| 1 | Supply installation, testing and commissioning of following HT panels complete with switchgear , metering,indication & protection relays |
| 2 | Supplying and erecting approved make 11kV Panel 1000A, 3 Pole Vacum Circuit breaker (Main In comer) (CT ratio-200/5A)withThree outgoing11kV Panel 800A, 3 Pole Vacum Circuit breaker (CT Ratio-50/5A each)( for two transformers & one stadup) as per enclosed drawing on provided MS cahnel /trench /foundation in an approved manner.Panel shall be Floor mounted free standing type, min. IP 41 enclosure, RAL7032, .As per attach GA &Section IV , VCB Specification No. 2, 2.1, 2.2All Incomers and outgoing shall be with bottom cable entry type.Make: Schnider, ABB, Sudhir Power Ltd. only |
| 3 | Supply installation, testing and commissioning of following transformer complete with complete assesories |
| 4 | Supplying and Erecting approved make 630- KVA,3 phase, 50 c/s Oil immersed and naturally cooled outdoor type, copper wound transformer with delta conn. on HV side & star connection on LV side with additional neutral brought out on loadside, voltage rating 11 / 0.415kV with HV tapping of +/- 2.5% - 5% continuously rated for full load with standard accessories complete with Test Certificate with losses below 1000 watts at no load, 7000 watts at full load as per IS:2026) Section IV , Transformer Specification No. 3, 3.1, 3.2 Make: Schnider, ABB, Sudhir Power Ltd. only |
| 5 | Miscellaneous Work |
| 6 | Dismetaling existingold 11 KV, 3 nos., OCB Complete from existing panel board in an approved manner in good condition. |
| 7 | Dismantling the existing Distribution Transformer of 500 KVA (each)capacity from the plinth / foundation safely without any damages and storing in safe place by crane. |
| 8 | Supplying , erecting & terminating 3 x 120 sq mm 11 kV, XLPE(E) armoured cable on wall/ceiling or laid in provided trench / pipe in an approved manner as per specification no.CB-HT. |
| 9 | Providing and erecting Heat shrinkable indoor termination kit for 11 kV ( E ) XLPE HT cable 3x120 to 185 sq. mm. with necessary material as per specification No. CB-JT/HT. |
| 10 | Providing structural steel work in single stanchions composed of R.S.J. Channel etc. with caps, bases, mild steel plates, angle brackets, cleats, gusset plates, anchor bolts etc. as per detailed design and drawings or as directed including cutting, fabricating, hoisting,erecting fixing in position, making riveted / bolted / welded connection and one coat ofanticorrosive paint and over it two coats of oil painting of approved quality and shade complete. Spec. No. : Bd.C. 6/Page No. 277 . |
| 11 | Providing earthing with Copper earth plate size 60 x 60 x 0.315 cm complete with all materials, testing & recording the results as per specification No. EA-EP, |
| 12 | Supplying and erecting copper strip of required size25 x 5 mm used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint in an approved manner with joints required. as per specification No(EA-EP) |
| 13 | Buy Back of 500KVA X 2 Nos. Transformers & 11 KV OCB X 3 Nos. (Less during a final order ) |