Assam Electronics Development Corporation Limited-AMTRON has published Procurement Installation And Commissioning Of Fire Fighting Equipments Refer Rfp. Submission Date for this Tender is 13-12-2021. Fire Fighting Consumable Tenders in Tech City Bongara Assam. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 16-Nov-2021 | Date Extension | Date | 26-11-2021 |
2 | 20-Nov-2021 | Date extension_2 | Date | 29-11-2021 |
3 | 23-Nov-2021 | Date Extension_3 | Date | 08-12-2021 |
4 | 01-Dec-2021 | Date extension_4 | Date | 13-12-2021 |
5 | 09-Dec-2021 | Clause and Appendix-III Amendments | Technical Bid | 13-12-2021 |
Sl. No. | Item Description |
1 | FIRE PROTECTION SCHEDULE ITEMS |
2 | PUMPS |
3 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required: (a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. (b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-"F" insulation, conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Suitable cement concrete foundation duly plastered with anti-vibration pads. |
4 | 2850 lpm at 88 m Head Note: *The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point. |
5 | Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520. Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered |
6 | 2850 lpm at 88 m Head Note: * The head of the pump is selected in a manner so as to give a minimum 3.5kgf/cm2 pressure at the highest/farthest point. |
7 | Supplying, installation, testing and commissioning of electric driven pressurization pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-"F" insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti-vibration pads. |
8 | 180 lpm at 88 m Head |
9 | CONTROL PANELS |
10 | Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required: |
11 | Incomings: 630A, 50kA 4 Pole MCCB, Ics=100% Icu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-630 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 800Amps |
12 | Outgoings (Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) |
13 | Main Fire Pump 200 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets |
14 | Jockey Pump 100 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. - 2 sets |
15 | Diesel Engine Control Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specification |
16 | PIPES & ACCESSORIES |
17 | Providing laying, testing & commissioning of "C" class heavy duty MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. |
18 | 200 mm. dia (wall thickness = 6.3 mm) |
19 | 150 mm. Dia |
20 | Providing, laying, testing & commissioning of "C" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
21 | 25 mm dia |
22 | 32 mm dia |
23 | 40 mm dia |
24 | 50 mm dia |
25 | 65 mm dia |
26 | 80 mm dia |
27 | 100 mm dia |
28 | 150 mm dia |
29 | 200 mm dia (wall thickness 6.3 mm) |
30 | 250 mm dia (wall thickness 6.3 mm) |
31 | 300 mm dia (wall thickness 7.1 mm) |
32 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : |
33 | Single headed Gunmetal |
34 | Single headed Stainless steel |
35 | Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required : |
36 | Single headed Gunmetal |
37 | Single headed Stainless steel |
38 | Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
39 | 40 mm dia |
40 | 50mm dia |
41 | 65 mm dia |
42 | 80 mm dia |
43 | 100 mm dia |
44 | 150 mm dia |
45 | 200 mm dia |
46 | 250 mm dia |
47 | 300 mm dia |
48 | Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required : |
49 | 40mm dia |
50 | 50 mm dia |
51 | 65mm dia |
52 | 80mm dia |
53 | 100mm dia |
54 | 150mm dia |
55 | 200mm dia |
56 | 250mm dia |
57 | 300mm dia |
58 | Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required. |
59 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : |
60 | 40mm dia |
61 | 50mm dia |
62 | 65mm dia |
63 | 80mm dia |
64 | 100mm dia |
65 | 125mm dia |
66 | 150mm dia |
67 | 200mm dia |
68 | 250mm dia |
69 | 300mm dia |
70 | Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. |
71 | 80 mm dia |
72 | 100mm dia |
73 | 150mm dia |
74 | 200mm dia |
75 | 250mm dia |
76 | 300mm dia |
77 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : |
78 | Gun Metal |
79 | Stainless Steel (Grade 304) |
80 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. |
81 | 30 m |
82 | 40 m |
83 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : |
84 | Gun metal |
85 | Stainless Steel (Grade 304) |
86 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : |
87 | 2 way-100 mm dia M.S. Pipe |
88 | 4 way - 150 mm dia M.S. Pipe |
89 | 3 way - 150 mm dia M.S. Pipe |
90 | Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required. |
91 | Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : |
92 | Pendent Sprinkler |
93 | Upright Sprinkler |
94 | Horizontal side wall sprinkler |
95 | Concealed sprinkler |
96 | Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required. |
97 | Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required. |
98 | 100mm dia |
99 | 150mm dia |
100 | Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required : |
101 | 80mm dia |
102 | 100mm dia |
103 | 150mm dia |
104 | Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. |
105 | 700mm |
106 | 1000mm |
107 | 1200mm |
108 | 1500mm |
109 | Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required. |
110 | FIRE DETECTION SCHEDULE ITEMS |
111 | Micro processor based. Intelligent Addressable Main Fire alarm panel , Central Processing Unit ,with the following loop module and with each loop capacity of 120 detector per loop with total of 240 detectors and devices with loop length up to 2 kmtr, network communication card, minimum 320 character graphics,LCD display with touch screen or other keypad and 1000 event history logs in the non volatile memory (EEPROM) power supply unit at 230+ 5 % V, 48 Hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout logs and facility to have integration with analog voice evacuation system( which is part of the schedule of work under SH: PA System) and shall be complete with all accessories . The panel should be compatible for integration with IBMS system with open protocol Bacnet/IP , complete as per specs and as required for following loops. |
112 | 10 Loop Control Panel having CPU with 640 character display including backlite LCD display qwerty programming and operating manuals, supporting 1 to 10 signaling line circuits (upto 5 extendable cards & supporting 103 network modes) complete as required. Control and expander moudules. Dress Plate. Battery dress plate. Chassis low profile. Dress Panel blanck covers. BACnet protocol. |
113 | Two Loop Control Panel having CPU with 640 character display including backlite LCD display qwerty programming and operating manuals, supporting 1 to 10 signaling line circuits (upto 5 extendable cards & supporting 103 network modes) complete as required. Control and expander moudules. Dress Plate. Battery dress plate. Chassis low profile. Dress Panel blanck covers. BACnet protocol. |
114 | Central graphical fire alarm management system i/c software |
115 | 320 character LCD display repeater panel. |
116 | Intelligent photothermal detector |
117 | Response indicator on surface/recessed MS Box having two LED’s metallic covers complete with all connections etc. |
118 | Intelligent addressable programmable sounder. |
119 | Cost of fault isolator complete with base |
120 | Cost of intelligent aspiration detector |
121 | Cost of intelligent addressable thermal detector |
122 | Cost of control module |
123 | Cost of addressable fire phone control module |
124 | Cost of addressable beam detector with remote test features |
125 | Cost of intelligent duct detector unit with photothermal detector complete with base |
126 | Cost of manual call point |
127 | Cost of Horn cum strobe |
128 | Cost of Strobe. |
129 | Cost of fire fighter telephone handset |
130 | Intelligent interface unit BACnet protocol for communication link between building management system and fire alarm control panel. |
131 | Cost of fire fighter phone jack |
132 | 6 Zone, voice alarm controller with USB, MP3, AM/FM player (including zone button paging station). |
133 | Cost of 1.5/3/6W Ceiling Speaker |
134 | Cost of 1.5/3/6W Metal Ceiling Speakers. |
135 | Cost of wall mounted loud speaker, 3/1.5 Watt in ABS enclosure |
136 | Cost of 2 watt, 70 Volts ceiling speaker. |
137 | Cost of Digital audio amplifier 50 Watt 25VRMS operating of 240 Volt AC Supply. |
138 | Digital audio amplifier 75 Watt 25VRMS operating of 240 Volt AC Supply. |
139 | Cost of Exit point directional sound speaker with voice and integral audio amplifier with selectable sound pulse patterns |
140 | Cost of Digital voice command keypad |
141 | Cost of 25 mm Outer dia PVC/ABS Pipe with end caps including making air sampling operning of appropriate dia on appropriate interval. |
142 | Cost of Fire Survival armoured cable,Fibre glass tape wrapped, ZH inner, outer sheath 2x1.5 Sq. mm cable. |
143 | Cost of Fire alarm armoured FRLS cable 2 x 1.5 sqmm |
144 | Speaker cable of following pairs ,cores and size of PVC insulated FRLS copper conductor cable with LHC in the existing surface / recessed steel conduit / PVC casing and capping including connections etc. |
145 | Cost of single pair 2-core 48/0.2 mm, speaker cable |
146 | Supply, instalation, testing & commissionig of Addressable monitoring module to connect NO/NC contacts such as pressure switch, flow switches, fire pump contacts (provided by Fire fighting contractor). Panel shall be located at Security room and reception area.Approved Make:VIGNARTA (APOLLO) / RAVEL/NOTIFIRE |
147 | Supply, instalation, testing & commissionig of Addressable control relay modules having potential free contact (1NO+1NC) for trippingfor 230 volt for AHU , Lift, PA, ACS, Pressurissation fans, smoke extraction fans Approved Make: Approved Make:VIGNARTA (APOLLO) / RAVEL/NOTIFIRE |
148 | PA SYSTEM |
149 | Supplying, installing, testing and commissioning solid state Amplifier of 1000 W RMS out put in rack, including necessary control wires, jocks etc. complete. |
150 | Supplying, installing, testing and commissioning of P.A. Console 8 zone shall expandable up to 60 zones , with priority module micro processor based, mixing amplifier, with 6 zone for suitable selection module, power supply unit & goose neck micro phone etc. |
151 | Supplying, installing, testing and commissioning of P.A. Call station of 8 zones with priority module micro processor based & goose neck micro phone etc shall be located in the reception / security for the announcement necessary communication cable/CAT 6 shall be considered form PA controller to call station . |
152 | Supplying, installing, testing and commissioning of 19" Rack 650mm depth, 16U high amplifier rack assembly made of aluminum channel equivalent to euro rack system, with side and rear panels made of 14 swg powder coated sheet steel front transparent persplexdoor and with rails, rollers & bearings. Fans shall provided at the top for ventilation side panels will be ventilated type. The rack shall be powder coatedof approved color and spare "U" shall be covered with blank panels. |
153 | NON SCHEDULE ITEMS FOR FIRE PROTECTION SYSTEM |
154 | Supply, Providing & fixing 150 mm dial type Pressure gauge of (0-16kg/cm2) range with gun metal shut off cock etc. duly calibrated before installation in MKS and FPS units and fixing the same where required as directed including all fittings, short piece, nipples, elbows testing the joints etc.all complete. (Quantity of this item will be payable only where it has not been included in the relevant composite items). |
155 | Providing and fixing exhaust, Diesel engine driven pump exhaust M. S. pipe class ’B’ of suitable dia (150mm dia) for the engine including fitting like flanges, bends, reducers, etc. The pipe shall be provided with 12 mm thick supercera ceramic fibre rope, 21 gauge, necessary excavation, fixing of silencer connections at engine exhaust, necessary supports, back filling, cutting and making good, bird proof and weather proof flap complete in all respect as directed. Structural support made by angle / channel - measurement shall be taken separately. |
156 | 150 mm dia |
157 | Providing & fixing double flanged flexicon rubber expansion (bellows) joint with unit control of standard length as per maufacturers specifications suitable for working pressure of 15Kg/Sqcm including rubber gaskets, flanges, nuts, bolts and washers complete as required for suction and delivery of pumps. |
158 | a) 200 NB |
159 | b) 150 NB |
160 | c) 65 NB |
161 | d) 50 NB |
162 | Providing and installation of GM Ball Valve, IS-318 LTB-2 SS Stem AISI 410, Ball SS 304/CF8, teflon gland packing, screwed female threads to IS-554, |
163 | a) 25 NB |
164 | Providing and Installation of vibration eliminationpads for pumps. |
165 | a) Type A (for Jockey pumps) |
166 | b) Type B ( Mainfire pumps) |
167 | Gun-metal Fire brigade suction hose coupling (Draw-out Connection) with nut for female coupling as per IS:902-1974 complete with 100 mm dia. MS suction pipe and 100 mm dia. 1 No. CI foot valve flanged (to be connected to static water tank). |
168 | Providing & Fixing of C.I. Foot Valve of following sizes and complete in all respect with all labour, tools & plants, transportation, taxes, levies etc. and as per specification, drawing and direction of Engineer-in-charge. |
169 | 100mm NB |
170 | L.T.Cables |
171 | Supply, installation, testing and commissioning of following sizes of PVC sheathed XLPE insulated Aluminium Conductor/ power/control armoured cables of 1100V grade on surface of wall or in existing cable trays with fixing hardware etc. as required. |
172 | Aluminium Conductor armoured cables: |
173 | 3.5 x 120 Sq mm |
174 | 3.5 x 70 Sq mm |
175 | 3.5 C x 4 Sq.mm |
176 | 4 C x 4 Sq.mm |
177 | 4 C x 2.5 Sq.mm |
178 | Cable Termination : |
179 | Supply &making end termination with brass Double compression glands for the following XLPE insulated PVC sheathed 1100 V grade cable including cost of crimping lugs/ ferrules, compression glands, solder, cable sockets, insulation tape etc. complete as reqd. |
180 | Suitable for aluminium conductor armoured cables: |
181 | 3.5 x 120 Sq mm |
182 | 3.5 x 70Sq mm |
183 | 3.5 C x 4 Sq.mm |
184 | 3.5 C x 4 Sq.mm |
185 | 3.5 C x 2.5 Sq.mm |
186 | EARTHING |
187 | Supply, installation, testing & commissioning of following size G.I. Strip/G.I. wire clamped to existing cable tray, wall for system/equipment earthing complete as required including interconnection etc. |
188 | 25mm*6mm G.I Strip |
189 | 8 SWG . G.I wire |
190 | Providing and fixing RCC Hume Pipe NP 3 as per IS: 458 (For Road Crossing) / HDPE SN-8 |
191 | 300 mm dia |
192 | Air release valve complete with 25 mm dia. brass air valve (ball valve, pressure gauge type), 25 mm dia brass stop cock, nipple, tees, B46 elbow, pipe and all accessories as required including fixing brackets. |
193 | Providing and fixing 5 mm thick glass door (with M.S. frame) of size 2100mm x 900mm with center opening for fire hose cabinet. Suitably marked on the outside with the letters "FIRE HOSE" including locking arrangement. All M.S. work to be in Red P.O. colour over appropriate primer. |
194 | Air release valve complete with 25 mm dia brass air valve with ball valve, nipple, tees, elbow, pipe and all accessories as required. |
195 | Supply, Installation of Structural steel (Angle & Channel) for supporting purpose for pipe dia 100 mm dia and above. |
196 | FIRE EXTINGUISHERS & SIGNAGES |
197 | Providing& fixing Water based Carbon-di-oxide 9 ltrs. fire extinguishers as per IS specification consisting of welded MS cylindrical body ,squeeze lever discharge valve fitted with internaldischarge tube ,30 cm long high pressure discharge hose ,discharge nozzle,suspension brackets,finished exteranally with red enemel paint and fixed to wall with brackets with rawl plug/dash fastners complete with initial charging. |
198 | Providing& fixing ABC type(Dry powder type ) extinguishers. Including all accessories as per IS specification (IS :15683) Consisting of welded MS cylindrical body with discharge hose ,discharge valve ,suspension brackets,initial filling etc. complete as required., initial filling etc complete as required. Capacity - 6 kg |
199 | MECHANICAL FOAM type extinguishers 9 ltrs capacity as oer IS specifications. For fire & plumbing pump room |
200 | Trolly mounted co2 22.5 ltrs FOR DG ROOM, TRANSFORMER ROOM OR PUMP ROOM |
201 | Trolly mounted mech foam 50 ltrs FOR DG ROOM, TRANSFORMER ROOM OR PUMP ROOM |
202 | SIGNAGES |
203 | Supply and installation in position the "FIRE EXIT" Sign with luminicent colour having size 300 x 100 mm |
204 | Supply and fixing in position the signages " FIRE ORDER" contain the following matter on 3 mm thick "Opaque" PVC foam board of computerised cut, PVC non-reflective self adhesive vinyle painted foam board of size 1200 x 1000 mm. |
205 | ALERT THE SECURITY AT SECURITY ROOM BY ACTUATING MANUAL CALL POINT LOCATED AT STRATEGIC LOCATION. |
206 | EVACUATE THE OCCUPANTS BY USING FIRE EXIT AND EMERGENCY EXITS ONLY AND ASSEMBLE AT ASSEMBLY POINTS. |
207 | BE CALM AND DO NOT GET PANIC, WALK DO NOT RUN |
208 | IF POSSIBLE TRY TO EXTINGUISH FIREBY USING NEAREST / SUITABLE PORTABLE EXTINGUISHER OR WATER FROM NEAREST HOSE REEL/ HYDRANT VALVE. |