Military Engineer Services-MES has published Repair / Maintenance Of Exhaust System, Fire Detection System And Other Misc Repair Of Manekeshw Centre Under Ge ( U ) P And M, Delhi Cantt -10.. Submission Date for this Tender is 03-10-2022. Flame Detectors Tenders in delhi Delhi. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 14-Sep-2022 | Corrigendum No 1 | BOQ | 26-09-2022 |
2 | 14-Sep-2022 | Corrigendum No 1 | Date | 26-09-2022 |
3 | 26-Sep-2022 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 03-10-2022 |
Sl. No. | Item Description |
1 | Material and labour for de-scaling of condensers of central AC plantcapacity 3X270 TR by opening side plate, flushing the condenser tubes using de-scaling solution, Roding the condenser tubes carefully removing all the deposited materials completely and raising the solution through condenser tubes till clear water starts to come out from the condensers as complete including re-fixing the side plates by replacing gaskets & testing complete for satisfactory working at complete at Manekshaw Centre all as specified and directed by Engr-in-Charge. Notes :- (i)Necessary T&Psuch as pump, tube, descaling solution etc shall be arranged by the contractor without any extra cost to Department.(ii) Descalling of all condensers in one AC plant shall be considered as one job. |
2 | Material and labourfor servicing of AHU unit including cleaning of bottom tray and cleaning of cooling coil complete with high pressure and coil shine solutionsand jet ofwater pressure with pump without damaging cooling coils and fins and remove all the scale and foreign material deposited in side the coil followed with air pressure to sweep up all the particles and ensure through flow of air over the cooling coil, checking aligning and tightening of blower fan, greasing of all movable parts, replacement of worn out bolts, nuts shaft keys etc all as directed for following capacity AHU:- |
3 | 18000 CFM AHU |
4 | 7000 CFM AHU |
5 | 4000 CFM AHU |
6 | 8000 CFM AHU |
7 | 14000 CFM AHU |
8 | 22000 CFM AHU |
9 | 6000 CFM AHU |
10 | 13000 CFM AHU |
11 | 13500 CFM AHU |
12 | 11000 CFM AHU |
13 | Material and labourfor servicing of ceiling mounted AHU unit including cleaning of bottom tray and cleaning of cooling coil complete with high pressure vaccum cleaner without damaging cooling coils and fins and remove all the scale and foreign material deposited in side the coil followed with air pressure to sweep up all the particles and ensure through flow of air over the cooling coil, checking aligning and tightening of blower fan, greasing of all movable parts, replacement of worn out bolts, nuts shaft keys etc all as directed for following capacity AHU:- |
14 | 6000 CFMceiling mounted AHU |
15 | 8000 CFMceiling mounted AHU |
16 | 5000 CFMceiling mounted AHU |
17 | 3000 CFMceiling mounted AHU |
18 | 2000 CFMceiling mounted AHU |
19 | 2500 CFMceiling mounted AHU |
20 | Supply and fixing in repair of AHU Shaft bearing (02 Nos in each) of size for following capacityAHU as per site requirement complete all as specified and directed by Engineer-in-Charge. (Make - MTM/SKS or equivalent as approved by Accepting Officer.) |
21 | 18000 CFM AHU |
22 | 7000 CFM AHU |
23 | 4000 CFM AHU |
24 | 8000 CFM AHU |
25 | 14000 CFM AHU |
26 | 22000 CFM AHU |
27 | 6000 CFM AHU |
28 | 13000 CFM AHU |
29 | 13500 CFM AHU |
30 | 11000 CFM AHU |
31 | 3000 CFMceiling mounted AHU |
32 | 2500 CFMceiling mounted AHU |
33 | 2000 CFMceiling mounted AHU |
34 | Supply and topping up Refrigerator Gas R-134A complete all as specified & directed by Engr-in-Charge.(Make:- Mefron/ Floron/ Refron.) |
35 | M &L for disamtling the one side puff panel of AHU and then diconnecting the chiller pipe and cooling coil of AHU of required andthen Supply and fixing in replacement of bottom tray for fan and coil section of AHU of any size and any capacity made out of SS sheet tray of grade 304 and also including 25mm thick thermocol insulation covered with tarfelt for AHU bottom complete all as specified and directed. |
36 | Supply and fixing in replacement of shock absorbing rubber pads at the bottom of the AHU unit for absorbing shocks and vibrations, heavy duty of suitable size as per ground requirement complete all as speicifed and directed by Engr-in-charge. |
37 | Supply and fixing in replacement of Pre filter 10 micron of size 610mm x 610x 50mm made of out of GI wire mesh interspaced with two crimp layers and three flat layers flanged deep box type and efficiency 90% as per existing size and pattern for the AC Plant air handling unit complete all as speicifed and directed by Engr-in-charge. (Make- Thermodyne/ AAF or equivalent as approved by Accepting Officer.) |
38 | ditto- all as per item No. 8.00 above but size 610mm x 300mm x 50mm. |
39 | ditto- all as per item No. 8.00 above but size 300mm x 300mm x 50mm. |
40 | ditto- all as per item No. 8.00 above but size500mm x 450mm x 50mm. |
41 | ditto- all as per item No. 8.00 above but size 500mm x 500mm x 50mm. |
42 | ditto- all as per item No. 8.00 above but size 500mm x 400mm x 50mm. |
43 | S&F in repair bimetallic thermaloverload relay,9 to 15 Ampscomplete as specified and directed. |
44 | S&F in repair bimetallic thermaloverload relay,14 to 23 Ampscomplete as specified and directed. |
45 | S&F in repair bimetallic thermaloverload relay,20 to 33 Ampscomplete as specified and directed. |
46 | S&F in repair bimetallic thermaloverload relay,24 to 40 Ampscomplete as specified and directed. |
47 | Supply and fixing in replacement of Rubber Tyre Coupling (TC-14) set for chiller / condensor pump motor complete all as specified and directed by Engr-in-charge. (Make:- Unique or equivalent make as approved by Accepting Officer) |
48 | Supply and fixing in replacement of Rubber Tyre Coupling (TC-13) set for chiller / condensor pump motor complete all as specified and directed by Engr-in-charge. (Make:- Unique or equivalent make as approved by Accepting Officer) |
49 | Supply and fixing in replacement of Rubber Tyre Coupling (TC-11) set for chiller / condensor pump motor complete all as specified and directed by Engr-in-charge. (Make:- Unique or equivalent make as approved by Accepting Officer) |
50 | Supply and fixing in replacement of multifunction electronic timer( 0 to 60 Sec) type Series 525 complete all as specified and directed by Engr-in-charge. (Make:- Siemens/L&T// ABB) |
51 | Material and Labour for frame work with angle ironfor frame support, with fabrication, welding joining including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling,boltingor riveting, etc., and similar work conforming to Fe-290 Gde E-165 including taking down old unserviceable one complete all as specified and asdirected by Engr-In-charge. |
52 | Supply and fixing in replacement fully automatic star delta starter suitable for 3 phase, 415V,containing Electric over current protection relay range of suitable range with external CT 960 Amp, AC-3, 25 Amp rating contractor and back up protection HRC fuse of suitable rating motors of upto 30 HP Capacity including it is to be mounted on existing LT Panels of AC plants andconnections with suitable size single core copper conductor wire & brass terminals of 6 way including taking down old unsv one complete all as specified and directed by Engr-in-Charge. (Make -L&T/Siemens/Legrand/ ABB/Crompton.) |
53 | M&L for repairing /servicing Condenser or Chillerpump (Centrifugal pump) of following capacities by disconnecting the pump from motor, opening for inspection, replacing the worn out parts like gland bush, bearings, gland bolts and nuts, gland packing, gasket, water seal etc including repairing to pump shaft by remetalling, grinding, polishing and reassembling complete pump & refixing in same position & connecting including replacing the rusted nuts, bolts, washers etc and testing and commissioning including loading/unloading and transportation to & from authorised workshopcomplete all as specified and directed: - |
54 | Condenser or Chiller Pump of capacity 30 HP |
55 | Hotwater generator Pump of capacity 25 HP |
56 | Disconnecting from mains/taking out existing unserviceable/defectivemotor of following capacity of any size, type, and make including disconnecting all electrical connectionsremoving from foundation transporting to repair workshop disconnecting unserviceable burn out winding completely including insulating materials and rewinding of the complete stator with super enameled copper wire of existing size applying proper insulation ‘F’ class varnish drying in oven, assembling, transporting back to site, re-installating, testing and commissioning complete all as specified and as directed by Engineer-in-Charge. |
57 | Condenser or Chiller Pump of capacity 30 HP |
58 | Hotwater generator Pump of capacity 25 HP |
59 | M&Lfor repairing/ servicingAHU Fan Motor/ exhaust AHU of following capacity, opening themotor, cutting & removing old burnt windingwire, rewinding the motor with new super enamelled copper winding wire of size & description to match with existing including insulating materials, varnishing, drying, replacement of both driven end, non driven end bearings and base plate,reassembling, refixing in same position & connecting including testing and commissioning complete all as specified & directed :- |
60 | 2 HP Motor |
61 | 3 HP Motor |
62 | 5 HP Motor |
63 | 7.5 HP Motor |
64 | 10 HP Motor |
65 | 15 Hp Motor |
66 | Supply, fixing and testing in replacement of three pole power contactors of capacity MNX-32 includingNO or NC auxiliary contact block, coil voltage 230 V ,control wiring, thimbles, etc and including taking down of old one complete all as specified and as directed by Engr-in-Charge. (Make -L&T/Siemens/ ABB/ C & S.) |
67 | Supply, fixing and testing in replacement of three pole power contactors of capacity MNX-25 includingNO or NC auxiliary contact block, coil voltage 230 V ,control wiring, thimbles, etc and including taking down of old one complete all as specified and as directed by Engr-in-Charge. (Make -L&T/Siemens/ ABB/ C & S.) |
68 | Supply, fixing and testing in replacement of three pole power contactors of capacity MNX-18 includingNO or NC auxiliary contact block, coil voltage 230 V ,control wiring, thimbles, etc and including taking down of old one complete all as specified and as directed by Engr-in-Charge. (Make -L&T/Siemens/ ABB/ C & S.) |
69 | Supply and fixing in replacement Rigid UPVC piping of following dia complete with fittings, supports as perspecifications and duly insulated with 6mm thick closed cell nitrile rubber insulation. |
70 | 40mm dia |
71 | 32mm dia |
72 | Supply and fixing in replacement over load relay 30-50 Amps complete all as specified and directed by Engr-in-Charge (Make -L&T/Siemens/Legrand/ ABB/ C & S.) |
73 | Supply & fixing in replacementbrass terminals of follwing ways complete all as specified and directed by Engr-in-Charge. |
74 | 3 way |
75 | 4 way |
76 | 6 way |
77 | 10 way |
78 | M&L for control wiring with 6 coreX 1.5 sqmm sqmm , FRLS PVC round insulated and sheathed wire featuring a bright annealed bare copper conductor cable 1100 Volts grade with multi stranded, wire colour black,drawn through concealed conduit including PVC rigid conduit medium grade 50 mm dia as per IS 694complete all as specified and directed Make : Finloex/Havells/Polycab |
79 | Supply & fixing in replacement single phasing preventer type VSP2 complete all as specified and directed by Engr-in-Charge.(Make:- Minilec/ L&T/ Siemens/Legrand/ ABB/ C & S.) |
80 | M & L in replacement of unserviceable 3 way modulating motorized valve with Teflon gland, with linear movement actuator 24 V AC input supply, 0-10 V input signal with modulating thermostat & transformerof following sizes completeall as specified and directed. |
81 | 32mm dia |
82 | 65mm dia |
83 | 50 mm dia |
84 | 40 mm dia |
85 | 80 mm dia |
86 | 100 mm dia |
87 | Supply and fixing in replacement Water temperature sensor suitable chiller units of 270 TR as per existing model and makecomplete all as specified and directed by Engineer-in-Charge. |
88 | Supply and fixing in replacement Air Vent valves made out of brass of size 15mm dai for chiller chiller pipe line complete all as specified and directed by Engineer-in-Charge. |
89 | Dismantling the old broken fan hub assembly including blades of cooling tower and replacement with new fan hub assembly with dry cast aluminium blades heavy duty as per existing size including U-clamps, nuts, bolts & washers suitable for cooling tower for 3 x 270 TRcapacity AC Plant complete all as specified and directed by Engineer-in-Charge. |
90 | Disconnecting the defective FRP cooling tower of Cap 270 TR and repair the same by replacing defective broken/unserviceable spare parts including repair to minor leakages & assembling, testing & comminssioning for satisfactory performance complete all as specified & directed by Engr-in-Charge. Note:- (i) Required Spare parts shall be measured and paid seperatly as "Supply only" under item No. 40.01 to 40.09 . (ii) Labour charges for taking down old spares and fixing of new sparesshall deemed to be included in unit quoted rate. |
91 | Supply only of following spare parts for FRP cooling tower complete all as specified & directed by Engr-in-Charge:- |
92 | Eliminator |
93 | PVC fins of size 600mm x 300mm x 165mm |
94 | PVC Pipe 63 mm dia 3 Mtr long |
95 | PVC End Cap 63 mm |
96 | PVC Separator 63 mm dia |
97 | PVC Socket |
98 | PVC End cap 100 mm |
99 | Nut Bolt any size |
100 | FRP Compound Note for item No 40.01 to 40.09 :- (i) Materials of item Nos.40.01 to 40.09 to be incorporated in item No 39 here-in-before. (ii)Labour charge of item Nos.40.01 to 40.09 are deemed to be included in the quoted rate in item Nos. 39 here-in-before. (iii) Make of item Nos.40.01 to 40.09 as approved by Accepting officer. |
101 | Supply and fixing in replacement cast iron Y strainer flenged ends with SS perforated sheet screen of following size complete all as specified and directed by the Engr-in-Charge.(Make: - ADVANCE/ AUDCO/ LEADER/CASTLE/ NVR/ ZOLOTO). |
102 | 100mm dia |
103 | 150mm dia |
104 | 200mm dia |
105 | 32mm dia |
106 | 65mm dia |
107 | 50 mm dia |
108 | 80 mm dia |
109 | Supply and fixing in replacement cast iron butter fly valves lever operated SS disc type nitrile/EPDM rubber lining PN 16 of following size dai complete all as specified and directed by the Engr-in-Charge.(Make: - ADVANCE/ AUDCO/ LEADER/CASTLE/ NVR/ ZOLOTO). |
110 | 300 mm dia. |
111 | 200 mm dia. |
112 | 150 mm dia. |
113 | 125 mm dia. |
114 | 100 mm dia. |
115 | 80 mm dia. |
116 | 50 mm dia. |
117 | 65 mm dai |
118 | Supply, Laying, jointing and testing of under electric cable XLPE insulated, 1100 volt grade heavy duty armoured with stranded aluminium conductor laid in trenches/duct/pipe including all electrical connection with required lugs and nuts, bolts complete all as specified and directed by Engr-in-Charge for the following:- |
119 | 4 core 10 Sqmm |
120 | 4 core 16 Sqmm |
121 | 4 core 25 Sqmm |
122 | 3.5 core 35 Sqmm |
123 | 3.5 core 50 Sqmm |
124 | 3.5 core 70 Sqmm |
125 | 3.5 core 95 Sqmm |
126 | Supply and fixing in replacementmotorized spring return actuator for device with control panel and temprature sensor complete all as specified and directed. |
127 | Supply , installation, testing and commission in replacement of fire dampers complete with smoke detector/ thermister linkage etc and actuator as required for operation complete all as specified and directed. |
128 | Supply and fixing in replecement Acoustic treatment/ lining of area of AHUroom with 22G, GI channels of 50x50 mm size fitted at 600x600mm girds. These girids will be fitted with 50mm thick 32 kg/cum fiber glass insulation covered be fiber glas tissue and 24 G Al perforated sheet and as required . The joint shall be minimium overlapping of 75mm with 30mmx 3mmaluminium strip covering. All corners shall be provided with 20x20x2mm aluminium angle with stainless steel counter sunk screws complete all as specified and directed. |
129 | M&L for control wiring with 4 coreX 4 sqmm , FRLS PVC round insulated and sheathed wire featuring a bright annealed bare copper conductor cable 1100 Volts grade with multi stranded, wire colour black,drawn through concealed conduit including PVC rigid conduit medium grade 32 mm dia as per IS 694complete all as specified and directed. Make : Finloex/Havells/Polycab |
130 | M&L for control wiring with 4 coreX 6sqmm , FRLS PVC round insulated and sheathed wire featuring a bright annealed bare copper conductor cable 1100 Volts grade with multi stranded, wire colour black,drawn through concealed conduit including PVC rigid conduit medium grade 40 mm dia as per IS 694complete all as specified and directed Make : Finloex/Havells/Polycab |
131 | M&L for control wiring with 2 coreX 1.5 sqmm , FRLS PVC round insulated and sheathed wire featuring a bright annealed bare copper conductor cable 1100 Volts grade with multi stranded, wire colour black,drawn through concealed conduit including PVC rigid conduit medium grade 32 mm dia as per IS 694complete all as specified and directed. Make : Finloex/Havells/Polycab |
132 | M&L for control wiring with 2 coreX 2.5 sqmm , FRLS PVC round insulated and sheathed wire featuring a bright annealed bare copper conductor cable 1100 Volts grade with multi stranded, wire colour black,drawn through concealed conduit including PVC rigid conduit medium grade 32 mm dia as per IS 694complete all as specified and directed Make : Finloex/Havells/Polycab |
133 | M & L For Providing,fixing, testing and commissioning in replacement of Duct mounted inline fans ofG.I. construction, complete with centrifugal fan with motor,canvas connection at inlet & outletcomplete as specified and directed of following capacity:- Make : Otsberg, ZECO, EDGEtech. |
134 | 600 CFM, 15 mmwg static pressure. |
135 | 1200 CFM, 15 mmwg static pressure. |
136 | 2000 CFM, 15 mmwg static pressure. |
137 | Supply and fixing in replacement bakelite terminal plate of 6 way including brass studs, bolts and nuts etc suitable to match any make of 3 phase electric motors and capacity up to 30 HP complete all as specified and directed by Engr-in-Charge. |
138 | Supply and fixing in replacement thermometer suitable for condenser water line with suitable housing for mounting on pipe line 0-50°C complete including taking down old unsv thermometer all as specified and directed by Engr-in-Charge.( Make :- Indfoss/ Renutrol). |
139 | Supply and fixing in replacement Compound pressure gauge (Discharge pressure) of size 100 mm dia suitable for 0 to 300 PSI complete including taking down old unsv pressure gauge all as specified and directed by Engr-in-Charge. Make: Adarsh/Febic/ H guru |
140 | S&F in repair Exhaust AHU Fan complete section with DIDW centrifugal curved fan, Fan selected for follwing CFM, FC type ,suitableas per existingmm Fan dia, RPM speed, Fan outlet velocity,kw shaft absorbing powerwith completedrive set & V-belt installedas per existing exhaust AHU with base frame and connected nutbolts and accessories all as per specified & directed by Eng-in-charge. FAN Make:- Kruger/nicotra |
141 | Upto 4000 CFM |
142 | Upto 10000 CFM |
143 | Supply and fixing in replacement indicator lamp assembly complete LED type suitable for the existing system supply voltage 230V / 440V ACcomplete all as specified and directed by Engr-in-Charge. (Make:- MIMIC CONTROL/ GE CONTROLS / RR MICRO / L&T / SIEMENS/ BCH/ SCHNEIDER) |
144 | Supply and topping up Compressor Oil RL-170 H complete all as specified & directed by Engr-in-Charge. (Make:- HPCL(Seetal)/ HP (Seetal)/ Servo.) |
145 | Material and labourfor servicing of Exhaust AHU of capacity up to 10000 CFM including cleaning of bottom tray and with air pressure to sweep up all the particles andchecking aligning and tightening of blower fan, greasing of all movable parts, replacement of worn out bolts, nuts shaft keys etc all as directed and specified by engineer in charge. |
146 | Supply and fix in replacementGalvanised iron strip 32X6 mm as earth continuity conductor including fixing arrangement on suitable size insulator complete all as directed. |
147 | M&L earthing complete with GI plate electrode of size 600 x 600 x 6 mm thick bured directly in ground vertically at a depth not less 2.25 mtr below normal ground level with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level surrounded from all sides by 1.5 cm thick packed layer of charcoal of dust and common salt filling in alternate layers and making electrode connection by using GI strip of size 32X6 (up to 7 meter GI strip included) mm by means of bolts nuts check nuts and washers made of brass and earth strip protected by light grade 40 mm dia GI Pipe upto test point and connected to main switch board are main controlled board with provision of GI pipe medium grade 20mm bore for watering including funnel wire mass RCC pit cover and PCC Chamber pit with 1:2: 4 type C2 (including excavation earth work) all as specified and shown on plate No 5 of SSR Part-1. |
148 | Supply, install, testing and commissioning in replacementof Duct insulation with 25mm thick Nitrile Rubber insulation of class "o" fire retardantwithMechanicalprotection over insulation with fiber glass cloth & UV paint (for exposedduct) for Ducts installed outside, (exposed to sunlight) complete all as specified and directed by the Engineer-in-charge. |
149 | Supply and fixing in repair MCB TP 63 Amps, capacity 10 KA, C curve including taking down old unsv one complete all as specified and directed by Engr-in-Charge (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.) |
150 | Supply and fixing in repair MCB TP 40 Amps, capacity 10 KA, C curve including taking down old unsv one complete all as specified and directed by Engr-in-Charge (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.) |
151 | M&L for preparation of surfaces of Cenral AC Plant of capacity 3 x 270 TR at Manekshaw Centre for painting of trap door, condensers,chillers,compresors, Induction motors, pumps, hot water boiler, C channels, all pipe lines, valves and outer body of cooling towers and AHU"s with different colors following the color code system as directed by the site-in-charge.Job includes removing the old paint by rubbing, brushing and applying one coat of red oxide zinc chrome primer and two coats of Synthetic Enamel Paint (1st grade quality) complete all as specified and directed by the Engr-in-Charge. (Make of paint and primer:- ASIAN/ BERGER/ JHONSON & NICHOLSON/ SHALIMAR.) |
152 | Supply & fixing MCCB 4 Pole of capacity 100 Amps, 50 Hz, 415V with rupturing capacity of 25 kA with thermal magnetic release including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.) |
153 | Supply & fixing MCCB 4 Pole of capacity 63 Amps, 50 Hz, 415V with rupturing capacity of 25 kA with thermal magnetic release including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.) |
154 | Supply & fixing MCCB 3 Pole of capacity 100 Amps, 50 Hz, 415V with rupturing capacity of 16 kA including spreader terminals with taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.) |
155 | Supply & fixing MCCB 3 Pole of capacity 63 Amps, 50 Hz, 415V with rupturing capacity of 25 kA including spreader terminals with taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.) |
156 | Supply & fixing MCCB 4 Pole of capacity 125 Amps, 50 Hz, 415V with rupturing capacity of25 kA including spreader terminals including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.) |
157 | Supply & fixing MCCB 3 Pole of capacity 125 Amps, 50 Hz, 415V with rupturing capacity of 25 kA including spreader terminals including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.) |
158 | Supply & fixing MCCB 4 Pole of capacity 160 Amps, 50 Hz, 415V with rupturing capacity of 25 kA including spreader terminals including taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.) |
159 | Supply & fixingMCCB 3 Pole of capacity 160 Amps, 50 Hz, 415V with rupturing capacity of 25 kA including spreader terminals including taking down old unserviceable one complete all as specified and directed by Engr-in-charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.) |
160 | Supply & fixing MCCB 3 Pole of capacity 200 Amps, 50 Hz, 415V with rupturing capacity of 35 kA including spreader terminals with taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.) |
161 | Supply & fixing MCCB 3 Pole of capacity 250 Amps, 50 Hz, 415V with rupturing capacity of 35 kA including spreader terminals with taking down old unserviceable one complete all as specified and directed by Engr-in-Charge. (Make:- L&T/ Siemens/Legrand/ ABB/ C & S.) |
162 | Supply and fixing in replacement V-belt of size SPA-1120 complete all as specified and directed by Engr-in-Charge. (Make - Feener or equivalent as approved by Accepting Officer.) |
163 | ditto- all as per item No. 75.00 above but size SPA-1750 |
164 | ditto- all as per item No. 75.00 above but size SPA-1850 |
165 | ditto- all as per item No. 75.00 above but size A-1610 |
166 | ditto- all as per item No. 75.00 above but size SPA-1800 |
167 | ditto- all as per item No. 75.00 above but size B-2350 |
168 | ditto- all as per item No. 75.00 above but size A-1630 |
169 | ditto- all as per item No. 75.00 above but size SPB-1320 |
170 | ditto- all as per item No. 75.00 above but size SPA-1550 |
171 | ditto- all as per item No. 75.00 above but size A-2270 |
172 | ditto- all as per item No. 75.00 above but size SPA-900 |
173 | M & L for replacement ofchilled water or refrigerent MS class "C" pipe insulation inside the building but excluding valves/strainers/pr gauges etc and adequately supported on rigid supports and duly insulated withclosed cell elastometric nitrile rubber of class "O" insulation and insulation applied by adhesive confirming to standard OEM specifications secured with 0.63 mmGI sheet cladding complete at the joints and repairing of damage to the buildings if any etc as per specifications and as required complete in all respects.The size of pipes and insulation shall be as shown below:- |
174 | 50 mm Pipe (32mm thick insulation) |
175 | 65 mm Pipe (32mm thick insulation) |
176 | 80 mm Pipe (40mm thick insulation) |
177 | 100 mm Pipe (40mm thick insulation) |
178 | 125 mm Pipe (40mm thick insulation) |
179 | 150 mm Pipe (40mm thick insulation) |
180 | 200 mm Pipe (40mm thick insulation) |
181 | 250 mm Pipe (40mm thick insulation) |
182 | Supply and fixing in replacement 80 mm dia cast iron non return valves of pressure class PN 1.6 including nuts, bolts, washers, gaskets, etc for Central type AC plants complete all as specifed and directed by Engineer-in-Charge.(Make: - ADVANCE/ AUDCO/ LEADER/CASTLE/ NVR/ ZOLOTO). |
183 | ditto- all as per item No. 87.00 above but 100mm dia |
184 | ditto- all as per item No. 87.00 above but 150mm dia. |
185 | Ditto- all as per item No. 87.00 above but 250mm dia. |
186 | Supply, Installation , Testing and commissioning in repair of perfabricated type cable tray of size 45mm wide x 50mm x 1.6mm fabricated out of perforated hot dip galvanized sheet of minimum 1.6mm thick with 50mm flange to be installed horizontally or vertically. The cable tray shall be complete including cost of bends, elbows, cross, tees, reducers etc. site condition and rate shall include cost of anchor fastners, screw, nuts, bolts and misc. and other fixing hardware painting of support structure etc as required complete all as specified and as directed. |
187 | All as per Item No.91.00 above but of size75mm wide x50mm x 1.6mm complete all as specified and as directed. |
188 | All as per Item No.92.00 above but of size150mm wide x50mm x 1.6mm complete all as specified and as directed. |
189 | S&F in replacement of outer body casing panels Factory made Double skin ofExhaust Air Handling unit as specifications as under:-.The front side of AHU panel dimension having casing panels shall be made of sandwich construction of at least 25 mm thick injected with CFC free R141b blended Poly Urethene foam insulation having density of 38-40 Kg/Cu.m and thermal conductivity of 0.02 W/m-deg K. The Casing panels(inside and outside) shall be constructed of 1.2 mm steel sheetcoated with 220 gm/Sq.m galvanized Zinc(Zn) and 3% Chromate.The outer skin shall be 0.6 mm and inner skin 0.6 mm . Material of frame shall beSelf supporting extruded aluminium with thermal break of AHU. The panels are removable type and are fixed to the frame with self tapping screws. Labyrinth type gasket sealing between panel and frame be provided to eliminate air leakages. The front side of AHU panel unit shall be supported on full perimeter base frame constructed from heavy duty galvanized steel sheetwith complete all fittings as per site required as directed and specified by Eng-in-Charge. |
190 | All as per item no. 94.00 but frame work of filters (back side)all fittingsas per specified & directed by Eng-in charge |
191 | All as per item no.94.00 but for side panel (left/ Right) (widthXheight). |
192 | All as per item no.94.00 but for side panel (left/ Right) (widthXheight) with the AHU door opening shall be interlocked with micro switch ( AHU motor is trip when door is open)directed&specified by Eng-in-charge. |
193 | All as per item no.94.00 but for panel (top side) (lengthXwidth) and all fittings with space for top duct as per existing, directed&specified by Eng-in-charge. |
194 | All as per item no.94.00 but fforpanel (bottom side) (lengthXwidth) directed&specified by Eng-in-charge. NOTE:-The exhaust AHU shall be suitable for conventional floor Landing(with vibration pads)with all accessories and controls for AHU (Antivibration with spring mechanisim set of four) |
195 | M&L for Supply, fixing of powder coated extruded aluminum rectangular diffusers complete with black anodized extruded aluminum VCD (wherever specified), nuts, bolts, screws etc.complete as required at site all as specified and directed by engineer-in-charge. |
196 | (a) Supply air diffusers of required sizes with volume control damper. |
197 | (b) Return air diffusers of required sizes without volume control damper |
198 | M&L for Supply & Fixingofpowder coated extruded aluminum supply & return grilles complete with nuts, bolts, screws etc. to make the system complete, as required at site all as specified and directed by engineer-in-charge. |
199 | M&L for Supply and installation in replacement of thermal insulation material for non-exposed Ducts with closed cell class o nitrile rubber elastomeric insulation of density 40-60 Kg/m3 thermal conductivity of 0.033-0.038 W/mk and µ>=7000 (k-flex st) to be applied on ducts using manufacturers recommended rubber based adhesive as per the approved specification the material shall be from global approved complete all as specified and directed by engineer-in-charge. |
200 | (a) 19 mm thick |
201 | (b) 25 mm thick |
202 | M&L for Supply, installation, testing and commissioning in replacement of flexible fire retardant canvas connector cloth including flanged from both side with inspection chain in it removing of old one complete all as specified and directed by Engineer-in-charge. |
203 | Supplyand fixing in replacementrubber mat LT 1.1KV volt grade 1mtrx 2mtr x 10mm |
204 | Supply & fixing PVC insulated single core copper conductor cable of size 16 sqmm for connections in LT Panels including copper thimbles including taking down old unserviceable onecomplete all as specified and directed by Engineer-in-Charge.(Make:- RR KABEL./ FINOLEX/ POLYCAB/ KEI INDUSTRIES LTD./ HAVELLS.) |
205 | Supply & fixing PVC insulated single core copper conductor cable of size 25 sqmm for connections in LT Panels including copper thimbles including taking down old unserviceable onecomplete all as specified and directed by Engineer-in-Charge.(Make:- RR KABEL./ FINOLEX/ POLYCAB/ KEI INDUSTRIES LTD./ HAVELLS.) |
206 | Supply & fixing in replacement aluminium lugs for cable of cross sectional area 10 Sqmm complete all as specified and directed by Engineer-in-charge. |
207 | Supply & fixing in replacement aluminium lugs for cable of cross sectional area 16 Sqmm complete all as specified and directed by Engineer-in-charge. |
208 | Supply & fixing in replacement aluminium lugs for cable of cross sectional area 25 Sqmm complete all as specified and directed by Engineer-in-charge. |
209 | Supply & fixing in replacement aluminium lugs for cable of cross sectional area 35 Sqmm complete all as specified and directed by Engineer-in-charge. |
210 | Supply & fixing in replacement aluminium lugs for cable of cross sectional area 75 Sqmm complete all as specified and directed by Engineer-in-charge. |
211 | Supply & fixing in replacement aluminium lugs for cable of cross sectional area 95 Sqmm complete all as specified and directed by Engineer-in-charge. |
212 | Supply & fixing in replacement aluminium lugs for cable of cross sectional area 120 Sqmm complete all as specified and directed by Engineer-in-charge. |
213 | Supply & fixing in replacement copper lugs for cable of cross sectional area 10 Sqmm complete all as specified and directed by Engineer-in-charge. |
214 | Supply & fixing in replacement copper lugs for cable of cross sectional area 16 Sqmm complete all as specified and directed by Engineer-in-charge. |
215 | Supply & fixing in replacement copper lugs for cable of cross sectional area 25 Sqmm complete all as specified and directed by Engineer-in-charge. |
216 | Material and labour for maintenance of AHU supply panel / feeder pillar/LT panel indoor/outdoor type including removing the carbonized/melted sparked thimbles, cleaning the carbonized bus bar making cable ends fresh and supply and crimping new thimbles/lugs and fixing the cable on bus bar/MCCB/Main switch/MCB including providing new nut bolts and washer if required greasing the doors of feeder pillar/LT panel outdoor/indoor type complete all as specified & directed by Engr-in-Charge. |
217 | Attending complaint of control panel wiring and making it fully serviceable with and including PVC tape, PVC tie, Nut bolt, and other items complete all as specified and directed. Notes: - After intimation ofbreakdownby Engineer in Charge/JE E&M through telephone or verbally, the contractor shall arrange theMechanic to attend the complaint within 2 hours and make the plant functional.If contractor failed to attend complaint with in time frame, a penalty of Rs 400/- per Hrs per complaint shall imposed on contractor and shall be recovered from contractor"s dues |
218 | Cleaning of inside surface of supply ducts of HVAC (minimum open area of duct 1.00Sqm and maximum area 16.00Sqm) system of any area using high power vacuum air compressor robotic camera, air hammer, special nozzles, air sweep with other required accessories given/showing inspection of dust before and after cleaning of duct using colour video inspection complete all as specified & asdirected by Engineer-in-Charge. |
219 | M & L for servicing of LT ACB 1600 Amps, 1200 Amps or 600 Amps draw out type 415 volts, 50 Hz, brushing, greasing and tightening of nuts and bolts fixed and movingcontacts for smooth functioning and replacing of minor accessories complete all as specified and directed by the Engr-in-Charge. |
220 | M&L for disconnecting & opening of all parts of Package type Air Washer of capacity 7200 CFM installed at the roof top of Manekshaw Centre and servicing,repairing & Overhauling for satisfactory working condition complete including Motor , Blowers , Pumps Fill pad Aluminium chasing etc.And refixing the same after servicing and testing complete including replacement of the following parts:- |
221 | Blower unit |
222 | Motorof capacity 5 HP, 1440 RPM |
223 | Pump 1/4 HP |
224 | Fill Pad 200 mm thick |
225 | Double Skin |
226 | Aluminium Chasing |
227 | Filter Wire Mesh |
228 | Water Tank SS 304 Note for item No 121.01 to 121.08 :- (i) Materials of item Nos.121.01 to 121.08 to be incorporated in item No 121.00 here-in-before. (ii)Labour charge of item Nos.121.01 to 122.08 are deemed to be included in the quoted rate in item Nos. 121.00 here-in-before. (iii) Make of item Nos.121.01 to 121.08 as approved by Accepting officer. |
229 | M & L in repair of site fabricated GSS Sheet metal, rectangular/round ducting complete with neoprene rubber gaskets,elbows,splitter damper vanes,hangars,supports as per approved drawings and specifications of following sheet thickness complete |
230 | 0.63 mm thickness sheet (24 gauge) |
231 | 0.80 mm thickness sheet(22 gauge) |
232 | Inspection, checking, cleaning, testing and commissioning of fire alarm cum fire detection system complete including fire detectors, smoke detectors, heat detectors, response indicators, wiring etc. through trained/experianced technician of OEM, the system and carry out planned maintenance in systematic and controlled manner at Manekshaw centre building complete except new server room all as specified and directed by Engineer-in-charge. |
233 | Notes for Serial item No. 123.00 (a) Fire Alarm control panel:- These shall be kept clean by checking for its controls, indicating equipment’s system and all operations/fault indicators including checking of panel circuits for its healthiness and including of healthy battery/UPS/battery charger system. (b) Smoke Detectors &Fire Detectors: - All smoke/fire detectors shall be removing dust/dirt accumulated on them due to local ambient conditions. These shall be tested & cleaned once in a quarterly and report shall be maintained as directed by Engineer-in-Charge duly signed by user and concerned JE/Engineer-in-charge. (c)Response Indicators, Manual Call Point and Hooter:All items which are installed inside a cabin, room or above ceiling shall be tested by actuating the particular detectors every quarterly so as to ensure proper functioning of indicator. (d) Wiring and cables:Complete wiring shall be inspected jointly by contractor, MES rep and users so that structure or occupancy changes doesn"t damage the cable/wiring/trigger device (Manual call points smoke heat ionization detector etc) (e)During attending complaint and quarterly maintenance check any spares/items required forreplacemnet will done by the technician of OEM (i.e detectors, panels, response indicators, hooters wiring, battery) (f) Quarterly maintenance schedule submit by the contracor to the Engineer-in-Charge for his approval before going to the quarterly check. |
234 | (g) Deployed Technician/mechanic fully equiped with necessary tools and plants are deemed to be included in the quoted rate. (h) Arrangement of testing equipment provided by the contractor deemed to be included in quoted rates. (i) The mechanic shall also be in possesion of mobile and two wheeler for communication and mobility. (j) The contractor deemed to have visited the site and seen the scope of work before quoting the rates. (l) Quarterly inspection test report will be submitted to deptt duly signed by user/ Engr-in-Charge. (m) Mock drill will be conducted once in quarterlyin presence of user after completion of cleaning and testing. (n) Adequate manpower shall be deployed at site to carried out for quarterly maintenance check as per CA provision. (o) All the work mentioned in notes above are deemed to be included in the quoted rates. (p) The rates for making necessary arrangement of scaffaolding/ ladders is deemed to be included in the quoted rates. (q) Any damage to smoke and fire detection system during maintenance shall be repaired by the contractor at his own cost. |
235 | Checking and attending day to day complaints by means of finding the faultsonlyrelated to fire alarm, detectors, hooters, response indicators, wiring and all other accessories and fixtures maintained by the department complete all as specified and directed. NOTE :- (i) The rate of this item are included for attending of complaints only. (ii) Taking down of unserviceable materials and fixing of new materials will be measured and paid seperately under relevent items as mentioned in Section-IV here-in-after. (iii) Complaints shall be attend any time from user/MES rep without fail, failing which recovery of rate Rs 1000/- per complaint shall be effected from the RARs/FB. (iv) Minor materials such as PVC wire of any size as per requirement upto 1.0 mtr length, thimble, electric tape, fixing accessories, etc shall be deemed to be included in the quoted rate of this itmes. (v) The complaints shall be attend and defects shall be rectified within 08 Hrs commencing from date and time of notifing the complaint, failing which a penauly Rs 1000/ per complaint shall be leived/imposed on the contractor and recovery shall be made from his dues. (vi) Contractor shall be arrange suitable T&P incl necessary ladder and scaffolding for approach and safety measures to make it functional complete all as specified and directed. The rates for which are deemed to be included in the quoted rate. |
236 | Supply and fixing of Multi Detector, optical type low current draw, wide operating voltage 8 to 30 VDC, Bi-colour LED detector status indicator, Automatic drift compensation, tested and approved to EN54 - 7:2000 (Amendment 1)including taking down old unserviceable one complete all as specified and directed by Engineer-in-charge. (Make: APPOLO / EDWARD / SEIMENS/HONEYWELL). |
237 | Supply and fixing of response indicators with MS Box 16 SWG and plastic coverincluding taking down old unserviceable one complete all as specified and directed by Engineer-in-charge. (Make: APPOLO / EDWARD / SEIMENS/AGNI). |
238 | Supply and fixing of maintanance free battery 7 AH, 12 Volts with 8 Hours backup and 12 months warrantyincluding taking down old unserviceable one complete all as specified and directed by Engineer-in-charge. (Make:- EXIDE/ AMARON/ STANDARD FURKKAVA) |
239 | Supply and fixing of PVC conduit pipe medium grade size of 25mmincluding taking down old unserviceable one complete all as specified and directed by Engineer-in-charge. (Make- Kalinga/ Polycab/Finolex/ Havells/ Anchor). |
240 | Supply and fixing of multi-stranded copper conductor cable 1.5 Sq. mm nominal cross-sectional area, two core, PVC insulated and unsheathedFRLSH cable 1100 volts grade for sub main wiringincluding taking down old unserviceable one complete all as specified and directed by Engineer-in-charge. (Make- Havells/Polycab/Finolex/ RR Kabel) |
241 | Supply, fixing, commissioning and testing of Microprocessor based 6 loop capacity , Networkable analogue addressable type fire alarm control panel with 640 character LCD display. The panel shall be equipped with sufficient numbers of loop with 20% spare capacity with each loop shall have a capacity of minimum 159 detectors and 159 analog addressable devices in one loop. Four access levels, capable of taking Flash Scan devices, flash EPROM sufficient numbers of programmable relay controls for controlling AHUs, pressurization fans, ventilation fans at fire pump room, monitoring of fire sprinkler and fire hydrant pump, 240 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as requiredincluding taking down old unserviceable one complete all as specified and directed by Engineer-in-charge.(UL 9th Edition Approved) (Make - NOTIFIER/CPU2-3030D/WITH 6 LOOP/WITH NCM-W) |
242 | Material and labour for rectification, maintenance of addressable zones, searching the faults, up/down loading software of main control panel at Manekshaw center and reprogramming entire system and testing by authorized Technical Engineer of OEM complete all as directed by Engr-in-charge. and including Inspection, testing and commissioning of complete fire alarm system installed done by authrized OEM of Honywell manufacturer only all as required complete all as specified and directed by Engineer-in-charge. |
243 | Supply, fixing, commissioning and testing of automatic Floating Sensitivity type Analog addressable Acclimate Photo thermal smoke detector with mounting based LED, Address Switch from 01-159 , to programme the detectors, complete as required. (In Changing Environment Area) ul- 7th editionincluding taking down old unserviceable one complete all as specified and directed by Engineer-in-charge. (Make: - NOTIFIER/ GST/APPOLO/ EDWARD/HONYWELL). |
244 | Supply, fixing, commissioning and testing of analog addressable Rate of Rise Cum Fixed temperature detector with mounting based LED, Address Switch from 01-159 , to programme the detectors complete as required. Ul- 7th editionincluding taking down old unserviceable one complete all as specified and directed by Engineer-in-charge. (Make: - NOTIFIER/ GST/APPOLO/ EDWARD/HONYWELL). |
245 | Supply,fixing,testing and commissioning of addressable type fault for isolating module shorted, dewired and loose circuits between two successive fault isolators with automatic resetting arrangement (base Model)including taking down old unserviceable one complete all as specified and directed by Engineer-in-charge. (Make: - NOTIFIER GST/APPOLO/ EDWARD/HONYWELL). |
246 | Supply and fixing of addressable control modules for Hooters / Sounders / Strobes etc. including taking down old unserviceable one complete all as specified and directed by Engineer-in-charge. (Make : - NOTIFIER/ GST/APPOLO/ EDWARD/HONYWELL). |
247 | Supply and fixing of Strobe Lights Cum Hooter with 110 cd. The strobes shall be synchronized for better evacuationincluding taking down old unserviceable one complete all as specified and directed by Engineer-in-charge. (Make:- NOTIFIER/ GST/APPOLO/ EDWARD/HONYWELL). |
248 | Supply and fixing of manual call pointincluding taking down old unserviceable one complete all as specified and directed by Engineer-in-charge. (Make: - NOTIFIER/ GST/APPOLO/ EDWARD/HONYWELL). |
249 | Supply and fixing in replacement oflinear BEAM type smoke detectorconsistingof a combined transceiver unit and an accompanying reflector which is to be fitted with all technical specifications as under :- |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy