Comprehensive Annual Maintenance Contract (Amc) For Electrical Gadgets (Transformer And Stabilizer) Installed At Various Irrigation Cum Dewatering Scheme Fall Under The Mechanical Irrigation Division Shadipora For The Year 2022-23, Ganderbal-Jammu And Kashmir

Irrigation And Flood Control Department-IFCD has published Comprehensive Annual Maintenance Contract (Amc) For Electrical Gadgets (Transformer And Stabilizer) Installed At Various Irrigation Cum Dewatering Scheme Fall Under The Mechanical Irrigation Division Shadipora For The Year 2022-23. Submission Date for this Tender is 24-06-2022. Transformer Supply Tenders in Ganderbal Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

32561993
Corrigendum : Comprehensive Annual Maintenance Contract (Amc) For Electrical Gadgets (Transformer And Stabilizer) Installed At Various Irrigation Cum Dewatering Scheme Fall Under The Mechanical Irrigation Division Shadipora For The Year 2022-23
Open Tender
Indian
Jammu And Kashmir
Ganderbal
24-06-2022

Tender Details

Comprehensive Annual Maintenance Contract (Amc) For Electrical Gadgets (Transformer And Stabilizer) Installed At Various Irrigation Cum Dewatering Scheme Fall Under The Mechanical Irrigation Division Shadipora For The Year 2022-23

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 21-Jun-2022 Extension of Closing Date Date 24-06-2022

Key Value

Document Fees
INR 1000 /-
EMD
INR 15380.0 /-
Tender Value
INR 7.68 Lakhs /-

BOQ Items

Name of Work:Comprehensive Annual Maintenance Contract (AMC) for Electrical Gadgets for variousLift IrrigationCum Dewatering purposes fall under the Mechanical Irrigation Division Shadipora for the year 2022-23
Sl. No. Item Description
1VOLTAGE STABILIZERS Dismantling of 415V 3-ph Voltage Stabilizer by way of opening of top lid, disassembling of voltage regulator, removing of all incoming and outgoing connections, taking out of damaged copper legs after removal of core, etc. The job includes draining out of T. Oil and its safe placement for further refilling >50 upto 100kVA
2>100kVA upto 250 kVA
3greater than 250 kVA
4Assembling of all parts of 3-ph Voltage Stabilizer, connecting of leads of all incoming and outgoing connections and refilling of old drained out of T. Oil >50 upto 100kVA
5>100kVA upto 250 kVA
6greater than 250 kVA
7TRANSFORMER Dismantling of transformer by way of disconnecting of all HT and LT connections, opening of top lid, draining out of T. Oil and its safe placement for further refilling, taking out of coils after removal of core assembly, etc. Job also includes detaching of core HV/LV coils. >50 upto 100kVA
8>100kVA upto 250 kVA
9greater than 250 kVA
10Complete assembling of the transformer by way of fitting of HT/LT coils in the tank. Job further includes closing of the transformer lid by way of fitting of existing nuts/bolts and gaskets. Refilling of t.oil upto required level in tank. Reconnecting of HT/ LT connections and testing. >50 upto 100kVA
11>100kVA upto 250 kVA
12greater than 250 kVA
13VOLTAGE STABILIZERS Rewinding burnt/ damaged windings of voltage stabilizer coil assembly (comprising of three limbs) using superior quality copper wire of proper gauge as per requirement with superior insulation. (Note: The unserviceable scrap copper windings extracted shall be property of the firm and is taken into account for estimation of rates). 100kVA rating
14150kVA rating
15200kVA rating
16250kVA rating
17300 Kva rating
18400 Kva rating
19500kVA rating
20Retapping of existing windings of voltage stabilizer coil assembly (comprising of three limbs) using existing copper wirewith superior insulation. 100kVA rating
21150kVA rating
22200kVA rating
23250kVA rating
24300 Kva rating
25400 Kva rating
26500kVA rating
27Replacement of copper contact point on regulator plate complete job
28Providing and complete replacement of tap changer rotary switch/ regulator (double plate) of voltage stabilizer of nominal size: 18 sq. inch
2916 sq. inch
3012 sq. inch
31Providing and Fitting of HT/LT bush rod as under 25mm
3219mm
3316mm
3412mm
35Providing and Fitting of HTbush cup with washer and ring (25Kva to 630 kva)
36Providing and Fitting of LT insulator as under 25mm
3719mm
3816mm
3912mm
40TRANSFORMER Rewinding of Copper wound 3-Ph 11/0.44kV distribution transformer by way of P/F of HT Cu wound toroidal coils of proper gauge, insulation and separated with proper specification by way of using silicon taping, teflon paper, cork sheet and Bakelite sheets. Complete winding to be done and connections coming out duly insulated. LT windings shall be circular and concentric with HT windings on the outside. The connections shall be connected in delta or star for primary and secondary winding as specified, the neutral with separate insulated terminal. The job also includes decarburising laminated core. The core then firmly fixed with channelled frame to prevent noise and vibration. The arrangement of winding shall made robust in electrical /mechanical construction and should permit free circulation of oil to avoid hot spots. (Note: The unserviceable scrap copper windings extracted shall be property of the firm and is taken into account for estimation of rates). 400kVA rating
41500kVA rating
42Rewinding of Aluminium wound 3-Ph 11/0.44kV distribution transformer by way of P/F of HT Aluminium woundtorroidal coilsof proper gauge, insulation and separated with proper specification by way of using silicon taping, teflon paper, cork sheet and Bakelite sheets. Complete winding to be done and connections coming out duly insulated. LT windings shall be circular and concentric with HT windings on the outside. The connections shall be connected in delta or star for primary winding and secondary winding as specified, the neutral with separate insulated terminal. The job also includes decarburising laminated core. The core then firmly fixed with channelled frame to prevent noise and vibration. The arrangement of winding shall made robust in electrical /mechanical construction and should permit free circulation of oil to avoid hot spots. (Note: The unserviceable scrap aluminium windings extracted shall be property of the firm and is taken into account for estimation of rates). 63kVA rating
43100kVA rating
44200kVA rating
45250kVA rating
46300kVA rating
47Retapping of Copper wound 3-Ph 11/0.44kV distribution transformer by way of tapping existing copperwound LT legs , new insulation and separated with proper specification by way of using silicon taping, teflon paper, cork sheet and Bakelite sheets. Complete winding to be done and connections coming out duly insulated. LT windings shall be circular and concentric with HT windings on the outside. The connections shall be connected in delta or star for primary and secondary winding as specified, the neutral with separate insulated terminal. The job also includes decarburising laminated core. The core then firmly fixed with channelled frame to prevent noise and vibration. The arrangement of winding shall made robust in electrical /mechanical construction and should permit free circulation of oil to avoid hot spots. 400kVA rating
48500kVA rating
49Rewinding of Aluminium wound 3-Ph 11/0.44kV distribution transformer by way of P/F of LT Al woundLegs of proper gauge, insulation and separated with proper specification by way of using silicon taping, teflon paper, cork sheet and Bakelite sheets. Complete winding to be done and connections coming out duly insulated. LT windings shall be circular and concentric with HT windings on the outside. The connections shall be connected in delta or star for primary winding and secondary winding as specified, the neutral with separate insulated terminal. The job also includes decarburising laminated core. The core then firmly fixed with channelled frame to prevent noise and vibration. The arrangement of winding shall made robust in electrical /mechanical construction and should permit free circulation of oil to avoid hot spots.(Note: The unserviceable scrap aluminium windings extracted shall be property of the firm and is taken into account for estimation of rates). 63kVA rating
50100kVA rating
51200kVA rating
52250kVA rating
53300 Kva rating
54Retapping of Aluminium wound 3-Ph 11/0.44kV distribution transformer by way of tapping existing of LT Al woundLegs , new insulation and separated with proper specification by way of using silicon taping, teflon paper, cork sheet and Bakelite sheets. Complete winding to be done and connections coming out duly insulated. LT windings shall be circular and concentric with HT windings on the outside. The connections shall be connected in delta or star for primary winding and secondary winding as specified, the neutral with separate insulated terminal. The job also includes decarburising laminated core. The core then firmly fixed with channelled frame to prevent noise and vibration. The arrangement of winding shall made robust in electrical /mechanical construction and should permit free circulation of oil to avoid hot spots. 63kVA rating
55100kVA rating
56200kVA rating
57250kVA rating
58300 Kva rating
59Providing and fitting of LV (1.1 KV) porcelin bushings of rating: 250 A
60400 A
611000 A
622000 A
633150 A
64Providing and fitting of rubber gasket with nuts and bolts to the transformer tank of rating: 63 Kva
65100-250 Kva
66300-500 Kva
67Dehydration of transformer core(upto 500Kva) in Electrically operated oven
68Credit value of scrap aluminium winidings extrated
69Credit value of scrap copper winidings extrated.
70Providing and fitting of XLPE insulated 1100V single core industrial unarmoured aluminium cable as under (Any Reputed Make) 25 sqmm
7135 sqmm
7250 sqmm
7370 sqmm
7495 sqmm
75120 sqmm
76150 sqmm
77185 sqmm
78240 sqmm
79300 sqmm
80400 sqmm
81Providing and fitting of XLPE insulated 1100V 3.5-core industrial armoured aluminium cable as under (Any Reputed Make)185 sqmm
82240 sqmm
83Providing and fitting of PVC insulated HT aluminium cable
84Providing and laying of ACSR conductor on poles 0.03
850.05 ACSR conductor on poles
86Providing and fitting of XLPE insulated HT Single -core industrial armoured aluminium cable as under (Any Reputed Make) 185 sqmm
87MCCB SWITCHGEAR Providing and fitting of 3-pole 415V MCCB withthermal magnetic release having 50kA breaking capacity (Ics= 100% Icu) (Make: Any Reputed Brand) having max. of thermal release range as under: 160A
88200A
89250A
90320A
91400A
92500A
93630A