}

Supply Installation Testing And Commissioning Of Led Lights High Mast Flood Lighting System Supply Installation Testing And Commissioning Of Led Lights High Mast Flood Lighting System , Providing Supply, Installation, Testing And Commissioning Of 50Hz, Ou, bemina-Jammu And Kashmir

Jammu And Kashmir Small Scale Industries Development Corporation Limited has published Supply Installation Testing And Commissioning Of Led Lights High Mast Flood Lighting System Supply Installation Testing And Commissioning Of Led Lights High Mast Flood Lighting System , Providing Supply, Installation, Testing And Commissioning Of 50Hz, Ou. Submission Date for this Tender is 21-02-2022. Bolts Tenders in bemina Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

31070755
Supply Installation Testing And Commissioning Of Led Lights High Mast Flood Lighting System Supply Installation Testing And Commissioning Of Led Lights High Mast Flood Lighting System , Providing Supply, Installation, Testing And Commissioning Of 50Hz, Ou
Open Tender
Indian
Jammu And Kashmir
bemina
21-02-2022

Tender Details

Supply Installation Testing And Commissioning Of Led Lights High Mast Flood Lighting System Supply Installation Testing And Commissioning Of Led Lights High Mast Flood Lighting System , Providing Supply, Installation, Testing And Commissioning Of 50Hz, Outdoor Type, Delta Star, Aluminum Wound, Onan Cooled, Distribution Transformer, Confirming To Is: 2026-1977 With Latest Amendments Dully Tested, Painted And Oil Filled To Is: 335 Of 1983 With Latest Amendments The Transformer Shall Be Complete With Following: - A) Oil Conservator With Oil Level Indicator, Minimum Level Marking And Drain Plugs,B) Top Mounted Ht Bushings With Arcing Horn.C) Lt Bush Enclosure. D) Lifting Lugs And Bi-Directional Roller E) Rating Diagram And Terminal Marking Plate F) Explosion Vent And Valves For Filtration, Drainage And Filling E. With Necessary Plugs, Including Air Release Plug A). 100 Kva, 11/0 433Kv , B) 200 Kva, 11/0 433Kv , C).250 Kva, 11/0 433Kv , Servo 1. Type Three Phase Unbalanced Load 2. Input Voltage Range 155-465 Volts (Three Phase) 3. Output Voltage415 Volts With Deviation Of 1% 4. Frequency50hz With Deviation Of 1% 5. Motor Drive Heavy Duty A.C Synchronous Motor 6. Indication Main On ,Output On , Low Cut -Off ,High Cut Off 7.Alarms A) Input Low Voltage Cutoff B) Input High Voltage Cutoff C) Output Low Voltage Cutoff D) Output High Voltage Cutoff 8.Controls A. Auto/ Manual B. Manual Bypass C. Manual Raise/ Lower For Output Voltage 9. Metering Voltmeter For L/P & O/P Voltage Along With Selector Switch Meter For I/P & O/P Current 10. Type Of Cooling Onan Cooled. 11. Protection 1- Over Voltage, Under Voltage, Overload Short Circuit 12. Environmental Protection Ip 30 13. Class Of Insulation: Class E 14. Stabilizer Standard: As Per Is: 98:15 15. Oil Standard : As Per Ls: 315 A).Rating15 Kva , B). Rating 25 Kva , C). Rating 30 Kva , D). Rating 35 Kva , E). Rating 50 Kva , F). Rating 100 Kva , G). Rating200 Kva , H). Rating250 Kva , Providing Supply,Installation, Testing And Commissioningof 35 Mmsq 11 Kv Grade, 3 Corealuminum Conductor Abc Cable , Xlpe Insulated With Aluminum Alloy Messenger Wire For Carrying The Weight Of The Cable Of Maximum System Voltage Of 12 Kv ( Havells / Polycablskytone/ Gloster Make),The Cable Should Be Anchored On The Poles Using Suitable Galvanized Hooks. If Substation Capacity Is Enhanced To 250 Kva 50 Mm Cable Amount Will Be Enhanced , Outdoor Endkiits Heat Shrink Type For Above 35 Mm Sq 11 Kv Three Core Abc Cable Type , St Poles 9_Mtr Long Complete With Base Plate And Top Cap Confirming To Is 410 Sp 33 To Be Erected In Cement Concrete 1:3:6 (1 Cement 1 3 Coarse Sand: 6 Graded Stone Aggregate 40 Mm Nominal Size) Foundation Including Excavation,Refilling, Formwork Etc As Required At Site. , 11 Kv God For Tapping Points And Substation , 11 Kv Lightening Arrestor. The Arrestor Should Be Station Type And Of 10 Ka Rating Including Clamps Of Appropriate Size. , 11 Kv Drop Out Fuse / Arcing Horn Gap , Providing Of Chemical Earthing , 1Oox50x5ox6 Nis Channeis,8.5 Feet Long Including Cutting, Fabrication And Installation On St Poles For Distribution Transformer (Dtr) Frame To Be Erected As Per Rec Guidelines Using Gi Clamps. , Supplying Laying Testing And Commissioning Of Additional Copper Piping, 6.35Mm, 0.8Mm Thick With 13Mm Insulation , 45X45x5ms Angle Iron 8.5 Feet Long Including Cutting,Fabrication And Installation Forbelt For Transformer , Fabricated Clamps Of 50X5mm Gi Strip For Erection Of Dtr Channels Etc. , Supply, Testing And Commissioning Of Ht Meter , 35 Mm Sq Core Xlpe Armored Aluminumconductor 11 Kv Cable Of Maximumsystem Voltage Of 12 Kv (Havells/Poly Cab Paramount / Sky Tone Make) , Supplying And Laying Of 32Mm Ppr Pipe With Allied Accessories For Drain Use Complete As Required , 185 Mm Sq Aluminum Armored Xlpethree And A Half Core Lt Cable 1.1 Kv Grade Ofhavelles,Polycabl, Paramount , Skytonekei Make , 3 Inch Dia 2.5 Inch Dia A Classgipipefor Use Asconduitfor Xlpe Cable Fordtras Requiredat Site , Supply Installation Testing Commissioning Of Factory Fabricated Factory Assembled Sheet Steel Clad Powder Coated, Stand Mounted Cubicle Board Outdoor Type, Rain- Proof Distribution Panel With Double Door Made From 1.6Mm Thick Crca Sheet Dust And Vermin Proof Dully Phosphates And Powder Coated, Provided With Hinged Gasketed Door Padlocking Facility And Including Suitably Rated Pvc Insulated 2 Nos Of 4- Strip Aluminum Busbars Of 300 A And 50 A Capacity Complete With Interconnections, Providing Lugs, Earthing Terminals, Etc Including Providing Fixing Of Requisite Accessories To Operate Successfully Digital Voltmeter With Selector Switch =1 Set Digital Amp Meter With Selector Switch & 1 Set Indication Lamps R/Y/B 2. The Panel Should Have Two Door I.E Main Door And Internal Sub Distribution Doors Both Lockable Types For 12 Meter High 10 To 16 Masts. , Supply Installation Testing Commissioning Of Factory Fabricated Factory Assembled Sheet Steel Clad Powder Coated, Stand Mounted Cubicle Board Outdoor Type, Rain- Proof Distribution Panel With Double Door Made From 1.6Mm Thick Crca Sheet Dust And Vermin Proof Dully Phosphates And Powder Coated, Provided With Hinged Gasketed Door Padlocking Facility And Including Suitably Rated Pvc Insulated 2 Nos Of 4- Strip Aluminum Busbars Of 300 A And 50 A Capacity Complete With Interconnections, Providing Lugs, Earthing Terminals, Etc Including Providing Fixing Of Requisite Accessories To Operate Successfully Digital Voltmeter With Selector Switch =1 Set Digital Amp Meter With Selector Switch & 1 Set Indication Lamps R/Y/B 2. The Panel Should Have Two Door I.E Main Door And Internal Sub Distribution Doors Both Lockable Typesfor 16 Meter To 20Meter High Mast Upto 16 Lights Per Mast , Supply Installation Testing Commissioning Of Factory Fabricated Factory Assembled Sheet Steel Clad Powder Coated, Stand Mounted Cubicle Board Outdoor Type, Rain- Proof Distribution Panel With Double Door Made From 1.6Mm Thick Crca Sheet Dust And Vermin Proof Dully Phosphates And Powder Coated, Provided With Hinged Gasketed Door Padlocking Facility And Including Suitably Rated Pvc Insulated 2 Nos Of 4- Strip Aluminum Busbars Of 300 A And 50 A Capacity Complete With Interconnections, Providing Lugs, Earthing Terminals, Etc Including Providing Fixing Of Requisite Accessories To Operate Successfully Digital Voltmeter With Selector Switch =1 Set Digital Amp Meter With Selector Switch & 1 Set Indication Lamps R/Y/B 2. The Panel Should Have Two Door I.E Main Door And Internal Sub Distribution Doors Both Lockable Types For 24 To 30 Meters High Mast 16-54 Lights Per Mast. , Making Of G.I Pipe Earthings Using 2” Dia 8 Feet Long Gi Pipe With 12”X12” Cast Iron Manhole Cover Fixed In Requisite Masonry Work , Making Of Plate Earthing (Copper Plate 2’X2’) Including 25X3mm Gi Earth Riser Strips For Dg And Gi Masts , Cement Concrete Foundation Using M15 For Servo 8’X6’X4’ Sizeand For Dg Set 6’X5’X4’ Size (Or Sizeas Specifiedby Dg Manufacturer For Dg Only) With3 Inchslab And Plastering Complete Includingform Work Etc. , Supply Installation, Testing And Commissioning Of Sports Led Flood Light Canis Lens Type Designed For Outdoor Sports Lighting Applications Having Housing Of Pressure Die Cast Aluminum Construction With Thermal Management Heat Sink Design, Flood Light Cover Shall Be Of Toughened Optically Clear Glass Construction Mounted In A Metal Frame With Silicon Gasket For Ip Protection. Led Flood Light And Driver Enclosure Ip Protection Ip 65 Minimum. Flood Light Should Be Equipped = With Cradle Type Epoxy Powder Coated Adjustable Ms Flood Light Bracket Suitable For Mounting On Sports Lighting Tower. (For Detailed Led Fixture Specification Please Refer To Sbd Of This Tender); Led Fixture Makes: Apex Led Flood Light Osram Led Flood Light , Lokozo Ledfloodlightwiproledfloodlightgoldwynled/Philipsflood Light Surya Or Equivalent 200 Watts , 250 Watts , 400 Watts , 500 Watts , 1000 Watts , Supply Installation,Testing And Commissioning Of 30 M High Galvanized Polygon Tubular Sports Lighting Tower 8.0Mm Thick With Max. 3 Sections, 20 Sided Polygon, Of S355 Grade As Per Bsen 10025, Galvanization As Per Bs En Iso 1461, Designed As Per Is 875 Part Ill, Poles As Per Bs En Iso 1461, C/W Head Frame Of Gi Channel Tube Construction For Mounting Of 10 Nos. To 20 No’Ssports Flood Lights, C/W Single Gear Double Drum (Sgdd ) Winch Min, Load Of Swl 750 Kgs, Heavy Duty Motor With Mechanical Tripping Facility, Electrical Cable Of Epr Insulated, Weather Proof Ip65 Junction Box, Ss 316 Grade Wire Rope, Lightening Protection, Led Twin Aviation Obstruction Light Of Low Intensity Continuous Burning Red Color Type. Drawings For Ga Of The S Orts _Lighting Tower And Foundation Details To Be Enclosed With The Tender Bi For Foundation Calculation 10 Sbc Of Sbcof 10 Mt To Be Considered ( Itis Theresponsibilityof The Contractor Executing The Works To Arrange For Soil Testing And Sbc Reports Of Ground Conditions Each Sports Lighting Tower Foundation Location And Revised Foundation Drawing From The Sports Lighting Towermanufacturer To Besubmitted For Approvalbeforestartingofthe Foundationworks) , Supply Installation,Testing And Commissioning Of 30 M High Galvanized Polygon Tubular Sports Lighting Tower 8.0Mm Thick With Max. 3 Sections, 20 Sided Polygon, Of S355 Grade As Per Bsen 10025, Galvanization As Per Bs En Iso 1461, Designed As Per Is 875 Part Ill, Poles As Per Bs En Iso 1461, C/W Head Frame Of Gi Channel Tube Construction For Mounting Of 20 Nos. To 30 No’Ssports Flood Lights, C/W Single Gear Double Drum (Sgdd ) Winch Min, Load Of Swl 750 Kgs, Heavy Duty Motor With Mechanical Tripping Facility, Electrical Cable Of Epr Insulated, Weather Proof Ip65 Junction Box, Ss 316 Grade Wire Rope, Lightening Protection, Led Twin Aviation Obstruction Light Of Low Intensity Continuous Burning Red Colour Type. Drawings For Ga Of The S Orts _Lighting Tower And Foundation Details To Be Enclosed With The Tender Bi For Foundation Calculation 10 Sbc Of Sbcof 10 Mt To Be Considered ( Itis Theresponsibilityof The Contractor Executing The Works To Arrange For Soil Testing And Sbc Reports Of Ground Conditions Each Sports Lighting Tower Foundation Location And Revised Foundation Drawing From The Sports Lighting Towermanufacturer To Besubmitted For Approvalbeforestartingofthe Foundationworks) , Supply Installation,Testing And Commissioning Of 30 M High Galvanized Polygon Tubular Sports Lighting Tower 10.0Mm Thick With Max. 3 Sections, 20 Sided Polygon, Of S355 Grade As Per Bsen 10025, Galvanization As Per Bs En Iso 1461, Designed As Per Is 875 Part Ill, Poles As Per Bs En Iso 1461, C/W Head Frame Of Gi Channel Tube Construction For Mounting Of 30 Nos. To54 No’Ssports Flood Lights, C/W Single Gear Double Drum (Sgdd ) Winch Min, Load Of Swl 750 Kgs, Heavy Duty Motor With Mechanical Tripping Facility, Electrical Cable Of Epr Insulated, Weather Proof Ip65 Junction Box, Ss 316 Grade Wire Rope, Lightening Protection, Led Twin Aviation Obstruction Light Of Low Intensity Continuous Burning Red Colour Type. Drawings For Ga Of The S Orts _Lighting Tower And Foundation Details To Be Enclosed With The Tender Bi For Foundation Calculation 10 Sbc Of Sbcof 10 Mt To Be Considered ( Itis Theresponsibilityof The Contractor Executing The Works To Arrange For Soil Testing And Sbc Reports Of Ground Conditions Each Sports Lighting Tower Foundation Location And Revised Foundation Drawing From The Sports Lighting Towermanufacturer To Besubmitted For Approvalbeforestartingofthe Foundationworks) , Supply Installation , Testingand Commissioning Of 24 M High Galvanized Polygon Tubular Sports Lighting Tower 8.0Mm Thick With Max. 3 Sections, 20 Sided Polygon, Of S355 Grade As Per Bsen 10025, Galvanization As Per Bs En Iso 1461, Designed As Per Is 875 Part Ill, Poles As Per Bs En Iso 1461, C/W Head Frame Of Gi Channel Tube Construction For Mounting Of 10 Nos. To 20Nos Sports Flood Lights, C/W Single Gear Double Drum (Sgdd ) Winch Min, Load Of Swl 750 Kgs, Heavy Duty Motor With Mechanical Tripping Facility, Electrical Cable Of Epr Insulated, Weather Proof Ip65 Junction Box, Ss 316 Grade Wire Rope, Lightening Protection, Led Twin Aviation Obstruction Light Of Low Intensity Continuous Burning Red Color Type. Drawings For Ga Of The S Orts _Lighting Tower And Foundation Details To Be Enclosed With The Tender Bi For Foundation Calculation 10 Sbc Of Sbcof 10 Mt To Be Considered ( Itis Theresponsibilityof The Contractor Executing The Works To Arrange For Soil Testing And Sbc Reports Of Ground Conditions Each Sports Lighting Tower Foundation Location And Revised Foundation Drawing From The Sports Lighting Towermanufacturer To Besubmitted For Approvalbeforestartingofthe Foundationworks) , Supply Installation , Testingand Commissioning Of 20 M High Galvanized Polygon Tubular Sports Lighting Tower 8.0Mm Thick With Max. 3 Sections, 20 Sided Polygon, Of S355 Grade As Per Bsen 10025, Galvanization As Per Bs En Iso 1461, Designed As Per Is 875 Part Ill, Poles As Per Bs En Iso 1461, C/W Head Frame Of Gi Channel Tube Construction For Mounting Of 10 Nos. To 20 No’Ssports Flood Lights, C/W Single Gear Double Drum (Sgdd ) Winch Min, Load Of Swl 750 Kgs, Heavy Duty Motor With Mechanical Tripping Facility, Electrical Cable Of Epr Insulated, Weather Proof Ip65 Junction Box, Ss 316 Grade Wire Rope, Lightening Protection, Led Twin Aviation Obstruction Light Of Low Intensity Continuous Burning Red Color Type Along With Feeder Pillar. Drawings For Ga Of The S Orts _Lighting Tower And Foundation Details To Be Enclosed With The Tender Bi For Foundation Calculation 10 Sbc Of Sbcof 10 Mt To Be Considered ( Itis Theresponsibilityof The Contractor Executing The Works To Arrange For Soil Testing And Sbc Reports Of Ground Conditions Each Sports Lighting Tower Foundation Location And Revised Foundation Drawing From The Sports Lighting Towermanufacturer To Besubmitted For Approvalbeforestartingofthe Foundationworks) , Supply Installation,Testing And Commissioning Of 20 M High Galvanized Polygon Tubular Sports Lighting Tower 8.0Mm Thick With Max. 3 Sections, 20 Sided Polygon, Of S355 Grade As Per Bsen 10025, Galvanization As Per Bs En Iso 1461, Designed As Per Is 875 Part Ill, Poles As Per Bs En Iso 1461, C/W Head Frame Of Gi Channel Tube Construction For Mounting Of 20 Nos. To 30 No’Ssports Flood Lights, C/W Single Gear Double Drum (Sgdd ) Winch Min, Load Of Swl 750 Kgs, Heavy Duty Motor With Mechanical Tripping Facility, Electrical Cable Of Epr Insulated, Weather Proof Ip65 Junction Box, Ss 316 Grade Wire Rope, Lightening Protection, Led Twin Aviation Obstruction Light Of Low Intensity Continuous Burning Red Color Type Along With Feeder Pillar. Drawings For Ga Of The S Orts Lighting Tower And Foundation Details To Be Enclosed With The Tender Bi For Foundation Calculation 10 Sbc Of Sbcof 10 Mt To Be Considered ( Itis Theresponsibilityof The Contractor Executing The Works To Arrange For Soil Testing And Sbc Reports Of Ground Conditions Each Sports Lighting Tower Foundation Location And Revised Foundation Drawing From The Sports Lighting Towermanufacturer To Besubmitted For Approvalbeforestartingofthe Foundationworks) , Foundations Of 30Mtr High Mast Poles. Contractor To Furnish Sbc Report And Foundation Design For Approval) , Foundations Of 24Mtr High Mast Poles. Contractor To Furnish Sbc Report And Foundation Design For Approval) , Foundations Of 20Mtr High Mast Poles. Contractor To Furnish Sbc Report And Foundation Design For Approval) , Ferruling , Galvanized Nuts And Bolts Of Sorts As Required At Site , Earthing Of 9 Mtr. Long St Poles Using 8 Swg Gi Wire , 0.03 Acsr For Jump Ring Of Transformer On Ht Side , Aluminum Thimbles Of Sizes Required For Cables Of Different Sizes Used Including Crimping , 25X3 Mm Gi Strip For Earthing Extensions , Epoxy Insulator Of Sizes Required For Earthing Of Dtr Structure , 12”X9” Danger Plates For Ht And Lt Notification , Painting Of Dtr Frame And Tapping Point Frame With Two Coats Of Red Oxide And Two Coats Of Aluminum Paint , Supply Erection Testing And Commissioning Of 70Mm Sq Aluminum Conductor, Armored Xple Three And A Half Core Lt Cable 1.1 Kv Grade Of Havells, Polycabl, Paramount, Sky Tone Make , 50Mm Sq Aluminum Conductor, Armored Xlpe Thee And A Half Core Lt Cable 1.1 Kv Grade Of Havells, Polycab Paramount, Skytone Make , 25 Mm Sq Aluminum 3 Cores Lt Cable 1.1 Kv Grade Of Havells, Polycab, Paramount, Skytone Make , Trench For Cable Laying Through 3” Hdpe Pipe Including Excavation Laying Of Sand Bed Placing Of Layer Of Bricks (Cost Of Sand And Bricks Included) Including Metallic Cable Markers With Grouting After Every Ten Meters. The Cable Route Marker Should Be Of 45X45 Angle Iron 2.5 Feet Long With Circular Metallic Disc 4” Dia At The Top With Lt Cable Embossed On It. The Route Marker Should Begrouted1 Feetinsidethe Concreteand 1.5 Feetabovegroundwith Clearlylegiblemarking , Supply & Installation Of 3,4Mm Thick Octagonal High Mast Having Bottom Dia Of 300Mm And Top Dia Of 100Mm Thick.12Mtr High. , Supply & Installation Of 6,4Mm Thick Octagonal High Mast Having Bottom Dia Of 360Mm And Top Dia Of 150Mm Thick 14Mtr High. , Supply & Installation Of 6,4Mm Thick Octagonal High Mast Having Bottom Dia Of 360Mm And Top Dia Of 150Mm Thick 16Mtr High. , Foundation Work For High Mast Inlc. Gi Anchor Bolts, Anchor Plates, Double Nuts, Washersa)For 12Mtr. , B)For 14Mtr. , C)For 16Mtr. , Supplying And Fixing Of Special Arm Suitable For Mounting Led Flood Lights For 12Mtr High Masts. , A). Sub Main Lt Panel Outdoor Type , B). P/F Of 6-32 Amp. Mcb Complete With Connections As Req. , C).P/F Of 4-Pole Connector 16 Amp Complete With Connections As Req. , Supplying, Installation, Testing & Commissioning Of 2.5X2c Copper Flexible Wire Of Approved Made , Supplying/Laying Hdpe Pipe , Supplying And Fixing Of Gi Wire (8Swg) , P/Laying Of Armored Aluminum Conductor To Be Laid In Already Excavated Cable Trench. The Job Incl. Refilling After Cable Laying And Removal/Disposal Of Surplus Earth. A). 10Mm 4 Core Armored Aluminum Conductor , B). 16Mm 4 Core Armored Aluminum Conductor , C). 25Mm 3.5 Core Armored Aluminum Conductor , D). 25Mm 4 Core Armored Aluminum Conductor , E). 35Mm 4 Core Armored Aluminum Conductor , F). 50Mm 3.5 Core Armored Aluminum Conductor , G). 70Mm 4 Core Armored Aluminum Conductor , Fabrication, Supply & Installation Of Outdoor Canopy Suitable For Main Panel Board And Servo Stabilizer With Complete Cement Concrete Foundation And Locking Arrangement Complete Job. , High Must Ac Street Light With S.T Pole(6 Lights - 50 W Each) Luminary – Led 50 Watt Each Pole - 9 Meter Length (Tabular Pole With Cement Bottoming In Ratio Of 1:3:6 Mix With 2X2x2.5) Including Nut Bolts And Other Accessories

Key Value

Document Fees
INR 1000 /-
EMD
Refer document
Tender Value
Refer document

BOQ Items

Name of Work:FIXATION OF RATEIN RESPECT OF SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF LED LIGHTS/ HIGH MAST FLOOD LIGHTING SYSTEM
Sl. No. Item Description
1Providing supply, installation, testing and commissioning of 50hz, outdoor type, delta star, aluminum wound, ONAN cooled, distribution transformer, confirming to is: 2026-1977 with latest amendments dully tested, painted and oil filled to is: 335 of 1983 with latest amendments the transformer shall be complete with following: - A) oil conservator with oil level indicator, minimum level marking and drain plugs,B) top mounted ht bushings with arcing horn.C) LT bush enclosure. D) lifting lugs and bi-directional roller E) rating diagram and terminal marking plate F) explosion vent and valves for filtration, drainage and filling e. With necessary plugs, including air release plug a). 100 KVA, 11/0 433kv
2b) 200 KVA, 11/0 433kv
3c).250 KVA, 11/0 433kv
4SERVO 1. Type Three phase unbalanced load 2. Input voltage range 155-465 volts (three phase) 3. output voltage415 Volts with deviation of 1% 4. Frequency50hz with deviation of 1% 5. Motor drive Heavy duty A.C synchronous motor 6. Indication main on ,output on , low cut -off ,high cut off 7.Alarms a) input low voltage cutoff b) input high voltage cutoff c) output low voltage cutoff d) output high voltage cutoff 8.Controls a. auto/ manual b. manual bypass c. Manual raise/ lower for output voltage 9. Metering voltmeter for l/p & o/p voltage along with selector switch meter for I/P & O/P current 10. Type of cooling ONAN cooled. 11. Protection 1- over voltage, under voltage, Overload short circuit 12. Environmental protection IP 30 13. Class of insulation: Class E 14. Stabilizer standard: As per IS: 98:15 15. Oil standard : As per lS: 315 a).Rating15 KVA
5b). Rating 25 KVA
6c). Rating 30 KVA
7d). Rating 35 KVA
8e). Rating 50 KVA
9f). Rating 100 KVA
10g). Rating200 KVA
11h). Rating250 KVA
12Providing supply,installation, testing and commissioningof 35 mmsq 11 kv grade, 3 corealuminum conductor abc cable , XLPE insulated with aluminum alloy messenger wire for carrying the weight of the cable of maximum system voltage of 12 kv ( Havells / PolycablSkytone/ Gloster make),the cable should be anchored on the poles using suitable galvanized hooks. If substation capacity is enhanced to 250 kva 50 mm cable amount will be enhanced
13Outdoor endkiits heat shrink type for above 35 mm sq 11 KV Three core abc cable type
14ST poles 9_Mtr Long complete with Base Plate and top cap Confirming to IS 410 SP 33 to be erected in cement concrete 1:3:6 (1 cement 1 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation,refilling, formwork etc as required at site.
1511 KV GOD for tapping points and substation
1611 KV Lightening Arrestor. The arrestor should be station type and of 10 KA rating including clamps of appropriate size.
1711 KV Drop out fuse / Arcing horn gap
18Providing of chemical earthing
191OOX50X5OX6 NIS channeis,8.5 feet long including cutting, fabrication and installation on ST poles for Distribution Transformer (DTR) frame to be erected as per REC guidelines using GI clamps.
20Supplying laying testing and commissioning of additional copper piping, 6.35mm, 0.8mm thick with 13mm insulation
2145x45x5MS angle iron 8.5 feet long including cutting,fabrication and installation forbelt for transformer
22Fabricated clamps of 50x5mm GI strip for erection of DTR channels etc.
23Supply, Testing and commissioning of HT meter
2435 mm sq core XLPE armored aluminumconductor 11 KV cable of maximumsystem voltage of 12 kv (Havells/Poly cab Paramount / Sky tone make)
25Supplying and laying of 32mm PPR pipe with allied accessories for drain use complete as required
26185 mm sq Aluminum armored XLPEthree and a half core LT cable 1.1 KV grade ofHavelles,Polycabl, Paramount , SkytoneKEI make
273 inch dia 2.5 inch dia A classGIpipefor use asconduitfor XLPE cable forDTRas requiredat site
28Supply installation testing commissioning of factory fabricated factory assembled sheet steel clad powder coated, stand mounted cubicle board outdoor type, rain- proof distribution panel with double door made from 1.6mm thick CRCA sheet dust and vermin proof dully phosphates and powder coated, provided with hinged gasketed door padlocking facility and including suitably rated PVC insulated 2 nos of 4- strip Aluminum busbars of 300 A and 50 A capacity complete with interconnections, providing lugs, earthing terminals, etc including providing fixing of requisite accessories to operate successfully Digital voltmeter with selector switch =1 set Digital amp meter with selector switch & 1 set Indication lamps R/Y/B 2. the panel should have two door i.e main door and internal sub distribution doors both lockable types for 12 meter high 10 to 16 masts.
29Supply installation testing commissioning of factory fabricated factory assembled sheet steel clad powder coated, stand mounted cubicle board outdoor type, rain- proof distribution panel with double door made from 1.6mm thick CRCA sheet dust and vermin proof dully phosphates and powder coated, provided with hinged gasketed door padlocking facility and including suitably rated PVC insulated 2 nos of 4- strip Aluminum busbars of 300 A and 50 A capacity complete with interconnections, providing lugs, earthing terminals, etc including providing fixing of requisite accessories to operate successfully Digital voltmeter with selector switch =1 set Digital amp meter with selector switch & 1 set Indication lamps R/Y/B 2. the panel should have two door i.e main door and internal sub distribution doors both lockable typesfor 16 meter to 20meter high mast upto 16 lights per mast
30Supply installation testing commissioning of factory fabricated factory assembled sheet steel clad powder coated, stand mounted cubicle board outdoor type, rain- proof distribution panel with double door made from 1.6mm thick CRCA sheet dust and vermin proof dully phosphates and powder coated, provided with hinged gasketed door padlocking facility and including suitably rated PVC insulated 2 nos of 4- strip Aluminum busbars of 300 A and 50 A capacity complete with interconnections, providing lugs, earthing terminals, etc including providing fixing of requisite accessories to operate successfully Digital voltmeter with selector switch =1 set Digital amp meter with selector switch & 1 set Indication lamps R/Y/B 2. the panel should have two door i.e main door and internal sub distribution doors both lockable types for 24 to 30 meters high mast 16-54 lights per mast.
31Making of G.I pipe earthings using 2” dia 8 feet long GI pipe with 12”x12” cast iron manhole cover fixed in requisite masonry work
32Making of plate earthing (Copper plate 2’x2’) including 25x3mm GI earth riser strips for DG and GI masts
33Cement Concrete Foundation using M15 for servo 8’x6’x4’ sizeand for DG set 6’x5’x4’ size (or sizeas specifiedby DG manufacturer for DG only) with3 inchslab and plastering complete includingform work etc.
34Supply Installation, testing and commissioning of sports LED Flood Light canis lens type designed for outdoor Sports Lighting applications having Housing of Pressure Die Cast aluminum construction with thermal management heat sink design, Flood light Cover shall be of toughened optically clear glass construction mounted in a metal frame with silicon gasket for IP protection. LED flood Light and driver enclosure IP protection IP 65 minimum. Flood light should be equipped = with Cradle type epoxy powder coated adjustable MS flood light bracket suitable for mounting on Sports lighting tower. (For detailed LED Fixture Specification please refer to SBD of this tender); LED Fixture makes: APEX LED Flood light Osram LED Flood light , LOKOZO LEDFloodlightWIPROLEDfloodlightGOLDWYNLED/PhilipsFlood Light Surya or equivalent 200 watts
35250 watts
36400 watts
37500 watts
381000 watts
39Supply Installation,testing and commissioning of 30 m high galvanized polygon tubular Sports Lighting Tower 8.0mm thick with max. 3 sections, 20 sided polygon, of S355 Grade as per BSEN 10025, galvanization as per BS EN ISO 1461, designed as per IS 875 part Ill, poles as per BS EN ISO 1461, c/w Head frame of GI Channel tube construction for mounting of 10 nos. to 20 no’sSports flood lights, c/w Single gear double drum (SGDD ) winch min, load of SWL 750 kgs, heavy duty motor with mechanical tripping facility, electrical Cable of EPR insulated, weather proof IP65 Junction box, SS 316 grade wire rope, lightening protection, LED twin aviation obstruction light of low intensity continuous burning RED color type. Drawings for GA of the S orts _Lighting tower and Foundation details to be enclosed with the Tender Bi For foundation calculation 10 SBC of SBCof 10 Mt to be considered ( Itis theresponsibilityof the contractor executing the works to arrange for soil testing and SBC reports of ground conditions each sports lighting tower foundation location and revised foundation drawing from the Sports Lighting Towermanufacturer to besubmitted for approvalbeforestartingofthe foundationworks)
40Supply Installation,testing and commissioning of 30 m high galvanized polygon tubular Sports Lighting Tower 8.0mm thick with max. 3 sections, 20 sided polygon, of S355 Grade as per BSEN 10025, galvanization as per BS EN ISO 1461, designed as per IS 875 part Ill, poles as per BS EN ISO 1461, c/w Head frame of GI Channel tube construction for mounting of 20 nos. to 30 no’sSports flood lights, c/w Single gear double drum (SGDD ) winch min, load of SWL 750 kgs, heavy duty motor with mechanical tripping facility, electrical Cable of EPR insulated, weather proof IP65 Junction box, SS 316 grade wire rope, lightening protection, LED twin aviation obstruction light of low intensity continuous burning RED colour type. Drawings for GA of the S orts _Lighting tower and Foundation details to be enclosed with the Tender Bi For foundation calculation 10 SBC of SBCof 10 Mt to be considered ( Itis theresponsibilityof the contractor executing the works to arrange for soil testing and SBC reports of ground conditions each sports lighting tower foundation location and revised foundation drawing from the Sports Lighting Towermanufacturer to besubmitted for approvalbeforestartingofthe foundationworks)
41Supply Installation,testing and commissioning of 30 m high galvanized polygon tubular Sports Lighting Tower 10.0mm thick with max. 3 sections, 20 sided polygon, of S355 Grade as per BSEN 10025, galvanization as per BS EN ISO 1461, designed as per IS 875 part Ill, poles as per BS EN ISO 1461, c/w Head frame of GI Channel tube construction for mounting of 30 nos. to54 no’sSports flood lights, c/w Single gear double drum (SGDD ) winch min, load of SWL 750 kgs, heavy duty motor with mechanical tripping facility, electrical Cable of EPR insulated, weather proof IP65 Junction box, SS 316 grade wire rope, lightening protection, LED twin aviation obstruction light of low intensity continuous burning RED colour type. Drawings for GA of the S orts _Lighting tower and Foundation details to be enclosed with the Tender Bi For foundation calculation 10 SBC of SBCof 10 Mt to be considered ( Itis theresponsibilityof the contractor executing the works to arrange for soil testing and SBC reports of ground conditions each sports lighting tower foundation location and revised foundation drawing from the Sports Lighting Towermanufacturer to besubmitted for approvalbeforestartingofthe foundationworks)
42Supply Installation , testingand commissioning of 24 m high galvanized polygon tubular Sports Lighting Tower 8.0mm thick with max. 3 sections, 20 sided polygon, of S355 Grade as per BSEN 10025, galvanization as per BS EN ISO 1461, designed as per IS 875 part Ill, poles as per BS EN ISO 1461, c/w Head frame of GI Channel tube construction for mounting of 10 nos. to 20nos Sports flood lights, c/w Single gear double drum (SGDD ) winch min, load of SWL 750 kgs, heavy duty motor with mechanical tripping facility, electrical Cable of EPR insulated, weather proof IP65 Junction box, SS 316 grade wire rope, lightening protection, LED twin aviation obstruction light of low intensity continuous burning RED color type. Drawings for GA of the S orts _Lighting tower and Foundation details to be enclosed with the Tender Bi For foundation calculation 10 SBC of SBCof 10 Mt to be considered ( Itis theresponsibilityof the contractor executing the works to arrange for soil testing and SBC reports of ground conditions each sports lighting tower foundation location and revised foundation drawing from the Sports Lighting Towermanufacturer to besubmitted for approvalbeforestartingofthe foundationworks)
43Supply Installation , testingand commissioning of 20 m high galvanized polygon tubular Sports Lighting Tower 8.0mm thick with max. 3 sections, 20 sided polygon, of S355 Grade as per BSEN 10025, galvanization as per BS EN ISO 1461, designed as per IS 875 part Ill, poles as per BS EN ISO 1461, c/w Head frame of GI Channel tube construction for mounting of 10 nos. to 20 no’sSports flood lights, c/w Single gear double drum (SGDD ) winch min, load of SWL 750 kgs, heavy duty motor with mechanical tripping facility, electrical Cable of EPR insulated, weather proof IP65 Junction box, SS 316 grade wire rope, lightening protection, LED twin aviation obstruction light of low intensity continuous burning RED color type along with feeder pillar. Drawings for GA of the S orts _Lighting tower and Foundation details to be enclosed with the Tender Bi For foundation calculation 10 SBC of SBCof 10 Mt to be considered ( Itis theresponsibilityof the contractor executing the works to arrange for soil testing and SBC reports of ground conditions each sports lighting tower foundation location and revised foundation drawing from the Sports Lighting Towermanufacturer to besubmitted for approvalbeforestartingofthe foundationworks)
44Supply Installation,testing and commissioning of 20 m high galvanized polygon tubular Sports Lighting Tower 8.0mm thick with max. 3 sections, 20 sided polygon, of S355 Grade as per BSEN 10025, galvanization as per BS EN ISO 1461, designed as per IS 875 part Ill, poles as per BS EN ISO 1461, c/w Head frame of GI Channel tube construction for mounting of 20 nos. to 30 no’sSports flood lights, c/w Single gear double drum (SGDD ) winch min, load of SWL 750 kgs, heavy duty motor with mechanical tripping facility, electrical Cable of EPR insulated, weather proof IP65 Junction box, SS 316 grade wire rope, lightening protection, LED twin aviation obstruction light of low intensity continuous burning RED color type along with feeder pillar. Drawings for GA of the S orts Lighting tower and Foundation details to be enclosed with the Tender Bi For foundation calculation 10 SBC of SBCof 10 Mt to be considered ( Itis theresponsibilityof the contractor executing the works to arrange for soil testing and SBC reports of ground conditions each sports lighting tower foundation location and revised foundation drawing from the Sports Lighting Towermanufacturer to besubmitted for approvalbeforestartingofthe foundationworks)
45Foundations of 30Mtr high mast poles. Contractor to furnish SBC report and foundation design for approval)
46Foundations of 24Mtr high mast poles. Contractor to furnish SBC report and foundation design for approval)
47Foundations of 20Mtr high mast poles. Contractor to furnish SBC report and foundation design for approval)
48Ferruling
49Galvanized nuts and bolts of sorts as required at site
50Earthing of 9 Mtr. Long ST poles using 8 SWG GI Wire
510.03 ACSR for jump ring of transformer on HT side
52Aluminum Thimbles of sizes required for cables of different sizes used including crimping
5325x3 mm GI strip for earthing extensions
54Epoxy insulator of sizes required for earthing of DTR structure
5512”x9” Danger plates for HT and LT notification
56Painting of DTR frame and tapping point frame with two coats of red oxide and two coats of aluminum paint
57Supply erection testing and commissioning of 70mm Sq aluminum conductor, armored XPLE three and a half core LT cable 1.1 KV grade of Havells, Polycabl, Paramount, Sky tone make
5850mm Sq Aluminum conductor, armored XLPE thee and a half core LT cable 1.1 KV grade of Havells, Polycab Paramount, Skytone make
5925 mm sq Aluminum 3 cores LT cable 1.1 KV grade of Havells, Polycab, Paramount, Skytone Make
60Trench for cable laying through 3” HDPE pipe including excavation laying of sand bed placing of layer of bricks (cost of sand and bricks included) including metallic cable markers with grouting after every ten meters. The cable route marker should be of 45x45 angle iron 2.5 feet long with circular metallic disc 4” dia at the top with LT CABLE embossed on it. The route marker should begrouted1 feetinsidethe concreteand 1.5 feetabovegroundwith clearlylegiblemarking
61Supply & installation of 3,4mm thick octagonal high mast having bottom dia of 300mm and top dia of 100mm thick.12Mtr high.
62Supply & installation of 6,4mm thick octagonal high mast having bottom dia of 360mm and top dia of 150mm thick 14Mtr high.
63Supply & installation of 6,4mm thick octagonal high mast having bottom dia of 360mm and top dia of 150mm thick 16Mtr high.
64Foundation work for high mast inlc. GI Anchor bolts, anchor plates, double nuts, washersa)For 12Mtr.
65b)For 14Mtr.
66c)For 16Mtr.
67Supplying and fixing of special arm suitable for mounting Led Flood Lights for 12Mtr high masts.
68a). Sub Main LT Panel Outdoor type
69b). P/f of 6-32 Amp. MCB complete with connections as req.
70c).P/f of 4-pole connector 16 amp complete with connections as req.
71Supplying, installation, Testing & Commissioning of 2.5x2C Copper flexible wire of approved made
72Supplying/laying HDPE pipe
73Supplying and fixing of GI Wire (8SWG)
74P/Laying of armored aluminum conductor to be laid in already excavated cable trench. The job incl. refilling after cable laying and removal/disposal of surplus earth. a). 10mm 4 core armored aluminum conductor
75b). 16mm 4 core armored aluminum conductor
76c). 25mm 3.5 core armored aluminum conductor
77d). 25mm 4 core armored aluminum conductor
78e). 35mm 4 core armored aluminum conductor
79f). 50mm 3.5 core armored aluminum conductor
80g). 70mm 4 core armored aluminum conductor
81Fabrication, Supply & Installation of outdoor Canopy suitable for main panel board and Servo Stabilizer with complete cement concrete foundation and locking arrangement complete job.
82High Must AC street light with S.T Pole(6 lights - 50 W each) Luminary – LED 50 Watt each Pole - 9 meter length (Tabular pole with cement bottoming in ratio of 1:3:6 mix with 2x2x2.5) including nut bolts and other accessories
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail