Preventive Maintenance Of Fire Alarm System, Smoke Detection, Fire Fighting System And Other Fire Fighting Assests And Connected Items Under Age Em-Ii Of Ge (U) At Chandimandir, chandimandir-Haryana

Military Engineer Services-MES has published Preventive Maintenance Of Fire Alarm System, Smoke Detection, Fire Fighting System And Other Fire Fighting Assests And Connected Items Under Age Em-Ii Of Ge (U) At Chandimandir. Submission Date for this Tender is 13-10-2022. Alarm Systems Tenders in chandimandir Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

34145093
Preventive Maintenance Of Fire Alarm System, Smoke Detection, Fire Fighting System And Other Fire Fighting Assests And Connected Items Under Age Em-Ii Of Ge (U) At Chandimandir
Open Tender
Indian
Haryana
chandimandir
13-10-2022

Tender Details

Preventive Maintenance Of Fire Alarm System, Smoke Detection, Fire Fighting System And Other Fire Fighting Assests And Connected Items Under Age Em-Ii Of Ge (U) At Chandimandir

Key Value

Document Fees
INR 1000 /-
EMD
INR 115000.0 /-
Tender Value
INR 60 Lakhs /-

BOQ Items

Name of Work: PREVENTIVE MAINTENANCE OF FIRE ALARM SYSTEM, SMOKE DETECTION, FIRE FIGHTING SYSTEM AND OTHER FIRE FIGHTING ASSESTS AND CONNECTED ITEMS UNDER AGE EM-II OF GE (U) AT CHANDIMANDIR
Sl. No. Item Description
1Servicing/Maintenance of fire alarm system Make:- Morley installed at War Gaming Centre complete all as specified and directed comprising following services/maintinance to be carried out under this item:- (i) Small spare parts as required (like wire,lugs,pvc caps,nuts and bolts etc.) shall be measured under this item. (ii) The work shall be executed by OEM or his authorised agency only as approved by GE. (iii) Checking of Alarm, signal should not lost when primary power failure untill the alarm signal processed. (iv) Checking of audio amplifiers and tone generating equipment (v) Checking of smoke detector sensibility. (vi) checking of all speaker circuit and loops.
2Servicing/Maintenance of fire alarm system Make: Morley installed at COMPAD Building (Chanakya Bldg) complete all as specified and as directed comprising following services/maintinance to be carried out under this item:- (i) Small spare parts as required (like wire,lugs,pvc caps,nuts and bolts etc.) shall be measured under this item. (ii)The work shall be executed by OEM or his authorised agency only as approved by GE. (iii) Checking of Alarm, signal should not lost when primary power failure untill the alarm signal processed. (iv)Checking of audio amplifiers and tone generating equipment. (v)Checking of smoke detector sensibility. (vi)Checking of all speaker circuit and loops.
3Servicing/Maintenance ofof fire alarm system Make: Morley installed at HQ Western Command Building complete all as specified and directed comprising following services/maintinance to be carried out under this item:- (i)Small spare parts as required (like wire,lugs,pvc caps,nuts and bolts etc.) shall be measured under this item. (ii)The work shall be executed by OEM or his authorised agency only as approved by GE. (iii) Checking of Alarm, signal should not lost when primary power failure untill the alarm signal processed. (iv)Checking of audio amplifiers and tone generating equipment. (v)Checking of smoke detector sensibility. (vi)Checking of all speaker circuit and loops.
4Servicing/Maintenance of fire alarm system Make: Morley installed at Maneakshaw auditorium complete all as specified anddirected comprising following services/maintinance to be carried out under this item:- (i)Small spare parts as required (like wire,lugs,pvc caps,nuts and bolts etc.) shall be measured under this item. (ii) The work shall be executed by OEM or his authorised agency only as approved by GE. (iii) Checking of Alarm, signal should not lost when primary power failure untill the alarm signal processed. (iv)Checking of audio amplifiers and tone generating equipment (v)Checking of smoke detector sensibility. (vi)Checking of all speaker circuit and loops.
5Supply,Installation,Testing and Commissioning in replacement of analog addressable type self acclimatising multi sensing Photo and heat detector with standard mounting base,LED,Address switch, complete for mounting on surface /on false ceilling/ below false floor, cable Lugs at ends,cable compression glands,cable tags and ferruling complete all as specified and directed. Make:-Morley/Honeywell/Notifier or as per make mentioned in Appx "B".
6Supply,Installation,Testing and Commissioning in replacement of EL listed analog addressable dual action manual pull station/ glass break with address switch and all mounting accessories, complete for mounting on surface /on false ceilling/ below false floor, cable iugs at ends, cable compression glands, cable tags and ferruling complete all as specified and directed. Make:-Morley/Honeywell/Notifier
7Supply,Installation,Testing and Commissioning in replacement of addressable control input module with address switch and all mounting accessories, complete for mounting on surface, cable lugs at ends, cable compression glands, cable tags and ferruling complete all as specified and directed. Make:-Morley/Honeywell/Notifier
8Supply,Installation,Testing and Commissioning in replacement of addressable control output module with address switch and all mounting accessories, comlete for mounting on surface, cable lugs at ends,cable compression glands, cable tags and ferruling complete all as specified and directed. Make:-Morley/Honeywell/Notifier
9Supply,Installation,Testing and Commissioning in replacement of fault isolator module,complete for mounting on surface, cable lugs at ends,cable compression glands, cable tags and ferruling complete all as specified and directed. Make:-Morley/Honeywell/Notifier
10Supply & Fixing in replacement of hooter with all required accessories for mounting complete all as specified and directed. Make:- Morley/Honeywell/Notifier or as per make mentioned in Appx "B".
11Supply & Fixing in replacementresponse indicator withmatching screws complete with GI junction box etc all as specfied and direected. Make:- Morley/Honeywell/Notifier
12Supply, Installation, Testing and Commissioning in replacementof EL listed with qwerty keypad networkable repeater panel having 640 character backlit LCD displays function keys and soft keys, Repeater panel should be on true peer to peer network complete all as specified and directed. Make:- Morley/Honeywell/Notifier
13Supply and fixing in replacementof hose pipe reel in red colour with capacity of minimum working pressure of 20 bar complete all as specified and directed. Make:- Morley/Honeywell/Notifier or as per make mentioned in Appx "B"
14Supply,Installation,Testing and Commissioning in replacement2 Loop Control Panel 230Vac 4 sounder circuits , 4 line display and networking capability , 6 Amp PSU with 460 Ma loop capability 500*500*195 mm (H8W8D) including Mother Board with power Supply completely complete all as specified and directed. Make:-Morley/Honeywell/Notifier
15Supply, Installation, Testing and Commissioning in replacement4 Loop Control Panel 230Vac 4 sounder circuits , 4 line display and networking capability , 6 Amp PSU with 460 Ma loop capability 500*500*195 mm (H8W8D) including Mother Board with power supply complete all as specified and directed. Make:-Morley/Honeywell/Notifier
16Supply,Installation,Testing and Commissioning in replacementLoop Driver Card suitable for 4 line display complete all as specified and directed. Make:- Morley/Honeywell/Notifier.
17Supply,Installation,Testing and Commissioning in replacementRS 485 Communication Card complete all as specified and directed. Make:- Morley/Honeywell/Notifier.
18Supply,Installation,Testing and Commissioning in replacementLoop control module suitable for 4 line display complete all as specified and directed.Make:- Morley/Honeywell/Notifier.
19Supply , fixing & Testingin replacement ofZHFR cable of size 1.5 Sqmm2 core Sheathedincluding passing through exisiting conduit / exisiting route and necessary cutting and chessing of wall / roof for laying of cable and neceesary PCC work in type B0 (1:2:4) for cutting surface complete all as specified and directed.
20Supply and fixing in replacement of Lead Acid Battery 12V 7AH complete all as specified and directed.
21Supply and fixing in replacementintelligent and addressable FSB-200 Series is the industry"s most reliable smoke sensing technology Beam indicatorwith reflector complete set, FSB-200 Single-ended beam smoke detector Operating Temperature: –22°F to 131°F (–30°C to 55°C), FSB-200S Single-ended beam smoke detector with integral sensitivity test, Operating Temperature: –22°F to 131°F (–30°C to 55°C), 16 to 328 foot protection range , Single-ended, reflected type design, Paintable cover complete all as specified and directed.Make.System Sensor/Morley/ Notifier/ Minimax.
22Supply and fixing in replacement PVC Canvas Fire Hose Pipe, Dia 65 MM , length 30 mtr , with lining, Min pressure 0.8 Mpa, including 65 mm dia stainless steel male femalecoupling complete all as specified and directed by Engineer-in-Charge.
23Supply and fixing in replacement MS pipe 100 mm dia medium gradeincluding welding work complete all as specified.
24Supply and fixing glow sign board such as "FIRE EXIT", ""FIRE HYDRANT BOX"" etc. on the board with base frame made from mild steel angle iron of size 40 x 40 x 3 mm and back side from ACP sheet 3 mm thick with IP 68 protecttion LED module, good quality virgin monomer acrylic sheet, acrylic letter with 5 mm sun board channel, including complete wiring and SMPS power supply with IP 68 protection, Each letter will be made with computer offset for having same letter style and type as approved by Engineer-in-Charge, complete all as specified and directed.
25M & L for preparing old painted steel surfaces of over 10 cm in width or girth and applying priming with one coat of red oxide and two coats of synthetic enamel paint as per the colour standard complete all as specified and directed.
26Supply and fixing in replacement PVC Canvas Fire Hose Pipe, Dia 65 MM , length 15 mtr , with lining, Min pressure 0.8 Mpa, including 65 mm dia stainless steel male femalecoupling complete all as specified and directed by Engineer-in-Charge.
27Supply and fixing 1 KVA/600 W Capacity UPS including battery overload protection , Electric surge protection , Voltage fluctuation protection and short circuit protection, Led indication , Audible alarm, AVR technology, 7 AH -02 Nos battery 12 Volt sealed Lead Acid battery ,output voltage 220 volt complete all as specified and directed.
28Supply,Installation,Testing and Commissioning in replacement ofSensing Photo and heat wire less smoke detector, 3 V powered withinbuilt -in wireless transmitter with standard mounting base,LED,Address switch,comlete with MS powder coated junction box for mounting on surface /on false ceilling/ below false floor, cable Lugs at ends,cable compression glands,cable tags and ferruling complete all as specified and directed. Make:-Morley/Honeywell/Notifier or make mentioned in Appx "B".
29Supply and fixing inreplacement of wifi fire alarm panel, electro optical type , LCD display, alarm more than 90 DB and 1 loop complete all as specified and directed.
30Supply and fixing inreplacement of Nozzle made of brass for connecting with hose reel for extinguishing fire of size 65 mm including nut and bolts complete all as specified and directed by Engineer-in-Charge.
31Material and Labour for drilling and welding for connection of 4 inch hydrant line to 0.5 inch using nipples and gate valves on both ends complete all as specified and directed by Engineer-in-Charge.
32Supply and fixing inreplacement of Hydrant valve single headed , 65 mm bore including flange, washer, and nut and bolt complete all as specified.
33Taking down carefully centrifugal pump set 60 HP by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, inlet, delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at location as directed by Engr-in-Charge, testing on load for smooth operation , complete all as specified and as directed. Spare parts if any required to be replaced shall measured and paid under respective schedule of item here in- after item Sl No 34 to 44, labour element for fixing of any defective part/spare shall be part of this item. Make of existing pump:- Kirloskar.
34Supply only pump shaft sleeve made of gun metal suitable for 60HP motor pump as per manufacturer"s design complete all as specified and as directed.
35Supply only key for main shaft/impeller (SS 410) suitable for 60HP motor pump as per manufacturer"s design complete all as specified and as directed.
36Supply only check nut suitable for 60HP motor pump as per manufacturer"s design complete all as specified and as directed.
37Supply only stuffing box bush suitable for 60HP motor pump as per manufacturer"s design complete all as specified and as directed.
38Supply only motor pump M S coupling with spacer LR 226 type complete with nut, bolts etc suitable for 60HP motor pump as per manufacturer"s design complete all as specified and as directed.
39Supply only water seal suitable for 60HP motor pump as per manufacturer"s design complete all as specified and as directed.
40Supply only stuffing box packing and greasing suitable for 60HP motor pump as per manufacturer"s design complete all as specified and as directed.
41Supply only star couplingtype LR-226 suitable for 60HP motor pump as per manufacturer"s design complete all as specified and as directed.Make- Unique or equivalent as approved by GE.
42Supply only bronze impeller suitable for 60HP motor pump as per manufacturer"s design complete all as specified and as directed.
43Supply only pump set bearing housing DE/NDE of CI grade FG 210 suitable for 60HP motor pump as per manufacturer"s design complete all as specified and as directed.
44Supply only ball bearing (roller/ thrust/ any other type) DE/NDE suitable for 60HP motor pump as per manufacturer"s design complete all as specified and as directed.Make- NBC/ SKF/ TATA. Note:All the items/parts mentioned srl 34 to 44 here-in-before shall be suitable/ compatible for the type and make of pumping set as mentioned against each item and cost of fixing of items is deemed to be included in the quoted rate of item No. 33
45Taking down carefully jockey pump set 10 HP by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, inlet, delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at location as directed by Engr-in-Charge, testing on load, complete all as specified and as directed.Note.Spare parts if any required to be replaced shall measured and paid under respective schedule of item here in- after item Sl No 46 to 55, labour element for fixing of any defective part/spare shall deemed to included in quoted rates of this item.Make of pump:- Kirloskar.
46Supply only pump shaft sleeve made of gun metal suitable for 10HP motor pump as per manufacturer"s design complete all as specified and as directed.
47Supply only key for main shaft/impeller (SS 410) suitable for 10HP motor pump as per manufacturer"s design complete all as specified and as directed.
48Supply only check nut suitable for 10HP motor pump as per manufacturer"s design complete all as specified and as directed.
49Supply only stuffing box bush suitable for 10HP motor pump as per manufacturer"s design complete all as specified and as directed.
50Supply only motor pump M S coupling of suitable size complete with nut, bolts etc suitable for 10HP motor pump as per manufacturer"s design complete all as specified and as directed.
51Supply only water seal suitable for 10HP motor pump as per manufacturer"s design complete all as specified and as directed.
52Supply only stuffing box packing and greasing suitable for 10HP motor pump as per manufacturer"s design complete all as specified and as directed.
53Supply only tyre coupling of suitable size suitable for 10HP motor pump as per manufacturer"s design complete all as specified anddirected.Make- Unique or equivalent as approved by GE.
54Supply only cast iron impeller suitable for 10HP motor pump as per manufacturer"s design complete all as specified and as directed.
55Supply only ball bearing (roller/ thrust/ any other type) DE/NDE suitable for 10HP motor pump as per manufacturer"s design complete all as specified and as directed. Make - NBC, SKF & TATA. Note:All the items/parts mentioned srl 46 to 55 here-in-before shall be suitable/ compatible for the type and make of pumping set as mentioned against each item and cost of fixing of items is deemed to be included in the quoted rate of item No.45
56Taking down defective electric motor, squirrel cage type of any make, from base plate after unscrewing nuts, bolts of foundation/ coupling, 3 phase, 415/440 volts, 50 c/s, AC, capacity 60 HP,shifting the same to workshop, strip opening after unscrewing nuts, bolts/ screws etc. taking out rotor from stator, cutting and taking out burnt winding carefully from the stator, cleaning of slots, rewinding of stator with super enameled copper winding wire of appropriate size matching with manufacturer"s design including replacement of all insulating materials such as glass paper, leathered paper, PVC insulated copper conductor wire connection leads of appropriate size with sleeves of suitable size upto terminal connection box, varnishing, drying up and re-assembling, re-fxing and re-installationat site and testing on load all as specified and directed by Engineer-in-Charge. Note:- Required T&P such as chain pulley block and tranportation shall be contractors responsibility. Repair/ replacement shall be done within a period as intimated by the Engr-in-Charge failing which necessary recovery @ Rs 1000/day shall be made.
57Taking down defective electric motor, squirrel cage type of any make, from base plate after unscrewing nuts, bolts of foundation/ coupling, 3 phase, 415/440 volts, 50 c/s, AC, capacity 10 HP,shifting the same to workshop, strip opening after unscrewing nuts, bolts/ screws etc. taking out rotor from stator, cutting and taking out burnt winding carefully from the stator, cleaning of slots, rewinding of stator with super enameled copper winding wire of appropriate size matching with manufacturer"s design including replacement of all insulating materials such as glass paper, leathered paper, PVC insulated copper conductor wire connection leads of appropriate size with sleeves of suitable size upto terminal connection box, varnishing, drying up and re-assembling, re-fxing and re-installationat site and testing on load all as specified and directed by Engineer-in-Charge.Note:- Required T&P such as chain pulley block and tranportation shall be contractors responsibility. Repair/ replacement shall be done within a period as intimated by the Engr-in-Charge failing which necessary recovery @ Rs 1000/day shall be made.
58Demolition ofcement concrete included removing from site not exe 1.5 km old PCC and M & L for Plain cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate (mass concrete) for pump set bed including necessary form workcomplete all as specified and directed.
59S & F in replacement rolled mild steel channel, angle or tee sections, fixed independently, without connection plate, etc Fe-290 (Gde E-165) including nuts, bolts and washers for base frame of motor pump set, drilling of holes of suitable size for bolts & painting with 2 coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed by Engineer-in-charge
60Supply and fixingin replacement duty contactor 10 KVAR Inbuilt 1 NO/NC auxiliary contact complete all as specified and directed.
61Material labour for finding minor fault in the main panel and providing in replacement worn out small control fuses, indicating lamps, various type of copper lugs, thimbles terminals all as deemed necessary or directed including minor spare parts and components in order to make system serviceable all as specified and directed.
62Supply and fixing in replacement of HRC Fuse 250/200/150 Amps all as specified and directed by Engineer-in-Charge.
63Supply and fixing in replacement of CT of 300/5 including complete wiring all as specified and directed by Engineer-in-Charge.
64Supply and fixing in replacement of CT of 200/5 including complete wiring all as specified and directed by Engineer-in-Charge.
65Supply and fix in replacement 3 pole power contactor MNX-A2 and MNX-A1 complete all as specified and directed.
66Supply and fixing in replacement MCCB, triplepole, 200 Amp 415 volts. 50 Hz breaking capacity not less than 35 kA with adjustable thermal and adjustable magnetic protection release with spreader links, Ics = 100% Icucomplete all as specified and as directed
67Dismantalling ofexisting cable and Supply, laying and testingPVC cable with copper conductor , galvanised steel strip armoured, heavy duty LT power cables, 1100 volts grade cross sectional area70 sqmm 3 core including lux of cable complete all as specified and directed.
68Dismantalling ofexisting cable and Supply, laying and testingPVC cable with copper conductor , galvanised steel strip armoured, heavy duty LT power cables, 1100 volts grade cross sectional area16 sqmm 3 core including lux of cable complete all as specified and directed.
69Supplying and fixing in replacement of MS Double Door Glass Cabinet for housing Hose reel, nozzle etc. of size 2 feet X 2 feet complete all as specified and directed by Engineer-in-Charge.