Setting Up Semiclean Room Cum Dark Room Facility In Room No 320 ( Main Building-First Floor ) For Mstd In Niist Campus, Trivandrum Setting Up Semi-Clean Room Cum Dark Room Facility In Room No 320 ( Main Building-First Floor ) For Mstd In Nii, Trivandrum-Kerala

Council Of Scientific And Industrial Research-CSIR has published Setting Up Semiclean Room Cum Dark Room Facility In Room No 320 ( Main Building-First Floor ) For Mstd In Niist Campus, Trivandrum Setting Up Semi-Clean Room Cum Dark Room Facility In Room No 320 ( Main Building-First Floor ) For Mstd In Nii. Submission Date for this Tender is 23-05-2022. Building Work Tenders in Trivandrum Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

32219509
Setting Up Semiclean Room Cum Dark Room Facility In Room No 320 ( Main Building-First Floor ) For Mstd In Niist Campus, Trivandrum Setting Up Semi-Clean Room Cum Dark Room Facility In Room No 320 ( Main Building-First Floor ) For Mstd In Nii
Open Tender
Indian
Kerala
Trivandrum
23-05-2022

Tender Details

Setting Up Semiclean Room Cum Dark Room Facility In Room No 320 ( Main Building-First Floor ) For Mstd In Niist Campus, Trivandrum Setting Up Semi-Clean Room Cum Dark Room Facility In Room No 320 ( Main Building-First Floor ) For Mstd In Niist Campus, Trivandrum

Key Value

Document Fees
INR 590 /-
EMD
INR 19670.0 /-
Tender Value
INR 9.83 Lakhs /-

BOQ Items

Name of Work: Renovation cum Refurbishment of Room No - 320 (Main Building First Floor) for setting up of Semi-Clean Room cum Dark Room Facility for MSTD in NIIST Campus, Trivandrum.Sub Head: Setting up of Semi-Clean Room cum Dark Room Facility for MSTD in NIIST Campus, Trivandrum.
Sl. No. Item Description
1WALL / CEILING PANELS
2Supplying and Fixing Prefabricated Double Skin Panel 80mm thick made of 0.6mm thick PPGI sheets on both sides with EPS (Thermocole – TF-Fire retardant grade) core, all joints duly sealed, with conduits as provision for wiring and complete with accessories such as floor track, fasteners, supports, scratch guardfilm, silicone sealant, cutouts for electrical sockets, View Panel etc. (Colour shall be decided by the Engineer-in-charge)
3Supplying and Fixing Prefabricated Double Skin Panel 50mm thick made of 0.6mm thick PPGI sheets on both sides with EPS (Thermocole – TF-Fire retardant grade) core, all joints duly sealed, with conduits as provision for wiring and complete with accessories such as necessary accessories like tuen buckles,theared rods ,nut and bolts,t- grid, fasteners, supports, scratch guardfilm, silicone sealant, cutouts for electrical sockets, View Panel etc. (Colour shall be decided by the Engineer-in-charge)
4Coving: Aluminium powder coated section (2” radius) to round off 90º joints between wall-wall, wall-floor, wall-ceiling in the same colour as the Panels, backed with aluminium clip-on angle & finished with Silicone sealant.
53D Corners - Supplying and fixing of 3D corners on all exposed corners with suitable material and matching with the wall / ceiling panel colour, backed with clip on angle & finished with silicone sealent.
6C-Cap - Supply and Installation of C-Cap for covering cutouts of lighs, module, doors etc as per the manufacturer specification.
7Clean Room Hinged Doors : Metallic scientific doors with double glazed view panel of size 450 X 750 mm with 5mm thick glass; door closer, SS handle etc.Size:1.0m X 2.1m
8Clean Room Hinged Doors : Metallic scientific doors with double glazed view panel of size 450 X 750 mm with 5mm thick glass; door closer, SS handle etc.Size:Maintenance Door Double Door for Equipment Service Size:1.8m X 2.1m
9FLOORING
10Epoxy flooring: Self leveling , seamless floor using 2-component system with suitable surface preparation 2mm total thickness
11AIR SHOWERS
12Supply & Installation of Air Shower shall be a high velocity, low pressure type system in accordance with Federal Standard 209E and Air Force Tech Order 00-25-203.The Air Shower design will provide normal entrance to and exit from a contamination controlled area. The Air Shower shall be a completely self contained unit, equipped with air filtration systems, blowers, motors, controls, solid-state programmable microprocessor, interlocking doors with view panels, lighting, and pre-wired electrical panel All exterior and interior Air Shower surfaces shall be completely sealed with materials compatible with Class ISO 5 Adjustable air nozzles shall be white SS construction sized and spaced to provide average 5,000 fpm air flow at the face of the nozzle. Return air registers suckes from bottom with return air grilles, built into the Air Shower system"s walls. Interior ceilings shall include an appropriate number of air nozzles and a fluorescent light, or HEPA filters and lighting above a protective grille (on models with laminar flow ceilings). HEPA filters capable of emoving 99.99% of dust particles to 0.3 microns in size shall be used. Filter access is from above unit, or as specified. . Replaceable pre-filters of 30% efficiency shall be used to maximize life of the absolute filters and shall be accessible from Air Shower interior, within return air grille(s) - Size of working area shall be 1200x1000x2000mm
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy