Madhya Pradesh Madhya Kshetra Vidyut Vitaran Company Limited-MPMKVVCL has published Rate Contract For Supply Installation Commissioning And Testing Of Scada Rt Das Equipments At Various Locations In Mpmkvvcl - 1 Remote Terminal Unit ( Rtu ) For 2 No. Power Transformer ( Having 1 Mcu 6A, 1 Power Card, 5 Di Card Of 32 Digital Input, . Submission Date for this Tender is 02-03-2022. Connectors Supply Tenders in bhopal Madhya Pradesh. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 18-Jan-2022 | Pre bid link against TS-738 | Other | 27-01-2022 |
2 | 27-Jan-2022 | Amendment against TS-738 | Technical Bid | 27-01-2022 |
3 | 27-Jan-2022 | Date extension against TS-738 | Date | 08-02-2022 |
4 | 08-Feb-2022 | Amendment2 against TS-738 | Technical Bid | 08-02-2022 |
5 | 09-Feb-2022 | Date Extension TS-738 | Date | 14-02-2022 |
6 | 14-Feb-2022 | Date extension against TS738 | Date | 21-02-2022 |
7 | 22-Feb-2022 | Date Extension | Date | 02-03-2022 |
Sl. No. | Item Description |
1 | REMOTE TERMINAL UNIT (RTU) FOR 2 NO. POWER TRANSFORMER (having 1 MCU 6A, 1 Power Card, 5 DI card of 32 digital input, 3 DO card of 16 Digital output, 1 DCAI card, 1 COM 6 cards, 1 DC Voltage Transducer) with communication protocol IEC 103/61850 ed2, DNP 3.0, Modbus, etc., 48V operated, with space to accomodate 1 number additional rack |
2 | MULTI FUNCTION TRANSDUCER 48V (5 Amp, 110 V with RS485 Modbus communication protocol |
3 | CONTACT MULTIPLYING RELAYS (CMRS) with 2NO + 1 NC operating at 30V DC |
4 | HEAVY DUTY RELAY (HDR) FOR CB TRIP/CLOSE (48V DC, 2 NO, 1 NC) |
5 | LDMS along with necessary LDMS software License and convertor 48V DC to 230V AC, 200 W(along with one chair and one table) |
6 | 48 V DC POWER SUPPLY (DCPS) SYSTEM BASED ON SMPS |
7 | DCPS battery set (48 V, 150/160 AH) capacity |
8 | Numerical relay SCADA compatible for 33 KV & 11 KV feeder protection |
9 | Auxiliary relay (MTR) 4 No and 4NC, 30V DC, 10 Amp |
10 | SCADA Compatible WINDING TEMPERATURE INDICATOR (WTI), DIAL 150MM, WITH CAPILARY, MERCURY SWICTH TYPE |
11 | SCADA Compatible OIL TEMPERATURE INDICATOR (OTI), DIAL 150MM, WITH CAPILARY, MERCURY SWICTH TYPE |
12 | 11KV/33KV stand-alone Fault Passage Indicator (1 Gateway/FRTU + 3 FPI) complete with GPRS enabled modem (SCADA Compatible) |
13 | 11KV/33KV stand-alone Fault Passage Indicator (1 Gateway/FRTU + 6 FPI) complete with GPRS enabled modem (SCADA Compatible) |
14 | 11KV/33KV stand-alone Fault Passage Indicator (1 Gateway/FRTU + 9 FPI) complete with GPRS enabled modem (SCADA Compatible) |
15 | Battery for 11KV stand-alone Fault Passage Indicator (FPI) 3.6V-2000 mAH |
16 | Battery for 11KV stand-alone Fault Passage Indicator (FRTU/Gateway) 12V - 21AH |
17 | AC/DC Auxiliary Supply Board with suitable MCB & Fuse protection |
18 | Earthing of RTU/FRTU Panel |
19 | FRTU Supply & installation:- comprising panels, racks, sub-racks, Power Supply modules, minimum 02 cards of 32 Digital Input module, CPU Analog MCU card with minimum 03 Ethernet port04 COM port, DCAI, 1 DC Voltage Transducer & support all standard Protocol IEC (i.e. 103, 61850, 104, Modbus), DCPS (24V) with dual battery of minimum 4 hrs backup as per specification interfacing equipment along with 30V DC to 24V DC convertor, dual sim 4G modem with active-active mode with fallback facility of 4G/3G/2G, and 50% additional space for modules as well as space for 1 number additional rack |
20 | MULTI FUNCTION TRANSDUCER 24V (5 Amp, 110 V with RS485 Modbus communication protocol |
21 | DC Voltage Transducer |
22 | Dual SIM 4G Router/ modem with Active-Active mode with fallback facility of 4G/3G/2G |
23 | Additional Rack for RTU/FRTU |
24 | MCU 6A Module Card Master 48V operated |
25 | MCU 1A Module Card Master 48V operated |
26 | MCU 4A Module Card Slave 48V operated |
27 | MCU 6A Module Card Master 24V operated |
28 | MCU 1A Module Card Master 24V operated |
29 | MCU 4A Module Card Slave 24V operated |
30 | Power Module Card 48V operated |
31 | Power Module Card 24V operated |
32 | DI Card having 32 Digital input, 48V operated |
33 | DI Card having 32 Digital input, 24V operated |
34 | DO Card having 16 Digital output, 48V operated |
35 | DO Card having 16 Digital output, 24V operated |
36 | AI Card having 8 Analog input, 48V operated |
37 | COM 6 Card, 48V operated |
38 | DCPS (24V) with dual battery of minimum 4 hrs backup |
39 | Convertor 48V DC to 230V AC (200 watt) |
40 | Convertor 30V DC to 48V DC (400 watt) |
41 | Convertor 30V DC to 24V DC (200 watt) |
42 | SCADA RTU installation on suitable stand/ civil structure |
43 | SCADA RTU commissioning & integration with control center, creation of database, SLD and End to End testing |
44 | RT-DAS FRTU commissioning & integration with control center, creation of database, SLD and End to End testing |
45 | SCADA Feeder Panel retrofitting and termination of either ends including all cables, lugs, ttb, connectors and accessories etc. |
46 | SCADA PTR Panel retrofitting and termination of either ends including all cables, lugs,ttb, connectors and accessories etc. |
47 | SCADA Capacitor Bank retrofitting and termination of either ends including all cables, lugs, ttb, connectors and accessories etc. |
48 | RT-DAS Feeder Panel work with termination of either ends including all cables, lugs, ttb, connectors and accessories etc. |
49 | RT-DAS PTR Panel work with termination of either ends including all cables, lugs, ttb, connectors and accessories etc. |
50 | RT-DAS Capacitor Bank Panel work with termination of either ends including all cables, lugs, ttb, connectors and accessories etc. |