Supply Installation Testing Commissioning Of Lt Panel Board At Bapu Park Kotla Bps. , Lt Distribution Panel Sheet Steel Enclosure Made Out Of 2Mm Crca Sheet Totally Enclosed, Powder Coated Free Standing, Floor Mounted Type, Dust& Vermin Proof, Outward Opening, Lockable Doors Having Hidden Hinges And A Bolted Back Cover Both Using Non-Deteriorating Neoprene Rubber Gaskets To Provide Ip-54 Protection .The Each Part Of The Fabricated Panel Will Be Strictly Subjected To Seven Tank Treatment. The Various Components, Assemblies And Sub Equipments Of The Panel Will Be As Per Standard Given In Relevant Is. The Bus Bar Of The Panel Will Be Shaped Out Of High Conductivity, Electrolytic Conductor And Shall Be Liberal Sized In Aluminium. The Control Wiring Of The Panel Will Be Done With Pvc Flexible Copper Wires Of 1.5 Mm Cross Section. Each Wire Will Be Terminating With A Ferule Crimped To The Wire, Size 1800Mmx1600x375mm. , Mccb 415V, Tp 3Phase High Breaking Capacity 50Ka 50Hz, 630Amp With Spreader & Handle . Make: L&T Or Any Djb Approved Make. , Mccb 415V, Tp 3Phase High Breaking Capacity 50Ka 50Hz, 320Amp With Spreader. Make: L&T Or Any Djb Approved Make. , Mcb Single Pole 6Amp. Make: L&T Or Any Djb Approved Make. , Mcb Triple Pole 32Amp. Make: L&T Or Any Djb Approved Make. , Mcb Triple Pole 63Amp. Make: L&T Or Any Djb Approved Make. , Pvc Insulated Copper Flexible Cable Single Core 70 Sq.Mm Make: Havells Or Any Djb Approved Make. , Over Load Relay ( Ct Operated ) 135-225 Amp. Make: L&T Or Any Djb Approved Make. , Over Load Relay 6-10 Amp Range. Make: L&T Or Any Djb Approved Make. , Amp. Meter Digital. Make: Ae Or Any Djb Approved Make. , Volt Meter Digital. Make: Ae Or Any Djb Approved Make. , Motor Protection Relay. Make: L&T Or Any Djb Approved Make. , Power Contactor 220V 3Phase250amp. Make: L&T Or Any Djb Approved Make. , Power Contactor 220V 3Phase25amp. Make: L&T Or Any Djb Approved Make. , Star Delta Timer On Delay.Make: L&T Or Any Djb Approved Make. , Indicating Lights Led Type Ryb & On / Off. Make: L&T Or Any Djb Approved Make. , Start Push Button Green . Make: L&T Or Any Djb Approved Make. , Stop Push Button Red.. Make: L&T Or Any Djb Approved Make. , Current Transformer 500 / 5. Make: Ae Or Any Djb Approved Make. , Current Transformer 250 / 5. Make: Ae Or Any Djb Approved Make. , Current Transformer 30 / 5. Make: Ae Or Any Djb Approved Make. , On Load Change Over Switch 630Amp. Open Execution Type . Make: L&T Or Any Djb Approved Make. , Fitting Of The Above Components In Panel Enclosure With Terminal Blocks, Channels, Ferrules, Thimble, Support Insulator On Bus Bar, Required Hard Wares, Control Wiring In 1.5 Sq. Mm Wire Complete In All Respect. Job Including Make Star Delta Starter Provision ( 2 Nos ) . , Dismantling Of Old Panel, Structure, Damaged Components And Installation Of The Panel At Site By Making Foundation , Termination Of Cable Both Incoming & Out Going Side , Mongeringof Complete Panel , Including Cable Connection, . This Includes Cartage, Loading& Unloading Etc. , Testing& Commissioning Of Thepanelwith Relevant Is As Follow: - Check Equipments Specification - Continuity And Earthing -Mccb Mechanism And Alignment -Meggaring Of All Equipments For Phase To Phase, Neutral To Body, Neutral To Earth And Phase To Earth. - All Functional Tests -Checking Forall Tightness Of Nuts And Bolts -Alignments Of Doors Etc. -Interlocking Tests