| 1 | S&F PT 33 KV outdoor type single Phase oil cooled PT of ratio 33/rt3/110/rt3/110rt3 class 0.50-3, burden 50 VA, insulation level 70/170 KV voltage factor 1.2 Cont and 1.9 for 30 second confirming to IS 3156 including taking down old unserviceable PT complete all as specified and directed including taking down existing old unserviceable PTcomplete all as specified and directed. |
| 2 | M&L forattending fault/ breakdown in HT Over Head line /Breaking UG Cable due to any reason like falling of tree branches, Bird hits, Cracking of Pin/ Disc insulator, breaking Over Head conductor complete including patrolling of LT line, Meggering, removing of fault, replacement of insulator any type, replacement offuses and restoring the feeder complete all as specified and directed for following areas :-Notes : (i)All T&P required to complete job is included in unit rate. (ii)Unit rates also included the conveyance & communication facilities requiredto complete the job. |
| 3 | MH feeder (Approximate 8 KM go and back ) |
| 4 | New Cantt feeder (Approximate 12 KM go and back ) |
| 5 | Upper Camp feeder (Approximate 10 KM go and back ) |
| 6 | Mall Road feeder (Approximate 6 KM go and back ) |
| 7 | RIMC feeder(Approximate 5KM go and back ) |
| 8 | Birpur feeder (Approximate 9 KM go and back upto Bijapur PH ) |
| 9 | Ganghora feeder (Approximate 3 KM go and back upto Seven Oak school) |
| 10 | M&L attending fault/ breakdown in HT Over Head line/ HT UG Cable/Service connection Cable/AC Connection due to any reason including removing of fault, and restoring the electric supply complete all as specified and directed.(Except Birpur Ganghora Area)Notes :(i)All T&P required to complete job is included in unit rate. (ii) Unit rates also include the vehicle 4 wheeler/two-wheeler required to complete the job and minor spares like thimbles, leads jumpers etc |
| 11 | M&L for spraying of agricultural based chemical inside the installation to control the growth of unwanted herb, shrubs etc including cutting, removing the vegetation growth & surface dressing all around the installation yard/ transformer /LT panel Board area external only to keepinstallation always clean and tidy condition complete all as specified and directed.Note:- All the installation yards/area shall be kept clean throughout contract period by repeatedly removing the grass / shrubs as many times required depending on the growth of grass measurement will be measured & paid only once throughout contract period complete all as specified and directed. |
| 12 | S&F station class type lightning arrestor suitable for 33 KV discharge current 65 KAfixed on existing steel structure including connection with earth strip conforming IS 3070 (Part -3) 1983 Class \"A\"complete all as specified and directed including taking down existing old unserviceable complete all as specified and directed. |
| 13 | S&F of Insulator pin type porcelain vitreous, white brown or green 150mm height and 150mm dia including one galvanized mild steel spindle, two galvanized washers and one galvanized iron nutfor conductor working pressure 33000 volt grade complete all as directed including disconnection and taking down existing lightning arrestor complete all as specified and directed. |
| 14 | M&L for shifting of existing VCB 11 KV indoor type panel having two incoming bus coupler bus riser and four outgoings from MRS Anarwala to MRS Garhi Cantt on newly constructed duct including disconnecting of elect connections, dismantling of bus bar including lifting with crane loading unloading including transportation etc and re fixing, connection, installation testing and commissioning to get satisfactory results at new location complete all as specified and directed. |
| 15 | M&L for servicing 33 KV yard structure complete including replacement unserviceable jumper, sleeves vice type conductor, bolt nut and washers connecting lugs / thimble knife contact, applying petroleum jelly to the moving as well as fixed contacts tightening all the connection for its smooth functioning preparing old painted surface of this structure such as poles, cross arms, bracing supports, clamp and back plate complete painting of two coats of anti corrosive weather proof heat resistant aluminium paints over a coat of red oxide zinc chrome primer and providing Red/Yellow andBlack paint including writing SM/MES NO or all other direction/marker/code etc. with grey/black paint on boards etc. not less then 40mm height & 10mm thick complete all as specified and directed. Note: No extra payment will made for the spares required to keep the yard structure in satisfactory functional throughout contract period other than given in schedule. |
| 16 | Supplying in replacement of existing unserviceable control cable includinglaying or fixing with saddles or cable tie etc, jointing and testingLT PVC insulated copper conductor armoured electric power cable ISI marked with multi stranded copper conductor heavy duty 1100 volts grade of 2.5 Sq mm 4 corecomplete all as specified and directed. |
| 17 | All as per item No 9 here -in-before but 2.5 Sqmm 6 core complete all as specified. |
| 18 | Supply & filling the new transformer oil of rupturingcapacity 50KV for 60 Sec for topping up to required level of transformer complete all as specified and directed. |
| 19 | Supply and fix transformer breathers transparent of standard size suitable for 5 MVA transformers 33/11 KV volts cast alluminiumtransparent typeincluding removing the existing unserviceable one complete all as specified and directed. |
| 20 | M&L Filtration/dehydration of the existing transformer oilat site of any make of transformer and capacity up to required dielectric strength as per IE rules and refilling in the transformer up to required level complete all as specified and directed. (The dielectric strength shalld not be less than 50 KV after filtration process) |
| 21 | M&L for replacement of old unserviceable LT studs of transformer any type or size including taking out transformer oil opening up of top lid and replacement of unserviceable studs including top up of oil replacement of gasket etc and making transformer leak proof complete all as specified and directed. |
| 22 | Material and labour for fault detection in UG HT cable of any size ortype at any depth with fault locator including material T&P required for the same and testing complete all as specified and directed.Note 1- Joint, excavation for layingof cable shall be measured and paid separately.2. Each fault shall be treated as one job and contractor have to attend the said fault immediately. |
| 23 | Taking out of HT cable 33 or 11 KV of any size from ground or poles etc and testing for serviceability and kept aside for reuse including proper rolling, loading unloading, transportation etc complete all as specified and directed. Note:- Earth work for the same shall be measured and paid separately. |
| 24 | Laying only of existing serviceable cable 33 or 11 KV in ground retrieved against item No 16 here and before complete including unrolling, unloading, transportation etc testing connections complete all as specified and directed. |
| 25 | M & L for under ground XLPE insulated, screened, PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 volts (earthed) grade copper sheet wrapped cross sectional area 95 sqmm 3 core including taking down of old unserviceable cable complete all as specified and directed. |
| 26 | All as per above item No 18 here-in-above but 11000 Volts 120 Sqmm 3 core. |
| 27 | All as per above item No 18 here-in-above but 11000 Volts 185 Sqmm 3 core |
| 28 | M & L for cable end jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 120 to 185sqmm including testing after jointing complete all as specified & directed. |
| 29 | All as per Item No 21 here-in-before but 11 KV 240 to 300 Sqmm indoor type complete all as specified. |
| 30 | M & L for cable end jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 120 to 185sqmm including testing after jointing complete all as specified & directed. |
| 31 | All as per Item No 23 here -in-before but 11 KV 240 to 300 Sqmm outdoor type complete all as specified. |
| 32 | M & L for straight through cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 120 to 185 sqmm including testing after jointing complete all as specified & directed. |
| 33 | All as per Item No 25 here -in-before but 11 KV 240 to 300 Sqmm outdoor type complete all as specified. |
| 34 | M&L for transformer cable boxes or LT panel board cover/ panel doors etc made out of 3.0 mm CRCA sheet duly powder coated complete to make the system safe and secure complete including making hole nut bolts washer etc all as per site requirement complete all as specified and directed. |
| 35 | Dismantling and taking out old unserviceable cross arms and M&L for cross arms, bracing, supports clamps back plates, gantry bay structure etc fabricated from structural steel section such as suitable I section channel ISMC angle iron and flat iron GI nut, bolt & Washers with welding, cutting, drilling hole etc for insulator bolts clamps in any shape and size including one coat of red oxide and two coats of epoxy heat resistant paint all complete all as specified and directed. |
| 36 | Dismantling existingsteel poles/ struts, any size carefully for reuse including necessary excavation demolition of concrete shifting cost etc. and removing the old unserviceable rubbish etc complete all as specified and directed. |
| 37 | Fixing only of steel poles of any length and dia retrieved against respective item of demolition / dismantling includingloading, shiftingunloading erection in true vertical position complete all as specified and directed. Note - Excavation and PCC shall be measured and paid separately. |
| 38 | S&F disc type insulator (single disc assembly) porcelain vitreous, white brown or green 145 mm height and 255 mm dia ball and socket type with tension clamp galvanized iron nutfor conductors working pressure 11000 volt grade complete including disconnection and taking down existing insulator complete all as specified and directed. |
| 39 | S&F Insulator pin type porcelain vitreous, white brown or green 150mm height and 150mm dia including one galvanized mild steel spindle, two galvanized washers and one galvanized iron nutfor conductor working pressure 11000 volt grade complete including disconnection and taking down existing insulator complete all as specified and directed. |
| 40 | Taking down of GOD vertical/Horizantal mounted including insulator and opening mechanism forservicing repair or replacement to existing GOD switch with DO fuse of any size complete all as specified and directed. |
| 41 | M & L for switch Air break gang operated triple pole out door type 11 KV 50 cycle AC(GOD) suitable for current rating upto 200 Amps mechanically operated mounted on silicon rubber insulators (9 insulators) and frame with operating mechanism from ground level with earth switch and including locking arrangement complete all as directed. |
| 42 | Material and labour for fixing only of existing GOD any type or size after repairincl replacement of blades bushings etc complete all as specified and directed. |
| 43 | M & L for lightning arresters silicone rubber type 12 KV grade complete with all fittings, station class, discharge capacity 65 Kilo Amps complete all as specified and as directed including taking down old unserviceable lightning arresters complete all as specified and directed. |
| 44 | S&F insulator pin type porcelain vitreous white, brown or green LT 1100 Volt including 01 galvanized M.S.spindle, two galvanised iron washers and one galvanised. iron nut of size 100mmx65mm all as specified and directed by E-in-charge including disconnection and taking down existing insulator complete all as specified and directed. |
| 45 | Supply and fixing shackle type insulator porcelain vitreous LT 1100 Volt 100x115mm including G.I. mild steel strip at 31 x 6 mm 12mm diainsulator bolts, washers, nuts suitable for working pressure 1.1KVincluding disconnection and taking down existing insulator complete all as specified and directed. |
| 46 | S&F of oval shape min 65 mm dia or higher size cable route indicators HT or LT made out of cast iron and fixed on 25 mm equal angle of 45 cm long complete including grouting the same in PCC complete all as specified and directed. |
| 47 | M&L for Trimming/ pruning of tree branches up to 5 metersabove & below andboth sides to obtain clearance all around the LT over head lines / HT over head linesconductor upto 5 mtr from furthest conductor on pole including removing of cut branches and cleaning of site complete all as specified and directed. |
| 48 | M&L for painting to existing 4 pole structure including pole, cross arm, bracing clamps, GO DO fuse etc with 2 coat of heat resistance aluminium paint above coping complete all as specified and directed. |
| 49 | All as per item No 41 here -in-before but 2 pole structure complete all as specified. |
| 50 | Taking down out door CTs & PTs from MRS Garhi Cantt, carefully duly disconnecting the existing connection with out damaging any other connection parts deposit to MES store yard,complete all as specified. |
| 51 | Supply in replacement, Install, Testing and commissioningof 33 KV, single phase, out door oil cooled CT of ratio 400/5- 5 Amp, class 1.0 / 5P10, burden 15 VAcomplete all as specified and directed. |
| 52 | S&Fin replacement of SCADA compatible Outdoor Type Marshalling Box (suitable for 5 MVA 33/11KV OLTC Transformer)having OTI, WTI, TTB, Heater, Lamp, Door Switch & Control MCB. Control wiring from Marshalling Box to VCB will be done by contractor including supplying & laying of control cable of 2.5 sq. mm size complete all as specified.. |
| 53 | M&L Complete servicing/overhauling of On Load Tap Changer & replacement of burnt / damaged wiring,complete all as specified. |
| 54 | Taking downRTCC Panel fromMRS Garhi Cantt, carefully duly disconnecting the existing connection with out damaging any other connection parts deposit to MES Store yard, completeall as specified. |
| 55 | Supply in replacement, Install, testing & Commissioning of SCADA compatible Indoor Type Compact RTCC Panel (suitable for 5 MVA 33/11KV OLTC Transformer)having Automatic Voltage Regulating Relay (AVR) model ITE-501 or equivalent, Tap Position Indicator, Push Buttons, Selector switch for Auto & Manual, TTB, Heater, Lamp, Door Switch & Control MCB. Control wiring from On Load Tap Changer (OLTC) to RTCC Panel will be done by contractor including supplying & laying of control & power wiring, complete all as specified and directed. |
| 56 | Supply and laying in replacement synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified. |
| 57 | M&L attending fault/ breakdown in LT Over Head line/ LT UG Cable/Service connection Cable/AC Connection due to any reason including removing of fault, and restoring the electric supply complete all as specified and directed.(Except Birpur Ganghora Area)Notes (i)All T&P required to complete job is included in unit rate. (ii) Unit rates also include the vehicle 4 wheeler/two-wheeler required to complete the job and minor spares like thimbles, leads jumpers etc |
| 58 | M &L disconnecting and taking out old unserviceable damaged/burn out cable of any size & make and supplying, laying, jointing and testing LT underground cable, heavy duty cable ofsize 10 Sqmm 4 Core, 1100 Volts, XLPE insulated and PVC sheathed, armoured, multi-stranded aluminium conductor cable conforming to IS , laid in trenches/ducts or fixed to poles/walls or laid under roads/paths/drains/culverts duly protected in galvanised steel pipe of suitable sizes all bare conductor of cable including cable gland and lugs etc at both endsincl disconnecting and taking out unserviceable damaged cable complete all as specified and directed. Note : Excavation, earth work, cable sand cushioning & cable protection shall be measured separately under relevant items of this schedule. |
| 59 | All as per item No 51 here -in- before but 16 Sq mm,4 core |
| 60 | All as per item No 51 here -in- before but 25 Sq mm, 4 core |
| 61 | All as per item No 51 here -in- before but 50 Sq mm, 3.5 core |
| 62 | All as per item No 51 here -in- before but 95 Sqmm 3.5Core |
| 63 | All as per item No 51 here -in- before but 150 Sqmm 3.5Core |
| 64 | All as per item No 51 here -in- before but 185 Sqmm 3.5Core |
| 65 | All as per item No 51 here -in- before but 300 Sqmm 3.5Core |
| 66 | All as per item No 51 here -in- before but 400 Sqmm 3.5Core |
| 67 | Excavation in trenches in any type of soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of cable, foundation etcand getting out complete all as specified and directed. |
| 68 | Sand cushioning and covering of UG cable using crushed metal sand in trenches for cable protection complete all as specified and directed. |
| 69 | Returning filling in including spreading levelling watering and well ramming in layers not exceeding 25 cm in soil complete all as specified and directed by Engr-In-Charge. |
| 70 | Removing excavated material not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified. |
| 71 | M&L for laying reinforced precast concrete cable cover, Class LV, Type I, flat, size 250 mm x 150mm x 40mm to U/G cable laid dry flat over the cable with width equal to length of the cable and abutting each other with gap between adjacent slab not exceeding 10mm over under ground cable for cable protection in trenches all as specified and directed by Engineer-in-Charge. |
| 72 | Cutting existing road/hardstand of any type by using crow bar chisel uprto adepthof 30 cm for laying GI pipe including making good the surface by returning filling watering ramming in layers 150 mm thick PCC 1:2:4 over 200 mm thick hard core of broken bricks/stones over returning filling watering ramming in layers not exceeding 25 cm thick complete all as specified and directed by Engineer-in-Charge. |
| 73 | M&L for plain cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate in foundation of stay assembly, basisi of pole etc including necessary form work, all as specified and directed. |
| 74 | M&L for plain cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate for coping around poles , including necessary form work finishing even and smooth without using extra cement , completeall as specified and directed. |
| 75 | S & Fin replacement MCCB 4Pole,, 400 Amps, 36 KA, 415 V , with adjustablethermal & adjustable magnetic setting Ics=100% Icu complete all as specified and directed. |
| 76 | All as per item No 68 here in above butMCCB 4Pole, 320 Amps, 36 KA, 415 V |
| 77 | All as per item No 68 here in above but, 250 Amps, 36 KA, 415 V , |
| 78 | All as per item No 68 here in above butMCCB 4Pole, 200 Amps, 25 KA, 415 V |
| 79 | All as per item No 68 here in above butMCCB 4Pole, 160 Amps, 25 KA, 415 V |
| 80 | All as per item No 68 here in above butMCCB 4 Pole, 125 Amps, 25 KA, 415 V |
| 81 | All as per item No 68 here in above butMCCB 4 Pole, 100 Amps, 25 KA, 415 V |
| 82 | All as per item No 68 here in above butMCCB 4Pole, 63 Amps, 25 KA, 415 V |
| 83 | Supply and lay in trenches fixed to poles wall laid in floor GI steel tubing medium grade of following bore including fitting bolt, nut & washers etc or wooden rubber bushing at the ends of complete all as specified and directed incl disconnection and taking down existing tubing complete. |
| 84 | 80mm bore (dia) |
| 85 | 40mm bore (dia) |
| 86 | Taking down existing connection from LT Panel/Bus Bar Chamber/Feeder Piller/ Electric Poles/ Building carefully (any capacity ,any type)carrying out repair work at siteincluding replacement of unserviceable/ defective screw/nut & bolts/ Washers/Lugs/Spreaders/Hinges of doors/Repair to Locks & handles/ Indication Lamps/meters/Cable glands/Bus Bar (Copper/Aluminium)etc, refixing the fittings in its original position, testing and commissioning, including removal of bushes, creapers and trimming of branches around the LT Panel/Bus Bar Chamber/Feeder Piller/ Electric Poles including takingout fixing site complete all as specified and directed .Note:(i)If any major repair is required, attending complaints and replacement of any nature in LT Power network at any point and time, the items shall be replaced with respective item of sch \"A\" is deemed to be inclusive (ii) Tools, ladder, vehiclerequired to carry out the work shall be provided by the contractor.(iii)Contractor will ensure the safety of the workers employed at his own risk.(iv) Contractor shall provided SkilledITI Electrician and Produce theCertificatebefore thecommencment of work. (v) Contractor should ensure torendering completion of all attended complaintsto respective JEs/Engr-in Charge as day to day basis . |
| 87 | Supply and fix, cable jointing kit for straight throughheat shrinkable typejointwith jointing material andall connected accessories suitable forXLPE armoured aluminium conductorcable 1100voltsgrade of size 3.5 core 240 to 300 sqmmincluding taking down of old existing joint complete all as specified,and as directed. |
| 88 | All as per item No 80 here in above but cable jointing kit of size 150 to 185 sqmm |
| 89 | All as per item No 80 here in above but cable jointing kit of size 70 to 120 sqmm |
| 90 | All as per item No 80 here in above but cable jointing kit of size 25 to 50 sqmm |
| 91 | All as per item No 80 here in above but cable jointing kit of size 6 to 16 sqmm |
| 92 | S & Fin replacementmulti functional digital meter module- analog including provision forfor Ammeter, Voltmeter,Analog with selector switch complete all as specified and directed. |
| 93 | S & Fin replacementLED indication Lamps (RYB) complete all as directed. |
| 94 | S&F in repair TPN DB VTPN 4 way 415 Volts, 50 Hz indoor type double door Sheet metal enclosureIP-43 DB\"s flush mounted with 250 Amp Copper busbar for each phase with two neutral bar & two earthbar and cable ties for cable managenment including mounting arrangement for DPX3 MCCB 125 Amps four pole 415 volts as incomer including connection terminal strip complete pre wiredwith suitable size copper conductor. The DB\"s should hold type test certificate (CPRI) as per IEC 61439-3 complete all as specified and directed by Engr-in-charge, Make: Legrand enclosure cat no 5077 45 or eqvt in L&T/Schneider |
| 95 | S&F MCB TPN 63 Amps 10 kA, 430 Voltcomplete all as specified & directed by Engr-in-Charge. |
| 96 | M&L in replacement submain wiring with 6 runs (3 Nos of Phase+Neutal+2 Nos of Earth continuityconductor) of 10 Sqmm single core,PVC insulated, unsheathed,multistranded copper conductorFRLS cable 1100 volts grade, recommended colour code, drawn throughand including surface PVC conduit pipe of medium duty not less than32 mm dia including necessary PVCconduit specials and all wires connecting with suitable size thimbles and taking down old existing submain wiring complete all as directed. (Note:-6 runs of10 Sqmm size PVC copper cable, and one run of PVC conduit shallbe measured as one unit length). |
| 97 | M&L for earthing completewith galvanized iron or steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtrs below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to galvanized iron strip 25x4 mm by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge of (0.68mm) 8 mesh per liner inch, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-Iand specified includingprovision of earth wire protected by 40mm dia medium grade GI pipe and watering pipe shall be 20mm bore medium grade GI pipe, and including all excavation andearth work & connecting the earthing to an earthing test point /transformer nuetral/body/ Lt panel etc. and testing on completion, complete all as specified & directed by Engr-in-Charge. |
| 98 | All as per item No 90 here-in-above but earhing with GI Srip of sixe 32x 6mm, complete all as specified & directed by Engr-in-Charge. |
| 99 | M&L forearthing with Copper electrode chemical advance maintenancefree chemical gel earthing electrode 50mm dia thick buried directly in ground vertically to a depth not less than 2.10 mtr below ground level filled with highly conductive metalic compound mixture CCM with the permanentsealing of the both end, outer dia pipe 50mm with strip terminal 50x6 with terminal holes incl one bag 25 kg of bfc compound, earth connected with earth lead GI wire 4.00 mm dia by means of bolts, Nuts, Check Nuts and washers of galvanized iron and thimbles and other end of the earth wire connected to main switch board protected by galvanized iron pipe medium 15 mm bore, with PCC chamber in cement concrete 1:3:6 type C-2 & 75 mm thick RCC (1:2:4) type B1 cover slab reinforced with 8mm TMT bars 100mm c/c both ways complete all as specified & shown in elect plate No. 3 of SSR part I of 2009 or PVC chamber as per manufacturer instruction and testing on completion.Note: (i) Earthing has to done by CPRI approved firm and if the desired earth resistance is not found within permissible limit shall be redone by contractor at no extra cost.(ii) Cost of GI wire 4 sqmm and 15 mm dia pipe medium grade upto 7.5 mtr is included in the rate quoted for this itemcomplete all as specified & directed by Engr-in-Charge. |
| 100 | M%L for shifting of LT Panel/Bus Bar Chamber/Feeder Piller from the foundation duly disconnectig existing inoming/out going connectioncarefully (any capacity ,any type)and re-installed where ever directed by Engr-in-Charge, duly necessary connectionand PCC foundation and earth work etc complete all as specified and directed |
| 101 | Taking down/dismantling LT Panel/Bus Bar Chamber/Feeder Piller from the foundation duly disconnectig existing inoming/out going connectioncarefully (any capacity ,any type)for caryout repair all as specified and directed. |
| 102 | S&F Rolled mild steel sections as in framing for panel board , stand, cladding, glazing and the like fixed with angle cleats and connecting plates, etc. and fixing conforming to Fe-410-W (Gde-E-250) quality A complete all as specified and directed. |
| 103 | M&L for fabricating MS CRCA sheet of 3mm thick, the inner shell duly compartmented for each control gear, including Powder coating internally and externally the entire steel surfaces.All the cover shall be provided with suitable locking arrangements welded with exisiting panel complet all as specified. |
| 104 | M&L for fabricating and fixing alluminium bus bars of exisiting gauge/size duly connected with existing incoming/outgoing connections complete all as specified. |
| 105 | M&L for 12 Volts 65 Ah SMF maintenance free battery complete all as specified.Make :- Amaron or equivalent to Exide/Luminious. |
| 106 | S&F Cable glands of exisiting gauge/sizeduly connected with existing incoming/outgoing connections complete all as specified. |
| 107 | M&L for painting of LT Panel/Bus Bar Chamber/Feeder Pillar box of any type & size. Removing old paint with emery paper/wire brush, fill the cavilties with metallic putty and made smoth surface, applyone caot of allumiium paint over a coat of metallic primer surface complete all as specified. |