National Security Guard-NSG has published Orm Of Fire Fighting Equipment At Nsg Manesar For The Year 21-22 Sh Sitc Of Starter Panel For Fire Pumps At Old Magazine And Providing And Fixing Of Ups In The Firing Fighting System Nsg Campus Manesar Orm Of Fire Fighting Equipment At Nsg Manesar For The. Submission Date for this Tender is 01-02-2022. Fire Fighting Consumable Tenders in manesar Haryana. Bidders can get complete Tender details and download the document.
Sl. No. | Item Description |
1 | Laying and Jointing PVC Pipe. Heading |
2 | SUB HEAD A REPAIR AND MAINTENACE OF PANEL |
3 | Fabrication, supply, installation, testing & commissioning of Electrical control panel of cubical construction, floor-mounted type, fabricated out of 2 mm thick CRCA sheet, with enclosure protection class IP 42, suitable for operation on415-volt, 50 Hz, 3 phase, 4 wire A.C. supply system, dust and vermin proof, powder-coated in an approved siemens grey shade after 7 tank treatment processes, compartmentalized with hinged lockable doors, detachable cable gland plates made of 3 mm thick CRCA sheet, cable alleys of suitable size on both sides for cabling routing, openable type rear cover and complete with 4 strips of copper bus bars of 800 Amps capacity with heat-shrinkable coloured sleeves and DMC/SMC bus bar supports at required intervals, control terminals, and suitable sized terminal blocks for incoming and outgoing cables, including providing interconnection with suitable sized copper conductor cable/solid copper strip and control wiring with suitable sized insulated copper conductor cable. The entire panel shall have one common copper bar of size 20 mm x 5 mm at the rear with 2 earth studs/terminals. |
4 | The panel shall be supplied with a bottom base MS channel, not less than 100 mm x 50 mm x 5 mm thick. Suitable size of M.V. Danger Boards shall be fixed on panel. The panel base should have four 300 mm long legs (made of angle irons 50 x 50 x 6 mm) to raise the panel from the floor, and a removable 2 mm thick powder-coated CRCA sheet cover must be provided on four sides of the pedestal. The base frame of the panel should be grouted into the floor with four 12mm dia x 200mm long bolts and nuts.The panel shall have provision to accommodate the following switch gears as mentioned below in Item No 2 and with the required front area (approximate front area 1800 mm X 2200 mm) and depth minimum 300 mm. (Drawings will be approved before fabrication of the panel). |
5 | Providing and fixing following switch gears, meters and accessoriesin existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. |
6 | Incomer |
7 | 630 Amps , FP, MCCB, 50 KA breaking capacity , Ics = 100% Icu withAdjustable overloadand Adjustable short-circuit protection with Spreaders Terminals - 1(Incomer ) |
8 | Rotary Handle (RHOM) for 630 A MCCB |
9 | 3Ph LED Ammeter Cl 1 with Inbuilt selector switch for 3 phases. |
10 | 3Ph LED Voltmeter Cl 1 (0-500V) with Inbuilt selector switch for 3 phases. |
11 | CTs 600/ 5 amps,with class 1.0 accuracy3Nos |
12 | LED Indicator Red, 240V AC. |
13 | LED Indicator Yellow, 240V AC. |
14 | LED Indicator Blue, 240V AC. |
15 | MCB TP 6A C-Curve 10kA |
16 | OUTGOING |
17 | STAR DELTA STARTERS for (120 HP / 90 KW, Three phase, 415 voltmotor pump set)3 NOS |
18 | 320 Amps , TP, MCCB, 50 KA breaking capacity , Ics = 100% Icu withAdjustable overloadand Adjustable short-circuit protection with Spreaders Terminals. |
19 | Rotary Handle (RHOM) for 320 A MCCB |
20 | 3 Pole, 415 V,Power Contactor AC3 dutyRating250 A. |
21 | Overload Relay. ( 60-100 A) |
22 | Add-on aux. contact Block (1 NO + 1 NC) for star delta starter. |
23 | CTs 400/ 5 amps,with class 1.0 accuracy. |
24 | Single Phasing Preventer with u/v &o/v , 3 PH 415 VAC. |
25 | Star Delta Timer.3-120s |
26 | LED Indicator Red, 240V AC. |
27 | LED Indicator Yellow, 240V AC. |
28 | LED Indicator Blue, 240V AC. |
29 | 3Ph LED Ammeter Cl 1 with Inbuilt selector switch for 3 phases. |
30 | Push Button for START(Green) |
31 | Contact block NO for Push Button |
32 | Push button forSTOP ( Red) |
33 | Contact block NC for Push Button |
34 | MCB DP, 10KA, 6AMP for Control circuit. |
35 | ON, OFF, trip indicating lamps. |
36 | Auto-Manual Selector Switch. |
37 | Providing and fixing following switch gears, meters and accessoriesin existingpanel boardof pump room including drilling holes inpanel, making connections, etc. as required including dismantling of existing switchgears and accessories. |
38 | STAR DELTA STARTERS for (20 HP / 15 KW, Three phase, 415 voltmotor pump set) |
39 | 80 Amps , TP, MCCB, 50 KA breaking capacity , Ics = 100% Icu withAdjustable overloadand Adjustable short-circuit protection with Spreaders Terminals. |
40 | Direct Rotary Handle (RHOM) |
41 | 3 Pole, 415 V,Power Contactor AC3 dutyRating80 A. |
42 | Overload Relay. ( 14-23 A). |
43 | Add-on aux. contact Block NOfor star delta starter. |
44 | Add-on aux. contact Block NC for star delta starter. |
45 | CTs 100/ 5 amps, with class 1.0 accuracy |
46 | Single Phasing Preventer with u/v &o/v . 3 PH 415 VAC. |
47 | Star Delta Timer. (3-120s) |
48 | LED Indicator Red, 240V AC. |
49 | LED Indicator Yellow, 240V AC. |
50 | LED Indicator Blue, 240V AC. |
51 | 3Ph LED Ammeter Cl 1 with Inbuilt selector switch for 3 phases. |
52 | Push Button for START(Green) |
53 | Contact block NO for Push Button |
54 | Push button forSTOP. (Red) |
55 | Contact block NC for Push Button |
56 | MCB DP, 10KA, 6AMP for Control circuit. |
57 | MCB SP, 10KA, 6AMP for Control circuit. |
58 | ON, OFF, trip indicating lamps |
59 | Auto-Manual Selector Switch |
60 | SITC of 1 Kva True Online, Double Conversion, UPS with minimum 15minute backup having 2 nos 12 V / 9 AH inbuilt Sealed Maintenance FreeBattery suitable for operation input voltage range 180-240 V and output voltage 230 +-1% i/c connection etc as reqd [ UPS Warranty - 12 Month ] |