| 1 | Particulars of works for erection of 11KV line with ACSR Weasel Conductor on 9 Mtrs PCC poles |
| 2 | Supply, Erection, Testing & Commissioning of 9 Mtr Long PCC Pole (WL-300Kg) including Transportation to erection site, excavation of pit and back filling of soil & consolidating by ramming, watering etc. |
| 3 | Supply, Transportation, Fabrication & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc. |
| 4 | Supply, Laying & Stringing of ACSR WeaselConductor on Cross arms through insulators including proper binding & twisting with soft Aluminium Wire |
| 5 | Providing & Fixing of PG Clamps for 30mm² ACSR Conductor. |
| 6 | Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 10kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm. |
| 7 | Providing & Fixing of 11kV Polymeric composite Disc Insulator with fitting12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 8 | Providing & Fixing of Galvanized Nuts and Bolts |
| 9 | Providing & Fixing of Danger Plates with Clamps |
| 10 | Providing & Fixing of Anti-Climbing Device with Clamps |
| 11 | Providingof Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip. |
| 12 | Providing & Fixing of Stone Pad (300 mm x 300 mmx 75 mm) |
| 13 | Providing & Fixing of Aluminium Jointing Sleeves |
| 14 | Providing & installationof Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete |
| 15 | Particulars of works for erection & commissioning of Isolation point |
| 16 | Supply, Erection, Testing & Commissioning of 9 Mtr Long PCC Pole (WL-300Kg) including Transportation to erection site, excavation of pit and back filling of soil & consolidating by ramming, watering etc. |
| 17 | Supply ,Fabrication & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc. |
| 18 | Supply, Laying & Stringing of ACSR WeaselConductor on Cross arms through insulators including proper binding & twisting with soft Aluminium Wire |
| 19 | Providing & Fixing of PG Clamps for 30mm² ACSR Conductor |
| 20 | Supply, Installation, Testing & Commissioning of 11 KV GO AB Switch, 3-phase, 3-pole, 400 Amp. |
| 21 | Supply, Installation, Testing & Commissioning of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, line Type |
| 22 | Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 10kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 23 | Providing & Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm |
| 24 | Supply &Fixing of Stay Set with 50 x 8 mm Stay Clamp, Guy Insulator (2 Nos), Anchoring Plate (200 x 200 x 6 mm), Nut & Bolts, 2 No Turn Buckle, 1.8m long, 16 mm diameter solid Stay Rod & 7/3.15 mm dia stranded wire complete |
| 25 | Supply & Fixing of Danger Plates with Clamps |
| 26 | Supply & Fixing of Anti Climbing device with Clamps |
| 27 | Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20 mm, 2.5 Mtr Long through GI Strip(2 nos for PCC poles & ino. For G O Switch/LA) |
| 28 | Providing of Stone Pad 300 mmx300mmx75mm |