Establishment Of National Data Centre For North Eastern Region At Guwahati, guwahati-Assam

Public Works Department-PWD has published Establishment Of National Data Centre For North Eastern Region At Guwahati. Submission Date for this Tender is 15-02-2022. Building Repair Tenders in guwahati Assam. Bidders can get complete Tender details and download the document.




Tender Notice

30656469
Corrigendum : Establishment Of National Data Centre For North Eastern Region At Guwahati
Open Tender
Indian
Assam
guwahati
15-02-2022

Tender Details

Establishment Of National Data Centre For North Eastern Region At Guwahati

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 29-Jan-2022 Extension Notice Date 15-02-2022

Key Value

Document Fees
INR 12500 /-
EMD
INR 31154000.0 /-
Tender Value
INR 155.76 Crore /-

BOQ Items

Name of Work: "Establishment of National Data Centre for North Eastern Region at Guwahati"
Sl. No. Item Description
1Surface dressing of the ground including removing vegetation and inequalities not exceeding 15 cm deep and disposal of rubbish, lead up to 50 m and lift up to 1.5 m. All kinds of soil
2Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-incharge. All kinds of soil
3Earth work in surface excavation not exceeding 30 cm in depth but exceeding 1.5 m in width as well as 10 sqm on plan including getting out and disposal of excavated earth upto 50 m and lift upto 1.5 m, as directed by Engineer-in- Charge: All kinds of soil
4Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials. All kinds of soil
5Eart work in excavation by machanical means (hydruolic excavator ) / manual means in foundation trenches or drains ( not exceeding 1.5 m in width or 10 sqm on plan ) including dressing of sides and remaining of bottoms , lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed , with in a lead of 50m All kinds of soil
6Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
7Supplying chemical emulsion in sealed containers including delivery as specified. Chlorpyriphos/ Lindane emulsifiable concentrate of 20%
8Diluting and injecting chemical emulsion for POST CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : Providing anti – termite treatment to buildings conforming to I.S.S. 6113 part II 1971 (revised) including adoptingprecautions for health hazards and safety measures as required therein with the cost of all labour, plants, equipments required for the treatment and furnishing a guarantee for a minimum period of 10 years from the date of completion including eradicatingany infestation of termite free of cost during the guaranty period complete. (The payment will be made on plinth of the building. (Note : Guarantee to be furnished as per approved format on Rs 100/- stamp paper) Labour Rate Only
9Providing and laying in position cement concrete of specified grade excludingthe cost of centering and shuttering - Allwork up to plinth level : 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
10Providing and laying in position ready mixed plain cement concrete, with cement content as per approved design mix and manufactured in fully automatic batching plant and transported to site of work in transit mixer for all leads, having continuous agitated mixer, manufactured as per mix design of specified grade for plain cement concrete work, including pumping of R.M.C. from transit mixer to site of laying and curing, excluding the cost of centering, shuttering and finishing, including cost of curing, admixtures in recommended proportionsas per IS : 9103 to accelerate/ retard setting of concrete, improve workability without impairing strength and durability as per direction of the Engineerin- charge. All works above plinth and upto floor V level : Cement concrete in platforms M-15 grade plain cement concrete (cement content considered @ 240 kg/cum)
11Cement concrete in sunken floor M-10 grade plain cement concrete (cement content considered @ 220 kg/cum)
12Extra for providing and mixing water proofing material in cement concrete work in doses by weight of cement as per manufacturer"s specification.
13Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement: 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top smooth.
14Centering and shuttering including strutting, propping etc. and removal of form work for : a)Foundations, footings, bases and foundations for shed columns
15b) Walls ( any thickness) including attached pilasters, buttresses,plinth and string courses etc.
16c) Suspended floors, roofs, landings, balconies and access platform.
17d) Shelves (Cast in situ)
18e) Lintels, beams, plinth beams, girders, bressumers and cantilevers
19f) Columns, piers, abutments, pillars, posts and struts.
20g) Stairs, (excluding landings) except spiral-staircases
21h) Weather shade, Chajjas, corbels etc., including edges
22Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of de-shuttering and decentering at all levels, over a height of 3.5 m, for every additional height of 1 metre or part thereof (Plan area to be measured). Suspended floors, roofs, landing, beams and balconies (Plan area to be measured)
23Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources and using recycled concrete aggregate (RCA) as coarse aggregate and fine aggregate within permissible utilization of 20% each, Portland Pozzolana /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. a)All works upto plinth level : Concrete of M35 grade with minimum cement content of 370 kg /cum
24All works above plinth level up to floor V level : Concrete of M35 grade with minimum cement content of 370 kg /cum
25Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Concrete of M25 grade with minimum cement content of 330 kg /cum A) Upto Plinth level
26B) Above plinth level upto floor V level
27Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto Plinth level. Thermomechanically Treated Reinforcement TMT
28Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in foundation and plinth in: Cement mortar 1:6 (1 cement : 6 coarse sand)
29Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in : Cement mortar 1:6 (1 cement : 6 coarse sand)
30Providing and laying autoclaved aerated cement blocks masonry with 150 / 250 / 300 mm thick AAC blocks in super structure above plinth level up to floor V level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately).
31Providing and laying Aerocon panels 100x600x3000mmwith approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge.Make-Birla,AEROCON
32Providing and laying Aerocon panels 75x600x3000mmwith approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge.Make-Birla,AEROCON
33Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level. Cement mortar 1:4 (1 cement : 4 coarse sand)
34Providing and laying autoclaved aerated cement blocks masonry with 100 mm thick AAC blocks in super structure above plinth level up to floor V level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rate includes providing and placing in position 2 Nos 6 mm dia M.S. bars at every third course of masonry work.
35Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry.
36Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite stone slab colour black, Cherry/Ruby red Area of slab over 0.50 sqm
37Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length ( hold fast lugs or dash fastener shall be paid for separately). Second class teak wood
38Providing and fixing ISI marked flush door shutters conforming to IS2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws
39Extra for providing lipping with 2nd class teak wood battens 25 mm minimum depth on all edges of flush door shutters (over all area of door shutter to be measured).
40Extra for providing vision panel not exceeding 0.1 sqm in all type of flush doors (cost of glass excluded) (overall area of door shutter to be measured): Rectangular or square
41Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. Fixed to openings /aluminium frames with rawl plugs screws etc.
42Providing and fixing aluminium die cast body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 35 kg and door width upto 700 mm), with necessary accessories and screws etc. complete.
43Providing and fixing aluminium pull bolt lock, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed of required colour and shade, with necessary screws bolts, nut and washers etc. complete.
44Providing and fixing 50 cm long aluminium kicking plate of size 100x3.15 mm, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary
45Providing and fixing IS : 12817 marked stainless steel butt hinges with stainless steel screws etc. complete :100X58X1.90 mm
46Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete :150x10 mm
47Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete :100mm
48Providing and fixing aluminium casement stays, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.
49Providing and fixing panelling or paneling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows ( area of opening for panel inserts excluding portion inside grooves or rebated to be measured). Panelling for panelled and glazed shutters 25mm to 40mm thick: Pre-laminated with decorative lamination on both side exterior Grade - I MDF Board 12 mm thick confirming to IS:14587
50Providing and fixing of non-metallic asbestos free composite fire cum smoke check door frame with shutter for 2 hrs. Fire Rating door system duly tested for Stability, Integrity and Insulation a criteria clause 9.4 as per I5 3614 Part -1 nd BS 476 Part 22 for single and double leaf Doors |tested from CBRI Roorkee with 2nd class teak wood Frame of section 145mm x 70mm with heat activated intumescent fire seal strip of size 10mm x 4mm (Astroflame/Marshall) and one coat of anti-termite fire retardant primer along with minimum 55mm thick fire/smoke check wooden shutters of 120 minute fire rating comprising of two Nos. 9mm thick only Starpancalcium silicate board only a 100% without asbestos, Brucite and Meerschaum having density not more than 950 Kg/M3 and thermal conductivity 0.14 W/m*k sandwiching 31mm thick fire resistance insulation filler coated with FR sealants and faced with 3mm thick commercial ply facing on both sides with heat activated intumescent fire seal strips of size 10mmx 4mm (astroflame U.K.) mounted in the grooves of hardwood lipping on three sides except bottom. The door shall be finished with 1mm thick laminate on both sides. The single/double leaf doors shall be provided with vision panel of minimum size 300 x 300 mm made out of 5 mm thick clear boro silicate fire rated glass (imported) for 120 minutes fire rating of Schott (Germany) /Pilkington/Aasahi(lapan) fully transparent in fire/non-fire conditions having minimum moulding beading and filling the gap between moulding /beading and glass with suitable sealant including fixing each shutter with hinges of size 102mm x 76mm x 3mm with SS screws Marshall/ IR Briton / Assa Abloy.The door frame in this item and edges of the door shutters shall be painted with fire retardant paint of "BERGER"/" SUKRI" or equivalent to provide Class 1 surface spread of flame conforming to BS 476 Part 7, IS: 12777 in desired shade over a coat of fire resistant primer The manufacturer should have tested the entire assembly from CBRI Roorkee along with the fire rated vision panels,same brand of calcium silicate board and hardware for achieving 2 hrs.fire rating and shall submit the same for both single leaf and double leaf configurations prior to manufacturing to the Engineer-in-charge for approval of production. (Hardware to be paid for seperataly only vision panel cost is included in the item.
51HINGES: Supply and fixing of Dorma’s BB4330 /Ingersoll Rands" Briton’s / Marshall’s fire rated 304 grade stainless steel ball bearing hinges of size 102x76x3mm of approved make with 8 Nos. stainless steel screws for 2hrs. Wooden / metal fire doors and for Class room acoustic doors.Make Marshall,IR Briton,Assa Abioy
52Providing and fixing of 2 hrs. fire rated stainless steel 304 grade push type panic bars for double leaf 2 hour fire rated door shutter tested and certified as per IS 3614 Part II and BS 476 Part 20 & 22 from CBRI Rorkee with necessary accessories and screws etc. all complete as per the specifications of the approved vendor and as per the direction of the Engineer – in-charge. Make and Catalogue No/Item Code: (Ingersoll Rand’sBriton Exit Device Rim - BT F-600 - R- SS 3 SS 304 & Vertical Rod BT F - 600V - SS 3 X8 SS 304 (which strike), Assa Abbloy s Yale - YPE RM501P + YPEVR506P SSS, Marshall"sSSS MH-P- RM11002and Dorma"sPHA 2000 active leaf 1-point moular, inactive leaf 2 - point modular.(for double leaf doors).Make Marshall,IR Briton,Assa Abioy
53Providing and fixing of 2 hrs. fire rated stainless steel 304 grade push type panic bars for single leaf 2 hour fire rated door shutter tested and certified as per IS 3614 Part II and BS 476 Part 20 & 22 from CBRI Rorkee with necessary accessories and screws etc. all complete as per the specifications of the approved vendor and as per the direction of the Engineer – in-charge. Make and Catalogue No/Item Code: (Ingersoll Rand’sBriton Exit Device Rim - BT F-600 - R- SS 3 SS 304 & Vertical Rod BT F - 600V - SS 3 X8 SS 304 (which strike), Assa Abbloy s Yale - YPE RM501P + YPEVR506P SSS, Marshall"sSSS MH-P- RM11002and Dorma"sPHA 2000 active leaf 1-point moular, inactive leaf 2 - point modular.(for single leaf doors).Make Marshall,IR Briton,Assa Abioy
54OUTSIDE ACCESS DEVICE :Provindig and fixing of stainless steel 304 grade outside access trim for single/double leaf door shutterwith necessary accessories and screws etc. all complete as per the specifications of the approved vendor and as per the direction of the Engineer – in-charge. Make and Catalogue No/Item Code: (Ingersoll Rand’sBriton -BT 600- BT 1600 L - SS including cylinder, Assa Abbloy s Yale - YPE ACC004 , Marshall"s MH- PB- ACC11003and Dorma"sPHX03 Trim. - for Staircase locations and Auditorium exit doors.Make Marshall,IR Briton,Assa Abioy
55D- TYPE HANDLE:Supply and fixing of 304 grade stainless steel D-type back to back pull handle of size 300mm long and 22 mm dia with complete screws for wooden, metal fire doors & class room doors. Make and Catalogue No/Item Code: (Ingersoll Rand"s Briton – C4721. 300B2B, Marshall - MHBTB-1000 & Dorma"s -TGDID-9125407).Make Marshall,IR Briton,Assa Abioy
56DEAD LOCK: Providing and fixing 2 hours fire rated dead lock system with required80mm thick pin cylinder with both sides key arrangement of approved makes in Wooden / Metal fire door shutters with necessary accessories and screws etc. all complete as per the specifications of the approved vendor and directions of the Engineer- in-charge. Make and Catalogue No./Item Code: (Briton- 5410 series / Dormakaba- 288a, Marshall: MH-L-13002 XX) for both metal & wooden fire doors and class room doors.Make Marshall,IR Briton,Assa Abioy
57DOOR CLOSER:Providing and fixing of Dorma"s TS 89, Ingersoll Rand"s Briton"s LCN 1460 and Marshall"s MH DC S14016 C extruded aluminum body heavy duty 2 hours fire rated door closer with stainless steel full body cover. The door closers should be of size 1-6, non handed havingback check, and delayed action and shall be tested and certified along with thefire doors from CBRI Roorkee as per IS 3614 Part II & BS476 Part - 20 & 22The door closer shall have 10 years mechanical warranty from the manufacturer and the same shall be submitted to the Engineer - in - Charge. The door closer complies with EN 1154 - for 100000 cycles and is ANSI/BHIMA certified. - for Staircase, Corridors, AuditoriumMake Marshall,IR Briton,Assa Abioy, Lift lobby, Prefunction, Transformer, Electrical and all other mechanical rooms.
58FLUSH BOLT: Supply and fixing of Dorma’s 9114306, Briton’s DAL FBH 6, Marshall’s MS 300 304 grade Stainless Steel exposed Tower Bolt of size 16mm dia rod and 250 mm long with complete screws. (Marshall Make)Make Marshall,IR Briton,Assa Abioy
59ALLENKEY :Providing and fixing of allen"s key from Ingersoll Rand"s Briton, Assabloy, Marshall & Dorma. - for Shaft doors.Make Marshall,IR Briton,Assa Abioy
60FRAME: Providing and fixing non load bearing fixed frame for fire resistant glazed partition for 120 min fire rating, made out to a profile of dimension 60mmx70mm of 1.6 gauge stainless steel 304 grade steel sheet as per test evidence suitable for fixing fire rated glass for 120 min of stability & integrity and 20 minutes of insulation. The profile has to be fixed to supporting construction by means of Anchor fasteners of size M10x80, every 150 mm from the edges and every 500mm (aprox) c/c. Linear measurement of frame shall be measured for payment. The frame shall be filled with rockwool insulation of density not less than 96kg/m3. The fixed partition frarning as a complete shall achieve 120 minutes Integrity & Stability and 20 minutes insulation criteria as per the requirements of NBC 2016 Make-Sukriti doors,MPP doors,Signum doors, Godrej
61SHUTTER :Providing and fixing glazing in fire resistant door shutters, fixed panels & partitions etc., with Stainless Steel made out of 1.6 mm thick of size 20 x 33 mm screwed with M4 x 38 mm SS screws at distance 75 mm from the edges and 150 mm c/c & special ceramic tape of 5 x 20 mm size etc complete in all respect as per direction of Engineer- in- charge. The glass shall be clear, toughened, single layered, clear glass panes minimum 10mm thickness for full glazing of approved brand having minimum 120 minutes fire resistance of various sizes and at required locations in the fire doors. The glasses shall be clear borosilicate fully transparent in firetesting non- fire condition (929% transparency ) completly non- opaque, toughened from Schott (Germany)/ Pyro guard (France}/ Pilkington ( U.K) glass of 120 minutes fire rating and fixing in position with S.S. beading and sealants at joints etc. complete as directed by the Engineer-in-Charge. The glass shall be tested from CBRI Roorkee/ Warrington"s Fire Research Laboratory as per BS-EN 1364-1: 1999/ BS476 Part 2/ EN 13501-2: 2003 along with the complete a5sembly of the fire door with hardware. The manufacturer shall submit 3rd party the valid test reports for approval of the specialized agency. Make-Sukriti doors, MPP doors, Signumdoors,Godrej Make of Fire Rated Glass SCHOTT Germany, Asahi India, Plikington
62HINGES: Providing and fixing of Dorma’s / Ingersoll Rands" Briton’s / Marshall’s fire rated 304 grade stainless steel ball bearing hinges of size 102x89x3mm of approved make with 8 Nos. stainless steel screws for glazed fire doors.Make Marshall,IR Briton,Assa Abioy
63Providing and fixing of stainless steel 304 grade Offset D-type Pull Handles (for Glazed Fire doors) of 350 mm x 25mm dia (minimum) of approved make with necessary accessories and screws etc. all complete as per the specifications of the approved vendor and directions of the Engineer-in-Charge. Make and Catalogue No/Item Code: (Briton – C4723.400/ Assa Abbloy: AEH-06A/ Marshall - MHOD1001 & Dorma"s - 9125422)
64NARROW STYLE DEAD LOCK: Supply and fixing of 2hrs fire rated Narrow Style dead lock with 80mm double cylinder one side key and other side knob with 1 years’ mechanical warrantyfor glazed fire doors. Make and Catalogue No./Item Code: Ingersoll Rand"s, Marshall"s MH-MP 13004 SSS & Dorma"s – 917
65FLUSH BOLT: Supply and fixing of Dorma’s 9114306, Briton’s DAL FBH 6, Marshall’s MS 300 304 grade Stainless Steel exposed Tower Bolt of size 16mm dia rod and 250 mm long with complete screws. - for all lockable double leaf doors.
66Providing and fixing factory made single extruded WPC (Wood Polymer composit) doorframe comparising of virgion PVC polymer of K value 58-60(susprnsion grade) calcium carbonate and natural fibers (wood powder /rise husk/wheat husk) and non toxic addatives (maximum toxcity index of 12 for 100 gms) fabricated with mitered joints after applying PVC solvent cement and screwed with full body threaded star headed SS screws having minimum frame density of 850 Kg/Cum screw withdrawl strength of 2200 N Face and 1100 N Edgemodulus of elasticity 900 N/mm2 and resistant to spread of flame of class a catagory with properity of being termite/borer proof water/moister proof and fire retardant and fixed in position with MS hold fasts /lugs /SS dash fasteners of required dia and length complete as per direction of Engineer in Charge (MS Hold fasts/lugs or SS dash fasteners to be paid seperately.Make of WPC Doors framesshall beEcoste,Quite Extrusions,Echon Note:-For WPC Solid door frames minus 5mm tolreance in dimensions i e depth and width of profile shall be acceptable . Varitoion in profile dimensions on plus side shall be acceptable but no extra payment on this account shall be made. Frame size 63x125mm
67Providing and fixing factory made single extruded WPC (Wood Polymer composit) doorframe comparising of virgion PVC polymer of K value 58-60(susprnsion grade) calcium carbonate and natural fibers (wood powder /rise husk/wheat husk) and non toxic addatives (maximum toxcity index of 12 for 100 gms) fabricated with mitered joints after applying PVC solvent cement and screwed with full body threaded star headed SS screws having minimum frame density of 850 Kg/Cum screw withdrawl strength of 2200 N Face and 1100 N Edgemodulus of elasticity 900 N/mm2 and resistant to spread of flame of class a catagory with properity of being termite/borer proof water/moister proof and fire retardant and fixed in position with MS hold fasts /lugs /SS dash fasteners of required dia and length complete as per direction of Engineer in Charge (MS Hold fasts/lugs or SS dash fasteners to be paid seperately.Make of WPC Doors frames shall beEcoste,Quite Extrusions,Echon Note:-For WPC Solid door frames minus 5mm tolreance in dimensions i e depth and width of profile shall be acceptable . Varitoion in profile dimensions on plus side shall be acceptable but no extra payment on this account shall be made. Frame size 45x95mm
68Providing and fixing factory made single extruded WPC (Wood Polymer composit) solid decorative type flush door shutters of required sizeof K value 58-60(susprnsion grade) calcium carbonate and natural fibers (wood powder /rise husk/wheat husk) and non toxic addatives (maximum toxcity index of 12 for 100 gms) having minimum frame density of 650 Kg/Cum screw withdrawl strength of 1800 N Face and 900 N Edge modulus of elasticity 850 N/mm2 and resistant to spread of flame of class A catagory with properity of being termite/borer proof water/moister proof and fire retardant . WPC to be laminated with PVC foil of 14 microns thick of approved design pasted with hot melted adhesive on both faces of shutter and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk SS screwsas per direction of Engineer in Charge (Stainless steel butt hinges and SS screws shall be paid seperately) Make of WPC Doors shall beEcoste,Quite Extrusions,Echon 35 mm thick
69Providing and fixing factory made single extruded WPC (Wood Polymer composit) solid decorative type flush door shutters of required sizeof K value 58-60(susprnsion grade) calcium carbonate and natural fibers (wood powder /rise husk/wheat husk) and non toxic addatives (maximum toxcity index of 12 for 100 gms) having minimum frame density of 650 Kg/Cum screw withdrawl strength of 1800 N Face and 900 N Edge modulus of elasticity 850 N/mm2 and resistant to spread of flame of class A catagory with properity of being termite/borer proof water/moister proof and fire retardant . WPC to be laminated with PVC foil of 14 microns thick of approved design pasted with hot melted adhesive on both faces of shutter and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk SS screwsas per direction of Engineer in Charge (Stainless steel butt hinges andSS screws shall be paid seperately) Make of WPC Doors shall beEcoste,Quite Extrusions, Echon 30 mm thick
70Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid board one side white color and other side of board laminted with PVC foil of minimum 14 micron thickness of approved design pasted with hot melt adhesive for cup boards, work stations and bathroom/kitchen cabinet etc. of required sizes comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) & 900 N (Edge), , modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with property of being termite/ borer proof, water/moisture proof and fire retardant and fixing with stainless steel piano hinges/soft close clip on concealed hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In- Charge. (Note: stainless steel piano hinges/soft close clip on concealed hinges and necessary S.S screws shall be paid separately) Make of WPC board shall beEcoste,Quite Extrusions,Echon 18mm thick
71S & F 18 mm thick block board with commercial ply veneering on both side
72Providing and fixing panelling or panelling and glazing in panelled or panelled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured). Panelling for panelled or panelled and glazed shutters 25 mm to 40 mm thick : Float glass panes 5.0 mm thick glass panes (weight not less than 12.5 kg per sqm)
73Providing and fixing approved brand and manufacture SS304 Grade Towerbolt( TS1210SS -12" SS304) with screws etc. complete in all respects as per manufacturers" specifications & as directed by Engineer-incharge (Dorset) 300 x 10mm
74Providing approved brand Stainless Steel 304 Grade -Sliding Bolt (250X16mm) along with necessary accessories and screws etc. complete. a) 250 x 16mmMake Dorset Item code no. ALD SM SS 304 (250x16) or equivalent as per Specifiation.
75b) 300 x 16mmMake Dorset Item code no. ALD SM SS 304 (300x16)
76Providing and fixing Brass Door stopper - Door Mounted Hanging Type ( Dorset DSHT) along with necessary accessories and screws etc. complete. (Dorset)
77Providing approved brand and manufacture SS304 grade 250mm Pull Handle with 10 mm dia (SOP10SS (10MM)) fixed with Ssscrews etc.complete in all respects as per manufacturers" specifications & as directed by Engineer-in-charge 250 mm x10mm D-Shape Handle (Make; Dorset Item Code no. SOP 10 SS
78Providing approved brand and manufacture SS304 grade D type 300mm Pull Handle with 19 mm dia (SD12PSS (19MM)) fixed with Ssscrews etc.complete in all respects as per manufacturers" specifications & as directed by Engineer-in-charge
79Providing & fixing special quality & designCentre patch lock with cylinderPSS :Polished lock for frame less 12 mm thick toughened glass shutters including necessary SS Screws etc.of make DorsetItem code no. DPF-325 complete as per the direction of Engineer-in-charge.
80Alumin Sliding Rails top of Aluminimum alloy of size 100x100mmwith iron and Nylon wheel integral bearingrollers and sliding arrangement set complete
81Providing approved brand and manufacture SS304 graded or Buffer wall mounted 22 mm dia,75 mm long (DB(22)) without Cover fixed with SS screwsetc. complete in all respects as per manufacturers" specificatios & asdirectedby Engineer-in-charge (Dorset)
82Providing and fixing IS : 12817 marked stainless steel butt hinges (heavy weight) with stainless steel screws etc. complete : 125x64x2.50 mm
83Providing Only 1 mm thick 35 mm wide bright finished stainless steel piano hinges complete :
84Providing and fixing special quality chromium plated brass cupboard locks with six levers of approved quality including necessary screws etc. complete. Size 50mm
85Providing and fixing special quality chromium plated brass cupboard locks with six levers of approved quality including necessary screws etc. complete. Size 75mm
86Providing and fixing approved brand and manufacture SS304 Grade Towerbolt( TS610SS -6" SS 304) with screws etc. complete in all respects as per manufacturers" specificatios&asdirectedby Engineer-incharge (Dorset) 150 x 10mm(Cup Boards)
87Providing approved brand and manufacture SS304 grade 200mm Pull Handle with 10 mm dia (SOP8SS (10MM)) fixed with Ssscrews etc.complete in all respects as per manufacturers" specifications & as directed by Engineer-in-charge 200 mm x10mm D-Shape Handle (Make; Dorset Item Code no. SOP 8 SS
88Providing and fixing magnetic catcher of approved quality in cupboard / ward robe shutters, including fixing with necessary screws etc. complete. Double strip (horizontal type)
89Supply and fixing 12mm thick compact laminate HPL Board cubicals for WC/Toiletswith SS 304 foot sliding latch with idicator (corona Saftey) withAccessories: Standard - Merino Make Aluminum, Stainless Steel - 304 Grade accessories) ,Aluminum "U" Channel,F Channel, door stopper channel , SS Coat Hook, SS Privacy Thumb turn c/w Occupancy Indicator ,SS Door Knob,SS Spring Loaded Butt Hinges with Cover ,SS Adjustable Foot 316 Grade ,Rubber Door Stopper Lining,S.S.Screws 304 G & P.V.C Wall PlugsMake Marino Size of Cubicle : 1000 X 1500X 2003mm (H) Door Size : 1750mm (H) x 600mm (W) Divider Size : 1775mm (H) Overall Height Of Cubicle : 2003mm (Including bottom Gap of 150mm)
90Structural steel work in single section, fixed with or without connecting plate,including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
91Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
92Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6 mm angle iron and 3 mm M.S. gusset plates at the junctions and corners, all necessary fittings complete, including applying a priming coat of approved steel primer. Using M.S. angels 40x40x6 mm for diagonal braces
93Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25 mm M.S. laths with 1.25 mm thick top cover
94Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.).
95Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
96Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry, but excluding the cost of nosing of steps etc. complete. 40 mm thick with 20 mm nominal size stone aggregate
97Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge. In flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand)
98Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge. In dado/skirting on 12 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand)
99Supply and installation of Simpurity PUR homogeneous vinyl sheet flooring manufactured by Armstrong World Industries, Inc, 2 metre wide and overall thickness of 2mm. The thickness of wear layer would be 2mm. The product should be homogeneous and single layered. The wear surface shall consist of impregnated polyurethane homogeneous mixture of PVC with TRUESHIELD & Diamond 10 technology, Plasticizers without DOP, Urethane, color pigments and filler calendered to form a sheet. Color and pattern details shall be dispersed throughout the thickness of the wear layer. Simpurity shall conform to group "T" wear resistance as per EN 649, Clean Room certified with class "A" as per ASTMF5100, Flammability resistance of class Bfl-s1 as per EN13501-1, Dynamic coefficient of friction of class DS as per EN 13893, Impact sound reduction of 3dB as per ISO 10140, Slip Resistance of class R9 as per DIN 51130, Color fastness rating of =6 as per ISO 105-B02, total weight being 3.3kg/m2 as per EN430. The product shall be suitable for applications in class 23/34/43 areas as per EN685. Product shall exhibit antistatic behaviour, resistance to bacteria,resistance to chemical, resistance to staining,suitability to castor chair. The product shall be FloorScore certified with no SVHC content published by European Chemicals Agency(REACH). Product shall contribute to LEED points under Indoor environmental quality(LEED EQ) and Material & Resource (LEED MR) category.
100Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/sqm including pointing the joints with white cement and matching pigment etc., complete.
101Deduct for not using 20 mm thick cement mortar 1:4 (1 cement : 4 coarse sand) bedding in laying of floor tiles and jointing with grey cement slurry @ 3.3 kg/ sqm.
102Fixing glazed/ Ceramic/ Vitrified floor tiles with cement based high polymer modified quick-set tile adhesive (Water based) conforming to IS: 15477, in average 3mm thickness.
103Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
104Providing and laying Antiskid Vitrified tilesin floor with different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately). Size of Tile 600 x 1200 mm
105Providing and laying Vitrified tiles in floor with different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately). Size of Tile 600x600 mm
106Providing and laying full body Vitrified tiles in floor with different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately). a)Size of Tile 600x1200 mm
107b)Size of Tile 600x1200 mm Corridor dado
108c)Size of Tile 600x900 mm Fire Stair Case dado
109Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately). Size of Tile 600x600 mm
110Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size of Tile 800x800 mm
111Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix of 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg), including filling / grouting and finishing complete as per direction of Engineer-in-charge. Size of Tile 600x600 mm
112Providing and fixing removable raised/false access flooring with system and its components of approved make for different plenum height with possible height adjustment upto 50 mm, comprising of modular load bearing floor panels supported on G.I. rectangular stinger frame work and G.I. Pedestal etc. all complete, as per the architectural drawings, as specified and as directed by Engineer-in-charge consisting of:FLEXI CL64 800 Bare Panel PANEL Flexi CL64 800 lbf Access Floor Panels having dimensions of 600 x 600 mm ± 0.20 mm shall be all Steel welded construction with an enclosed bottom pan of 64 hemispherical cones. The Top plain Sheet is fuse welded to the bottom pan at 144 Locations to form a Panel of an overall thickness of 28mm. The Panel after required pre-treatment is epoxy coated to a thickness of 40 to 60 Microns epoxy coating to ensure corrosion resistance. The inner empty core of the Panel is injected with a light weight, non-combustible cementitious compound at high pressure to fill in all the crevices of the Panel and ensure support of not less than 90% of the top surface area of the Panel. Panel shall be capable of withstanding 800 lbf point load tested as per CISCA testing procedure and conforming to Master specs standard for Raised Flooring SUB-STRUCTURE - PEDESTAL& STRINGER ASSEMBLY: Sub structure installed to support the panel shall be suitable to achieve a minimum finished floor height of 950 mm from the existing floor level. Pedestal design shall confirm speedy assembly and removal for relocation and maintenance. The assembly shall provide easy adjustment of levelling and accurately align panels for a maximum of ± 25 mm in the vertical direction. Pedestals shall support an axial load without permanent deflection and an ultimate load as laid out in System Performance requirement. The bottom of the Pipe is beaded to achieve perpendicularity & resistance to moment which will arise from lateral loading & also arresting the vertical movement before riveting the pipe to the base plate. The Sub structure assembly shall be anchored to the floor with Adhesive for FFH upto 450 mm, and above FFH 450 mm with suitable Adhesive and Machine Screw wherever necessary, as recommended by the Consultant in list of approved makes. 950 mm Finished Floor Height (FFH).
113Providing & Fixing of Flocked textile floor covering of Nylon 6.6 face fiber or equivalent ofapproved make with 100% Nylon and completely water proof resilient backing. The flooringshould be Anti static with thickness of 4.3 mm and approximate weight of 1.8 k.g./sqm of rollform. The carpet should be completely stain resistant and of a density approx. 80 millionfibers/sq.mtr (70 million fiber/sq.yd) in the width of 2 mtr .The floor covering should have FireTest EN-13501, Appearance Retention Hexapod ISO 140-8, Friction Slip Resistance Test EN14041 Class DS, SANITISED anti-microbial treatment, with resilient waterproof backing, antiallergic which is certified by British allergy foundation, with ten year guarantee. The carpetshould have permanent static control Make JCC/Modulyss/Flotex
114Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
115Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
116Providing and laying Polished Granite stone dado/skirtingin required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
117Deduct for not using 20 mm thick cement mortar 1:4 (1 cement : 4 coarse sand) bedding in laying of floor tiles and jointing with grey cement slurry @ 3.3 kg/ sqm.
118Add for 12 mm cement plaster of mix :1:4 (1 cement: 4 coarse sand)
119Providing and laying tactile tile (for vision impaired persons as per standards) of size 300x300x9.8mm having with water absorption less than 0.5% and conforming to IS:15622 of approved make in all colours and shades in for outdoor floors such as footpath, court yard, multi modals location etc., laid on 20mm thick base of cement mortar 1:4 (1 cement : 4 coarse sand) in all shapes & patterns including grouting the joints with white cement mixed with matching pigments etc. complete as per direction of Engineer-in-Charge.
120Supply and installation of 2mm thick vinyl flooring laid over approved adhesive.The installation shall be undertaken as per manufacturers installation instructions.
121Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick
122Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete.
123Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/sqm including pointing the joints with white cement and matching pigment etc., complete.
124Deduct for not using 20 mm thick cement mortar 1:4 (1 cement : 4 coarse sand) bedding in laying of floor tiles and jointing with grey cement slurry @ 3.3 kg/ sqm.
125Fixing glazed/ Ceramic/ Vitrified floor tiles with cement based high polymer modified quick-set tile adhesive (Water based) conforming to IS: 15477, in average 3mm thickness.
126Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
127Surface Preparation: Cleaning the surface thoroughly with wire brush, soft brush and required tools to eliminate all defective materials and foreign matter.Repair all cracks joints and junctions withpolymer modified cementitious mortarso as to achieve the sound surface for treatment. Makingfilletwithpolymer modified mortarat the junction of the slab and wall so as to achieve curvature and seal the junctions.(size-75mm x 75mm) Base Waterproofing Coating on RCC Slab :- Providing and applying Texgum Rubberise coating.To be applied in 2 coats a flexible waterproofing coating over the Priming coat. coating to be done as per manufecture specifications, while providing the intermediate layer of 30 gsm Geo mesh sandwitched between the two coats. Coating has a crack bridging capacity upto 1-2mm. 1) Providing and applying thermal insulation laying Sopra XPS 50mm thick XPS, extruded polystyrene. XPS polystyrene should have minimum thickness of 50mm and shall have closed cell structure so as to ideal for insulation of roofs. XPS should have compressive strength of 300 KPa (as per EN 826) ; Resistance to Fire of "E" Class; Water Absorption of <0.7% (as per EN 12087) ; Thermal resistance of 1.5 sqm.KW; Thermal Conductivity of 0.029- 0.034 W/m-k (as per EN 12667) and should be laid directly over the cured waterproofing layer as per manufacturer specification. Third Part:Supplying and installingBBA Certified 1.2mm thick single ply waterproofing sheet membrane comprising of TPO membrane. SIngle ply TPO roof waterproofing membrane shall be asbestos free, and should exceed /meet specifications of EN 13956:2012. Single Ply Flagon TPO Roof Membrane is a modified polyolefin membrane that accepts roof movement and thermal shock.It should be lapped and seamed using hot air heat welding equipment with an overlap of 80mm. Joints shall be of 80mm overlapin case of covered roof systemand shall be welded with automatic single seam machine such as Varimat V2 of Leister technologies and terminations by hand welding. Control tests of the welds with Welding tester shall be performed. Termination strip to be used for fixing single ply TPO membraneat the final termination point for accomodating wind load impact; Such metal strip shall be sealed with PU Sealant. Conduct weld tests with Welding tester, and test of triple points with vacuum cap. Single Ply TPO membrane shall be from original product manufacturer and method statement shall be produced by original product manufacturer. Single Ply TPO membrane shall be asbestos free, and should haveCE (European Conformity for Quality) under original product manufacturer. 1.2mm thick single ply TPO membrane shall have following minimum properties , (i) Tensile Strength > 1100 N/5cm as per EN 12311-2;(ii) Elongation of > 15% as per EN 12311-2;(iii) Tear Strength > 300 N, as per EN 12310-2;(iv) Cold bending of minimum <(-) 25 deg as per EN 495-5 ;(v) Fire classification – Class E as per En 13501-1 & EN ISO 11925-2,(vi) Static Puncture Resistance - > 20 kg as per EN 12730.Flashings required should be included in rate for roof area. Approved Product: Flagon EP/PR of Soprema, Sintec, Isoltema Termination of Waterproofing: Waterproofing shall be taken minimum 300mm above FFL. Terminated with TPO Termination strip & sealed with sealent. Fourth Part: Providing and laying 200 GSM Polyester Geotextile with joints sealed with tape. Geotextile shall be 100mm overlapped Approved product: Rooftex Geotextile of Soprema, Sintec, Isoltema
128Supply of durlum POLYLAM® vertical Aluminium AA 3000 Series baffle system, exhibiting space-delineating characteristics. The system com-prises baffles 50 mm width X 150mm deep manufactured out of 0.7mm Thick Aluminium, installed at 150mm C/C distance. The carrier rails run perpendicular to the baffles. Individual baffle lengths be-tween 300 and 2400 mm can be selected. Baffle ceiling are supplied with the end cap matching the similar finish of baffle. Tolerances ac-cording to TAIM, DIN EN 13964 and quality controlled to ISO 9001:2015 approved by SIS. Substructure for durlum POLYLAM® Ver-tical baffle system consisting of U shaped galvanized slotted carriers minimum 1.2mm Thick installed perpendicularly to baffle ceiling at maximum 1200mm C/C using officially approved dowels. The primary profiles must be connected to one another with longitudinal splice connectors. The entire ceiling module shall be suspended with 6mm diameter galvanized steel threaded rods from the true ceiling offi-cially approved anchor fasteners maximum at 1200mm Centres as per the requirements of DIN EN 13964 and the statics of the system. En-sure horizontal and flush alignment during installation. Baffle lengths less then 1500mm requires 2 carrier rails. Surface: Baffles shall be in Wood Grain Finish Mode of Measurements: Measurements shall be wall to wall without any deductions for lights, diffuses, columns etc.
129Supply of durlum Custom made Vertical curve Polylam Blades Ceilings as per the design intent. The vertically curve baffle system POLYLAM exhibiting space- delineating characteristics. The system comprises vertically curve baffle with 100-150mm deep curved rafters manu-factured out of 1.2 mm Aluminium to provide wave effect. The mod-ule for fixing baffle shall be 150mm centres as per design require-ment. The carrier rails run perpendicular to the baffles axis and can be mounted with M6 threaded rods using technical approved fasten-ers as per EN 13964 standards. The individual baffle lengths between 1200- 2400 mm can be selected. Baffles lengths less than 1500mm required two carrier rails mounted at the baffle ends. Baffle longer than 1500mm require additional carrier rails mounted in the centre. Finish RAL Powder Coated. No Pre-Coated products shall be accepted. The spacing of the grid an-gles is according to the requirements of DIN 18168 and DIN EN 13964 and quality controlled to ISO 9001:2015 approved by SIS & LEED cer-tification by Indian Green Building council (IGBC). GMS 1.2 carrier and 1.2 L angle Make Durlum, Harsons, Green, Dampa, Dexune
130Supply of durlum S4 Hook On plank ceiling with form fitting & tension free planks 300 Wide, upto 1500- 1800 mm Long manufactured of 0.7 mm AL. Perforation 1.8 dia holes with acoustic fleece soundtex tissue for 0.7 NRC The ceiling planks shall be with square edges on 4 side. The substructure consisting of form punched angles as a lateral grid which is suspended pressure-rigid from the bare ceiling with M6 threaded rods using officially approved dowel plugs. The angles are to be connected at the ends by means of longitudinal connectors. The spacing of the grid angles is according to the requirements of DIN 18168 and DIN EN 13964 and quality controlled to ISO 9001:2008 ap-proved by TUV. On the grid angles, Z-shaped carrier profiles are attached as longitu-dinal profile with M6 bolts [secured against loosening]. The longitudi-nal connection of the Z-shaped carrier profiles is made by means of profile connectors. The planks shall be manufactured on advanced equipment which includes several levelling stages in manufacturing process. The plank ends will be raised with pips & stops to ensure ac-curate fixing & demounting of individual panel. Panels to be installed in segmented curve pattern to achieve the design orientation. Speci-fication of sub structure will be as per the manufacturer recommen-dation. Finishes of ceiling planks shall be RAL powder coating with approved 3d printing on metal planks. The spacing of the grid angles is accord-ing to the requirements of DIN 18168 and DIN EN 13964 and quality controlled to ISO 9001:2015 approved by SIS & LEED certification by Indian Green Building council (IGBC). Finish Wood Grain 3D digital printing pattern
131Providing and fixing Microline grid Wall angle of 19mmx19mmx0.40mm shall be screw fixed to brick wall/partition with the help of approved screws at 600mm centres. Then suspending Microline Main T grid of 15mm x 35mmx 0.3mm of length 3600mm is hung with adjustable level clips 85 x 31 x 0.6mm with 4mm Dia Rod which are connected to Soffit Cleat 37mmx27mmx1.6mm and 8mm dia 40mm long Anchor Fasteners @1200mm centres or as approved from RCC Slab.. The Cross T of 15mm x 35mmx0.3mm of 1200mm length shall be interlocked between main T Grid at 600mm centres to form 1200 x 600mm modules.  Then USG BORAL Olympus Max™ ceiling panel having FLB edge of size 600x1200mm shall be placed into the above grid of size 600x1200mm. This ceiling panel confirms to ASTM E84 surface burning characteristics. (Class A, Flame Spread<25 & Smoke developed<50). The Ceiling panel provides NRC 0.7, CAC minimum: 35. Light Reflectance: 88%, can withstand Relative Humidity up to RH 99% (limiting conditions –Max 49 degree C/99%RH) and have Recycle content 61%. The tile contains a broad-spectrum antimicrobial additive on the face and back of the panel that provides resistance against the growth of mold and mildew. Third party certified for low-emitting performance as per ASTM Standard Guide D5116 - 10.USG Boral Microline 15mm T Grid System (600mm x 1200mm)
132SECUROCK Glass mat sheathingBoard(1220mm x 2440mm): This includes USG Boral Thundersteel Perimeter Channel 0.50 mm thick having one flange of 20 mm and another flange of 30 mm and a web of 28 mm) screw fixed to brick wall/partition with the help of approved screws at 600 mm centers Then suspending USG Boral Thundersteel intermediate section 45 mm x 0.90 mm thick with two flanges of 15 mm each) from the soffit at 1220 mm centers with USG Boral Thundersteel Ceiling L Angle 25 x 10 mmx 0.50 mm thick) fixed to RCC Slab with USG Boral Soffit Cleat 37 x 27 x 1.6 mm and 8 mm Dia 40 mm Long Anchor Fasteners 1200 mm Centers, respectively USG Boral Thundersteel profiles are rolled with AZ Steel 150 GSM 310 MPa Yield Strength) having base metal conforming to IS 513 2016 as per IS 15961 2017 AS 1397 2001 USG Boral Thundersteel Ceiling Section 51 mm x 0.50 mm thick with two flanges of 27 mm each) are then fixed to the USG Boral Intermediate channel with the help of 2.64 mm dia wire connecting in perpendicular direction to the intermediate channel at 400 mm centers 12.7 mm thick USG Boral SECUROCK Glass mat sheathingBoard is screw fixed with 25 mm long Drywall screws at 230 mm centers The screw fixing of gypsum boards to the metal framing at the periphery, openings and cut edges should be at 150 mm centers All the boards must be staggered All joints to be taped finished with USGBORAL Paper tape All Purpose Joint Compound confirming to ASTM C 475 of Make USG Boral,Knauf,Saint Gobain 12.7 mm thick USG Boral SECUROCK Glass mat sheathingBoard
133Providing& fixing in position wall panelling at all heights of thickness 25 mm with CredenceFiber Glass Acoustical Wall Panels of size 600x1500 mm creda resin bonded square edges having NRC of 0.9 minimum. The panels should be manufactured from high density bio-soluble resin bonded glass wool absorber having density of 96 Kgs/m3 and wrapped on the front side with an acoustically transparent fabric having option of colours and fabric type like jute, etc. as per approved by architect/engineer-in-charge plain tissue backer and fabric wrapped hardened edges. Panels should have humidity resistance up to 90 %, thermal conductivity = 0.03 (m² k / w) thermal resistance = 0.9 (m² k / w) & moisture rate = 1% (JC/T670 – 2005). The panel should be fully recycled and fire retardant as per Class A. The installation comprises a GI framework for acoustic wall panelling as per design drawing (made from especially fabricated galvanized iron sheets 0.55 mm thick pressed section galvanizing @ 120 grams per sqm including both sides) consisting of floor channel of size 50X32X32X0.55 mm thick bottom and top fixed with nylon sleeves and screw. Further vertical GI studs of size 48X34X36X0.55 mm thick are placed at 600 mm center to center vertically on the wall using 12 mm dia 50 mm long wedged type expanded zinc alloy dash fastener with 10 mm bolt, to avoid any undulations on the wall. The extra channel must be used at openings and junctions as required. Further, wooden batten/ply of 6mm thickness and a width of 5” to be placed at 600 mm center to center horizontally on the vertical GI Studs. Surface impalers of size 3”X4” having projecting element called spikes shall be fixed on the wooden batten surface at 1200 mm center to center horizontally and 600 mm center to center vertically, using self tapping screws. Silica based construction adhesive to be dabbed on to the projecting elements (spikes) of the impalers. Silica based construction adhesive to be dabbed on to the projecting elements (spikes) of the impalers. Wall Panels shall be pierced through the spikes of the impalers ensuring line & level of panel are maintained. The panels should be mounted on the impalers horizontally or vertically as per the approved design or as per the directions of the engineer-in-charge.
134Supply of durlum aluminium perforated Clip in type ceiling system with swing down slide function of size 600X600mm of approved make, made up of 0.7 mm Aluminium, measured without RAL Non-metallic powder coating, bevelled edge, finish of ceiling tiles should be electrostatically applied polyester powder coated finish of mini-mum 60 microns paint thickness, perforations with hole diameter 1.8 mm and open area 21%, with soundtex tissue at back of the panel to achieve 0.70 NRC as per EN ISO 354, applicable norms EN13964/10152/10346,supported by fully concealed clip in suspen-sion system manufactured in accordance with European standards & technical regulation of TAIM e.V., the components of substructure to be manufactured from cold rolled zinc-galvanized steel in accordance with EN 13964/10152/10346/14195 and EN ISO 12944.The clip in profile made of galvanized steel 0.60 mm Installed at 600mm c/c and cross connected to the suspension channel connector made of gal-vanized 0.70 mm steel @ 1200 c/c for clip in swing down ceiling ,length 100 mm along with hanger lower section for suspension chan-nel, hanger upper section for available ceiling void, including safety pin, self-tapping screws etc, The ceiling system elements, manufac-tured from zinc-galvanized steel , including powder coated surface in colour RAL non-metallic and bonded acoustic tissue on reverse side should be tested & approved according to EN 13501-1 building class A2-s1,d0, The installation & maintenance has to be carried out in ac-cordance with manufacturers guidelines as well as technical stand-ards issued by TAIM as approved by the Engineer-in-Charge. Finishes of ceiling tiles: RAL non-metallic polyester powder coat finish with minimum 60 microns paint thickness.
135Supply of durlum SW 4.2 Custom Made wall cladding Panels size 1200mm(L) x 300mm(W) manufactured out of 0.9 mm aluminum with Powder Coating. The Perforated and Non-PERFORATED wall panels shall be with square edges. All panels are fixed onto vertical C Chanel profiles 2.0mm Thick GMS installed with adjustable C Bracket 1.2mm GMS installed to the concrete/ prefixed sub frame (If re-quired). Tolerances and quality requirements according to TAIM, DIN EN 13964.All fixing accessories shall be external grade SS. No additional framing, bridging, lateral supports considered in the quoted prices Panel Thickness: 1.20mm Aluminum Surface Finish: RAL Flexible PPC with Digital Printed 3D Pattern Perforations: 2.1 mm dia holes. Sound Absorption: Soundtex tissue acoustic fleece for 0.7 NRC Dimensions: Upto 1200mm (L) X 300(W) mm Substructure: Proprietary hook-on vertical substructure SW02 man-ufactured out of 2.0mm Galvanized Steel, Wall Bracket SW01, other fixing accessories included. Additional back frame from wall to support the substructure of Dur-lum SW 4.2 wall paneling shall be in the Main contractor scope.
136Providing & Fixing wall planter base pots having minimum 5 years of warranty made in high quality unbreakable plasic in stackable mechanism which allows cascading iriigation method. The cost includes instlattion of different plant species as per direction of engg-inchargeor by architect. The whole integrated system shall include the installation of framework, plants, irrigation system, HDPE drip pipe, Lateral dipper, Filters , joints & Auotmation timer etc. Make Wonderwall, Four leaf, Bio Vertical
137Providing and fixing factory made 30MM (18MM Flutes + 12 MM Base) thick Homogeneous HDHMR pasted on a 12 MM thick HDHMR Plain Board with a second Generation MS polymer based hybrid All surface sealant, pressed in Temperature & Pressure controlled press, Solid Dark Green Colour board Fluting Panel, with CNC (Computer Numeric Control) Routed of approved design (Rectangular or Arched or both) by Engineer-in-charge which are machine cut for Panelling/Partitioning and acoustic Purposes comprising of Wood Fibre/Wood chips & synthetic thermosetting resin, having a minimum density of 820 kg/cum and screw Withdrawal strength of 1500 N (Face), 1250 N (Edge), Modulus of Elasticity average, 3200N/mm2, Modulus of rupture average 3200N/mm2 with properties of being termite/borer proof, moisture/water Wall Paneling: Providing and fixing factory made 30MM (18MM Flutes + 12 MM Base) thick Homogeneous HDHMR pasted on a 12 MM thick HDHMR Plain Board with a second Generation MS polymer based hybrid All surface sealant, pressed in Temperature & Pressure controlled press, Solid Dark Green Colour board Fluting Panel, with CNC (Computer Numeric Control) Routed of approved design (Rectangular or Arched or both) by Engineer-in-charge which are machine cut for Panelling/Partitioning and acoustic Purposes comprising of Wood Fibre/Wood chips & synthetic thermosetting resin, having a minimum density of 820 kg/cum and screw Withdrawal strength of 1500 N (Face), 1250 N (Edge), Modulus of Elasticity average, 3200N/mm2, Modulus of rupture average 3200N/mm2 with properties of being termite/borer proof, moisture/water proof and fixing on M.S. Frame (mild steel) made of 50 X 50 X 1.5 MM Square Hollow Box section including applying a priming coat of approved steel primer, with necessary stainless steel fasteners and SS Screws etc., all complete as per direction of Engineer – in – charge. (Note; MS (Mild Steel) or G.I. Framework with priming coat and necessary SS fasteners and SS screws shall be paid separately).Make Greenlam, Ecoste, Merlin Ply-la
138Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
13912 mm cement plaster of mix : 1:4
14015 mm cement plaster on the rough side of single or half brick wall of mix :1:6 (1 cement: 6 fine sand)
14120 mm cement plaster of mix 1:4 (1 cement: 4 fine sand)
1426 mm cement plaster of mix : 1:3 (1 cement : 3 fine sand)
143Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface Water thinnable cement primer
144Finishing walls with textured exterior paint of required shade : New work (Two or more coats applied @ 3.28 ltr/10 sqm) over and including priming coat of exterior primer applied @ 2.20kg/10 sqm) Stone granule paint finish
145Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives. New work (Two or more coats applied @ 1.43 litre/ 10 sqm. Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm.
146Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade: Two or more coats on new work
147Painting with synthetic enamel paint of approved brand and manufacture to give an even shade : Two or more coats on new work
148Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
149Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. Two or more coats on new work
150Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade : Two or more coats on New work.
151Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer"s specifications including appropriate priming coat, preparation of surface, etc. complete. On steel work
152Providing and fixing dry cladding upto all heights with 18mm thick gang saw cut stone with (machine cut edges) of uniform colour and size upto 1.22mx1.82m, fixed to structural steel frame work and/ or with the help of cramps, pins etc. and sealing the joints with approved weathersealant as per Architectural drawing and direction of Engineer-in-charge. (The steel frame work, stainless steel cramps and pins etc. shall be paid for separately). Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
153Deduct for not using 20 mm thick cement mortar 1:4 (1 cement : 4 coarse sand) bedding in laying of floor tiles and jointing with grey cement slurry @ 3.3 kg/ sqm.
154Providing and fixing of 8mm thick "Tectiva" through-coloured Cement-Composite Cladding Untrimmed Panels as a ventilated-facade system on the exterior walls of the building using the exposed-fastening system with rivets to an aluminium substructure. The vertical aluminium substructure shall consist of "T" and "L"profiles spaced at a maximum interval of 600mm c/c to coincide with the horizontal spacing of the rivets with provision for uninterrupted natural ventilation of min. 25mm space between the cladding panels and the structural wall from top to bottom. Vertical "T" profiles measuring approx. 120mm x 60mm shall be fixed at the vertical joints of two panels. Vertical "L" profiles measuring approx. 40mm x 60mm shall be fixed at intermediate fixing points, or where the edge of only one panel is to be fixed. At the outer corners, aluminium tubular profiles of 38mm x 62mm shall be used to take fixings of corner panels on adjacent faces of the building. The aluminium substructure shall be fixed to the plastered masonry structure or unplastered R.C.C. structure using HDG Steel L-brackets (Galvanized thickness minimum 80 microns)with AISI 304 stainless steel screws and Hilti/ Fischer AISI 304 stainless steel anchor fasteners as required at a maximum spacing of 1800mm c/c vertically (actual spacing to be derived from the structural calculation). The Cement-Composite Cladding Panels shall be riveted from the front to the vertical aluminimum sub-frame behind. The facade boards must be fixed with a fix-point in the middle of the board. All other fixations are sliding points. In case of two intermediate supporting profiles, two fix-points at the same horizontal level are allowed. The rivets shall have a maximum spacing of 600mm c/c in the horizontal direction and 600mm c/c in the vertical direction (however the actual rivet distances may be lower depending on the wind load). The rivets located near the panel edges shall be at a minimum distance of 30mm to 100mm from the vertical edges of the panels and 70mm to 100mm from the horizontal edges of the panels. Also, 6mm foam tape vertically to be fixed between tectiva panels and aluminium profiles. Thejoints between adjacent panels to be an 8-12mm open grooves horizontally and 8-12mm grooves vertically (aluminimum profile running behind the grooves in vertical groove) and profile behind the grooves should be painted black on visiable surface (horizontally and vertically). A minimum open groove of 25mm shall be left open at the top and bottom of the Cement-Composite Panel Wall for air circulation which may be concealed using a perforated profile, complete all to the satisfaction of the Engineer-in-charge.Make Equitone,Fibrec,Swisspearl,. Fabricator shall Be ALKARMA, AGVALFAB, WINDORZ 8mm thick "Tectiva" through-coloured Cement-Composite Cladding
155Providing and fixing of Aluminum composite panel (LEED CERTIFIED FOR GREEN BUILDING) of total thickness 4mm comprising of aluminium skin of 0.5mm with KYNAR 500 based fluorocarbon paint finish (70% resin) + 3mm Fire Retardant Mineral Filled Core comprising of around 70% Inorganic Compound which is 100% non-combustible mineral and balance virgin polymer + 0.5 mm aluminium skin with mill finish/service coat. Aluminium skin and core material must be bound together with adhesive film of minimum 100 microns’ thickness. The thickness of the adhesive film used for the lamination of the panels should be 100 microns. The weight of the panel should be minimum 7.5 kg/m2 (± 5%). The ACP product must conform to either NFPA 285 & BS 8414 standards along with Class B s1 d0 of EN 13501 standard. The manufacturer must furnish Class 1A certificate from TUV for this FR ACP produced in the plant from which it is going to be supplied. The aluminium composite panel top and bottom skin should confirm to Aluminium Alloy 3xxx series and H 14/24 temper with mechanical properties confirming to EN 485-2 standard. The top coated surface shall comply with the “specification for coated coil for the exterior building application” issued by ECCA (European Coil Coating Association). The coating shall confirm to AMMA-2605 for superior performing of exterior grade finish. The finished surface shall be protected with a self-adhesive (Rubber based) peel off foil with 70 microns thickness white or black, tested to withstand up to 6 months exposure to local weather condition without losing the original peel off characteristic or causing stain or other damages on the coated surface of the aluminum composite panel. Environment and Health aspects: - Environment management system (ISO 14001:2015), Occupational Health & Safety (OHSAS 18001:2007) and Quality management system (ISO 9001:2015)
156Providing and fixing factory made 18 mm thick single extruded WPC (Wood Polymer Composite) solid plain white colour board Jali, CNC (Computer numeric control) routed of approved design by Engineer in -charge which are machine cut for duct/shaft covering, partitions and facades comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium corbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives(maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/ cum and screw withdrawal strength of 1800 N (Face) minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with properties of being termite/borer proof, water/moisture proof and fire retardant and fixing on M.S (mild steel) frame made of 25 x 25 x 1.5 mm square hollow box section including applying a priming coat of approved steel primer, placed at grid made at 1.0 x 1.0 m or as per requirement at site with necessary stainless steel fasteners and SS screws etc., all complete as per direction of Engineer-In- Charge. (Note: M.S (mild steel) framework with priming coat and necessary SS fasteners and SS screws shall be paid separately.
157Providing and fixing structural steel frame (for dry cladding with 18/25/40mm thick gang saw cut with machine cut edges sand stone or GRC Jali ) on walls at all heights using M.S. square/ rectangular tube in the required pattern as per architectural drawing, including cost of cutting, bending, welding etc. The frame work shall be fixed to the wall with the help of M.S. brackets/ lugs of angle iron/ flats etc. which shall be welded to the frame and embedded in brick wall with cement concrete block 1:2:4 (1 cement :2 coarse sand :4 graded stone aggregate 20 mm nominal size) of size 300x230x300 mm, including cost of necessary centring and shuttering and with approved expansion hold fasteners on CC/RCC surface, including drilling necessary holes. Approved cramps/ pins etc. shall be welded to the frame work to support stone cladding, the steel work will be given a priming coat of Zinc primer as approved by Engineerin- charge and painted with two or more coats of epoxy paint (Shop drawings shall be submitted by the contractor to the Engineer-in-charge for approval before execution). The frame work shall be fixed in true horizontal & vertical lines/planes. (Only structural steel frame work shall be measured for the purpose of payment, stainless steel cramps shall be paid for separately and nothing extra shall be paid).
158Providing and fixing of pre-painted solid aluminium panels of 2mm thickness.These solid aluminium sheets should be pre-painted with high quality PVDF coating on continuous colour coating lines to maintain colour consistency.The product must conform to Class A1 s1 d0 of EN 13501 standard. The weight of the panel will be 5.4 kg/m2 with a tensile strength of = 125 Mpa.The solid aluminium sheet should confirm to Aluminium Alloy 3003 grade series and H24 temper with mechanical properties confirming to standards.The top coated surface shall be pre coated. Post painting by way of powder coating or spray coating is not allowed. Colour consistency with pre coating is desired - (Aluminium Solid sheet to be folded/bend/routed as per designs on 50mmx50mmX2mm thick Aluminium tubular frame with screw,struts,cleats. ) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to perform as per specification and drawing. Joint between two panels to be filled with backup rod and all weather silicon.
159Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket (thermal break profile) etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) : For fixed portion:Polyester powder coated aluminium (minimum thickness of polyester powder coating 50 micron)
160For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Polyester powder coated aluminium (minimum thickness of polyester powder coating 50 micron)
161Providing and fixing Insulated profiles of Polyamide for thermal separation of having U value not more than 3.3 w/m2 degree C, to minimize the thermal effect of the environment on the building’s air conditioning in Aluminium profiles of approved door/window/ventilator systems, as per technical specifications, drawings and direction of Engineer-in charge complete.
162Providing & fixing for hardwares in Aluminium thermal break windows/doors/ventilators with proper water drainage slots & gaps and wool pile for dust proof along with silicone at crimping joints in sliding and casement systems with hardware listed below (a&b) to with stand the weight of Insulated Glass panel, etc. , as per technical specifications, drawings and direction of Engineer-in charge complete. a) Hardware for casement window with 2 Locking Point shall be stainless steel 304 Grade and as under:Unica Handle item code 01150FFF of GIESSE make or equivalent.External Kititem code 2409 of GIESSE make or equivalent.Rod driveitem code 4099 of GIESSE make or equivalent Adjustable Pawlitem code 4030 of GIESSE make or equivalent Strikeritem code 1343 of GIESSE make or equivalent Polymideof Nylon item code 3524590 of GIESSE make or equivalent Friction Stay Type C Plus 14” Armitem code 8224 of GIESSE make or equivalent. b) Hardware for Top Hung window/Ventilator with 2 Locking Point shall be stainless steel 304 Grade and as under: Euro Cremone item code 01000FFF of GIESSE make or equivalent. Connection Blockitem code 2236 of GIESSE make or equivalent. Corner driveitem code 4019 of GIESSE make or equivalent Adjustable Pawlitem code 4030 of GIESSE make or equivalent C W Strikeritem code 1267 of GIESSE make or equivalent Polymideof Nylon item code 3524590 of GIESSE make or equivalent Friction Stay Type P Plus 20” Armitem code 8539 of GIESSE make or equivalent. Limiter Arm item code 8184 of GIESSE make or equivalent
163Designing, fabricating, testing, protection, installing and fixing in position semi (grid) curtain wall glazing using mechanically fixed DGU Glass with the support of aluminium pressure plate and cover plate. (a) Functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, nuts, bolts, clamps etc., structural and weather silicone sealants, microwave cured EPDM gaskets for ALP/Mona Make for water tightness, pressure equalisation & drainage and protection against fire hazard including: (b) All glazing panels will be pre-fabricated from factory & no fabricaion & cutting will be done on site inorder to have a tight quality control . Fabricating and supplying serrated M.S. hot dip galvanised brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners of Hilti / canon/ fisher Make. (c) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-incharge. (GLASS IS A SEPERATE ITEM)Providing and fixing Insulated profiles of Polyamide for thermal separation will be paid in item no. 10.6 extra over this item. 1.1
164Extra for openable side /top hung vision glass panels (DGUs) including providing and supplying at site all accsories and hardware sfor the openable panel sas specified and of the approved make such as heavy duty stainless steel friction stay, 2 points cremone locking sets of Kinlong/ giessie/ Assabloy make with stainless steel plates,handles,buffers etc.including necessary stainless steel screws /fasteners, nuts, bolts, washers etc. all complete as Per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge.
165Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as required and specified, comprising of an outer heat strengthened float glass 6mm thick, of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an inner Heat strengthned clear float glass 6mm thick, spacer tube 12mm wide, dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor. (Payment for fixing of IGU Panels in the curtain glazing is included in cost of item No.25.2) For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm. Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/ m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement.
166Providing and fixing stainless steel (SS 304 grade) adjustable friction windows stays of approved quality with necessary stainless steel screws etc. to the side hung windows as per direction of Engineerin- charge complete. 205 X 19 mm
167Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete.
168Providing and fixing 12 mm thick frameless toughened glass doorshutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double action hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-incharge (Door handle, lock and stopper etc.to be paid separately).
169Auto mated Glass door : Supply and fixing of Automatic frameless sliding door by (GEZE ,SIO or Equivalent) and operator, modular design including internal cover with operator dimensions (H X T) not exceeding 120mm x 175mm and of length required to suit the opening size given below: Clear opening of size 2500mm X 2400mm: GEZE EC Drive, compact linear sliding door automatic, with self cleaning rollers, TUV type tested as per DIN 18650. In general, the sliding door consists of 16 bit Microprocessor Control unit, monitoring of closing force, automatic reverse on contact with obstruction, operator commissioning without any additional instrumentation and self-teaching. Operating Modes: Continuous open, automatic operation, closing time, night lock, multi-sensor detector(radar motion detector with direction detection and self-monitoring, (light barrier) for convenient safeguarding of the opening width),(Option: Electromagnetic locking, integrated in the drive unit, with manual emergency unlocking.) The operator will be provided with short circuit proof power supply unit 220 / 240 V, 50 / 60 hz (power point shall be made available at site by electrical contractor). Operator shall have opening speed adjustable from 10 to 60 cm / sec / leaf, closing speed adjustable from 10 to 55 cm / sec / leaf, adjustable creep speed 3 - 9 cm / sec / leaf and adjustable hold open time 0 - 180 seconds all confirming to manufacturers specification. Rate is not included for providing 12mm thick clear toughened glass sliding shutter as per design, handling, loading and unloading, installation, power required for erection, protecting the module and glass till handing over, testing, commissioning all necessary hardware’s of GEZE make or equivalent and the module to be erected with the structural supports etc. complete and all as per manufacturers specifications as directed: ( 12 mm thick toughened glass shutter shall be paid extra.)
170Filling the gap in between aluminium/ stone/ wood frame and adjacent RCC/Brick/ Stone/ wood/ Ceramic/ Gypsum work by providing weather/structural non sag elastomeric PU sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete, complying to ASTM C920, DIN 18540- F & ISO 11600 Upto 5 mm depth and 5 mm width
171Supply and Installation ofVertical Louvers,CS- 200 Vertical Fin system as manufactured by Construction Specialties International, All components has to be in Aluminum extrusion Alloy 6063-T5/T6/1100/3000 Series, with minimum thickness of the extruded minimum 1.5 mm, with Blades Multi tube tapered from 27” down to 10” projection, extruded aluminum rectangular tube design.Tubes shall be factory assembled to outriggers using stainless steel, type F, thread cutting screws through internal screw slots in blades.Welding is not acceptable.Blades to be mechanically secured to allow for replacement in case of damage.Fasteners to be hex head.All the fasteners used shall be of Stainless steel for the construction of the louvers and should be mechanically fastened. Louver must be factory fabricated and finish so that only assembly/ installation will be done at the site. Finish will as per the approved RAL color in Super durable Powder Coat System, Complying with AAMA-2604 standards. Finish thickness to be minimum 2 mils.Furnish manufacturer"s 20-year warranty for finish.
172Providing and fixing in position factory made EPS cement sandwich wall/roof/floor light weight solid core panels made of core material of EPS granule balls/beads (conforming to IS 4671:1984 and shall have density not less than 15kg per cum) adhesive, cement, sand, flyash and other bonding material in mortar state processed to form in a preset mould. The outer face on both sides of the panels will be non asbestos fiber cement board confirming to IS 14862:2000 or Calcium silicate board confirming to EN 14306:2009 of 5mm thick each. Panel shall be laid on 6mm thick cement mortar (1 cement: 2 fine sand) mixed with chemical adhesive of 0.5kg per 50kg of cement or shall be preferably fixed into ‘C’ channel made of 1.2mm thick MS plate screwed/fastenened to the slab/column/ beam etc. The panel shall fixed vertically with tongue and groove joint and horizontally locked with steel bar between each other and floors and filled with cement mortar and adhesive. Panels should be used as floor & roofing with additional structural support, steel or RCC depending upon the design. All the operation shall be completed in all respect as per drawings, Manufacturers specifications and under the overall direction of Engineer-in-Charge (Cost of all the material is included except “C channel” which will be paid seperately). Non load bearing panels 75mm thick of required size
173Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item) With float glass panes of 8 mm thickness (weight not less than 20 kg/sqm):
174Reflective film on glass
175Pipes being fixed for plumbing shall befixedinholeswhichare mechanicallycorecut,morethan the dia of the pipes. Pipes shall be fixed by grouting the annular space with Epoxy grout ofpropreitory make. Before grouting the pipes shall be wrapped withatwo-wayselfadhesivetape atleast2incheswideandthen grouted to fill in the grout, ensuring total watertight plumbing fittings. Application shall be carried outbyapprovedapplicatorof manufacture and as per recommendedbymanufacturer.
176Surface Preparation: Cleaning the surface thoroughly with wire brush, soft brush and required tools to eliminate all defective materials and foreign matter.Repair all cracks joints and junctions withpolymer modified cementitious mortarso as to achieve the sound surface for treatment. Base Waterproofing Coating on RCC Slab :- Providing and applying BULWARK LM Bituminous PU coating.To be applied in 2 coats a flexible waterproofing coating over the Priming coat. coating to be done as per manufecture specifications, while providing the intermediate layer of 30 gsm Geo mesh sandwitched between the two coats. Protection Plaster:- Providing and applying a protection plaster ofavg. 15- 20mm thick 1:4 ratio, cement, sand mortar admixed with integral waterproofing compound.
177Treatment of old to New concrete Joints (While casting the concrete) : Providing hydrophilic expanding swellable Water Bars fixed with adhesive on all construction joints before placing the shuttering for new concrete.
178Sealing of Tie Rod Holes: Sealing the periphery of sockets, grooves withNon Shrink Grout.
179Surface Preparation: Cleaning the surface thoroughly with wire brush, soft brush and required tools to eliminate all defective materials and foreign matter.Repair all cracks joints and junctions withpolymer modified cementitious mortarso as to achieve the sound surface for treatment. Base Waterproofing Coating on RCC Slab :- Providing and applying BULWARK LM Bituminous PU coating.To be applied in 2 coats a flexible waterproofing coating over the Priming coat. coating to be done as per manufecture specifications, while providing the intermediate layer of 30 gsm Geo mesh sandwitched between the two coats. Protection Plaster:- Providing and applying a protection plaster ofavg. 15 mm thick 1:4, cement sand mortar admixed with integral waterproofing compound.
180InjectionGrouting:- Providing and applyingNON- SHRINK POLYMERIC WATERPROOF GROUTING COMPOUND’ admixed with Cement Slurry through the Nozzles under pressure by pump. The grout should flow through all pores and voids thereby sealing them. Providing and laying water proofing treatment by chemical injection grout process in whole area vertical and horizontal. using 18mm dia MS nozzles fixing 1mtr c/c on horizontal surface and 1.5 mtr c/c on the vertical walls and0.7m in construction joints, consisting of injecting cement slurries of different viscossitites under pressure by pump using "BULWARK GROUT"Non-shrink chemical mixed with neat cement slurry and sealing off nozzles after the injection operation with polymeric mortar. Epoxy injection grout in concrete/RCC work of approved make
181Surface Preparation: Cleaning the surface thoroughly with wire brush, soft brush and required tools to eliminate all defective materials and foreign matter.Repair all cracks joints and junctions withpolymer modified cementitious mortarso as to achieve the sound surface for treatment. Elastomeric Coating:- Providing and Applying of a two component heavy duty elastomeric coating, the waterproofing coating after the surface cleaning and surface preparation.First layer of the coating shall be provided over the structure and side walls up to the top level, after the complete coating. Second layer of waterproofing coating to be provided over the first layer after minimum 4-5 hours as per the prevailing temperature and allowing the treated surface to air cure for 4-5 hours followed with water curing for 24-48 hours as per the actual site conditions. Coner Tape:- Providing and applying corner tape in the joint and junction. Protection Plaster:- Providing and applying a protection plaster ofavg. 15 mm thick 1:4, cement sand mortar admixed with integral waterproofing compound.
182Technical parameters FIRESTONE RubberGard: MATERIAL : 1.1 mm thick non reinforced vulcanized EPDM RUBBERGARD meeting ASTM D 4637 requirement. The sheet should be as large as possible but not less than 3m unspliced width. Weight - 1.4 kg per sqm, Tensile strength - > 9 N/ mm²,Elongation - > 300 %, Tear resistance - > 25kN/m, Brittleness point - < -45 ° C,Water absorption - < 2 % Provide EPDM membrane, splice tape, primer and bonding adhesive that are FM approved. Identify materials with FM Approvals markings. All the materials used should be from the same manufacturer. Artificial ageing compliance for more than 7500 hours as per EN 1297 EPDM RUBBERGARD : Laying 1.1 mm EPDM membrane confirming to above mentioned technical values is loose laid over the insulation boards.The width of Firestone EPDM sheet should be minimum 9 meter or large as possible to minimize the number of joints. Adjacent sheet shall be laid in similar fashion with an overlap of minimum 100 mm . Min 75mm wide rubber polymers butyl splice tape having 100% solid content together with synthetic-rubber polymer primer having 16-18% solids, Specific Gravity 0.793 and Flash point-17.8 degree centigrade, should be used to make watertight QuickSeam between 2 EPDM membranes. Verticalwall:The surface of wall shall be smooth, hard , dry and free from dust before applying treatment. 1.1mm thick EPDM RUBBERGARD confirming to above standards is fully bonded to the RCC substrate using FM approved solvent based Neoprene Bonding adhesive. All the insertions shall be treated with Firestone uncured EPDM. The treatment to be terminated atleast at the height of 300mm above the roof floor level using termination bar and appropriate fasteners. Water block sealant should be used on top edge behind membrane and lap sealant should be applied on the edges of termination detail. Uncured EPDM flashing material factory laminated to splice tape should be used to flash inside and outside corners, pipes, drain outlets, scuppers and other penetrations or unusually shaped walls/details where the use of cured membrane flashing is not practical. PROTECTION Geotextile: 300 gsm shall be laid all over EPDM RubberGard treatment.The geotextile membrane must be overlapped for 75mm. Make Firestone/ Genflex/Sealecs Sweden
183Protection Plaster:- Providing and applying a protection plaster ofavg. 15 mm thick 1:4, cement sand mortar admixed with integral waterproofing compound.
184Providing and fixing 120 minutes Fire resistance fire stop with light weight cement specially formulated cement composition supplied as a pre-mixed dry powder for on site addition of water to seal the openings in floors (as per NBC 2016) through which services are passing from one compartment to another in accordance with the criteria of BS 476 Part 20 1987, AS 1530 Part 4 ,and AS 4072 Part 1 For 120 min fire resistance the promstop mortar , 3M , Hilti is mixed with suitable amount of water and the mixture is cast uniformly , 40mm thick over mineral wool of minmum of 50mm x96 Kg/Cum when supproted with metal shuttering of all around angle of minimum 25x25x3mm with intermediate angles at every 300mm complete in all respect for sealing of the shaft for 2 hrs fire rating
185Providing and fixing 8"x8" size6MM acrylic with a layer of 1MM PVC material name plate having ADA lettering and graphics. 5/8” tall tactile letters in futura medium type face. 4.5” tall tactile symbols. Letters and symbols chemically welded to and raised 1/32 inch above plaque surface. ADA compliant Grade 2 doomed braille positioned 3/8 inch below text.All signs to comply with ADA specifications.Name plate of Title Name,Ladies Toilet,Gents toilet and Handicap Toilet.
186Providing and fixing 36"x24" size6MM acrylic with a layer of 1MM PVC material. Having ADA lettering and graphics. 5/8” tall tactile letters in futura medium typeface. 4.5” tall tactile symbols. Letters and symbols chemically welded to and raised 1/32 inch above plaque surface. ADA compliant Grade 2 doomed braille positioned 3/8 inch below text. All signs to comply with ADA specifications.Name plate of EVACUTION PLANandFLOOR DIRECTORY.All signage are photoluminescent.
187Providing and fixing 8"x8" size6MM acrylic with a layer of 1MM PVC material. Having ADA lettering and graphics. 5/8” tall tactile letters in futura medium typeface. 4.5” tall tactile symbols. Letters and symbols chemically welded to and raised 1/32 inch above plaque surface. ADA compliant Grade 2 doomed braille positioned 3/8 inch below text. All signs to comply with ADA specifications.Name plate of IN CASE OF FIRE (PL).All signage are photoluminescent.
188Providing and fixing 18"x18" size6MM acrylic with a layer of 1MM PVC material. Having ADA lettering and graphics. 5/8” tall tactile letters in futura medium typeface. 4.5” tall tactile symbols. Letters and symbols chemically welded to and raised 1/32 inch above plaque surface. ADA compliant Grade 2 doomed braille positioned 3/8 inch below text. All signs to comply with ADA specifications.Name plate of LIFT SIGNAGE SET.All signage are photoluminescent.
189Providing and fixing 18"x6" size6MM acrylic with a layer of 1MM PVC material. Having ADA lettering and graphics. 5/8” tall tactile letters in futura medium typeface. 4.5” tall tactile symbols. Letters and symbols chemically welded to and raised 1/32 inch above plaque surface. ADA compliant Grade 2 doomed braille positioned 3/8 inch below text. All signs to comply with ADA specifications.Name plate of FINAL EXIT DOOR (PL) , EXIT ARROW DIRECTION(PL)andFIRE EXIT (PL).All signage are photoluminescent.
190Providing and fixing 24"x4" size6MM acrylic with a layer of 1MM PVC material. Having ADA lettering and graphics. 5/8” tall tactile letters in futura medium typeface. 4.5” tall tactile symbols. Letters and symbols chemically welded to and raised 1/32 inch above plaque surface. ADA compliant Grade 2 doomed braille positioned 3/8 inch below text. All signs to comply with ADA specifications.Name plate of PUSH BAR TO OPEN (PL).All signage are photoluminescent.
191Providing and fixing 8"x10" size6MM acrylic with a layer of 1MM PVC material. Having ADA lettering and graphics. 5/8” tall tactile letters in futura medium typeface. 4.5” tall tactile symbols. Letters and symbols chemically welded to and raised 1/32 inch above plaque surface. ADA compliant Grade 2 doomed braille positioned 3/8 inch below text. All signs to comply with ADA specifications.Name plate of FIRE HOSE REEL (PL) andFIRE EXTINGUISHER (PL).All signage are photoluminescent.
192Providing and fixingLOGO (69 LETTER"S)Halo Illuminated Letters of18" heightfollowing : Spec - INDIVIDUAL LETTERS READING "MARKS & SPENCER" RAL 9005 JET BLACK DESCALED ACRYLIC LETTERS WITH GLOSS FINISH RETURN WITH BLACK ACRYLIC FOLLOWED BY EQUAL SIZE WHITE ACRYLIC HALO ILLUMINATED BLACK ACRYLIC LETTER RETURN WILL BE EQUAL TO WIDTH OF STROKE OF LETTER "M" ACRYLIC SHEET TO BE USED TO FORM BLACK ACRYLIC LETTERS – SEAMLESS JOINT FINISH REQUIRED ALL WIRES TO BE CONCEALED IN FLEXIBLE CONDUIT LIGHT COLOR TEMPERATURE – 5000K (Manufacturer’s color temperature certificate required post execution)
193Providing and fixingEXTERNAL DIRECTORIESof size72"x10" Sign Panel, sides - front and back Illuminated, 1mm aluminium sheet with laser cut graphics, painted to required colour. Fixed to aluminium extrusion structure using VHB tapes. Acrylic sheet of 3mm, 040 opacity fixed in graphic space from inside. Illumination provided by LED modules from inside. Modules of 0.72W with 12V or 24V supply with 3 years life.
194Providing and fixingEXTERNAL DIRECTORIESSupport Structure : two poles Of stainless steel grade-304, squre pipe of size-75mmX75mmX1mm of length- 10" fixed with use of SS 304 anchor plates of size - 200mmX2mmX4mm fixed to RCC base with anchor fastners RCC Base : size - 24"x18"x18" grade - M25/30
195Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by percussion drilling using Direct mud circulation (DMC) or Bailer and chisel technique by tripod and mechanical Winch Machine all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Note: Truck Mounted rotary/TMR/Tubewell boring machine shall not be used . 500 mm dia piles
196Add for using extra cement in the items of design mix over and above the specified cement content therein.
197Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Note: 1. Initial and Routine Load Test shall not be carried out by Dynamic method of testing. Note: 2. Testing agency shall submit the design of loading platform for the approval of Engineer-in-charge. Group of two or more piles upto 50 tonne Safe capacity Initial test (Test Load 2.5 times the Safe capacity)
198Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Note: 1. Initial and Routine Load Test shall not be carried out by Dynamic method of testing. Note: 2. Testing agency shall submit the design of loading platform for the approval of Engineer-in-charge. Group of two or more piles upto 50 tonne Safe capacity Routine test (Test Load 1.5 times the Safe capacity)
199Integrity testing of Pile using Low Strain/ Sonic Integrity Test/ Sonic Echo Test method in accordance with IS 14893 including surface preparation of pile top by removing soil, mud, dust & chipping lean concrete lumps etc. and use of computerised equipment and high skill trained personal for conducting the test & submission of results, all complete as per direction of Engineer-in-charge. Note :- The inclusion of the above item in the schedule of work shall be judiciously decided by the technical sanctioning authority, keeping in view the quality control, type of soil strata & importance of the project.
200Preparation and consolidation of sub grade with power road roller of 8 to 12 tonne capacity after excavating earth to an average of 22.5 cm depth, dressing to camber and consolidating with road roller including making good the undulations etc. and re-rolling the sub grade and disposal of surplus earthwith lead upto 50 metres.
201Extra for compaction of earth work in embankment under optimum moisture conditions to give at least 95% of the maximum dry density (proctor density).
202Construction of granular sub-base by providing close graded Material conforming to specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tippers to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per specifications and directions of Engineer-in-Charge. With material conforming to Grade-I (size range 75 mm to 0.075 mm) having CBR Value-30
203Providing, laying, spreading and compacting graded stone aggregate (size range 53 mm to 0.075 mm ) to wet mix macadam (WMM) specification including premixing the material with water at OMC in for all leads & lifts, laying in uniform layers with mechanical paverfinisher in sub- base / base course on well prepared surface and compacting with vibratory roller of 8 to 10 tonne capacity to achievethe desired density, complete as per specifications and directions of Engineer-in-Charge.
204Construction of dry lean cement concrete sub base over a prepared sub-grade with coarse and fine aggregate conforming to IS:383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per specifications, cement content not to be less than 150 Kg/cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant, transported to site, for all leads & lifts, laid with a mechanical paver, compacting with 8-10 tonne vibratory roller, finishing and curing etc. complete as per direction of Engineerin- charge.
205Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The ready mixed concrete shall be laid and finished with screed board vibrator, vacuum dewateringprocess and finally finished by floating, brooming with wire brush etc. complete as per specifications and directions of Engineer-incharge. (The panel shuttering work shall be paid for separately). (Note:- Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix is payable/ recoverable separately).
206Providing and laying factory made chamfered edge Cement Concrete paver blocks GRASS PAVERSin footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge Grass pavers 40:60 shall be 80mm thick cement concrete paver block of M-30 grade with approved colour, design & pattern.
207Providing and laying factory made chamfered edge Cement Concrete paver blocks GRASS PAVERSin footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge. Providing and laying in position bitumen hot sealing compound for expansion joints etc. Using grade ‘A’ sealing compound.
208Painting road surface marking with adequate nos of coats to give uniform finish with ready mixed road marking paint conforming to IS : 164, on bituminous surface in white/yellow shade, including cleaning the surface of all dirt, scales, oil, grease and foreign material etc. complete. New work (Two or more coats)
209Making bell mouth opening/ entrance of size 100x50x50 cm for drainage pipe under footpath, including providing cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) for shape of bell mouth, including plastering providing and fixing precast R.C.C./ S.F.R.C. slab including plastering with cement mortar 1:3 (1 cement : 3 fine sand) of 6 mm thickness on exposed surface of the slab & bell mouth including centring, shuttering & neat cement punning inside the bell mouth etc. all complete.
210Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge).
211Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge. 80mm thick cement concrete paver block of M-30 grade with approved colour, design & pattern.
212Manufacturing, supplying and fixing retro reflective sign boards made up of 2 mm thick aluminium sheet, face to be fully covered with high intensity encapsulated type heat activated retro reflective sheeting conforming to type - IV of ASTM-D 4956-01 in blue and silver white or other colour combination including subject matter, message (bi-lingual), symbols and borders etc. as per IRC ; 67:2001, pasted on substrate by an adhesive backing which shall be activated by applying heat and pressure conforming to class -2 of ASTM-D-4956-01 and fixing the same with suitable sized aluminium alloy rivets @ 20 cm c/c to back support frame of M.S. angle iron of size 25x25x3 mm along with theft resistant measures, mounted and fixed with 2 Nos. M.S. angles of size 35x35x5 mm to a vertical post made up to M.S. Tee section ISMT 50x50x6 mm welded with base plate of size 100x100x5 mm at the bottom end and including making holes in pipes, angles flats, providing & fixing M.S. message plate of required size, steel work to be painted with two or more coats of synthetic enamel paint of required shade and of approved brand & manufacture over priming coat of zinc chromate yellow primer (vertical MS-Tee support to be painted in black and white colours).Backside of aluminium sheet to be painted with two or more coats of epoxy paint over and including appropriate priming coat including all leads and lifts etc. complete as per drawing , specification and direction of Engineer—in-charge. a)Mandatory/ Regulatory sign boards of 900 mm diametre with support length of 3750 mm
213b)Cautionary /warning sign boards of equilateral triangular shape having each side of 900 mm with support length of 3650 mm
214Manufacturing, supplying and fixing retro reflective overhead signage boards made up of 2 mm thick aluminium sheet, face to be fully covered with high intensity and encapsulated lens type heat activated retro reflective sheeting conforming to type - III of ASTM-D-4956-01 as approved by Engineer-in-charge, letters, borders etc. as per IRC : 67-2001 in silver white with blue colour back ground and with high intensity grade, pasted on substrate by pressure sensitive adhesive backing which shall be activated by applying pressure conforming to class II of ASTM-4956-01 and fixing the same to the plate of structural frame work by means of suitable sized aluminium alloys, rivets or bolts & nuts @ 300 mm centre to centre all along the periphery as well as in two vertical rows along with theft resistant measures, including the cost of painting with two or more coats of epoxy paint in grey colour on the back side of aluminium sheet including appropriate priming coat. The rate includes the cost of rounding off the corners, lowering down the structural frame work from the gantry, fixing and erecting the same in position all complete as per drawings, specification and direction of the engineer-incharge.( Structural frame work including M.S. plate to be provided separately. Rectangular area of the sheet only shall be measured for payment). Overhead informatory road signage
215Providing and Fixing of Fire Sealent to close the cutouts of Cables, refrigerant pipes and tray all complete as required and as per final direction.
216FIRE FIGHTING SPRINKLER AND HYDRANT SYSTEM Supplying,installation,testingandcommissioningof Electric driven Main Fire Pump suitablefor automatic operationandconsistingoffollowing,completeinall respects, as required : (a)Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. (b)Suitable HP Squirrel cage induction motor, TEFC, synchronousspeed1500RPM,suitableforoperation on415volts,3phase50Hz,ACsupplywithIP55 protectionforenclosure,horizontalfootmountedtype with Class-"F" insulation, conforming to IS-325. (c)M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d)Suitablecementconcretefoundationdulyplastered with anti vibration pads. Note: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point. (i)2280 lpm at 88 m Head (Main Hydrant Pump)
217(ii) 2280 lpm at 88 m Head (Main Sprinkler Pump)
218Supplying,installation,testingandcommissioningof diesel engine driven main fire pump suitable for automatic operation and consistingof following, completeinallrespects,asrequired:(DieselDriven Pump) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. SuitableHP,1500RPMwatercooledwithradiator, diesel engine conforming to relevant IS standard completewithautostartingmechanism,12/24volts electricstartingequipment,dieseltank,exhaustpipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. SuitableHP,1500RPMwatercooledwithradiator, diesel engine conforming to relevant IS standard completewithautostartingmechanism,12/24volts electricstartingequipment,dieseltank,exhaustpipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitablecementconcretefoundationdulyplastered and with anti vibration pads. 2280 lpm at 88m Head Note: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point.
219Supplying,installation,testingandcommissioningof electricdrivenpressurisationpumpsuitablefor automaticoperationandconsistingoffollowing, complete in all respects, as required : (Jockey Pump) Horizontaltype,multistage,centrifugalpumpofcast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. SuitableHPsquirellcageinductionmotorTEFCtype suitableforoperationon415volts,3phase50Hz AC supply with IP 55 class of protection for enclosure, horizontalfootmountedtypewithClass-"F"insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitablecementconcretefoundationdulyplastered and with anti vibration pads. 180 lpm at 88 m Head
220Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet,compartmentalisedwithhingedlockabledoors, dustandverminproof,powdercoatedofapproved shade after 7 tank treatment process, cable alley, inter-connectionwithsuitablesizecopperconductor cable/solidcopper strip, havingswitchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitableformainfirepump,pressurisationpump& dieselpumpsetcompleteasperCPWDspecification withfollowingincomingandOutgoings,suitablefor operationon415V,3phase,50HzAcSupplywith enclosure protection class IP 42 as required : Incomings : 630A, 50kA4 Pole MCCB, Ics=100% Icu Rating;Digital Voltmeter 0-500V with selector switch;Ammeter (0-630 A) with selector swtich & CTs etc.;LEDtypeRYBphaseindicatinglamps,ON,OFF,trip indicating lamps;Set of CopperBus Bar 800Amps Outgoings (Note:Alloutgoingfeedersforpumpsshouldhave digital Ammeter with selector switches,and LED type ON, OFF, trip indicating lamps) : Main Fire Pump :200Amp,50kATPNMCCB,Ics=100%Icu,withfully automaticStar/Deltastartersuitablefor100hppump withoverloadprotection,currentsensingtypesingle phasepreventorcompletewithallacceessoriesand internalwiringrequiredforautomaticoperation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets Jockey Pump : 100 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star Delta/Dol starter with respect to its capacity ,with overload protection, current sensing type single phase preventorcompletewithallacceessoriesandinternal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation.- 2 sets DIESEL ENGINE CONTROL : Control for diesel engine comprising - Automatic/Manualselctorswitch&3attemptsstarting device,timersandrelaysasrequired,pushbuttons, start/stop in manual mode;Indicatinglampforhigh/LowLub.Oilpressure,High Water Temp and Engine on indication;Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter;All standard relays and accessories for automatic operation of diesel engine System Controller : Designing,Supply,Installation,Testingand commissioning of system controllertocontrol operation ofmainelectricfirepump,dieselpump,Pressurization pump,Terracepumpinsequenceasperspecification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification
221Supplyingandfixingoffirebrigadeconnectionof cast iron body with gun metal male instantaneous inlet couplingscompletewithcapandchainasreqd.for suitabledia MS pipe connectionconforming to IS 904 as required : 4 way-150 mm dia M.S. Pipe
222Providing and fixing fire brigade suction hose coupling (draw out connection) with nut for female coupling as per IS-902 complete with 150mm dia. Suction pipe and foot valve (to be connected to static tank) complete as required andas per enclosed specification.
223Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required.
224Constructing masonry Chamber 90x90x100 cm inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I. surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size ) and inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished with a floating coat of neat cement complete as per standard design :With common burnt clay F.P.S.(non modular) bricks of class designation 7.5
225Supplyingandfixingsingleheadedinternalhydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheelISI marked conformingtoIS5290(Type-A)withblank Gunmetal/Stainless Steel cap and chain as required :(Bidder can submit the rate of either Gunmetal or Stainless Steel.) Single headed Stainless steel
226Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/StainlessSteel couplingand cast iron wheel, ISImarked,conformingtoIS5290(typeA)withblank Gunmetal/Stainless Steel cap and chain as required : Single headed Stainless steel
227Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter sizenozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : Stainless Steel (Grade 304)
228Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
229Supplying and fixing 63 mm dia, 15 m long RRL hose pipewith63mmdiamaleandfemalecouplingsduly boundwithGIwire,rivetsetc.conformingtoIS636 (type-A) as required : Stainless Steel (Grade 304)
230Supplying andfixing first-aidHoseReelwithMS constructionspraypaintedinpostofficered, conformingtoIS884completewiththefollowingas required. 20mmnominalinternaldiawaterhosethermoplastic (Textile reinforced) type -2 as per IS: 12585 20mmnominalinternaldiagunmetalglobevalve& nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 m
231Providing and fixing stainless steel standard fireman"s axe with heavy insulated rubber handle tested to 20000 volts as per IS : 926 complete.
232Providing and fixing angle iron (40mmx40mmx5mm) door frame and MS sheet (6mm thick) cum glass shutter of size 2.1mtrx0.9mtr(N.S.) with 25mmx25mmx3mm angle frame all around and stiffened in between i/c hinges, handle, locking arrangement, painting with approved synthetic enamel paint i/c sign writing on glass at internal hydrant including providing & fixing S.S. sheet 2mm thick on remaining portion above door to close opening i/c painting etc. as required. Glass shall be 6 mm thick.
233Providing & fixing of MS fireHose cabinet outdoor type of size 0.90 Mx 0.60 Mx 0.50 M made of 6mm thick MS sheet with 6mm thick glazed glass doors i/c necessary locking arrangement suitable to accomodate 2nos 15m long hoses, one no branch pipe, etc. and mounted on 400 mm height agle . The cabinet shall be painted with redcolour shade No. 536 of IS: 5 externally & white internally complete in all respects for internal hydrant and as per enclosed specification.
234Providinglaying,testing&commissioningof"C"class heavydutyMSPipeconformingtoIS1239/3589i/c fittingslikeelbows,tees,flanges,tapers,nutsbolts, gasketsetc.ingroundincludingwelding,excavation& providingcementconcreteblocksassupports, anticorrosivetreatmentwithcoaltar/asphalttapeasper IS10221,refillingthetrenchetc.offollowingsizes complete as required. a)150 mm. Dia
235b)100 mm. Dia
236c)80 mm. Dia
237Providing,laying,testing&commissioningof "C"class heavydutyMSpipeconformingtoIS3589/IS1239 includingWelding,fittingslikeelbows,tees,flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : a)250 mm dia (wall thickness 6.3 mm)
238b)200 mm dia (wall thickness 6.3 mm)
239c)150 mm dia.
240d)100 mm dia.
241e)80 mm dia.
242f)65 mm dia.
243g)50mmdia.
244h)40 mm dia.
245i)32 mm dia.
246j)25 mm dia.
247Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI markedcompletewithnuts,bolts,washers,gaskets conforming to IS 13095 of following sizes as required : a)200mm dia.
248b)150mm dia.
249c)100mm dia.
250d)80mm dia.
251e)65mm dia.
252f)50mm dia.
253Providing,installation,testingandcommissioningof non-returnvalveoffollowingsizesconfirmingtoIS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : a)200mm dia.
254b)150 mm dia.
255d)80 mm dia.
256e)50mm dia.
257Supplying,fixing,testing&commissioningofdouble flangedsluicevalveofratingPN1.6withnonrising spindle,bronze/gunmetalseat,ISImarkedcomplete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : (Sluice valve will be used in pump room only) a)200mm dia.
258Providing and fixing tamper switch on butterfly valve / sluice valve / isolation valve for remote mointing of the valve open / close position and installed in plantroom.The tamper switch shall be provided with potential free contact with 2 nos. NONC.The valve shall also be provided with manual lock & chain arrangement.
259Providing and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end) : a)25 mm nominal bore
260b)50 mm nominal bore
261Providing and fixing inspectors test assembly complete with test valve, sight glass sectional drain valve, union with corrosion resistant orifice all complete strictly as per drawing. 50NB
262Providing,installation,testingandcommissioningof stainlesssteelY-strainerfabricatedoutof1.6mm thickstainlesssteel,Grade304,sheetwith3mmdia holes with stainless steel flange. a)150 mm dia.
263c)80 mm dia.
264Providing & fixing of 25mm dia. gunmetal air release valve with all fittings and forged ball valve on header complete as required and as per enclosed specification.
265Providing and fixing following size Pressure gauge (0-15 Kg/Cm2) complete with shut off valve duly calibrated before installation complete as required & as per enclosed specification. 150mm dia.
266Providing, fixing, testing & commissioning of installationcontrolvalveofcastironbody, brass/ bronzeworking partscomprisingofwater motor alarm,bronzeseatclapper,clapperarmand hydraulicallydrivenmechanicalgongbelltosound continuousalarmwhenthewetriser/sprinklersystem activates,pressuregauges,emergencyreleases, strainer,pressureswitch,cockvalvecompletewith drainvalveandbypass,testcontrolbox,ballvalves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes asrequired : 150 mm dia.
267Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valveontopandflangedconnectiontoriser,drain arrangementwith25mmdiagunmetalwheelvalve withrequiredaccessories,pressuregaugeand paintingwith synthetic enamel paint of approved shade as required.
268Providing and fixing reinforced neoprene rubber vibration eliminators / expansion joints (to provide relief from stresses at pipe flanges) suitable for upto 20 kg/cm2 pressure, complete as perspecification. a)150mm dia.
269b)80mm dia.
270c)50mm dia.
271Providing, fixing, testing & commissioning of MS air cushion tank on top of each riser fabricated from 6mm thick MS plate, 200 mm in diameter and 1.2 m in height with dished ends fabricated from 8mm thick MSplate with Air release valve with stop cock, flanged inlet connection and drain arrangement with 25mm dia valve, pressure gauge with gun metal stop cock complete with all accessories as required and conforming to IS 4736-1968. Recommended dia.: 450 mm Height of shell : 2000mm Working pressure: 9 Kg/Sq.cm Test Pressure : 14 Kg/Sq.cm
272Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. a)150 mm dia
273b)100 mm dia
274c)80 mm dia
275d)65 mm dia
276Providing and fixing modular construction annunciation panel for flow control switches having 54 zones , 1sets Fault indication for each zone Fire/fault hooter. Alarm panel for fire/fault Battery for emergency Battery Charger Mains supply
277Providing, fixing, testing & commissioning of 15mm dia quartzoidbulbtypesprinklersofrating68degree centigrade with required accessories : a)Pendent Sprinkler
278b)Upright Sprinkler
279Supplying, installation, testing & commissioning of sprinklerflexiblepipe(ULListed)ofstainlesssteel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875PSI(Burst)withbranchline(Inlet)25mmNPT malethreadtosprinklerhead(Outlet)15mmNPT femalethreadwithreducer,nipple,2sidebrackets, center bracket, stockbar of following sizes complete as required. 1000mm
280Provding & Fixing Powder coated double plate rosette plate for pendentsprinkler where ever required.
281Providing and fixing heavy duty copper flexible cables 1.1 KVA grade including necessary support clamps at ceiling level and connection legs complete in all respects. Control cable 2 core 1.5 Sq.mm
282Providing and fixing heavy duty copper armored cables 1.1 KVA grade including necessary support clamps at ceiling level and connection legs complete in all respects. a)Power cable 3 core 16 Sq.mm
283b)Power cable 3 core 95 Sq.mm
284Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. It should be complete as per specifications & directions of Engineer-in-charge. a)3 X 16 sq. mm (25mm)
285b)3 X 95 sq. mm (38mm)
286Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
287Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. a)300 mm width X 50 mm depth X 1.6 mm thickness
288b)150 mm width X 50 mm depth X 1.6 mm thickness
289Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
290Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
291Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
292Supply, installation, testing and commissioning ISI marked (IS:15683) Fire Extinguisher, Carbon-di-oxide type capacity 4.5 Kg. Flat base including valve, discharge hose of not less than 10 mm dia, 1M long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1966 and walll suspension braket as required as per specifications.
293Supply, installation, testing and commissioning of 6kg ABC (Powder Type) Fire Extinguisher. Mild Steel Cylinders ISI marked fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC 90 powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall suspension bracket and conforming to IS:15683 as required as per specifications.
294Supply, installation, testing and commissioning ISI marked (IS:15683) Fire Extinguisher, Carbon-di-oxide type capacity 9 Kg. Flat base including valve, discharge hose of not less than 10 mm dia, 1M long and complete in all respects including initial fill with CO2 gas conforming to IS:307-1966 and walll suspension braket as required as per specifications.
295Supply, installation, testing and commissioning ISI marked (IS:15683) portable fire extinguisher, water (gas pressure) type capacity 9 ltr. with gun metal cap and nozzle and complete in allrespectsincluding initial fill and wall suspension brackets as required as per specifications.
296Providing, fixing, testing and commissioning of 50 Litres (trolley mounted) Mechanical Foam type Fire Extinguisher. In HP Mild Steel Cylinders ISI marked TAC approved fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged complete in all respects including wall suspension bracket / trolley mounted and confoming to IS:13386 .
297Providing and fixing CO2 type fire extinguishers consisting of welded M.S. cylindrical body automatic modular CO2 type extinguisher actuated through a sprinkler head mounted on The extinguisher body finished externally with red enamel with trolly mounted complete with internal charge.(Capacity 22.5 Kg.)
298SANITARY INSTALLATION : Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required. W.C. pan with ISI marked white solid plastic seat and lid
299Providing and fixing white vitreous china battery based infrared sensor operated urinal of approx. size 610 x 390 x 370 mm having pre & post flushing with water (250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer-in-charge.
300Providing and fixing stone slab with table rubbed, edges rounded and polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth. Granite Stone of approved shade
301Providing and fixing uplasticised PVC connection pipe with brass unions : 45 cm length , 15 mm nominal bore
302Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require : White Vitreous China Flat back wash basin size 550x400 mm with single 15 mm C.P. brass pillar tap
303Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS: 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : 510x1040 mm bowl depth 200 mm
304Providing and fixing CP Brass Single lever mixer for sink of quality & make as approved by Engineer in charge. (a) 15 mm nominal dia. Hind ware Model No-F520028 or Equivalent
305Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. Flexible pipe-40 mm dia
306Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
307Providing and fixing toilet paper holder :C.P. brass
308Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms.
309Providing and fixing CP Brass 32mm size bottle trap of approved quality & make and as per the direction of engineer in charge.
310Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms.
311Providing and fixing Coat Hook Jaquare- ACN1161N or Equivalent.
312Providing ,Fixing of straight / offset type flexible single body push fit type WC pan connector ofwith integral single mould sealing fins made of flexible EVA body to be fixed with manufacture supplied grease, including rubber bush / adaptor for use with C.I pipe as supplied with the pan connector.
313Providing & fixingCP brass 2 way Bib tab including cutting and making good the walls /metalic sheetforwash basin where required as approved by engineer in charge.Jaquare- F52005 or Equivalent.
314Providing and fixing 8mm dia C.P./S.S. Jet with flexible tube upto 1meter long with S.S. Triangular plate to european type W.C. Of approved quality and make as approved by engineer in charge.
315Providing and fixing solid state, no touch operting, fully hygienic hand drier of approved shade with single blower, with time delay, summer & winter control, music while drying, volume ON/OFF controls including providing necessary brackets, cable from drier to Plug, Plug top key and lock etc, complete as required. Jaquare- EH27 or Equivalent.
316Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore
317Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 15mm nominal bore
318Providing & Fixing of Grab bar600 mm of non slipping grip as per standard specification of use in disabled toilet complete with brackets suitable for wall installation as per approved sample complete in all respect.Hindware - standard size 24.6 inchor Equivalent.
319Providing and Fixing SS Swing grab bar, fixed to PVC cleats with C.P.brass screws wherever required with approved make & quality and as per the directions and to the satisfaction of Engineer-in-charge. Hindware - standard size 24 inchor Equivalent.
320Providing and fixing S.S. body tissue paper dispenserfixed to PVC cleats with C.P.brass screws wherever required of approved make & quality and as per the directions and to the satisfaction of the Engineer-in-charge.standard size - 250 -300 papers holding size or Equivalent.
321Supply,Installation, testing and commissioning ofWater Heater complete with heavy gauge hot and cold water flexible pipe connections, Nano polymer coated tank, 8 bar pressure ,of approved make complete with all necessary material as directed by Engineer - in - Charge. a)15-Litre Storage capacity
322b)50-Litre Storage capacity
323Supply installation, testing and commissioning of water cooler with Inbuilt Aquagaurd RO purification + UV(50LPH) .Cooling capacity shall be 60 liter & 80 liter shall be storage capacity.Its should have 7 stages purification process,fully automatic,rectangular tank with Forced fin and tube condenser,Non-corrosive SS-304 outer body,Food-grade SS-304 stainless steel inner tank (18/8 or 18/10),PUF insulation,Reciprocating compressor with R22 Refrigerant.Water outlet temp is aprrox 17 deg c ,Operating power supply 230 + 10% V AC,50 Hz,1 PH,No of Cold water Faucet-2.Dimension (660W x 480DX1355H)
324Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet : 100 mm diameter
325Providing and fixing brass stop cock of approved quality : 15 mm nominal bore
326Providing and fixing PTMT shelf 440 mm long, 124 mm width and 36 mm height of approved quality and colour, weighing not less than 300 gms.
327Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms.
328WATER SUPPLY : Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc. a) 15mm nominal bore
329b)20mm nominal bore
330c)25mm nominal bore
331d)32 mm nominal bore
332Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c cutting and making good the walls etc. Internal work - Exposed on wall a)15mm nominal bore
333b)20mm nominal bore
334c)25mm nominal bore
335d)32 mm nominal bore
336e)40mm nominal bore
337f)50mm nominal bore
338g)65mm nominal bore
339h)80mm nominal bore
340Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality : Internal work - Exposed on wall a)15mm nominal bore
341b)20mm nominal bore
342c)25mm nominal bore
343d)32 mm nominal bore
344e)40mm nominal bore
345f)50mm nominal bore
346g)65mm nominal bore
347h)80mm nominal bore
348Providing and fixing brass/bronze lever operated ball valve of full flow with stainless steel ball (AISI 304 and spindle AISI 410) with setting and gland of superior quality having minimum working pressure of 16 kg/cm2. a)15 mm nominal bore
349b)20 mm nominal bore
350c)25 mm nominal bore
351d)32 mm nominal bore
352e)40 mm nominal bore
353Providing & fixing of following sizes of butterfly valve of rating PN 16, wafer type, in cast iron body with Ductile Iron disc, EPDM seal, SS single piece shaft, conforming to IS-13095 of the following sizes complete with cast iron hand lever companion flanges, bolts, nuts, washers & inserted rubber gaskets, as required and as per enclosed specification. a)50 mm nominal bore
354b)65 mm nominal bore
355c)80 mm nominal bore
356d)100 mm nominal bore
357Providing & fixing Auto Air vent for cold water supply risers, suitable for pressure not less than 15 Kg/Sq.cm. a)15mm
358Providing, fixing, testing and commissioning moterise Ball valve of following sizes, for filling of overhead tanks complete with high & low level switchs & pressure switch to control the valve. The level controller shalll be installed in over head tank. The level switch will close the valve when water level is high & open the valve when level is low in the tank. The system should be complete in all respect with accessories, 220V AC / 24 V DC, IP 67 water level control unit, Control Panel, copper control wiring in whether proof casing etc. 40 mm dia
359Providing and fixing soil, waste and vent pipes a)100mm dia - Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905(Pipe will be Hubless and some of fittings will be required to be provided SS )
360b)75mm dia - Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905
361Providing and filling the joints with spun yarn cement slurry and cement mortar 1:2 (1 cement: 2 fine sand) in S.C. I I C. I pipes a)100 mm dia pipe
362b) 75 mm dia pipe
363Providing and fixing M.S. holder bat clamps of approved design to sand cast iron/cast iron (spun) pipe embedded in and including cement concrete blocks 10 x 10 x 10 cm of 1:2:4 mix ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size ) including cost of cutting holes and making good the walls etc. a)For 100mm dia pipe
364b)For 75mm dia pipe
365Providing and fixing bend of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts 100 mm dia - Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905
366b)75 mm dia pipe
367Providing and fixing plain bend of required degree. 100mm dia Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905
368Providing and fixing plain bend of required degree. 75mm dia Hubless centrifugally cast (spun) iron pipes epoxy coated inside & outside IS:15905
369Providing and fixing heel rest sanitary bend: a)100 mm dia Sand cast iron S&S as per IS:3989
370b)75 mm dia Sand cast iron S&S as per IS:3989
371Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. a)100x100x100 mm Sand cast iron S&S as per IS - 3989
372b)75x75x75 mm Sand cast iron S&S as per IS - 3989
373Providing and fixing single equal plain junction of required degree : a)100 x 100 x 100mm Hubless centrifugally cast (spun) iron epoxy coated inside & outside as perIS:15905
374b)75 x 75 x 75mm Hubless centrifugally cast (spun) iron epoxy coated inside & outside as perIS:15905
375Providing and fixing door piece, insertion rubber washer 3mm thick, bolts & nuts complete : a)100 mm Sand cast iron S&S as per IS - 3989
376b)75 mm Sand cast iron S&S as per IS - 3989
377Providing and fixing terminal guard. a)100mm Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
378b)75mm
379Providing and fixing shielded coupling for Hubless centrifugally cast iron pipe. a)100mm dia SS 304 grade coupling with EPDM rubber gasket
38075mm dia SS 304 grade coupling with EPDM rubber gasket
381Providing lead caulked joints to sand cast iron/centrifugally cast (spun) iron pipes and fittings of diameter : a)100mm dia
382b)75mm dia
383Providing and fixing M.S. stays and clamps for sand cast iron/ centrifugally cast (spun) iron pipes of diameter : a)100mm dia
384b)75mm dia
385Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : a)100 mm inlet and 100 mm outlet Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
386b)100 mm inlet and 75 mm outlet Hubless centrifugally cast (spun) iron epoxy coated inside & outside as per IS:15905
387Painting sand cast iron / centrifugally cast (spun ) iron soil, waste vent pipes and fittings with paint of any color such as chocolate grey ,or buff etc .over a coat of primer (of approved quality ) for new work . a)100 mm diameter pipe
388b)75 mm diameter pipe
389Providing and fixing cast brass Floor Clean Out plug100mm with suitable insert keys for opening, male threaded joint with G.I. socket lead caulked to soil pipe / waste pipe of C.I. and C.I.(LA) pipe as required complete as per instruction of the Engineer in charge. 100 mm dia
390Providing & fixing GI pipes complete with GI fittings and clamps, including cutting & making good the walls etc. a)32 mm dia
391c)50 mm dia
392Painting GI pipes and fittings with two coats of anti corrosive bitumestic paint of approved quality. a)32mm dia nominal bore
393c)50mm dia nominal bore
394Providing and fixing 100mm dia G.I. inlet fitting consisting of 100mm dia (Lenght upto 450mm) main G.I pipe with multiple G.I. sockets (Inlets) of required diameter welded to it (as per site requirement) and fixing the same to C.I trap and setting incement concrete, complete as per instructions of the Engineer in charge.
395Construction of brick masonry Grease Trap of Effective depthfor Kitchen drainage with precast concrete block in cement mortar 1:4 (1 cement : 4 coarse sand) , foundation concrete 1:4:8 mix (1 cement : 4 coarse sand; 8 graded stone aggregate 40mm nominal size), inside and outside plastering 12mm thick with cement mortar 1:3 (1 cement : 3 coarsesand), finished with a floating coat of neat cement inside and rough plaster on outside, including fixing of grating , neatly finished with 1 nos.manhole cover complete in all respects including necessary excavation, refilling and disposal of surplus earth, complete as per attached Sketch . Grease Trap 2000x1000x1000 MM
396RAIN WATER WORK Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. 110 mm diameter
397Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion. a)Single Push fit coupler 110 mm dia
398b)Single Tee with door 110x110x110 mm
399c)Bend 87.5 Deg 110 mm dia
400d)Shoe (Plain) 110 mm dia
401Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15 cm diameter and weighing not less than 440 grams.
402Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. 110 mm dia
403Making khurras 45x45 cm with average minimum thickness of 5 cm cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate of 20 mm nominal size) over P.V.C. sheet 1 m x1 m x 400 micron, finished with 12 mm cement plaster 1:3 (1 cement : 3 coarse sand) and a coat of neat cement, rounding the edges and making and finishing the outlet complete.
404Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. Including all the fittings ,pipe clips,coupler etc. 160 mm diameter
405EXTERNAL WATER SUPPLY : Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. a)40 mm nominal dia Pipes
406b)50 mm nominal dia Pipes
407c)65 mm nominal dia Pipes
408Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality : a)40mm nominal bore
409b)50mm nominal bore
410c)65mm nominal bore
411Providing and filling sand of grading zone V or coarser grade alround the GI pipes in external work. A)40mm dia nominal bore
412b)50mm dia nominal bore
413c)65mm dia nominal bore
414Constructing masonry chamber 60x60x75cm, inside with 75 class designation brick work in cement mortar 1:4(1 cement : 4 coarse sand) for sluice valve,with C.I. Surface box 100mm top diameter , 160 mm bottom diameter and 180 mm deep ( inside ) with chained lid and RCC top slab 1:2:4 (1 cement:2 coarse sand:4 graded stone aggregate 20mm nominal size) necessary excavation foundation concrete 1:5:10 (1 cement:5 fine sand: 10 graded stone aggregate 40mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarsesand) 12mm thick finished with a floating coat of neat cement complete as per standard design with F.P.S. bricks. with common burnt clay F.P.S.(non module) brick of class designation 7.5
415Providing and fixing brass/bronze lever operated ball valve of full flow with stainless steel ball (AISI 304 and spindle AISI 410) with setting and gland of superior quality having minimum working pressure of 16 kg/cm2. 40mm dia
416Providing & fixing of following sizes of butterfly valve of rating PN 16, wafer type, in cast iron body with Ductile Iron disc, EPDM seal, SS single piece shaft, conforming to IS-13095 of the following sizes complete with cast iron hand lever companion flanges, bolts, nuts, washers & inserted rubber gaskets, as required and as per enclosed specification. a)65mm dia
417b)50mm dia
418Providing and fixing enclosed type water meter (bulk type) conforming to IS : 2373 and tested by Municipal Board complete with bolts,nuts, rubber insertions etc. (The tail pieces if required will be paid separately) : 80mm nominal bore
419SupplyingandfixingofTank inletconnectionof cast iron body with gun metal male instantaneous inlet couplingscompletewithcapandchainasreqd.for suitabledia MS pipe connectionconforming to IS 904 as required : 2 way - 100 mm dia M.S. Pipe
420Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required a)50mm dia
421b)65mm dia
422Making connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete : 50 to 80 mm nominal bore
423Providing and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc. External Work a) 20 mm nominal dia Pipes
424b) 80 mm nominal dia Pipes
425Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic paint of approved quality : a)20mm nominal bore
426b)80mm nominal bore
427Providing and filling sand of grading zone V or coarser grade alround the GI pipes in external work. A)20mm dia nominal bore
428b)80mm nominal bore
429Constructing masonry chamber 30x30x50cm, inside with 75 class designation brick work in cement mortar 1:4(1 cement : 4 coarse sand) for sluice valve,with C.I. Surface box 100mm top diameter , 160 mm bottom diameter and 180 mm deep ( inside ) with chained lid and RCC top slab 1:2:4 (1 cement:2 coarse sand:4 graded stone aggregate 20mm nominal size) necessary excavation foundation concrete 1:5:10 (1 cement:5 fine sand: 10 graded stone aggregate 40mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarsesand) 12mm thick finished with a floating coat of neat cement complete as per standard design with F.P.S. bricks. with common burnt clay F.P.S.(non module) brick of class designation 7.5
430Constructing masonry chamber 60x60x75cm, inside with 75 class designation brick work in cement mortar 1:4(1 cement : 4 coarse sand) for sluice valve,with C.I. Surface box 100mm top diameter , 160 mm bottom diameter and 180 mm deep ( inside ) with chained lid and RCC top slab 1:2:4 (1 cement:2 coarse sand:4 graded stone aggregate 20mm nominal size) necessary excavation foundation concrete 1:5:10 (1 cement:5 fine sand: 10 graded stone aggregate 40mm nominal size) and inside plastering with cement mortar 1:3 (1 cement : 3 coarsesand) 12mm thick finished with a floating coat of neat cement complete as per standard design with F.P.S. bricks. with common burnt clay F.P.S.(non module) brick of class designation 7.5
431Providing & fixing of following sizes of butterfly valve of rating PN 16, wafer type, in cast iron body with Ductile Iron disc, EPDM seal, SS single piece shaft, conforming to IS-13095 of the following sizes complete with cast iron hand lever companion flanges, bolts, nuts, washers & inserted rubber gaskets, as required and as per enclosed specification. 80mm dia
432Providing & fixing in position 25 mm dia lawn hydrants consisting of 25 mm dia Ball valve, GI nipple and threaded hose receiver complete as required.
433Excavating trenches of required width forpipes, cablesetc.Including excavation for sockets, and dressing of sides, rammingof bottoms, depth upto1.5M including gettingout the excavated soil,and then returningthesoilas required, in layers not exceeding20 cms in depth includingconsolidatingeach depositedlayerbyramming, watering,etc.And disposing of surplus excavated soil as directed within a lead of 50 m Hard/dense soil. All kind of soil Pipes, cables etc, exceeding 80mm dia but not exeeding 300 mm dia
434Extra for Excavation trenches for pipes, cables etc. in all kind of soil for depth exceeding 1.5m but not exceding 3m (Rate is over corresponding basic item for depth up to 1.5m)
435Earthwork in excavation by mechanical means ( Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift up to 1.5m, including getting out the excavated soil and disposal of surplus excavated soil as directed, with in a lead of 50m. All kind of soil
436Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : 150 mm dia
437Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round RCC. pipes including bed concrete as per standard design : 150 mm diameter
438Constructing brickmasonry manholewith 75 classdesignationbricksincement mortar1:4(1 cement:4 coarsesand) R.C.C. top slab 1:2:4 mix (1 cement:2 coarse sand: 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement: 4 coarse sand: 8 graded stone aggregate 40 mm nominal size) inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design. Inside size 90x80 cm and 45 cm deep including CI Cover with frame (light duty as per IS:12592) 455x610 mm internal dimensions total weight of cover and frame to be not less than 38 kg ( weight of cover 23 kg and weight of frame 15 kg) with common burnt clay F.P.S.(non module) brick of class designation 7.5
439Extra for depth for manholesSize 90 x 80 cmwith common burnt clay F.P.S.(non module) brick of class designation 7.5
440Constructing Brick Masonry circular type manhole 0.91 m internal dia at bottom and 0.56m dia at top with FPS bricksclass designation 75in cement mortar 1:4 (1 cement : 4 Coarse sand), inside cement plaster 12mm thick with cement mortar 1:3 ( 1 cement : 3 coarse sand) finished with a floating coat of of neat cement, foundation concrete 1:3:6 mix ( 1 cement : 3 coarse sand :6 graded stone aggregate 40mm nominal size) and making necessary channel in Cement Concrete 1:2:4 ( 1 Cement : 2 Coarse Sand : 4 Graded Stone Aggregate 20mm nominal size) finished with a floating coat of neat cement complete as per standard design. 0.91m deep with SFRC cover and frame (heavy duty HD-20 grade designation) 560mm internal diameter conforming to I.S:12592, total weight of cover and frame to be not less than 182Kg. fixed in cement concrete 1:2:4 mix (1cement: 2 coarse sand: 4 graded stone aggregate 20mm nominal size) including centering, shuttering all complete.(Excavation foot rests and 12mm thick cement plaster at the external surface shall be paid for separately) with common burnt clay F.P.S.(non module) brick of class designation 7.5
441Extra depth for circuler type manholes 0.91 m internal dia ( at bottom ) beyond 0.91m to 1.67 m . with common burnt clay F.P.S.(non module) brick of class designation 7.5
44212 mm cement plaster finished with a floating coat of neat cement of mix : 1:3 (1 cement: 3 fine sand)
443Providing and fixing square-mouth S.W.gully trapclass SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design: 100x100 mm size P type. With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
444Providingorange colour safety foot rest of minimum 6mm thickplasticencapsulated as per IS : 10910 on12mm dia steelbar conformingto IS :1786 having minimum cross section as 23mm x 25mm and over allminimum length 263mm andwidth as 165mmwith minimum 112mm space between protrude legshaving2mm tread on top surface by ribbing or chequering besides necessary andadequate anchoring projections on tail length on 138mmas per standard drawing and suitable to with dtand the bendtest andchemical resistancetest as per specifications and havingmanufacture"spermanent identification make to be visible even afterfixing, including fixing in manholes with 30x20x15cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) complete as per design.
445Excavating trenches of required width forpipes, cablesetc.Including excavation for sockets, and dressing of sides, rammingof bottoms, depth upto1.5M including gettingout the excavated soil,and then returningthesoilas required, in layers not exceeding20 cms in depth includingconsolidatingeach depositedlayerbyramming, watering,etc.And disposing of surplus excavated soil as directed within a lead of 50 m Hard/dense soil.All kind of soil Pipes, cables etc, exceeding 80mm dia but not exeeding 300 mm dia
446Extra for Excavation trenches for pipes, cables etc. in all kind of soil for depth exceeding 1.5m but not exceding 3m (Rate is over corresponding basic item for depth up to 1.5m)
447Earthwork in excavation by mechanical means ( Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift up to 1.5m, including getting out the excavated soil and disposal of surplus excavated soil as directed, with in a lead of 50m. All kind of soil
448Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : a)150 mm dia
449b)200 mm dia
450c)250 mm dia
451d)300 mm dia
452Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) up haunches of RCC. pipes including bed concrete as per standard design : a)150mm dia RCC Pipe
453b)200 mm dia
454c)250 mm dia
455d)300 mm dia
456Constructing brickmasonry manholewith 75 classdesignationbricksincement mortar1:4(1 cement:4 coarsesand) R.C.C. top slab 1:2:4 mix (1 cement:2 coarse sand: 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement: 4 coarse sand: 8 graded stone aggregate 40 mm nominal size) inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design. Inside size 90x80 cm and 45 cm deep including CI Cover with frame (light duty as per IS:12592) 455x610 mm internal dimensions total weight of cover and frame to be not less than 38 kg ( weight of cover 23 kg and weight of frame 15 kg) with common burnt clay F.P.S.(non module) brick of class designation 7.5
457Extra for depth for manholesSize 90 x 80 cmwith common burnt clay F.P.S.(non module) brick of class designation 7.5
458Constructing Brick Masonry circular type manhole 0.91 m internal dia at bottom and 0.56m dia at top with FPS bricksclass designation 75in cement mortar 1:4 (1 cement : 4 Coarse sand), inside cement plaster 12mm thick with cement mortar 1:3 ( 1 cement : 3 coarse sand) finished with a floating coat of of neat cement, foundation concrete 1:3:6 mix ( 1 cement : 3 coarse sand :6 graded stone aggregate 40mm nominal size) and making necessary channel in Cement Concrete 1:2:4 ( 1 Cement : 2 Coarse Sand : 4 Graded Stone Aggregate 20mm nominal size) finished with a floating coat of neat cement complete as per standard design. 0.91m deep with SFRC cover and frame (heavy duty HD-20 grade designation) 560mm internal diameter conforming to I.S:12592, total weight of cover and frame to be not less than 182Kg. fixed in cement concrete 1:2:4 mix (1cement: 2 coarse sand: 4 graded stone aggregate 20mm nominal size) including centering, shuttering all complete.(Excavation foot rests and 12mm thick cement plaster at the external surface shall be paid for separately) with common burnt clay F.P.S.(non module) brick of class designation 7.5
459Extra depth for circuler type manholes 0.91 m internal dia ( at bottom ) beyond 0.91m to 1.67 m .with common burnt clay F.P.S.(non module) brick of class designation 7.5
460Constructing brick masonry road gully chamber 50x45x60 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450 mm pre-cast R.C.C. horizontal grating with frame complete as per standard design : with common burnt clay F.P.S.(non module) brick of class designation 7.5
461Constructing brick masonry road gully chamber 45x45x77.5 cm with bricks in cement mortar 1:4 (1 cement : 4 coarse sand ) with precast R.C.C. vertical grating complete as per standard design : with common burnt clay F.P.S.(non module) brick of class designation 7.5
46212 mm cement plaster finished with a floating coat of neat cement of mix : 1:3 (1 cement: 3 fine sand)
463Providingorange colour safety foot rest of minimum 6mm thickplasticencapsulated as per IS : 10910 on 12 mm dia steelbar conformingto IS :1786 having minimum cross section as 23mm x 25mm and over allminimum length 263mm andwidth as 165mmwith minimum 112mm space between protrude legshaving2mm tread on top surface by ribbing or chequering besides necessary andadequate anchoring projections on tail length on 138mmas per standard drawing and suitable to with dtand the bendtest andchemical resistancetest as per specifications and havingmanufacture"spermanent identification make to be visible even afterfixing, including fixing in manholes with 30x20x15cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) complete as per design.
464Making connection of drain or sewer line with existing manhole including breaking into and making good the walls, floors with cement concrete 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) cement plastered on both sides with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement and making necessary channels for the drain etc. complete :For pipes 250 to 300 mm diameter
465Earthwork in excavation by mechanical means ( Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift up to 1.5m, including getting out the excavated soil and disposal of surplus excavated soil as directed, with in a lead of 50m. All kind of soil
466Extra for every additional lift of 1.5 m or part thereof in excavation / banking excavated or stacked materials All kinds of soil Qty for 1.5-3.0 M depth RWH & Desilt Chamber
467Providingorange color safety foot rest of minimum 6mm thickplasticencapsulated as per IS : 10910 on12mm dia steelbar conformingto IS :1786 having minimum cross section as 23mm x 25mm and over allminimum length 263mm andwidth as 165mmwith minimum 112mm space between protrude legshaving2mm tread on top surface by ribbing or chequering besides necessary andadequate anchoring projections on tail length on 138mmas per standard drawing and suitable to with dtand the bendtest andchemical resistancetest as per specifications and havingmanufacture"spermanent identification make to be visible even afterfixing, including fixing in manholes with 30x20x15cm cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size) complete as per design.
46812 mm cement plaster of mix : 1:4 (1 cement: 4 coarse sand)
46912 mm cement plaster finished with a floating coat of neat cement of mix :1:3 (1 cement: 3 fine sand)
470Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
471Brick work with common burnt clay modular bricks of class designation 7.5 in foundation and plinth in:Cement mortar 1:6 (1 cement :6 coarse sand)
472Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer-in-charge, upto 90 metre depth below ground level. All types of soil300 mm dia
473Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge.200 mm nominal size dia
474Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge.200 mm nominal size dia
475Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge.
476Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge.
477Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in required thickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -in-charge.
478Gravel packing in tubewell construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge
479Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III): 3 graded stone aggregate 20 mm nominal size)
480Centering and shuttering including strutting, propping etc. and removal of form for Suspended floors, roofs, landings, balconies and access platform
481Edges of slabs and breaks in floors and walls Under 20 cm wide
482Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. TMT steel bars
483Supply Installation testing and commissioning of Vertical/horizontal monoblock centrifugaltransfer pumping set with SS-316body and SS-316 impeller, SS-316 shaft mechanical seal, connected to a TEFC induction motor suitable for 415 volts ± 3% phase 50 cycles AC supply with a common suction headerwith valves on main connecting & pumps inlet and a common delivery header with valves, includingt water shock absorber, non return valves with MS galvanized supports and painting with one coat of primer and two coats of synthetic enamel paint including a 100mm dia pressure gauge, Vibration eliminating pads under foundation, all mounted on a common base plate of MS 80x40mm I section bolted to RCC foundation, including elctrical control panel , Auto level controller, cable panel to pumpscomplete in all respects. (i)FOR FILTER FEED PUMP No. ofPumps: 2 (1 Working + 1 Stand by ) Capacity:60 LPM Head :30m
484(ii)FOR RAW WATER LIFTINGPUMP No. ofPumps: 2 (1 Working + 1 Stand by ) Capacity:60 LPM Head :60m
485(iii)FLUSHING WATER LIFTING PUMP No. ofPumps: 2 (1 Working + 1 Stand by ) Capacity:60 LPM Head :60m
486Supply of packaged variable skid mounted hydropneumatic system comprising of :- Vertical, inline multistage centrifugal pumping set with stainless steel SS-304stage casing and SS-304 impellers with stainless steel SS-431 shaft as per IECstandards and GJL250 cast iron suction& discharge casing, connected to TEFC ventilated induction motor of2 pole, 2900rpm, suitable for 400/440 Volts, 3 phase, 50 Hz A.C.Pressure vessel of non corrosiveFRP composite construction lined with NSF and/or FDA listed material,likehigh density polyethylene with fully replaceable polyurethane. Air cell burstpressure of minimum of 5 times the vessel operating pressure and cycle tested for 2,50,000 cycles.No. and capacity of Pressure Vessel – 01 Nos. x 60 Ltrs Control Panel with programmable logic controller (PLC) for cyclic operation of pumps. Pump workingsequence should change after every operation.Contractor overload relays and MCBs should confirm to IEC 898 – 1995/ specifications. Blinking indications for pumps start, trip, low level trip, health supply should be provided in the panel along with the ammeter& voltmeter. Control panel should also consist of cooling fan. Pressure switches bellowtypefittedwithmicro switch and having maximum pressure and differentialscaleshould confirming BS-6134 standards and IP55 protection class. Stainless steel suction and delevery header,ball valve on each pump on section delivery side, non return valves, Y stainer complete in all respect. Ball valves tobe used should be Hot Pressed brass OT-58withstainless steelballand P.T.F.Eseal and O-Ring. NRVs to be used shouldbewithSpringsandO-Ring arrangement. Complete set system tobemountedona commonbase frameand shallfollow following duty. e. Set of accessories such as pressure switches, pressure transducers, inter connecting power and control cabling etc. complete f. Accessories like pressure gauge, MS base frame (Synthetic enamel painted over a coat of primer) g. SS suction and delivery header with flanges for inlet connection, common outlet header with flanges for outlet connections as required, and inter connecting piping with flexible connections, eccentric type reducers etc. all necessary indigenous accessories as required to complete the installation. DOMESTIC WATER TRANSFER PUMPS (HPN) No. ofPumps: 2 (1 Working + 1 Stand by ) Capacity:180 LPM Head :15m-20m
487Submersible single stage single entry pumps with C.I.body and C.I. two vane enclosed type impeller connectedto TEFC submersible motor for 415 volts, 3 phase, 50 cycles including MCC panel with level controllers, auto control, sequential change over facility with one proper working at low level & two proper working at high level with an audible alarm including all interconnectivity cables, with both pumps connected to common outlet header including valves, non return valves, lifting chains etc. complete in all respect SUBMERSIBLE UNDER GROUND FOR BOREWELL No. ofPumps: 1 (1 Working ) Capacity:60 LPM Head :70 m
488Submersible single stage single entry pumps with C.I.body and C.I. two vane enclosed type impeller connectedto TEFC submersible motor for 415 volts, 3 phase, 50 cycles including MCC panel with level controllers, auto control, sequential change over facility with one proper working at low level & two proper working at high level with an audible alarm including all interconnectivity cables, with both pumps connected to common outlet header including valves, non return valves, lifting chains etc. complete in all respect (one working + one standby/both working in high flow conditions) PUMP ROOM SUMP PUMP (Solid handiling capacity 10-12mm) Capacity- 200 lpm (Each) Head- 15 m
489Pressure Filter (Domestic Water):Providing, fixing, testing & commissioning of vertical FRP filterwith adequate dirt holding capacity. The filter shall be complete having PVC frontal piping with 50 mm multiport valve including all supporting structure with initial charge filter media. The filter shall be provided withset of internals for raw water inlet and bottom collecting system.Velocity in frontal piping and valves shall be 1.50 m/sec. The working pressure shall be 3.5Kg/Sq.cm and the filter shall be tested for 6Kg/Sq.cm. (Make - Pentair/any Reputed make) Discharge:3600 lphper filter Filtration Rate:15000 lit./m2/h Suggested dia app.:600 mm
490Activated Carbon Filter:Providing, fixing, testing and commissioning of vertical self supporting Activated Carbon Filter. Activated Carbon Filter shall be constructed of FRP/composit material with inner shell of integrated Polyethylene with Fiber Reinforced Plastic as per manufacturer standard. The inner distribution system and the under bed draw off system shall be of Hub & Lateral type/Riser tube with top & bottom strainers of Polypropylene material. Filter shall be supplied with initial charge with supporting media like silex, gravel etc. The filter shall be complete with pressure gauge at inlet & outlet, sample cock, PVC face piping/interconnected piping, Multiport valve and all necessary accessories. Activated Carbon Filter Flow Rate : 3600 LPH Filteration velocity : 15 cum/hr/sqm Max. operating pressure: 3.5 kg/sq.cm Test pressure: 5.5 kg/sq.cm Suggested Diameter : 750 mm
491Water Softener:Providing, fixing, testing &commissioning of FRP watersoftening plant (suitable for 3 Kg/Sqcm working pressure)complete with initial charge with T-40 NA Resin, multiport valve with built in ejector for controlling all operations), regenerationsystem and HDPE tank, pressure gauge at inlet, outlet and back wash (each with isolation cock), valves, fittings and water hardness testing kit & associatedworks. Velocity in frontal piping and valves shall be 1.50 m/sec Softenershallbe suitable for the following duty: (Make- Pentair/any reputed make) Minimum expected rate of flow:3600 lph Total soft water to be produced between two regenerations:36 KL Expected raw water hardness : app. 300-400 ppm Expected treated water hardness: less than 120 ppm Max. working pressure: 4 kg/cm2
492POST CHLORINATION OF WATER Supply Installation testing and commissioning of On line electronic chemical solution dosing system comprising of electronic metering pump (with both frequency and stroke length controls to control the dosage rate between 10-100 % of rated maximum capacity), virgin HDPE chemical grade solution tank of rquired capacity, necessary injection fitting assembly, foot valve cum strainer and suction and delivery tubing etc. upto the point of injection complete in all respects as required. For Cholorination of filtered water Dosing capacity : 0-6 ltrs. per hour, Dosing Head : 3.5 kg/cm2
493To switch on the pumps (includingRaw Water Pump, Domestic water supply pump etc.) when the level of water in the supply water tank is lowandto cut off the pump when the level in thereceiving watertank is high and switch off the pumps when the level of water in the supply water tank is low. To indicate 5 levels of water in all tanks through a control panel with LEDs To start the pumps in a cyclic order. The system shall be complete to ensure automatic quotation of pump in accordance to water level in respective tanks. The Contractor will include all the under ground and over head tanks and all the pumps as required for level control in this item
494Design, Installation testing & commisioning ofSewerage treatment plant in MBBR (MOVING BED BIO REACTOR TECHNOLOGY) process electro Mech. work only, Tertiary treatment completelyfor Domestic Sewege capciaty 15 cum/day. Outlet Parameter should be match for using the water for Gardening & Flushingpurpose. Bidder should include following items as specified below suitable for 15 cum/day STP. (Bidder Must visit the site before quote) Depth of Incomming sewer 1.5m to be consider. The STP shall be designed based on the following parameters:Daily average flow - 15 Cum / Day;pH - 6.5 – 8.5;BOD5 - 250 – 450 Mg/L;S. Solids - 200 – 400 Mg/L;COD - 400 – 600 Mg/L;Oil & Grease - 30 Mg / L;Effluent discharge standard after treatment :pH - 6.0 – 8.5;BOD5 - Less than 5Mg/L;S. Solids - Less than 5 Mg/L;COD - Less than40 Mg/L;Oil & Grease - Nil;E Coli - Nil;Sewerage treatment plant contaning following Electro Mech. Items including 2 years O & M a)1 Nos. Stainless Steel-316 Perforated Corrugated Screen of fabricated through 5mm thick plate having holes of 8 mm at a distance of 10 mm with suitable lifting arrangement-1 set b)mechanical punched hole fine screen for 2-3 mm size complete as required MOC - SS 304 - 1 set Level and Measurmement Control,sight tube (of 3.5 to 4.5 m length) with isolation valve at top/bottom c)Equalization Transfer pump (1 Working +1 standby)-1 set d)2 No. twin type rotary air blowers (1W + 1S) for Aeration Tank and Equlisation tank- 1 set e)2 No. twin type rotary air blowers (1W + 1S) for TW membrane scouring system- 1 set f)Disc type, EPDM membrane based, non clog type air dispersion system for Imported fine bubble membrane diffusers for equalisation tank, aeration tank & sludge holding tank, MBBR tank,MS pipe (C Class),SS Piping ( Schedule 10),Butterfly Valve,Non-Return Valve,Ball Valve,MS Class "B"with hot dip galvanized puddle flange,instrument for the auto operation of System and saftey,- 1 set g)MBBR module immersed type with permeate - 1 set h)Automation of complete plant from raw effluent pump to permeate pump out put with proper flow control i)Ultravoilet dis-infection unit- 1 set j)MBBR Permeate pump with VFD (1 Working +1 standby)- 2 each k)Sludge Recycling Pump(2 Working +1 standby) (Solid handling size for this pump shal be 7-10 mm) - 2 each l)Hypo solution dosing pump comprising of FRP tank with inlet / outlet connection- 1 set m)Basket type Centrifuge Machine 48"" with Perforated Plate-4mm thick, SS 304 Main Shaft-En 8, Base Frame-MS Channel.Basket Size: 1500 (Dia)- 1 set n)MGF, ACF, Softener treasury treatment - 1 set o)Self priming sludge Feed pump (1 Working +1 standby)- 1 set p)Electrical Panel with Cable, Earthlingq)- 1 set Sewerage treatment plant 15 cum/day complete following above items.
495Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machineries required for the job, all complete as per direction of Engineer -in-charge, up to 90 metre depth below ground level. All Types of Soil-300mm dia
496Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge.200 mm nominal size dia
497Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge.200 mm nominal size dia
498Gravel packing in tube well construction in accordance with IS: 4097, including providing gravel fine/ medium/ coarse, in required grading & sizes as per actual requirement, all complete as per direction of Engineer-in-charge.
499Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by "V" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tube well, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge.
500Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for bore well of:200 mm dia
501Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tube well as per IS: 2800 (part I), including necessary bolts & nuts of required size complete.00 mm clamp.
502Providing and fixing Bail plug/ Bottom plug of required dia to the bottom of pipe assembly of tube well as per IS:2800 (part I). 200 mm dia
503ELECTRICAL & LV SYSTEMS: Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class pvc conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
504Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
505Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class pvc conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
506Supply and fixing of suitable size GI box with modular plate and cover in front on surface or in recess including providingandfixing 3 pin 5/6 amps modular socket outlet and 5/6 amps. modular switch, connection etc. as required.
507Supply and fixing of suitable size GI box with modular plate and cover in FRLSont on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps. modular switch, connection etc. as required.
508Supplying and fixing 20 amps, 240 volts, SPN, industrial type socket outlet, with 2 poles and earth metal enclosedplug top alongwith 20amps. "C" curve, SP MCB in sheet steel enclosure, on surface or in recess, with chainedmetal cover for the socket outlet, and complete with connections, testingandcommissioning etc. as required.
509Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc.as required.
510Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
511Supply and fixing The OccuSwitch is a movement detector (Light Sensor) with a build-in switch. (LRM1070, LRM1080)
512Supply, Testing & Commissioning, fixing of following bare GI tapes / wires including all necessary fixingaccessories and effecting connections as per specifications. A)50 x 10 mm thick GI tape.
513b)50 x 6 mm thick GI tape
514c)25 x 6 mm thick GI tape.
515d)8 SWG GI wire
516Providing and laying of 14.35 mm diaand 3 meter length.copper bonded earth rod in 150 mm dia. in an augured hole in ground , surrounded by ground enhancement material as per specification. Inspection chamber shall be of 400 x 500 mm with concrete base CI manhole cover with frame painted with bitumastic paint. 2 Nos. of 50 x 6 mm cross section & 300 mm long copper strip to be clamped with copper claded rod electrode have sufficient nos ( But not less than 4 Nos.) of 10 mm dia. GI nuts & bolts for connection to the equipment / interconnection to the other pits to form equi-potential bonding .The pH value of ground enhance material shall be 6.9 to 7.2 of 1000gm / lit @ 20 deg.c.The minimum 30 Kg of ground enhancement material shall provided for each electrode with 10 kg of compound as per clause 14.5(d) and 20kg of compound as per clasue 14.5 (b) of IEEE 80:2013.
517Providing, laying, testing and commissioning of following 1100 volts grade PVC insulated sheathed copper conductor unarmoured cable including copper thimbles, fixing hardware as required. Single core 25 sq.mm Green colour cable
518Supply, laying, testing and commissioning of GI pipe under road / paved area crossing etc. including excavation back filling ramming and making good. A)50 mm diapipe.
519b)75 mm diapipe.
520Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). a)6 way , Double door
521b)8 way , Double door
522c)12 way , Double door
523Supplying and fixing followingway, horizontal type TP&N, sheet steelMCB distribution board,415 V on surface /recess,completewithtinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required (But without MCB / RCCB / Isolators). 8 Way (4+24), Double door
524Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB’s (but without MCB’s and incomer ) as required 12 way (4 + 36), Double door
525Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 6 A to 32 A ratings , SP MCB,
526Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
527Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. A)40 amps
528B) 63 amps
529Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. a)40 amps
530b) 63 amps
531Supplying of following 1100 volt grade XLPE insulatedPVC sheathed aluminium conductor armoured cables as per specification in existing trenches, cable trays, ducts over bed of sand, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning. A) 3½ X 300 sq. mm
532b) 3½ X 120 sq. mm
533c) 3½ X 50 sq. mm
534d) 3½ X 35 sq. mm
535Supplying of following 1100 volt grade XLPE insulated PVC sheathedcopper conductor armoured cables as per specification in existing trenches, cable trays, ducts over bed of sand, clamped includes anchor fastners wall with suitable clamps, saddles fixing bolts including connecting testing and commissioning. a)4 X 10 sq. mm
536b)4 X 16 sq. mm
537c)3 X 10 sq. mm
538d)1 X 120 sq. mm
539e)1 X 300 sq. mm
540Supplying & making ofend terminations with brass compression gland and Al. lugs for following sizes of PVC insulated and PVC sheathed/ XLPE Al. conductor cable of 1.1 KV grade as required. A) 3½ X 300 sq. mm (70mm)
541b) 3½ X 120 sq. mm (45mm)
542c) 3½ X 50 sq. mm (35mm)
543d) 3½ X 35 sq. mm (32mm)
544e)4 X 10 sq. mm
545f)4 X 16 sq. mm
546g)3 X 10 sq. mm
547h)1 X 120 sq. mm
548i)1 X 300 sq. mm
549Laying and fixing of one number PVC insulated and PVC sheathed / XLPE aluminium power cable of 1.1 KV grade of following size on cable tray as required.a) Above 185 sq. mm and upto 400 sq. mm
550b) Above 95 sq. mm and upto 185 sq. mm
551c) Above 35 sq. mm and upto 95 sq. mm
552d) Upto 35 sq. mm
553Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. (For Road crossing) 100 mm dia
554Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required. A)150 mm width X 50 mm depth X 1.6 mm thickness
555B)300 mm width X 50 mm depth X 1.6 mm thickness
556C)600 mm width X 50 mm depth X 2.0 mm thickness
557D)750 mm width X 62.5 mm depth X 2.0 mm thickness
558E)900 mm width X 62.5 mm depth X 2.0 mm thickness
559SANDWICH BUS BAR TRUKING:- Supplying, installing by suspension on ceiling/ along the wall, testing and commissioning of following capacity Sandwich Type Rising Mains for use on 3 phase 4 wire 415 volts, 50Hz A.C A)2000 A 50KA ISC for 1 sec
560B)3200 A 50KA ISC for 1 sec
561C)4000 A 50KA ISC for 1 sec
562D)2000 A Copper Flexible at both end
563E)3200 A Copper Flexible at both end
564F)4000 ACopper Flexible at both end
565Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
566GI RACEWAY & JUNCTION BOXES:-Providing and laying 2 MM thick GI factory fabricated raceways in partition of the following sizes including providing removable 3 mm thick GI cover knock out holes and fixing accessories completerequired including floor supports, bends, access boxes and tap off boxes as per specification and cross over as per site requirement. A)400 mm wideX 40 mm deep raceway
567B)300 mm wideX 40 mm deep raceway
568C)250 mm widex 40 mm deep raceway
569D)200 mm widex 40 mm deep raceway
570E)150 mm wide x 40 mm deep raceway
571F)100 mm wide x 40 mm deep raceway
572G)65 mm wide x 40 mm deep raceway
573Providing and fixing of 450 x 450 x 60 mm deep (Nominal size) junction box including providing 3 mm thick GI steel cover required as per specification.
574Providing and fixing of 350 x 350 x 60 mm deep (Nominal size) junction box including providing 3 mm thick GI steel cover required as per specification.
575Providing and fixing of 300 x 300 x 60 mm deep (Nominal size)junction box including providing 3 mm thick GI coverrequired as per specification.
576Providing and fixing of 250 x 250 x 60 mm deep (Nominal size)junction box including providing 3 mm thick GI coverrequired as per specification.
577Providing and fixing of 200 x 200 x 60 mm deep (Nominal size)junction box including providing 3 mm thick GI coverrequired as per specification.
578Providing and fixing of 150 x 150 x 60 mm deep (Nominal size)junction box including providing 3 mm thick GI coverrequired as per specification.
579Providing and fixing in position the following PVC conduits concealedas called for including all accessories i.e. bends, junction boxes, with cover plates of approved make and design. 25 mm dia
580Supplying, installation, testing and commissioning of 3.0meterHeighthotdipgalvanisedcontinously tapered (bolt fixing type) octagonalPole including 60 watt LED Fixture, colour cool white , integral driver, protection IP 65, CLASS Iwithtop 70 mm dia and bottom 130 mm dia made of 3 mm thick H T sheet Steelconforming to grade S 355 complete with G Ibase plate of size 220 mm(L) X 220 mm(B) X 12 mmthicknesswelded at bottom of pole completewith4 Nos 20 mm dia 750 mm longfoundationboltsconfromingtoEN8grade,inbuilt/Vandalresistance,weathproofelectrical junction box having terminalblock,MCB etc. mounted on bakelite sheet forlooping in /looping out of cables,withflushdoorhavinglockingarrangement, earthing arrangement(atatleast 0.5mheight) and mounted on RCC foundation of size 450 mm x 450 mm x 800 mm in ground and 200 mm above ground level with foundation bolt duly embeded before casting and supply and embedding ofsuitable size HDPE pipe sleeve for cable entry. complete including erection of Pole complete in all respectas required.
581Supplying,installation,testing and commissioningof 7.5 meterHeight hotdipgalvanisedcontinously tapered (bolt fixing type) octagonalPole including 90 watt LED Fixture, colour cool white , integral driver, protection IP 65, CLASS Iwithtop 70 mm dia and bottom 130 mm dia made of 3 mm thick H T sheet Steelconforming to grade S 355 complete with G Ibase plate of size 220 mm(L) X 220 mm(B) X 16 mmthicknesswelded at bottom of pole completewith4 Nos 20 mmdia 750 mm longfoundationboltsconfromingtoEN8grade,inbuilt/Vandalresistance,weathproofelectrical junction box having terminalblock,MCB etc mountedon bakelite sheet forlooping in /looping out of cables,withflushdoorhavinglockingarrangement,earthingarrangement(atatleast 0.5mheight) and mounted on RCC foundation of size 450 mm x 450 mm x 1000 mm in ground and 200 mm above ground level with foundation bolt duly embeded before casting and supply and embedding ofsuitable size HDPE pipe sleeve for cable entry. complete including erection of Pole complete in all respect as required.
582Supply,Installation,testingandcommissioningof1000mmlongDoublearmbracketofapproved designandshapemadeupofMSmetalwithhotdipgalvanisedsuitableforpoletopof70mmdia complete with fixing arrangement as required
583Supply,Installation,testingandcommissioningof1000mmlongSinglearmbracketofapproved designandshapemadeupofMSmetalwithhotdipgalvanisedsuitableforpoletopof70mmdia complete with fixing arrangement as required
5841 X 18 W LEDFixture suitable for mounting on gate with allaccessories etc as approved by Architect.
585Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper inding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin,nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.1200 mm sweep
586Supply & installation of 28W lmi1161 rc380b LED36s-6500 Light Fixture with all accessories as per standard item.
587Supply & installation of 10W WALL MOUNTED LED (MIRROR) with all accessories as per standard item. (Model : Wipro or Equivalent).
588Supply and installation of bn308c LED40s-6500 L12o with all accessories as per standard item. (Model : Wipro or Equivalent).
589Supply & installation of 10 LED BULKHEAD FITTING with all accessories as per standard item. (Model : Wipro or Equivalent).
590Supply & installation of dn296b LED12s psu wh with all accessories as per standard item. (Model : Wipro or Equivalent).
591Supplying and fixing following size / modules, GI box along with modular base & cover plate for modular switches inrecessetc as required 1 or 2 Module (75 mm x 75 mm)
592Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc as required . A)Telephone Socket outlet
593B) TV Antenna socket outlet
594Supply and fixing offollowingsizes of medium class PVC conduit along with accessories in surface/recess including cuttingthe wall and making good the same in case of recessed conduit as required : (For Telephone, TV, Data wiring) 25 mm.
595Supply and drawing followingpair, 0.5 sq.mm. FRLS PVC insulated annealed copper conductor, unarmoured telephone cable in the existing surface / recessed steel/ PVC conduit as required. 2 Pair
596Supply and drawing co-axial TV cable RG-6 grade, 0.7 mm. Solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface / recessed steel/ PVC conduit as required.
597Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable
598Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc as requiredData socket outlet
599Supply & Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 33 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. 3 C x 300 sq.mm 33 KV XLPE (E) cable
600Supplying and making cable end terminations for the following size of 33 KV grade, XLPE (E) aluminium conductor armoured cable including termination kit complete heat shrinkable sleeve etc. A)3 C x 300 sq.mm 33 KV XLPE (E) cable (Indoor)
601B)3 C x 300 sq.mm 33 KV XLPE (E) cable (outdoor)
602Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. (For Road crossing) A)100 mm dia
603B) 150 mm dia
604Supplying and laying of following 1100 volts grade PVC insulated sheathed copper conductor armoured control cables in existing trenches cables trays, clamped on wall with suitable saddles, fixing bolts, including testing and commissioning. 7 Core 2.5 sq mm PVC insulated copper conductor armoured control cables
605Cable end termination of the following PVC insulated sheathed aluminium conductor armoured cables of 1100 volt grade including supplying and fixing of crimping lugs. Double compression glands, cable sockets etc as required. 7 Core 2.5 sq.mm Control cable
606Supplying, fixing, testing and commissioning of following bare GI/CU tapes including all necessary fixingaccessories and effecting connections. A)50 mm x 10 mm thickCU tape.
607B)50 mm x 10 mm thickGI tape.
608Providing and laying of 14.35 mm diaand 3 meter length.copper bonded earth rod in 150 mm dia. in an augured hole in ground , surrounded by ground enhancement material as per specification. Inspection chamber shall be of 400 x 500 mm with concrete base CI manhole cover with frame painted with bitumastic paint. 2 Nos. of 50 x 6 mm cross section & 300 mm long copper strip to be clamped with copper claded rod electrode have sufficient nos ( But not less than 4 Nos.) of 10 mm dia. GI nuts & bolts for connection to the equipment / interconnection to the other pits to form equi-potential bonding .The pH value of ground enhance material shall be 6.9 to 7.2 of 1000gm / lit @ 20 deg.c.The minimum 30 Kg of ground enhancement material shall provided for each electrode.
609Supply and laying medium class GI pipe under road/paved areas/wall crossing etc. including earth excavations refilling, ramming and making good as approved. 150 mm dia GI pipe
610Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
611Supplying and fixing of high voltage insulation mat of class B having 33 KV dielectric strength, 1000mm width and thickness of 2.5mm ISI approved as required including cutting to required lengths.
612Supplying and fixing of high voltage insulation mat of class B having 1.1 KV dielectric strength, 1000mm width and thickness of 2.0 mm ISI approved as required including cutting to required lengths.
613Supplying of 33 KV hand gloves as required.
614Supplying of resuciation kit coomplete with instruction manual etc. as required.
615Supplying of fire bucket painted red with stand and approved quality conforming to IS:254/1974
616Supplying and Fixing of Powder Fire Extinguisher (Stored Pressure type)Capacity 5 Kg duly ISI marked conforming to IS: 15683:2006, with IS 14609, ISI marked ABC powder complete with squeeze grip release valve, discharge pipe, locking arrangement, pressure gauge & suitable M.S. bracket as required.
617Supplying of first aid box as approved complete with standard kit as prescribed by Indian Red Cross.
618Supplying and fixing of shock treatment chart written in English and Local language duly framed in glass as required.
619SITC of Remote Monitoring of Earthing system as per specificationn of each earth pits comprising of suitable numberes of sensor, remote terminal units and peripheral command center including all accessories essential to establish communication with the building managemnent system / SCADA .
620CCTV SYSTEM Supply, installation, testing and commissioning of32 Channel NVR , H.264 Recording and Playback , Embedded Linux OS, Pre-Installed VMS with licenses,ONVIF profile S & G , Intel Based i7 Processor , 8TB, DDR3 RAM , Intel HD Graphics , Throughput Input: 640Mbps / Output: 640Mbps,Decoding Rate Up to 3840 PPS @ D1, 2.5” SATA x 1 (for OS) + 3.5” SATA x 8 ports , e-SATA Port for External Storage Device , RAID 0/1/5/6/10 Support , COM Port RS-232 x1 and RS-485 x 1, USB 3.0 x 2 + USB 2.0 x 3 , Digital Input : TTL-level x 4 , Digital Output : Relay NC/NO x2 (DC24V/1A) , 1 x WAN (10/100/1000 BaseT) , 1x LAN (10/100/1000 BaseT), 1 x SFP Port (1 Gbps). (Including all software licence )
621DOME CAMERA - Supply, Installation, Testing & Commissioning ofIP Network TDN Low-Light IR Dome Camera, 1/3" CMOS, 2 MP @ 25fps or better, triple stream, Min. Illumination required 0.2 lux @ F1.4 (colour), 120dB True WDR, Min. Pixels 1920×1080p, triple stream, 3mm - 12 mm motorized focus & zoom lens, Intelligent Video Analytics such as Tripwire, Object Removed, Object Left Behind, etc Backlight Compensation, 3DNR, Privacy Mask, 3 IR LEDs Smart IR with upto 20m IR distance, H.264& MJPEG, Dual channel Audio G.711a/G.711u/AAC, 128GB SD card support, IP 54 & IK10, Alarm: 1 In & 1out,PoE, H.264 High Profile and MJPEG, PoE Class 3/ 12V DC/24VAC,Die-Cast Aluminium Construction,Having Operating temp range : –30°C to 60° C. Certifications: ONVIF Profile S & Profile G compliant. Safety Certification : UL, CE, EN, FCC &RoHS compliant. Cyber security Certification : UL-CAP
622OUTDOOR BOX CAMERA - Supply, Installation, Testing & Commissioning ofIP Network TDN Low-Light IR Outdoor Box/Bullet type fixed Camera, 1/3" CMOS, 2 MP @50fps, triple stream, Min. Illumination required 0.01 lux @ F1.4 (colour), 120dB True WDR, Min. Pixels 1920×1080p, triple stream, 5mm - 50mm variable focus & zoom lens, Intelligent Video Analytics such as Tripwire, Object Removed, Object Left Behind, etc. Backlight Compensation, Highlight Compensation, 3DNR, Privacy Mask, Internal/External Smart IR LEDs with upto 50m IR distance, H.264& MJPEG, Dual channel Audio G.711a/G.711u/AAC, 128GB SD card support, IP 54 & IK10, Alarm: 1 In & 1out,PoE, H.264 High Profile and MJPEG, PoE Class 3/ 12V DC/24VAC, Die-Cast Aluminium Construction,Having Operating temp range : –30°C to 60° C. Certifications: ONVIF Profile S & Profile G compliant, UL, CE, EN, FCC &RoHS compliant. Cyber security Certification : UL CAP
623VIDEO MANAGEMENT SOFTWARE - Supply, Installation, Testing & Commissioning of Video Management Software for 100 Cameras.
624LED - Supplying, Installation, Testing & Commissioning of 55" LED TV with 1920x1080 full HD resolution and as per specifications attached suitable for mounting on wall including connection etc.
625WORK STATION - Supply, Installation, Testing & Commissioning of Client WorkStation with CPU of Intel Core i7 Processor, With 8GB RAM, 1 GB Graphic Card, and 500 GB HDD.
626Supply , Installation , Testing and Commissioning of 36 port L2 Managed switch having port density 36 Nos of 10M/100M/1G RJ45 Port POE /POE+ ports , 2 Nos of GbE RJ45/SFP Combo Port , 1X console port , Available POE power 370 W , 52 Gbps switching bandwidth , 8K MAC address support , Support L2 feature STP, RSTP ,MSTP . Support 802.1Q VLAN , port based VLAN , 4K VLAN entries , MAC based VLAN , IP subnet based VLAN . Support IEEE 802.3ad LACP . L3 features - static routing , DHCP feature , Device Management system - topology view , floor view ,map view , dashboard , traffic monitoring , cable diagnostics.CE,FCC certified. Approved Make : Cisco/ Impulse / Juniper / Extreme/ Arista
627Supply , Installation , Testing and Commissioning of 24 port L2 Managed switch having port density 24 Nos of 10M/100M/1G RJ45 Port POE /POE+ ports , 2 Nos of GbE RJ45/SFP Combo Port , 1X console port , Available POE power 370 W , 52 Gbps switching bandwidth , 8K MAC address support , Support L2 feature STP, RSTP ,MSTP . Support 802.1Q VLAN , port based VLAN , 4K VLAN entries , MAC based VLAN , IP subnet based VLAN . Support IEEE 802.3ad LACP . L3 features - static routing , DHCP feature , Device Management system - topology view , floor view ,map view , dashboard , traffic monitoring , cable diagnostics.CE,FCC certified. Approved Make : Cisco/ Impulse / Juniper / Extreme/ Arista
628Supply , Installation , Testing and Commissioning of CAT 6 UTP cable 23 AWG solid copper conductors for Connectivity of Hub room to End Point.
629Supply and fixing of 16 guage MS Conduits in following sizes including cost of junction boxes, bends, elbows, sockets, tees etc. laying in slab cutting chasis and making good or surface mounted including all fixing hardware. 25 mm dia
630Supply, installation, testing and commissioning of wall/floor mounted cabinet with drawer shelves and wiring channels to accommodate CCTV system equipment and accessories as mentioned in the BOQ above and including all connections and terminations as required fabricated from minimum 2 mm thick CRCA sheet including power coating after surface treatment complete as required.
631Supply, installting, testing and commissioning of Microprocessor based intelligent and electronically addressable, modular,2 loops expandable upto 4 Loop (each loop consist of 159 detector & 159 devices) Fire Alarm Control Panel with minimum6 inch / 640 character LCD display, multiple access levels, event history file in non-volatile memory (EEPROM). The panel shall support programmable relays controlled by powerful Boolean logic equation. The panel shall have 240 volts AC power supply, automatic battery charger, 24 volts, sealed lead acid maintenance free batteries sufficient for 24 hours normal working and then be capable of operating the system for 60 minutes during emergency condition. The panel shall be UL listed9th Edition
632Supply, installing, testing and commissioning of Passive repeater panel with minimum 6 inch / 640 character LCD display complete with accessories as required.
633Supply, installing, testing and commissioning of UL listed addressable intelligent Multitech (Photo-Thermal) detector with auto floating sensitivity (Acclimate type) with mounting base,dual LED, complete with base as required. (For Below False Ceiling Area). UL Listed 7th Edition.
634Supply, installing, testing and commissioning of UL listed addressable intelligent rate of rise thermistor type resettable Heat detector with mounting base, dual LED, complete with base as required. UL Listed 7th Edition.
635Supply, installing, testing and commissioning ofUL listed Hgh Sensivity detector (very high early warning detector with minimum sensitivity of 0.03% obscuration per foot)addressable intelligent photo electric smoke detector, optical type with mounting base, multi-cooperative, dual LED, complete as required. UL Listed 7th Edition.
636Supply, installing, testing & commissioning of addressable Manual call point (Pull station-double action).
637Supply, installation, testing and commissioning of Strobes cum Dual tone hooters with minimum of 110cd and 93 db complete as required.
638Supply, installing, testing and commissioning of addressable and automatic commandable Relay modules.
639Supply, installing, testing and commissioning of addressable and automatic commandable control modules.
640Supply, Installation, testing and commissioning of Addressable Monitor modules.
641Supply, installing, testing and commissioning of addressable type Fault Isolators for isolating shorted, de wired and loose circuits between two successive fault isolators with automatic resetting arrangement.
642Supply, installation, fixing, testing and commissioning of Response Indicator cum lamp assembly mounted on walls /partitions, surface /recessed etc. in dust tight enclosure, including chase cutting complete as required.
643Addressable Fire Fighter"s Telephone Jack with suitable module for two way communication between Remote Fire Fighter & Fire Command Center
644Fire Fighter"s Telephone Handset for two way communication between Remote Fire Fighter & Fire Command Center
645Supply, Installation, Testing and commissioning of 2x1.5sq. mm. 600V Fire Survival type, which can withstand 950 Deg C for three hours as per BIS standards and shall also withstand CWZ test on one single Cable. The Item should also includes the Glands & seals for both ends.
646Supply, installing, testing and commissioning of Networkable Integrated 8 channel(FOR 8 DIFFERENT TYPE OF MESSAGES TO GET RELAYED SIMULTANEOUSLY) Digital Voice Evacuation and 2 way Communication Fire Fighters System capable to supervise all the speaker circuits, with required number of zone control as given below and accessories required to complete the system.The equipment shall be of same make as panel. DVC shall offer minimum one fire man"s telephone circuit & one speaker"s circuit. DVC shall be with in-built digital microphone, fire man"s telephone hand set & PA Zone control DVC with 48 zone control with Network Card
647Supply, installing, testing and commissioning of Addressable & fully supervised DIGITAL AMPLIFIERS with minimum Wattage as given below with 70.7 VRMS. The Digital Amplifiers shall have inbuilt minimum of 4 Speakers Zone Circuits and minimum 1 Fire Fighters communication. The Amplifiers shall be stand alone with its own battery backup incase of Main fire Alarm panel / Digital Voice Panel failure and the Digital Amplifiers shall still be in position to carry out Voice Evacuation. 400 Watts
648Supply, installing, testing and commissioning of Fire panel supervised 78db-90db Ceiling Mounted Speakers as specified & same make as of panel. Speakers shall be 2 Watt with multi taps of 0.25W, 0.5W, 1W and 2W.
649Supply, installing, testing and commissioning of Fire panel supervised 78db-90db Wall Mounted Speakers as specified & same make as of panel. Speakers shall be 2 Watt with multi taps of 0.25W, 0.5W, 1W and 2W.
650Supplying and Laying of 2 core twin twisted 48/0.2 ATC, Multi strand, over all armouredspeaker cable as specified in the Tender Specifications.
651Supply, installation, testing and commissioning ofOil Type, 33 / 0.433KV, 3 phase, 50 Hz, DYn -11, vector groupcopper wound, Class A insulation associated with winding temperature indicator / controller actuated by means of resistance temperature detector embedded in LV winding, outdoor typetransformerwith approximately impedance as per IS (5.0% / 4.0%) tapping for ON load operation on HV side in steps of2.5% for + 5% to - 10%with RTCC (along with necessary Control cabling) having cable end boxes on HV side suitable for 3 core x 300 Sq.mmXLPE cable of 33 KV grade and 4000 Amp bus trunking arrangementon LV side with neutral brought out separately including supplying and laying ofcopper conductor multicore control cable from transformer to HT breaker for safety tripping suitably mounted onMS channel includingsupplyingandgroutingofsuitableMSchannelswithallaccessoriesand conforming toIS:11171:1985 withupto dateamendments &asperTechnicalspecifications complete in all respect E.G soak pit ,sump etc.( Total losses in transformer 6.611 kW @ 50% load & 19.888 kW @ 100% load) 2500 KVA Transformer (Approx Weight - 9200 Kg.)
652Providing, Installing,TestingandCommissioningof"StandardType"DieselGeneratingsetalongwith having PrimePower Rating of 1800 KVA to 2000 KVA, 415 volts at1500 RPM,0.8 lagging power factorat 415V suitable for 50 Hz, 3 phase system and consisting of the followings: (Total of a to h). Diesel Engine: Diesel engine 4 stroke water cooled, Radiator type electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 40 Degree C, 50% RH & at 1000 Meter MSL and conforming toBS5514,BS649,IS10000,capableoftaking10%overloadingforonehourafter12hoursof continuous operation. The engine will be fitted complete with all required accessories. Engine mounted Instrument Panel fitted with and having digital display for following: Start-stop switch with key; Water temperature indication; Lubrication oil pressure indication; Lubrication oil temperature indication; Battery charging indication; RPM indication; Over speed indication; Low lub. Oil trip indication; Engine Hours indication. Alternator: Synchronous alternator rated at 1800 KVA to 2000 KVA, 415 volts at 1500 RPM, 3 phase 50 Hz, AC Supply with 0.8 lagging power factor at 40 Degree C, 50% RH & AT 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and self - regulated through AVR conforming to IS: 4722/BS 2613 Suitable for tropical conditions and with class - H insulation. Base Frame & Foundation: BoththeengineandalternatorshallbemountedonsuitablebaseframemadeofMSchannelwith necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer. Fuel Tank: Daily service fuel tank of 990 litres capacity fabricated out of 3 mmthick M.S. Sheet complete with all standard accessoriesand fuelpiping between fueltankand diesel engine with MS class "C"pipes of suitable dia. Complete with valves, level indications & accessories as required as per specifications. Exhaust System: Dry exhaust mainfold with hospital exhaust silencer as per technical specification, Starting System: 24VDCstartingsystemcomprisingofstartermotors:voltageregulatorandarrangementforinitial excitation complete with2 nos. of batteries (180 Amp. Hour capacity lead acid type) as required as per specifications. Accoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per specifications. (Approx Weight - 22000 Kg.)
653Fabrication,supply &erectionofMSsupportforfixingofexhaustpipingandMSstructureincluding Angle/chanels/flats/beamasperapproveddrawingsforsupportingofDGexhauststackfrom ground. floor level and above terrace level completein all respect.
654Supply, installation, testing & commissioning of Main LT panel / Isolator panel/ Main distribution panels / sub-distribution panels, fabricated out of 14 gauge CRCA sheet steel in cubicle compartmentised modular 3b construction, free standing floor mounted, dust and vermin proof withreinforcement of suitable size angle iron, channel, `T’ sections and / or flats wherever necessary. 16 gauge CRCA sheet steel shall be used for final distribution panels. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specifications and final approved shade. 2 Nos. earthing terminalsshall be provided for all distrtibution panels. Panels shall be suitable for 415V, 3 phase, 4 wire, 50 HZsupply system. Lifting hooks shall also be provided in case of large panels. STAND BY TRANSFORMER PANEL Incoming-I From 2500kVA Transformer-02):4000 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unitfor short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories :Digital electronic energy multi function meter(conzerve – EM 6400 with RS-485 or equivalent) with inbuilt selector switch and 4000/5 Amps 15 VA, CL 1 CTs . - 1 SetDigital VAF meter with 1 Nos. 4000/5 amps 15VA CTs with inbuilt slector switchPhase indicating light shall be protected by 2 amps MCB’s. -1 SetsON / OFFindicating lights with control MCB’s. - 1 Set.Under voltage release - 1 SetAuto-manual / test selector / switch - 1 SetAuxiliary contacts required for necessary interlocking of breakers.Temprature scanner, Surge Protection Device Type -1, spark gap type fpr 10/350µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 40KA per mode. Bus Bars5000 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves - 1 Set.Outgoing 3 No. 4000 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification. SPARE FEEDERS :-1 No. 4000 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification. Notes : All outgoing feeders except capacitor shall have suitable range of followings All outgoing feeder shall have digital electronic energy meter ( EM 6438 of conzerv make or equivalent ) with suitable no. of CT,s and RS 485 port .Interlocking of all incoming air circuit breakers/bus coupler shall be through PLC comprising suitable nos. digital inputs (24 VDC) and output (Relay)Wiring with space heater, humidistat and control MCB’s shall be provided all vertical sections of main LT panel.Suitable danger board shall be provided.All bus bar section / backside panels shall have pad locking facility and hinged type door.2500/1250/5A,15VA,CL-1.0 CTs shall be provided in the incommer of transformer for APFC relay of capacitor panel.All incoming / outgoing air circuit breakers shall be suitable for minimum 50 kA breaking capacity.9 W fitting with CFL / LED lamp, switch shall be provided in each vertical section.Incoming breakers shall have suitable provision for busduct connection..All Electronic Energy meter shall be pre wired for BMS connection upto central point within the panel with sheilded cable. Stand by Transformer as described above.
655MLTP-I : Incoming-I From 2500kVA Transformer-01) 4000 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unitfor short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories : Digital electronic energy multi function meter(conzerve – EM 6400 with RS-485 or equivalent) with inbuilt selector switch and 4000/5 Amps 15 VA, CL 1 CTs . - 1 Set;Digital VAF meter with 1 Nos. 4000/5 amps 15VA CTs with inbuilt slector switch;Phase indicating light shall be protected by 2 amps MCB’s. -1 Sets;ON / OFFindicating lights with control MCB’s. - 1 Set.;Under voltage release - 1 Set;Auto-manual / test selector / switch - 1 Set;Auxiliaryontacts required for necessary interlocking of breakers;Temprature scanner,Surge Protection Device Type -1, spark gap type fpr 10/350µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 40KA per mode. Incoming-II (From DG Synchronizing Panel) :4000 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unitfor short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories;:Digital energy meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3 Nos. 4000/5 amps 15VA CTs.;3 Nos. phase indicating lights with control MCB’s.;Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set;24 V DC Shunt trip coil. - 1 Set;240 V under voltage release. - 1 Set;Auto-manual / test selector / switch - 1 Set;Breaker control switch - 1 Set;Auxiliary contacts required fornecessary interlocking of breakers. Incoming-III (From STAND BY TXFR PANEL) :4000 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unitfor short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories : Digital energy meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3 Nos. 4000/5 amps 15VA CTs.3 Nos. phase indicating lights with control MCB’s.Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set24 V DC Shunt trip coil. - 1 Set240 V under voltage release. - 1 SetAuto-manual / test selector / switch - 1 SetBreaker control switch - 1 SetAuxiliary contacts required fornecessary interlocking of breakers. Bus Bars 5000 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves - 1 Set. Outgoing : 2 No. 4000 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification. 1 No. 2500 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification. 1 No. 1600 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification.400 amps TP+N MCCB.- 4 No., 250 amps TP+N MCCB.- 1 No., 100 amps TP+N MCCB.- 3 No.SPARE FEEDERS :- 1 No. 2000 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and/OFF/Trip & shunt trip coil etc. as per specification. 400 amps TP+N MCCB.- 1 No., 250 amps TP+N MCCB.- 1 No. Notes :All outgoing feeders except capacitor shall have suitable range of followings . All outgoing feeder shall have digital electronic energy meter ( EM 6438 of conzerv make or equivalent ) with suitable no. of CT,s and RS 485 port . Interlocking of all incoming air circuit breakers/bus coupler shall be through PLC comprising suitable nos. digital inputs (24 VDC) and output (Relay), Wiring with space heater, humidistat and control MCB’s shall be provided all vertical sections of main LT panel. Suitable danger board shall be provided. All bus bar section / backside panels shall have pad locking facility and hinged type door. 2500/1250/5A,15VA,CL-1.0 CTs shall be provided in the incommer of transformer for APFC relay of capacitor panel. All incoming / outgoing air circuit breakers shall be suitable for minimum 50 kA breaking capacity. 9 W fitting with CFL / LED lamp, switch shall be provided in each vertical section. Incoming breakers shall have suitable provision for busduct connection.. All Electronic Energy meter shall be pre wired for BMS connection upto central point within the panel with sheilded cable. MLTP-I as described above.
656MLTP-II : Incoming-I From 2500kVA Transformer-03):4000amps 4 pole electrically operated manually drawout type air circuit breaker, with ON / OFF / TRIP indicating lamps with control MCB’s, shunt trip, U/V release breaker control switch etc complete as per specs and SLD. - 1 Set. Digital electronic energy multi function meter(conzerve – EM 6400 with RS-485 or equivalent) with inbuilt selector switch and 4000/5 Amps 15 VA, CL 1 CTs . - 1 SetDigital VAF meter with 1 Nos. 4000/5 amps 15VA CTs with inbuilt slector switchPhase indicating light shall be protected by 2 amps MCB’s. -1 SetsON / OFFindicating lights with control MCB’s. - 1 Set.Under voltage release - 1 SetAuto-manual / test selector / switch - 1 SetAuxiliary contacts required for necessary interlocking of breakers.Temprature scanner,Surge Protection Device Type -1, spark gap type fpr 10/350µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 40KA per mode. Incoming-II (From DG Synchronizing Panel)4000 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unitfor short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories : Digital energy meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3 Nos. 4000/5 amps 15VA CTs., 3 Nos. phase indicating lights with control MCB’s., Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set, 24 V DC Shunt trip coil. - 1 Set, 240 V under voltage release. - 1 Set, Auto-manual / test selector / switch - 1 Set, Breaker control switch - 1 Set, Auxiliary contacts required fornecessary interlocking of breakers. Incoming-III From STAND BY TXFR PANEL: 4000amps 4 pole electrically operated manually drawout type air circuit breaker, with ON / OFF / TRIP indicating lamps with control MCB’s, shunt trip, U/V release breaker control switch etc complete as per specs and SLD. - 1 Set., Digital electronic energy multi function meter(conzerve – EM 6400 with RS-485 or equivalent) with inbuilt selector switch and 4000/5 Amps 15 VA, CL 1 CTs . - 1 Set, Digital VAF meter with 1 Nos. 4000/5 amps 15VA CTs with inbuilt slector switch, Phase indicating light shall be protected by 2 amps MCB’s. -1 Sets, ON / OFFindicating lights with control MCB’s. - 1 Set., Under voltage release - 1 Set, Auto-manual / test selector / switch - 1 Set, Auxiliary contacts required for necessary interlocking of breakers., Temprature scanner, Surge Protection Device Type -1, spark gap type fpr 10/350µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 40KA per mode. Bus Bars : 5000 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves - 1 Set. Outgoing 2 No. 4000 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification., 1 No. 2500 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification., 1 No. 1600 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification., 400 amps TP+N MCCB.- 4No., 100 amps TP+N MCCB.- 3 No.,SPARE FEEDERS :- 1 No. 2000 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification., 400 amps TP+N MCCB.- 1 No., 250 amps TP+N MCCB.- 1 No., 160 amps TP+N MCCB.- 1 No. Notes : All outgoing feeders except capacitor shall have suitable range of followings , All outgoing feeder shall have digital electronic energy meter ( EM 6438 of conzerv make or equivalent ) with suitable no. of CT,s and RS 485 port ., Interlocking of all incoming air circuit breakers/bus coupler shall be through PLC comprising suitable nos. digital inputs (24 VDC) and output (Relay), Wiring with space heater, humidistat and control MCB’s shall be provided all vertical sections of main LT panel., Suitable danger board shall be provided., All bus bar section / backside panels shall have pad locking facility and hinged type door., 2500/1250/5A,15VA,CL-1.0 CTs shall be provided in the incommer of transformer for APFC relay of capacitor panel., All incoming / outgoing air circuit breakers shall be suitable for minimum 50 kA breaking capacity., 9 W fitting with CFL / LED lamp, switch shall be provided in each vertical section., Incoming breakers shall have suitable provision for busduct connection..,All Electronic Energy meter shall be pre wired for BMS connection upto central point within the panel with sheilded cable. MTPL-II as described above.
657Design, fabrication, assembling, wiring, supply, installation, testing and commissioning of Synchronizing panel and DG Aux. Panel fabricated out of 14 gauge CRCA sheet steel in cubiclecompartmentised free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel `T’ section and / or flats wherever necessary. 3 mm thick cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before powder coating as per specification and final approved shade. 2 Nos. earthing terminals shall be provided for all panels. Panels shall be suitable for 415 V, 3 phase, 4 wire, 50 HZ supply system. Lifting hooks shall also be provided in all panels. Approval shall be taken for each panel in the form of shop drawings before fabrication. Galvanised hardwares with zinc passivation shall be used in fabrication of panels. ( DG sync panel shall be extensible type ), Fire Suppression system in panel as per NBC 2016 SECTION-I : Incoming (From 2 No. 1800kVA DG Set) :Incoming for 2 No. 1800 KVA DG sets each comprises the following and as per single line diagram.2 No. 3200 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unitfor short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories :Digital energy meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3 Nos. 3200/5 amps 15VA CTs.Battery charger with voltmeter of range 0-50 volts and ammeter of range 0-50 amps for trickle and boost charging.3 Nos. phase indicating lights with control MCB’s.Excitor field DC voltmeter and ammeter.Breaker control switch.Differential protection relay with PS class CT’s on both side. ( 3 Nos. L & T SC14S )Master trip relay.Trip circuit supervision relay.24 V DC shunt trip.Emergency stop push button.Selector switch for Auto / Manual / TestSelector switch for engine control OFF/ON.;Five push buttons – start, stop, reset, test and accept.Three indicating lamps “load on set’, ‘Load on Mains’ and “ Set fail to start’.12 Window alarm annunciators panel with hooter, push buttons, aux. Contactors etc as required as per specification.Temperature scanner, Bus Bars4000 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves - 1 Set.Outgoing1 No. 4000 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification.Bus Coupler: Breaker 3200amps 4 pole electrically operated manually drawout type air circuit breaker, with ON / OFF / TRIP indicating lamps with control MCB’s, shunt trip, U/V release breaker control switch etc complete as per specs and SLD. - 1 Set.SECTION-II:Incoming (From 2 No. 1800kVA DG Set) : Incoming for 2 No. 1800 KVA DG sets each comprises the following and as per single line diagram.2 No. 3200 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unitfor short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories :Digital energy meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3 Nos. 3200/5 amps 15VA CTs.Battery charger with voltmeter of range 0-50 volts and ammeter of range 0-50 amps for trickle and boost charging.3 Nos. phase indicating lights with controlCB’s.Excitor field DC voltmeter and ammeter.Breaker control switch.Differential protection relay with PS class CT’s on both side. ( 3 Nos. L & T SC14S )Master trip relay.Trip circuit supervision relay.24 V DC shunt trip.Emergency stop push button.Selector switch for Auto / Manual / TestSelector switch for engine control OFF/ON. Five push buttons – start, stop, reset, test and accept. Three indicating lamps “load on set’, ‘Load on Mains’ and “ Set fail to start’.12 Window alarm annunciators panel with hooter, push buttons, aux. Contactors etc as required as per specification. Temperature scanner, Bus Bars : 4000 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves - 1 Set. Outgoing : 1 No. 4000 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification.1 No. 250 amp 4 P MCCB Bus Coupler: Breaker: 3200amps 4 pole electrically operated manually drawout type air circuit breaker, with ON / OFF / TRIP indicating lamps with control MCB’s, shunt trip, U/V release breaker control switch etc complete as per specs and SLD. - 1 Set.SECTION-III : Incoming (From 2 No. 1800kVA DG Set For Future) Incoming for 2 No. 1800 KVA DG sets each comprises the following and as per single line diagram. 2 No. 3200 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unitfor short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories : Digital energy meter (conzerve – EM 6400 with RS-485 or equivalent) of accuracy class-I, with 3 Nos. 3200/5 amps 15VA CTs., Battery charger with voltmeter of range 0-50 volts and ammeter of range 0-50 amps for trickle and boost charging., 3 Nos. phase indicating lights with control MCB’s., Excitor field DC voltmeter and ammeter., Breaker control switch., Differential protection relay with PS class CT’s on both side. ( 3 Nos. L & T SC14S ), Master trip relay. Trip circuit supervision relay., 24 V DC shunt trip., Emergency stop push button., Selector switch for Auto / Manual / Test, Selector switch for engine control OFF/ON., Five push buttons – start, stop, reset, test and accept., Three indicating lamps “load on set’, ‘Load on Mains’ and “ Set fail to start’., 12 Window alarm annunciators panel with hooter, push buttons, aux. Contactors etc as required as per specification., Temperature scanner, Bus Bars : 4000 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves - 1 Set. Outgoing : 1 No. 4000 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification. 1 No. 250 amp 4 P MCCB Notes :All breakers shall be electrically interlockedasper schematic diagram, All ACB’s/MCCB’s shall be suitable for 65 kA breaking capacity., PLC for load management , interlocking , DG auxiliary and supervision., 2 kVA UPS for 30 MinutesBackup for control wiring. Auto starting / Auto synchronizing / Auto loadbalancing and auto load management panel for 6 No. DG Sets as described above
658SOLAR PANEL : Incoming-I (From Solar System) 2 No. 400 amps TPN MCCB with contactor & ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 400/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set, Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 630 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing : 1 No. 125 amp TP+N MCCB - 1No., 63 Amps 4P MCB - 11 No., Spare MCCB’s/MCB of the following : 1 No. 125 amp TP+N MCCB - 1No., 63 Amps 4P MCB - 1 No., 40 Amps 4P MCB - 2 No. Notes:-All MCCB"s shall be of 50 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. Solar Panel described as above
659UPS I/P PANEL-01 & 02 : Incoming : 4000 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unitfor short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories : Digital electronic energy multi function meter(conzerve – EM 6400 with RS-485 or equivalent) with inbuilt selector switch and 4000/5 Amps 15 VA, CL 1 CTs . - 1 Set,Digital VAF meter with 1 Nos. 4000/5 amps 15VA CTs with inbuilt slector switch,Phase indicating light shall be protected by 2 amps MCB’s. -1 Sets,ON / OFFindicating lights with control MCB’s. - 1 Set.,Under voltage release - 1 Set,Auto-manual / test selector / switch - 1 Set,Auxiliary contacts required for necessary interlocking of breakers.,Temprature scanner,Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars :5000 amps TPN Aluminium bus bars with colour coded heat shrinkable insulating sleeves - 1 Set. Outgoing : 2 No. 2000 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification. Spare MCCB’s/MCB of the following : 1 No. 2000 Amps4P manually operatedfully drawouttypeair circuit breaker with built in microprocessor based release unitfor short circuit, over current and earth fault protection with adjustable setting and ON/OFF/Trip & shunt trip coil etc. as per specification. Notes:- All MCCB"s shall be of 50 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. UPS I/P Panel-01 & 02 described as above
660PAHU PANEL-01 & 02 : Incoming : 1 No. 400 amps TPN MCCB with ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 400/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set, Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 630 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing : 40 Amps 4P MCB - 26 No., Spare MCCB’s/MCB of the following : 40 Amps 4P MCB - 3 No. Notes:- All MCCB"s shall be of 35 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. PAHU Panel-01 & 02 described as above
661UPS I/P PANEL-03 Incoming : 2 No. 400 amps TPN MCCB with ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 400/5 Amps 15 VA, Phase indicating light shall be protected by 2 Amps SPMCB"s 1SetCL 1 CTs . - 1 Set,Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set, Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 630 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing : 250 amps TP+N MCCB.- 2 No. Spare MCCB’s/MCB of the following : 250 amps TP+N MCCB.- 2 No. Notes:-All MCCB"s shall be of 50 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. UPS I/P PANEL-03 described as above
662UPS I/P PANEL- 04 : Incoming : 2 No. 400 amps TPN MCCB with ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 400/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set, Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 630 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing:400 amps TP+N MCCB.- 2 No. Spare MCCB’s/MCB of the following : 400 amps TP+N MCCB.- 2 No. Notes:- All MCCB"s shall be of 50 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. UPS I/P PANEL- 04 described as above
663UPS O/P PANEL-03 : Incoming : 2 No. 250 amps TPN MCCB with contactor & ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 250/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 400 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing : 125 amps TPN MCCB.- 1 No., Spare MCCB’s/MCB of the following : 125 amps TPN MCCB.- 2 No. Notes:- All MCCB"s shall be of 50 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. UPS O/P Panel-03 described as above
664UPS O/P PANEL-04 Incoming : 2 No. 400 amps TPN MCCB with contactor & ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 400/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 630 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing : 400 amps TPN MCCB.- 2 No. Spare MCCB’s/MCB of the following : 125 amps TPN MCCB.- 1 No. Notes:- All MCCB"s shall be of 50 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. UPS O/P Panel- 04 described as above
665PAHU PANEL-03 Incoming : 1 No. 125 amps TPN MCCB with ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 125/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set, Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 160 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing :40 Amps 4P MCB - 18 No., Spare MCCB’s/MCB of the following :63 Amps 4P MCB - 2 No., 40 Amps 4P MCB - 2 No. Notes:-All MCCB"s shall be of 50 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. PAHU Panel-03 described as above
666HVAC VENTILATION PANEL Incoming (SECTION-01):1 No. 100 amps TPN MCCB with contactor & ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter (conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 100/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars :160 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing : 40 Amps 4P MCB - 6 No. Spare MCCB’s/MCB of the following : 40 Amps 4P MCB - 4 No. Bus Coupler: Breaker - 100amps 4 pole contactor, with ON / OFF / TRIP indicating lamps with control MCB’s etc complete as per specs and SLD. - 1 Set. Incoming (SECTION-02) - 1 No. 100 amps TPN MCCB with contactor & ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter (conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 100/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars :160 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing : 40 Amps 4P MCB - 12 No. Spare MCCB’s/MCB of the following : 40 Amps 4P MCB - 4 No. Notes:- All MCCB"s shall be of 35 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. HVAC Vantilation Panel described as above
667LIFT PANEL Incoming : 2 No. 100 amps TPN MCCB with contactor ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 100/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 125 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing :63 Amps 4P MCB - 2 No., 40 Amps 4P MCB - 2 No., 32 Amps DP MCB - 1 No. Spare MCCB’s/MCB of the following : 63 Amps 4P MCB - 1 No., 40 Amps 4P MCB - 1 No., 32 Amps DP MCB - 2 No. Notes:- All MCCB"s shall be of 35 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. Lift Panel described as above
668UPS PANEL (LIGHTING & SECURITY SYSTEM) : Incoming:1 No. 125 amps TPN MCCB with ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 125/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars :160 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing:63 Amps 4P MCB - 5 No., 40 Amps 4P MCB - 1 No., 40 Amps DP MCB - 4 No. Spare MCCB’s/MCB of the following : 63 Amps 4P MCB - 1 No., 40 Amps 4P MCB - 1 No., 40 Amps DP MCB - 2 No. Notes:-All MCCB"s shall be of 25 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. UPS Panel (Lighting & Security System) described as above
669AHU PANEL-01 FOR OFFICE AREA (LHS) : Incoming : 1 No. 100 amps TPN MCCB with ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 100/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 160 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing : 40 Amps 4P MCB - 9 No. Spare MCCB’s/MCB of the following : 40 Amps 4P MCB - 4 No. Notes:- All MCCB"s shall be of 25 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. AHU Panel For Office Area (LHS) described as above
670AHU PANEL-02 FOR OFFICE AREA (RHS) : Incoming : 1 No. 100 amps TPN MCCB with ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 100/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 160 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing : 40 Amps 4P MCB - 15 No. Spare MCCB’s/MCB of the following : 40 Amps 4P MCB - 4 No. Notes:- All MCCB"s shall be of 25 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. AHU Panel-02 For Office Area (RHS) described as above
671PLUMBING PANEL : Incoming : 1 No. 100 amps TPN MCCB with ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 100/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 160 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing : 4 No. 40 Amp TP MPCB with 5 HP DOL starter and outgoing feeder to pumps. Compartment shall contain CT operated digital electronic ammeters of 0-40 amps range with built in selector switch with CT’s,Auto/Manual selector switch and three indicating lamp and PB’s with MCB’s for ON/OFF / TRIP status of motor., 6 No. 40 Amp TP MPCB with 3 HP DOL starter and outgoing feeder to pumps. Compartment shall contain CT operated digital electronic ammeters of 0-40 amps range with built in selector switch with CT’s,Auto/Manual selector switch and three indicating lamp and PB’s with MCB’s for ON/OFF / TRIP status of motor. Spare MCCB’s/MCB of the following :63 Amps 4P MCB - 2 No., 40 Amps 4P MCB - 2 No. Notes:- All MCCB"s shall be of 25 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. Plumbing Panel described as above
672FIRE-FIGHTING PANEL : Incoming : 2 No. 250 amps TPN MCCB with contactor & ON/OFF indicating lamps & with the following accessories etc., Digital electronic energy multi function meter (conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 250/5 Amps 15 VA, CL 1 CTs . - 1 Set, Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set, Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 400 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing :2 No. 160 Amp TP MCCB with 75 HP DOL starter and outgoing feeder to pumps. Compartment shall contain CT operated digital electronic ammeters of 0-160 amps range with built in selector switch with CT’s,Auto/Manual selector switch and three indicating lamp and PB’s with MCB’s for ON/OFF / TRIP status of motor.,1 No. 63 Amp TP MPCB with 12.5 HP DOL starter and outgoing feeder to pumps. Compartment shall contain CT operated digital electronic ammeters of 0-63 amps range with built in selector switch with CT’s,Auto/Manual selector switch and three indicating lamp and PB’s with MCB’s for ON/OFF / TRIP status of motor. Spare MCCB’s/MCB of the following :160 Amps TP+N MCCB - 2 No., 63 Amps 4P MCB - 1 No. Notes:-All MCCB"s shall be of 25 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. Plumbing Panel described as above
673UPS O/P PANEL-01 & 02 : Incoming / Outgoing :2 No. 2000 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unitfor short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories : Digital electronic energy multi function meter (conzerve – EM 6400 with RS-485 or equivalent) with inbuilt selector switch and 2000/5 Amps 15 VA, CL 1 CTs . - 1 Set, Digital VAF meter with 1 Nos. 2000/5 amps 15VA CTs with inbuilt slector switch,Phase indicating light shall be protected by 2 amps MCB’s. -1 Sets,ON / OFFindicating lights with control MCB’s. - 1 Set.,Under voltage release - 1 Set,Auto-manual / test selector / switch - 1 Set,Temprature scanner Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Notes:- All MCCB"s shall be of 35 KA (Ics) breaking capacity., All MCB"s shall be of 10 KA breaking capacity. UPS O/P Panel-01 & 02 described as above
674CHILLER PANEL-01 & 02 (FOR CHILLED WATER PUMP MOTOR) : Incoming :1 No. 400 amps TPN MCCB with ON/OFF indicating lamps & with the following accessories etc.,Digital electronic energy multi function meter(conzerve – EM 6438 with RS-485 or equivalent) with inbuilt selector switch and 400/5 Amps 15 VA, CL 1 CTs . - 1 Set,Phase indicating light shall be protected by 2 Amps SPMCB"s 1Set,Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth Bus Bars : 630 Amps TPN Aluminiunbus bars with heat coloured shrinkable insulation sleeve. - 1 Set Outgoing : 100 Amps TP+N MCCB - 5 No. Spare MCCB’s/MCB of the following : 100 Amps TP+N MCCB - 2 No. Notes:- All MCCB"s shall be of 25 KA (Ics) breaking capacity.,All MCB"s shall be of 10 KA breaking capacity. Chiller Panel-01 & 02 described as above
675ATS PANEL (FOR CHILLED WATER PUMP MOTOR) : 100 amps 4P wall mounted ATS in MS encloser suitable for the connection for 2No. 3.5C X 35sq.mm. aluminium cable as incoming & 1No. 3.5C X 35sq.mm. aluminium cable as outgoing.
676DC ISOLATION (FOR PDU-1A, 1B, 2A & 2B) : Incoming / Outgoing : 1 No. 2000 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unitfor short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories : Digital electronic energy multi function meter (conzerve – EM 6400 with RS-485 or equivalent) with inbuilt selector switch and 2000/5 Amps 15 VA, CL 1 CTs . - 1 Set, Digital VAF meter with 1 Nos. 2000/5 amps 15VA CTs with inbuilt slector switch,Phase indicating light shall be protected by 2 amps MCB’s. -1 Sets,ON / OFFindicating lights with control MCB’s. - 1 Set., Under voltage release - 1 Set, Auto-manual / test selector / switch - 1 Set, Temprature scanner Surge Protection Device Type -2, MOV type fpr 8/20µs surge, 3 Nos line to earth and 1 No neutral to earth (3+1) mode with minimum discharge capacity of 20KA per mode.and 40KA for Neutral to earth. Isolation Transformer & TVSS are part of PDU, branch / Server level monitoring is through IPDU. Notes:- All MCCB"s shall be of 25 KA (Ics) breaking capacity. ,All MCB"s shall be of 10 KA breaking capacity. DC Isolation described as above
677800 kVAR CAPACITOR AUTOMATIC CONTROL PANEL: Incoming : 1600 amps 4 pole electrically operated manually draw out type air circuit breaker with microprocessor release unitfor short circuit, over current and earth fault protection with adjustable setting as per specification and with following accessories : 96 x 96 mm sq. 0-500 Volt digital voltmeter with selector switch ,96 x 96 mm sq. 0-1600A digital Ampere meter with selector switch ,Phase indicating light shall be protected by 2 Amps SP MCB’s.- 3 Set,Breaker ON / OFF / TRIP indicating lights with control MCB’s. - 1 Set,Power factor compensating relay (including power factor meter) in 14 steps for automatic cut off or add on capacitor units to keep the power factor at 0.99 with variation of loads. All associated auxiliary contactors / relays / timer / auto manual selector switches to be provided -1 Set. Bus Bars : 2000 amps TPN Aluminium bus bars with coloured heat Shrinkable insulated sleeves.- 1 set Outgoings -I : Outgoing feeders consisting of following accessories. 100 amps TPN MCCB-4 Sets,100 amps or capacitor duty 525 volts 50Hzcontactors. -4 Sets,“ON” /”OFF”push buttons and indicating lamps. -4 Sets,25 KVAR capacitor unit with7 % detune filters with thyristor switch moduleas specified - 4 Sets Outgoings -II :Outgoing feeders consisting of following accessories. 160 amps TPN MCCB-4 Set,160 amps or capacitor duty 525 volts 50Hzcontactors. -4 Set,“ON” /”OFF”push buttons and indicating lamps. -4 Set,50 KVAR capacitor unit with 7 % detune filters with thyristor switch module as specified -4 Set Outgoings -III : Outgoing feeders consisting of following accessories. 200 amps TPN MCCB-4 Set,200 amps or capacitor duty 525 volts 50Hzcontactors. -4 Set,“ON” /”OFF”push buttons and indicating lamps. -4 Set,75 KVAR capacitor unit with 7 % detune filters with thyristor switch module as specified -4 Set Outgoings -IV : Outgoing feeders consisting of following accessories. 250 amps TPN MCCB-2 Set, 250 amps or capacitor duty 525 volts 50Hzcontactors. -2 Set, “ON” /”OFF”push buttons and indicating lamps. -2 Set, 100 KVAR capacitor unit with 7 % detune filters with thyristor switch module as specified -2 Set Notes : All ACB / MCCB"s shall be of65 KA (Ics) breaking capacity., Fast semiconductr fuses shall be used for protection of Thyristor Switch Module, Discharge resistors shall be used for fast discharging of capacitors., High speed semiconductor Fuses of suitable rating shall be used as a secondary protection in each step. Capacitor automatic control panel (800 KVAR) as described above.
67833KV HT PANEL BOARD (FOUR BREAKER) (One incomers, and Three outgoings) Design,manufacture,supply, installation, testingandcommissioningof630Amps.,33KV,26.24KA breakingcapacity (1500 MVA)VCB panel board fabricatedout of2mmsheetsteel, dusttight, vermin proof, totally enclosed & fully interlocked , IP 4X protection, cubical type,floor mounting,extensible on both sides,suitable for indoor operation at 33 KV, 3 phase,50 Hz,AC supply complete with rack in - rack out mechanisms,switches, plugs & sockets and all required accessories, cable termation box at back with bottom cable entry for cable size upto 3 core 300 Sq.mm.armoured cable for each section, internalcopperwiring,earthterminals,paintingetc.asrequired,asperTechnincalspecifications& SLD with the following equipped switch gears and accessories complete in all respect. Incomers - 1 Set. Each feeder shall consist of : 630 Amps.,33KV horizontal draw out type VCB with motorized spring charge mechanism and required safty switchgears complete., 33 KV / 110 voltPT of class 1.0 accurancy & 100 VA burden.,Set ofdual coredual ratio CTsof80/160/5/5 Amps.of 15 VA burden and accurancy class1.0 for metering and class 5 P 10 for protection.,96mm x 96mm type 630 Amp ammeter Digital type with ASS,96mm x 96mm square Digital type Voltmeter protected by HRC fuses / MCBs with inbuilt VSS,Digital Trivector Meter (Smart Controller) having 30 days memory, Class 0.5 with MDI & RS 485 port.,Frequency meter,Set of LED indication lamp protected by MCB for RYB Phases, trip, ON & OFF, spring charge, auto trip / trip healthy of breaker complete.,Master trip& trip circuit supervision relay, Antipumping Relay, Auxiliary Relay etc.,Limit Switch for tests and service position, circuit breaker control switch (T/N/C).,Trip coil operation at 24 Volts DC through battery bank.,Limit switch for tests & service position, circuit breaker control switch (T/N/C),Trip / Closing coil operation at 24 Volts DC through battery bank Busbar : 630A TP Copper bus bar OUT GOING- 3 Sets.Each feeder shall consist of : 630 Amps.,33KV horizontal draw out type VCB with motorized spring charge mechanism and required safty switchgears complete.,Set of dual coreCTs of 25- 50/ 5 Amps.CT for 630 KVA TRF, of15VAburden&accurancy class1.0formeteringand class 5 P 10 for protection.,96mm x 96mm square Digital Ammeter with inbuilt ASS,MicroprocessorbasedfeederprotectionnumericalrelaywithadjustableO/L,E/Fandshortcircuit protection with communication port. (O/L Setting 50-200% and E/F setting 20-80%),Set of LED indication lamp protected by MCB for RYB Phases, trip, ON & OFF, spring charge, auto trip / trip healthy of breaker complete.,Annunciator window (with minimum6 window) for feeder alarm / tripping annunciations with electronic hooter.,Master trip& trip circuit supervision relay, Antipumping Relay, Auxiliary Relaycomplete.,Limit switch for tests & service position, circuit breaker control switch (T/N/C),Trip and closed coil operation at 24 Volts DC through Ppower pack HT PANEL BOARD (TOTAL OF A TO CABOVE)
679SUB HEAD-LIGHTNING PROTECTION : Air Terminal (Horizontal) : SITC of 8 mm Aluminum Round Conductor complete as specified in drawing and directed by Engineer & Meets the requirements of (IS / IEC 62305).
680SITC of aluminium ferrule for joint 8 mm Aluminum Round Conductor complete as specified in drawing and directed by Engineer & Meets the requirements of (IS / IEC 62305).
681SITC of seam sheet conductor holder all as specified in drawing and directed by Engineer, made of SS 304.
682SITC of sheet conductor holder down conductor all as specified in drawing and directed by Engineer, made of SS 304.
683SITC of Nylon Conductor Holder for down conductor on brick wall having hole Ø 7 mm all as specified in drawing and directed by Engineer, made of SS 304.
684SITC of SS Cross connector for 8 mm round conductor (At every corrsing of conductor) as specified in drawing and directed by Engineer tested as per IEC 62561 for IS/EC 62305 & NBC 2016 requiement
685SITC ofExpansion Pcswith 2 nos ferrule (at every 20 metre)8mm Aluminimum round conductor and shape specified by manufacturer as specified in drawing and directed by Engineer.
686SITC of stainless steel Test Joint, suitable for connect 8 mm / 10 mm round to round conductor assembled in Polycarbonate Enclosureas specified in drawing and directed by Engineer
687SITC of Lightnig counter - LCD screen shows the number of lightning strikes, hour and date of lightning eventsButtons enable TIME/DATE setting and log viewing. Replaceable battery, working life minimum five years, meet the requirements for IS/IEC 62305 and IEC 62561-2.Tested for Electrical ,Mechanical and Chemical as per IEC 62561.
688SITC of Lightning Management system for prediction with both audio and visual annunciation integrated with online monitoringincluding all accessories essential to establish communication with the building managemnent system / SCADA.SITC of E1/E2 Filter as per specification. a) 100 A, 4 Pole
689b) 125 A, 3 Pole
690c) 125 A, 4 Pole
691d) 200 A, 3 Pole
692e) 200 A, 4 Pole
693SITC of 10mm dia copper bonded steel solid conductor for ring Earthing, Conductor shall be minim 100 micron copper bonded and meet the requirements of IS/ IEC 62305 and IEC 62561-2
694SITC of maintenance free Copper coated earth rod of 3 metre electrode having diameter of 17.2 mm with copper coating with rod to tape clamp for terminating flat conductor. Earth enhancing mineral compound 25 kg(with 10 kg of compound as per clause 14.5(d) and 15kg of compound as per clasue 14.5 (b) of IEEE 80:2013) which is not required frequent addition of water. Heavy dduty earth electrode inspection chambershould have minium top dia of 250 mm in cylinderical shape . The systems is conforming to IEC 60364, IEC 62561, IEC 62305, IS 2309 & IS 3043
695SITC of Remote Monitoring of Earthing system as per specificationn of each earth pits comprising of suitable numberes of sensor, remote terminal units and peripheral command center including all accessories essential to establish communication with the building managemnent system / SCADA .
696SITC of 10 mm dia 1000 mm longAl. vertical interception rod with mounting accessories on roof sheet / solar structure .
697Passenger Lift :- Supplying, installation, testing & commissioning of 15 Passenger (1020 Kg), Gearless type,Machne room-less passenger lift of any of M/s OTIS, M/s Kone, M/s Thyssenkrupp, M/s Schindler, Liftsmake having contract speed 1.5 MPS serving different floors in the lift shaft as per detailed specifications as under and additional details given in schedule of technical particulars. Provisions of General CPWD specifications for lift works are to be followed. Speed- 1.5 Metre/Sec.,Floor - G + 6 = 7 stops,Travel-30.0 Mtr. (Approx.),Stop & Opening - 7 Stops & 7 Openings (Front side opning),Type and Position of Machinery- Gear type, with Machine Room ,Controller- Micro processer based AC variable voltage & variable frequency Control,Automatic rescue device complete with dry maintenace free batteries as required.,Operation-Microprocessor based Simplex Full Collective with / without attendant.,Power -415 V ±10%, 3 Phase, 50 Hz.,Type or Design of Lift Car -Stainless steel scratch resistant .,Car door-Power operated centre opening horizontal sliding stainless steel Scratch resistant ,Door operation- Full Height Infra-red cross-multi beam,Landing doors -Centre opening, stainless steel scratch resistantat all floors. It must be fire-rated for minimum 1-Hrs and supplier must provide the certiifcate for the same alongwith material supply.,Car operating Panel / Landing operating panel-Car operating panel with braile symbol luminous buttons and braile illuminated push buttons on all landing in Stainless Steel Mirror finish.,Hand rail- Shall be SS finish fixed above 900mm from the car-floor level on rear-wall or side wall.,Voice announcement system - In car to announce the position of the elevetor in hoist way as the car passes or stop at a floor served by the elevator,Intercom system- 3-way intercom,Clear Opening of Doors- 900mm x 2400mm (Wide x Height),Lift Car inside size - 1300 x 2400 ( Width x depth). ,Size of Lift Well -2200 x 2500 mm(Width x Depth),Entrance-900mm
698Passenger/ Service Lift :- Supplying, installation, testing & commissioning of Passenger cum Service (3000 Kg), Gearless type,Machne room-less passenger lift of any of M/s OTIS, M/s Kone, M/s Thyssenkrupp, M/s Schindler, Liftsmake having contract speed 1.5 MPS serving different floors in the lift shaft as per detailed specifications as under and additional details given in schedule of technical particulars. Provisions of General CPWD specifications for lift works are to be followed. Speed- 1.5 Metre/Sec., Floor - G + 6 = 7 stops,Travel-30.0 Mtr. (Approx.),Stop & Opening - 7 Stops & 7 Openings (Front & Back side opning),Type and Position of Machinery- Gear type, with Machine Room ,Controller- Micro processer based AC variable voltage & variable frequency Control,Automatic rescue device complete with dry maintenace free batteries as required.,Operation-Microprocessor based Simplex Full Collective with / without attendant.,Power -415 V ±10%, 3 Phase, 50 Hz.,Type or Design of Lift Car -Stainless steel scratch resistant .,Car door-Power operated centre opening horizontal sliding stainless steel Scratch resistant ,Door operation- Full Height Infra-red cross-multi beam ,Landing doors -Centre opening, stainless steel scratch resistantat all floors. It must be fire-rated for minimum 1-Hrs and supplier must provide the certiifcate for the same alongwith material supply.,Car operating Panel / Landing operating panel-Car operating panel with braile symbol luminous buttons and braile illuminated push buttons on all landing in Stainless Steel Mirror finish.,Hand rail- Shall be SS finish fixed above 900mm from the car-floor level on rear-wall or side wall.,Voice announcement system - In car to announce the position of the elevetor in hoist way as the car passes or stop at a floor served by the elevator,Intercom system- 3-way intercom,Clear Opening of Doors- 1500mm x 2400mm (Wide x Height),Lift Car inside size - 1600mm x 3550mm ( Width x depth). ,Size of Lift Well -3000 x 3550 mm(Width x Depth),Entrance-1500mm (Back) & 1500mm (Front)
699HSD Tank :-Supply, Installation, Testing & Commissioningof 30 KL capacity mild steel horizontal cylindrical underground HSD tank with shell 6 mm and end plate 8 mm thick suitable for underground installation complete with manhole accessories, fittings, Fuel polisher for input / output piping, piping inside the tank paint with inside surface scrapped clean.Tank will be tested at works under hydrostatic pressure of 5 psi before being painted with two coats of RedOxide Primer as required as per specifications.(Note: As per TIA-942, HSD fuel supply shall be with redundant piping system. Hence Bidder have to considered 2 sources of fuel supply )
700Supply & erection of Flame Proof Roterygear type HSD pump inside the fuel tank yard having mechanical seal complete with all accessories, fixing on M.S. channel including making earthing as required. 110 LPM,Suction head not less than .20 M and total head shall be 50 meter.
701Supply, Installation, testing and commissioning of pump shed (constructed with MS sheet) of required size with proper MS supporting arrangement coated with one coat of primer & two coat of final enamel paint.
702Providing & fixing M.S. seamless’ (heavy duty) pipe & fittings like tees, elbows, junctions, unions, bends, plugs etc.Including a coat of Synthetic enamel paint over two coats of primer complete as required. A)25 mm dia
703B)40 mm dia
704C)50 mm dia
705D)80 mm dia
706Providing & fixing fire safe desighn single peace CS ball valves of the following sizes suitable for pressure of 10 kg/ sqcm complete with all necessary fittings as required. A)25 mm dia
707B)40 mm dia
708C)50 mm dia
709D)80 mm dia
710Providing & fixing G.M./ C S non return valves of the following sizes G.M. suitable for pressure of 10 kg/ sqcm complete with all necessary fittings as required. A)40 mm dia
711B)50 mm dia
712Providing and fixing Y strainer for oil supply line: 50 mm dia
713Supply,Testing and Commissioning of theBucket type strainer. Frefabricated with 4 to 5 mm thick MS Pipe with 8 mm flange and top plate complete with flanges and gasket 150 micron mesh. 80 mm dia
714Providing and fixing flame proof level Switch with High level & low level contact for buffer oil storage tanksincluding wiring, cabling, probes with all other accessories ready for automatic operation of fuel oil pump complete as required.
715Providing & Fixing of 100mm dia Dial type Pressure gauge for seeing motor Pressure.
716Supply and fixing of flow meter for diesel line as required with Flow rate 10.3 to 11 mcu/hr a)50 mm dia.
717b)25 mm dia.
718Providing & fixing of in door type wall mounted MCC control panel for operation of 2 nos. oil transfer pumps complete with FP MCB incomer, metering and outgoing with DOL starters complete with MCB with in-built O/L & SPP protection, suitable contactor, ON/OFF push buttons & indication lamps & control wiring etc. & A/M selector switches etc. The MCC shall have spares,
719Supply & Wiring for day oil tans & buffer tanks automation with 1.5 sq.mm FLEXIBLE copper wire i. as complete as required.
720Supply and installation of Unloading decanting antistatic Hose with high pressure Braided Black, antistatic Rubber Hose Pipe 3 mtrs length, with earthing wire extruded..
721Supply, installation, testing and commissioning of 990 litres capacity day oil storage tank fabricated from 3 mm thick MS plates . Tank shall include 450 mm ID manhole cover, level indicator and flanged connection for inlet, outlet, overflow drain and probe provision for level controller. Tank shall be mounted on 2 m high structure support with access ladder (painted with 2 coats of red oxide primer).
722Supply and erection of canopy type M.S.Structure made out of 40mm medium class M.S.ANGLES25 x 25 x 5 mm angle iron frame work and 14 SWG GI Sheet. Structureshall be grouted in C.C. 1:2:4foundation for hanging 4 Nos. 9litre each fire fightingbucketsincluding providing buckets with twocoats of anticorrosive paints etc. complete as required.
723Providing and fixing fire bucket of 9 lit capacity made of 24 gauge MS sheet on frame.
724CO2 4.5 kg capacity as per IS 2878
725Chemical foam type of 9 litre as per IS: 993
726Dry chemical powder type 5 kg
727Supplying, fixing, 50 liters DCP dry Mechanical foam Fire extinguishers with trolley mounting brackets first filling etc.
728Providing and fixing NO SMOKING & DANGER ZONE sign boards.
7291.8 meter height Fencing with gate as per PESO
730Liasioning work for getting the HSD Yard layout drawing approval and licence / NOC from concern department.
731Survey Design and providing and fixing testing and commissioning of following equipment required for solar power generating system of capacity (dc) Solar Rooftop System with >330Wp PV Modules 120(364*330W)KWp on Normal structure, Poly crystalline & Solar String inverter2*60 KWp or as per design. Balance of the system like: Module Mounting structure G.I./Al, wire, cable, ACDB, DCDB,LA, earthing system, remote monitoring, accessories.
732Super structure 10 feet lower side and upper side as per site
733Supply, erection, testing and commissioning ofMetring cubicle with33 KV PTs 33kV/110V, 33 KV CTs 140/5 5A with trivector meterindoor type as per local Electricity board, getting approvaland calibration as required by the Department. complete etc.
73433 kV RING MAIN UNIT : 2 No.33 KV, 1500 MVA, 50 Hz 3 phase, 630 Amps load break switch as per specifications and with following: MS sheet enclosed cubicle type panel with main aluminium Bus bar rated for 630 A and droppers rated for 630 A,630 Amps electrically operated trip free type SF6 breaker at 47 deg. C ambient.,Breaker control switch.,24 V DC tripping coil.,24 V DC closing coil.,240 V AC spring charging motor.,Set of ON/OFF/TRIP indicating lamps.,Set of Phase indicating lamps. (RYB),Clear lamp for trip circuit health supply.,Digital ammeter & voltmeter with selector switch.,VIP35 relay or equivalent with suitable CT"s.,3 Over current & earth fault IDMT relay range 50 – 200% ,3 Nos. Cast resin CTs of dual ratio 80 – 160/5, CL:1, 5P10, 15VA. ,Suitable space for termination of 1 No. 33 KV, 3 C x 300 sq.mm XLPE cable as incomingand outgoing Note:All protection relays shall be numerical type only.,One separate earthing truckshall be provided as per Technical Specifications. Ring Main Unit described as above
735AV SYSTEM:- Ceiling Microphone tile with 26 or more no. of omni directional microphone, coverage area : 55sq mtr or more, Dante connectivity : dual / redundant, POE enable (qty of microphone will vary as per the mentioned coverage area and built in micorphone), Lighting Indication on all four corner, It should work on open control protocol software andcompitable to monitor with a single sofware for all the microphone in the campus, should come with suspension mount kit etc complete required as per the specifications.
736Wireless digital Handheld Microphone with 18 or more channel, RF output 80mW or more, super cardiod pickup pattern, Frequency range : 1880 to 1930 MHz, Connectivity : RJ-45 (specifications includes single microphone set of transmitter and receiver) etc and complete as required.
737Wireless digital Headset Microphone with 18 or more channel, RF output 80mW or more, Omni-directional pickup pattern, Frequency range : 1880 to 1930 MHz, Connectivity : RJ-45, 256-bit AES Encryption(specifications includes single microphone set of transmitter and receiver) etc and complete as required.
738Wireless digital microphone charger, charging capacity : 4 or more simultaneously with lighting indication, monitoring : LAN / RJ45. Should be from same OEM as of wireless mic etc and complet required as per specifications.
7394.5-inch, 2-way, Full Range, Ceiling-mount loudspeaker. Rated Power - 16Watts, Sensitivity-89 dB SPL, Coverage Angle -140°, Maximum SPL Continuous/Peak-101dB/107dB, Rated Impedance - 8 Ohms. Transformer Tapping - 70V/100V(16, 8, 4,2 watts). Transducer - 4.5-inch Polypropylene cone with butyl rubber surround, Material - Painted ABS polymer Baffle and Power coated steel grille. Safety rating - UL1480, UL2043. Mounting rails and C-Ring for ceiling tile included.
740Quad channel class-D Energy Star rated amplifier. Wattage per Channel - 100 watts/channel into Low-Z loads (8O/4O). Four channels shall also be bridged in pairs, each pair providing up to 200 watts rms into 4/8 ohms andup to 175watts into 70V/100V. Signal to Noise (A weighted, 20 Hz-20 kHz)->100 dB, Frequency Response-20Hz-20kHz, Input Sensitivity-1.23 Vrms (+4 dBu), Input Impedance->10 kO balanced/unbalanced, Front Panel Indicators-Power, per channel Signal,Protect/Limit,Controls- 4O/8O/70V Bridge Highpass On/100V Bridged Highpass on per channel pair. Shall include all mounting accessories for mounting in half or 1 rack space.
741Digital Signal Processor with 8 Mic/Line inputs, 8 Line outputs and 8 software assignable channels, configurable as Mic/Line Inputs or Line outputs. The processor shall have minimum 16 assignable & routable AEC channels and 16 General Purpose Inputs (GPI) x 16 General Purpose Outputs (GPO) ports. The processor shall have minimum 8x8 Dante channels and shall also support up to 128x128 Network audio channels via Dante or AES67. It shall also support SIP Softphone integration for Audio conferencing and configurable 16x16 USB Audio channels via USB-B ports supporting AV USB Bridging for software or web based conferencing applications. The processor shall also have minimum 24 bit-A/D-D/A converters, 48 kHz Sample rate, Input frequency response of 20 Hz to 20 kHz @ +21dBu, Input dynamic range > 109.5 dB at @ +24 dBu sensitivity. The processor shall support third party device control via Ethernet, RS232 and GPIO and shall have front panel display for control and indicators for device status. Third party device control can also be added as software of hardware to meet the requirement.
742Scripting Engine Software License, Perpetual8x8 Dante License
743UCI Deployment Software License, Perpetual
744Network PTZ Conference camera with Min 20x optical zoom & 60 degree horizontal coverage. HDMI resolutions up to 1080p60. Image rotation controls to allow for inverted mounting using ceiling bracket. Auto exposure, auto focus and auto white balance modes. Low Noise CMOS Image Sensor, S/N Ratio = 55dB. , Video Outputs-HDMI and 3G-SDI,Ethernet-100BaseTX / 1000BaseT. Simultaneous IP Streaming, HDMI and 3G-SDI outputs. Power over Ethernet (PoE, 802.3af). Minimal Illumination: 0.5 lux at F1.8 (AGC On). S/N Ratio = 55dB.Video Resolutions HDMI / SDI:1080p 60/50/30/25. Shall include Wall mounting accessories
7458.0” PoE, IPS Touch Screen Controller with 16 million colors for Table Mounting. Resolution-1280x720, Brightness-400 Nits, Panel Orientation-Vertical / Horizontal,POE- IEEE 802.3af class 3, Aux power PSU-+24VDC @ 0.5A , Tabletop stand included. LAN -1000Mbps full-duplex RJ-45,Universal mounting accessories included. Drag & Drop designing without any programming experience.
746Internet protocol to Serial convertor, the convertor should have LAN RJ45 Connector and RS-232 connector, It should convert control-over-ethernet signal to Serial Commands
74798" UHD Professional Display, 24x7, 3840*2160 (4K UHD), 500nits, 4000:1 Contrast Ratio
748Cable Manager, cable manager should be made of steel or aluminium, it should have connectivity port like HDMI x1, Power x2, LAN x1 or more, Should have top with flip cover complete as required as per specification
749Seamless HDMI Matrix Switcher, the HDMI switcher should have at least 8 HDMI input ports supporting video resolution of up to 1080p or better, it should be consist of at least 8 HDMI output ports supporting video resolution of up to 1080p or better, the switcher shall support routing of any input to any output, it should have LCD Panel to facilitate quick view of input and output routing, the switcher shall have close-to-zero second seamless switching for continuous video streams, real-time switching, and stable signal transmissions, Should have built-in or external videowall layout selection feature, should have built-in scaling engine for video resolution management, should have EDID, HDCP and CEC Support, max data rate of 6.75 Gbps or better, Should be able to control from RJ45 Ethernet port, Serial RS-232 or IR via wireless remote, Shall be Fixed or modular type matrix. Shall support operating Temprature 0 to +45 °C or better.
750HDMI Extender, the extender should transmit HDMI signal totwisted pair/HDBaseT Receiver for HDMI,extends an HDMI connection up to 100m via a single Cat 5e/6/6a, Should transmit up to 1080p signal up to 150m via single Cat 5e/6/6a cable in long reach mode,. Data rate : 10.2 Gbps or higher. Resolution : 4K/UHD or better, HDCP 2.2 or better compliant. Input: 1x HDMI and 1x Twisted Pair output in transmitter and 1x Twisted Pair Input and Output: 1x HDMI in receiver. Should support CEC, complete as required as per specificaitons
751Video Extender Rack Mount Kit for up to 4 Tx/Rx in 1U Space
752HDMI Audio De-embedder, the HDMI Audio de-embedder should extract and convert Audio from HDMI input, it should repeat HDMI signal to up to 15m, should extract audio and output as additional Audio Source, should support digital optical/coaxial audio, should be HDCP Compliant, should support up to 1080p@60 signal, should have maximum Data rate of 6.75Gbps or more, should have 1x HDMI Input and 1x HDMI video output, should support audio output on 2x RCA, 1x Toslink or better complete as required as per specifications.
75315 Meter USB 3.2 Extension Cable, the cable should have data bandwidth of 5Gbps or more, should be backward compatible with USB2.0/1.1 Standards, it should be plug-and-plug cable and no software installation should be required, the cable should be active in nature to ensure high performance output even after extended usage etc complete as requried as per specification
754Twisted Pair CAT6 Cable, the cable should support signal transmission at resolutions up to 4K including digital and analogue data, audio, and video applications, should be atleast 23AWG gauge or better, should support frequency up to 400 MHz or better, should meet performance required set by HDBaseT Alliance for AV Signal transmission over long distance, should have compliance like : RoHS, UL 1685 (CM Rated),spool of 300m etc complete as required as per specifications
75516 Port Gigabit Switch with 8 or more PoE Ports
756Wireless Access Point
75742U 19" AV equipment Rack with all required accessories
758Bulk Cable and connectors
759Implementation servicesincludes - Design, Engineering,Labour, Installation, Testing and commissioning and training to users at the site to set the system up and operate the same.
760OmniPCX Enterprise Crystal hardware (AA15) : VoIP access board INT-IP3 board including one 10/100/1000 Base-T connecting card
761OmniPCX Enterprise basic package crystal hardware without Appliance Server, INT-IP3 board, ACT 28
762NDDI2-2 board analog trunk (8)
763CLIPIA card class services option (4 circuits)
764GPA2 board : conf 29, Dynamic + Static (4 language) Voice Guide
765NPRAE-2 board 2 x T2 accesses
766e-Z32-2 board, 32 analog interfaces
767e-UA32 board, 32 UA interfaces
76810/100/1000 Base-T connecting card
769ACT28 mounting kit for installation in data cabinet
770PSAL and 48V data cabinet (ACT) connecting kit
771Delivery kit for ACT to be mounted in 19-inch racks
77215 m MDF TY2 96pts DIN cable for PRA, BPRA, PCM (120 ohm) boards
77315 m MDF TY1 64pts DIN cable for UA, Z, NDDI, BRA boards
774Applications (CC11) : OmniVista 8770 release 4.2 software license
775CLIP on Z interface license - 1 user
776DISA service software license
777Automated attendant up to 6 voice guides software license
778Software license for the meet-me conference
779CSTA 500 bypass software license
780Alcatel-Lucent A4645 Voice Messaging software license - 1 user
781OmniVista 8770 Start Pack - Base license
782OmniVista 8770 Start Pack - User license
783Java Runtime Environment support
784User software licenses(CC40) : Alcatel-Lucent OmniPCX Enterprise R12.4 software license
785OmniPCX Enterprise Generic Appliance Server - System virtualization server license
786OmniPCX Enterprise Generic Appliance Server - System virtualization server license for redundancy
787Analog Premium license - 1 user
788IP Premium license - 1 user
789Digital Premium license - 1 user
790OmniPCX Enterprise High Availability service - Base license
791OmniPCX Enterprise High Availability – 1 Business Telephony user license
792OmniPCX Enterprise Release R12.4 software installation
793IP sets (DD15) : Premium Smart display module "s" Moon Grey, 14 programmable keys, clip included
7948068s WW Premium Deskphone Moon Grey, 3,5" 320x240 Color display, Wide Band Corded Confort Handset, Bluetooth 4.1 enabler, Alphabeti c Keyboard, Jack 3,5 mm 4 poles, USB, 10/100/1000 PC Connectivity POE
7959 series terminals (DD17) : 8029s INT Premium Deskphone Moon Grey, Black & White display, white backlight, 4 programmable keys with Led & Paper Label, Handsfree , Comfort handset, Magnetic alphabetic keyboard, Jack 3,5 mm 4 poles
796OEM Software(FF14) : Suse Linux support
797Software Support Services (NN02) : OmniPCX Enterprise SPS
798OmniVista 8770 SPS
799FCA Charges
800Appliance Server (HP DL 20 Gen10)
801FCBC with N+1 Rdundancy & 4 hours battery backup (Dyna 25 Amps with EXIDE batteries)
802Headset for Operator Console
803Windows PC for NMS with 18.5 Inch TFT
80442 U Server Rack with accessories
805Analog Phones with LCD display & CLIP Facility
806Access Control system :- Supply Installation Testing & Commissioning of Intelligent 2 Reader, 2 Door, TCP i/p Controller In proper housing on-board buffer memory of up to 30000 transaction and should have cardholder database of Minimum 50000 per controller, with Secured OSDP, UL-294, UL-1076 & RoHS certified, with on board support for the storage of biometric templates. The controller should be intelligent to take decision in offline mode when communication link is not available On-board Ethernet 10/100Base-T x2 on board port, Firmware stored in flash memory, background download of firmware updates supported. Ethernet Communication - 10BaseT/100Base-TX x2 on board. IO Module 8 inputs & 8 outputs Communication - 2-wire RS-485 3-ports, 2400 to 115K BPS, asynchronous with operating temperature 32 to 158 °F (0 to 70 °C) and humidity - 5 to 85% 0 to 95% RHNC. It should support microSD Card - On-board memory with no external add-on memory cards. Credential Number size - up to 128-bits 5-digit support. The hardware and software have to be from the same OEM.
807SITC of Contactless Smart card reader (OSDP) with Bluetooth / NFC withBluetooth credentials 13.56 MHz, IP-65 to IP-68 as per the Tender Specs (Life Time warranty -till the time readers are used by client) along with SS finish finished face plate (100x100mm) for reader. (UL) UL-294
808SITC of biometric Face with fingerprint cum smart card (Secured OSDP) ) with Bluetooth / NFC with Bluetooth credentials reader 13.56 MHz as per the Tender Specs.
809Supply of access control Bluetooth credentials
810Supply of Acces Control cards as spares
811Providing and fixing of Electromagnetic Locks for Single Leaf Door (Fail Safe Type) of 600 LBS holding force including door ajar alarm buzzer facility, with Status LED and Feedback Sensor, self alignment armature plate pivot, dual voltage incoming selectable DC supply, mounting bracket (L/C/Z/U etc.) / filler etc. and required power supply. Complete in all respect.
812Providing and fixing of Electromagnetic Locks for Double Leaf Door (Fail Safe Type) of 1200 LBS holding force including door ajar alarm buzzer facility, with Status LED and Feedback Sensor, self alignment armature plate pivot, dual voltage incoming selectable DC supply, mounting bracket (L/C/Z/U etc.) / filler etc. and required power supply. Complete in all respect.
813Providing and fixing of push button for Door Release, SS Finish, suitable for Single back Box (back box supplied by others) & fixing hardware etc. The Push button panel shall be fabricated from 304 Stainless steel. Complete in all respect.
814Providing and fixing of Emergency Break Glass to Exit for Door Release, (back box supplied by others) & fixing hardware, power supply etc. Complete in all respect.
815UHF Long Range Reader for the Gates
816TCp I/p Controller for the Long rage Reader
817LCD/LED Commercial Grade Display at the Gate
818Boom Barrier IP65 rating
819Supply installation testing & commissioning of customizable access control with with touch enabled UI enterprise software, Visitor management module to support unlimited number of readers and users, system adminitration,Alarm Monitoring, Guard Tour module, Automatic E-Mail Interface,ERP, HRMS, payroll integration, Unlimited User logins,Data import/export from any ODBC compliant format such as text, MS SQL. Integration with third party software. Supports multiple card formats on same system Support up to 72 card formats. Support custom card formats. It should support Door Interlocking. If the system requires the user to pass through two doors in a series to enter the premises and if the doors are interlocked, both the doors cannot be opened at a time. Thus, we can select more than two doors in a group. Bulk Import and Registration of employees with maker and checker module. ERP report: The user can configure the report settings & generate report in any required format. - User can set report for ERP as report header, date format, date seperator, field seperator and row terninator. - User can select the field required for ERP report just by drag-drop option. - User can add custom text field and can add column header The hardware and software have to be from the same OEM.
820Vehicle Access Management Software
821Vehicle TAG
822Supply Installation Testing & Commissioning of server machine of the specifications - (RAID-5 Configuration) , 19" rack mount with a minimum of Quad (4) Core Xeon Processor at 3.00GHz, with 16 GB of RAM, for Application Server. 500GB SSD HDDs for Application Server 1 Gigabit Network Controller , DVD Combo Drive, Monitor and Keyboard Latest release of Windows Server OS edition for both Application server The Main server shall be provided with 32- inch color monitor and 17-inch for Database server , standard 101-key keyboard and Scroll mouse, and DVD Combo Drive. The server computer system shall be of accepted make as given in the tender. The Servers shall be supplied with Ethernet Network Interface Card supporting both 10 BaseT and 10 base 2 topologies.
823Supply, installation, testing and commissioning of I7 Processor or Equivalet Desktop PC, 4MB Cache with 16 GB RAM, & 1 TB SSD HD, 10/100 Mbps Ethernet card, USB connection & internal modem, Microsoft(R) Windows(R) 10 or better or latest OS Professional Enterprise, Web server software, DVD-ROM Drive (with RAM), 100/1000 Mbps NIC for Network connection and anti virus software with 32" colour graphics monitor as per Tender Specifications. Accessories included Optical Mouse, Key Pad, Laserjet colour A4 printer.
8244 Core 0.75 Sqmm, PVC Insulated, PVC sheathed ATC conductor multistranded, Unarmored shielded cable for signal (Reader to Controller)
8254 Core 0.75 Sqmm, PVC Insulated, PVC sheathed ATC conductor multistranded, Unarmored shielded cable for signal (Controller to EML)
8262 Core 0.75 Sqmm, PVC Insulated, PVC Unsheathed ATC conductor multistranded, Unarmored unshielded cable for signal(Exit Push Button , EBG to Controller)
827Cat6 cable for communication between IP Controller & Biometric Readers to LAN switches
828Automatic Boom Barrier, Hydraulic with 5 mtr boom , opening /closing time 3.5 - 4.5 sec without inbuilt Dual Channel loop detector
829Automatic Boom Barrier, Hydraulic with 5 mtr boom , opening /closing time 3.5 - 4.5 sec without loop detector
830Push Button
831Pair of Photocell Safe beam
832Boom Rest
833Long Range RFID Readers, Read Range upto 8~12 Mtr
834Reader MS Mounting Pole
835Single Door, Two Reader Controller TCP/IP
836RFID Windsheild Tags
837Software for RFID Solution
838Computer
839UPS :- 2 sets of 3x400 kVA Modular UPS for 15 minutes backup with each UPS scalable to minimum 500 kW within the Frame : Supply of micro processor controlled 2 sets of 3x400 kVA Modular UPS in multiples of 50 kW Sub Power Modules for 15 minutes backup with each UPS scalable to minimum 500 kW within the Frame for future expansion with IGBT based rectifier to achieve input THDI < 5% and input power factor of greater than 0.99 at >25% loading. Greater than equal to i.e. =96.5% efficiency at 50-100% Loading condition in normal double conversion mode.Greater than equal to i.e. =98% efficiency at 50-100% Loading condition in Static Bypass Mode / Eco Mode / Inverter On Mode along with PF Correction to Unity at Input & Harmonic Correction (THDI) to < 5% at Input.- 3 Phase input and 3 phase 400 V output UPS system; andcomprising of the following complete as required and as per specification: a) Indivdual sub Power module shall be possible to plug out the Heathy or Faulty UPS sub module from the frame in normal Online Double Conversion operation without switching UPS to bypass / battery operation. The same shall be certified by Third Party agency for safe operation. b) Fully Rated Pluggable Swappable Static Switch Module (Draw In/Out) shall be provided. c) Remote Monitoring features like Modbus RTU, Modbus TCP/IP, SNMP, Web based monitoring over Ethernet etc. shall be provided. d) Mobile App Based Software for monitoring of UPS parameters, alarms, event logs, statistical data on the Smart Phone shall be provided.e) Inbuilt / External Phase Sequence Corrector at Input of UPS System shall be provided. f) Rodent/Reptile Mesh & Dust Filters shall be provided. g) AC/DC Capacitors - 10 years Operating Life. If Vendor does not comply, then One time replacement cost to be considered in Pricing. h) Power Analyzer used in case of non Availability of inbuilt oscilloscope.i) Top cable entry by default with Direct Aluminium Cable Termination in UPS shall be provided. Incase Aluminum Cable termination is not possible, vendor to provide separate cube/box with input & output breakers & busbars with each UPS module.,Supply of Li-ion Battery Solution: a. The battery cabinet shall feature lightweight, compact, long-life li-ion batteries which provide energy to support the load during a momentary loss of input power to the rectifier. b. Each battery cabinet shall require front access only for installation, service, and maintenance. c. 15 minutes backup @1.0 PF for 1000 kVA load with each 3x400 kVA UPS Set. d.Each LIB cabinet shall be provided with DC Breaker with series connected DC Fuses for isolation & protection along with battery management system to monitor voltage, temperature, State of Charge (SOC) & State of Health (SOH) of each cell and module. BMS at Cell Level, Module Level, Rack Level and System Level (Racks in Parallel) shall be provided respectively. Proposed LIB shall be UL 9450A Certified, i.e. Test Method for Evaluating Thermal Runaway Fire Propagation in Battery Energy Storage Systems. Certificate shall be provided by the bidder Vendor to provide complete details of make of Batteries, ampere hour ratings, no. of Batteries, Expected life, Final discharge voltage, Nominal float voltage, Battery recharge time & configuration of back up time, Battery sizing Calculations Receiving, assembling, installing in position, connecting, testing and commissioning of UPS System with Batteries as per specifications
840A)UPS,, 3 X 3, 120 kVA, 415V AC, 50 Hz : UPS, 3 X 3, 120 kVA, 3 Phase, 415V, 6 Pulse, Single Modulewith 400 Amp Battery Circuit Breaker - 4 SETS; Paralleling Cable Kit (10 Mtrs) (Stock available: 55 nos) (6P/12P) stock avail 55 nos. - 4 SETS SIC Card (6P/12P) - 4 SETS; 12V SMF / VRLA Battery, 2 Set of32Blocks, 120 Ah for 30 min back up on rated load @ 100 KVA load at 0.8PF - 4 SETS; (2 Years Warranty on Battery); Battery Rack - 4 SETS;Battery IRIT - 8 SETS; Nyvin Cable of size 00 (Idc=263 Amps, Std Dist=10 Mtr from UPS to Battery) - 4 SETS
841B)UPS, 3 X 3, 60 kVA, 415V AC, 50 Hz UPS, 3 X 3, 60 kVA, 3 Phase, 415V, Single Modulewith 200 Amp Battery Circuit Breaker - 1 SET Paralleling Cable Kit (10 Mtrs) (Stock available: 55 nos) (6P/12P) stock avail 55 nos. - 1 SET SIC Card (6P/12P) - 1 SET 12V SMF / VRLA Battery, 2 Set of16Blocks, 120 Ah for 30 min back up on rated load @ 50 KVA load at 0.8PF (2 Years Warranty on Battery) - 1 SET Battery Rack - 1 SET Battery IRIT - 1 SET Nyvin Cable of size 00 (Idc=263 Amps, Std Dist=10 Mtr from UPS to Battery) - 1 SET
842DATA CENTRE WORKS: Supply & Installation of false floor cementous panels of size 600 x 600mm, 35mm thicl(, top covered by antistatic Laminate & edge bounded with black colour onductive PVC edge beading with Accessories Finish Floor Height (FFH) 750mm UDL- 1600KG/Sqmt and Point Load-400KG,
843Supplyof thermal insulation underdeck with 25 mm thick XLPE/Nitrile rubber with aluminium foil including Volatile Organic Compounds (TVOCs) and Formaldehyde. The materials should have GREENGUARD Indoor Air Quality (IAQ) Certification, manufactured without the use of CFCs, HFCs or HCFCs. They should by fibre-free and dust free, and resist mold and mildew, made of a closed-cell structure to prevent moisture from wicking, since moisture accumulation will reduce insulation performance, Insulation must have a thermal conductivity of = 0.034 W/(m.K) at 0°C and = 0.036 W/(m.K) at 24°C to be measured according to ASTM C 177, ASTM C 518 or EN ISO 8497. Insulation must have water vapour permeability of 0.13 µgm/(N.h) to BS4370-2:1993 Insulation must achieve the following fire performance: BS 476-6:1989 – low contribution to fire growth with Fire Propagation Index of performance (I) no exceeding 12 and sub index (i1) not exceeding 6; and BS 476-7:1997 - of very low Surface Spread of Flame (Class 1). Protective coverings shall be installed on areas of insulation that are exposed to weather or subject to mechanical damage. The protective covering shall be: “Arma-Chek Silver” multi-layer laminate of aluminium, coated with a UV protective film and backed with a flexibleThe material should be adhered with Armaflex 520 Adhesive or equivalent, and all joins and seams secured with “Arma-Chek Silver Tape”. Installation shall be in all cases to the manufacturer’s recommendations. For Floor and Ceiling both Area PVC film.
844Supplyof thermal insulation underdeck with 13 mm thick XLPE/Nitrile rubber with aluminium foil including Volatile Organic Compounds (TVOCs) and Formaldehyde. The materials should have GREENGUARD Indoor Air Quality (IAQ) Certification, manufactured without the use of CFCs, HFCs or HCFCs. They should by fibre-free and dust free, and resist mold and mildew, made of a closed-cell structure to prevent moisture from wicking, since moisture accumulation will reduce insulation performance Insulation must have a thermal conductivity of = 0.034 W/(m.K) at 0°C and = 0.036 W/(m.K) at 24°C to be measured according to ASTM C 177, ASTM C 518 or EN ISO 8497. Insulation must have water vapour permeability of 0.13 µgm/(N.h) to BS4370-2:1993, Insulation must achieve the following fire performance: BS 476-6:1989 – low contribution to fire growth with Fire Propagation Index of performance (I) no exceeding 12 and sub index (i1) not exceeding 6; and BS 476-7:1997 - of very low Surface Spread of Flame (Class 1). Protective coverings shall be installed on areas of insulation that are exposed to weather or subject to mechanical damage. The protective covering shall be: “Arma-Chek Silver” multi-layer laminate of aluminium, coated with a UV protective film and backed with a flexible PVC film. The material should be adhered with Armaflex 520 Adhesive or equivalent, and all joins and seams secured with “Arma-Chek Silver Tape”. Installation shall be in all cases to the manufacturer’s recommendations. For Floor and Ceiling both Area
845AL Clad Sheet
846Grating Panel: Provididng & Fixing 600 x 600mm Grating Panel 46%o pening with volume control damper for monitoring airflow.
847Airplugs: Providing & Fixing Airplugs to enable wire & Cables to pass through floor panels. It allows wires to neately & safely penetrate from the cavity below the floor to the location.
848Panel Lifter : Supply of Panel lifter , for lifting heavy loaded tiles.
849Supply and installation of fire rated doors, the door must have been, manufactured with galvanised - GI sheet of GPSP Grade as per IS 277. All Fire doors must satisfy the requirement of latest Fire & Life Safety guidelines for 120 minutes Fire Rating with its Stability & Integrity for 120 minutes. The Prototype sample of the door must carry a prior test evidence as per IS 3614 part-2 / BS 476 Part 20 & 22. The manufacturer must submit the copy of test evidence prior to start of production .The offered test certificate should either carries it"s Validity or certificate must not be older than 5 years from NABL Accreditated Lab i.e Spectro / International Lab or by any accreditation body which operates in accordance with ISO/IEC 17011 and accredits labs as per ISO/IEC 17025 for testing and calibration scopes shall be eligible. The door must carry a Batch sticker with details of the door after scanning . All doors should be finished with Powder coating in desired regular RAL Shades. Door frame shall be Single rebate grooved profile of section 100 x 57 mm made out of 1.20mm thick galvanised steel sheet with a factory pre-punched groove so as to accomodate Fire & smoke seal size 10x4mm Frames should be butt jointed and field assembled with bolting system for proper strength .Frames should be provided with back plate for anchor fasteners for installation on a finished plastered wall opening. Any filling in frames is not suggested . Door leaf should be 46mm thick Navair make fully flush double skin door. Door leaf must be manufactured from 0.8mm thick galvanised steel sheet. The door should be provided with reinforcement pads & necessary provision for receiving appropriate Hardwares of Becker FS or equivalent make. The Shutter shall be filled with proprietary infill material Honey Komb Craft paper Insulation . For Double leaf doors will have astragal at their meeting stile for both active and inactive leaf. Vision panels wherever required should be of 120 minutes fire rating and should be of non-wired type. All hardwares , Fasteners and FR Glass shall be payable in Extra item. The door and the frames shall be finished with powder coating and shall pass the minimum 500hours Salt Spray test evidence. Fire Rated Door, Double Leaf 1800x2400mm
850Fire Rated Door, Single Leaf with Panic Bar 900X2100MM
851Fire Rated Door, Double Leaf 1200X2100MM
852Fire Rated Door, Double Leaf 1200X2100MM
853HYDRAULIC LIFTING PLATFORM, Capacity 4000Kgs, Platform Size (2000x1100MM) with SumpPumpas per noms.
854SITC of Software Solutions for Visitor Management Monuk Application, Real-time Visitor Status, Web-Based Application, Pre-scheduling for visit, Searchable Visitor History, Biometric Registration and verification, Email and SMS notification, Visitor Category listing, Automatic Database Backup
855SITC of Hardware Solution for Visitor Management : Mantra Standard Thermal Printer with Bluetooth
856WEB CAM - logitec C505E
857Smart Card R/W
858Bionic F9, Smart Facial Recognition Terminal, 5 inches, full viewing angle, 1000 Users, Dual Lens camera RGB+IR, Android 9 or higher, 8GB ROM, Ethernet, Bluetooth, WIFI, ISO 14443 Type A/B Mifare Cards, IP65 (Dual Weatherproof Enclosure), Distance to enroll within 0.6 meter to 1 meter
859SITC OF AIR CURTAIN SINGLE MOTOR, TWO BLOWER 4FEET: FITTED WITH 1/2 H.P MOTOR, SINGLE PHASE 2800 RPM, ALUMINUM BLOWERS 7x7 ARE DYNAMICALLY BALANCED, VELOCITY 18-20 M/SEC, NOISE LEVEL 55db TO 62db, BODY :MS POWDERED COATED BODY, 220V, DOUBLE SHAFT MOTOR
860SITC OF BAGGAGE SCANNER Baggage with tunnel size 600 mm x 400 mm, Inbuilt configuration will be provided.,Incoming & Outgoing roller tables 0.5 Mtr,1 KVA Online UPS with inbuilt control desk
861SITC OF Door Frame Metal Detector With People Counter & Battery Backup Model-6 Zone
862RODENT REPELLENTS : Providing Microprocessor based Main Panel / Controller wallmounting type with facility to connect 20 Transducers Operating Frequency > 20Khz and < 50 Khz. with 4 frequency bandsFront Facia having LCD display and on board controls to view and operate the menu. Panel to be with power supply supporting 230V AC.Panel to have BMS Compatibility Providing Microprocessor based Main Panel / Controller wall mounting type with facility to connect 20 Transducers Operating Frequency > 20Khz and < 50 Khz. with 4 frequency bandsFront Facia having LCD display and on board controls to view and operate the menu. Panel to be with power supply supporting 230V AC.Panel to have BMS Compatibility
863Ultrasonic transducer with 50 to 110 dB sound output complete as required
864MS bracket for mounting the panel
8652core.0.5 sq mm Cu cable complete as required
8664 Zone Water Leak Detection LCD Conventional Panel With Inbuilt Buzzer & Individual Zone ,Potential Free Contact for Connecting to the BMS System. Panel has Battery Backup Facility , Common Hooter ,Common Relay out for Alram & Falut Relay output Extra
867Water leak Sensor cable
868Hooter complete as required
8692core.1.5 sq mm Cu armoured cable, RED color complete as required
870Fire Suppression System :-140 Litres Capacity Seamless Cylinder CCOE Approved, complete with valve assembly and pressure gauge with a safety burst disc and a safety cap.gauge with a safety burst disc and a safety cap.
871FK-5-1-12 Fire Protection fluid compound of carbon, fluorine and oxygen (CF3CF2C(O)CF(CF3)2).
872Electric Control Head operated electrically from the Detection & Control System or locally with a manual lever on the control head.
873Pressure Operated Control Head which allows for pressure actuation slave cylinders and is mounted directly on top of the slave cylinders valve.
874Discharge Nozzles are designed to provide the proper flow rate and distribution of FK-5-1-12 to total flood a hazard area : 180 deg. / 360 deg.
875Master Cylinder Adapter Kit used to actuate the Slave Cylinder.
876Discharge Hose, 1-1/2” (use with 34, 80, 120 & 140 Ltr. Cylinders)
8771-1/2" Manifold Check Valve installed at the discharge manifold to allow removal of any FK-5-1-12 cylinder from the manifold while still retaining a closed system.
878Flexible Actuation Hose (Pilot pressure is directed to a pressure operated control head on each cylinder valve using 1/4 inch actuation hose)
879Manifold Supervisory Switch for indication of discharge of system
880Cylinder Strap for 120 & 140 Ltr. Cylinder
881Brass MaleTee
882Brass Male Elbow
883Directional Valve with Pneumatic Actuator & Handle
8843 way Pilot Manifold with accessories + N2 cyl (150 bar) capacity with valve
885SITC OF Data Center & User Connectivity System (Fiber & Copper) 24 (3 x 8F / 2 x 12F / 1 x 24F) Fiber MPO Trunk Cable (OM4, Multimode), LSZH,15 m - As per tender technical specifications
88624 (3 x 8F / 2 x 12F / 1 x 24F) Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 20 m - As per tender technical specifications
88724 (3 x 8F / 2 x 12F / 1 x 24F) Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 25 m - As per tender technical specifications
88824 (3 x 8F / 2 x 12F / 1 x 24F) Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 30 m - As per tender technical specifications
88924 (3 x 8F / 2 x 12F / 1 x 24F) Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 35 m - As per tender technical specifications
89024 (3 x 8F / 2 x 12F / 1 x 24F) Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 40 m - As per tender technical specifications
89124 (3 x 8F / 2 x 12F / 1 x 24F) Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 45 m - As per tender technical specifications
89224 (3 x 8F / 2 x 12F / 1 x 24F) Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 50 m - As per tender technical specifications
89324 (3 x 8F / 2 x 12F / 1 x 24F) Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 55 m - As per tender technical specifications
894MPO Adapter Plate (8 Port) - As per tender technical specifications
8951U Fiber Panel (Type 1) with 4 slots - As per tender technical specifications
8962U Fiber Panel with 12 slots - As per tender technical specifications
897OM4 MPO (Female) to MPO (Male), Array Cord, LSZH, 3 Meters - As per tender technical specifications
898MPO to 24F LC (3x8F / 2x12F / 1x24F), Method B, OM4 Cassette/Module - As per tender technical specifications
899OM4, LC to LC, Fiber Patch Cord, 1.6 mm, Duplex, LSZH, 3 Meters - As per tender technical specifications
900OM4, LC Uniboot to LC Uniboot, Fibe Patch cord, 1.5 mm, Duplex, LSZH, 3 Meters - As per tender technical specifications
9011U Fiber Panel (Type 2) with 4 slots - As per tender technical specifications
90212 Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 15 m - As per tender technical specifications
90312 Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 20 m - As per tender technical specifications
90412 Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 25 m - As per tender technical specifications
90512 Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 30 m - As per tender technical specifications
90612 Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 35 m - As per tender technical specifications
90712 Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 40 m - As per tender technical specifications
90812 Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 45 m - As per tender technical specifications
90912 Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 50 m - As per tender technical specifications
91012 Fiber MPO Trunk Cable (OM4, Multimode), LSZH, 55 m - As per tender technical specifications
911CAT 6A U/UTP Horizontal Cable, LSZH, 305 meters box - As per tender technical specifications
912CAT 6A U/UTP 24 port Jack Panel, Straight - As per tender technical specifications
913CAT 6A LSZH U/UTP RJ45 Patch Cords, 3 meters, Blue Color - As per tender technical specifications
91412 fiber Singlemode OS2, yellow color, LSZH, fiber cable - As per tender technical specifications
91512 F LC, singlemode OS2, splice cassette - As per tender technical specifications
91632F Splice Trays
91748F Splice Trays
918OS2, Singlemode, LC to LC, Fiber Patch Cord, 1.6 mm, Duplex, LSZH, 3 Meters - As per tender technical specifications
919CAT 6A U/UTP Information Outlet, Blue Color - As per tender technical specifications
920CAT 6A U/UTP Information Outlet, Red Color - As per tender technical specifications
9213 x 3 Square faceplate Dual port - As per tender technical specifications
922CAT 6A LSZH U/UTP RJ45 Patch Cords, 2 meters, Blue Color - As per tender technical specifications
923CAT 6A LSZH U/UTP RJ45 Patch Cords, 2 meters, Red Color - As per tender technical specifications
92412 fiber Multimode OM4, Aqua Color, Indoor/Outdoor, LSZH, Fiber Cable - As per tender technical specifications
92512 F, Multimode OM4, LC port splice cassette with pigtails - As per tender technical specifications
926Pathway Systems (Fiber & Copper) 6-foot horizontal straight section
9276-foot horizontal straight section Hinged cover
9284x12 90º horizontal elbow
9294x12 90° Horizontal Elbow Cover
930FiberGuide® Horizontal Cross, 4x12in, Yellow
931FiberGuide® Snap-on Cover for Horizontal Cross, 4x12in, Yellow
932Cut-in T
933Cut-in T Fixture
9344-inch Express Exit base with base cover
935Rear cover, 4-inch Express Exit—4x12 sys
9364x4 trumpet flare kit
9372-Inch Express Exit
938Trumpet Flare, 2x2in, Yellow
9394x12 snap-fit junction
94012mm dia. threaded rod (L=180 cm/ ea)
941Trapeze Bracket Kit for 4X12” to use with 12mm dia.
942Quick knobs (10)
943Kit - 10 black capture clips*
94412x4 inch 45° up elbow
94512x4 inch 45° up elbow snap on cover
94612x4 inch 45° down elbow
94712x4 inch 45° down elbow snap on cover
94812x4 inch end cap
949CMWB-SP Straight 100-300
950CMWB HP Horizontal Elbow
951CMWB-CP Cross 100-300
952CMWB TP Cut T
953CMWB Finish Spray
954CMWB DP Drop kit
955CMWB-AP Screw Jointing kit
956CMWB Ceiling mount Accessories for 300
957Threaded Rod M12, 1.8 Mtr length
958CMWB End Cap 100-300
959COLD AISLE CONTAINMENT FOR 19 SERVER RACK AND 2 NETWORK RACK:AISLE A BASIC FRAME STRUCTURE TAKING SUPPORT FROM RACK TOP - 1 SET TOP CEILING POLYCARBONATE 600WX1200D FILLER PANELS - 10 NOS. TOP CEILING POLYCARBONATE 800WX1200D FILLER PANELS- SET - 1 NO. AISLE ENTRY/EXIT SLIDING DOORS WITH AUTOMATIC DOOR CLOSURES - 2 SET FULL HEIGHT FILLER PANEL 600MM WIDE - 1 NO. GASKET - 2 SET
960COLD AISLE CONTAINMENT FOR 19 SERVER RACK AND 2 NETWORK RACK:AISLE B BASIC FRAME STRUCTURE TAKING SUPPORT FROM RACK TOP - 1 SET TOP CEILING POLYCARBONATE 600WX1200D FILLER PANELS - 10 NOS. TOP CEILING POLYCARBONATE 800WX1200D FILLER PANELS- SET - 1 NO. AISLE ENTRY/EXIT SLIDING DOORS WITH AUTOMATIC DOOR CLOSURES - 2 SET GASKET - 1 SET
961COLD AISLE CONTAINMENT FOR 19 SERVER RACK AND 2 NETWORK RACK:AISLE C BASIC FRAME STRUCTURE TAKING SUPPORT FROM RACK TOP - 1 SET TOP CEILING POLYCARBONATE 600WX1200D FILLER PANELS10 NOS. TOP CEILING POLYCARBONATE 800WX1200D FILLER PANELS- SET 1 NO. AISLE ENTRY/EXIT SLIDING DOORS WITH AUTOMATIC DOOR CLOSURES 2 SET FULL HEIGHT FILLER PANEL 80MM WIDE 1 NO. GASKET - SET 1 SET
962COLD AISLE CONTAINMENT FOR 19 SERVER RACK AND 2 NETWORK RACK :AISLE D BASIC FRAME STRUCTURE TAKING SUPPORT FROM RACK TOP -1 SET TOP CEILING POLYCARBONATE 600WX1200D FILLER PANELS - 10 NOS. TOP CEILING POLYCARBONATE 800WX1200D FILLER PANELS- 10 NOS. AISLE ENTRY/EXIT SLIDING DOORS WITH AUTOMATIC DOOR CLOSURES - 2 SET FULL HEIGHT FILLER PANEL 80MM WIDE - 1 NO. GASKET - 1 SET
963COLD AISLE CONTAINMENT FOR 21 SERVER RACK AND 2 NETWORK RACK:AISLE E BASIC FRAME STRUCTURE TAKING SUPPORT FROM RACK TOP1 SET TOP CEILING POLYCARBONATE 600WX1200D FILLER PANELS 11 NOS. TOP CEILING POLYCARBONATE 800WX1200D FILLER PANELS-1 NO. AISLE ENTRY/EXIT SLIDING DOORS WITH AUTOMATIC DOOR CLOSURES2 SET FULL HEIGHT FILLER PANEL 600MM WIDE1 NO. GASKET - 1 SET
964COLD AISLE CONTAINMENT FOR 22 SERVER RACK AND 2 NETWORK RACK :AISLE F BASIC FRAME STRUCTURE TAKING SUPPORT FROM RACK TOP 1 SET TOP CEILING POLYCARBONATE 600WX1200D FILLER PANELS11 NOS. TOP CEILING POLYCARBONATE 800WX1200D FILLER PANELS- SET1 NO. AISLE ENTRY/EXIT SLIDING DOORS WITH AUTOMATIC DOOR CLOSURES 2 SET GASKET - 1 SET
965COLD AISLE CONTAINMENT FOR 21 SERVER RACK AND 2 NETWORK RACK : AISLE G BASIC FRAME STRUCTURE TAKING SUPPORT FROM RACK TOP1 SET TOP CEILING POLYCARBONATE 600WX1200D FILLER PANELS 11 NOS. TOP CEILING POLYCARBONATE 800WX1200D FILLER PANELS- SET1 NO. AISLE ENTRY/EXIT SLIDING DOORS WITH AUTOMATIC DOOR CLOSURES 2 SET FULL HEIGHT FILLER PANEL 130MM WIDE1 NO. GASKET - 1 SET
966COLD AISLE CONTAINMENT FOR 21 SERVER RACK AND 2 NETWORK RACK : AISLE H BASIC FRAME STRUCTURE TAKING SUPPORT FROM RACK TOP1 SET TOP CEILING POLYCARBONATE 600WX1200D FILLER PANELS 11 NOS. TOP CEILING POLYCARBONATE 800WX1200D FILLER PANELS- SET1 NO. AISLE ENTRY/EXIT SLIDING DOORS WITH AUTOMATIC DOOR CLOSURES 2 SET FULL HEIGHT FILLER PANEL 130MM WIDE1 NO. GASKET - 1 SET
967COLD AISLE CONTAINMENT FOR 21 SERVER RACK AND 2 NETWORK RACK : AISLE I BASIC FRAME STRUCTURE TAKING SUPPORT FROM RACK TOP1 SET TOP CEILING POLYCARBONATE 600WX1200D FILLER PANELS 11 NOS. TOP CEILING POLYCARBONATE 800WX1200D FILLER PANELS- SET1 NO. AISLE ENTRY/EXIT SLIDING DOORS WITH AUTOMATIC DOOR CLOSURES2 SET FULL HEIGHT FILLER PANEL 70MM WIDE1 NO. GASKET - 1 SET
968COLD AISLE CONTAINMENT FOR 05 SERVER RACK AND 2 NETWORK RACK : AISLE J BASIC FRAME STRUCTURE TAKING SUPPORT FROM RACK TOP1 SET TOP CEILING POLYCARBONATE 600WX1200D FILLER PANELS 5 NOS. TOP CEILING POLYCARBONATE 800WX1200D FILLER PANELS- 1 NO. AISLE ENTRY/EXIT SLIDING DOORS WITH AUTOMATIC DOOR CLOSURES 2 SET GASKET - 1 SET
969COLD AISLE CONTAINMENT FOR 08 SERVER RACK AND 2 NETWORK RACK:AISLE K BASIC FRAME STRUCTURE TAKING SUPPORT FROM RACK TOP1 SET TOP CEILING POLYCARBONATE 600WX1200D FILLER PANELS 5 NOS. TOP CEILING POLYCARBONATE 800WX1200D FILLER PANELS- 1 NO. AISLE ENTRY/EXIT SLIDING DOORS WITH AUTOMATIC DOOR CLOSURES2 SET GASKET - 1 SET
970SITC of CONTINUOUS type copperbusbar trunking system (indoor), System voltage - 600 V& Insulation voltage of 1000V,250 Amps, 4/5 pole, with Oversized neutral by min 50% of phase conductor rating& externally mounted aluminium earth bus/housing ,Short circuit rating of 25 KA for 1 sec, IP-3x, with capability to place tap off boxes anywhere on the entire length without distance restrictions’ and color coding for easy identification of connected power supply as per SLD &detailed Specifications attached.
971Supplying, installation, testing & commissioning of 250 A End Flange Unit, TP+N, with RYB indicating lamps & MCCB, powder coated, with suitable bus bar to terminate. asperSLD&detailedSpecifications attached.
972250A joint pack
973250A end cap unit
974500A joint pack
975500A end cap unit
976Hangers
977Closure strip
978Supplying, installation, testing & commissioning of single phase 32A, single phase Tap-off box for racks upto 7 kW with 32A, 10kA, DP MCB, 32A single phase, 2P+N, 3 pin industrial socket with plug top as per IEC standard as per SLD &detailed Specifications attached.
979Supplying, installation, testing & commissioning of3 phase 16A, 3phase Tap-offbox for racks upto 11 kW box with 16A, 10kA, DP MCB, 16A single phase, 3P+N+E, 5 pin industrial socket with plug top as per IEC standard as per SLD &detailed Specifications attached.
980Supplying, installation, testing & commissioning of3 phase 32A, 3phase Tap-off box for racks upto 22 kWwith 32A, 10kA, DP MCB, 32A single phase, 3P+N+E, 5 pin industrial socket with plug top as per IEC standard as per SLD &detailed Specifications attached.
981Supplying, installation, testing & commissioning of3 phase 32A, 3phase Tap-off box for Storage racks with remote monitoring capabilities and capacity upto 22 kW with 32A, 10kA, DP MCB, 32A single phase, 3P+N+E, 5 pin industrial socket with plug top as per IEC standard as per SLD &detailed Specifications attached.
982Supply & instalaltion of Sandwich type, aluminum busduct un powder coated encloser for indoor use conforming to the detailed technical specification of 2000A TPN +100% integral earth IEC aluminum Busbar . All busbars must shall be ASTA certified to with standing the stress of a RMS symmetrical ampere fault of 50KA for 1-second duration (short circuit withstanding limit) . The maximum operating temperature shall comply with IEC 61439-6 in any position at its rated amperage and IP level of protection. Tap-off outlets shall meet lEC IP55 requirements (degree of protection) without the need for an additional cover. Busbars shall be fabricated from electrical grade, that is Aluminum (High Density 55% conductivity & all contacts shall be tin plated to avoid corrosion with Isolated Earth bar with 100% Al. Tapping units shall be - Circuit breakers (Current Limiting) TP&N 36KA & 50KA rated. The housing shall be of 3mm extruded aluminum section custom designed for the system.The manufacturer should have a standard range of accessories including horizontal and vertical elbows, T elements and double Elbows, connecting flange elements to switchgear and transformer. The threaded hanger rods should use to provide proper support to AL busbar from cieling slab. NOTES: EXACT LENGHT OF BUS DUCT REQUIRED TO BE MEASURED AT SITE AND GA DRAWING SHALL BE SUBMITTED AND GOT APPROVED BEFORE FABRICATION & SUPPLY TO SITE
983200A, End feed unit on 2000A AL line, to tap the power supply to staging rooms. Cable is used to connect End feed unit to staging room Panel
984100A, End feed unit on 2000A AL line, to tap the power supply to Telco room,Cable is used to connect End feed unit to TELCO room Panel
9852000 A special flange
9862000A - Flatwise Tee
9872000A- Flatewise Elbow
9882000- Distribution Length (Considering each 600mm for every 250 A IMPB feeder)
9892000A End cap
9902000A , AL HPB Hanger -Horizontal
991SITC of Server Rack, 42U 600mm x 1200mm,with front single and rear split perforated door, levelling feet & castors, with split Side Panel, Bottom Panel and Top Panel with cutout, bottom pannel, Swing handle locks & full sized cable management & PDU bracket. With mounting hardware (Pack of 30), baying kit (ganging kit) & self grounding feature and supply with 2 Horizontal cable manager per rack and. Refer detailed technical specification.
992SITC of Network Rack, 42U 800mm x 1200mm,with front single and rear split perforated door, levelling feet & castors, with split Side Panel, Bottom Panel and Top Panel with cutout, bottom pannel, Swing handle locks & full sized cable management & PDU bracket. With mounting hardware (Pack of 30), baying kit (ganging kit) & self grounding feature and supply with and with 2 vertical cable manager per rack. Refer detailed technical specification.
993Set of 20 nos of tool less PVC blanking panels each rack
994iPDU, Remotely Monitored Unit Level, Preferably suitable for Variable Power Configuration with all iPDUs capable to handle max. 22KW load, Vertical 0U, (30 Nos) Hybrid (Combination of C13 and C19) outlets, Universal Inlet to support 7 KW to 22 KW capacity so that same iPDU can be used in any rack ranging from 7 KW to 22KW. Suitable Universal inlet cables to be provided along with IPDU as per capacity requirement mentioned in RFP. Refer detailed technical specifications.
995Combo sensor (Temperature + Humidity + Dew point )
996i)Supply, Installation, Testing and Commissioning ofDCIM Solution as per detailed technical specifications in addition to mentioned in BOQ section. The DCIM application should be 100% web based without requiring any client to be deployed to view and explore application functionality. ii)Application should provide overview of data center operations through inventory management and location-based drill-down. Managing Layer - Inventory / Asset Management / Energy Cost Management. iii)A location-based drill-down view provides a structured overview of data center locations, from a global to local view down to single assets. iv)This software shall be seamlessly integrated to the Controller through industry standard protocol such as MODBUS IP, SNMP & BACnet IP. v) (a) Vendor to consider exact number of racks as mentioned in RFP and other supporting infrastructure as per IO list and system architecture. Rack Level power consumption to be seen in single Window/webpage. (b) Please determine the IO list on the SLD & layout Provided. i)Supply, Installation, Testing and Commissioning of Capacity planning predicts the optimal location for physical infrastructure and rack-based IT equipment based on the availability and requirements of physical infrastructure capacity. ii)Visualization of the Data Center and Racks. should visualize the heat maps in a rendering of the floor view &should allow to view actual rack heat load and to help balancing and optimizing the system and generate reports - with this feature DC operation team will be able to identify potential hot pockets, airflow problem on floor, also this must help operation team to optimize the cooling inside /outside of room/rack thus bringing room & rack level cooling efficiency iii)Vendor to consider exact number of racks as mentioned in the RFP and other supporting infrastructure as per IO list Supply, Installation, Testing and Commissioning of Standard Dashboard and Reporting, Audit Trail, Capacity, History ,Contiguous Free U-Space, Customer Inventory Report, Executive Power and Space Rack U. Customize Dashboard and Reporting as per Customer Expectation Vendor to consider exact number of racks as mentioned in RFP and other supporting infrastructure as per IO list and system architecture ii)System architecture design should work in 100% HAmode (High Availability mode) with Zero Data loss. i,e if One Primary DCIM Application fails for any reasonthen Secondary(HA) instance should take over as primary and work as production.
997Supply, Installation, Testing and Commissioning of necessary instrumentation controller required for monitoring layer should be supplied, configured and maintain. Qty may vary as per site requirement
998Required server hardware to be supplied along with operating system in HA configuration
999VESDA system with Coverage up to 250 m2 (5000 sq. ft.),Single pipe inlet,Maximum pipe lengths:1 x 25 m (80 ft) (Max. 12 holes),2 x 15 m (50 ft) per branch (Max. 6 holes per branch),Sensitivity Range- 0.025 to 20% obs/m (0.008 to 6.4% obs/ft),Ultrasonic Airflow Sensing,Laser-Based Absolute Smoke Detection,Dual Stage Air Filtration,Instant Recognition Display,Event log – up to 18000 events,Multiple Event Logging in separate logs,UL 268 listeFM/LPCB/VdS approved
1000VESDA system with coverage up to 500 m2 (10000 sq. ft.),Single pipe inlet,Maximum pipe lengths:1 x 25 m (80 ft) (Max. 12 holes),2 x 15 m (50 ft) per branch (Max. 6 holes per branch),Sensitivity Range- 0.025 to 20% obs/m (0.008 to 6.4% obs/ft),Ultrasonic Airflow Sensing,Laser-Based Absolute Smoke Detection,Dual Stage Air Filtration,Instant Recognition Display,Event log – up to 18000 events,Multiple Event Logging in separate logs,UL 268 listed,FM/LPCB/VdS approved
1001Power supply unit for above detector
1002Capillary Tube & sampling points
1003Air termination ( Nozzles)
1004Electronic hooter cum strobe unit
100525mm PVC pipe network
10062Cx1.5 sq mm Cu armoured cable complete as required
1007Testing and commissioning charges
1008VEDIO WALL FOR BMS ROOM: Samsung 55" Video Wall Display with 0.88 Bazel to Bazel Gap
10094 x 4 True 4K HDMI Matrix Video Wall Controller & Scaling Switcher with custom presets for layouts via web GUI
1010LockPro - HDMI Cable Lock
101120M TRUE 4K HDMI 2.0 Active Optical Cable
101230M TRUE 4K HDMI 2.0 Active Optical Cable
1013Video Wall Push And Pull Mount with all corner adjustment option
1014Implementation servicesincludes - Design, Engineering,Labour, Installation, Testing and commissioning and training to users at the site to set the system up and operate the same.
1015VIDEO WALL FOR NOC ROOM : Samsung 55" Video Wall Display with 0.88 Bazel to Bazel Gap
10168x9 4K HDMI Matrix Video Wall Controller & Scaling Switcher with custom presets for layouts via web GUI
1017LockPro - HDMI Cable Lock
101820M TRUE 4K HDMI 2.0 Active Optical Cable
101930M TRUE 4K HDMI 2.0 Active Optical Cable
1020Video Wall Push And Pull Mount with all corner adjustment option
1021Implementation servicesincludes - Design, Engineering,Labour, Installation, Testing and commissioning and training to users at the site to set the system up and operate the same.
1022VIDEO CONFERENCING ROOM : Ceiling Microphone tile with 26 or more no. of omni directional microphone, coverage area : 55sq mtr or more, Dante connectivity : dual / redundant, POE enable (qty of microphone will vary as per the mentioned coverage area and built in micorphone), Lighting Indication on all four corner, It should work on open control protocol software andcompitable to monitor with a single sofware for all the microphone in the campus, should come with suspension mount kit etc complete required as per the specifications.
1023Wireless digital Handheld Microphone with 18 or more channel, RF output 80mW or more, super cardiod pickup pattern, Frequency range : 1880 to 1930 MHz, Connectivity : RJ-45 (specifications includes single microphone set of transmitter and receiver) etc and complete as required.
1024Wireless digital Headset Microphone with 18 or more channel, RF output 80mW or more, Omni-directional pickup pattern, Frequency range : 1880 to 1930 MHz, Connectivity : RJ-45, 256-bit AES Encryption(specifications includes single microphone set of transmitter and receiver) etc and complete as required.
1025Wireless digital microphone charger, charging capacity : 4 or more simultaneously with lighting indication, monitoring : LAN / RJ45. Should be from same OEM as of wireless mic etc and complet required as per specifications.
10264.5-inch, 2-way, Full Range, Ceiling-mount loudspeaker. Rated Power - 16Watts, Sensitivity-89 dB SPL, Coverage Angle -140°, Maximum SPL Continuous/Peak-101dB/107dB, Rated Impedance - 8 Ohms. Transformer Tapping - 70V/100V(16, 8, 4,2 watts). Transducer - 4.5-inch Polypropylene cone with butyl rubber surround, Material - Painted ABS polymer Baffle and Power coated steel grille. Safety rating - UL1480, UL2043. Mounting rails and C-Ring for ceiling tile included.
1027Quad channel class-D Energy Star rated amplifier. Wattage per Channel - 100 watts/channel into Low-Z loads (8O/4O). Four channels shall also be bridged in pairs, each pair providing up to 200 watts rms into 4/8 ohms andup to 175watts into 70V/100V. Signal to Noise (A weighted, 20 Hz-20 kHz)->100 dB, Frequency Response-20Hz-20kHz, Input Sensitivity-1.23 Vrms (+4 dBu), Input Impedance->10 kO balanced/unbalanced, Front Panel Indicators-Power, per channel Signal,Protect/Limit,Controls- 4O/8O/70V Bridge Highpass On/100V Bridged Highpass on per channel pair. Shall include all mounting accessories for mounting in half or 1 rack space.
1028Digital Signal Processor with 8 Mic/Line inputs, 8 Line outputs and 8 software assignable channels, configurable as Mic/Line Inputs or Line outputs. The processor shall have minimum 16 assignable & routable AEC channels and 16 General Purpose Inputs (GPI) x 16 General Purpose Outputs (GPO) ports. The processor shall have minimum 8x8 Dante channels and shall also support up to 128x128 Network audio channels via Dante or AES67. It shall also support SIP Softphone integration for Audio conferencing and configurable 16x16 USB Audio channels via USB-B ports supporting AV USB Bridging for software or web based conferencing applications. The processor shall also have minimum 24 bit-A/D-D/A converters, 48 kHz Sample rate, Input frequency response of 20 Hz to 20 kHz @ +21dBu, Input dynamic range > 109.5 dB at @ +24 dBu sensitivity. The processor shall support third party device control via Ethernet, RS232 and GPIO and shall have front panel display for control and indicators for device status. Third party device control can also be added as software of hardware to meet the requirement.
1029Scripting Engine Software License, Perpetual8x8 Dante License
1030UCI Deployment Software License, Perpetual
1031Network PTZ Conference camera with Min 20x optical zoom & 60 degree horizontal coverage. HDMI resolutions up to 1080p60. Image rotation controls to allow for inverted mounting using ceiling bracket. Auto exposure, auto focus and auto white balance modes. Low Noise CMOS Image Sensor, S/N Ratio = 55dB. , Video Outputs-HDMI and 3G-SDI,Ethernet-100BaseTX / 1000BaseT. Simultaneous IP Streaming, HDMI and 3G-SDI outputs. Power over Ethernet (PoE, 802.3af). Minimal Illumination: 0.5 lux at F1.8 (AGC On). S/N Ratio = 55dB.Video Resolutions HDMI / SDI:1080p 60/50/30/25. Shall include Wall mounting accessories
10328.0” PoE, IPS Touch Screen Controller with 16 million colors for Table Mounting. Resolution-1280x720, Brightness-400 Nits, Panel Orientation-Vertical / Horizontal,POE- IEEE 802.3af class 3, Aux power PSU-+24VDC @ 0.5A , Tabletop stand included. LAN -1000Mbps full-duplex RJ-45,Universal mounting accessories included. Drag & Drop designing without any programming experience.
1033Internet protocol to Serial convertor, the convertor should have LAN RJ45 Connector and RS-232 connector, It should convert control-over-ethernet signal to Serial Commands
103498" UHD Professional Display, 24x7, 3840*2160 (4K UHD), 500nits, 4000:1 Contrast Ratio
1035Cable Manager, cable manager should be made of steel or aluminium, it should have connectivity port like HDMI x1, Power x2, LAN x1 or more, Should have top with flip cover complete as required as per specification
1036Seamless HDMI Matrix Switcher, the HDMI switcher should have at least 8 HDMI input ports supporting video resolution of up to 1080p or better, it should be consist of at least 8 HDMI output ports supporting video resolution of up to 1080p or better, the switcher shall support routing of any input to any output, it should have LCD Panel to facilitate quick view of input and output routing, the switcher shall have close-to-zero second seamless switching for continuous video streams, real-time switching, and stable signal transmissions, Should have built-in or external videowall layout selection feature, should have built-in scaling engine for video resolution management, should have EDID, HDCP and CEC Support, max data rate of 6.75 Gbps or better, Should be able to control from RJ45 Ethernet port, Serial RS-232 or IR via wireless remote, Shall be Fixed or modular type matrix. Shall support operating Temprature 0 to +45 °C or better.
1037HDMI Extender, the extender should transmit HDMI signal totwisted pair/HDBaseT Receiver for HDMI,extends an HDMI connection up to 100m via a single Cat 5e/6/6a, Should transmit up to 1080p signal up to 150m via single Cat 5e/6/6a cable in long reach mode,. Data rate : 10.2 Gbps or higher. Resolution : 4K/UHD or better, HDCP 2.2 or better compliant. Input: 1x HDMI and 1x Twisted Pair output in transmitter and 1x Twisted Pair Input and Output: 1x HDMI in receiver. Should support CEC, complete as required as per specificaitons
1038Video Extender Rack Mount Kit for up to 4 Tx/Rx in 1U Space
1039HDMI Audio De-embedder, the HDMI Audio de-embedder should extract and convert Audio from HDMI input, it should repeat HDMI signal to up to 15m, should extract audio and output as additional Audio Source, should support digital optical/coaxial audio, should be HDCP Compliant, should support up to 1080p@60 signal, should have maximum Data rate of 6.75Gbps or more, should have 1x HDMI Input and 1x HDMI video output, should support audio output on 2x RCA, 1x Toslink or better complete as required as per specifications.
104015 Meter USB 3.2 Extension Cable, the cable should have data bandwidth of 5Gbps or more, should be backward compatible with USB2.0/1.1 Standards, it should be plug-and-plug cable and no software installation should be required, the cable should be active in nature to ensure high performance output even after extended usage etc complete as requried as per specification
1041Twisted Pair CAT6 Cable, the cable should support signal transmission at resolutions up to 4K including digital and analogue data, audio, and video applications, should be atleast 23AWG gauge or better, should support frequency up to 400 MHz or better, should meet performance required set by HDBaseT Alliance for AV Signal transmission over long distance, should have compliance like : RoHS, UL 1685 (CM Rated),spool of 300m etc complete as required as per specifications
104216 Port Gigabit Switch with 8 or more PoE Ports
1043Wireless Access Point
104442U 19" AV equipment Rack with all required accessories
1045Bulk Cable and connectors
1046Implementation servicesincludes - Design, Engineering,Labour, Installation, Testing and commissioning and training to users at the site to set the system up and operate the same.
1047BUILDING MANAGEMENT SYSTEMS : Server Redundant Configuration SITC of IBMS Server for loading IBMS software intel Xeon 8 core 3.8 GHz processor, min 64GB RAM, with DVD drive, V.G.A card, 2GB nvidia graphics card, 8TB HDD, network interface 1/10Gb dual port NIC, sounder card with wave file for generating alarm sounds & messages, scroll mouse, SQL license & latest operating system, 8 USB ports, serial & parallel ports as per requirement, 59" LED color monitor with 24x7 Operation
1048IBMS Client Station SITC of Desktop min 8GB RAM, with DVD drive, V.G.A card, 2GB nvidia graphics card, 1TB HDD, network interface 1/10Gb single port NIC, sounder card with wave file for generating alarm sounds & messages, scroll mouse & windows latest operating system, 6 USB ports, serial & parallel ports as per requirement. 43" LED color monitor. A3 color laser Printer
1049Building Management System(BMS) Software Web Based Graphical interface software. The system should be accessible from anywhere on LAN or WAN or Ethernet without additional licenses. Software shall have point license of min. 100,000 points (Both Hard + Soft) which can be utlized for upcoming phases and shall be capable to manage entire data points on a single server. Separate server for historical data, report generation will not be acceptable. Software should include following as minimum. 1. Alarm manager 2. Trend Manager 3. Graphics manager with 3D graphics library 4. Report Manger for genration of various reports. 5. Remote monitoring module 6. Cyber Security Manager capturing all alarms related to security not captured in Alarm Log. Software shall be cpable of running advance utility Control logic like Demand Limiting and Load Rolling to ensure energy savings. All programming tools required for commissioning of system and shall be handed over to customer with all security passwords post commissioning. Also OEM needs to confirm that quoted software is backward compatible.
1050DDC CONTROLLERS Standalone and Networkable BACnet IP DDC Controllers with 32 bit, UL & BTL (at BACnet PR 18 or higher) certified. The controllers shall be capable of standalone operationwith real time clock and historical database. The DDC"s shall be capable of peer to peer communication without help of system interface controller or PC.Controllers shall have Adaptive Control capability which measures response time and adjusts control parameters accordingly to provide optimum control. Controller shall be equipped with 2 IP ports and can be configured in Ring / Star Topology.15% spares IOs shall be available.The DDCs shall be with suitable IP 54 lockable MS enclosure complete with all wiring and accessories. a)Controller for Chiller Plant Manager
1051b) Controller for AHU system ( 2 AHU in 1 DDC)
1052c) Controller for TFA ( 2 TFA in 1 DDC)
1053d) Controller forVentilation Fans( 4 Fan in 1 DDC)
1054e) Controller for Pressurization Fans( 4 Fan in 1 DDC)
1055f) Controller for DG
1056g) Controller for HT/LT Paneland Transformer
1057h) Controller for Lifts (2 at 1 DDC)
1058i)Controller for Plumbing (3 at 1 DDC)
1059j)Controller for Overhead/Underground Tank
1060k)Controller for Fire Fighting
1061System Integrator Units / Supervisory Controller / Server Controller. SITC of Microprocessor based 64 Bit ,BTL (at BACnet PR 18 or Higher) & UL Listed Embedded Web Server Engine-cum-Network & Supervisory Controller to integrate 3rd party systems as per IO summary on various protocols like BACnet , Modbus , OPC UA, Lon, M-Bus , KNX. It should have linux OS and capable of handling10/100/1000 MBPS data bandwidth. The Web server shall allow multiple simultaneoususer access minimum 10. It should have minimum 12 GB of Memory & 2 Gb RAM. It has to be of same make of DDC controller. a) For Chiller Plant Manager on Bacnet/IP b) For AHU VFDs on Modbus RS485 (7 Points per VFD) c) For FCU on Modbus RS485 d) For Fire Alarm System on BACnet/IP e) For DG on MODbus RS485 f)For UPS on MODbus RS485 g) For Electrical System on MODbus RS485 h) For Integration of PAC on MODbus RS485 i)For LMS (Lighting Management System) on MODbus j)For Energy meters Modbus over RS485 k)VESDA Integartion on Modbus over RS485 l)Rodent Integartion on Modbus over RS485 m) BTU Meter n) VACCUM DEGASSERS o) DCIMp) Chemical Dosing Pumps q) MIscelaneous if any Note: All the Equipment must have open Protocol /Licence and it should work with Building automation system with the help of third party integrtaion.OEM will share the Mapping point to BMS vendor for integration. Selected Bidder will make sure all the equipment shall be integrate with BMS properly. No extra charges shall be paid to bidder after award of the work.Tenatative IO summary are attached in Technical specfication. Selected Bidder will update the same as per the final equipment installation.
1062Supplying, installing, testing and commissioning of the following sensors / transducers / transmitters. The DDC shall support sensor with DC 0...20 mA or 4...20 mA, DC 0 ... 10 V, LG-Ni 1000, 2x LG-Ni1000, Pt 1000 , NTC 10k, NTC 100k, 1000 Ohm. A)Outside air temperature + humidity sensors for measuring outside air temperature. It should be provided with sun sheild and rain protection.
1063b)Immersion Temprature Sensor
1064c)DP Switch for Water
1065d)Differential pressure switch for Blower and Filter Status
1066e)Differential pressure Sensor for Water
1067f)Flow Meter - 150 MM Dia
1068g)Flow Meter - 200 MM Dia
1069h)Bi Level Switch
1070i)Duct type temperature
1071j)Duct CO2 Sensor
1072k)Current Relay
1073l)Voltage Transducer
1074m)Flame Proof Level Transmitter
1075Supply, installation, testing and commissioningof hand held portable operator terminals (POT) minimum 7 inch. TFT display with capacitive touch screen type, shall be able to view graphs , alarms , parameters etc. POT shall have integrated web server and a BACnet/ IP web interface to connect a HTML5 browser to a device on the network. POT With all required connectors etcas per technical specification etc.
10762 Core 1.5 Sqmm Annealed Tinned Copper, Twisted pair , Shielded armoured cable for signal and power as per specifications
10774 Core 1.5 Sqmm Annealed Tinned Copper, Twisted pair , Shielded armoured cable for signal and power as per specifications
1078Cat-6 unarmoured cable with required jacks and points
1079HOT DIP GALVANISED GALVANISED PERFORATED TYPE CABLE TRAY 150X50X1.6MM
1080GI Flexible 25 mm
1081Supply, installation, testing and commissioning of Layer 2 switch with 24 ports (RJ-45)including SFP modules, rack mountable, SMPS power supply & other termination accessories (Like Pigtails/LIUs/ Convertors/Splicing equipment ,Patch panel, Patch Cord, Etc) complete as per specifications and as required for BMS DDC Panel Networking. The switch to switch distance shall not exceed beyond 80 meters.
1082"HVAC WORKS - HIGH SIDE EQUIPMENT AIR COOLED SCREW CHILLER Supply, installation, testing and commissioning of Imported AHRI Certified Air Cooled twin rotor semi hermetic Screw Chillers of 400 TR Actual capacity at below mentioned operating conditions with refrigerant R-134a, with multiple semi-hermetic screw compressors with dedicated VFD"s for each compressor, having independent Refrigerant circuits driven by suitable KW Sq. Cage induction motor complete with Flooded Type shell and tube Evaporator with 2/3 pass. Air cooled condenser comprising of copper tubes and copperfins with epoxy coatingor industrial grade MCHX coil with e-coating to avoid failure on account of galvanic corossion , refrigerant piping. refrigerant and Oil (First Charge). Chiller should be complete with all accessories like fow switch, isolation services vales, 19 mm insulation for evaporator,water box, suction line, electronic expansion valve,Stepless capacity control etc. Microprocessor based automatic and safety controls all mounted on a M.S. frame. Refrigerant should be factory charged complete as per specifications as per following parameter. The unit shall be BMS compatible.Chiller control panel and VFD shall have min IP 54 protection rating. Coating on condenser coils to be mandatory done from chiller OEM factory with overall 5 years warranty on any type of failure of condenser coils. All compressors and condenser fans to be provided with VFD. Chiller should be designed to operate till max 52 degc ambient temperature without tripping. Vendor to submit AHRI certified sheet for same. Thechiller packageshallalsobecompleted with micro processorbased controlpanelcomprising of all adaptivecontrols , VFD Starter on all compressorsor individual refrigerant circuits, over load& controlpowertransformer protection andnecessarycontrol wiring. Main incoming isolator, 415V+/- 10% 3 Ph 50 Hz.The water chilling machines shall be flanged connections and 1 inch spring vibration isolator mountings. The chiller control panelshould have provision to accept armoured cable or necessary cable boxes with flexible cables needs to be provided. The chiller control panel should have provision for two separate power supply option for the mainboard and UPS power supply source for Control board for quick start has to be provided for the chiller.Thecontrol panel shall incorporate BMS integrator(open protocol)for complete integration ofdata of microprocessorpanel with BMS as per the specifications. Chiller shall be provided with wire mesh. Chiller to be supplied with quick start feature" "1 set.- Matching shell and tube water cooled condenser of M.S shell and integrally finned copper tubes having multiple passes. 1 set. - Matching shell and tube flooded type chiller for screw type units of MS shell and copper tubes. 1 Lot- Refrigerant piping fittings, Suction Shut off/ Check Valve, discharge check valve, other valves and accessories to inter connect compressor, condenser, chiller and liquid level float valve/ expansion valve. 1Set- Microprocessor based control panel complete with accessories as per specifications. ChillerActual capacity may be slightly higher(Aprrox 10 to 15%) and it will be acceptedif power consumption is less. Lot- Refrigerant line accessories comprising of safety valves, angle valve, liquid line indications, liquid level control etc. Lot- Water flow switches for Evaporator, pressure gauge, thermometer, water drain & air purge valves wherever required. Lot-Suction line and chiller insulation with minimum 19mm thick polyvinyl nitrile rubber insulation finished with 0.63mm thick G.S.S cladding complete as required. Lot- Frame work for mounting the abovechiller comperessor and motor with base plate complete with anti vibration pads/ springs. Lot- Initial / first charge of refrigerant gas & compressor oil Lot- RCC / cement concrete foundation for the chilling unit. Net Capacity : 400 TR (actual)(2Working + 1Standby) Refrigerant : R-134a Complete AHRI certified unit Location : Assam
1083The chiller operating parameters shall be : Chilled water IN77.0ºF (25.0ºC) Chilled water OUT63.0ºF (17.0ºC) (Note- Chiller also to be capable of operating @ 28/18.6 deg C (In/out) profile. Chiller Fouling Factor0.0005FPS Ambient Air Temperature- 39.5 C (N=20, ASHRAE 2017 Weather data) Max Pressure drop-10 Mtr Ikw/TR at 100% load at design conditions < 1.05 Ikw/TR NPLV- Less than 0.52 Ikw/TR IPLV- Less than 0.61 Ikw/TR Min. COP @ AHRI Condition- 3.30 Note: (1) It’s a IGBC Green Rating building system, hence need higher COP or less NPLV or IPLV or IKW/TR is prefered to Improve the PUE for the Project. OEM have to submit the analysis(AdditionalCapital cost Vs payback Period) in Guwahati region for Free cooling as well as adiabatic cooling and Bidder have to consider the same in quotedprice if it suits the Project requirments.ThisNew technical features in chillers may be improve the cooling performance with reduced TCO. 400TR actual capacity Air Cooled chilling machine as described above and at above mentioned operating conditions.(2 W+ 1s) which includes Installation, testing ,commissioning,loading,Local Transportation ,all other incidental charges ,clearing,port handling,custom duty,Auxillary duty and CIF (Guwahati).(2) OEM can also offer latest falling film/flooded design for high efficiencyand min flow operation with variable primary flow system .However Direct expansion type evaporator shall be accepted if it allows flow modulation as per variable primary flow system.(3) Vendor can offer higher COP to improve PUE. . (4) Chillers in AC Plant Room may see higher temperatures due to air short recycling and heat island effect. Factory performance test can also be done at 45 deg C and more as per Lab limitation by OEM. .Kindly note OEM make sure Chiller do not trip at higher ambient conditions e.g52 deg c
1084"Supply, installation, testing and commissioning of Imported AHRI Certified Air Cooled twin rotor semi hermetic Screw Chillers of 250 TR Actual capacity at below mentioned operating conditions with refrigerant R-134a, with multiple semi-hermetic screw compressors with dedicated VFD"s for each compressor, having independent Refrigerant circuits driven by suitable KW Sq. Cage induction motor complete with Flooded Type shell and tube Evaporator with 2/3 pass. Air cooled condenser comprising of copper tubes and copperfins with epoxy coatingor industrial grade MCHX coil with e-coating to avoid failure on account of galvanic corossion, refrigerant piping. refrigerant and Oil (First Charge). Chiller should be complete with all accessories like fow switch, isolation services vales, 19 mm insulation for evaporator,water box, suction line, electronic expansion valve,Stepless capacity control etc. Microprocessor based automatic and safety controls all mounted on a M.S. frame. Refrigerant should be factory charged complete as per specifications as per following parameter. The unit shall be BMS compatible.Chiller control panel and VFD shall have min IP 54 protection rating. Coating on condenser coils to be mandatory done from chiller OEM factory with overall 5 years warranty on any type of failure of condenser coils. All compressors and condenser fans to be provided with VFD. Chiller should be designed to operate till max 52 degc ambient temperature without tripping. Vendor to submit AHRI certified sheet for same Thechiller packageshallalsobecompleted with micro processorbased controlpanelcomprising of all adaptivecontrols , VFD Starter on all compressorsor individual refrigerant circuits,, over load& controlpowertransformer protection andnecessarycontrol wiring. Main incoming isolator, 415V+/- 10% 3 Ph 50 Hz.The water chilling machines shall be flanged connections and 1 inch spring vibration isolator mountings. The chiller control panelshould have provision to accept armoured cable or necessary cable boxes with flexible cables needs to be provided. The chillercontrol panel shall incorporate BMS integrator(open protocol)for complete integration ofdata of microprocessorpanel with BMS as per the specifications. Chiller shall be provided with wire mesh. " "1 set.- Matching shell and tube water cooled condenser of M.S shell and integrally finned copper tubes having multiple passes. 1 set. - Matching shell and tube flooded type chiller for screw type units of MS shell and copper tubes. 1 Lot- Refrigerant piping fittings, Suction Shut off/ Check Valve, discharge check valve, other valves and accessories to inter connect compressor, condenser, chiller and liquid level float valve/ expansion valve. 1Set- Microprocessor based control panel complete with accessories as per specifications. ChillerActual capacity may be slightly higher(Aprrox 10 to 15%) and it will be acceptedif power consumption is less. Lot- Refrigerant line accessories comprising of safety valves, angle valve, liquid line indications, liquid level control etc. Lot- Water flow switches for Evaporator, pressure gauge, thermometer, water drain & air purge valves wherever required. Lot-Suction line and chiller insulation with minimum 19mm thick polyvinyl nitrile rubber insulation finished with 0.63mm thick G.S.S cladding complete as required. Lot- Frame work for mounting the abovechiller comperessor and motor with base plate complete with anti vibration pads/ springs. Lot- Initial / first charge of refrigerant gas & compressor oil Lot- RCC / cement concrete foundation for the chilling unit. Location : Assam
1085Net Capacity : 250 TR (actual)(1Working + 1Standby) Refrigerant : R-134a Complete AHRI certified unit The chiller operating parameters shall be : Chilled water IN54.0ºF (12.0ºC) Chilled water OUT44.0ºF (7.0ºC) Chiller Fouling Factor0.0005FPS Ambient Air Temperature- 39.5 C (N=20, ASHRAE 2017 Weather data) Max Pressure drop-10 Mtr Ikw/TR at 100% load at design conditions < 1.28 Ikw/TR NPLV- Less than 0.68 Ikw/TR IPLV- Less than 0.63Ikw/TR Min. COP @ AHRI Condition- 3.2 Note: It’s a IGBC Green Rating building system, hence need higher COP or less NPLV or IPLV or IKW/TR is prefered to Improve the PUE for the Project.OEM have to submit the analysis(AdditionalCapital cost Vs payback Period) in Guwahati region for Free cooling as well as adiabatic cooling and Bidder have to consider the same in quotedprice if it suits the Project requirments.ThisNew technical features in chillers may be improve the cooling performance with reduced TCO. 250TR actual capacity Air Cooled chilling machine as described above and at above mentioned operating conditions.(1 W+ 1s) which includes Installation, testing ,commissioning,loading,Local Transportation ,all other incidental charges ,clearing,port handling,custom duty,Auxillary duty and CIF (Guwahati).(2)OEM can also offer latest falling film/flooded design for high efficiencyand min flow operation with variable primary flow system .However Direct expansion type evaporator shall be accepted if it allows flow modulation as per variable primary flow system.(3)Vendor can offer higher COP to improve PUE. (4) Chillers in AC Plant Room may see higher temperatures due to air short recycling and heat island effect. Factory performance test can also be done at 45 deg C and more as per Lab limitation by OEM. .Kindly note OEM make sure Chiller do not trip at higher ambient conditions e.g52 deg c
1086Supply, installation, testing and commissioning of Chiller plant Manager with required DDC controller, PC and Cabling for Integrating 5 Chillers as a Working and Provision for 2 Chiller in futute with primary pump e.g 5 Pumps as a working and provison for 2 pumps in future, Motorized valves,temperature sensors, DP senors. The quote shall include Thermowells,DP sensors with copper tubing for Pumps with required cabaling and accessories all complete as required and as per final direction. Vendor will cover all the accesories cost for functional in all aspects.
1087Supply, installation, testing and commissioning of PN16 rated primary chilled water variable speed pump with CI Casing, Bronze/SS(CF8) Impeller, SS shaft, Outside/Inside fitted(internally flushing) Type balanced Mechanical Seal(to be easily replaceable without disburing the pump and motor shaft), each pump capable of delivering the specified flow rate comprising the following and complete as per specifications. Pumps shall be BMS compatible and it will not be part of chiller Skid . i) Variable Speed Vertical InlineAxial Split Coupledcentrifugal pump with motor mounted IP55 factory integrated VFD capable to vary upto 50 Hz depending upon load requirement. The Pump VFD must display all the crtical parameters like amps, volts, frequency, dynamic flow and head of each operating pump to omit the requirement of separate flowmeter to be used. ii) Suitable HP, TEFC induction motor with Efficiency IE3, 4 Pole, class `F" insulation operating on 415 + 10% volts, 3 phase, 50 cycles AC supply. Separate Pump Controller with DP Sensor/Sensorless/Wireless control to be provided with IP55 protection to maintain the redundancy in Variable Speed Pumping System(VSPS). The controller should be provided with touch screen colorful display and it should stage or destage the pumps based on Best Efficiency Point(BEP) for the optimum efficiency of Variable Speed Pumping System.Controller should be capable to modulate the two way valve at bypass line for the minimum flow requirement of the chiller.Controller should be selected to control up to 4/5 pumps including future provisions. Note: Contractor must provide necessary vibration isolation arrangement, if required. Final Pump head shall be based on approved calculation, it should be required by the bidder after award the works. Primary Chilled water pumps Water flow rate : 670 USGPM;Head : 35mWc;Motor HP : 37 kw (suggested) or as per OEM standard;Efficiency : 75 % or above;(Flow rate shall be considerd based on Proposed delta T of the chiller). Pumps as mentioned above (2W+1S)
1088Suction Guide to be provided by Pump manufacturer for unit responsibility
1089Triple Duty Valve to be provided by Pump manufacturer for unit responsibility
1090Supply, installation, testing and commissioning of PN16 rated primary chilled water variable speed pump with CI Casing, Bronze/SS(CF8) Impeller, SS shaft, Outside/Inside fitted(internally flushing) Type balanced Mechanical Seal(to be easily replaceable without disburing the pump and motor shaft), each pump capable of delivering the specified flow rate comprising the following and complete as per specifications. Pumps shall be BMS compatible and it will not be part of chiller Skid . i) Variable Speed Vertical InlineAxial Split Coupledcentrifugal pump with motor mounted IP55 factory integrated VFD capable to vary upto 50 Hz depending upon load requirement. The Pump VFD must display all the crtical parameters like amps, volts, frequency, dynamic flow and head of each operating pump to omit the requirement of separate flowmeter to be used. ii) Suitable HP, TEFC induction motor with Efficiency IE3, 4 Pole, class `F" insulation operating on 415 + 10% volts, 3 phase, 50 cycles AC supply. Separate Pump Controller with DP Sensor/Sensorless/Wireless control to be provided with IP55 protection to maintain the redundancy in Variable Speed Pumping System(VSPS). The controller should be provided with touch screen colorful display and it should stage or destage the pumps based on Best Efficiency Point(BEP) for the optimum efficiency of Variable Speed Pumping System.Controller should be capable to modulate the two way valve at bypass line for the minimum flow requirement of the chiller.Controller should be selected to control up to 4/5 pumps including future provisions. Note: Contractor must provide necessary vibration isolation arrangement, if required. Final Pump head shall be based on approved calculation, it should be required by the bidder after award the works. Primary Chilled water pumps Water flow rate : 600 USGPM;Head : 35mWc;Motor HP : 22kw (suggested)or as per OEM standard;Efficiency: 75 % or above(Flow rate shall be considerd based on Proposed delta T of the chiller). Pumps as mentioned above (1W+1S)
1091Suction Guide to be provided by Pump manufacturer for unit responsibility
1092Triple Duty Valve to be provided by Pump manufacturer for unit responsibility
1093ACTIVE PERFORFORMANCE MANAGEMENT KIT All Variable Pumps must be provided with a cloud-based annual subscription service that enables Active Performance Management. It must proactively tracks and manages pump performance and provides early diagnostic messaging, web accessible trends and analysis along with automated reports helping end customer to make performance-based decisions and take immediate action to deliver the best possible HVAC pump performance.The cloud based subscription should deliver real-time alerts, such as: 1) Alarms & warnings on excessive vibration 2) Pump in hand 3) Dead head 4) Cavitation 5) Broken Coupling 6) VFD & Motor Overheating The connectivity kits supplied by OEM/authorized representative should have ability to connect and provide real time data for upto 8 pumps in a single plant room
1094Supplying, installing, testing and commissioning of pressurised chilled water expansion tank of suitable capacity suitable for total volume of water in chilled water circuits along with necessary accessories such as centrifugal air separator, pumps etc. in order to keep chilled water system under (+) pressure and to prevent entrapment of airin the system. The tank shall be precharged steel expansion tank with replaceable heavy duty butyl rubber bladder. The tank shall have a system connection with isolation valve, drain connections with ball valves and charging valve connection to facilitate the on site charging of the tank to meet system requirement. The expansion tank and air separator shall have pressure gauges fitted with isolation valves and high capacity auto air vents with isolation valves.The system shall also include a fully automatic pressurisation unit with 2 pumps (1 Working + 1 Standby) suitable for outdoor applicaiton with pressure switch & control panel completely assembled on skid with all necessary valves & manifolds. Air seperator to be of Centrifugal type with tangential & flanged in out connections. The tank shall be fitted with lifting rings and a floor mounting skirt for vertical installation. The complete system shall be supplied and installed with all accessories and safety fixtures as per tender dwgs for proper functioning of the complete hydronic system. The tank to be provided with 32 mm thick Nitrile Rubber insulation ,After insulation it should be cladded with 26 Guage alluminium sheet all complete as required and as per the final direction and approval of the Consultants.Approx Tank capacity shall be 2500 Literand 400mm Dia Air Separtorand itshall also be calculated by selected Vendor as per submitted Tender Drawing. No cost implication are accepted after award of works.The tank and air separator must be constructedin accordance with section VIII of the ASME Boiler and pressure vessel (Unfired)code and stamped 175 PSI working pressure.
1095Supplying, installing, testing and commissioning of pressurised chilled water expansion tank of suitable capacity suitable for total volume of water in chilled water circuits along with necessary accessories such as centrifugal air separator, pumps etc. in order to keep chilled water system under (+) pressure and to prevent entrapment of airin the system. The tank shall be precharged steel expansion tank with replaceable heavy duty butyl rubber bladder. The tank shall have a system connection with isolation valve, drain connections with ball valves and charging valve connection to facilitate the on site charging of the tank to meet system requirement. The expansion tank and air separator shall have pressure gauges fitted with isolation valves and high capacity auto air vents with isolation valves.The system shall also include a fully automatic pressurisation unit with 2 pumps (1 Working + 1 Standby) suitable for outdoor applicaiton with pressure switch & control panel completely assembled on skid with all necessary valves & manifolds. Air seperator to be of Centrifugal type with tangential & flanged in out connections. The tank shall be fitted with lifting rings and a floor mounting skirt for vertical installation. The complete system shall be supplied and installed with all accessories and safety fixtures as per tender dwgs for proper functioning of the complete hydronic system. The tank to be provided with 32 mm thick Nitrile Rubber insulation ,After insulation it should be cladded with 26 Guage alluminium sheet all complete as required and as per the final direction and approval of the Consultants.Approx Tank capacity shall be 1000 Liter and 150mm Dia Air Separtor itshall also be calculated by selected Vendor as per submitted Tender Drawing. No cost implication are accepted after award of works.The tank and air separator must be constructedin accordance with section VIII of the ASME Boiler and pressure vessel (Unfired)code and stamped 175 PSI working pressure.
1096Supply, Installation, Testing & Commissioning of Buffer Tank fabricated out of 24 mm thick MS Plate, duly insulated with 50 mm thick TF quality expanded polysterene & finished with 24 SWG aluminum cladding. Tank Capacity : 30 cumt or 30KLD(2 X 15KLD) (5 min backup time) all complete as required and as per final direction.Tanks should betested for leakage at 1.5 times the rated pressure. System pressure shall beasPN16(Approx weight for buffer tank shall be 40 Ton)Bidder take final confirmation from OEM.
1097HVAC LOW SIDE : PRECISION AIR HANDLING UNITS Server Rooms at First Floors Supply of Floor Mounted, Bottom discharge, CHW type units for server room application, equiped with most advanced industry technology to operate at higher return air temperatures, guaranteeing precise control of Data Centres and server room. The units shall be selected on the basis of following parameters: i) 176.8 kW of minimum Gross Sensible Cooling Capacity @ 45500 CMH ii)34 Deg C/ 25 %to 30 % RH of return air iii) Supply air in between 21 Deg C - 22 Deg C iv) Chiller Chilled Water Temp IN/OUT 25/17 Deg C and PAHU Chilled water Temp IN/OUT 17/ 25 Deg C v) Specific Power consumption shall be low as per site design conditions including compressor, evaporator fans and condensers. (vi) Inside Condition-24 ±2 degc. The Indoor unit shall comprise of Fibreglass corrossion resistant In-floor EC fans/Inside the unit cabinet, Evaporator Cooling Coil with hydrophilic coating,Microprocessor controllers, G4 Filter,3 way valve Internal power and Control wiring, Infrared/Electrode Humidifier, Heaters, Power and Control contactors, water leak detectors and Other Electrical accessories. The unit shall be suitable for operation on 415 Volts, 50 Hz, 3 Phase, 4 Wire AC supply. Each unit should be having individual display panel, which shall display date, time, actual & set values, operating conditions, signal faults, collective faults, limiting values and PAC wellness alarm / service alarm to reduce the down time and unit memory shall hold the 400 most recent events with ID number, time and date stamp for each event. Team Mode feature for PAC units controller for synchronising the Multiple No. of units to work as single system for all above units. Load sharing mode feature;Cascading Effect;Sequencing of above Units. Units should have high efficiency and meet the ECBC ,IGBC guidelines for certification as well as to improve PUE.CRAH rating should be match as given In and out temperature and air flow rate.
1098UPS Rooms-1 and 2 at Second Floor Supply of Floor Mounted, Front/Top discharge, CHW type units for UPS room application, equiped with most advanced industry technology to operate at higher return air temperatures, guaranteeing precise control of Data Centres and server room. The units shall be selected on the basis of following parameters: i) 90.3 kW of minimum Gross Sensible Cooling Capacity @ 25000 CMH ii)34 Deg C/ 25 to 30% RH of return air iii) Supply air in between 21-22 Deg C iv) Chiller Chilled Water emp IN/OUT 25/17 Deg C and PAHU Chilled water Temp IN/OUTIN/OUT 17 /25 Deg C v) Specific Power consumption shall be low as per site design conditions including compressor, evaporator fans and condensers (vi) Inside Condition-24 ±2 degc. The Indoor unit shall comprise of Fibreglass corrossion resistant In-floor EC fans, Evaporator Cooling Coil with hydrophilic coating,Microprocessor controllers, G4 Filter,3 way valve Internal power and Control wiring, Infrared/Electrode Humidifier, Heaters, Power and Control contactors, water leak detectors and Other Electrical accessories. The unit shall be suitable for operation on 415 Volts, 50 Hz, 3 Phase, 4 Wire AC supply. Each unit should be having individual display panel, which shall display date, time, actual & set values, operating conditions, signal faults, collective faults, limiting values and PAC wellness alarm / service alarm to reduce the down time and unit memory shall hold the 400 most recent events with ID number, time and date stamp for each event. Team Mode feature for PAC units controller for synchronising the Multiple No. of units to work as single system for all above units. Load sharing mode feature;Cascading Effect;Sequencing of above Units.Units should have high efficiency and meet the ECBC ,IGBC guidelines for certification as well as to improve PUE.CRAH rating should be match as given In and out temperature and air flow rate.
1099UPS Rooms-5 at Second Floor Supply of Floor Mounted, Front/TOP discharge, CHW type units for UPS room application, equiped with most advanced industry technology to operate at higher return air temperatures, guaranteeing precise control of Data Centres and server room. The units shall be selected on the basis of following parameters: i) 17.5 kW of minimum Gross Sensible Cooling Capacity @ 6000 CMH ii)35 Deg C/ 25 to 30 % RH of return air iii) Supply air in between 21 -22 Deg iv) Chiller Chilled Water emp IN/OUT 25/17 Deg C and PAHU Chilled water Temp IN/OUT 17 /25 Deg C v) Specific Power consumption shall be low as per site design conditions including compressor, evaporator fans and condensers. (vi) Inside Condition-24 ±2 degc. The Indoor unit shall comprise of Fibreglass corrossion resistant In-floor EC fans, Evaporator Cooling Coil with hydrophilic coating,Microprocessor controllers, G4 Filter,3 way valve Internal power and Control wiring, Infrared/Electrode Humidifier, Heaters, Power and Control contactors, water leak detectors and Other Electrical accessories. The unit shall be suitable for operation on 415 Volts, 50 Hz, 3 Phase, 4 Wire AC supply. Each unit should be having individual display panel, which shall display date, time, actual & set values, operating conditions, signal faults, collective faults, limiting values and PAC wellness alarm / service alarm to reduce the down time and unit memory shall hold the 400 most recent events with ID number, time and date stamp for each event. Team Mode feature for PAC units controller for synchronising the Multiple No. of units to work as single system for all above units. Load sharing mode feature;Cascading Effect;Sequencing of above Units.Units should have high efficiency and meet the ECBC ,IGBC guidelines for certification as well as to improve PUE.CRAH rating should be match as given In and out temperature and air flow rate.
1100Server Rooms - Lowside accessories and Installation & Commissioning: SITC of Precision AC units a)Lifting, shifting & positioning of units to site b)Commissioning of the system
1101c)Incoming Copper Cabling from Incoming Isolator to CRAC Unit (@5RMT/Unit)
1102d)Condensate drain piping with GI- B class pipes (@5RMT/Unit) Notes. Provision of stabilized power supply of 415 Volts +/- 10%, 50 Hz, 3 Phase, 4 Wire along with earthing terminating into the Indoor unit starter panel / electrical PDB in Electrical Contractor scope of works. Provision of humidifier feed water within 5 Rmt of each Precision AC indoor unit. The humidifier hardness should be in the range of 100-600 ppm.It will be in Plumbing Contractor scope of works Provision of drain / condensate disposal point within 5 Rmt of each indoor unit.It will be in HVAC contractor scope of works.
1103UPS Rooms-1 and 2 : Lowside accessories and Installation & Commissioning: SITC of Precision AC units comprising of a)Lifting, shifting & positioning of units to site b)Commissioning of the system
1104c)Incoming Copper Cabling from Incoming Isolator to CRAC Unit (@5RMT/Unit)
1105d)Condensate drain piping with GI- B class pipes (@5RMT/Unit) Notes. Provision of stabilized power supply of 415 Volts +/- 10%, 50 Hz, 3 Phase, 4 Wire along with earthing terminating into the Indoor unit starter panel / electrical PDB in Electrical Contractor scope of works. Provision of humidifier feed water within 5 Rmt of each Precision AC indoor unit. The humidifier hardness should be in the range of 100-600 ppm.It will be in Plumbing Contractor scope of works Provision of drain / condensate disposal point within 5 Rmt of each indoor unit.It will be in HVAC contractor scope of works.
1106UPS Rooms-5 : Lowside accessories and Installation & Commissioning: SITC of Precision AC units comprising of a)Lifting, shifting & positioning of units to site b)Commissioning of the system
1107c)Incoming Copper Cabling from Incoming Isolator to CRAC Unit (@5RMT/Unit)
1108d)Condensate drain piping with GI- B class pipes (@5RMT/Unit) Notes. Provision of stabilized power supply of 415 Volts +/- 10%, 50 Hz, 3 Phase, 4 Wire along with earthing terminating into the Indoor unit starter panel / electrical PDB in Electrical Contractor scope of works. Provision of humidifier feed water within 5 Rmt of each Precision AC indoor unit. The humidifier hardness should be in the range of 100-600 ppm.It will be in Plumbing Contractor scope of works Provision of drain / condensate disposal point within 5 Rmt of each indoor unit.It will be in HVAC contractor scope of works.
1109Supply, Lifting, shifting, & Installation ofMS Stands for indoor PAC units with rubber pads. The frame shall be painted with one coat of metal primertwo coats rust proof Epoxy Paint. The stand shall be Height adjustable type ± 25mm for Server Room stands all complete as required and as per final direction.
1110Active tiles with volume control damper
1111Active floor pressurization system (AFPS) includes sensors as per the requirement which is to be placed beneath the floor & gives the feedback to the microprocessor of the PAC to regulate the fan speed as per the load requirement
1112Supplying, installing, testing and commissioningof ‘EUROVENT CERTIFIED’ 43 mm thick double skin construction Ceiling Suspended Air Handling Units comprising of following: EC fan section shall be equipped with a Single Inlet Centrifugal Impeller with High Efficiency Backward curved blades and external rotor EC (Electronically Commutated) motor, energy optimized for operation without spiral housing for high efficiency and favorable acoustic behavior. The high efficiency backward curved impeller made of welded aluminium sheet/ high performance composite material, with external rotor motor balanced together statically and dynamically according to DIN ISO 1940. The EC fan should be capable of being fitted in horizontal or vertical position in the AHU, depending on the application. Pre filter (MERV 8) and ESP filter (MERV-14) in supply air stream. All AHU shall be provided with one set of commissioning Pre Filters which shall be replaced with actual pre filter after testing and commissioningor flush out.All AHU with 6 row deep cooling and TFA with 8 Row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. Drain pipe dia shall be 50mm withU-trap of same size.The minimum efficiency class of the motor shall be equivalent to IE4. The motor shall be Permanent magnet external rotor motor with integrated electronics and suitable for continuous operation. The speed of the motor shall be varied with an external 0-10V/ PWM control signal. The fan in totality shall be of most efficient type so that the power Consumption and noise level is minimal. The motor shall be minimum IP54 protection class. Controller module with RS 485 port compatible with BMS, on board protocol following : 1. EC fan operation status;2. Chilled water valve operation status;3. AHU Airflow (CFM);4. AHU power consumption;Controller shall also have fire trip alarm to shut AHU in case of signal from fire panel.Instrumentation Kit to be provided to give out the following option : 1. Supply air temperature / RH; 2. Return air temperature / RH; 3. Fresh air temperature / RH; 4. Chilled water in temperature; 5. Chilled water out temperature; 6. DP switch across filter for filter clog; 7.CO2 Sensor; 8. PICV Valves.Minimum 20-25 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. The Maximum Static not more than 65 MMWG;AHU"s shall be provided with mixing box with thermal brake profile. All AHU. shall be provided with thermal break profile;All AHU shall be provided with factory fitted tested PICB Valve in AHU Casing (as per approved list of makes and specifications).;From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring fromTerminal Box to multiple direct drive motors provided by AHU vendor .All AHU shall be provided with factory fitted Electrical in AHU Casing (as per approved list of makes and specifications).Smart Air Handling unit height shall be not more than 800 mm. Ground Floor:AHU 1 (NDC Exhibition); CFM-5100; TR-11.5; Approx motor KW-3.70; Mixing Box - Yes
1113Ground Floor:AHU 2 (Electrical rrom-1); CFM-4850; TR-9.7; Approx motor KW-3.70; Mixing Box - Yes
1114Ground Floor:AHU 3 (Electrical rrom-2); CFM-4550; TR-8.9; Approx motor KW-3.70; Mixing Box - Yes
1115First Floor:AHU 5 (NOC 25 seater); CFM-2750; TR-6.9; Approx motor KW-2.20; Mixing Box - Yes
1116First Floor:AHU 6 (BMS room); CFM-2900; TR-6.7; Approx motor KW-2.20; Mixing Box - Yes
1117Second Floor:AHU 10 (Corridor TFA); CFM-1150; TR-10.0; Approx motor KW-1.00; Mixing Box - Yes
1118Third Floor:AHU 12 (SOC); CFM-2150; TR-5.9; Approx motor KW-1.50; Mixing Box - Yes
1119Fourth Floor:AHU 14,15,16 (Right side future expansion); CFM-5000; TR-12.0; Approx motor KW-3.70; Mixing Box - Yes
1120Fourth Floor:AHU 17 (Left side future expansion); CFM-6000; TR-15.0; Approx motor KW-3.70; Mixing Box - Yes
1121Fifth Floor:AHU 18,19 (Office zone A); CFM-4650; TR-9.5; Approx motor KW-3.70; Mixing Box - Yes
1122Fifth Floor:AHU 20 (Conference); CFM-2500; TR-5.7; Approx motor KW-1.50; Mixing Box - Yes
1123Fifth Floor:AHU 21 (Reception & Lobby); CFM-1500; TR-3.1; Approx motor KW-1.1; Mixing Box - Yes
1124Fifth Floor:AHU 22 (TFA); CFM-2100; TR-18.0; Approx motor KW-1.50; Mixing Box - Yes
1125Fifth Floor:AHU 24 (Pre-function); CFM-5750; TR-14.1; Approx motor KW-3.70; Mixing Box - Yes
1126Supplying, installing, testing and commissioningof ‘EUROVENT CERTIFIED’ 43 mm thick double skin construction Ceiling Suspended Air Handling Units comprising of following: backward fan section shall be equipped with a Single Inlet Centrifugal Impeller with High Efficiency Backward curved blades and direct driven motor. The high efficiency backward curved impeller made of welded aluminium sheet/ high performance composite material withPre filter (MERV 8) and ESP filter (MERV-14) in supply air stream. All AHU shall be provided with one set of commissioning Pre Filters which shall be replaced with actual pre filter after testing and commissioningor flush out.All AHU with 6 row deep cooling and TFA with 8 Row deep cooling coil unless specified otherwise. SS 304 construction end plates to be provided. Drain pipe dia shall be 50mm withU-trap of same size.The minimum efficiency class of the motor shall be equivalent to IE4.The fan in totality shall be of most efficient type so that the power Consumption and noise level is minimal. The motor shall be minimum IP54 protection class. Minimum 20-25 mm (WC) external static pressure shall be considered. However, actual total static pressure shall be calculated and confirmed by the vendor at the time of bidding. The Maximum Static not more than 65 MMWG;AHU"s shall be provided with mixing box with thermal brake profile. All AHU. shall be provided with thermal break profile; From electrical panel there shall be single input to Single AHU terminal box. All necessary internal wiring fromTerminal Box to multiple direct drive motors provided by AHU vendor.Ground Floor:AHU 4 (Lobby); CFM-6250; TR-13.5; Approx motor KW-3.70; Mixing Box - Yes
1127First Floor:AHU 7 (Lobby & NOVEC area); CFM-5750; TR-12.1; Approx motor KW-3.70; Mixing Box - Yes
1128Second Floor:AHU 9 (Lobby); CFM-5800; TR-11.9; Approx motor KW-3.70; Mixing Box - Yes
1129Third Floor:AHU 11 (Lobby); CFM-5750; TR-12.1; Approx motor KW-3.70; Mixing Box - Yes
1130Fourth Floor:AHU 13 (Lobby); CFM-5200; TR-10.9; Approx motor KW-3.70; Mixing Box - Yes
1131Second Floor:AHU 8 (Canteen); CFM-5500; TR-18.5; Approx motor KW-3.70; Mixing Box - Yes
1132Fifth Floor:AHU 23 (Office zone B); CFM-4550; TR-11.3; Approx motor KW-3.70; Mixing Box - Yes
1133Photo hydro ionization (PHI) cell based on advanced oxidation technology with broad spectrum UV tube which is enclosed by Quad metallic catalyst having hydrophillic coating enhancing the formation of Hydroxyl , superoxide ions and hydrogen-peroxide. These are known as friendly oxidizer because they revert back to oxygen & water. The Guardian Air QR+ is an in-duct air purifier capable of purifying every cubic inch of air that your central heating and air conditioning system reaches. Proven to eliminate bacteria, viruses, mold and VOCs, the Guardian QR+ is also very effective at reducing unwanted odors from cooking, cleaning chemicals, pet areas, smoke and musty air. Ground Floor:AHU 1 (NDC Exhibition); CFM-5100; TR-11.5; Approx motor KW-3.70; Mixing Box - Yes
1134Ground Floor:AHU 2 (Electrical rrom-1); CFM-4850; TR-9.7; Approx motor KW-3.70; Mixing Box - Yes
1135Ground Floor:AHU 3 (Electrical rrom-2); CFM-4550; TR-8.9; Approx motor KW-3.70; Mixing Box - Yes
1136Ground Floor:AHU 4 (Lobby); CFM-6250; TR-13.5; Approx motor KW-3.70; Mixing Box - Yes
1137First Floor:AHU 5 (NOC 25 seater); CFM-2750; TR-6.9; Approx motor KW-2.20; Mixing Box - Yes
1138First Floor:AHU 6 (BMS room); CFM-2900; TR-6.7; Approx motor KW-2.20; Mixing Box - Yes
1139First Floor:AHU 7 (Lobby & NOVEC area); CFM-5750; TR-12.1; Approx motor KW-3.70; Mixing Box - Yes
1140Second Floor:AHU 8 (Canteen); CFM-5500; TR-18.5; Approx motor KW-3.70; Mixing Box - Yes
1141Second Floor:AHU 9 (Lobby); CFM-5800; TR-11.9; Approx motor KW-3.70; Mixing Box - Yes
1142Second Floor:AHU 10 (Corridor TFA); CFM-1150; TR-10.0; Approx motor KW-1.00; Mixing Box - Yes
1143Third Floor:AHU 11 (Lobby); CFM-5750; TR-12.1; Approx motor KW-3.70; Mixing Box - Yes
1144Third Floor:AHU 12 (SOC); CFM-2150; TR-5.9; Approx motor KW-1.50; Mixing Box - Yes
1145Fourth Floor:AHU 13 (Lobby); CFM-5200; TR-10.9; Approx motor KW-3.70; Mixing Box - Yes
1146Fourth Floor:AHU 14,15,16 (Right side future expansion); CFM-5000; TR-12.0; Approx motor KW-3.70; Mixing Box - Yes
1147Fourth Floor:AHU 17 (Left side future expansion); CFM-6000; TR-15.0; Approx motor KW-3.70; Mixing Box - Yes
1148Fifth Floor:AHU 18,19 (Office zone A); CFM-4650; TR-9.5; Approx motor KW-3.70; Mixing Box - Yes
1149Fifth Floor:AHU 20 (Conference); CFM-2500; TR-5.7; Approx motor KW-1.50; Mixing Box - Yes
1150Fifth Floor:AHU 21 (Reception & Lobby); CFM-1500; TR-3.1; Approx motor KW-1.1; Mixing Box - Yes
1151Fifth Floor:AHU 22 (TFA); CFM-2100; TR-18.0; Approx motor KW-1.50; Mixing Box - Yes
1152Fifth Floor:AHU 23 (Office zone B); CFM-4550; TR-11.3; Approx motor KW-3.70; Mixing Box - Yes
1153Fifth Floor:AHU 24 (Pre-function); CFM-5750; TR-14.1; Approx motor KW-3.70; Mixing Box - Yes
1154Fan coil units shall be of Ceiling Concealed type. The unit shall comprise of multirows deep chilled water cooling coil made out of copper tubes of dia not less than 9.6mm OD having tube wall thickness not less than of 27 G (0.41mm). The cooling coil shall be complete with aluminium fins of minimum 0.2 mm thickness arranged to have a maximum fin spacing of 5 fins/cm and pressure tested for hydraulic pressure of 21 Kg/Sq.cm. Fan coil unit shall have EC fan & motor suitable for 220 ± 10 volts, 50 Hz cycle single phase power supply, maximum RPM of motor shall be 960. The blower assembly should be easily openable having provision of wing nuts. Filter media shall be Non woven synthetic type with extruded aluminium frame. Drain pan shall be of single piece deep drawn stainless steel construction and insulated with 13mm thick closed cell elastomeric insulation material.Drain connection shall be of 25mm/ 32mm dia. Side, top and bottom panels shall be of 24/22 gauge die formed galvanized steel sheet construction and shall incorporate linear adjustable holes for overhead suspension for horizontal units. The fan coil units shall be provided with factory insulated auxiliary drain pan. The fan coil unit shall be factory assembled and tested for desired output. Noise level shall not exceed a standard level. Fan coil units shall have single or two sets of cooling coils as called for in the Schedule of Quantities FCU"s type & capacity shall be as follows: Horizontal unit with cabinet (Ceiling Hung) a) 1.0 TR
1155b) 1.5 TR
1156c) 2.0 TR
1157d) 2.5 TR
1158Supplying Installation, Testing and commissioning ofCOOLING THERMOSTAT for various fan coil units/ AHU"s .Thermostat shall be electric, fixed differential cooling as specified herein, with sensing element located in the return air stream. All thermostats shall be supplied with the standard mounting boxes, complete as required.Note: The actuator shall be controlled by Building Automation System & should accept a signal of 4–20mA/ 2–10 VDC a)The thermostat shall be snap acting type with digital temparature indicator for FCU
1159b) The thermostat shall be proportionatory type for modulating 2 way valve with digital temperature indicator for Normal AHUs.
1160Supplying, installation,testing and commissioning of AXIAL FLOWFAN shall be constructed of heavy gage sheetsteel. Fancasing, motor mount and straightening vane shallbe of welded steel construction. Motor mounting plateshall beminimum15 mm thick and machinedtoreceivemotor flange ,totallyenclosed energy efficient squirrel-cage fan cooled motor ,direct or belt drive,multi sheaved pulley mounted on motorand fan shaft, belt guard, motor mount, and vibration isolators.All the smoke evacaution fans shall have class-H motor insulation complete as required.The fan shall be selected for low noise level and low RPM .Fan motor shallbe suitable for 415 + 10% volts,50cycles,3 phasepower Supply complete as required. Fans should be AMCA Certified in Air & Sound Standard). DB level should not more than 75 DB. a) Ground Floor : 3500 CFM at 40mm TSP Incase of fire Exhaust Air& Make Up air for Plumbing Pump Room
1161b) Ground Floor : 1000 CFM at 40mm TSP Incase of fire Exhaust & make up Air for STP Pump Room
1162c) Ground Floor :5500 CFM at 40mm TSP Incase of fire Exhaust Air& Make Up air for Electrical Rom-2
1163d) Ground Floor : 7000 CFM at 40mm TSP Incase of fire Exhaust Air& Make Up air for Electrical Rom-1
1164e) Second Floor : 2500 CFM at 40mm TSP Incase of fire Exhaust Airfor Second Floor Corridor
1165f) TerraceFloor : 10000 CFM at 40mm TSP for Lift Well Pressurization.
1166Supplying, installing, testing and commissioning of INLINE FANS direct/belt driven. The cabinet shall be double skin, internally acoustically lined and constructed of galvanised steel.All outdoor application fan shall be of IP 55 rating. The fan shall be DIDW with forward curve impeller fitted with maintenance free external rotor motor. The motor shall be suitable for 220±10%/415±10%(as required).Cost to include necessary switching / Starter panel (suitable for out door applications) along with,including cabling ,wiring & earthing as required volt single phase 50 cycles AC Supplying. All units shall be complete as required with duct flexible connector and volume control damper.Complete inline fan shall have min. Total static pressure of 35 mm of wg. The fan shall have low sound level exceeding not more than 40 DBA at three metre distance. a)1200 CFM
1167b)800 CFM
1168c)600 CFM
1169d)500 CFM
1170e)400 CFM
1171f)350 CFM
1172g)300 CFM
1173h)200 CFM
1174Supplying, installing, testing and commissioning of direct driven PROPELLER FANS for exhaust air as shown in drawings. Each fan shall be complete with permanent split capacitor or shaded pole motor, mounting plate, accessories like wire guard, bird screen and fixed louvers for weather protection as required. Fan selection arrangement and Electrical characteristics shall be as follows : a)450 mm dia fan suitable for 220±10% volts 50 cycles, 1 phase AC supply.
1175b)375 mm dia fan suitable for 220±10% volts 50 cycles, 1 phase AC supply.
1176c)300 mm dia fan suitable for 220±10% volts 50 cycles, 1 phase AC supply.
1177d)250 mm dia fan suitable for 220±10% volts 50 cycles, 1 phase AC supply.
1178e)150 mm dia fan suitable for 220±10% volts 50 cycles, 1 phase AC supply.
1179Hi-Wall Type Unit ( 5 Star With R-134/R-32 Refrigerant) : Supply , Installation , Testing and Commissioning of splitunits, eachcomprisingofan outdooranda single indoor unit as shown on the drawings and as per the be factoryfabricated andpaintedtoa smooth finish . Oudoor unitshallconsist of hermatically sealed/ semi- hermatic scroll/rotary compressor/s, air cooled condenserwithfan. Indoor unit shall consist offan section withdynamically balancedcentrifugal fan/s drivenbyFHP/TEFCsquirrel cage induction motor, multirows deep DX- copper cooling coilwithaluminiumfins,thermostatic expansion valve,synthetic fibrefilters,insulateddrain pan, safetycontrols, safety controls,thermostat all completeina nit. Thequotedprice shall beinclusiveoffullcharge ofrefrigerant gas, M.S Stand for Outdoor Unit/Stablizer of Suitable Ratingvibrationisolationarrangement. a)1.5 TR
1180b)1.8 TR
1181Supply, Installation, Testing & Commissioning of the Copper Refrigerant piping complete with fittings, supports, 13mm thickwith closed cell elastomeric nitrile rubber with factory laminated GC (glass clothing) insulation , as per specifications, all accessories as per specifications and drawings, any other item required to make the system complete. Nominal Dia in mm OD. a)Ø 12.7mm dia
1182b)Ø 6.4mm dia
1183Supply, Installation, Testing & Commissioning of Probe Type Flow Meter to measure the Chilled water Flow. a)200 mm dia for Chilled water Pipe.
1184b)150 mm dia for Chilled water Pipe.
1185Chemical dosing system with required Pumps (N+1) and It will be BMS compatible.
1186Design, Supply, Fabrication and errection of MS Structure and platform for mounting of air Cooled chiller, Pumps, Pressurisation System,Chemical dosing comprising ISMBs and intermediate bracings, vertical hand horizontal supports, chequered plates ( Plateform ) around equipments, requirednos of access ladders of suitable width and all necessary accessories like Nuts, Bolts, Support, Anchor faschner, studs, etc. The complete structure to be painted with one layer of anti corrosive paint followed by 2 layers of epoxy paint all complete as required and as per final direction.
1187Supplying, installing, testing and commissioning of AIR HANDLING UNITS ( FAN SECTIONS ONLY) with double skin construction as per specificatopns, each complete with squirrel cage induction motor (mounted internally), a backward fan belt drive and vibrations isolators.Motors shall be suitable for 415 +- 10% volts, 50 cycles , 3 phase AC supply an static pressure shall be as indicated . Fan-motor assembly (as whole) shall be statically & dynamically balanced to grade G6.3 as per ISO-1940/AMCA 204-3. All AHUS (Fan sections) shall be suitable for outdoor duty and complete with duct flexible connections and volume control damper . In additional all supply fans (SF) shall be provided with prefilter.TerraceFloor 3500 CFM at 40mm SP Incase of fire Exhaust Air& Make Up air for Plumbing Pump Room
1188CONTROL PANEL OF AHU (WITH DOL /SD STARTER): Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels including anchoring into the wall, wiring and earthing terminating into MCCB in each panel shall be provided by the electrical contractor. All wiring, cabling (Cu.), cable trays, GI earthing from HVAC MCC to all equipments shall be in scope of HVAC contractor.Cable should be fire survival up to 250 deg c for 1 hours.(Refer NBC-2016).All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS and Potential free contacts for Start/ stop comand through fire alarm system directly. All starters shall be provided with potential free Contact for Connections to Building Automation System & Fire Alarm System. The panel shall include the following components and accessories : MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of 20 KA.;DOL / SD starter as per HP ratings ;Terminal block for power distribution.;Contractor, over load relay with built in single phasing protection.;Phase indicating lights and indicating light for ON status.;Digital voltmeter and digital ammeter with selector switches.;Time delay relay for delayed automatic restart of air handling unit motor.;Wiring/Control wiring from fire damper panel to AHU panel to fire damper motor & for micro switch for stopping the fan when fire damper closes(as required by application);For on/off/remote and local operation, 3 pole single throw switch shall be provided in each AHU panel to facilitate override of the automatic operation.;All starters shall be provided with suitable potential free contact for connections to the Building Automation System.;3 Nos of Single Pole MCB"s Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator & as a spare.;220 / 24 V Transformer (as required by application).Note: All the control panel for AHU are marked in the HVACdrawing, Bidder shall be consider the cost of cable,GI earthing,Nos. of terminations,Cable tray etc in Control Panel head. All Wiring from Panel to HVAC equipment in HVAC contractor scope of works. The number of AHU control panels shall be as follows: a)Suitable Size MPCBup to2HP
1189b)Suitable Size MPCBup to3HP
1190c)Suitable Size MPCBup to 5HP
1191d)Suitable Size MPCB for7.5HP
1192Variable speed drives.:Supply installation Commisioning ofVFDs with Minimum IP 54 enclosures , complying with the tender specifications and having: 1. built-in dual 5% impedance DC link reactor (harmonic filters) on the positive and negative rails of the DC bus of the VFD. 2. built-in EMC Filters (electromagnetic compatibility filters) for for VFDs for restriction of conducted emissions to comply with IEC61800: 3 (unrestricted distribution):2004 Category C 3, 3.Automatic Energy Optimization / Load dependent flux optimization functionality for maximum energy savings. 6. MODBUS RTU as the communication protocol between BMS & VFDs. 7. VFDs not meeting above requirements shall provide external disconnect, additional external EMC Filters to comply with IEC61800: 3 (unrestricted distribution):2004 Category C 3 (50 m), external PLCs / DDCs to achieve 3 Feedback PID Controller functionality and external devices controlling capabilities. Supply , Install, test and commission Variable Speed Drive package as described above and in specifications suitable for up to 3.7kW motor rating as per the specifications.
1193CONTROL PANEL FOR FANS:Design, manufacture, supply, installation, testing and commissioning of the following cubicle type, dead front, sheet steel, wall mounted control panels, including anchoring into the wall, wiring terminating into MCCB and copper earthing, in each panel shall be provided by the electrical contractor.All outgoing shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS and Potential free contacts for Start/ stop comand through fire alarm system directly. All starters shall be provided with potential free Contact for Connections to Building Automation System & Fire Alarm System.All wiring, cabling (Cu.), cable trays, GI earthing from HVAC MCC to all equipments shall be in scope of HVAC contractor.Cable should be fire survival up to 250 deg c for 1 hours.(Refer NBC-2016) The panel shall include the following components & accessories:MCCB as per the ratings given below, suitable for motor duty and able to withstand fault level of20 KA;DOL / SD starter as per HP gratings given;Terminal block for power distribution as required;Contractor, over load relay with built in single phasing protection;Phase indicating lights and indicating light for `ON’ status;144 mm x 144 mm voltmeter and digital ammeter;Time delay relay for delayed automatic restart of motor;Wiring for micro switch for stopping the fan when fire damper closes (in required by application);For on/off/remote and local operation, 3 pole single throw switch shall be provided in each panel to facilitate override of the automatic operation;All starters shall be provided with suitable potential free contract for connections to the Building Automation System;All starters for Air washer & Scrubber pumps (as required) with cabling,wiring & earthing shall be included in their control panel for fans;220 / 24 V Transformer (as required by application). .Note: All the control panel for Fans are marked in the HVACdrawing, Bidder shall be consider the cost of cable,GI earthing,Nos. of terminations,Cable tray etc in Control Panel head. All Wiring from Panel to HVAC equipment in HVAC contractor scope of works. The number of control panels shall be as follows. a)Suitable Size MPCB for 1.5 HP
1194b)Suitable Size MPCB for 2HP
1195c)Suitable Size MPCB for3HP
1196d)Suitable Size MPCB for5HP
1197e)Suitable Size MPCB for7.5HP
1198f)Suitable Size MPCB for10.0HP
1199MOTOR CONTROL CENTRES FOR AIR CONDITIONING (PLANT ROOM) : Design, manufacture, supply, installation, testing and commissioning of the following cubicle type 2 mm thick sheet steel enclosed separate compartment for each feeder, front operated, rear connections indoor typeLT motor control panel, dust and vermin proof, drawout/hinged and lockable doors, complete with internal wiring, colour coding with ferrules, cable glands, bonding to earth and painting. Quoted price for each panel & motor control centre shall include all cabling & earthing over cable trays into various equipment, all associated control wiring and interlocking circuitry.Each MCC shall include cost of wiring, control wiring & inter locking between chillers, primary CHW pumps, motorized valves at chillers , flow meter & flow switch installed in de-coupler by-pass line, in order to execute the required sequence of operation.All outgoing shall be provided with Stop/Manual/ Auto/selector switch to facilitate operation through BAS. All starters shall be provided with potential free Contact for Connections to Building Automation System. All Wiring from Panel to HVAC equipment in HVAC contractor scope of works. A separate set of CTs to be provided for BAS and wiring from CT’s and voltage transducers to be brought on to separate set of terminals. A)Motor Control Centre No. 1 (415 V) consisting of :(For Data Center) : Incoming : One Nos 2500 amps 4 Pole manual drawout type incoming microprocessor based ACB complete with the following :0 - 500 volts 96 x 96 sq mm digital voltmeter with selector switch.0 -2500 amps 96 x 96 sq mm digital ammeter with 2500/5 amps CT’s and selector switchOver voltage tripping mechanism for persistent voltage exceeding 110% of the rated voltage for more than 5 minutes Phase indicating lamps, with toggle switches.TPN bus bars shall be of aluminium and shall be sleeved. Phase bus bars shall be rated at 4000 amps and neutral bus bar shall be of 50% capacity.Maximum density of aluminium bus bars for current carrying capacity shall be one amp per square mm. Outgoings : 3 No.800 amps ACB, and outgoing feeders to 3 No. 400 KW starter panel and outgoing feeders to 3 No. chilling unit compressor motor. The ACB compartment shall contain :(Including one chiller stand by)96 x96 mm sq. 0-500 Voltdigital voltmeter with selectorswitch through 415 V / v3 : 110 V /v3PTsupply from indicating light1 Set0 -(800) amps 96 x 96 sq mm digital ammeter with (800/5) amps CT’s and selector switch.1 SetOver voltage tripping mechanism for persistent voltage exceeding 110% of the rated voltage for more than 5 minutes.Phase indicating lamps, with toggle switches.TPN bus bars shall be of aluminium and shall be sleeved. Phase bus bars shall be rated at 1000 amps and neutral bus bar shall be of 50% capacity.Maximum density of aluminium bus bars for current carrying capacity shall be one amp per square mm.3 No.100 amps MCCB, 50 HP,2No. outgoing feeders to Adjustable Frequency Drive (AFD) paneover load relay with built in single phasing protection and outgoing feeders to primaryVariable chilled water pumps motors. Each of these compartment shall contain CT operated digital ammeter of 0-100 amps range with selector switch, and an indicating lamp with MCB and toggle switch for ‘ON’ status of pump motors.(Including one Pump Stand by), One Nos 800 amps 4 Pole manual drawout type incoming microprocessor based ACB to Office area Panel Incomming supply., Necessary cable alleys, space for spare switches, internal wiring, control wiring/cabling and copper earthing of all equipment shall also be included. All switches and other components shall be motor duty rating. Note: Refer HVAC TerraceLayout , all the MCC for AC plant room are marked in the drawing, Bidder shall be consider the cost of cable,GI earthing, Nos. of terminations,Cable tray etc in respective head. Motor Control Centre No. 1 as described above.
1200B)Motor Control Centre No. 2 (415 V) consisting of (For Data Center) Incoming:OneNos 2000 amps 4 Pole manual drawout type incoming microprocessor based ACB complete with the following :96 x96 mm sq. 0-500 Voltdigital voltmeter with selectorswitch through 415 V / v3 : 110 V /v3PTsupply from indicating light1 Set0 -2000 amps 96 x 96 sq mm digital ammeter with 2000/5 amps CT’s and selector switchOver voltage tripping mechanism for persistent voltage exceeding 110% of the rated voltage for more than 5 minutes Phase indicating lamps, with toggle switches.TPN bus bars shall be of aluminium and shall be sleeved. Phase bus bars shall be rated at 4000 amps and neutral bus bar shall be of 50% capacity.Maximum density of aluminium bus bars for current carrying capacity shall be one amp per square mm. Outgoings:2 No.800 amps ACB, and outgoing feeders to 2 No. 400 KW starter panel and outgoing feeders to 2 No. chilling unit compressor motor. The ACB compartment shall contain :(Space Only, starter panel shall be installed in Phase-2)0 - 500 volts 96 x 96 sq mm digital voltmeter with selector switch.0 -800 amps 96 x 96 sq mm digital ammeter with 800/5 amps CT’s and selector switchOver voltage tripping mechanism for persistent voltage exceeding 110% of the rated voltage for more than 5 minutes.Phase indicating lamps, with toggle switches.TPN bus bars shall be of aluminium and shall be sleeved. Phase bus bars shall be rated at 1000 amps and neutral bus bar shall be of 50% capacity.Maximum density of aluminium bus bars for current carrying capacity shall be one amp per square mm.2 No.100 amps MCCB, 50 HP,2No. outgoing feeders to Adjustable Frequency Drive (AFD) paneover load relay with built in single phasing protection and outgoing feeders to primaryVariable chilled water pumps motors. Each of these compartment shall contain CT operated digital ammeter of 0-100 amps range with selector switch, and an indicating lamp with MCB and toggle switch for ‘ON’ status of pump motors.(Space Only, starter panel shall be installed in Phase-2)Necessary cable alleys, space for spare switches, internal wiring, control wiring/cabling and copper earthing of all equipment shall also be included. All switches and other components shall be motor duty rating.Bus Coupler shall be rated of 2000 AMP. Motor Control Centre No. 2 as described above.MCCB’s shall be motor duty.and suitable for 35 KA (ICS) fault current.
1201C)Motor Control Centre No. 3 (415 V) consisting of :(For Office) Incoming : One No 800 amps TPN manual drawout type incoming From MCC-1 microprocessor based ACB complete with the following :0 - 500 volts 96 x 96 sq mm digital voltmeter with selector switch.0 -800 amps 96 x 96 sq mm digital ammeter with 800/5 amps CT’s and selector switchOver voltage tripping mechanism for persistent voltage exceeding 110% of the rated voltage for more than 5 minutes Phase indicating lamps, with toggle switches.TPN bus bars shall be of aluminium and shall be sleeved. Phase bus bars shall be rated at 1000 amps and neutral bus bar shall be of 50% capacity.Maximum density of aluminium bus bars for current carrying capacity shall be one amp per square mm. Outgoings :2 No.630 amps MCCB, and outgoing feeders to 2 No. 300 KW starter panel and outgoing feeders to 2 No. chilling unit compressor motor. The MCCB compartment shall contain :(Including one chiller stand by)0 - 500 volts 96 x 96 sq mm digital voltmeter with selector switch.0 -630 amps 96 x 96 sq mm digital ammeter with 630/5 amps CT’s and selector switchOver voltage tripping mechanism for persistent voltage exceeding 110% of the rated voltage for more than 5 minutes.TPN bus bars shall be of aluminium and shall be sleeved. Phase bus bars shall be rated at 800 amps and neutral bus bar shall be of 50% capacity.Maximum density of aluminium bus bars for current carrying capacity shall be one amp per square mm.2No.63 amps MCCB, 30 HP,2 No. outgoing feeders to Adjustable Frequency Drive (AFD) panel over load relay with built in single phasing protection and outgoing feeders to primaryVariable chilled water pumps motors. Each of these compartment shall contain CT operated digital ammeter of 0-63 amps range with selector switch, and an indicating lamp with MCB and toggle switch for ‘ON’ status of pump motors.(Including one Pump stand by)Necessary cable alleys, space for spare switches, internal wiring, control wiring/cabling and copper earthing of all equipment shall also be included. All switches and other components shall be motor duty rating.Motor Control Centre No. 3 as described above.MCCB’s shall be motor duty.and suitable for 35 KA (ICS) fault current.
1202Supply, Installation, Testing & Commissioning of combined Air and Dirt Separators as per the Specifications on the return water line located at the pump suction or a suitable location as suggested and suitable for (X) USGPM CHW water flow respectively.The unit should be suitable for velocity 3 m/s. The medium used to de-aerate and remove dirt shall be manufactured of Steel Tube & a mesh made of copper wire. This medium should be non clogging in nature. An automatic air vent of at least 100mm free area to be connected at the top for the release of the air separated from the water.The separator should be complete with high capacity air vent,service valve,Drain Valve etc. The Minimum Free area of the Air Vent on top should be 100mm.The performance of the air & Dirt Separator shall be confirmed by TNO report
1203Supply, installation, testing & commissioning of ball valves with out Y-Strainer complete with bronze forged body, chrome plated bronze ball and control lever etc. duly insulated to the same specifications as the connected piping and adequately supported as per specifications. a)25 mm dia
1204b)32 mm dia
1205Supply, installation, testing & commissioning of ball valves with Strainer complete with bronze forged body, chrome plated bronze ball and control lever etc. duly insulated to the same specifications as the connected piping and adequately supported as per specifications. a)25 mm dia
1206b)32 mm dia
1207Supply & Installation testing & commissioning of Vacuum Degasser to be connected as a bypass to the main water pipline in the CHW system. The Vacuum degasser shall be of automatic operation and fitted with a high efficiency multisatge pump. The degasser shall be of 150 - 325 Cubic metre degassing capacity with a capacity to degas up to 1000 Litres per hour depending upon the model selected as per the system working pressure. The Vacuum Degasser shall be BMS Compatible.
1208Supply, installation, testing and commissioning of Pot strainer as per specification. a)150 mm dia
1209b)400 mm dia
1210Supply, installation, testing and commissioning of insulated neoprene rubber expansion belows with integral reinforced rubber flanges at chiller & chilled water pumps (inlet & outlet) and duly insulated to the same specifications as the connected piping and adequately supported as per specifications. a)150 mm dia
1211b)200 mm dia
1212Supply & Installation testing & commissioning of Automatic air vent to be fitted at all high points in the CHW system made out of brass .Air High Safety margin,(distance floater –valve) min 40 mm, to protect fouling of the valve The air release system shall comprise of a solid polypropylene float not mechanically coupled to the air release valve.The valve shall be pull- spring loaded so providing positive shut off. The Air vent connection size shall be of G1/2". The Deaeration cap should be of Brass. The Valve sealing should be of Viton and float should be of PP.The Design and manufacturing should be acc. 2014/68/EU
1213DrainValve 15 MM
1214Purge Valve 15 MM
1215MOTORIZED VALVE ON/OFF Type with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN16 pressure rating for chilled / hot water circulation as specified. 25 mm Dia.
1216Clean Gas Fire Suppression Systems for HVAC Electrical Panel . For Panel detail refer MCC-1,MCC-2,MCC_3
1217Supply & Application of acoustic lining/ internalthermalinsulation of supply/return air ducting with Open cell Nitrile Rubberinsulation as perthe specifications anddrawings.15 mmthick
1218Drain Pump for Hi-Wall
1219Supplying, installing and testing of fresh air aluminium extruded louvers with VCD & bird screen) complete as per specification.
1220Supplying, installing and testing of exhaust air aluminium extruded louvers with bird screen complete as per specification.
1221Supply,Installationand Testingofextruded aluminiumpowder coated air transfer grilles to be provided at toilet doors.Size:-600 X 150 MM
1222Providing and fixing in position the following uPVC pipes for condensate drain with 25 mm thick Fire retardant closed cell elastomeric nitrile rubber insulation polybrominated diphenyl ethers(PBDEs) free with glass cloth covering and factory laminated on condensate drain piping and fitting like valves,flanges union etcas per approved shop drawings and specifications: a)65 mm dia
1223b)50 mm dia
1224c)40 mm dia
1225d)32 mm dia
1226e)25 mm dia
1227Supply Installation Testing ,Commisioningof cladding on Chilled water PipinghavingClass B (GB 8624), Class 0 (BS 476) andFlammability Index = 5 (AS1530.2). Thickness ofCladding is 350µm with a total weight =500 g/m2 made from a 3-layer composite film of metallic appearance with aluminium intermediate layer and UV protection and having a permanent curl to be applied with 30-50mm overlap using plastic rivets and manufacturer"s recommended 50mm PSA Tapescomplete as per Specifications. All bends, T-sections and end caps shall be cladded with thermoformed fittings of the same composite covering system. a)400mmDia
1228b)350mmDia
1229c)300mmDia
1230d)250mmDia
1231e)200mmDia
1232f)150mmDia
1233g)125mmDia
1234h)100mmDia
1235i)80mmDia
1236j)65mmDia
1237k)50mmDia
1238l)40mmDia
1239m)32mmDia
1240n)25mmDia
1241Supply Installation, testing and commissioning of TWOWAY MODULATING VALVES (supplied by others) provided with spring return function & fitted with modulating actuatorsin chilled & hot water lines at each air handling unit. The actuator shall have required shut off capability of minimum 4 bar rating. The valves & actuators for AHU’s shall be compatible with Building Automation System. The actuator shall be provided with interface cards to receive 0-10V or 4-20 mA signal from Building Automation System.The valve shall be suitable for following pipe sizes and provided with matching flanges and accessories. a)150 mm dia.
1242b)200 mm dia.
1243INSULATED CHILLED WATER PIPING (Nitrile Rubber Insulation) Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubberinsulation of minimum 45 Kg / m3 density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class ‘O’ insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. Note:-The Pipes of sizes 150mm & below shall be M.S. "C" class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. a)400mmDia (32 mm thick insulation)
1244b)350mmDia (32 mm thick insulation)
1245c)300mmDia (32 mm thick insulation)
1246d)250mmDia (32 mm thick insulation)
1247e)200mmDia (32 mm thick insulation)
1248f)150mmDia (32 mm thick insulation)
1249g)125mmDia(32 mm thick insulation)
1250h)100mmDia(32 mm thick insulation)
1251i)80mmDia(32 mm thick insulation)
1252j)65mmDia(32 mm thick insulation)
1253k)50mmDia(32 mm thick insulation)
1254l)40mmDia(32 mm thick insulation)
1255m)32mmDia(19 mm thick insulation)
1256n)25mmDia(19 mm thick insulation)
1257INSULATED VALVES : Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber Seal & O- RingPN 16 pressure rating for chilledwater/ hot water circulation as specified a)400mmDia
1258b)350mmDia
1259c)300mmDia
1260d)250mmDia
1261e)200mmDia
1262f)150mmDia
1263g)125mmDia
1264h)100mmDia
1265i)80mmDia
1266j)65mmDia
1267k)50mmDia
1268l)40mmDia
1269INSULATED VALVES : Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilledwater circulation as specified. a)300 mm Dia.
1270b)250 mm Dia.
1271c)200 mm Dia.
1272d)150 mm Dia.
1273e)125 mmDia
1274f)100 mmDia
1275g)80 mmDia
1276h)65 mmDia
1277i)50 mmDia
1278j)40 mmDia
1279INSULATED VALVES : Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. NON - RETURN VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for chilled / hot water circulation including insulation as specified. a)200mmDia
1280b)150mmDia
1281e)80mmDia
1282f)65mmDia
1283g)40mmDia
1284Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. a)80mmDia
1285b)65mmDia
1286c)50mmDia
1287d)40mmDia
1288Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required
1289Providing & fixing in position the mercury in glass industrial type thermometers.
1290Supply, Installation, Testing and Commissioning of following sizes electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 2 way modulating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20 mA electric signal and shall provide similar transduced feedback output to control system. Maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have pressure rating of 25 Bar minimum. a)25mmDia
1291b)32mmDia
1292c)40mmDia
1293d)50mmDia
1294e)65mmDia
1295f)80mmDia
1296Supplying, fixing, testing and commissioning of following sizes Motorized Butterfly Valve with CI Body, SS Disc, O - ring and minimum PN-16 pressure rating, conforming to BS 5155, IS 13095, with IP-55 actuator, capable of accepting upto 10V DC , and upto 20 mA electric signal and providing similar transduced feedback output to control system as required. a)400 mmdia
1297b)350 mmdia
1298c)300 mmdia
1299d)250 mmdia
1300e)200 mmdia
1301f)150mmdia
1302g)125mmdia
1303h)100mmdia
1304i)80 mmdia
1305j)65 mmdia
1306k)50 mmdia
1307Supply, installation, balancing and commissioning of factory fabricated at siteGSSsheet metal rectangular/roundducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes,hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. a)Thickness 0.63 mm sheet (24 Guage)
1308b)Thickness 0.80 mm sheet (22 Guage)
1309c)Thickness 1.0 mm sheet (20 Guage)
1310d)Thickness 1.25 mm sheet(18 Guage)
1311Supply, installation, balancing and commissioning offabricated at siteGSSsheet metal rectangular/roundducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes,hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. a)Thickness 0.63 mm sheet (24 Guage)
1312b)Thickness 0.80 mm sheet (22 Guage)
1313c)Thickness 1.00 mm sheet (24 Guage)
1314d)Thickness 1.25 mm sheet (22 Guage)
1315Supply Installation testing & commisioning of Seismic Restraints & Seismic Vibration Isolation For Non-Structural Components For Mep Equipment & Distribution, Fire Fighting Eqipment & Distribution. Qty of Supporting Wire for Angular bracing, Nut,square and Round Washer,L-Cleat,Stiffener clamp,Sleeve,Anchor fastener,Threaded Rod,Strut shall be workout by the bidder based on Tender drawings and Refer detail Technical specfication.
1316THERMAL INSULATION : Supplying, fixing acoustic lining on wall and ceiling of AHU & AC Plant Room with 50 mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction fixed in 610 mm x 610 mm frame work made of 25X50X50X50X25 mm made out of 0.6mm thick GI sheet U shaped channel and covered with reinforced fiber glass tissue and finished with 0.8 mm perforated aluminium sheet etc. complete as required and as per specifications.
1317Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (class “O”) insulation on existing duct after applying two coats of cold setting adhesive (CPRX compound). The joints shall sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required. a)19 mm thick insulation.
1318b)25 mm thick insulation.
1319Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications.
1320Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control
1321Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
1322Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
1323Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.
1324Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted.The damper shall also be closed in the event of fire signal complete as required and as per specifications. a)Fire damper
1325b)Actuator
1326CONDENSATE DRAIN PIPING : Providing and fixingGIpipes complete with GI fittings and clamps ,I/c cutting and making good the walls etc. a)50 mm dia pipes
1327b)40 mm dia pipes
1328c)32 mm dia pipes
1329d)25 mm dia pipes
1330e)20 mm dia pipes
1331f)15 mm dia pipes
1332Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a)5/6 A switch
1333b)3 pin 5/6 A socket outlet
1334Onsite Comprehensive OPERATION ANDMAINTENANCEFOR ASSAM NATIONAL DATA CENTER 2nd Year Man Power cost (After One Year of DLP)
1335Onsite Comprehensive OPERATION ANDMAINTENANCEFOR ASSAM NATIONAL DATA CENTER3rd Year Man Power cost (After One Year of DLP)
1336Comprehensive AMCFOR ASSAM NATIONAL DATA CENTER - 2nd Year cost ( After One Year DLP )
1337Comprehensive AMCFOR ASSAM NATIONAL DATA CENTER - 3rd Year cost ( After One Year DLP )
1338RATE ONLY ITEM - Cost not tobe added in Total. Onsite Comprehensive OPERATION ANDMAINTENANCEFOR ASSAM NATIONAL DATA CENTER4th Year Man Power cost (After One Year of DLP)
1339RATE ONLY ITEM - Cost not tobe added in Total. Onsite Comprehensive OPERATION ANDMAINTENANCEFOR ASSAM NATIONAL DATA CENTER 5th Year Man Power cost (After One Year of DLP).
1340RATE ONLY ITEM - Cost not tobe added in Total. Comprehensive AMCFOR ASSAM NATIONAL DATA CENTER - 4th Year cost ( After One Year DLP )
1341RATE ONLY ITEM - Cost not tobe added in Total. Comprehensive AMCFOR ASSAM NATIONAL DATA CENTER - 5th Year cost ( After One Year DLP )