| 1 | Loading, carriage & Unloading of following materials from store to work site and its stacking. Distance approx (0-10) kms. |
| 2 | 250 KVA Transformer |
| 3 | AB LT Cable of different Size |
| 4 | ST poles 11/9.5 Mtr. including Pin Insulator (15 No.), GI Pin (15 No.), Disc Insulator (6 No.) |
| 5 | ACSR Dog/Weasel conductor |
| 6 | LT XLPE Cable size 1x300 |
| 7 | Electrical Work |
| 8 | Construction of Dist. T/F plinth size 1.2x1.2x1.2 cubic mtr. with solid brick work 75 mm thick C.C. in ratio 1:4:8 with cement, coarse sand and brick ballast and smooth finshing. All material will be provided by contractor. |
| 9 | Making Bore type Earthing system of 60 feet. by boring & fixing G.I. Pipe of 1.5\"\" diaincluding all accessories & fitting, Labour & T&P required |
| 10 | Fabrication, erection and painting with synthetic enamel bus green paint of T/F fencing jali with one side gate, welded fabricated wiremess 10 SWG with size 35x4 mm M.S. Flat X-bracing of frame size 10x8 Feet. (4 No.) including cost of M.S. Angle 40x40x5 mm M.S. Flat 35x5 mm and Nut & Bolt with washer. All material will be provided by Contractor. |
| 11 | Erection of 250 KVA Transformer on plinth with all related works including proper earthing of body & neutral with deep bore pipe, making connection (LT/HT) with proper size Alu. Lug, & providing & fixing LT circuit of 500V/500A (1 No.) etc including labour material & T&P required as per RESSPO norms.& direction of E/I (Only Transformer & LT cable will be provided by KESCo.) |
| 12 | Providing & Fixing following material on LT poles :- |
| 13 | Suspension clamp with eye hook & Holding Clamp |
| 14 | Dead & Clamp with eye hook |
| 15 | Dead & Sealing Cap |
| 16 | Ferrule connector 150-95 |
| 17 | LT Bare neautral connector |
| 18 | Piercing connector 120-25 mm2 |
| 19 | Piercing connector 120-120 mm2 |
| 20 | Other Related works |
| 21 | Laying of AB Cable Size of 150/120 mm2 on pole properlyas per RESSPO norms.& direction of E/I (Only AB cable will be provided by KESCo.) |
| 22 | Providing & Fixing Cable Box O/D type 3x70 sq mm Rachem make |
| 23 | With all precaution and safety Properly erection of ST Pole with stone pad and its concreting and Proper Painting of poles with primer as per RESSPO norms.& direction of E/I.(Only pole and insulator & cros armwill be provided by KESCo.) |
| 24 | With all precaution & safety construction of S/S type double pole on ST pole 11 meter long by proper errection of pole, providing stone pad (300x300x75) & its properly concreting up to 300 mm above ground level, fabrication, errection S/S type pole by fixing Top channel, droper channel of size100x50x2240, 100x50x2000 mm. Providing & fixing 11 KV fuse set on double pole including making connection of DO fuse set to T/F by PVC single core cable of 50 mm with Al lug etc as per RESSPO norms.& direction of E/I (Only pole & Insulator will be provided by KESCo.) |
| 25 | Proper grouting of stay rod in earth concreting stay rod with cement, stone ballat in ratio 1:2:4, fixing stay in stay rod and also fixing and proper tighting Stay wire with poleas per RESSPO norms.& direction of E/I including all labour, material & T&P required (Only Stay wire will be provided by KESCo.) |
| 26 | Providing & fixing of distribution box single phase as per RESSPO norms.& direction of E/I |
| 27 | Providing & fixing of distribution box single phase as per RESSPO norms.& direction of E/I |
| 28 | Strenghtning of Old & Jarjar with new Conductor by of ACSR Dog conductorproper fixing, tightning & jumphring of Dog (4900 mtr.)/Weasel conductor (200 mtr.) & new Dog conductor for HT connection and jumphring (Only Dog conductor & insulator will be provided by KESCo.) |
| 29 | Opening of service cable and reconnection in distribution box |
| 30 | Making guarding arrangment on overhead 33 KV line by providing & fixing 60x60x6 mm of 2-2 meter in length guarding angle on pole & laying guarding wire on pole including cros lacing of guarding by GI wire (6 lacing in each spane.) (GI wire will be provided by KESCo.) |