| 1 | Wiring for light point / fanpoint /exhaust fan /call bell point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit with modular switch, modular plates, suitable G.I. box and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required. |
| 2 | Group C. Makes:- Legrand(Myrius),L&T(Entice), Anchor Roma(Plus). |
| 3 | Wiring for twin control light point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit with 2-way, 5/6 amps. modular switch, modular plates, suitable G.I. box and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required. |
| 4 | Group C. Makes:- Legrand(Myrius),L&T(Entice), Anchor Roma(Plus). |
| 5 | Wiring for light plug with 2x1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required. |
| 6 | Makes:- KEI/Anchor/Polycab/L&T |
| 7 | Wiring for power plug with 2x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required. |
| 8 | Makes:- KEI/Anchor/Polycab/L&T |
| 9 | Wiring for power plug with 4x4 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.4 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable for earthing as required. |
| 10 | Makes:- KEI/Anchor/Polycab/L&T |
| 11 | Wiring for circuit/sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 1 No.HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required. |
| 12 | Makes:- KEI/Anchor/Polycab/L&T |
| 13 | 2x2.5 Sq. mm. |
| 14 | 2x6 Sq. mm. |
| 15 | 2x10 Sq. mm. |
| 16 | Wiring for circuit / sub-main with 4x10 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.10 Sq.mm. (4x10+2x10) HRFRLS/PVC insulated single core copper conductor cable for earthing as required. |
| 17 | Makes:- KEI/Anchor/Polycab/L&T |
| 18 | Wiring for circuit / sub-main with 3x25+1x16 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in surface/recessed steel conduit along with 2 No.16 Sq.mm. (3x25+3x16) HRFRLS/PVC insulated single core copper conductor cable for earthing as required. |
| 19 | Makes:- KEI/Anchor/Polycab/L&T |
| 20 | Supplying and drawing following size of PVC insulated, heat resistant, flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in existing surface / recessed, Steel/PVC conduit as required. |
| 21 | Makes:- KEI/Anchor/Polycab/L&T |
| 22 | 3x1.5 Sq. mm. |
| 23 | 3x2.5 Sq. mm. |
| 24 | 3x4.0 Sq. mm. |
| 25 | Supplying and fixing following rating Modular switch /socket in the existing switch box / cover plate including connections etc. as required. |
| 26 | S.P. 5/ 6 Amps one way Modular switch. |
| 27 | Makes:- Legrand(Myrius),L&T(Entice),Anchor Roma(Plus) |
| 28 | Supplying and fixing following rating Modular switch /socket in the existing switch box / cover plate including connections etc. as required. |
| 29 | 5 pin, 5/ 6 Amps Modular socket outlet. |
| 30 | Makes:- Legrand(Myrius),L&T(Entice),Anchor Roma(Plus) |
| 31 | Telephone socket outlet, Modular. |
| 32 | Makes:- Legrand(Myrius),L&T(Entice),Anchor Roma(Plus) |
| 33 | Supplying and fixing following rating Modular switch /socket in the existing switch box / cover plate including connections etc. as required. |
| 34 | S.P. 15/ 16 Amps one way Modular switch. |
| 35 | Makes:- Legrand(Myrius),L&T(Entice),Anchor Roma(Plus) |
| 36 | Supplying and fixing following rating Modular switch /socket in the existing switch box / cover plate including connections etc. as required. |
| 37 | 6 pin,15/16 Amps Modular socket outlet. |
| 38 | Makes:- Legrand(Myrius),L&T(Entice),Anchor Roma(Plus) |
| 39 | Supplying and drawing following pair of Fire Retardant, PVC insulated 0.5 sq.mm. (FR-Flexible) copper conductor, flat, unarmoured, telephone cable in existing surface / recessed, steel / PVC conduit as required. |
| 40 | 2 Pair |
| 41 | Makes:- KEI/Anchor/Polycab/L&T |
| 42 | Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 5 pin 5/6 amps modular socket outlet and 5/6 amps, modular switch, connections etc. as required. |
| 43 | Makes:- Legrand(Myrius),L&T(Entice),Anchor Roma(Plus). |
| 44 | Supplying and fixing G.I. Modular box of (140mmx78mmx50mm) size with modular plate and cover in recess including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps, modular switch, connections etc. as required. |
| 45 | Supplying & fixing of G.I. modular boxes of following sizes along with modular base and cover platefor modular switches in recess as required:- |
| 46 | Makes:- Legrand(Myrius),L&T(Entice),Anchor Roma(Plus) |
| 47 | 2 modules (78mmx78mmx50mm) |
| 48 | 4 modules(140mmx78mmx50mm) |
| 49 | 12 modules (205mmx135mmx60mm) |
| 50 | Supplying and fixing ceiling rose on the existingjunction box / wooden blockincluding connections etc. as required. |
| 51 | Makes:- Legrand(Myrius),L&T(Entice),Anchor Roma(Plus) |
| 52 | Supplying and fixing Ding-Dong / Electronic musical bell, suitable for D.C./A.C. single phase,230 volts complete as required:- |
| 53 | Makes:- Philips/Anchor/Bajaj |
| 54 | Supplying, Installation, Testing and Commissioning of indoor s/door,Cubical type L.T.Panel. The Panel shall be compartmentalized type having space and aPolycab/L&Tangement for incoming and outgoing cables/bus ducting, switchgear, insulated and properly supported compartmentalized bus-bars, interconnection between bus bars and switchgear with auxiliary bus bars/insulated conductors/strips etc. It shall be fabricated in 14G/16G CRCA sheet, baseframe 75X40X3MM angle duly painted with Siemens GreyPowder Coated paint, Assembly Charges of 400 TPN Aluminium Busbar ( Vertical) & Earth strip throughout the length of Panel (cuPolycab/L&Tent density of Aluminium Busbar shall be 1mmx1mm=1.0 Amp.) Aluminium shall be Electric Grade E-91E, Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured codedRed, Yellow, Blue & Black. Approximate Size of PanelH- 1850 X W-1300 X D-500 MM.Assembly Charges ofAluminium/Copper solid/ Copper flexible wire interconnection Busbar to MCCB/ SWITCH & MCCB/ SWITCHto field side for Cable terminationduly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables. Control Wiring with Copper Flexible Wire (size of control wire shall be 2.5 sq. mm copper flexible for C.T. Circuit & 1.0 sq. mm for Control & 1.0sq. mmfor ScadaWiring) with thimbles printed sleeves, tie & belt etc. Assembly Charges of Accessories like Gasket, Doorlocks, Copper Flexible door earth, legend plates etc and the panel should be approved/tested from the CPRI lab and should be Comfirm I.S.64139(EVA or approved Equivalent make) |
| 55 | L.H.S. Panel (1850mm (high) x 1300mm (wide) x 500mm (deep)(Approxi) |
| 56 | MATERIAL: |
| 57 | MAIN INCOMER :-MCCB 400A 4P 36kA with O/L & S/C Protecrtion-1 No., Spreader Link 400 A 4P-2 Nos.,Changeover 400A 4P., RHOM Ext.-1 No., Amp. Meter 96x96 MM-1 No., Volt Meter 96x96 MM-1 No., Ampere Selector Switch-1 No. Voltmeter Selector Switch-1 No., CuPolycab/L&Tent transformer-3 No,Phase indicating Lamp-3 No, Control SP MCB -3No,Terminal switch -1No. |
| 58 | OUTGOING : |
| 59 | MCCB 100 A 4P 25KA -01 MCCB 63 A 4P 25 kA-03 Nos with O/L & S/C protection,Spreater Terminal Mccb 100 A & 63 A 4P 8 Nos.RHOM Ext.4Nos. |
| 60 | The Panel shall include the following Switchgear & accessories; as per the Make of Schneider, L&T, Siemens, ABB etc. |
| 61 | All interconnections of fields side are supported by conical, L & finger type insulators of adequate size to support & sustain the weight of cables, Control wiring with copper flexible FRLS wirewith thimbles, printed sleeves, tie & belt etc. |
| 62 | The prices of complete job as per the specifications above shall be inclusive ofgasket, doorlocks, reading glass,wooden, copper flexible door earth, legend plates etc. |
| 63 | Supplying, Installation, Testing and Commissioning of indoor s/door,Cubical type L.T.Panel. The Panel shall be compartmentalized type having space and aPolycab/L&Tangement for incoming and outgoing cables/bus ducting, switchgear, insulated and properly supported compartmentalized bus-bars, interconnection between bus bars and switchgear with auxiliary bus bars/insulated conductors/strips etc. It shall be fabricated in 14G/16G CRCA sheet, baseframe 75X40X3MM angle duly painted with Siemens GreyPowder Coated paint, Assembly Charges of 250 TPN Aluminium Busbar ( Vertical) & Earth strip throughout the length of Panel (cuPolycab/L&Tent density of Aluminium Busbar shall be 1mmx1mm=1.0 Amp.) Aluminium shall be Electric Grade E-91E, Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured codedRed, Yellow, Blue & Black. Approximate Size of PanelH- 1650 X W-1100 X D-350 MM.Assembly Charges ofAluminium/Copper solid/ Copper flexible wire interconnection Busbar to MCCB/ SWITCH & MCCB/ SWITCHto field side for Cable terminationduly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables. Control Wiring with Copper Flexible Wire (size of control wire shall be 2.5 sq. mm copper flexible for C.T. Circuit & 1.0 sq. mm for Control & 1.0sq. mmfor ScadaWiring) with thimbles printed sleeves, tie & belt etc. Assembly Charges of Accessories like Gasket, Doorlocks, Copper Flexible door earth, legend plates etc and the panel should be approved/tested from the CPRI lab and should be Comfirm I.S.64139(EVA /Power system & control or approved Equivalent make) |
| 64 | L.H.S. Panel (1650mm (high) x 1100mm (wide) x 350mm (deep)(Approxi) |
| 65 | MATERIAL: |
| 66 | MAIN INCOMER :-MCCB 250A 4P 36kA with O/L & S/C Protecrtion-1 No., Spreader Link 250 A 4P-2 Nos., RHOM Ext.-1 No., Amp. Meter 96x96 MM-1 No., Volt Meter 96x96 MM-1 No., Ampere Selector Switch-1 No. Voltmeter Selector Switch-1 No., CuPolycab/L&Tent transformer-3 No,Phase indicating Lamp-3 No, Control SP MCB -3No,Terminal switch -1No. |
| 67 | OUTGOING : |
| 68 | MCCB 100 A 4P 25KA -01 MCCB 63 A 4P 25 kA-03 Nos with O/L & S/C protection,Spreater Terminal Mccb 100 A & 63 A 4P 8 Nos.RHOM Ext.4Nos. |
| 69 | The Panel shall include the following Switchgear & accessories; as per the Make of Schneider, L&T, Siemens, ABB etc. |
| 70 | All interconnections of fields side are supported by conical, L & finger type insulators of adequate size to support & sustain the weight of cables, Control wiring with copper flexible FRLS wirewith thimbles, printed sleeves, tie & belt etc. |
| 71 | The prices of complete job as per the specifications above shall be inclusive ofgasket, doorlocks, reading glass,wooden, copper flexible door earth, legend plates etc. |
| 72 | Supplying, Installation, Testing and Commissioning of indoor s/door,Cubical type L.T.Panel. The Panel shall be compartmentalized type having space and aPolycab/L&Tangement for incoming and outgoing cables/bus ducting, switchgear, insulated and properly supported compartmentalized bus-bars, interconnection between bus bars and switchgear with auxiliary bus bars/insulated conductors/strips etc. It shall be fabricated in 14G/16G CRCA sheet, baseframe 75X40X3MM angle duly painted with Siemens GreyPowder Coated paint, Assembly Charges of 125 TPN Aluminium Busbar ( Vertical) & Earth strip throughout the length of Panel (cuPolycab/L&Tent density of Aluminium Busbar shall be 1mmx1mm=1.0 Amp.) Aluminium shall be Electric Grade E-91E, Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured codedRed, Yellow, Blue & Black. Approximate Size of PanelH- 1550 X W-1100 X D-350 MM.Assembly Charges ofAluminium/Copper solid/ Copper flexible wire interconnection Busbar to MCCB/ SWITCH & MCCB/ SWITCHto field side for Cable terminationduly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables. Control Wiring with Copper Flexible Wire (size of control wire shall be 2.5 sq. mm copper flexible for C.T. Circuit & 1.0 sq. mm for Control & 1.0sq. mmfor ScadaWiring) with thimbles printed sleeves, tie & belt etc. Assembly Charges of Accessories like Gasket, Doorlocks, Copper Flexible door earth, legend plates etc and the panel should be approved/tested from the CPRI lab and should be Comfirm I.S.64139(EVA or approved Equivalent make) |
| 73 | L.H.S. Panel (1550mm (high) x 1100mm (wide) x 350mm (deep)(Approxi) |
| 74 | MATERIAL: |
| 75 | MAIN INCOMER :-MCCB 125A 4P 36kA with O/L & S/C Protecrtion-1 No., Spreader Link 125 A 4P-2 Nos., RHOM Ext.-1 No., Amp. Meter 96x96 MM-1 No., Volt Meter 96x96 MM-1 No., Ampere Selector Switch-1 No. Voltmeter Selector Switch-1 No., CuPolycab/L&Tent transformer-3 No,Phase indicating Lamp-3 No, Control SP MCB -3No,Terminal switch -1No. |
| 76 | OUTGOING : |
| 77 | MCCB 100 A 4P 25KA -01 MCCB 63 A 4P 25 kA-02 Nos with O/L & S/C protection,Spreater Terminal Mccb 100 A & 63 A 4P 8 Nos.RHOM Ext.4Nos. |
| 78 | The Panel shall include the following Switchgear & accessories; as per the Make of Schneider, L&T, Siemens, ABB etc. |
| 79 | All interconnections of fields side are supported by conical, L & finger type insulators of adequate size to support & sustain the weight of cables, Control wiring with copper flexible FRLS wirewith thimbles, printed sleeves, tie & belt etc. |
| 80 | The prices of complete job as per the specifications above shall be inclusive ofgasket, doorlocks, reading glass,wooden, copper flexible door earth, legend plates etc. |
| 81 | Supplying, Installation, Testing and Commissioning of indoor s/door,Cubical type L.T.Panel. The Panel shall be compartmentalized type having space and aPolycab/L&Tangement for incoming and outgoing cables/bus ducting, switchgear, insulated and properly supported compartmentalized bus-bars, interconnection between bus bars and switchgear with auxiliary bus bars/insulated conductors/strips etc. It shall be fabricated in 14G/16G CRCA sheet, baseframe 40X40X5MM angle duly painted with Siemens GreyPowder Coated paint, Assembly Charges of100 A TPN Aluminium Busbar ( Vertical) & Earth strip throughout the length of Panel (cuPolycab/L&Tent density of Aluminium Busbar shall be 1mmx1mm=1.0 Amp.) Aluminium shall be Electric Grade E-91E, Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured codedRed, Yellow, Blue & Black. Approximate Size of PanelH- 650 X W-1500 X D-200mm Assembly Charges ofAluminium/Copper solid/ Copper flexible wire interconnection Busbar to MCCB/ SWITCH & MCCB/ SWITCHto field side for Cable terminationduly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables. Control Wiring with Copper Flexible Wire (size of control wire shall be 2.5 sq. mm copper flexible for C.T. Circuit & 1.0 sq. mm for Control & 1.0sq. mmfor ScadaWiring) with thimbles printed sleeves, tie & belt etc. Assembly Charges of Accessories like Gasket, Doorlocks, Copper Flexible door earth, legend plates etc and the panel should be approved/tested from the CPRI lab and should be Comfirm I.S.64139(EVA/Power system & control or approved Equivalent make). |
| 82 | L.H.S. Panel (650mm (high) x 1500mm (wide) x 200mm (deep)(approxi.) |
| 83 | MATERIAL: |
| 84 | MAIN INCOMER :-MCCB100A 4P 25 kA with O/L & S/C Protecrtion-1 No., Spreader Link 100 A 4P-1 Nos.,Selector Switch-1 Phase indicating Lamp-3 No, Control SP MCB -3No,Terminal switch -1No. |
| 85 | OUTGOING : |
| 86 | Space for MCB 63 A DP Isolator & Rccb MCB 6 To 32 A SP 36 nosMCB Short Bus Bar 36 Nos. |
| 87 | The Panel shall include the following Switchgear & accessories; as per the Make of Schneider, L&T, Siemens, ABB etc. |
| 88 | All interconnections of fields side are supported by conical, L & finger type insulators of adequate size to support & sustain the weight of cables, Control wiring with copper flexible FRLS wirewith thimbles, printed sleeves, tie & belt etc. |
| 89 | The prices of complete job as per the specifications above shall be inclusive ofgasket, doorlocks, reading glass,wooden, copper flexible door earth, legend plates etc. |
| 90 | Supplying, Installation, Testing and Commissioning of indoor s/door,Cubical type L.T.Panel. The Panel shall be compartmentalized type having space and aPolycab/L&Tangement for incoming and outgoing cables/bus ducting, switchgear, insulated and properly supported compartmentalized bus-bars, interconnection between bus bars and switchgear with auxiliary bus bars/insulated conductors/strips etc. It shall be fabricated in 14G/16G CRCA sheet, baseframe75X40X3MM angle duly painted with Siemens GreyPowder Coated paint, Assembly Charges of 63 A TPN Aluminium Busbar ( Vertical) & Earth strip throughout the length of Panel (cuPolycab/L&Tent density of Aluminium Busbar shall be 1mmx1mm=1.0 Amp.) Aluminium shall be Electric Grade E-91E, Busbar supports shall be DMC epoxy Insulators. All Busbars Links shall be covered/ insulated with Heat Shrinkable sleeves of coloured codedRed, Yellow, Blue & Black. Approximate Size of PanelH- 650 X W-1500 D-200mm Assembly Charges ofAluminium/Copper solid/ Copper flexible wire interconnection Busbar to MCCB/ SWITCH & MCCB/ SWITCHto field side for Cable terminationduly covered/ insulated with Heat Shrinkable sleeves of coloured coded Red, Yellow, Blue & Black. All Interconnections of fields side are supported by conical, L & Finger type insulators of adequate size to support & sustain the weight of cables. Control Wiring with Copper Flexible Wire (size of control wire shall be 2.5 sq. mm copper flexible for C.T. Circuit & 1.0 sq. mm for Control & 1.0sq. mmfor ScadaWiring) with thimbles printed sleeves, tie & belt etc. Assembly Charges of Accessories like Gasket, Doorlocks, Copper Flexible door earth, legend plates etc.and the panel should be approved/tested from the CPRI Lab and should confirm I.S.64139(EVA /Power system & control or approved equivalent make) |
| 91 | L.H.S. Panel (650mm (high) x 1500mm (wide) x 200mm (deep)(approxi.) |
| 92 | MATERIAL: |
| 93 | MAIN INCOMER :-MCCB63 A 4P 25 kA with O/L & S/C Protecrtion-1 No., Spreader Link 63A 4P-1 Nos.,Selector Switch-1 Phase indicating Lamp-3 No, Control SP MCB -3No,Terminal switch -1No. |
| 94 | OUTGOING : |
| 95 | Space for MCB 63 A DP Isolator & Rccb MCB 6 To 32 A SP 36 nosMCB Short Bus Bar 36 Nos. |
| 96 | The Panel shall include the following Switchgear & accessories; as per the Make of Schneider, L&T, Siemens, ABB etc. |
| 97 | All interconnections of fields side are supported by conical, L & finger type insulators of adequate size to support & sustain the weight of cables, Control wiring with copper flexible FRLS wirewith thimbles, printed sleeves, tie & belt etc. |
| 98 | The prices of complete job as per the specifications above shall be inclusive ofgasket, doorlocks, reading glass,wooden, copper flexible door earth, legend plates etc. |
| 99 | Supplyinganderection of 6amps. to 32 amps. rating, 10 KA breaking capacity, 240volts, \"C\" curves, miniaturecircuit breaker of following poles in the existing MCB DB complete with connections etc. as required:- |
| 100 | Single pole. Cat-A. |
| 101 | Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 102 | 40 Amps. Cat-A. |
| 103 | Makes:- L&T/Legrand/Schneider. |
| 104 | 63 Amps. Cat-A. |
| 105 | Makes:- L&T/Legrand/Schneider. |
| 106 | Supplying and fixing following rating, double pole (single phase & neutral) 240 volts, residual cuPolycab/L&Tent circuit breaker (RCCB), having a sensitivity cuPolycab/L&Tent up to 300 miliampers in the existing MCB DB complete with connections, testing and commissioning etc. as required. |
| 107 | 40 Amps. Cat-A. |
| 108 | Makes:- L&T/Legrand/Schneider. |
| 109 | 63 Amps. Cat-A. |
| 110 | Makes:- L&T/Legrand/Schneider. |
| 111 | Supplyingand fixingoffollowingway, singlepoleandneutral sheetsteel MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus- bar, wire-set, neutral link, earth bar, din-bar, detachable gland plate, blanking plate, cable, identification labels interconnections, phosphatized and powder painted, including earthing etc. as required:- |
| 112 | Makes:- L&T/Legrand/Schneider. |
| 113 | Double door-4 way |
| 114 | Double door-6 way |
| 115 | Double door-12 way |
| 116 | Double door-16 way |
| 117 | ProvidingInstallation testing and commissionning of ceiling fan with socket size modular steo type electronicfanregulator including wiring the down rods of standardlengh (Up to20 cm) with 16/0.20 mmtwin twisted flexible,cotton braided copper cable,includingproviding and fixing phenolic laminated sheet cover on the fan box and earting etc. as required. |
| 118 | Ceiling Fan 1200 mm sweep, Category-AMakes:-Usha Striker/Crompton/Bajaj. |
| 119 | Ceiling Fan 1400 mm sweep, Category-A Makes:-Usha Striker/Crompton/ Bajaj. |
| 120 | Providing and installation of exhaust fan of following sizes in the existing opening, including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required:- |
| 121 | Exhaust Fan, Light duty, (Domestic) 300 mm sweep Makes:-Usha/Crompton/Bajaj. |
| 122 | Supplying and fixing surface mounting 2\"x2\" size LED solution suitable for surface application with the use of the latest technology 45 Watt (4500 lumen) 6000K and it should be compatible with specifications i.e. power factor = 0.9, harmonic distortion = 10% and efficacy = 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz complete with all accessories, connections, testing and commissioning etc. as required. |
| 123 | LED 45Watt, 2\"x2\" on Surface |
| 124 | Make :-PanasonicPCRM01458(Square)/Philips/ Wipro/Havell or equivalent. |
| 125 | Supplying and fixing surface /Recess mounting 1\"x4\" size LED solution suitable for surface application with the use of the latest technology 40 Watt (4000 lumen) 6000K and it should be compatible with specifications i.e. power factor = 0.9, harmonic distortion = 10% and efficacy = 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz complete with all accessories, connections, testing and commissioning etc. as required. |
| 126 | LED 40 Watt, 1\"x4\" Panel Surface/Recess. |
| 127 | Make :-Panasonic -PBLM06404(1X4) (Square)/Philips/Wipro/Havell or equivalent. |
| 128 | Supplying and fixing surface round type LED 20 Watt (2000 lumen), 6000K and it should be compatible with specifications i.e.power factor = 0.9, harmonic distortion = 10% and efficacy = 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz complete with all accessories, connections, testing and commissioning etc. |
| 129 | LED 20 Watt round on surface mounted |
| 130 | Make :-Panasonic-PDLM10206P 20 W(Round) /Philips/Wipro/Havell or equivalent. |
| 131 | Supplying and fixing surface Square type LED 20 Watt (2000 lumen), 6000K and it should be compatible with specifications i.e.power factor = 0.9, harmonic distortion = 10% and efficacy = 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz complete with all accessories, connections, testing and commissioning etc. |
| 132 | LED 20 Watt Square on surface mounted |
| 133 | Make :-Panasonic-PDLM11206P 20 W (Square)/ Philips/Wipro/Havell or equivalent. |
| 134 | Providing and fixing decorative extruded tube fixture having high quality design suitable for LED tube up to20Watt (2000 lumen) 6000K and it should be compatible with specifications i.e. power factor = 0.9, harmonic distortion = 10% and efficacy = 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz,including one no. tube rod 20 Watt complete with all accessories, connections, testing and commissioning etc. as required. |
| 135 | LED Aluminium Batton20W(4Feet Long) |
| 136 | Make :-Panasonic PBTM08208-20W-Tube Light 4 Feet Long))/Philips/Wipro/Havell or equivalent. |
| 137 | Supplying and fixing surface Square type LED 15 Watt (1500 lumen), 6000K and it should be compatible with specifications i.e.power factor = 0.9, harmonic distortion = 10% and efficacy = 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz complete with all accessories, connections, testing and commissioning etc. |
| 138 | LED 15 Watt Square on surface mounted |
| 139 | Make :-Panasonic -PDLM11 156P 15W (Square)/ Philips/Wipro/Havell or equivalent. |
| 140 | Supplying and fixing Bulk Head LED 10 Watt (1000 lumens), 6500K and it should be compatible with specifications i.e.power factor = 0.9, harmonic distortion = 10% and efficacy = 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz complete with all accessories, connections, testing and commissioning etc. |
| 141 | LED 10 Watt Bulk Head on surface/recess mounted |
| 142 | Make :-Panasonic (PBHM01107-10W)(Bulk Head)/ Philips/Wipro/Havell or equivalent. |
| 143 | Supplying and fixing LED Street Light solution suitable for StreetLightapplication with the use of the latest technology 30 Watt (3000 lumen) 6000K and it should be compatible with specifications i.e. power factor = 0.9, harmonic distortion = 10% and efficacy = 100 lumens per watt, CRI > 80, suitable for input voltage AC 220-240V, 50/60 Hz complete with all accessories, connections, testing and commissioning with G.I.pipe 35 mm dia. Bracket with nuts and boltsetc. as required complete in all respects. |
| 144 | LED Street Light 30 Watt |
| 145 | Makes:-Panasonicl(Cat No. :-PSTM16308/Philips/ Havell/Wipro or eqivalent. |
| 146 | Earthing with copperearth plate 600 mmx600 mmx 3 mm thick, including accessories and providing masonry enclosure with cover plate having locking aPolycab/L&Tangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required. |
| 147 | Extra for using salt and charcoal for G.I. or copper plate earth electrode complete as required. |
| 148 | Providing and fixing 8 SWG (4 mm dia.) copperwire on surface or in recess for loop earthing as required. |
| 149 | Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for vertical run) |
| 150 | Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for horizontal run) |
| 151 | Providing and fixing of lightning conductor finial, made of 25 mm dia. 300 mm long copper tube, having single prong at top, with 85 mm dia 3 mm thick copper base plate including holes etc. complete as required. |
| 152 | Providing and laying of one No. aluminium conductor, PVC insulated and PVCsheathed, armoured/XLPE power cable, working voltage 1100 volts grade direct in ground; to be laid 1 meter below the ground level including excavation and refilling the trench etc.as required, but excluding sand cushioning and protective covering:- |
| 153 | Makes:- KEI/Havell/Polycab. |
| 154 | Armoured cable 70 sq. mm (3.5 core) |
| 155 | Armoured cable 185 sq. mm (3.5 core) |
| 156 | Armoured cable 400 sq. mm (3.5 core) |
| 157 | Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVCsheathed, armoured/XLPE power cable, working voltage 1100 volts gradeon surface etc. of the required size:- |
| 158 | Makes:- KEI/Havell/Polycab. |
| 159 | Armoured cable 70 sq. mm (3.5 core) |
| 160 | Armoured cable 185 sq. mm (3.5 core) |
| 161 | Armoured cable 400 sq. mm (3.5 core) |
| 162 | Supplying and fixing of G.I.pipe class \"A\" 80 mm dia. as required complete in all respects |
| 163 | Supplying and fixing of G.I.pipe medium class 32 mm dia. as required complete in all respects |
| 164 | Supplying and fixing of following sizes of steel conduit along with the accessories in surface / recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required:- |
| 165 | 25 mm. dia |
| 166 | Supplying and fixing of following sizes of PVC conduit along with the accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required:- |
| 167 | 25 mm. dia |
| 168 | Makes: Diplast, BEC, Finolex. |
| 169 | Supplying and fixing of following sizes of PVC conduit along with the accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required:- |
| 170 | 50 mm. dia |
| 171 | Makes: Diplast, BEC, Finolex. |
| 172 | Providing and fixing extra conduit down rod of 20mm dia. x60 cmwith 16/0.20 mm twin twisted flexible, cotton braided, copper cable including painting, connections etc. as required. ( Note: More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored). |
| 173 | Supplying and drawing LAN cable CAT 6E, solid copper conductorprotected with PVC sheath in the existing surface / recessed, steel / PVC conduit as required. |
| 174 | UTP Cat 6 Computer LAN Cable with star Seprator Makes:- Havell/KEI/L&T |
| 175 | Supplying and fixing following rating Modular switch/socket in the existing switch box/cover plate including connections etc.as required |
| 176 | Socket 10 A/25Amps. Combined Makes;-L&T/Legrand/Anchor. |
| 177 | Providing and fixing TP&N switch disconnector fuse unit cubical type, 415/500 volts with 3 No. HBC/HRC fuses, in sheet steel enclosure including drilling holes on the board, connections, earthing the bodyetc. as required. |
| 178 | 32 Amp. Category-A Makes:- L&T/Legrand/ Schneider. |