts including cost of all labour,T&P completed as directed by the Engineer-in-charge. |
| 3 | Supplying and filling sand in foundation and over areas including watering, ramming, consolidating and dressing, labours, tools, taxes etc. all complete as per the specification and direction of Engineer-In-Charge. |
| 4 | Providing anti-termite treatment using approved quality of chemical emulsion, spraying the mixture uniformly by sprayer as pre-constructional anti termite treatment and creating a chemical barrier under and around the column pits, wall trenches, top surface of plinth filling, junction of walls & floors along with external perimeter of the building, expansion joints, surrounding the pipes and conducts etc. complete at the rate as directed by the manufacturer confirming to IS:6313 (Part-II) and as per direction of Engineer-in-charge including cost of all materials, labour, taxes, sundries, T&P. etc. complete (The payments shallbe made on the basis of actual plinth area of the building at Ground Floor & vertical faces will not be measured for payment) |
| 5 | Providing and laying plain cement concrete 1:3:6 (1 cement : 3 sand : 6 stoneagregate 40mm nominal size) as levelling course in floor and plinth including tempering, curring, shuttering etc. complete all depth and height. |
| 6 | Providing and laying plain cementconcrete1:2:4 (1 cement: 2 sand: 4 stoneaggregate 12mmnominal size) as levelling course in foundation and plinth etc. includingtempering, curring, shuttering etc.complete all depth and height. |
| 7 | Providing and laying plain cementconcrete1:4:8 (1 cement: 4 sand: 8 stoneaggregate 40mmnominal size) as levelling course in foundation and plinth etc. includingtempering, curring, shuttering etc.complete all depth and height. |
| 8 | First class Fly ash Brick masonry usingbricks of size 23 cm. x 11 cm. x 8 cm. having crushing strength not less than 75 kg. Per. Sqr. Cm. in cement mortar of mix( 1:6) with ordinary Portland slag cement(PSC) and screened & washed sand for mortar after immersing the bricks for 6 (Six) hours in water before use in Foundation & Plinth including splays cutting, circular moulding, corbelling, chamfering and similar such type of works, watering and curing etc. including cost, conveyance, loading, unloading, royalties and taxes of all materials, cost of all labour, scaffolding, sundries, T&P required for the works etc. complete in all respect as directed by the Engineer-in-Charge. |
| 9 | Fly Ash. brick masonryof size 23 cm. x 11 cm. x 8 cm. having crushing strength not less than 75 kg. Per Sqr. Cm. in cement mortar of mix (1:6) with approved grade cement and screened & washed sand for mortar after immersing the bricks for 6 (Six) hours in water before use in Superstructure including splays cutting, circular moulding, corbelling, chamfering and similar such type of works, watering and curing etc. including cost, conveyance, loading, unloading, royalties and taxes of all materials, cost of all labour, scaffolding, sundries, T&P required for the works etc. complete in all respect as directed by the Engineer-in-charge |
| 10 | Ground floor |
| 11 | First floor |
| 12 | Terrace floor |
| 13 | Half brick work with Fly Ash brick masonry in cement mortar (1:4) in super structurehaving a crushing strength of not less than 75 kg./sqcm with dimensional tolerance ± 2% including splays cutting circular moulding chamfering and corbelling and similar such type of works with all necessary projections watering and curing after immersing the bricks in water at least for six hours before use including cost, conveyance, royalties and taxes of all materials with all labour,labour cess and T & P required for the work complete in all respect as per direction of Engineer-in-Charge. |
| 14 | Ground floor |
| 15 | First floor |
| 16 | Providing, lifting, hoisting and laying Reinforced cement concrete of M-25 grade as per approved designs and drawings having a minimum compressive strength (in work test) 250 Kg. / Square cm. in 15 cm. cubes at 28 days after mixing and test conducted in accordance with I.S. 516 using 12 mm. to 20 mm. size black hard crushed broken granite stone chips and screened and washed sharp sand for mortar of approved quality from approved quarry, washed andcleaned ( 20mm. size chips not to exceeds 25 % ) to be mixed in concrete mixture with Portlandslag cement (PSC) including hoisting, lowering, laying and compaction concrete by using vibrators, watering and curing for 28 days, centering and shuttering then after dismantling and removing debris from the work site and finishing the exposed surface smooth providing grooves or beads wherever necessary including cost, conveyance, loading, unloading, royalties and taxes of all materials and cost of all labours, sundries, T & P required of the work etc. complete in all respect as directed by the Engineer-in-Charge. But excluding cost and conveyance of M.S. rods or Tor steel and binding wires and labour charges for straightening, cutting, bending etc. of M.S. rods or tor steel tying the grills and placing in proper position. |
| 17 | Ground floor |
| 18 | a) Footing |
| 19 | b) Column up to plinth and pedestal |
| 20 | e) Plinth Beam |
| 21 | f) Column above plinth |
| 22 | g) Lintel |
| 23 | h) Chajja |
| 24 | i)Shelves |
| 25 | i) Roof Beam |
| 26 | j) Slab |
| 27 | k) Stair case |
| 28 | First floor |
| 29 | f)Column |
| 30 | g) Lintel |
| 31 | h) Chajja |
| 32 | i)Shelves |
| 33 | i)Roof Beam |
| 34 | j) Slab |
| 35 | k) Stair case |
| 36 | Terrace floor |
| 37 | f)Column |
| 38 | h) Chajja |
| 39 | i)Roof Beam |
| 40 | j) Slab |
| 41 | Cutting, straightening coiled or bent up M.S. Rod or tor steel of SAIL/ TATA / RINL (VIZAG) make includingbending, binding, welding and joining if necessary and tying the grills and placing in position as required for R.C.C. Work and for providing fan hooks as required, hoisting, lowering, laying including cost, conveyances, taxes of M.S. Rod or tor steel and binding wires of 18 to 20 gauge and labour required for the work for bending, binding and tying the grills in all floors (Linear measurement will be taken and quantity will be calculated basing on the standard weight of B.I.S. for M.S. Rods or tor steel only. Wastage if any, including weight of binding wire will not be considered for measurement) etc. complete as per specification & direction of Engineer-in-charge. |
| 42 | Ground floor |
| 43 | First floor |
| 44 | Terrace floor |
| 45 | Providing 12mm thick cement plaster with cement mortar of mix (1:6) with screened and washed sharp sand for mortar and finished smooth to the rough surface of walls in all heights after racking out joints including watering and curing, rounding of corners, providing grooves where ever necessary with cost, conveyance, royalties and taxes of all materials with cost of all labour, T&P, and scaffolding required for the work etc. complete in all respect as directed by EIC |
| 46 | Ground floor |
| 47 | First floor |
| 48 | Terrace floor |
| 49 | Providing 16 mm thick cement plaster with cement mortar of mix (1:6) with screened and washed sharp sand for mortar and finished smooth to the rough surface of walls in all heights after racking out joints including watering and curing, rounding of corners, providing grooves where ever necessary with cost, conveyance, royalties and taxes of all materials with cost of all labour, T&P, and scaffolding required for the work etc. complete in all respect as directed by the EIC |
| 50 | Ground floor |
| 51 | First floor |
| 52 | Terrace floor |
| 53 | Providing 6mm thick cement plaster with cement mortar of mix (1:4) with screened and washed sharp sand for mortar and finished smooth to the rough surface of walls in all heights after racking out joints including watering and curing, rounding of corners, providing grooves where ever necessary with cost, conveyance, royalties and taxes of all materials with cost of all labour, T&P, and scaffolding required for the work etc. complete in all respect as directed by EIC |
| 54 | Ground floor |
| 55 | First floor |
| 56 | Terrace floor |
| 57 | Supplying, fitting & fixing of Granite Tiles of minimum Above 0.40 sqm. (20mm thick) of approved make in floors laid on 20 mm thick cement mortar (1:4)(1 cement : 4 course sand) and filling joints with slurry including cost of all materials, labour T&P etc. required for the work all complete incl. rubbing as per direction of the Engineer-in-charge. |
| 58 | Ground floor |
| 59 | First floor |
| 60 | Supplying, fitting & fixing of Granite Tiles of minimum Above 0.10 Sqm & up to 0.4 sqm (10mm. thick) of approved make in dadoes laid on 12 mm thick cement mortar (1:3)(1 cement : 3 course sand) and filling joints with slurry including cost of all materials, labour T&P etc. required for the work all complete incl. rubbing as per direction of the Engineer-in-charge. |
| 61 | Ground floor |
| 62 | First floor |
| 63 | Supplying, fitting & fixing of8-10 mm thick& sizeof 600x600 mm vertified floor tileof matt finish with veilcraft (VC/FT )shield( Scratch free/stain free) withwater absorption limitbetween 0.08% to 3% and conforming to IS : 15622:2006 (Group B Ib). laid on 20 mm thick cement mortar (1:4) (1 cement : 4 course sand) and filling joints with white cement of approved quality including cost of all materials, labour T&P etc. required for the work all complete as per direction of the Engineer-in-charge (for New Work only ) |
| 64 | Ground floor |
| 65 | First floor |
| 66 | Supplying, fitting & fixing of 8-10 mm thick and size of 600x600 mmvertifiedwall tile of in dadoes, skirting and risers of steps oflaid on 12 mm thick cement mortar (1:3) (1 cement : 3 course sand) jointed with slurry mixed with pigment to match the shades of the tiles etc. complete including cost of all materials, labour T&P etc. required for the work all complete as per direction of the Engineer-in-charge. |
| 67 | Ground floor |
| 68 | First floor |
| 69 | Providing and fixing seasoned sal wood work in frames at any locations including doors, windows,cupboard, clerestory and other framesfixing in position including cost of hinges, M.S. flat (30mm x 6mm) hold fasts lugs ordash fasteners of required dia and length as per drawing / specification, at all floors and all heights. |
| 70 | Ground floor |
| 71 | First floor |
| 72 | Providing and fixing 30 mm thick Flush Door shutters conforming to IS:2002 (Part I) decorative type, core of block board construction with frame of 1 st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both face of shutters inclusive of 4 Nos of Stainless steel Butt Hinges (100 mm x 60 mm x 2.5 mm) 40 mm stainless steel screws. Cylindrical Lock(Godrej-9843), Tower Bolt SS 10 x 300 mm(Bathroom)(Godrej 3264), PVC Door Buffer with SS Screw, teak wood lipping around the edges & paste with 1.5 mm thick laminate on both side of the flush door, etc. including the cost of all materials, hardware fittings, cost of all labour, conveyance, loading, unloading, T&P, etc, complete as per the direction of Engineer-in-charge. |
| 73 | Ground floor |
| 74 | First floor |
| 75 | Providing & fixing of Factory fabricated WINPLUS®Aluminium door Systems - For sliding door, made from 6063 alloy and T-6 temperedaluminium profile, in approved shade of hybrid /purepolyster surface coating (50-60micron Powder Coat), mechanically mitred & jointed with casted / aluminium extruded corner cleats along with Sliding window Flush Lock, Bearing Rollers , Siliconised Weather strip and 5mm ET 125 toughened glassasinfill shall be fitted into Shutter using siliconised microwave treated EPDM gaskets excluding taxes of all materials and cost of all labours required for the work etc. complete in all respect as desired by the Engineer in charge. |
| 76 | Ground floor |
| 77 | First floor |
| 78 | Supplying and installing uPVC- Casementopenable doors made out of lead free green profiles of KÖMMERLING make with a GREENLINE mark with frame dimension of 58mm x 69mm x 50mm for doorsand sash dimension ofsash dimensionof 58mm x 93mm x 54mm for doors with corners fusion welded, fully reinforced with Galvanized steel of 1.2 mm to 2 mm. The sash will be fitted with 6mm clear glass (toughened). The physical properties of the profiles like Vicat softening temperature, density, tensile strength, hardness, weatherability, impact strength and Modulus of Elasticity should be tested in accordance with ASTM/DIN-ISO standards and the thermal conductivity as per IS standards. The profile manufacturer should be a certified member of IGBC and should have extrusion facility in India and the windows to be assembled and installed by an authorised fabrication partner . The windows must be installed complete with all kinds of ironmongery (including EPDM gaskets,bridging wedges and glass packers) and with suitable water draining system. Application of Silicon sealant from Inside / Outside of Dowcorning / GE or equivalent. |
| 79 | Ground floor |
| 80 | First floor |
| 81 | Providing and fixing factory made 2 track 2 panel KOMMERLING uPVC white colour sliding window comprising of uPVC multi-chambered frame having section Frame 58mm x 49mm, Window sash: 37mm x 61mm, made out of lead free green profiles with corners fusion welded, fully reinforced with Galvanized steel 1.5/2.0 mm. The windows profile should fulfill the requirements of Viny 2010. The physical properties of the profiles like Vicat softening temperature, density, tensile strength, hardness, weatherability, impact strength and Modulus of Elasticity should be tested in accordance with ASTM/DIN-ISO standards and the thermal conductivity as per IS standards. The window comprising of uPVC extruded glazing beads of appropriate dimension, EPDM gasket, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size. The sash will be fitted with 5mm clear glass ( float ).complete in all respect as per specification and direction of the Engineer in Charge.etc. complete |
| 82 | Ground floor |
| 83 | First floor |
| 84 | Terrace floor |
| 85 | Supplying and Fixing of M.S. Grills, M.S.Doors, M.S. Gate etc including cost,conveyance of all materials,priming,and labour for fitting fixing etc.complete as per drawing / specification, at all floors and all heights andas per the instruction of Engineer-in-Charge. |
| 86 | Ground floor |
| 87 | First floor |
| 88 | Terrace floor |
| 89 | Priming one coat with wall cement primer (water bound) to make an even finished surface in all floors and heights to wall surface of approved make and shade including sand papering, applying putty wherever necessary & cost of scaffolding, staging charges with cost, conveyance, taxes of all materials, cost of all labour,labour cess T&P etc. complete as per the direction of the Engineer-in-charge. |
| 90 | Ground floor |
| 91 | First floor |
| 92 | Terrace floor |
| 93 | Painting two coats with approved anti-fungal weather seal paints (ISI) of approved colour, shade on wall surface over a coat of wall primer(ISI) water bound including sand papering, polishing the surface, cost, conveyances of all materials and cost of all labour,labour cess with T&P etc, complete as per specification & direction of Engineer-in-charge. |
| 94 | Ground floor |
| 95 | First floor |
| 96 | Terrace floor |
| 97 | Finishing plastered surfaces of walls with cement based wall putty (Water based) of approved make and finishing the surface smooth and even by sand papering to receive painting in walls, at all heights with staging wherever necessary with cost, conveyance, taxes of all materials, cost of all labour,labourcess, all T&P etc. required for the work complete in all respect as per the direction of the Engineer-in-charge. |
| 98 | Ground floor |
| 99 | First floor |
| 100 | Terrace floor |
| 101 | Painting two coats with approved plastic emulsion paintover a coat of wall primer of make Dulux / Berger / Asian to inside surface of walls finishedwith Acrylic Wall putty (water based) ofmake (Birla / JK) and finished smooth & even surface to receive painting using roller to the final coat including cost of scaffolding staging charges with cost, conveyances, taxes of all materials, cost of labour, T&P required for the work etc. complete for all floors as per specification & direction of the Engineer-in-charge. Note :- Sample of Paint & Primer shall be approved before procurement and use. |
| 102 | Ground floor |
| 103 | First floor |
| 104 | Terrace floor |
| 105 | Painting two coats with approved Enamel Paint on wood work over a coat of Wood Primer in Ground Floor |
| 106 | Ground floor |
| 107 | First floor |
| 108 | Painting two coats with approved Enamel Paint on Steel work in Ground Floor |
| 109 | Ground floor |
| 110 | First floor |
| 111 | Terrace floor |
| 112 | Supplying, fitting and fixing of Stainless steel of 304 grade in hand ralling using 50mm dia of 2mm thick circular pipe with Balustrade of size 32mm X 32mm X 2mm @ 0.90mtr. C/C and stainless square pipe bracing of size 32mm X 32mm X 2mm in 3 rows in stair case as per approved design and specification, buffing, polishing etc with cost, conveyance, taxes, all materials, labour, T&P etc. required for the complete in all respect. |
| 113 | Ground floor |
| 114 | First floor |
| 115 | 2.5 cm thick grading concrete (1:2:2) on roof slab with 6.7mm & down grades size hard granite crusher broken chips on new work in Ground Floor |
| 116 | First floor |
| 117 | Manufacturing, Providing and Installation of GFRC (Glass Fiber Reinforced Concrete) ,Make“SAMUDYAM”,GFRC Screen thickness 25 mm ±5 mm and border thickness of 40-50 mm with Pattern, design, and colour of approved make to be fixed on/between RCC /Block work Column or structural work with Dry Fixing method with appropriate frame work , using fasteners, and necessary hardware etc. in Building Façade. The element shall be made from \"53 grade\" Portland Cement make Birla/ \"JK Cement\" or equivalent, Quartz, Fine Silica Sand, Alkali Resistant Glass fibre make \"Owens Corning\" or equivalent, Super plasticizers / Additives make by \"BASF\" or equivalent, Polymers make \"BASF\" or equivalent and U.V resistant Synthetic inorganic pigments shall be used for pigmentation make \"BAYFERROX (Germany)\" or equivalent. The material casting shall take place in Synthetic Rubber / FRP Mould manufactured by Mould / Tool / Mould Grade Resin of Revex/ \"Reckli\" or equivalent. |
| 118 | Ground floor |
| 119 | First floor |
| 120 | Supply & apply of 1 Coat Weather coat exterior Primer (Alkali Guard-Anti efflorescent) + apply of Berger RUFF N’ TUFF TEXTURE ECO STANDARD-RAIN FALL FINISH + 2 coat of Weather coat Smooth Emulsion (approved shade) inclusive of All Accessories.(RUFF N’ TUFF (TROWL FINISH) ) |
| 121 | Ground floor |
| 122 | First floor |
| 123 | Surface preparation of roof slab - Clean the RCC slab surface & wall for treatment by removing dust, dirt and layers of concrete over the surface. Etc. by mechanical means. Drilling holes at construction joints and identify damaged/honeycombed/Crackof the concrete surface and sealing the same with polymer modified repair mortar or cement slurry admixed with SBR based bonding agent ReArm SBR 45. |
| 124 | Waterproofing Layer - Provide and apply 2 coats of acrylic based polymer modified water proofing coating UMof MYK Make as approved by the engineer-in-charge. It’s a two component elastomeric, seamless& flexible crack bridging waterproofing coating and apply over the prepared surface with two coat @ 2.0 kg/SQM with 1.2mm thick DFT. |
| 125 | Terrace floor |
| 126 | Carriage of excavated earth by mechanical means includiing cost of all and Complete. |
| 127 | Ground floor |
| 128 | Construction of embankment with approved material obtained from borrow pits with all lifts and leads, transporting to site by mechanical means within a lead of 5 KMs spreading, grading to required slope and compacting to meet requirement of table 300-2 & clause 305 of MoRT&H Specifications for Road & Bridge works (Latest Revision) including cost of royalty as per direction of the Engineer-in-charge. |
| 129 | Cleaning and grubbing road land including uprooting rank vegetation, grass, bushes, shrubs, saplings and trees girth up to 300mm, removal of stumps of trees cut earlier and disposal of unserviceable materials and stacking of serviceable materials to be used or auctioned, up to a lead of 1000 metres including removal and disposal of top organic soil not exceeding 150mm in thickness. |
| 130 | Loosening leveling & Comapcting minimum 150mm thick, levelling Compacting original ground supporting embankment to facilitate construction of earthen embankment, sprinkling water to OMC and compacting by rolling so as to achieve minimum required, density table 300-1, 300-2 in embankment construction as per technical specificationCl. 305.3.4of specification for road and bridge works MORT&H (5th revision) complete as per direction of Engineer-in-charge. |
| 131 | Providing and laying R.C.C M-25 grade in RCC drain as per approved drawing and technical specifications complete in all respect as per section 900, 1000, 1500, 1700, 2100 & 2200 of MoRT&H specifications for Road & Bride works (latest revision) & including cost & conveyance of all materials, labour, T&P, royalty etc complete and as per direction of Engineer-in-Charge. |
| 132 | A) Foundation |
| 133 | B)Sub-Structure |
| 134 | C) Super Structure |
| 135 | Supplying, mixing, providing laying and compacting graded stone aggregaresto Wet Mix Macadam (WMM) specification in approved layer thickness to line, level grade & slope as per approved working drawing and approved mix design conforming tograding specified in (Table 400-I3 ) & as per clause 406 of Technical specification for road and bridge works MORT&H (Latest revision) & as per direction of Engineer-in-charge. |
| 136 | Construction of granular sub-base by providing d Granular sub-base Grading-IV material as per table 400-1, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at OMC and compacting with vibratory roller to achieve the desired density complete as per Clause 401 of MoRT&H Specifications for Road & Bridge works (Latest Revision) as per direction of Engineer-in-charge. |
| 137 | Providing ,laying factory made 80 mm thick cement concrete interlocking paver blocks of M - 30 grade made by block making machine with strong vibratory compaction of approved size and shape laid over 50mm thick compacted bed of course sand layerincluding filling sand in the interstics/ joints,including cost conveyance of all materials, labour, and (T&P) required for the work etc comple and as per direction of Engineer in charge. |
| 138 | Construction of cement concrete kerb with top and bottom width 115 and 165 mm respectively, 250 mm high in M 20 grade PCC on M-10 grade foundation 150mm thick, foundation having 50mm projection beyond kerb stone, kerb stone laid with kerb laying machine, foundation concrete laid manually, all complete as per clause 408 |
| 139 | Painting two coats with any approved synthetic enamel paint of approved quality shade and make over a coat of priming to Road surface ncluding cost of the primer and paint,with cost, conveyance and taxes of all materials and labour with T&P required for the work etc. complete in all respect. |
| 140 | WALL PANELING WITH WOODEN SLAT HDF PLANK Supply & installation ofLower Reach wall paneling of slats surco high density fiberboard made out ofpure pinewood particles, Fire Resistance- Pink in colour core with5 test Fire Resistance BS 476 part 5 , BS 476 part 6 , BS 476 part 7 ISO 1182 ASTM E662 Smoke Density- Melamine laminated finish, perforated wooden grooved HDF slatsL16-2 (2 mm grooves @ 8 mm centers),tongue-groove edge for a seamless look of lineal dimension size 128 mm x 2440 mm x 16 mm thick having density 700 Kg /m3, weight -9 Kgs/m2 ,2mm Front Side Sound Abstroctor &1076 Distractor Holenonwoven acoustic to be pasted on slats surco is to be installed by using GI strut system. The technical parameters are as follows Core Variants - Fiberboard, Climate (OC RH) – 50, 70 Light reflectance – 75%,Green (RC %) – 25, Hygiene (VoC, Clean room) – Low, Class 1, NRC-0.85,Strength, Load capacity (Kg) - Anti sag, Ball-Impact.The concealed wall paneling system shall include GI Wall channel (WC25) having thickness 0.45mm, length 3600mm, unequal flanges of 15 & 20mm and web of 25mm should be fixed along the perimeters of the wall with nylon sleeves and suitable fasteners at every 300mm centers. Then fixed Main channels (MC45) having thickness 0.8mm, length 3600mm, equal flanges of 15mm and web 45mm from the side wall & fixed at every 1200mm centers with GI cross channel(CC25) having thickness 0.45mm, length 3600mm, knurled web 35mm, depth of 25mm and equal flanges 9.5mm is fastened to the Main channel in the direction perpendicular to the Main Channel at every 600mm centers. The framework will maintain 50 / 75 mm gap from the walls. Now clad the woodenslats surco on the CC 18 with the help of center & edge clips to get better locking of slats. The tongue & groove are to be properly aligned to get flush look . Synth poly fiber PF 5 x 50 wool of 500 gsm to be filled between the horizontal & vertical studs as in filler with the help of wire / stick 7 adhesive.5 Years Warreny Certificate & MTCshall be submitted after procurement of materials |
| 141 | WALL PANELING - FABRICSOAK CORD Supply & installation of Upper Reachpinewood wool magnesia bonded soak fabric cordbinary / Triangle design of selected colours (ref colour chart ) kerfs edge fabric wrapped ,pinewood fibers panels of size 600 X 600/ 1200 x 25 mm having density -400 Kg /m3 weight -10 Kg / mt 2 installed by using GI strut system. The GI strut works includes cross channels CC50 having thickness 0.45 mm , length 3600 knurled web 50, depth 50 mm & base 100 mm equal flanges of 13 mm is fastened to wall positioned horizontally in a regular manner at 600mm centers. PVC vinyl core UV treated H - spline having thickness 2 mm & length 2400 mm to be fixed or using Z bar or H splineon the back or edge of panels / tiles & similar on the back of channels perpendicular to the cross channels CC50at 600mm centers. Kerfed edge fabric wrapped factory panels shall be then inserting into the H - spline against wall to perfect fit. Panels shall be back lined with acoustical infill ofSynth PF 5 x 50 mm thick adhered to the wall using stick 7 adhesive. The technical parameters are as follows: core variant - pinewood fibers. Fire class 1 & P Acoustic - NRC 20 mm C10 - 0.75, Climate - OCRH - 50,90 Termite resistance - yes light reflectance - colour dependent, Green RC% - 10 , Hygiene ( Voc ,Clean Room ) - Low , Strength , Load Capacity ( Kg ) - Ball impact .5 Years Warreny Certificate & MTCshall be submitted after procurement of materials. |
| 142 | WALL PANELING STRETCH FABRIC NRC/HUSH GRAFICSupply and installation of Stretchable acoustical fabric NRC/HUSH GRAFIXfabric system by using FR Grade NRC /HUSH GRAFIX fabric of size 1700 mm width, shall be stretched by using wooden base 10 mm thick rigid vinyl stretch tracks half wrap/ full wrap 15 mm FS15 & mid seam 15 mm FS 15, 15 mm pinewood magnesia bonded Strand board, Synthetic poly fiber 5x50 infill with requisite accessories & tools. Pinewood wood based wool fiber having 15 mm thick square edge is first installed on the wall along the marking lines with metal fasteners inserted at 300 mm centers FS 15 tracks to be installed on wooden base after applying stick S7 adhesive on both surfaces for a true & continuous secure grip, & heavy - duty fasteners at 150 mm centers on both sides of stretch tracks. Pinewood wool panels having square edge Magnesite bonded pinewood fibers panels of size600 x 1200 x15 mm having density 400 Kg /m3 , weight 4 kg which is fixed to GI Channel CC25 on walls placed at 600 mm centersvertically / Horizontally with suitable fasteners with MC 45 at 1200 c/c & WC 25 is for supporting the main frame.. Synthetic poly fiber PF 5 x 50 mm thick adhered on strand tracks by following the fabric thread line or pattern. The fabric NRC is stretched & tucked into the stretch tracks & secure into the locking jaws so that it will be smooth, free of wrinkles with the tucking tools. Note - minimum 50 mm additional fabric is required for tucking hence maximum module wall fabric width would be 1600 mm The technical parameters of the system are core - pinewood fibre & polyfiber Fire - 1 Acoustic - NRC 0.85 Climate OCRH - 49, 90 Termite resistance - yes , light reflectance - colour dependant , Green RC % - 25 , Hygiene( Voc , Clean room ) - Low , Class 1. 3 Years Warreny Certificate & MTCshall be submitted after procurement of materials |
| 143 | MAGNESIA BOARD PLAIN CEILINGSupply and Installation of false ceiling 8 mm thick Tufbloc magnesium oxide HDFR boards of size 1200 x 2400 mm having Density-1000 kg/mt cube, with STC- 34 – 50, weight - 8.5 kg /sq mt, Fire Class - 1&P & Thermal Heat Resistance - 0.11792 W/mK Climate ( degree Centigrade , RH - 50,95 , Green VoC , RC% - Low & 30 Water resistant with wet expansion less than -0.02% from ambient to saturation, Moisture Movement - 0.02% from are to be fixed with Philips head screw is fixed by using concealed ceiling system. The concealed ceiling system shall include GI Wall channel(WC 25) having thickness 0.55 mm, length 3600 mm, unequal flanges of 15 & 20 mm and web of 22 mm should be fixed along the perimeters of the wall with nylon sleeves and suitable fasteners at every 300 mm centers. Then suspend Main channels(MC 45) having thickness 0.9 mm, length 3600 mm, equal flanges of 15 mm and web 45mm from the soffit at every 1200 mm centers with Suspender angle(SA 25) having thickness 0.45 mm, unequal flanges of 25 & 10 mm. GI Cross channel(CC 25) having thickness 0.45 mm, length 3600 mm, knurled web 35mm, depth of 25 mm and equal flanges 9.5 mm is fastened to the Main channel in the direction perpendicular to the Main Channel at every 600mm centers. Now the jointing & finishing of the same will be done by using Anutone jointing kit consist of powder mixed with water and apply the same with flat flap on the boards joints to finish the surface of the boards so as to look flush. Apply synthetic poly fiber PF 5 x 50 acoustic wool of 50 kg density to be kept on the top of the ceiling by laying on the framework. 5 Years Warreny Certificate & MTCshall be submitted after procurement of materials |
| 144 | GLASSFIBER TILES CEILING IN GRIDSUBTEX NUBBY STEP EDGESupply and Installation of 15 mm glassfiber steppe edge Glass fibre core ceiling tile of size 595 x 595 x 15mm having all edges encapsulated with chemical treated paint & having density 100-120 Kgs/ m3, weight 1.5 - 3.0 kg/m2 which is suspended by using 0.3mm thick and 15 mm wide pre coated metal T15/24 grid system. The technical parameters are as follows :Core - Glassfibre, Fire – Class 1 & P , Acoustics – NRC 0.95,Climate (OC RH) – 40, 95,Termite resistance ,Light reflectance – 85 %,Green (RC %) – 35, Hygiene (VoC, Clean room) – Low, Class 3 Strength, Load capacity (Kg) - Antisag. The T15/24Grid system of 600 x 600 mm module shall include wall angle(WA15) with unequal flanges of size 14 x 20 x3000mm wide, length 3000mm, 0.43 mm thick fixed along the perimeter of wall with the help of nylon sleeves and suitable fasteners at 300mm centers. Then suspend the Main T15(MT15W36) having flange width 15mm /24 mm , height32/38 mm and length 3600mm thickness 0.30 mm from the soffit with help of soffit cleat and wire at 1200mm c/c. Cross T15 (CT15W12) with flange width 15 mm, height 32 mm and length 1200 mm is then interlocked into the pre-cut slots in the Main T15 at 600mm centers in the direction perpendicular to the Main T15. Finally Cross T15 (CT15W06) having flange width 15 mm, height 32mm and length 600mm are then interlocked into the pre cut slots in the 1200 mm Cross T15 at 1200mm centers andin direction parallel to the Main T15.Subtex Nubby steppeedge of size 595 x 595 x 15mm thick shall be placed into the grid size of 600 x 600 mm. Ensure arrow marks behind subtex panels are orianted in one direction to achieve uniform shade.3 Years Warreny Certificate & MTCshall be submitted after procurement of materials |
| 145 | Woodend SPC FlooringProviding and Fixing of 5 mm thick Click-N-Lock tiles with wear layer is of 0.5 mm, made up ofSlsindia Stone Polymer composite and has an IXPE Cushion backing of 1 mm ,100% Water & Termite proof, Scratch / Fire / UV resistant, a Recyclable Green product having Slsindia LOCK click system with suitable skirting. Classification of abrasion resistance ( Rubbing action of two abrading wheels of S-42 Type , load Applied 500 grams, No. of Cycles 4,200).Design as approved by the Engineer |
| 146 | Chocolet King Bed 187.5 x 207.8 x 133.3Side Tabel 61 x 45.5 x52.953 Door Wordrobe132.1 x 54.8 x 191King size mattress with Pillow |
| 147 | Divine Sofa1 Seater 84 x 99 x 982 Seater 136 x 99 x 983 Seater 190 x 99 x 98 |
| 148 | Bloom Coffee Table |
| 149 | Rio Sofa 3 Seater77 x 84.5 x 81 |
| 150 | Alice Coffee Table 100 x 64 x 45 |
| 151 | Kareena Visitor Chair |
| 152 | Alice Coffee Table 100 x 64 x 45 |
| 153 | Satafe Dinning table 6 seater160 x 90 x 77Terrene Chair 45 x 50 x 90 |
| 154 | Chocolet King Bed 187.5 x 207.8 x 133.3Side Tabel 61 x 45.5 x52.953 Door Wordrobe132.1 x 54.8 x 191King size mattress with Pillow |
| 155 | Adirina Single Wooden Bed with Mattress Pillow113.1 x 206 x 94.5 |
| 156 | Rio Sofa 2 Seater132 x 84.5 x 81 |
| 157 | Gegacy Dinning Table 8 Srater178 x 90 x 76Echo Chair 45 x 45 x 105 |
| 158 | WOODY DINING TABLE 90 x 90 x 75PEBBLE CHAIR 82 X 58 X 86.5 |
| 159 | Divine Sofa2+2+32 Seater 136 x 99 x 983 Seater 190 x 99 x 98 |
| 160 | Bloom Coffee Table |
| 161 | Mingle_ MODULAR TAB |
| 162 | Ececutive Chairs for confernce Table |
| 163 | IMPRESSComprises of Main Desk , ERU + Pedestal 1800 x 900 x 750 |
| 164 | Kareena High Back Ececutive Chairs for Impress Table |
| 165 | Kareena ViSITOR Chair Ececutive Chairs for Impress Table |
| 166 | MAESTROComprises of Main Desk , ERU + Pedestal + Ruturn desk1800 x 900 x 750 |
| 167 | Kareena High Back Ececutive Chairs for Impress Table |
| 168 | Kareena ViSITOR Chair Ececutive Chairs for Impress Table |
| 169 | E.I WORKSub-Head I (modular Wiring Items)Recessed wirring tolight point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLSH/LSZHPVC insulated copper conductor of ISI markedMake- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI or equievalant reputed makeA catagory ISI marked as approved with 20 mm dia PVC flexible non metallic conduit FRLS , HMS type ISI markedMake-AKG/Anchor/Havells or equievalant reputed make A catagory ISI marked as approved 6A modular type (anti bactorial & flame retradant type)switch ISI marked Make-Schneider/legrand( Arteor) /Panasonic (vision) or equievalant reputed make & model A catagory ISI marked as approved, and ceiling rose ISI marked Make- Anchor/Havells of modular type G.I box with metallic cover plate (both side) (anti bactorial & falme retradant type) Make-Schneider(Zencelo)/legrand( Arteor) /Panasonic (vision)or equievalant reputed make & model A catagory ISI marked as approvedof suitable size, modular box with 1.5 sq. Mm FRLSHPVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. |
| 170 | GROUP-A |
| 171 | GROUP-B |
| 172 | GROUP-C |
| 173 | Group control of point in Recessed wirring tolight point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLSH/LSZHPVC insulated copper conductor of ISI markedMake-Make- Finolex/Anchor/Polycab/HAVELLSor equievalant reputed make A catagory ISI marked as approved as approved20 mm dia PVC flexible non metallic conduit FRLS,HMStype ISI markedMake-AKG/Anchor/Kinjal or equievalant reputed make A catagory ISI marked as approvedwith 6A modular type((anti bactorial & falme retradant type)) switch ISI markedMake-Schneider(Zencelo)/legrand( Arteor) /Panasonic (vision) or equievalant reputed make & model A catagory ISI marked as approved,and ceiling rose ISI markedMake-Schneider(Zencelo)/legrand( myrius) /Panasonic (Equievalant model) or equievalant reputed make & model A catagory ISI marked as approved of modular type G.I box withmetallic cover plate (both side)(anti bactorial & falme retradant type) Make-Schneider/legrand( Arteor) /Panasonic (vision)or equievalant reputed make & model A catagory ISI marked as approved, of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. CATAGORY AS FOLLOWS ,complete suitable for IPH standard hospital.(Maximum 02 nos point in one circuit). |
| 174 | Recessed wirring to group controllight point/ fan point call bell point with 1.5 sq.mm FRLSH/LSZHPVC insulated copper conductor of ISI markedMake- Finolex/Polycab/HAVELLS/RR KABLE/KEI or equievalant reputed makeA catagory ISI marked as approved with 20 mm dia PVC flexible non metallic conduit FRLS, HMS type ISI markedMake-AKG/Anchor/Havells or equievalant reputed make A catagory ISI marked as approved 6A Piano type ( flame retradant type)switch ISI marked Make-Havells/Schneider/legrand /Panasonic or equievalant reputed make & model A catagory ISI marked as approved, and ceiling rose ISI marked Make- Anchor/Havells of modular type G.I box with metallic cover plate (both side) ( flame retradant type) Make-Schneider/legrand) /Panasonic or equievalant reputed make & model A catagory ISI marked as approvedof suitable size, GI box with 1.5 sq. Mm FRLSHPVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. |
| 175 | Supplying ,fixing of 6A Plug on the same board in existing switch board with complete fitting by 01 no of 6A switch & socket (modular type)( (anti bactorial & flame retradant type)) & other required accessories of ISI marked as approved as per direction of Engg. -in -Charge. Make-Schneider(Zencelo)/legrand( Arteor) /Panasonic (vision) or equievalant reputed make & model A catagory ISI marked as approved, complete suitable for IPH standard hospital. (Maximum 02 nos point in one circuit). All the switches & sockets should be warrantied for a replacement period of 10 yearsagainstdefects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 176 | Supplying,fixing of 6A Plug on the separate board with complete fitting by 01 no of 6A switch & socket(modular type)( (anti bactorial & flame retradant type))with suitable size modular box & cover(anti bactorial & falme retradant type) including supplying of all requiredaccessoriesof ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Arteor) /Panasonic (vision) or equievalant make & model ISI marked as approved , complete suitable for IPH standard hospital.(Maximum 02 nos point in one circuit).All the switches & sockets should be warrantied for a period of 10 yearsagainst manufacturing defects against which ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 177 | Supplying,fixing of 1x16A Plug on the separate board with complete fitting by 01 no of 16A switch & socket(modular type)((anti bactorial & flame retradant type))with suitable size modular box & cover(anti bactorial & falme retradant type) including supplying of all requiredaccessoriesof ISI marked as approved as per direction of engg-in-charge.. Make-Schneider(Zencelo)/legrand( Arteor) /Panasonic (vision)or equievalant reputed make A catagory ISI marked as approved,(For equipement power)All the switches & sockets should be warrantied for a replacement period of 10 yearsagainstdefects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 178 | Supplying,fixing of 2x6A+1X1 6A Plug on the separate board with complete fitting by 01 no of 16A+2 no 6Aswitch & socket(modular type) ( (anti bactorial & flame retradant type) with suitable size modular box & metallic cover plate (both side)(anti bactorial & falme retradant type)including supplying of all requiredaccessoriesof ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Arteor) /Panasonic (vision)or equievalant reputed make & model A catagory ISI marked as approved, |
| 179 | Supplying,fixing of 3x6A+1X1 6A Plug on the separate board with complete fitting by 01 no of 16A+3 nos6Aswitch & socket(modular type) ( (anti bactorial & flame retradant type) with suitable size modular box & metallic cover plate (both side)(anti bactorial & falme retradant type)including supplying of all requiredaccessoriesof ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Arteor) /Panasonic (vision)or equievalant reputed make & model A catagory ISI marked as approved, |
| 180 | Receass wiring for circuit/submain wiring with the following mentioned size PVC FRLSH/LSZHinsulated, copper conductor, single core cable (Finolex/Polycab/ HAVELLS/RR KEBLE) or equievalant reputed make A catagory ISI marked as approved, inrecessed PVC conduit Heavy duty FRLS, HMStype of mentioned size (AKG/Anchor/Kinjal or equievalantISI marked as approved) as required as per direction of Engg.-in-Charge. Ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials |
| 181 | 2 nos single core 1.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor. In 20 mm dia non metallicheavy duty flexible conduit (LDB to LSB/LIGHT CKT)(2X1.5+1X1.5) |
| 182 | 2 nos single core 2.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallicheavy duty flexible conduit.(BDB to LSB/LIGHT CKT/5A PLUG/INVERTER POINT TO EACH QTR) (2X2.5+1X1.5) |
| 183 | 4 nos single core 2.5 sq. mm copper wire for phase and neutral and 02 nos of single core 2.5 sq. mm copper wire for earth continuty conductor .in 25 mm dia non metallicheavy duty flexible conduit(LDB to LSB/5A SOCKET) (4X2.5+2X2.5) |
| 184 | 2 nos single core 4 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallicheavy duty flexible conduit .(PDB to PSB/ GAYSER POINT/AC POINT/ROOM LIGHT CONTROL TO CORRIDOORPOINT/DG PANELESSENTIAL LOAD) (2X4+1X1.5) |
| 185 | 4 nos single core 4 sq. mm copper wire for phase and neutral and 02 nos of single core 2.5 sq. mm copper wire for earth continuty conductor in 32 mm dia non metallicheavy duty flexible conduit.(PDB to PSB/GAYSER. POINT/AC POINT/DG PANEL ACCL TO EACH QTRESSENTIAL LOAD) (4X4+2X2.5) |
| 186 | 2 nos single core 6 sq. mm copper wire for phase and neutral and 01 no of single core 2.5 sq. mm copper wire for earth continuty conductor in 25 mm dia non metallicheavy duty flexible conduit .(LFDB TO LBDB) (2X6+1X2.5) |
| 187 | 4 nos single core 6 sq. mm copper wire for phase and neutral and 02 nos of single core 2.5 sq. mm copper wire for earth continuty conductor in 32mm dia non metallicheavy duty flexible conduit.(LFDB TO LBDB/power unit/point) (4X6+2X2.5) |
| 188 | 4 nos single core 10 sq. mm copper wire for phase and neutral and 02 nos of single core 4 sq. mm copper wire for earth continuty conductorin 32 mm dia non metallicheavy duty flexible conduit .(LFDB TO FLOOR PANEL TO TPN BDB light ) (4X10+2X4) |
| 189 | Supplying and fixing 20 amps, 240 volts, SPN, industrial type socket outlet, with 2 pole and earth metal enclosed plug top along with 32 amps. C-series, SP MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket outlet, and complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge.. . Make-Legrand/Schneider/Siemens/panasonic or equievalant reputed make & model A catagory ISI marked as approved, |
| 190 | Supplying and fixing following size/ modules, GI box along with modular base & metallic cover plate (both side)(anti bactorial type) plate for modular switches in recess etc as required as per direction of Engg.-in-Charge. MAKE-Legrand/Siemens/Panasonic/ Schneider or equievalant reputed make & model A catagory ISI marked as approved .All the Components should be warrantied for a replacement period of 5 yearsagainstdefects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 191 | 4 moudle(125mmx75mm) |
| 192 | 1 moudle(75mmx75mm) |
| 193 | 12 moudle(200mmx150mm) |
| 194 | Supplying and fixing of following sizes of medium class PVC FRLS, HMS conduitISI marked along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required as per direction of Engg.-in-Charge .MAKE KINJAL/ AKG/Anchor or equievalant reputed make A catagory ISI marked as approved |
| 195 | 20 MM |
| 196 | 25 MM |
| 197 | Supply and fixingmodular type indicator on the existing switch box/cover . Equievalant higher model of Schneider/Hager/Siemens/Panasonicmake or equievalant reputed make & model A catagory ISI marked as approved as required as per direction of Engg.-in-Charge.All the Components should be warrantied for a replacement period of 5 yearsagainstdefects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 198 | Supplying and installation of AC starter Modular type, Equievalant higher model of Schneider/Hager/Siemens/Panasonicmake or equievalant reputed make & model A catagory ISI marked as approved coil voltage-415 Volt A.C. & O/L range of 9-14A range on mod Box of suitable size including modular coveras required as per direction of Engg.-in-Charge .All the Components should be warrantied for a replacement period of 5 yearsagainstdefects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 199 | Supply and fixingCALL bell (Ding dong type) /Buzzer on the existing switch box/cover. Equievalant higher model ofSchneider/Hager/Siemens/Panasonicmake or equievalant reputed make & model A catagory ISI marked as approved .as required as per direction of Engg.-in-Charge.All the Components should be warrantied for a replacement period of 5 yearsagainstdefects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 200 | S/F of Bakelite angle holder/batten holder (make-Anchor/Havells/Panasonic or equievalant reputed make A catagory ISI marked as approved )of ISI marked conforming to IS-1258/1987 in place of ceiling roseas per direction of Engg.-in-Charge .All the Components should be warrantied for a replacement period of 5 yearsagainstdefects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 201 | Supplying,fixing of Blanking plate(modular type)( (anti bactorial & flame retradant type))in existing switch box(anti bactorial & falme retradant type) including supplying of all requiredaccessoriesof ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Arteor) /Panasonic (vision), complete suitable for IPH standard hospital.Itshould be warrantied for a period of 10 yearsagainst manufacturing defects against which ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials. |
| 202 | Supplying,laying of 3cx2.5 sq.mm copper flexible cable with insulated cover of reputed make,ISI marked with all other concerned materials as per direction of Engg.-in-Charge. Ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials |
| 203 | Sub-Head II (Light fitting Fixture & Fan) |
| 204 | Supplying, installation, of exhaust fan of heavy duty 300 mm sweep(Make-Equievalant higher model with 5 star ratedof Havells/almonard/Usha or equievalant reputed make & model A catagory ISI marked as approved) of exhaust fan in the existing wall, including fixing & conntection as required as per direction of Engg.-in-Charge. Replacement Warranty will be 5 years. |
| 205 | Supplying, installation, of exhaust fan of heavy duty 380 mm sweep 1400 rpm with louvers Make-Equievalant higher model with 5 star ratedof Havells/almonard/Ushaor equievalant reputed make & model A catagory ISI marked as approved ) of exhaust fan in the existing wall, including fixing & conntection .as required as per direction of Engg.-in-Charge. Replacement Warranty will be 5 years. |
| 206 | Supplying, installation, testing and commssioning of 1400 mm sweep white/milky colour ceiling fan Make-Equievalant higher model with 5 star ratedof Havells/Almonard/Panasonic/Ushaor equievalant reputed make & model A catagory ISI marked as approved) including wiring the down rod of standard length (upto 30 cm) with 1.5 sq mm PVC insulated, copper conductor, single core cable etc. as required.(With fan Regulator) as required as per direction of Engg.-in-Charge.Replacement Warranty will be 5 years. |
| 207 | Supplying, installation, testing and commssioning of 1200 mm sweep white/milky colour ceiling fan Make-Equievalant higher model with 5 star ratedof Havells/almonard/Panasonic/Ushaor equievalant reputed make & model A catagory ISI marked as approved ) including wiring the down rod of standard length (upto 30 cm) with 1.5 sq mm PVC insulated, copper conductor, single core cable etc. as required as per direction of Engg.-in-Charge,Replacement Warranty will be 5 years.. .(With fan Regulator) |
| 208 | Supplying and fixing of Energy efficient surface mounted square shape 20 W LED luminaireof dimension of 225x 225 x 35 mm consists ofwhite powder coated , die-castAlluminiumhousingwith high quality frosted diffuser for glare-free uniform lighting distribution with wattage not more than 20 watt and lumen output of 1500 lumens, , CRI not lessthan 80,CCT of 6000 degree K,THD less than 10%, with electronic driver, internal surge protection of 2.5 KV , L70 B50: 30000 hrs (2 yrs warranty)and all other accessories suitable for operationon 220 V to 240 Vsupply as required as per direction of Engg.-in-Charge. ( Make : Panasonic /Trilux/Osram/PHILIPS/Wipro or equievalant reputed make & model A catagory ISI marked as approved).The luminaire should be Replacement Warranty will be 5 years |
| 209 | Supplying and fixing of Energy efficient recess mounted LED luminaire with white powder coated ,pressure die-cast Al housing ,with high transmititivity,non-yellowing PMMA diffuser, with wattage not more than 20watt and lumen output not less than 2600 Lumen ( 130 lumens/watt ) of size 595 x595 x 70 mm , ,CRI not lessthan 80,CCT of 5700-6500 degree K,THD less than 10%, with Non integrated isolateddriver (protects the output /secondary side from any disturbance on the input / primary side ensuring safe operation), all other accessories , life : 50,000 burning hours (5 years warranty) , Internal surge protection of 3 KV suitable for operationon 230 V, 50 Hz supply as required as per direction of Engg.-in-Charge. ( Make : Panasonic / similar modelofof LT /Wipro/PHILIPSor equievalant reputed make & model A catagory ISI marked as approved.) The luminaire should be Replacement Warranty will be 5 years. |
| 210 | SITC of energy efficient LED tube light fittings with decorative alluminiumbatten and LED tube light having power rating not more than 20 watt and lumen output not less than 2200 lumen complete with electronic driver and all other accessories withdiffuser having 5 years warrantyi/c connection etc as requiredas per direction of Engg.-in-Charge. (Similar to Panasonic /PHILIPS/LT/wipro or equievalant reputed make & model A catagory ISI marked as approved.). The luminaire should be Replacement Warranty will be 5 years . |
| 211 | SITC of Sleek LED 10 watt mirror light fitting with extruded polycarbonate housing,High optically efficient diffuser,above wash basin complete with all accessoriesetc. directly on wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required as per direction of Engg.-in-Charge.( Make : WIPRO / PHILIPS/Panasonicor equievalant reputed make & model A catagory ISI marked as approved. )The luminaire should be Replacement Warranty will be 5 years |
| 212 | Supply ,Installation testing commissioning of 45W, High efficient LED with aluminium housing in Pure Polyster UV resistant powder coated black finish and Top maintainable product with top opening die cast cover with acrylic clear glass reflector.CRI>70, IP66, Ambient temp-0 to 45DegC, Driver efficiency>85%, CCT-4000/5700K,THD<10%,Powerfactor>0.95, Surge protection-4 kV, Multistage Isolated Constant Current-Constant Voltage operated driver with range 150-300V AC and Safety Extra Low Voltage Safe level<60V DC as per IEC standard. Luminaire lumen = 4275 lumens (110 lm/W). Similar to Wipro Make or equivalent Philips/ LT/Trilux make. & model A catogory, ISI marked as approved, with proper model make having warrantied for a period of 5 years .The luminaire to be installed through moveable G.I braket as per the direction of Engg-in -charge. |
| 213 | Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as requiredas required as per direction of Engg.-in-Charge .(Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)of ISI mark as approved. |
| 214 | Supplying and fixing of Energy efficient Recess mounted LED luminaire made up of CRCA powder coatedsheet steel housingof 595 X 595 mm x 70 mmsize with of not more than25W and system lumens output not less than 3250lumens (120 lm/ wt)withdiffusers for better light transmission and pure effect with High luminous flux LEDs for better light output, CRI not less than 80, CCT of 5700-6500 degree K, THD less than 10%,internal surge protection of 3 KV,complete with Non integrated isolated electronic driver(protects the output /secondary side from any disturbance on the input / primary side ensuring safe operation)and all other accessories suitable for operation on140- 270 V, 50 Hz ,L70 @50,000 burning hrs (5 years warranty)supply .as required as per direction of Engg.-in-Charge (Make: Panasonicor similar modelofLT/Trilux /Philips/Wipro/jaquaror equievalant reputed make & model A catagory ISI marked as approved.) . The luminaire must be Replacement Warranty will be 5 years. |
| 215 | SITC of IP 20 Non-integral flexible LED strip light,High optically efficient diffuser,, 4000K with 12 w/mtr @ 5Mtrpool with Driver extra as required as per direction of Engg.-in-Charge ( Make : Panasonic/PHILIPS/Wipro/jaquar or equievalant reputed make & model A catagory ISI marked as approved. )The luminaire should be Replacement Warranty will be 5 years |
| 216 | Supplying and fixing of small focus light for small monuments as 30W , 5700 Krequired as per direction of Engg.-in-ChargeMake : Panasonic /PHILIPS/LT/WIPRO or equievalant reputed make & model A catagory ISI marked as approved.)The luminaire should be Replacement Warranty will be 5 years |
| 217 | BDBS,DB,AC DB,FLOOR PANELS,MCBS |
| 218 | Supplying and fixing of following mentionedway, three pole/single pole and neutral, sheet steel,double door MCB distribution board, 415 volts/240 volts shall be as per IEC 61439-3,integrated door earthing system offering additional safety to the user,High quality polyurethane Gasket,the box and cover shall be fabricated to withstand IK09,the DB should be properly pre-treated with 7 tank process and duly powder coated, phosphatized with powder coated finish, on surface/recess, complete with terminal blocks,with suitable size FR PVC insulated copper conducter up to terminal blocks, tinned copper busbar, neutral busbar, earth bar, din bar. Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/ /ABB(Equivalant model) or equievalant reputed make & model A catagory ISI marked as approved.as per direction of Engg.-in-Charge. The Distribution boardsshould be Replacement Warranty will be 5 years |
| 219 | 4 Way(8+12) Way TPN MCB DD DB Horizontal Type as per IEC 61439-3 suitable for Flush mounting and Surface mounting with 100A Copper Bus Bar for each phase, with neutral Bus bar, Earth Bar & Cable ties for cable management, prefitted masking sheet, IP43-IK09 with metal door(FOR LIGHT,POWER INDOOR,3-PH,POWER LOAD) Warranty on DB is 2 years. |
| 220 | Supply and fixing of 12 wayDD single pole and neutral sheet steel MCB distribution board 250V on surface/recess complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted including earthing etc. as required (but with out MCB/ RCCB/ Isolator) (ALL LIGHT WITHCORRIDOOR/COMMON AREA,EM LIGHT,UPS LOAD, EM LOAD LIGHT LOAD,POWER LOAD ) |
| 221 | 2+4 way MCB EnclosureDB (GLAZEDdoor)(only each EM. CONNECTION UPS LOAD) |
| 222 | Supplying and fixing 20 amps rating, 240 volts, C series, Double poles MCB of Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/L&T (Equievalant model)/ABB(Equivalant model) or equievalant reputed make & model A catagory ISI marked as approved in the existing MCB DB complete with connections as per direction of Engg.-in-Charge.The MCBshould be Replacement Warranty will be 5 years .MCB should have the fault indication system in different colour for ON, OFF & TRIP condition or Mid trip position for Trip conditions for easier identification of fault.Warranty on MCB is 5 years. |
| 223 | Supplying and fixing 6 amps to 32 amps rating, 240 volts, C series, single poles MCB of Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/L&T (Equievalant model)/ABB(Equivalant model)or equievalant reputed make & model A catagory ISI marked as approved.the existing MCB DB complete with connections as per direction of Engg.-in-Charge.The MCBshould be Replacement Warranty will be 5 years.MCB should have the fault indication system in different colour for ON, OFF & TRIP condition or Mid trip position for Trip conditions for easier identification of fault.Warranty on MCB is 5years. |
| 224 | Supplying and fixing 40 Amps rating, TPN, 415 volts, RCCB,300mA .Make-Equievalant highermodel ofLegrand/Snheider/Siemens / L&T/ABBor equievalant reputed make & model A catagory ISI marked as approved in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. .(4W TPN BDB IC)AC ODU CONTROLLER). TheRCCBshould be Replacement Warranty will be 5 years |
| 225 | Supplying and fixing 25Amps DP 240 volts, RCCB,300mA Make-Equievalant highermodel ofLegrand/Snheider/Siemens / L&T/ABBor equievalant reputed make & model A catagory ISI marked as approved in the existing MCB DBin the existing MCB DB complete with connections as per direction of Engg.-in-Charge.TheRCCBshould be Replacement Warranty will be 5 years |
| 226 | Supplying and fixing 40Amps DP 240 volts, RCCB,300mA Make-Equievalant highermodel ofLegrand/Snheider/Siemens / L&T/ABB or equievalant reputed make & model A catagory ISI marked as approved in the existing MCB DBin the existing MCB DB complete with connections as per direction of Engg.-in-Charge. TheRCCBshould be Replacement Warranty will be 5 years |
| 227 | Supplying and fixing 63Amps DP 240 volts, RCCB,300mA Make-Equievalant highermodel ofLegrand/Snheider/Siemens / L&T/ABBor equievalant reputed make & model A catagory ISI marked as approved in the existing MCB DB in the existing MCB DB complete with connections as per direction of Engg.-in-Charge.TheRCCBshould be Replacement Warranty will be 5 years |
| 228 | Supplying and fixing 63Amps TPN 415 volts, RCCB,300mA Make-Equievalant highermodel ofLegrand/Snheider/Siemens / L&T/ABB or equievalant reputed make & model A catagory ISI marked as approved in the existing MCB DBin the existing MCB DB complete with connections as per direction of Engg.-in-Charge.(for power BDB & AC ODU, 8 way TPN BDB IC).The RCCBshould be Replacement Warranty will be 5 years |
| 229 | (Earthing) INSTALLATION |
| 230 | S/IT/C Of Earthing with copper earth plate 600 mm x 600mm x 6 mm thick ISI marked including accessories and providing masonary with cover plate having loccking arrangement and watering pipe etc (WITHcharcoal and salt) as required as per direction of Engg.-in-Charge.The entire earthing systemshould be Replacement Warranty will be 5 years |
| 231 | S/IT/C of materials and installation of pipe earth electrode made out of 50mm dia class B G.I. pipe of 3.0 metre long with arrangements for fitting/ terminationofG.I. flat / wire withG. I. nutbolts& washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge.The entire earthing systemshould be Replacement Warranty will be 5 years |
| 232 | Providing and fixing 4 mm dia copper wire on surface or in recess for loop earthing as required.as per direction of Engg.-in-Charge. |
| 233 | Providing and fixing 25mm x 5mm copper strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. |
| 234 | Providing and fixing 50mm x 5mm copper strip on surface or in recess for connections including insulator etc. as required as per direction of Engg.-in-Charge. |
| 235 | Supplying and making brick massonary pedastal with extra super structure including cement plastering etc as required as per direction of Engg.-in-Charge. |
| 236 | CABLINGAND END TERMINATIONMAIN AREA |
| 237 | Supplying of one number PVC insulated armoured and PVC sheathed XLPE propertyAL. conductor power cable of 1.1 KV gradePOLYCAB/HAVELLS/Finolex or equievalant reputed make ISI marked as approved of following size cables as per direction of Engg.-in-Charge.Ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials |
| 238 | 3.5core x 240 sq mm ( TO MAIN PANEL)(02 runs) |
| 239 | 3.5core x 95 sq mm ( FOR DG 2 RUNS,FDB POWER 01 RUN ) |
| 240 | 4core x 16 sq mm (FDB LIGHT) |
| 241 | 4 core x 4 sq mm (for small power) |
| 242 | 3.5core x 35 sq mm (To FDB LIGHT / power BDB/UPS PANEL,separate panel) |
| 243 | LAYINGOF CABLE |
| 244 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kvgrade size not exceeding 25 SQ. MMdirect in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge. |
| 245 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kvgrade sizeexceeding 25 SQ. MMbut not exceeding 120 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge. |
| 246 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kvgrade sizeexceeding 120 SQ. MMbut not exceeding 400 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge. |
| 247 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kvgrade size not exceeding 25 SQ. MMdirect in ground in the EXISTING PIPE etc as required as per direction of Engg.-in -charge. |
| 248 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kvgrade sizeexceeding 25 SQ. MMbut not exceeding 400 SQ. MM direct in ground in the EXISTING PIPE etc as required as per direction of Engg.-in -charge. |
| 249 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kvgrade size not exceeding 25 SQ. MMin open duct etc as required as per direction of Engg.-in -charge. |
| 250 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kvgrade sizeexceeding 25 SQ. MMin open duct 400 SQ. MM direct in ground in the EXISTING PIPE etc as required as per direction of Engg.-in -charge. |
| 251 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kvgrade size not exceeding 25 SQ. MMin surface with shaddle and screw etc as required as per direction of Engg.-in -charge. |
| 252 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kvgrade size not exceeding 120 SQ. MM From 25 SQ. MM in surface with shaddle and screw etc as required as per direction of Engg.-in -charge. |
| 253 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kvgrade size not exceeding 400 SQ. MM From 120 SQ. MM in surface with shaddle and screw etc as required as per direction of Engg.-in -charge. |
| 254 | Supplying and making end termination with brass compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge. |
| 255 | 3.5 core x240 sq mm |
| 256 | 4 core x16sq mm |
| 257 | 3.5 core x35 sq mm |
| 258 | 3.5 core x95 sq mm |
| 259 | Providing,fixing and laying offollowing dia G.I. pipe (medium class) in ground complete with G.I fitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge. |
| 260 | 50 mm dia |
| 261 | Providing,fixing and laying of fallowing dia HDPE pipe (medium class) in ground complete withfitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge. |
| 262 | 200 mm dia |
| 263 | PANELS |
| 264 | MAIN CONTROLPANEL AT GF |
| 265 | S/I/T&Commissioning of LT indoor floor mounted cubical type electrical main panel (for both light and power circuit) made out by 2mm CRCA steel sheet duly derusted & painted by siemens gray powder cote paint is designed asG.A drawing as per direction of Engg.-in-Charge.Warrentee period of replacement of panel & accessoriesmust be 2 years & compelete test certificate must be submitted along with panel board including component list. |
| 266 | In commer-1-01 numberof 630A (400-630)4P Icu=100%Ics,0,LSIG MCCB with micro processor based release Electrical locking for normal & DG (make-ABB/Siemens/SCHNEIDER/L&T/Legrand, ISI marked) |
| 267 | In commer-2-01 numberof250A 4P Icu=100%Ics, 0LSIG MCCB with micro processor based release with adjustable overload from 36%-100% & Electrical locking for normal & DG (make-Siemens/SCHNEIDER/L&T/Legrand, ISI marked) along with 01 no of 250A 4P onload changeover switch (125 KVA DG 01 NO) |
| 268 | 01 set of Energy monitoring system with PLC |
| 269 | Busbar-1&2 04 numbers of 500Amps Aluminium busbar with 1A/SQ.MM current carring capacity. busbar duly sleeved by color coated PVC sleeve & supported by suitable size DMC insulator.(for outgoing) |
| 270 | Out going- 10 numbers of 63A 4P MCB (make- Legrandor equivalent reputed make ISI marked)BDB P/AC,(timer panel & water supply management,,FIRE,WTP,STP & GF POWER) |
| 271 | Out going- 2 numbers of125A 4P Icu=50%Ics, LSIG MCCB withTMR based release with adjustable overload(make- LEGRAND/Schneider/ABB/Siemens, ISI marked)(FLOOR RAW POWER PANEL ,SPARE,,AC ) |
| 272 | Out going- 2 numberof250A 4P Icu=50%Ics, LSIG MCCB withTMR based release with adjustable overload(make- LEGRAND/Schneider/ABB/Siemens, ISI marked)(APFC,FIRE,AC ) |
| 273 | Out going-6 numbers of 32A 4P MCB ((make-ABB/Siemens/SCHNEIDER/L&T/Legrand, ISI marked)(LIGHT SUPPLY) |
| 274 | Instrument- (i) 18 numbers phase indicating lamp with toggle switch & HRC fuse. |
| 275 | (ii) 05 set of digital type multifunction meter with CT for voltage,current,frequency,PF,THD indication with RS 485 COMPACTIVITY FOR bms data. |
| 276 | (iii)8 nos of 65kA SP VSD WITH 32A SP MCB |
| 277 | FDB POWER AT 1F |
| 278 | S/I/T&Commissioning of LT indoor floor mounted cubical type electrical main panel (for both light and power circuit) made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder cote paint is designed asG.A drawing. (FOR ALL MAIN CONNECTED LOAD) BUILDINGLIGHT)as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessoriesmust be 2 years & compelete test certificate must be submitted along with panel board including component list. |
| 279 | In commer-1 number of250A 4P Icu=50%Ics, LSIG MCCB withTMR based release with adjustable overload(make- LEGRAND/Schneider/Siemens, ISI marked) |
| 280 | Busbar- 04 numbers of250Amps,50kA Electrolytic copper busbar duly sleeved by color coded PVC sleeve & supported by suitable size DMC insulator. |
| 281 | Out going-6 numbers of 32A 4P MCB ((make-ABB/Siemens/SCHNEIDER/L&T/Legrand, ISI marked)(PwerSUPPLY) |
| 282 | Out going-4 numbers of 63A 4P MCB ((make-ABB/Siemens/SCHNEIDER/L&T/Legrand, ISI marked)(PwerSUPPLY) |
| 283 | Instrument- (i) 03 numbers phase indicating lamp with toggle switch & HRC fuse. |
| 284 | (ii)RS PORT MFM & CTS.(DIGITAL)(Sicure/L&T,CT-KAPPA or equievalant make & model) |
| 285 | (iii) 01 set of 0-500 voltmeter .(DIGITAL)(Sicure/L&T or equievalant make & model) |
| 286 | FDB UPS AT 1F |
| 287 | S/I/T&Commissioning of LT indoor floor mounted cubical type electrical main panel (for both light and power circuit) made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder cote paint is designed asG.A drawing. (FOR ALL MAIN CONNECTED LOAD) BUILDINGLIGHT)as per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessoriesmust be 2 years & compelete test certificate must be submitted along with panel board including component list. |
| 288 | In commer- 01 no 40 A 4P MCB 10kA,Cseries with on/off trip indication Light load for each floor. ( Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/L&T (Equievalant model) /ABB(Equivalant model)or equievalant make with proper model ISI marked) |
| 289 | Busbar- 05 numbers of 40Amps,50kA Electrolytic copper busbar duly sleeved by color coded PVC sleeve & supported by suitable size DMC insulator. |
| 290 | Out going-4 numbers of 32A 2P MCB ((make-ABB/Siemens/SCHNEIDER/L&T/Legrand, ISI marked)(LIGHT SUPPLY) |
| 291 | Instrument- (i) 03 numbers phase indicating lamp with toggle switch & HRC fuse. |
| 292 | (ii) RS PORT MFM & CTS.(DIGITAL)(Sicure/L&T,CT-KAPPA or equievalant make & model) |
| 293 | (iii) 01 set of 0-500 voltmeter .(DIGITAL)(Sicure/L&T or equievalant make & model) |
| 294 | 50KVAR APFC PANEL (Reactive power management) |
| 295 | S/I/T&Commissioning of LT indoor floor mounted cubical type electricalCapacitor bank panel of 50 KVAr APFC with 125A MCCB 3Pto be merge with main panel busbar as I/C, all branch protection is with MCB along with capacitor duty contactors, 7% Aluminium Reactor & Capacitor is with 480V AC MPP Technology (The capacitor should have over current withstand capability of 2.5xIn, Peak Inrush withstand capability of 350xIn, Number of Switching operation per year should not less than 15000 & the operating life should be min 200000 hrs) and designed asG.A drawing.s per direction of Engg.-in-Charge. Warrentee period of replacement of panel & accessoriesmust be withcompelete test certificate must be submitted along with panel board including component list.Make-Equievalant higher model of L&T/Schneider/Siemens/Legrand or equievalant reputed make with proper specification & model ISI marked as approved ) |
| 296 | CABLE TRAY /RACE WAY FOR DISTRIBUTION OF POWER |
| 297 | HOT DIPP GALVANIZED(GC) AS PER EN-ISO-1461 ,CARBON STEEL WIRE MESH CABLE TRAYS with internal dimensions ofsize 54mm(H) x 200mm(W),of Legrand - Cablofil make or equievalant reputed make & model A catogory, ISI marked as approved.The Load bearing capacity of the Cable Traysshould be minimum of104.8Kg/meter at the span of1.5Meter as per UL specifications.(With all accessories,bend,cover,supporter)WITH REQUIRED SIZED JUNCTION BOX ,COVER CONNECTORas required as per direction of Engg.-in-Charge. Warrentee period oftraymust be 5 years & compelete test certificate must be submitted . |
| 298 | HOT DIPP GALVANIZED(GC) AS PER EN-ISO-1461 ,CARBON STEEL WIRE MESH CABLE TRAYS with internal dimensions ofsize 54mm(H) x 300mm(W),of Legrand - Cablofil make or equievalant reputed make & model A catogory, ISI marked as approved.The Load bearing capacity of the Cable Traysshould be minimum of104.8Kg/meter at the span of1.5Meter as per UL specifications.(With all accessories,bend,cover,supporter)WITH REQUIRED SIZED JUNCTION BOX ,COVER CONNECTORas required as per direction of Engg.-in-Charge. Warrentee period oftraymust be 5 years & compelete test certificate must be submitted . |
| 299 | HOT DIPP GALVANIZED(GC) AS PER EN-ISO-1461 , FLOOR RACE WAY WITH JUNCTION with internal dimensions ofsize 34mm(H) x 225mm(W),of Legrand - Cablofil makeor equievalant reputed make ISI marked as approved.The Load bearing capacity of the Cable Traysshould be minimum of104.8Kg/meter at the span of1.5Meter as per UL specifications.(With all accessories,bend,cover,supporter)WITH REQUIRED SIZED JUNCTION BOX ,COVER CONNECTORas required as per direction of Engg.-in-Charge. |
| 300 | 8 PASSENGER LIFT WITH WIRRING |
| 301 | Design Supply, Installation, Testing & Commissioning and putting into operation with compelete inspection by concerned electrical inspector, Director Factory and Boilers, Odisha with proper testing certificate and final testing of Automatic Lift complete with all standard equipments accessories and control equipments as per Manufacturer\"s Design with lift control panel including BMS facility and as per BIS and fulfilling following requirements.It includes supply,laying of power cable and fixing of glands,lugs etc.( Machine room less, Gearless Type).Design and as per CPWD /OPWD specification (Part - III Lifts) 1981 with valid lisence for installation and fulfilling following requirements on turnkey basis as per direction of Engg.-in-Charge.LIFT OF machineroom less type(Make-Johnson/OTIS/Schindler/Thysenkrup or equievalant reputed make & model A catogory, ISI marked as approved )Warrentee period of accessories & system must be 5 years & compelete test certificate must be submitted along with Liftincluding component list . |
| 302 | Type:PASSENGERLIFT |
| 303 | Load: 8 PASSENGER(520 KG) |
| 304 | Speed: 1.0 Meter Per Second. |
| 305 | Control: Variable voltage with variable frequency |
| 306 | Operation:Microsprocessor based simplex collective selective with / without Lift Attendant. |
| 307 | Total Rise: About 9 Meters. |
| 308 | Landings: For All on same side. |
| 309 | Floors Served: GF,1F |
| 310 | Signals: Digital Car Position Indicator, Car Travel direction Indicator in Car & at all Landings. |
| 311 | Lift Shaft Size: About as 8 passengerlift standard, finished with Plaster. |
| 312 | Lift Car Size: Aboutlift standard. |
| 313 | Car Entrance: Clear Openinglift standard high Protected with Car Door. |
| 314 | Landing Entrance: Clear Openinglift standard high Protected with Landing Door. |
| 315 | Car Door: Stainless with front glass to transparentTwo Panel Center opening flush type.outer visible. |
| 316 | Landing Door: Mild Steel Two Panel Center opening flush type P. |
| 317 | Door Operation: Automatic Electric Power operated Door with in infrared protection. |
| 318 | Car Interior: Stainless Steel Panel with Hair line finish on all sides. |
| 319 | Car Floor: Hard Wood covered with PVC / Marblex Tiles. |
| 320 | Car Ceiling & Lighting: Fluorescent Lighting Concealed by suspended false ceiling with plain acrylic diffiuser. The frame of suspended false ceiling shall be of powder coated Aluminum. |
| 321 | Car Ventilation: Pressure Fan with anodized Aluminum Grill. |
| 322 | Emergencing Lighting in Car: Battery operated Emergencing Lighting in the Lift Car. |
| 323 | Intercom System: Battery operated intercom system in Lift Car and Control Room. |
| 324 | Emergencing Alarm: Battery operated Alarm Bell System in Lift Car and Control Room. |
| 325 | Position of Machine Room: Directly above the Lift Shaft. |
| 326 | Electric Power Supply: AC 415 Volt 3 Phase 50 Hz terminated in control room along with control panel with facility of BMS connectivity system .The scope of lift control panel is inclussive with lift vender scope. |
| 327 | OTHER SPECIAL PROVISIONS |
| 328 | • VVVF CONTROLLER |
| 329 | • AUTOMATICE RESCUE DEVICE (ARD) |
| 330 | • EMERGENCY LIGHT AND BATARY OPERATED ALARAM BELL |
| 331 | • DOT MATRICKX SEVEN SIGMENT DIGITAL POSITION INDICATORS |
| 332 | • FIRE RATED DOOR FOR 1 HOUR |
| 333 | • 3 WAY INTER COM/PRESS AND SPEAK BUTTON WITH HAND SET |
| 334 | • FLOOR ANNUNCIATOR WITH MUSIC |
| 335 | • INFRA RED SCREEN |
| 336 | • OVER LOAD WARNING INDICATOR |
| 337 | • BRAILLE BUTTONS |
| 338 | • FREE SERVICE FOR 5 YEARS |
| 339 | • PIT LADER |
| 340 | • FULL CAR HEIGH CAR FIXTURE ARRIVAL CHIME |
| 341 | • PROVISION FOR CC CEMARAWITH INSTRUEMENT |
| 342 | Fire Man Switch: Fire Man Switch at Main Landing Terminal. |
| 343 | 125 KVA DG |
| 344 | Supply, Transportation, erection, testing and commissioning of 3 Phase, 415V, 50Hz, water cooled multi cylinder diesel generator set with alternator of 125 KVA ( Make -Kirloskar / Jakson / sterling) out put contineous rating directly coupled Engine and Alternator with guard and mounted on a common base plate of Robust construction and complete with AMF panel having IP-52 protection, Acoustic Enclosure as per CPCB norms , sound absorbing material, to restrict sound level up to 75 dB up to 1 mtr distance and as per CPCB norms etc as per following specifications mentioned below.A. Alternator make : Kirloskar / Stamford /Leroy Somer /Caterpillar or equievalant reputed make & model ISI marked as approved as per direction of Engg.-in-Charge. Warrentee period of panel must be 5 years & compelete test certificate must be submitted along with DG set including component list & smoke exhaust system drawing,certified ISO 8528 |
| 345 | ALTERNATOR:The alternator of the output rating shall be 3 Phase, 415V, 50Hz, Ac , 0.8 P.F. lagging at 1500 RPM. The alternator is self excited, self regulated, and shall confirm to IS: 13364 of 1992 with regulation of +5% from no load to full load. degree of protections shall be IP21. |
| 346 | ENGINE:Diesel Engine make : Kirloskar / Cummins / Caterpillar / Perkins /Tata or equievalant make & model ISI arked as approved . Diesel Engine start, developing suitableBHP output at 1500 RPM with mechanical / electronic governing so as to enable the alternator to give 125 KVA continuous output at 0.8 P.F. lagging at NTP conditions. The diesel engine shall be capable of providing 10% O/L for 1 Hr for every 11 Hrs of continuous running at full load. The engine with 1st filling of oil and Diesel etc.01. Exhaust pipe of required size and length with insulation or clading.02. Diesel tank suitable for 8 to 12 Hours running capacity.03. Residential Silencer.04. SMF Batteries with leads as per the Manufacturer standards |
| 347 | AMF PANEL: Cubical, Compartmentalized, AMF Panel Baord with all Power & Control Contractors, Switches, Meters and other accessories, Internal Wiring, connection, inter-connection etc. for Trouble Free smooth function for 125 KVA DG Set complete with Battery Charger & leads as required. |
| 348 | BASE PLATE: Common Base Plate of required size for mounting of Engine Alternator Set fabricated from MS Channerl and vibration damping arrangement with cushy foor mounting including paintng etc. as required. |
| 349 | FOUNDATION: Suitable size Cement Concrete (1:2:4) foundation duly plastered and finished with neat coat Cement as required along withsmoke exhaust system piping including base frame of structure & lightening protection system. *It also includes 2 nos copper plate earthing for body and 2 nos copper plate earthing for neutral, control cable of 15mtr 2.5sqmm 6core , civil foundation work.(The Manufacturing of DG set shall not in any case be more than six months old from the date of award of work) |
| 350 | UPS SYSTEM (For CONF.& Common Area) |
| 351 | Supply ,installation ,testing & commissioning of10KVAUPS SYSTEM WITH suitable size battery bank, rated of battery ,IGBT based inverter system with inbuilt isolation transformer & automatic phase sicuency correctorof 3ph in put to 3 ph output,415V,protection for fault by OL,UV,EF,GF,OC,Ph. Sicuency release of A catogory, ISI marked as approved ) including supply of rack inverter stand with sufficient backup upto 30 minutes with all required accessories to complete the job including all connection.LOAD OF Conf. & common load) as per direction of Engg.-in-Charge. Compelete test certificate must be submitted along with upsincluding component list & SLD. Make-Rellio/Emerson/Numeric/Power one or equievalant. |
| 352 | EXTERNAL LIGHT SYSTEM |
| 353 | Supply ,Installation testing commissioning of elegant look Panasonic single arm by 1x 60 W LED street light having die cast aluminium housing with toughened glasshaving lumenoutput of 14500 or more (As per LM 79 report of third party NABL lab) ,IP 66 protection or more , LED street lightmodel will be vide Panasonic / Philips/LT/WIPRO or equievalant reputed make & model A catogory, ISI marked as approved, with proper model make having warrantied for a period of 5 years .The luminaire to be installed in 6 mtr long GI hot dip galvanized pole of Valmount/Transrail/RR/UTKASH /Utkal Galvanizer make equievalant make with proper model complete with SA bracket internal JB with 4 way connector and MCBas per the pole drawing and direction of EIC against which inspection mat take place.It should be installed after making proper size RCC foundation by considering RCC foundationby using M20 grade RCC & Fe 415 grade reinforcement and fixing the 4 nos. En 8 grade J type fdn bolts in the foundation. The luminaire needs to be wired with 3 c 1 sq mm wire from JB as per the direction of Engg-in -charge. |
| 354 | Supplying, Erection, Fixing, connection & testing of Panasonic 40 LED GATE Light of Panasonic / Philips/LT/WIPROor equievalant reputed make A catagoryISI marked as approved maintenance free having 2 years warrantyG.I P ipewith braket including MCB box & including with foundation as per the Drawing for inspection as required & as perdirection of Engg.-in-Charge. |
| 355 | Supplying ,installation & fixing of 11W(BOLLARD), High efficient LED with extruded Aluminium housing with PC diffuser.CRI>70, IP65, CCT - 6500K, Ambient temp-0 to 45DegC, Driver efficiency>80%,THD<25%, Powerfactor>0.9, Surge protection-2 kV, Multistage Isolated Constant Current-Constant Voltage driver and Safety Extra Low Voltage Safe level<60V DC as per IEC standard. Luminaire lumen = 565 lumens (51 lm/W). Similar to Wipro/ Bajaj/Philips/ LT/Trilux make. including with foundation as per the Drawing for inspection as required & as perdirection of Engg.-in-Charge. |
| 356 | Supply of materials and installation of pipe earth electrode made out of 50mm dia class B G.I. pipe of 3.0 metre long with arrangements for fitting/ terminationofG.I. flat / wire withG. I. nutbolts& washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge.The entire earthing systemshould be Replacement Warranty will be 5 years |
| 357 | Providing and fixing 4 mm dia copper wire on surface or in recess for loop earthing as required as per direction of Engg.-in-Charge. |
| 358 | Providing and fixing 25mm x 5 mm copper strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge. |
| 359 | CABLING |
| 360 | Supplying and laying of one number PVC insulated armoured and PVC sheathed XLPEAL. conductor power cable of 1.1 KV gradePOLYCAB/FINOLEX/HAVELLS or equievalant reputed ISI MARKED MAKE of following size cables as per direction of Engg.-in-Charge.Ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials |
| 361 | 3.5core x 35 sq mm |
| 362 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kvgrade size not exceeding 25 SQ. MMdirect in ground in the trench in one horizental formation including excavation ,sand coushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge. |
| 363 | Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kvgrade size not exceeding 120 SQ. MM From 25 SQ. MM in surface with shaddle and screw etc as required as per direction of Engg.-in -charge. |
| 364 | Supplying and making end termination with brass compression gland and aluminium lugs for following mentioned size cable.as per direction of Engg.-in-Charge. |
| 365 | 3.5 core x35sq mm |
| 366 | S/I/T&Commissioning of LT OUT DOOR FLOOR mounted cubical type MCB ENCLOSUREmade out by 2mm CRCA steel sheet duly derusted & pented by simens gray powder cote paint is designed asG.A drawing. (FOR USE) with 20A TPN MCB 01 NOLegrand/Schneider/L&T/ABB or equievalant make & model as per direction of Engg.-in-Charge. Ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period 2 years ofacceptance of materials |
| 367 | Supplying,laying of 3cx2.5 sq.mm copper flexible cable with insulated cover of reputed make,ISI marked with all other concerned materials as per direction of Engg.-in-Charge. Ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials |
| 368 | Providing,fixing and laying of fallowing dia HDPE pipe (medium class) in ground complete withfitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge. Ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials |
| 369 | 50 mm dia |
| 370 | S/I/T&Commissioning of LT OUT DOOR FLOOR mounted cubical type timer panel with 32A 4P MCB ,40A TP CONTACTOR ,TIMER with 15 nos 10A SP MCB C as per direction of Engg.-in-Charge. .(Equievalant modeleach item of Legrand/Schneider/L&T/ABB or equievalant make & model)Ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for 2 years after acceptance of materials. |
| 371 | FRONT ELEVATION DECORATION |
| 372 | Supplying and installation of flood light outdoor type luminaries incorporating aluminium Die Cast Housing body with powder coated , tempered glass cover 150W 30Degree Luminaire having Life of50000BH IP66, PF >.9 Working Temperature -10D to 45D, Cowl / Honeycomb louver (Make- Leksa/Canara Lighting/Havells/Wipro/Panasonic/Havells/Phiips or equievalant repute make ISI marked as approved and direction of Engg.-in.-charge). |
| 373 | Supplying and installation of flood light outdoor type luminaries incorporating aluminium Die Cast Housing body with powder coated , tempered glass cover 150W 10Degree Luminaire having Life of50000BH IP66, PF >.9 Working Temperature -10D to 45D, Cowl / Honeycomb louver availavle/DMX .(Make-Havells/Wipro/Bajaj/Canara lighting/Leks/Philips/Panasonic or equievalant repute make ISI marked as approved and direction of Engg.-in.-charge) . |
| 374 | Supplying and installation of flood light outdoor type luminaries incorporating RGB Linear Grazer Light / BeamAngle 10 deg X 60 Deg / 24W /IP66 IK08 / Aluminium Die-casting body with powder coated surface/tempered glass cover with Dark grey colour body finish.Make-Panasonicor equievalant repute make ISI marked as approved and direction of Engg.-in.-charge . |
| 375 | Supplying and installation of flood light outdoor type luminaries incorporating aluminium Die Cast Housing body with powder coated , tempered glass cover 24W 60Degree Luminaire having Life of50000BH IP66, PF >.9 Working Temperature -10D to 45D, Cowl / Honeycomb louver availavle/DMX.(Make-Wipro/Havells/Philips/Canara Lighing/Leksa/Panasonicor equievalant repute make ISI marked as approved and direction of Engg.-in.-charge) . |
| 376 | DC24V 200W LED Power Supply both for flood & linear light |
| 377 | Male & female Connectors |
| 378 | DMX Controller Online & Offline Master type |
| 379 | DMX Controller Online & Offline Slave type |
| 380 | AIR CONDITIONER |
| 381 | Supply of A,C with indoor and outdoor unit (Make- Hitachi/Carrier/Voltas/Toshiba or equivalent) |
| 382 | 1.5 TR high wall split A.C |
| 383 | 2 TR high wall split A.C |
| 384 | Supply,installation of hard/soft copper refregrant piping,complete with fitting of bends and other nesessary material to complete the job. |
| 385 | 1 TR to 2 TR high wall split A.C |
| 386 | Supply,installation & fabrication ofMS base frame for both indoor and outdoor unit and other nesessary material to complete the job. |
| 387 | 1 TR to 2 TR high wall split A.C |
| 388 | Supply,installation & fabrication ofInsulated drain water piping from indoor to nearestdrain point separate to alland other nesessary material to complete the job. |
| 389 | 25mm nom. Dia pipe,B1 |
| 390 | CONTROL CABLE |
| 391 | Supply,laying of control cableand other nesessary material to complete the job. |
| 392 | For 1 TR to 2 TR high wall split A.C |
| 393 | ON GRID SOLARSOLAR PV SYSTEM |
| 394 | Supply Installation Testing and Commissioning of on grid Solar Photovoltaic Power Plant conforming to MNRE specifications as amended, consisting of Mono Crystalline silicon solar cells, net metering facility ,necessary protections, earthing, mounted on Aluminium / GI structure of suitable strength with following components a complete aas arequired: a) Solar Photovoltaic Module of capacity 330Wp or above, manufactured in India, conforming to IS14286 / IEC61215, IS/IEC61730-Part-1,IS/IEC61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 16.5%. PV modules used in solar power plants /systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. b) Power Conditioning Unit (PCU) of 350-800 V DC Input voltage range and 400 V AC, three phase , 4 wire, 50Hz +/- 2.5Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree Celcious.The PCU shall adjust the voltage and frequency level to suit the Grid Voltage,frequency. c) Data Monitoring System complete with accessories.d)Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugsand other accessories etc. asarequired.e) Lightning and surge voltage protection. f) Connections & Interconnections by supplying & fixing required size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/ conduit lugs and other accessories etc. asrequired. with all required accessories as requiredas per the direction of Engg-in-charge.Make-JAKSON Solar/ LUME SOLAR/EMMVEE/ or equievalant reputed make & model A catogory, ISI marked as approved by MNRE. The entire SOLARsystemshould be Replacement Warranty will be 5 years |
| 395 | SOLAR WATER HEATING SYSTEM 100 LTR |
| 396 | Supplying,installation,testing and commissioning of 100LPD Solar Water Heating System Collector Type COPPER with Chrome Coated Total Space required for the Collector 82.64 M2 with all required accessories as requiredSpecification as attached ,tank 100 LPDSS-304, 5mm thickness with 100mm Insulation at testing 7.5 bar.FPC Collector each of 100 Ltrs 24Nos,Accessories ( Stand, Gasket, Welded Nipple, Hose pipe, Nut bolt, etc…500ltrsSS-304, 3mm thickness tank with PUF insulationat testing of 5bar & Stand,5Kw, Water dischargecapacity 415LPHas per the direction of Engg-in-charge .Make-Kamal Solar/ EMMVEE/ Venus /or equievalant reputed make & model A catogory, ISI marked as approved. |
| 397 | (LIGHTENING CONDUCTOR) |
| 398 | AIR TERMINAL & ACCESSORRIES LIGHTNING ARRESTER+ MAST: Providing and fixing of lightning conductor finial made of 25 mm dia, 3 x 300mm (=900mm) long, G.I tube,having single prong at top, with 85 mm dia 3 mm thick G.I base plate including holes etc complete as required with as per direction of Engg.-in-Charge.(RATE REFERING OSR 2018 SOR NO-4.2) .The entire LA systemshould be Replacement Warranty will be 5 years |
| 399 | Reveting, sweating and soldering of copper / G.I. tape ( with another copper / G.I. tape, base of the finial or any other metallic object) as required .as per direction of Engg.-in-Charge. (RATE REFERING OSR 2018 SOR NO-4.4) The entire LA systemshould be Replacement Warranty will be 5 years |
| 400 | Providing and fixing of G.I. tape 20 mm x 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For horizontal run) as per direction of Engg.-in-Charge.(RATE REFERING OSR 2018 SOR NO-4.7)The entire LA systemshould be Replacement Warranty will be 5 years |
| 401 | Providing and fixing of G.I. tape 20 mm x 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For virticalrun) as per direction of Engg.-in-Charge. (RATE REFERING OSR 2018 SOR NO-4.8) The entire LA systemshould be Replacement Warranty will be 5 years |
| 402 | Providing and fixing of testing joint, made of 20 mm x 3 mm thick G.I. strip, 125 long with 4 nos of G.I. bolts, check nuts and spring washer etc complete as required as per direction of Engg.-in-Charge. (RATE REFERING OSR 2018 SOR NO-4.12) The entire LA systemshould be Replacement Warranty will be 5 years |
| 403 | Providing and laying of G.I. tape 32 mm x 6 mm from earth electrode directly in ground as required as per direction of Engg.-in-Charge. .(RATE REFERING OSR 2018 SOR NO-4.14) The entire LA systemshould be Replacement Warranty will be 5 years |
| 404 | S/IT/C Of Earthing with copper earth plate 600 mm x 600mm x 6 mm thick ISI marked including accessories and providing masonary with cover plate having loccking arrangement and watering pipe etc (WITHcharcoal and salt) as required as per direction of Engg.-in-Charge.The entire earthing systemshould be Replacement Warranty will be 5 years |
| 405 | FIRE FIGHTING SYSTEM |
| 406 | Supplying, installation, testing and commissioning of Electric Motor DrivenPressurization Terrace Pump having discharge of 450 LPM at 35 MWC head complete with Pump Set, Electric Motorsuitable for operation on 415 V ,3 ph, 50 c/s AC supply , Base Frame , 2 no. pressure switch, 1 no. pressure gauges, 2 nos. Butterfly valves, 1 no. NRV asrequired |
| 407 | Supply, installation, testing and commissioning of Floor/Wall mounted sectionalised, front operated top entry dust and vermin proof M.V.Panel Boards suitable for operation at 415V, 3 phase, 4 wire, 50Hz distribution system fabricated out of 2.0 mm thick CRCA sheet, insulated busbar with heat shrinkable PVC sleeve, base frame, complete with all accessories including interconnections, earth bus etc as required comprising of.One (1)-63 Amp, 10 KA,TPN (Class-C) MCB with 3 Nos Phase indicating lamps with control fuse/ MCB,Digital Voltmeter with selector switch. DOL starter with O/L and Single Phasing Preventor suitable formotor. ON/OFF indication lamps, Auto manual switch and ON/OFF push button.One (1) - Set of Auxilliary relay for automatic operation through pressure switch. |
| 408 | PIPE & VALVES ETC.Supply,Installation,Testing & Commissioning of \"C\" Class heavy duty MS pipe (as per IS 1239 upto 150 mm NB and IS 3589 for above 150 mm 6.33mm thick) with flanges and fitting such as bends, tees, reducers, rubber insertions and galvanized nuts and bolts of following size on surface along wall / shaft with MS bracket, suspended from ceiling/ beam with suspenders duly painted with two coats of primer and finished with enamel paint of approved colour laid through pipe or in trench after wrapping with hassen cloth after applying coal tar primer as required as per direction of Engineer-in- charge. |
| 409 | 150mm NB |
| 410 | 100mm NB |
| 411 | 80mm NB |
| 412 | 65mm NB |
| 413 | 50mm NB |
| 414 | Supply,Testing & Commissioning of \"C\" Class heavy duty MS pipe (as per IS 1239 upto 150 mm NB and IS 3589 for above 150 mm 6mm thick) with flanges and fitting such as bends, tees, reducers, rubber insertions and galvanized nuts and bolts of following size including laying in ground after excavation and refilling of trench along with providing 4mm thick pipecoat for underground pipe after applying wrapping coating primer as required as per direction of Engineer-in- charge. |
| 415 | 150mm NB |
| 416 | Providing, fixing, testing and commissioning of following size manually operated hand lever type cast iron double flanged slim seal wafer type Butterfly valves with EPDM iron disc as per IS-13095 having pressure ratting PN -1.60 including fixing the same with supply of required jointing materials like rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of E.I.C. |
| 417 | 200mm NB |
| 418 | Providing, fitting & fixing of following size cast iron double flanged type dual plate Non return Valve as per IS- 5312 (Part 1): 2004 with ISI mark of pressure ratting PN-1.60 including fixing the same with supply of required jointing materials like flanges, rubber insertion, MS nuts & bolts, paint etc. and testing the joints with required water pressure etc. all complete as per specification & direction of Engineer-in-charge. |
| 419 | 150mm NB |
| 420 | Supply,Installation,Testing & Commissioning of orifice plate made of 6mm thick stainless steel with orifice of required size in between flane and landing valve of external and internal hydrant to reduce pressure to working pressure of 3.5 Kg/ sq cm complete as required. |
| 421 | Supply,Installation,Testing & Commissioning of Pressure gauge of 0-16 Kgf/sq.cm. range with cut-off bronze ball valves of suitable size with all accessories as per direction of Engineer-in-charge. |
| 422 | Supply,Installation,Testing & Commissioning of Pressure Switch with cut-off bronze ball valves with integral strainer & flare nut (mixed ends) of suitable size with all accessories as per direction of Engineer-in-charge. |
| 423 | Supply,Installation,Testing & Commissioning of stainless steel strainer fabricated out of 1.6 mm thick stainless steel sheet Y Stainer with 3 mm dia hloes with stainless steel flange as required. |
| 424 | 200mm NB |
| 425 | WET RISER CUM DOWN COMER SYSTEM |
| 426 | Supply,Installation,Testing & Commissioning of Stainless steel Hydrant Valve / Landing valve, of 63 mm NB size, type-A, single headed , oblique type, as per IS :5290/93 and as per direction of Engineer-in-charge. |
| 427 | Supply,Installation,Testing & Commissioning of SS short branch pipe with 63 mm male inlet and 19 mm outlet nozzle, as per IS:903 and as per direction of Engineer-in-charge. |
| 428 | Supply,Installation,Testing & Commissioning of 63 mm NB and 15meter long RRL Fire Hose fitted with63mm intstantaneous stainless steelmale & female SS coupling, complete by GI wire binding for Internal Hydrant as per direction of Engineer-in-charge. |
| 429 | Providing supply & fixing of MS Hose Box for of suitable size(750X600X250mm) to accomodate 2 nos. of 15/ 1 no of 30 mtr long fire hose and a branch pipe, wall mounted type as per direction of Engineer-in-charge. |
| 430 | Supply,Installation,Testing & Commissioning of Swinging pattern wall fixing first aid hose reel made from MS sheet and waterways and moving parts with rubber hose of 20 mm dia. and 30 mtrs. long with ABS(Plastic) shut-off nozzle as per IS: 444/IS: 12585 Type-I., complete with all accessories as per direction of Engineer-in-charge. |
| 431 | Providing, fitting and fixing of C.I. 25 MM single air relief valve with stop cock confirming to IS:14845/2000 with ISI mark for water works purpose including fixing the same with hydrant riser including testing & commissioning the system etc. all complete as per approved specification & direction of Engineer-in-charge. |
| 432 | EXTINGUISHER SYSTEM |
| 433 | Portable Fire Extinguisher System Supplying, installation, testing and commissioning of CO2 type Fire Extinguisher 4.5 kg capacity confirming to IS: 2878 made from ISI marked seamless cylinder confirming to IS: 7285, fitted with ISI marked controlled valve confirming to IS: 3224, high pressure 1mtr discharge hose & horn complete with initial gas charged with carrying handle & wall mounting bracket as per direction of Engineer-in-charge. |
| 434 | Supplying, installation, testing and commissioning of ABC type fire extinguishers of 6 kg capacity including cost of all material & labour etc complete. |
| 435 | Providing and fixing the signages \"Fire Exit, Fire Exit Arrow Down,Fire Exit Arrow Left,Fire Exit Arrow Right\" of 1.5in height letters in white with green back ground.The size of the board shall be 25cm x 15 cm and shall be fixed at the height of 2 mts |
| 436 | Supplying, installation, testing and commissioning of Mechanical Foam type 9 litre capacity Fire Extinguisher,ISI marked, IS: 10204, containing 540 ml AFFF liquid ISI marked, IS: 4989 Part II and a polyurethane coated CO2 Gas Cartridge, ISI marked, IS: 4947 complete with gunmetal union cap, nylon hose with plastic foam making branch and wall mounting bracket as per direction of Engineer-in-charge. |
| 437 | AUTOMATIC FIRE ALARMING SYSTEM |
| 438 | Supply, Installation, Testing & commissioning of Addressable Manual Call Point soft addressable type with in built fault isolator asrequired.(Make:Cooper/ Morley/ Edward/ Notifier/ Hochiki/ Siemens/ GST) |
| 439 | Supply, Installation, Testing & commissioning ofResponse Indicator complete as required.(Make:Cooper/ Morley/ Edward/ Notifier/ Hochiki/ Siemens/ GST) |
| 440 | Supply, Installation, Testing & commissioning ofAddressable Loop Powered Hooter cum Strobe (sound output of minimum 90db) cum strobe (strength of light 10cd) complete with inbuilt isolator as required. (Make:Cooper/ Morley/ Edward/ Notifier/ Hochiki/ Siemens/ GST) |
| 441 | Supply & Fixing of 2 core 1.5 sq.mm, multi strand, copper conductor, FRLS (Fire Retardent Low Smoke)-PVC insulated GI Screened Armoured cable with saddle and required accessories.& Power Cable. |
| 442 | (Lan System) |
| 443 | Supply & Laying of Cat6 23Awg UTP Cable, through existing conduit, Make: Legrand/Tyco/Honeywell/Schnieder |
| 444 | Supply & fixing of RJ-45Jack of Category 6 with Dual-port British-style Face plate 86x86 mm with Curveture and wall mount box Make: Legrand/Tyco/l/Honeywell/Schnieder |
| 445 | Supply & fixing of Cat6 24 Port Loaded Patch Panel: make:-Legrand/Tyco/Honeywell/Schnieder |
| 446 | Supply & Installation of Cat6 Factory crimpped moulded patchcord, 1mtr, Make : Legrand/Tyco/Honeywell/Schnieder |
| 447 | Supply & Installation of Cat6 Factory crimpped moulded patchcord, 2mtr. Make: Legrand/Tyco/Honeywell/Schnieder |
| 448 | Supply & Installation of 6F Single Mode Armoured FO Cable through existing conduit. Make: Legrand/ Tyco/ Honeywell/ Schnieder |
| 449 | Supply & Installation of 24 Port Rack Mount Loaded LIU including SM SC Adaptor and Pigtail. Make: Legrand/Tyco/Honeywell/Schnieder |
| 450 | Supply & Installation of 9U/500Wall Mount Rack with FAN, PDU, Cable manager and H/W Pkt. Make : Legarnd/Valrack/Retail |
| 451 | (IP-PBX System) |
| 452 | Supply & Installation of IP based PoE Phone with single lie Displaywith 2 Ethernet Port. Make: Grandstream/Panasonic/HikVision/Honeywell |
| 453 | Supply and installation of Grand Stream UCM-6302, IP PBX System support upto 1000Users and minimum8 concurrent calls, integrated 2 PSTN trunk FXO ports through External Gateway, 2 analog telephone FXS ports with lifeline capability and up to 50 SIP trunk accounts, Gigabit network ports with Integrates PoE, USB, SD card, Supports up to a 5-level IVR (Interactive Voice Response), Supports any SIP video endpoint that uses the H.264, H.263 or H.263+ codecs |
| 454 | (IP-CCTV System) |
| 455 | Supply & Installation of 5Megapixel H.265 Vendal Proof Mini Dome Camera with build in audio. Support microSD/SDHC/SDXC Card Local Storage, up to 256G. BLC, HLC, 2D DNR, 3D DNR, Defog, AWB, EIS, IP Address Filtering, AGC, Anti-flicker, Corridor Mode, Deblur, Watermark. SIP/VoIP Support Yes, Voice & Video-over-IPEvent Trigger Motion Detection, Network Disconnection, Audio Alarm, etc.Motion Detection, Network Disconnection, External Input, Audio Alarm, etc. (Multi-interface Version).Event ActionFTP Upload, SMTP Upload, SD Card Record, SIP Phone, HTTP Notification, etc.;FTP Upload, SMTP Upload, SD Card Record, External Output, SIP Phone, HTTP Notification, etc. (Multi-interface Version) Video Analysis Region Entrance, Region Exiting, Advanced Motion Detection, Tamper Detection, Line Crossing, Loitering, Human Detection, People Counting, Object Left, Object RemovedSystem Compatibility ONVIF Profile G & Q & S & T, API Model No. MS-C5373-PB. Make: Milesight/Grandstream/HikVision/Honeywell |
| 456 | Supply & Installation of 5Megapixel H.265 Vendal Proof Mini Bullet Camera. Support microSD/SDHC/SDXC Card Local Storage, up to 256G. BLC, HLC, 2D DNR, 3D DNR, Defog, AWB, EIS, IP Address Filtering, AGC, Anti-flicker, Corridor Mode, Deblur, Watermark. SIP/VoIP Support Yes, Voice & Video-over-IPEvent Trigger Motion Detection, Network Disconnection, Audio Alarm, etc.Motion Detection, Network Disconnection, External Input, Audio Alarm, etc. (Multi-interface Version).Event ActionFTP Upload, SMTP Upload, SD Card Record, SIP Phone, HTTP Notification, etc.;FTP Upload, SMTP Upload, SD Card Record, External Output, SIP Phone, HTTP Notification, etc. (Multi-interface Version) Video Analysis Region Entrance, Region Exiting, Advanced Motion Detection, Tamper Detection, Line Crossing, Loitering, Human Detection, People Counting, Object Left, Object RemovedSystem Compatibility ONVIF Profile G & Q & S & T, API Model No. MS-C5373-PB. Make: Milesight/Grandstream/HikVision/Honeywell |
| 457 | Supply & Installation of 32 Chanel 4K H.265 Pro NVR with support 8*SATA HDD(upto 10TB each), RAID0, RAID1, RAID5, RAID6, RAID10 support. Video Compression H.265 +/H.265(HEVC)/H.264+/H.264. Audio Compression G.711/AAC/G.722/G.726Sample Rate 8KHz/16KHz Storage SATA 8*SATA HDD (3.5”) eSATA 1*eSATA Capacity Up to 10TB capacity for each HDD,Disk Array Array Type RAID0, RAID1, RAID5, RAID6, RAID10,Recording. Management Recording Type Continuous, Event (Motion Detection, Alarm, VCA, Smart Analysis)Snapshot Type Continuous, Event (Motion Detection, Alarm, VCA, Smart Analysis) Playback Type General Playback, Event Playback, Tag Playback, Split Playback, Picture Playback,Backup Backup Video Backup, Image Backup.Network Protocol IPv4/IPv6, TCP, UDP, RTP, RTSP, RTCP, HTTP, HTTPS, DNS, DDNS, DHCP, NTP, SNTP, SMTP, SNMP, UPnP, NFS. External InterfaceNetwork Interface 2*RJ45 10/100/1000Mbps Serial Interface 1*RS-485 Series Port for PTZ. 1*RS-232 Series Port for Console 1*RS-485 Series Port for Keyboard. USB Interface 1*USB 3.0; 2*USB 2.0. Audio Input/Output 1*RCA/2*RCAAlarm Input/Output 16-CH/4-CHModel No. MS-N8032-UH. Make: Milesight/Grandstream |
| 458 | Supply & Installation of Surveliance 8 TB HDD. Make:- WD, Segate/HikVision/Honeywell |
| 459 | Supply & Installation of 55\" IPS Ultra HD AI ThinQ TV Make: LG/Samsung/Panasonic |
| 460 | (AUDIO VISUAL SYSTEM) |
| 461 | Supplying, installation, testing & commissioning of 6 zone,voice alarm controller with USB, MP3 player (including 6 zone button paging station) with seamless integration facility with main fire alarm panel for voice evacuation complete as required |
| 462 | Supplying, installation, testing & commissioning of digital audio amplifier 600 Watt, 25V rms operating at 240 Volt AC Supply complete as required. |
| 463 | Supplying, installation, testing & commissioning of ceiling/wall mounted loud speaker, 3/15 Watt in ABS enclosure complete as required |
| 464 | Supplying and drawing of speaker cable Single pair, 2-core, 1.5 sqmmin existing conduits |
| 465 | (SINAGE SYSTEM) |
| 466 | Supplying, installation, testing & commissioning of digital signage ar per direction of Engg. In charge. |
| 467 | P.H WORKSupplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor PVC pipes conforming to ASTM-D-1785/89 of the following nominal bore, tube fittings and clamps including making the wall good. ceiling and floor, testing all complete as per specification and direction of the Engineer in charge.(Oriplast/Supreme/Finolex) |
| 468 | 20mm dia PVC ASTM pipe (sch-80) |
| 469 | Ground floor |
| 470 | First Floor |
| 471 | 25mm dia PVC ASTM pipe (sch-80) |
| 472 | Ground floor (Water Supply) |
| 473 | First Floor |
| 474 | 32mm dia PVC ASTM pipe (sch-80) |
| 475 | Ground floor |
| 476 | First Floor |
| 477 | 40mm dia PVC ASTM pipe (sch-80) |
| 478 | 50mm dia PVC ASTM pipe (sch-80)top floor |
| 479 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes conforming to IS:15778, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge |
| 480 | 20mm dia C - PVC pipe |
| 481 | Ground floor |
| 482 | First Floor |
| 483 | Supplying all materials, labour T&P and fitting and fixing brass/CP fittings of the following nominal bore with supply of all joiniting materialsincluding cost & conveyance of all materials to worksite, payment oftaxes etc. allcomplete as per P.H specification and direction of the Engineer-in-charge. |
| 484 | 15mm dia CP angle stop cock(FLR-ACR-5053N) |
| 485 | 15mm dia CP two way bib cock(FLR-CHR-5041N) |
| 486 | 15 mm dia CP S.B. Bib cock(CON-CHR-037KN) |
| 487 | 15 mm dia CP L.B. Bib cock(CON-CHR-107KN) |
| 488 | 15mm dia CP Pillar Cock (FLR-ACR-5015) |
| 489 | WALL MIXER WITH PROVISION FOR OVERHEAD Shower (FLR-ABR-5273UPR) |
| 490 | 20mm dia CP Con. stop cock (CON-CHR-089KN) |
| 491 | 25mm dia brassfull way valve (Shakti make) |
| 492 | 32mm dia brassfull way valve (Shakti make) |
| 493 | 40mm dia brassfull way valve (Shakti make) |
| 494 | 50mm dia brassfull way Valve (Shakti make) |
| 495 | 15mm dia CP Health faucet (Con-ALD-MCH-573 Jaquar make) |
| 496 | 15mm CP Extension piece |
| 497 | 125mm CP grating |
| 498 | 15mm size C.P. flange |
| 499 | Supplying all materials , labour, T&P and fixing rotational mouldedpolyethylene cylindrical vertical water storage tanks conforming to IS:12701/1996 including cutting holes through the tank and fixing mild steel tubes and fittings and providing extra sockets and jam nuts, fixing ball valve etc. including hoisting upto a height of 5 metres above ground level and placing the tank to the required position and providing 5.40 mtr. lengthx0.25 mtr widthKBbrickwork in cement mortar (1:6) of 0.46m height in staging and 0.13mtr thick circular protection wall of 0.46mtr height to support the tank,12mm thick cement plaster in cement mortar (1:6) over brick work, RCC slab of size 1.60mX1.60m and 0.10m thick ,RCC beam of 0.25mx0.30m and 3.40m average length in cement concrete (1:2:4) using 12mm size crusher broken hard black granite chips and required steel reinforcement including centering and shuttering,watering,curing ,cost of all materials,conveyance of all materials to worksite , payment of royalty, all taxesetc.all complete as per approved drawing , P.H. specification and direction ofEngineer-in-charge.(10 no. Tank for Fire Fighting & 4 nos. Tank for Residential Use) |
| 500 | 2000 liters capacityPVC water storage tank top of 1st floor |
| 501 | supplying all materials, labour, T&P and cutting holes through existing brick work including making good the damages in cement mortar (1:4) for taking G.I. Pipes and fittings/ P.V.C. pipes and fittings including watering, curing, cost & conveyance of all materials to worksite,payment of royality, taxes etc. all complete as perdirection ofEngineer-in-charge. |
| 502 | Ground floor |
| 503 | First Floor |
| 504 | Supplying all materials , labour, T&P and cutting holes in RCC floors and roofs upto 19cm thick for passing P.V.C pipes and G.I fittings etc. , and repairing the holes after insertion of pipe etc. with cement concrete (1:2:4) including finishing complete so as to make it leak-proofas per P.H. specification and direction of Engineer-in-charge |
| 505 | Ground floor |
| 506 | First Floor |
| 507 | Supplying all materials, labour, T&P and cutting grooves in pucca floors and walls for taking G.I./P.V.C. pipes and making good the damagesincluding watering ,curing , cost & conveyance of all materials to worksite, payment of royality, taxes etc all complete as per direction of the Engineer-in-charge. |
| 508 | Ground floor |
| 509 | First Floor |
| 510 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer\"s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches , cost & conveyance of all materials to worksite, payment oftaxes etc.all complete as per P.H specification and direction of the Engineer-in-charge. |
| 511 | 110mm U-PVC SWR Pipe (Supreme/Ashirvad) |
| 512 | 110mm U-PVC‘P’ Trap(Ori Plast/Finolex/Supreme Make) |
| 513 | 110mm U-PVC door bend(Ori Plast/Finolex/Supreme Make) |
| 514 | 110mm U-PVC Plain tee(Ori Plast/Finolex/Supreme Make) |
| 515 | 110mm U-PVC offset without ear(Ori Plast/Finolex/Supreme Make) |
| 516 | 100mm U-PVC Cowl(Ori Plast/Finolex/Supreme Make) |
| 517 | 110mm U-PVC S/Jn door(Ori Plast/Finolex/Supreme Make) |
| 518 | 110mm U-PVC D/Jn door(Ori Plast/Finolex/Supreme Make) |
| 519 | 110mm U-PVC Socket(Ori Plast/Finolex/Supreme Make) |
| 520 | Supplying all materials, labour, T&P and fixing vitreous china water closet, squatting pan (Indian type W.C pan/Orissa pattern squatting pan) duly embedded in cement concrete (1:5:10) using 4cm size hard granite metal including fixing a pair of vitreous china 250mm x 130mm x30mm footrest, fixing 100mm dia HCI \"p\" or \"s\" trap (with/without 50mm dia horn) for water colset squatting pan including jointing the trap with pan in cement mortar (1:1) cutting the floor and mending good the damages , cost & conveyance of all materials to worksite, payment of royality , taxes etc. all complete as per P.H specification and direction of the Engineer-in-charge. |
| 521 | 580mm size Orissa pan (Hindware/Parryware/Neycer make) |
| 522 | Supplying all materials, labour, T&P and fixing the following vitreous china Wash Down Water Closet(European type W.C pan) with integral ‘P’or ‘S’ trap to the floor with wooden plug and chromium plated pedestal screws including jointing the trap with soil pipe in cement mortar (1:1), fixing plastic seat and cover for wash down water closet with chromium plated brass hinges and rubber buffers including polishing etc all complete as per specification and direction of the Engineer in charge.One piece commod(Hindware)ELEMENT Cat No.92084. |
| 523 | Supplying all materials, labour, T&P and fixing the following vitreous china Wash Down Water Closet(European type W.C. pan)with integral \"p\" or \"s\" trap to the floor with wooden plug and chromium plated pedestal screws including jointing the trap with soil pipe in cement mortar (1:1) fixing plastic seat and cover for wash down water closet with chromium plated brass hinges and rubber buffers including polishing , cost & conveyance of all materials to worksite, payment of royality, taxes etc. all complete as per P.H specification and direction of the Engineer-in-charge |
| 524 | European water closet with ‘S’ trap plain (Hindware)No.20040 |
| 525 | Supplying all materials, labour T&P and and fixing 12.50 liters/10 liters capacity low level flushing cistern with a pair of cast iron or M.S. brackets complete with fittings such as siphonic arrangements 15mm nominal size brass/pvc ball valve with polythene float CP brass handle,unions and couplings for connection with inlet, outlet and overflow pipes, 32mm dia CP long flush bend, 15mm dia pvc inlet connection pipe including cutting holes and making good the same and connecting the flush bend with cistern and closet and connceting the inlet pipe with suupply main , cost & conveyance of all materials to worksite, payment oftaxes etc. all complete as perP.H specification and direction of the Engineer-in-charge |
| 526 | 10 ltr. Capacity pvc L.L. cistern with 32mm. Dia CP long flush bend ( Slimline-white-Parryware make ) |
| 527 | Supplying all materials, labour T&P and fixing wash basins with hole for pillar taps with cast iron or M.S.brackets painted white including cutting holes in walls and making good the damages with supply of wooden plugs, screws and cement etc, fixing pedestal for wash basin recessed at the back for the reception of pipes and fittings, fixing PVC waste pipe of 32mm nominal diameter for wash basin including brass check nut complete, fixing pillar taps capstan head screw down high pressure lettered \"Hot\" and \"Cold\" with long screws, shanks and back nuts of 15mm dia nominal bore, fixing 15mm dia PVC inlet connection pipe and making connection with pillar cocks and supply mains for wash basin, fixing 32mm dia CP brass waste, cost & conveyance of all materials to worksite, payment oftaxes etc. all complete as perP.H specification and direction of the Engineer-in-charge |
| 528 | Wash Basin Counter Top Hindware(Cat No.91008) |
| 529 | 550mmx400mm W.H.basin (Hindware/Parryware/Neycer make)with 15mm dia C.P.pillar cock (Jaquar make) with PEDESTRAL |
| 530 | Supplying all materials, labour, T&P for fitting & fixing Kitchen sink of all standard sizes with a pair of bracket, C.P. waste, trap & P.V.C. waste pipe & painting brackets including supply of cement concrete & mortar etc. all complete. 24” x 18” x 10” sink of nirali make. |
| 531 | Supplying all materials, labour, T&P and fixing standard sized CP towel rail complete with CP brass brackets fixed to wooden plugs with CP screws as per specification and direction of the Engineer in charge |
| 532 | 25mm x 600mm long CP towel rail(Jaquar)ACN-ACR-1111N |
| 533 | CP towel Ring(Jaquar)ACN-ACR-1121N |
| 534 | Supplying all materials, labour, T&P and fixing standard sized glass-shelf with CP brass brackets and guard rail complete fixed to wooden plugs with CP screws as per specification and direction of Engineer in charge. |
| 535 | 600 x 125mm plate glass shelf with CP guard rails(Jaquar)AKP-CHR-35771P |
| 536 | Supplying all materials, labour, T&P and fixing mirror of superior glass mounted on 6mm.thick A.C. sheet or ply wood sheet and fixed to wooden plugs with CP screws and washers complete as per specification and direction of Engineer in charge. |
| 537 | 600mmx450mm size B.E mirror (swivelled type) |
| 538 | Design Large Mirror.14 .00mtx0.90m x 0.90mt = |
| 539 | Supplying all materials, labour, T&P and fixing CP soap holder complete with CP brass brackets fixed to wooden plugs with CP screws as per specification and direction of the Engineer in charge |
| 540 | CP soap holder (Jaquar)ACN-ACR-1131N |
| 541 | Elena prime manual 10 ltr gyser (Jaguar make) EPM-WHT-V010 |
| 542 | Supplying all materials labor T&P & Fitting & fixing CP shower with rim with supply of red lead and yarn nail complete as per direction of Engineer in charge. |
| 543 | 15mm CP revolving shower (Jaquar)CON-CHR-209KN |
| 544 | Supplying all materials , labour, T&P and cutting holes through existing brickor laterite masonry wall for takingU-PVC pipes and fittings including making good the damages etc. all complete as per P.H. specification and direction of Engineer-in-charge |
| 545 | Supplying all materials , labour, T&P and cutting of RCC chajja for taking HCI or U-PVC pipe and fittings including making good the damages etc. all complete as per P.H. specification and direction of Engineer-in-charge |
| 546 | Supplying all materials labour T&P filling sand in lavatories well watered and rammed including lead of materials to work site. |
| 547 | Ground floor61.83 sqm x 0.10 mt = |
| 548 | Supplying all materials, labour, T&P and providing cement concrete ( 1:2:4 ) with 12mm size crusher broken hard black granite chips including watering, curing,cost of all materials, conveyance of all materials to work site with payment of royalty, all taxes etc all complete as per P.W.D specification and direction of Engineer-in-charge |
| 549 | Ground floor61.83 sqm x 0.10 mt = |
| 550 | First Floor66.08sqm x 0.10mt = |
| 551 | Supplying the waterproofing material Pidifin 2K of Dr.fixit or equivalent water proofing material and appling in two coat over the concrete floor and dado upto 1’6\" in wall including cleaning,applying and mending as per specification including all labour charges as per direction of Engineer-in-charge. |
| 552 | First Floor(Qnty same as Floor tiles in F.F) |
| 553 | Supplying all materials, labour, T&P and providing and fixing ceramic tiles in floors, treads or steps and landing on 25mm thick bed of cement mortar (1:1) ( 1 cement : 1 sand ) jointed with neat cement slurry mixed with pigment to match the shades of the tilesincludingwatering, curing,cost of all materials, conveyance of all materials to work site , payment of royalty, all taxes etc all complete as per P.W.D specification and direction of Engineer-in-charge ( ceramic floor tiles of premium grade having thickness 7mm to 8mm conforming to IS 13755 of size 30cmx30cm Kajaria/Jhonson/Orient make to be pre-approved by the Engineer-in-charge ) |
| 554 | Kajaria/Somany/Johnson tile 60cmx60cm |
| 555 | Ground floor Washrooms |
| 556 | VIP Suite=2 x 3.60 mt x 1.95mt = |
| 557 | Drawing Room =2 x 3.00 mt x 1.50mt = |
| 558 | Guest Room ,Care Taker & Kitchen = 3 x 2.40 mt x 1.50mt = |
| 559 | Drivers Dormitory 1 x 2.40 mt x 1.28mt = |
| 560 | 1 x 2.40 mt x 1.15mt = |
| 561 | Gents Toilet & Ladies Toilet 2 x 4.63 mt x 2.23 mt = |
| 562 | Door Sill = D3 9 x 0.75 mt x 0.15 mt = |
| 563 | Door Sill = D12 x 1.00 mt x 0.25 mt = |
| 564 | First Floor Washrooms |
| 565 | VIP Suite=2 x 3.60 mt x 1.95mt = |
| 566 | Drawing Room =2 x 3.00 mt x 1.50mt = |
| 567 | Guest Room =1 x 2.40 mt x 1.50mt = |
| 568 | Bed Room =4 x 2.40 mt x 1.80mt = |
| 569 | Gents Toilet & Ladies Toilet 2 x 4.63 mt x 2.23 mt = |
| 570 | Door Sill = D3 9 x 0.75 mt x 0.15 mt = |
| 571 | Door Sill = D12 x 1.00 mt x 0.25 mt = |
| 572 | Supplying all materials,labour,T&P and providing 12mm thick cement plaster(1:4) on brick work including watering,curing,cost of all materials, conveyance of all materials to worksite,paymentof royalty,all taxes etc.all complete as per PWD specification and direction of the Engineer-in-charge. |
| 573 | Ground floor - (Qnty same as Wall Tiles in G.F) |
| 574 | First Floor - (Qnty same as Wall Tiles in F.F) |
| 575 | Supplying all materials, labour, T&P and providing and fixing porcelain glazed tiles in dado skirtingon 12mm thick cement plaster (1:3) jointed with neat cement slurry mixed with pigment to match the shades of the tilesincludingwatering, curing,cost of all materials, conveyance of all materials to work site , payment of royalty, all taxes etc all complete as per P.W.D specification and direction of Engineer-in-charge( ceramic wall tiles of premium grade having thickness 6.5mm to 6.7mm conforming to IS 13753 of size 30cmx45cm Kajaria/Jhonson/Orient make to be pre-approved by the Engineer-in-charge ) |
| 576 | Kajaria/Somany/Johnson tile 60cmx30cm |
| 577 | Ground floor |
| 578 | VIP Suite= 2 x2(3.60m+1.95m) x 2.10m= |
| 579 | Drawing Room = 2 x 2(3.00m+1.50m) x 2.10m= |
| 580 | Guest Room=3 x 2(2.40m+1.50m) x 2.10m= |
| 581 | Drivers Dormitory 1 x 2(2.40m+1.28m) x 2.10m= |
| 582 | Drivers Dormitory 1 x 2(2.40m+1.15m) x 2.10m= |
| 583 | Gents Toilet & Ladies Toilet2 x 2(4.63m+2.23m) x 2.10m = |
| 584 | Partion Wall =2 nos x (1.63 + 0.30+0.30) x 2.10 x 2 sides = |
| 585 | Door Face (D1)=2 nos xx 2 sides x 0.25 x 2.10 = |
| 586 | Door Face (D3)= 9 nos xx 2 sides x 0.15 x 2.10 = |
| 587 | Deduction- Door-D1- (-)2 x 1.00m x 2.10m= |
| 588 | Deduction- Door-D3 (-)9 x 0.75m x 2.10m= |
| 589 | First Floor Washrooms |
| 590 | VIP Suite= 2 x2(3.60m+1.95m) x 2.10m= |
| 591 | Drawing Room =2 x 2(3.00m+1.50m) x 2.10m= |
| 592 | Guest Room=1 x 2(2.40m+1.50m) x 2.10m= |
| 593 | Bed Room = 4 x 2(2.40m+1.80m) x 2.10m= |
| 594 | Gents Toilet & Ladies Toilet2 x 2(4.63m+2.23m) x 2.10m = |
| 595 | Partion Wall =2 nos x (1.63 + 0.30+0.30) x 2.10 x 2 sides = |
| 596 | Door Face (D1)=2 nos xx 2 sides x 0.25 x 2.10 = |
| 597 | Door Face (D3)= 9 nos xx 2 sides x 0.15 x 2.10 = |
| 598 | Deduction- Door-D1- (-)2 x 1.00m x 2.10m= |
| 599 | Deduction- Door-D3 (-)9 x 0.75m x 2.10m= |
| 600 | Granite Tiles 20mm thick |
| 601 | Ground floor ( 2 x 3.00 x 0.75.) +(2.00 x 0.75) = |
| 602 | First Floor. (2 x 3.00 x 0.75) = |
| 603 | Factory made single leaf Solid WPC (Wood polymer) composite door shutter of 25mm thickcompacted with wood grain finishstructural foam panel of 29mm thickness and a density of 20kg/cu.mtr shall be used as core material for fitting the metal fittings such as tower bolts, aldrops, handles etc shall be provided. A structural adhesive compatible with (EPS) foam shall be used for bending the core material,The material and process for manufacturing the door shutters shall conform to RV-TIFAC composites Design Centre\"s standards and specifications and the door shutters Conforming to relevant I.S.specification. The finish of door shutter will be plain colour white/ Ivory/ Beige/ Light grey/ Mahogany/ Teak wood or any other colour using high quality pigments. Three heavy whight mild steel butt hinges type-I(ISI marked) size 100mm are to be fitted on one side of shutter. |
| 604 | D3 = 26 nos x 0.75 x 2.10 = |
| 605 | D1 = 4 nos x 1.00 x 2.10 = |
| 606 | Factory made Solid WPC door frame of size 95mmx55mm fabricated .The door frame consist of four segments which are provided with plug-in-socket arrangement in-situ in the mould. The segments are plugged in and are joined together by means of screw. The WPC frame shall be provided with The material and process for manufacturing the door frames shall conform to Relavent I.S.specification. The finish of door frame will be plain colour white/ Ivory/ Beige/ Light grey/ Golden brown/Mahogany/ Teak wood/sand stone/Champagne/Pastel blue or any other colour using high quality pigmentscomplete in all respect as per specification and direction of the Engineer in charge |
| 607 | D3 = 26 nos x (0.75 + 2.10 + 2.10)= |
| 608 | D1 = 4 nos x (1.00 + 2.10 + 2.10) = |
| 609 | Supplying all materials, labour, T&P and providing brick work in super structure with fly ash bricks having crushing strength not less than 75kg/cm² with dimensional tolerance ± 8 percent in cement mortar (1:4) including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 610 | Ground floor |
| 611 | First Floor |
| 612 | Supplying all materials, labour, T&P & constructing mesonary drain of size 0.30mtr x 0.45mtr drains as per P.H. design & specification including lead of all materials to site. |
| 613 | Supplying all materials, labour, T&P and providing fitting and fixing (Aqua guard) pure chill 120 PSS UV of size 750 x 570 x 1350mm hight with water storage capacity 120 liter\"s along with 3 noa of faucets 2 for cold water and 1 for normal water including a flow of 1.5 ltr per munite etc all complete as per approved drawing , specification and direction of the Engineer in charge |
| 614 | Aqua guard pure Chill 120 PSS UV |
| 615 | Ext. S/D Portion |
| 616 | Supplying all materials, labour, T&P and laying in trenches (to level or slope) unplasticized P.V.C. pipe conforming to IS 4985/2000 of the following out side dia for class- 3 (0.60mpa ) including jointing with supply of approved solvent cement by non-heat application method/as per manufacture\"s specification, provoding and laying in trench cement concrete (1:4:8) with 40mm size hard granite metal in the type C-1 standard bedding surrounding or encasing including concrete for bedding and curing etc all complete as per P.H. specification and direction of the Engineer in charge |
| 617 | 110mm dia P.V.C. pipe |
| 618 | 160mm dia P.V.C. pipe |
| 619 | Supplying all materials ,labour ,T&P and constructing Inspection Chamber ofinside size 760mmx760mmx460mmwith cement concrete (1:3:6) using 40mm size crusher broken hard black granite metal on bed , KB brick work in cement mortar (1:6) in foundation and plinth, moulding and shaping the channel inside and benching with cement concrete (1:2:4) using 12mm size crusher broken hard black granite chips,12mm thick cement plaster (1:3)with cement punning to inside, cement flush pointing (1:3) to outside, R.C.C cover slab (1:2:4) using 12mm size crusher broken hard black granite chips with R.C.C man hole cover, earth work in excavation in all kinds of soil and refilling the cavity around the chamber including watering,curing,cost of all materials, conveyance of all materials to worksite, payment of royalty,all taxesetc.all complete as perapproved drawing, P.H specification and direction of Engineer-in-charge |
| 620 | Inside size 76cmx76cmx46cm with 18” dia RCC MH cover |
| 621 | Supplying all materials labor T&P and constructing MH chamber of sizes earth work in excavation in all kinds of soil CC(1:1:8) with black granite chips size 46mm brick work with K.B. brick having crossing strength not less than 75 Kg /CM2 to 90 Kg/CM2s in CM(1:6)12mm C.P(1:8) inside MH chamber over benching with cement slush pointing (1:3)outside the MH chamber providing painting MS or CI step iron RCC(roof of slab with CC(1:2:4)with black granite chips size 12mm bending binding tying the grills placing of the reinforcement providing RCC color of required size refilling the cavity around the MH chamber with excavated earth including channeling the bed of MH etc all complete as per PH specification. |
| 622 | MH size 0.91m x 0.91 m with 0.45 m (18” dia RCC Cover ) |
| 623 | Supplying all materials labour T&P and constructing 1.40m dia x 2.00 m deep soak way pit with dry brick having crossing strength not less than 75Kg/CM2 to 99Kg/CM2 in CM(1:6) for the remaining 0.4572mm height of wall at top CC(1:3)inside and outside inside fill with dry brick khoa size 38mm ,CM thick RCC perforated slab to a height of 1.9012m from bottom covered by means of 50mmthick RCC wall cover in pieces filled with iron plugs including earth work in excavation refilling of cavity around the pit and painting the iron works complete as per PHD design and specification including carriage of all materials to site. |
| 624 | Supplying all materials ,labour ,T&P and constructing gully trap chamber ofinside size 250mmx250mmwith 8cm thick RCC precast cover slab in cement concrete (1:2:4) mix using 12mm size crusher broken HG chips, foundation concrete (1:4:8) using 40mm size crusher broken HG metal on bed and around trap, KB brick work in cement mortar (1:6) in foundation and plinthand inside 12mm thick cement plastering (1:3) finished with a floating coat of neat cement including fixing 100mmx100mm size HCI gully trap, 150mmX150mm size CI gratingetc.all complete as per drawing,specification and direction of Engineer-in-charge |
| 625 | 2 nos 50 users RCC septic tank |
| 626 | Earth work in excavation of foundation in all kinds of soil within 50m initial lead and 1.5m initial lift including rough dressing & breaking clods to maximum 5cm to 7cm and laying in layers not exceeding 0.30m in depth and as per direction of theEngineer-in-Charge. |
| 627 | 2 nos x 6.80 x 2.74 x1.50= |
| 628 | Extra lifts of 1.50 mtr or part thereof over the initial lift of 1.5 mtr in all kinds of embankments and road works and ordinary earthwork in general. |
| 629 | 2nos x 6.80x2.74x 0.90= |
| 630 | Supplying all materials, labour, T&P and providing shoring and shuttering foundation trenches, pits etc with close wooden planks or sheets shuttering etc all complete as per direction of the Engineer in charge. |
| 631 | 2nos x 2x(6.80+2.74)x2.40= |
| 632 | Supplying all materials, labour, T&P and filling in foundation and plinth with sand well watered and rammed including conveyance of all materials to worksite, payment of royalty, taxes etc.all complete as per direction of the Engineer incharge. |
| 633 | 2nos x 6.50x2.37x0.20= |
| 634 | Supplying all materials, labour, T&P and providing cement concrete (1:3:6) with 4cm size hard granite metal including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 635 | 2nos x 6.50x2.37x0.20= |
| 636 | Supplying all materials, labour, T&P and providing cement concrete (1:1.5:3) with 12mm size hard broken granite chips for R.C.C works including hoisting, laying, watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 637 | Base-1 x 5.80x2.40x0.20= |
| 638 | Wall - 2( 5.40 + 1.60) x 0.20 x 2.40 = |
| 639 | Slab- 1 x 5.40 x2.00 x 0.13= |
| 640 | Supplying all materials, labour, T&P and providing M.S reinforcement for R.C.C work including cutting, bending, binding, and tying the grills and placing in position including cost of binding wire 18 to 20 gauge, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 641 | Supplying all materials, labour, T&P and providing rigid and smooth centering and shuttering for R.C.C works including false work and dismantling them after casting including conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 642 | R.C.C floor and roof slabs, landings, balconies, projecting sunshades and chajjas up to 4.30 mt height |
| 643 | Slab- 2 x 5.00x1.60= |
| 644 | R.C.C beams,columns,girder and bressmer etc. |
| 645 | Wall -I/S- 2 nos x 2x(5.00+1.60)x2.40= |
| 646 | Wall -O/S- 2 nos x 2(5.40+2.00)x2.55= |
| 647 | Supplying all materials, labour, T&P and providing 6mm thick cement plaster (1:4) on RCC work including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 648 | Base - 1 x 5.00 x 1.60 = |
| 649 | Inside Wall - 1 x 2(5.00+1.60) x 2.40 = |
| 650 | Supplying all materials, labour, T&P and providing cement punning including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 651 | Supplying all materials, labour, T&P and providing 12mm thick cement plaster (1:4) on brickwork including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 652 | 2x2x1.60x1.65= |
| 653 | Supplying all materials, labour, T&P and providing brick work with K.B bricks having crushing strength not less than 75kg/cm² with dimensional tolerance ± 8 percent in cement mortar (1:4) including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge |
| 654 | 2 x 1.60x0.25x1.50= |
| 655 | Supplying all materials, labour, T&P and making MS step iron in 20mm diameter MS steel bars and fixing into walls ofman hole/septic tank duly embedded in cement concrete (1:3:6) complete as per specification and direction of the Engineer in charge. |
| 656 | Filling in foundation and plinth with excavated materials, moorum including watering and ramming as directed by the Engineer in charge |
| 657 | 1/3 rd of excavated earth =1/3(55.89+33.54)= |
| 658 | 2 no 30,000ltr R.C.C. Sump (6.00x2.50x3.00) |
| 659 | Earth work in excavation of foundation in all kinds of soil with in 1.5m initial lift including dressing and leveling of bed and breaking the clods and the excavated materials with in 50m initial lead as per direction of Engineer in charge. |
| 660 | 2x8x4.50x1.50= |
| 661 | Earth work in excavation of foundation in all kinds of soil with in 1.5m initial lift including dressing and leveling of bed and breaking the clods and the excavated materials with in 50m initial lead as per direction of Engineer in chargewith 1st extra lift of 1.50 m over initial laft. |
| 662 | 2x8x4.50x1.00= |
| 663 | Supplying all labor T&P & filling foundation and plinth with excavated materials well watered & rammed etc. all complete as per direction of EIC. |
| 664 | Supplying all materials labor T&P filling sand in foundation and plinth with well watered and rammed etc all complete as per direction of Engineer-in-charge |
| 665 | 2x7x3x0.15= |
| 666 | Supplying all materials, labour, T&P and providing cement concrete ( 1:3:6 ) with 40mm size crusher broken hard black granite metal including watering, curing,cost of all materials, conveyance of all materials to work site with payment of royalty, all taxes etc all complete as per P.W.D specification and direction of Engineer-in-charge. |
| 667 | 2x7x3x0.15= |
| 668 | Supplying all materials, labour, T&P and providing cement concrete (1:1½:3) with 12mm size crusher broken hard black granite chips for RCC works including hoisting, laying, watering, curing,cost of all materials, conveyance of all materials to worksite, payment of royalty,all taxes etc. all complete as per PWD specification and direction of the Engineer in charge. |
| 669 | 2x6x2x0.20= |
| 670 | 2x2(6.00+2.00)x2.50x0.20= |
| 671 | 2x6.40x2.40x0.20= |
| 672 | Supplying all materials, labour, T&P and providing steel reinforcement of Fe-415 /Fe-500 grade for RCC work including cutting,bending,bindingand tying the grills and placing in position including cost of binding wire 18 to 20 gauge,cost of steel, conveyance of all materials to worksite, payment of royalty,all taxes etc all complete as per PWD specification and direction of the Engineer-in-charge. |
| 673 | Supplying all materials, labour, T&P and providing rigid & smooth centering and shuttering for RCC works including false work and dismantling them after casting including conveyance of all materials to worksite, payment of royalty, taxes etc. all complete as perspecification and direction of the Engineer-in-charge |
| 674 | RCC floor, roof slab chhaja up to 4.430 m height |
| 675 | 2x2x2x(5.80+2.40)x1.50= |
| 676 | Supplying all materials,labour,T&P and providing 12mm thick cement plaster(1:3) on brick work including watering,curing,cost of all materials, conveyance of all materials to worksite,paymentof royalty,all taxes etc.all complete as per PWD specification and direction of the Engineer-in-charge. |
| 677 | 2x2(6.40+2.40)x2.50= |
| 678 | 2x2(6.00+2.00)x2.50= |
| 679 | 2x2x6.00= |
| 680 | 2x6.40x2.40= |
| 681 | Supplying all materials, labour, T&P and providing cement punning including watering, curing,cost of all materials, conveyance of all materials to worksite, payment of royalty,all taxes etc. all complete as perspecification and direction of the Engineer-in-charge |
| 682 | Supplying and fitting and fixing stainless steel 34 grade in said rail using 5mm dia 2mm thick circular pipe and balustrade 32mmx32mmx2mm at the rate of mtr.Center to center and square pipe 32x32x2mm below including welding with stanless steel elect rod and fixing with necessary accessories etc.complete as per direction of the Engineer-in-charge. |
| 683 | Providing fitting and fixing RCPCcoveretc complete as per direction of Engineer-in-charge |
| 684 | Construction of 2 nos production well including scientific source finding through consolidated and unconsolidated rock with down the ODEX drilling rig with PVC, GI, MS pipe and installation of submersible pump set with all accessories. |
| 685 | Labour for drilling a perfectly vertical bore hole of specified dia for a specified depth below ground level through consolidated and unconsolidated rock with combination drilling rig as required to suit the site condition as per the direction of Engineer-in-charge including supply of own rig with its accessories, tools and plant and consumables etc. for lowering of 200mm /150mm dia M.S. Pipe / PVC casing fitted with socket and with or without well screen as per the necessity for sub-medium hard and boulder formation (M.S./PVC casing pipe if required to prevent collapse of over burden is to be provided by contractor including lowering and withdrawing after completion of the tube well) 200mm dia x 400mm dia in over burden position inlcluding packing of gravel supplied by Contractor for 400mm bore only etc as per direction of Engineer incharge. |
| 686 | Drilling for 200mm dia bore |
| 687 | 00mtr to 20 mtr |
| 688 | 21mtr to 40 mtr |
| 689 | Drilling for 150mm dia bore |
| 690 | 41mtr to above |
| 691 | Lowering the following size of G.I. / PVC / M.S. housing pipe with or without slotted pipe as per the necessity for ground level upto 45 mtr depth and fitted and fixed up perfectly vertical position including cutting and threading of pipes and slotted pipes and supplying and fixing all jointing materials, tools and plants etc all complete and keeping the top of the casing pipe threaded including plugging tube wells to prevent entry of foreign materials. |
| 692 | Lowering 200mm dia M.S.ERW pipe casing pipe |
| 693 | 00mtr to 40 mtr |
| 694 | cleaning and developing the tube well with supply of compressor worked till clear and adequate discharge in obtained from the tube well including supply and use of all necessary equipment and labour as per direction of Engineer-in-charge. |
| 695 | By DTH / Rotary |
| 696 | Supplying all labour, materials and T&P for providing sanitary sealing by cement concrete grouting of annular space around M.S. casing pipe uptp 5 mtr below groun dlevel to plug the bore hole excluding cost of cement etc all complete as per direction of EIC. |
| 697 | Supplying all materials, labour, T&P and providing, fitting and fixing submersible pump with squirrel cage induction type submersible type submersible electric motor to run on 3 phase/1 phase line voltage ranging from 320 volt to 450 volt conforming to IS: 8034/89 with following specifications with suitable control panel, jointing with GI/PVC/HDPE pipes, electrification, testing, commissioning, trial running, conveyance of all materials to worksite, payment of taxes etc all complete as per specification and direction of the Engineer in charge (Texmo/Crompton Greaves/Kirloskar make) |
| 698 | 2 H.P. Single phase/ three phase 7 stagehead renge of 20 to 35 mtr with discharge capasity 145 to 110 L.P.M With outlet dia 25 mm |
| 699 | DOL Control panel |
| 700 | 40mm dia steel short piece |
| 701 | Well cap |
| 702 | 50mm size CI bracket |
| 703 | 2.50sqmm flat cable |
| 704 | 20mm dia rigid UPVC pipes |
| 705 | Steel rope with cover |
| 706 | Labour charges for lowering including transportation |
| 707 | Supplying all materials, labour, T&P and providing and fixing to wall or ceiling and floor HDPE pipes and pipe fittings conforming to IS: 4984/2000 (10kgf/sqcm) of the following nominal bore with clamps and jointing by Fusion welding method including testing, making good the wall, ceilingand floor all complete as per specification and direction of the Engineer in charge |
| 708 | 32mm HDPE pipes (Finolex/Supreme make) |
| 709 | 1nos Pump House of size8\"-0\"\"x8\"-0\"\" (Internal) |
| 710 | Earth work in excavation of foundation in all kinds of soil with in 1.5m initial lift including dressing and leveling of bed and breaking the clods and the excavated materials with in 50m initial lead as per direction of Engineer in charge. 4 x 2.65 x 0.80 x0.90= |
| 711 | Supplying all labor T&P & filling sand in foundation and plinth with well watered & rammed etc. all complete as per direction of EIC. |
| 712 | F&P= 4 x 2.65 x0.80 x 0.15 = |
| 713 | Floor= 1 x 2.40 x 2.40 x 0.15 = |
| 714 | Supplying all materials, labor T&P providing CC (1:4:8) with 4 cm HG metal including watering curing lead of all materials to site etc. complete. |
| 715 | 4x2.65 x 0.80 x 0.15 = |
| 716 | 2.40 x 2.40 x0.08 = |
| 717 | Supplying all materials labour T&P and providing 1st class Fly Ash brick work in CM (1:6) in F&P including watering and curing and lead of materials to site. |
| 718 | 1st Footing = 4x 2.65 x0.65 x0.30 = |
| 719 | 2nd Footing = 4x 2.65 x0.50 x0.30 = |
| 720 | 3rd Footing = 4x 2.65 x0.38 x0.30 = |
| 721 | Supplying all materials, labour, T&P & providing 2.5cm thick D.P.C. flooring with cement concrete (1:2:4) 12mm hard broken granite chips including conveyance of all materials, watering curing payment of royalty taxes etc. all complete as per direction of Engineer-in-charge. |
| 722 | 4 x 2.65 x 0.38 = |
| 723 | Supplying all materials, labor T&P providing CC (1:2:4) with 4 cm HG metal including watering curing lead of all materials to site etc. complete. |
| 724 | 2.40x 2.40 x0.10 = |
| 725 | Supplying all materials labour T&P and providing 1st class Fly Ash brick work in CM (1:6) in Super Structure including watering and curing and lead of materials to site. |
| 726 | Wall=4x 2.65 x0.25 x2.80 = |
| 727 | Deduct Door = 1 x 0.90 x 0.25 x2.10=(-) |
| 728 | Deduct Window =1 x 0.90 x 0.25 x1.20=(-) |
| 729 | ProvidingC.C. (1:1½:3)with 12mm size hard granite chips of RCC workincluding hoisting and laying and curing with leadof all materials to site. |
| 730 | slab 3.20 x 3.20 x 0.10 = |
| 731 | Chajja 2 x 1.00 x 0.60 x0.08 = |
| 732 | Lintel 2 x 1.50 x 0.25 x 0.150 = |
| 733 | Supplying all materials, T&P and providing MS reinforcement for RCC work including cutting, bending, binding and tying the grills and placing in position including cost of binding wire 18 to 20 gauges. |
| 734 | Supplying all materials labour T&P and providing 12mm thick C.P (1:6) including watering curing and conveyance of all materials to site. |
| 735 | Inner Side Wall=4 x 2.40 x2.80 = |
| 736 | Outer Side Wall=4 x 2.90 x2.80= |
| 737 | Celling=1 x 2.40x 2.40= |
| 738 | Deduct Door =1 x 0.90 x2.10=(-) |
| 739 | Deduct Window = 1 x 0.90 x1.20=(-) |
| 740 | Rigid & smooth centering & sheltering for RCC work including falls work & dismantling than after casting including cost of materials in ground floor. |
| 741 | RCC floor, roof slab chhaja up to 4.430 m height |
| 742 | Roof Slab1 x 3.20 x 3.20 = |
| 743 | Roof edge 4 x3.20 x0.10 |
| 744 | Supplying all materials, labour, T&P & providing 2.5cm thick A.S. flooring with cement concrete (1:2:4) 12mm hard broken granite chips including conveyance of all materials, watering curing payment of royalty taxes etc. all complete as per direction of Engineer-in-charge. |
| 745 | 2.40 x 2.40 = |
| 746 | Supplying all labor T&P & filling foundation and plinth with excavated materials well watered & rammed etc. all complete as per direction of EIC. |
| 747 | 1/3rd of Excavated Material = (1/3) x 7.63 = |
| 748 | Supplying all materials labour T&P providing on two coats of white washing ceiling |
| 749 | Same as Plaster Area |
| 750 | Supplying fitting, fixing in position angle iron window frame made out of 35mm x 35mm x 5mm, M.S. angle with required nos. of hinges and steel shutter made out of 25mm x 25mm x3mm, M.S. angle fitted with 20 gauge G.P. sheet/ steel plate and welded with tower bolt, handle hold fast & M.S. flat of 19mm x 3mm & welded with entire grill on windows and one coat of red oxide primer and fixing with C.C. (1:3:6) using 12mm size HBG CB Chips and making good to the damages and finishing the exposed surface smooth with watering curing etc. as per direction of the Engineer-in-charge. |
| 751 | Rain Water Harvesting |
| 752 | Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer\"s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches , cost & conveyance of all materials to worksite, payment oftaxes etc.all complete as per P.H specification and direction of the Engineer-in-charge. |
| 753 | 110mm U-PVC SWR Pipe (Supreme/Ashirvad) |
| 754 | 110mm U-PVC door bend(Ori Plast/Finolex/Supreme Make) |
| 755 | 110mm U-PVC Socket(Ori Plast/Finolex/Supreme Make) |
| 756 | 125mm CP grating |
| 757 | Supplying all materials, labour, T&P and laying in trenches (to level or slope) unplasticized P.V.C. pipe conforming to IS 4985/2000 of the following out side dia for class- 3 (0.60mpa ) including jointing with supply of approved solvent cement by non-heat application method/as per manufacture\"s specification, provoding and laying in trench cement concrete (1:4:8) with 40mm size hard granite metal in the type C-1 standard bedding surrounding or encasing including concrete for bedding and curing etc all complete as per P.H. specification and direction of the Engineer in charge |
| 758 | 160mm dia P.V.C. pipe |
| 759 | Supplying all materials ,labour ,T&P and constructing Inspection Chamber ofinside size 760mmx760mmx460mmwith cement concrete (1:3:6) using 40mm size crusher broken hard black granite metal on bed , KB brick work in cement mortar (1:6) in foundation and plinth, moulding and shaping the channel inside and benching with cement concrete (1:2:4) using 12mm size crusher broken hard black granite chips,12mm thick cement plaster (1:3)with cement punning to inside, cement flush pointing (1:3) to outside, R.C.C cover slab (1:2:4) using 12mm size crusher broken hard black granite chips with R.C.C man hole cover, earth work in excavation in all kinds of soil and refilling the cavity around the chamber including watering,curing,cost of all materials, conveyance of all materials to worksite, payment of royalty,all taxesetc.all complete as perapproved drawing, P.H specification and direction of Engineer-in-charge |
| 760 | Inside size 76cmx76cmx46cm with 18” dia RCC MH cover |
| 761 | Supplying all materials labour T&P and constructing 1.80m diax2.60m deep soak way pit with dry brick having crossing strength not less than 75Kg/CM2 to 99Kg/CM2 in CM(1:6) for the remaining 0.4572mm height of wall at top CC(1:3)inside and outside inside fill with dry brick khoa size 38mm ,CM thick RCC perforated slab to a height of 1.9012m from bottom covered by means of 50mmthick RCC wall cover in pieces filled with iron plugs including earth work in excavation refilling of cavity around the pit and painting the iron works complete as per PHD design and specification including carriage of all materials to site. |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy