| 1 | Repair/Routine maintenance including carrying out daily check of fire alarm/fire fighting system complete with electronic control panel consisting of 16 zones in 08 (Eight) Buildings Dhanush, Vrishabh, Tula, Makar, Mesh, \"G\" block, \"H\" block and Kumbh (G+14 floors) ie 15 stories includingpersonnel to attend the fire alarm system faults,testing, checking andreplacement of unserviceable components ie nuts, bolts, washers etc other than mentioned in schedulehere-in after.The fire alarm system consisting the following :-(a) Indicator(b) Electronic hooter(c) Manual call point(d) Smoke detector(e) Heat detector(f) Electronic fire control panel(g) Main/Zone cards(h) Battery of Fire panel DC supply(J) All wiring and cable connections |
| 2 | All as above item No 1 but17 zones in 2 (Two) Buildings Jyesta & Dhanista (G+15 floors) ie 16 stories complete all as specified and directed. |
| 3 | All as peritem No 1 above but 15 zones in 05 (Five) Buildings G block, F1 block, AQ block, AR Block and 200 Sailors accn (G+6 floors) ie 07 stories complete all as specified and directed. |
| 4 | All as peritem No 1 above but 12 zones in 02 (Two) Buildings i.e. Mulla Auditorium and SHO buildings (G+1 floors) ie 02 stories complete all as specified and directed. |
| 5 | All as per item No. 1 above but 16 zones in 02 (Two) Buildings Meena, Swati (G+13 floors) ie 13 stories complete all as specified and directed. |
| 6 | All as above item No 1 but17 zones in 4 (Four) Buildings Kanya, Chitra, Anuradha & Alaknanda (G+13 floors) ie 15 stories and 01 (One) Buildings Archana (G+15 floors) complete all as specified and directed. |
| 7 | All as peritem No 1 above but 15 zones in 04 (Four) Buildings Bharani, Saravana, Vidya & Vijaya (G+12 floors) ie 13 storiescomplete all as specified and directed. |
| 8 | All as peritem No 1 above but 12 zones in 04 (Four) Buildings Revati, Rohini, Karthikeya & Gemini (G+9 floors) ie 10 stories complete all as specified and directed. |
| 9 | Repair/Routine maintenance including carrying out daily check offire fighting system 09 zone complete 04 (Four) Buildings WNC Mess main bldg, Annex bldg, Hemadri and transist bldg (G+07 floors) ie 08 stories 04 (Four) Buildings Narmada, Tapti, Kaveri, Hoogly and Vishkarmabldg (G+06 floors) ie 07 storiesincluding attending system faults,testing, checking including replacement of unserviceable componentsie nuts, bolts, washers etcother than mentioned in schedule “A”here-in aftercomplete all as specified and directed |
| 10 | Supply and replacement, installation, testing & commissioning of micro processor based 2 wire fault tolerant loop, required loop net workable type 2 loop (each loop accessing maximum 99 detectors and 99 modules) fire alarm/detection control panel.The panel shall be able to give location of all fire/fault signal with address.The panel shall have rectifier, loop cards, 80 character LCD unit to indicate Fire/Fault signal with address.The panel shall have a built in power supply and battery charger alongwith maintenance free 7.2 AH, 2x12 volt SMF lead acid batteries capable of running for a minimum of 48 hours with battery charger complete as required and as per specifications duly approved by EN 54 complete including of all 15 Amp power point connection from meter room to fire control panel all as specified and directed by Engr-in-Charge.Make :- Bosch/Honey well/Schneider |
| 11 | Supply & fix in repair detectors Complying with and type certified to EN - 45 Addressable type multisensor detector with heat and smoke combination complete all as specified and directed. Make :- Schneider / Honey Well / Bosch |
| 12 | Supply and fix Beam Master detector with Transmitter and receiver complete all as specified and directed. |
| 13 | Supply & fix in repair Maintenancefreebattery duly charged12 V 7.2 AH complete all as specified and directed Make :- EXIDE / TATA Green / Amaron |
| 14 | Supply fix in replacement, Installation,Testing & Commissioning of Addressable electronic sounder cum strobe complete all as specified and directed. Make :- Schneider / Honey Well / Bosch |
| 15 | Supply,replacement, Installation,Testing & Commissioning of Addressable Type Manual Call Point with Mounting Base as required conforming (UL\"s Latest Edition Approved and NFPA compliant / VDS or LPCB tested and EN54 compliant) complete all as specified and directed. Make :- Schneider / Honey Well / Bosch |
| 16 | Supply and fixing in repair PVC insulated PVC sheathed armoured copper conductor cable of size 4Core x 1.5 Sqmm including fixing on walls with saddles complete all as specified and directed. |
| 17 | Supply, laying, jointing and testing in replacement of PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, conforming to IS 694 6 Core 0.5 sqmm including making necessary connection, with busbar/MCCB/DB\"s & testing complete all as specified and directed. |
| 18 | Material and labour for factory fabricated MS fire cabinet box as per Existing design made out flat CRCA of appropriate size and thickness 2 mmall as directed including and applying two coats of synthetic enamel paint over a coat of red oxide primer on panel fitted inside bldg on each floor by approved colour & fixed on wall withnecessary nuts/bolts or welding to existing MS pipe by supporting angle complete all as specified & directed. |
| 19 | Supply & fix in repair rubber hose pipe 30 mtr,20mm dia plain 2 ply rayon confirming IS-12585 braided high pressure complete all as specified and directed. Make:-Minimax / Safex /DUNLOP |
| 20 | Supply & fix in repaircanvas fire hose 63mm bore 15 m long confirming to IS 636-1988 having male/female brass coupling both end complete all as specified and directed. Make:-Minimax/Safex/DUNLOP |
| 21 | Supply & fix in repair Stainless steelNozzle 25 mm bore suitable for 63mm dia canvas pipe complete all as specified and directed.Make:-Minimax/Safex/DUNLOP |
| 22 | Supply & fix in repair hose Reel drum suitable for 30 mtrs X 20 mm dia rubber hose pipe complete all as specified and directed. Make:-Minimax/Safex/DUNLOP / Jyothi |
| 23 | Supply & fix in repair 100mm dia ERW MS pipe confirming IS-1239 and applying two coats of synthetic enamel paint over a coat of red oxide primer to pipeincluding supporting brackets complete all as specified and directed. |
| 24 | Supply & fix in repair 150mm dia ERW MS pipe confirming IS-1239 and applying two coats of synthetic enamel paint over a coat of red oxide primer to pipe including supporting brackets. complete all as specified and directed. |
| 25 | Supply & fix in repair gun metal Two way fire brigade inlet conection with adaptor ofsize 80 mm dia X 63 mm dia complete all as specified and directed. Make :- Minimax / Safex / DUNLOP |
| 26 | Supply & fix in repairsBranch pipe gun metal 63mm instantaneous inlet, made threaded outlet, 15mm bore nozzle complete all as specified and directed. Make :- Minimax / Safex / DUNLOP |
| 27 | Supply & fix in repair twin outlet hydrant valve 100mm having 65mm outlet with lock pin wheel complete all as specified and directed. Make:-Minimax/Safex/DUNLOP |
| 28 | Supply & fix in repair single outlet hydrant valve 100mm having 65mm outlet with lock pin wheel complete all as specified and directed. Make:-Minimax/Safex/DUNLOP |
| 29 | Supply & fixin repair sluice valve 150mm size both ends flayed with high tensile stainless steel spindle, I body as per IS-14846, ISI Marked,PN-1.6 including all joints with rubber or fibre board, nuts, bolts, washers complete all as specified and directed. |
| 30 | Supply & fixin repairSluice Valve 100mm size both ends flayed with high tensile brass spindle, bodyincluding all joints with rubber or fibre board, nuts, bolts, washers complete all as specified and directed. |
| 31 | Supply and fix in repair Foot valve150 mm dia ball type10/15Kg/sqcm (MODEL B-5) of(ISI marked) in position at location including Material and labourfor making flanged joints and repair and making good to existing PCC surface complete all as specified and directed. |
| 32 | M& L for Disconnecting motor frompump of any Make, model andremove Bearing using bearing puller gear and fix new bearingsat DE /NDE including necessary greasing ,check for proper shaft alignments such that no vibration produce during opertion of following capacity Motors. |
| 33 | (a)Pump coupled with 75 HP motor (Bearing size 6313-ZZ & 6312ZZ Make SFC/NBC/SKF) |
| 34 | (b)Pump coupled with 60 HP motor (Bearing size 6312 ZZ & 6311ZZ Make SFC/NBC/SKF) |
| 35 | (c)Pump coupled with up to 15 HP motor(Bearing size 6307 ZZ & 6309ZZ Make SFC/NBC/SKF) |
| 36 | Supply and fixingself lubricated asbestos non metallic and non graphite gland packingof sizes 8 to 12 mm complete all as specified and directed Make : Champion or techno and commercial equivalent |
| 37 | Material and labour scrapping of paint complete pump and motor, base frame and accessories complete including making new synthetic enamel paint of two coats over a coat of red oxide primer of motor of capacity 15 HP to 75 HP complete all as specified and directed. |
| 38 | Supply and fixing in repair fabrication of Iron frames size and thickness as per existing on site including nut bolts, washers , two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. |
| 39 | Supply and fixing in repair rubber vibration pads heavy dutyfor base frame as per sample suitable for the following size of pumpsets complete all as specified and directed. |
| 40 | 50 to 75 HP |
| 41 | 05 to 15 HP |
| 42 | Demolition of Exisiting concrete supporting block ofpumps and motor exceeding 15cm of thickness aboveand below ground level all specfied and directed by Engineer-in-charge |
| 43 | Material and labourcement concrete 1:2:4, type B-2 (using 40 mm graded stone aggregate) as in support of Base frame with MSbolts placed in concrete andhardstanding finishing even and fair without using extra cement all as specified. Note: Location of bolts and size of bolts should macht the previous one |
| 44 | Supply and laying in replacement of PVC insulated single core stranded copper unamoured power cable of sizes given below including HDPE pipe of suitable size fixing on walls with saddles :- |
| 45 | 35 Sq mm |
| 46 | 25 Sqmm |
| 47 | 16 Sqmm |
| 48 | Material and labourfor Disconnecting motor power cables of various sizes from electrical motor of different capacities and decoupling from thepump sets,removing and taking down carefully and transporting to authorised workshop ,Dismantaling stator and rotor carefully andrewinding stator assembly with supper enamelled copper windingwire of suitable gauge matching to existing gaugeand cleaning of slots ,core with carbon tetra chloride solution and apply two coats of insulation varnish and keep stator assembly in heating chamber to improve insulation strength ,reassemble motor completey and transporation to site ,coupling pump to motor and check for proper shaft alignments such that no vibratiobn produce during opertioncoupling to pump with exact alingment, connect power cables to motor and testing of following capacity motor complete all as specified and directed. |
| 49 | (a)75HP |
| 50 | (b) 60 HP |
| 51 | (c) up to 15 HP |
| 52 | Supply and fix in repair Star delta starter with Sheet metal enclosure company made, suitable for 75 HP/55 KW Pump set having contactor of size 65A, over load relay ranging from 45A to 65 Amp complete all as specified and directed. |
| 53 | Supply and fix in repair Star delta starter with Sheet metal enclosure company made, suitable for 60 HP/45 KW Pump set having contactor of size 50A, over load relay ranging from 45A to 65 Amp complete all as specified and directed. |
| 54 | Supply and fix in repair Star delta starter with Sheet metal enclosure company made, suitable for 15 HP/11 KW Pump set having contactor of size 25A, over load relay ranging from 12A to 18 Amp complete all as specified and directed. |
| 55 | Construction of brick masonery valve chamber in repair of size 1.2 x 1.2 x 1.2 M (internal dimension) (above GL 0.30 mtr) suitable for fixing of sluice valves, 15cm thick foundation using PCC 1:4:8 type D-2 over 15cm thick hardcore of broken stone, 23cm thick brick walls built in cement and sand mortar 1:4, 15mm thick internal and external plaster including top of floor in cement and sand mortar 1:3, 15mm thick, finished even and smooth, without using extra cement, 5 mm thick plate cover on 50mm x 50mm x 6mm MS angle frame embeded in PCC 1:2:4 type B-1coping, having rectangular, hinged, opening of size 150 x 100mm with locking arrangements ,hold fasts, etc, applying one coat of red oxide primer and two coats of synthetic enamel paint to all steel surfaces and earth work in any type of soil including disposal of debris outside MoD landcomplete all as specified and directed. |
| 56 | Supply and fixingPVC water storage Tank 5000 ltr capacity 3 layers , ISI marked, hosting and fixing in position at any locationremoving existing tank disconnecting all incoming & out going connection , provision of new tank fittings & connecting it at existing positionup to 50 mm GI Pipe connection completeall as specified and directed. |
| 57 | Supply and fixingPVC water storage Tank 3000 ltr capacity 3 layers, ISI marked,hosting and fixing in position at any locationremoving existing tank disconnecting all incoming & out going connection , provision of new tank fittings & connecting it at existing positionup to 50 mm GI Pipe connection completeall as specified and directed. |