Sales : +91-777 804 8217
| Sl. No. | Item Description |
| 1 | Earthwork in excavation in foundation trenches in ordinary soil (vide classification of soil item-A) and disposal of excavated earth as obtained to a distance upto 50 M. including all lifts, levelling, ramming the foudation trenches, removing roots of trees, shrubs all complete as per approved design, building specification and direction of E/l. |
| 2 | Extra for earthwork in hard soil as per specification and direction of E/l (vide classification of soil item-B) |
| 3 | Earth filling in foundation trenches and plinth in layers not exceeding 150 mm. thick well watered, rammed, fully compacted and fine dressed with earth obtained from excavation of foundation frenches within a lead of 50 M. and lift of 1.5 M all complete as per building specification and direction of E/l (Mode of measurement compacted volume). |
| 4 | Providing coarse clean sand in filling in foundation trenches or in plinth including ramming and watering in layers not exceeding 150mm thick with all leads and lifts including\" cost of all materials, labour, royalty and taxes all complete as per building specification and direction of E/l (Mode of measurement complacted volume). |
| 5 | Providing designation 75 B brick work in C.M. (1:6) in foundation and plinth with approved quality of clean coarse sand of F.M. 2 to 2.5 including providing 10mm thick mortar joints, cost of screening materials, raking out joints to 15mm depth, curing, taxes and royalty all complete as per building specification and direction of E/l. |
| 6 | Providing designation 125 mm thick reinforced designation 75 A brick work in C.M (1:4) in superstructure with approved quality of clean coarse sand of F.M. 2 to 2.5 including the cost of screening, carriage of materials , scafolding, raking out joints to 15 mm depth, curing, taxes and royalty ( but excluding the cost of reinforcement) all complete as per building specification and direction of E/l. |
| 7 | Providing designation 100A brick work with fly ash lime brick (FLAG) confirming to IS 12894-1990 (9\" x 4.5\" x 3\") in C.M. (1:6) in superstructure with approved quality of clean sand of F.M. 2 to 2.5 including providing 10mm thick mortar joints, cost of screening materials, raking out joints to 15mm depth, curing, taxes and royalty all complete as per building specification and direction of E/I. |
| 8 | Providing 112mm thick reinforced designation 100A brickwork fly ash lime brick (FLAG) confirming to IS 12894-1990 (9\" x 4.5\" x 3\") in C.M. (1:4) in superstructure with approved quality of clean sand of F.M. 2 to 2.5 including the cost of screening carriage of material scaffolfing raking out joint to 15mm depth curing taxes and royalty (but excluding the cost of reinforcement ) all complete as per building specification and direction of E/I. |
| 9 | Extraforbrick workfor eachconsecutive floor abovefirst floor including watering and scafolding, all complete as per direction of E/l. |
| 10 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : |
| 11 | 1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size) |
| 12 | 1:3:6 (1 Cement : 3 coarse sand (zone-III) : 6 graded stone aggregate 20 mm nominal size) |
| 13 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size) |
| 14 | Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement: 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including finishing the top smooth. |
| 15 | Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :1:1.5:3 (1 cement : 1.5 coarse sand (zone-III): 3 graded stone aggregate 20 mm nominal size) |
| 16 | Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. above plinth level up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement :1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) : 3 graded stone aggregate 20 mm nominal size) |
| 17 | Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcementwith 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III): 3 graded stone aggregate 20 mm nominal size). |
| 18 | Centering and shuttering including strutting, propping etc. and removal of form for : |
| 19 | Foundations, footings, bases of columns, etc. for mass concrete |
| 20 | Suspended floors, roofs, landings, balconies and access platform |
| 21 | Lintels, beams, plinth beams, girders, bressumers and cantilevers |
| 22 | Columns, Pillars, Piers, Abutments, Posts and Struts |
| 23 | Stairs, (excluding landings) |
| 24 | Weather shade, Chajjas, corbels etc., including edge |
| 25 | Supplying, fitting and fixing 35mm thick solid core type decorative single leaf flush door shutter with both sides decorative veneered with black board core bended with high quality phenol formal dehydes synthetic resin of standard make with Aluminium fittings such as hinges, tower bolts, handle, cleats and sand blocks and taxes all complete as per building specification and direction of E/l. |
| 26 | Supplying, fitting and fixing 35mm thick solid core type decorative double leaf flush door shutter with both sides decorative veneered with black board core bended with high quality phenol formal dehydes synthetic resin of standard make with Aluminium fittings such as hinges, tower bolts, handle, cleats and sand blocks and taxes all complete as per building specification and direction of E/l. |
| 27 | Providing Tor steel reinforcement of 8mm. dia. rods as per approved design and drawing with cutting, bending and binding with annealed wire with cost of wire, removal of rust placing the rods in position all complete as per building specification and direction of E/l. TMTFe 500 ( Only valid for Tata (Tiscon), SAIL, JSPL, Electrosteel Steels Ltd.. Bokaro, and Vizag (RINL). |
| 28 | Providing Tor steel reinforcement of 10mm. ,12mm & 16mm dia. bars as per approved design and drawing with cutting, bending and binding with annealed wire with cost of wire, removal of rust placing the rods in position all complete as per building specification and direction of E/l. |
| 29 | (a) 10mm TMTFe 500 ( Only valid for Tata (Tiscon), SAIL, JSPL, Electrosteel Steels Ltd.. Bokaro, and Vizag (RINL). |
| 30 | (b) 12mm TMTFe 500 ( Only valid for Tata (Tiscon), SAIL, JSPL, Electrosteel Steels Ltd.. Bokaro, and Vizag (RINL). |
| 31 | (c) 16mm TMTFe 500 ( Only valid for Tata (Tiscon), SAIL, JSPL, Electrosteel Steels Ltd.. Bokaro, and Vizag (RINL). |
| 32 | Providing Tor steel reinforcement of 20mm. 25mm. 28 mm, 32mm dia. bars as per approved design and drawing with cutting, bending and binding with annealed wire with cost of wire, removal of rust placing the rods in position all complete as per building specification and direction of E/l. |
| 33 | Supplying, fitting and fixing M.S. grill made of 20x6mm M.S. flat as per approved design and drawing, properly fabricated with joints continuous fillet welded and finished smooth , carriage of grill to work site, hoisting as per building specification and direction of E/l. (where materials is not supplied by the deptt.) |
| 34 | Supplying, fitting and fixing callapsible gate of approved size and make properly fabricated with vertical double channels 20 x 10 x 2 mm at 100mm. centres and braced with M.S. flat diagonals 20 x 3mm with top and bottom rails of T.iron 40x40x6mm with 38mm dia steel pulleys complete with bolts, nuts, locking arrangements, stoppers, handles, including applying a priming coat of red lead paint, carriage , hoisting and taxes all complete as per building specification and direction of E/l. |
| 35 | Supplying, fitting and fixing M.S. grill gate with M.S. grills made of 20x6mm M.S. flats or 16mm square bars fitted on 25x25x6mm M.S Angle frame including cost of fabrication , providing necessary locking arrangement with haskal and domny duly fixed in P.C.C. (1:2:4) blocks of required size, applying a priming red lead paint over steel work, taxes all complete as per drawing specification and direction of E/l. (where steel is not supplied by the deptt.) |
| 36 | Providing designation 75B one brick flat soling joints filled with local sand including cost of watering taxes royalty all complete as per building specification and direction of E/l. |
| 37 | Providing 12 mm cement plaster (1:3) with clean coarse sand of F.M 1.5 with floating coat of neat cement in skirting including rounding of junctions with floor, curring, taxes and royalty all complete as per building specification and direction of E/l. |
| 38 | Providing and laying Double charged vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less then 0.08% and conforming to IS: 15622/ISO 13006 of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4 (1 cement:4 Coarse sand0, jointing with grey cement slurry @ 3.3 kg/sqm including grouting the joints with wite cement and matching pigments etc, complete Size of tiles 600 x 600 mm. |
| 39 | Providing 12mm cement plaster (1:3) with clean coarse sand of F.M. 1.5 including screening, curingwithall leadsand liftsof water, scaffolding taxes and royalty all complete as per building specification and direction of E/l. |
| 40 | Providing 12mm cement plaster (1:6) with clean coarse sand of F.M. 1.5 including screening, curingwithall leadsand liftsof water, scaffolding taxes and royalty all complete as per building specification and direction of E/l. |
| 41 | Providing 6mm thick cement plaster (1:4) in ceiling with clean coarse sand of F.M. 1.5including screening, curingwithall leadsand liftsof water, scaffolding taxes and royalty all complete as per building specification and direction of E/l. |
| 42 | Providing 1.5mm cement punning including curing, carriage of water with all leads and lifts as per building specification and direction of E/l. |
| 43 | Extra for plaster work over exterior surface for each consecutive floor above first floor including cost of scaffolding etc. all complete as per direction of E/l. |
| 44 | Making 6x6mm grooves in plaster surface over walls truely horizontal or verical as specified at regular intervals, at all heights including cleaning, finishing scaffoding and curing with all leads and lifts of water all complete as per building specification and direction of E/l. |
| 45 | Providing two coats of oil bound distemper of approved shade and make over a coat of cement primer over new surface including preparing the plastered surface by rubbing smooth with pumice stone or fine sand paper, applying putty wherever required, scaffolding, washing of floors and taxes all complete as per building specification and direction of E/l. |
| 46 | Providing two coats of snowcem of approved shade and make over a coat of cement primer on new surface including preparing the plastered surface smooth with sand paper, scaffolding, curing and taxes all complete as per building specification and direction of E/l. |
| 47 | Supplying, fitting and fixing 30mm thick solid core type decorative single leaf flush door shutter with one sides teak decorative and another side commercial veneered with black board core bended with high quality phenol formal dehydes synthetic resin of standard make with Aluminium fittings such as hinges, tower bolts, handle, cleats and sand blocks and taxes all complete as per building specification and direction of E/l. |
| 48 | Providing primer one coat of red lead paint of approved make over new steel surface including preparing the surface after cleaning, removing rust , dirt, , scales , smokes and grease and cleaning the surface thoroughly including cost of scaffolding and taxes all complete as per building specification and direction of E/l. ( Mode of measurement Area shall be multiplied by the co-efficient as indicated in building specification) |
| 49 | Providing two coats of synthetic enamel paint of approved shade and make over steel surface including cleaning the surface thoroughly, scaffolding and taxes all complete as per building specification and direciton of E/l. |
| 50 | Providing 250mm. wide brick drain in cement mortar (1:6) with av. 250mm. clear depth and 250mm. apron including cost of earthwork involved with 75 mm. ~ cement concrete (1:4:8) over one brick designation 75A flat soling in proper grade and slope at the base, the drain duly plastered in C.M.(1:3) with punning over exposed surface all complete as per building specification and direction of E/l. |
| 51 | Water proofing for old and New Roof Slab :- Providing and laying water proofing treatment on roof slab by applying two Component, factory designed, ready to use, acrylic modified flextble material brush, roller or spray for water proofing coating per manufacturer Specifications with following steps :-(a)surface preparation .-Providing and cleaning of concrete surface to remove dust, oil, grease including removal of existing (loose paint / coating, and cement laitance by cleaning with compressed air water jet including all materials, labour, tools complete. Ponding test to be done after plugging all outlets and to be checked from soffit to identify seepage leakage. On identification of seepage cement grouting to be donewith non shrink expanding admixture of Sika India Pvt.L.td.) MYK Schomberg / Dr Fixiti/ Fosroc or equivallent. Providing and reparing of all Corner and joints such as those between the parapet wall and the roof slab etc shall be chamfered with 150Mrn X 150 mm fillet of mortar (Cement: sand - 1:4) admixed with acrylic pc?\" lymer of Sika/ Fosroc/MYK Schomberg/Dr1:4) admixed with acrylic polymer of Sika/ Fosroc/MYK Schomberg/Dr Fixit or equivalent.,Befor \"Chamfering a prime coat shall be given with the slurry of acrylic polymer Repairing surface irregularities, damaged concretein base slab, dead cracks if any, with an acrylic polymer modified repair mortar-including a coat of bonding agent of the same with cement slurry including all material, labour, tools complete.(b)lst Coat :- Apply 1st coat of two component acrylic modified, ready to use, flexible cementitiot.is material on surface saturated dry roof and inside wall of Parapet.Wall upto 600 mm by brush or roller . After 1st coat of application , 45 gsm of Fibre glass cloth to lay when the first layer is still green. 1st coat shOUld be applied @1.50 kg/Sqmt/coat. For the purpose of measurer-11609-1\"e entire treated surface will be measured.\" (c) 2nd Coat :-To apply the 2nd coat of two component acrylic modified read to use, flexible cementtiOus material right angle to the 1st. coat over the glass fibre laid surface: 2nd coat-,should be applied @ 0.7 Sqmt/coat. For the purpose of measurement the entire treated surface will be measured.\" After three days of drying the 2nd coat , the rain water outlets to be plugged and ponding test to be done for 48 hours to identify seepage, leakage from soffit and if found necessary rectification to be done as per satisfaction of E/C. The waterproof coating to be protected from damage before screed over it. Water proofingBrand:- Sika Topseal 109hi / Fosroc Brushbond RFXI Dr. Fixit Pidiffin 2K / MYK Aquafin TG . Product Performance - Chemical Base Part A: Acrylic copolymer, Part B: Specially graded cementitious powder - Density 1.6 kg/I (mixed density) at +27°C Tensile Strength -2Nimm2 after 28 days (with Fibre cloth) (According to ASTM D 2370) Pullout BondSiren th -2 f\l/mm2 concrete failure Accordin\" to ISO4624) Slant-Shear Bond Strength -4 Nimm2 (According to FIP 5.15) Elongation at Break -35% Without Fibre Cloth and 20% with Fibre Cloth (According to ASTM D 2370) (d) )Protection of treated surface with PCG :- The treated surface should be covered with 25mm/50mm F\"CC of M-20 grade (1.1.5:3). with proper slope ( 1:120) towards the rain outlets in alternate panels of 2 mt x 2 mt keeping 6 rnm gap between the panel joint. Integral water proofing admixture conforming to IS 2645 co of 100 ml per bag of of cement to be added in the screed concreie(paid separately.for this items).All corners shall be chamfered with 150mm X 150 mm fillet. The rainwater outlets shall be just leveled with the screed concrete to ensure smooth discharge of water - the peripheral gaps between pvc pipe outlet and concrete surface should be packed prorSeqswith ridti:corict\"ete and the peripheral mouth to be sealed with,moisture insensitive epoxy putty of. Sika India .Pvt.Ltd. / MYK Schornbefg /Dr Fixit/Fosroc .For the purpose of measurement the entire treated surface will be measured.\" (e)Groove of PCCsurface should be filled with POlysulphide Sealant.(Paid Separately). Be d - Sika India Pvt.Ltd. / MYK Schomberg / Dr Fixit/Fosroc . Warranty for five years. |
| 52 | Covering of treated surface with PCC:-providing 25 mm thick Cement Concrete M20 (1:1:5:3) maintaining slope in alternate 2 mtx 2mt panels With approved quality of stone chips of 20mm to 6 mm size graded andCleaned sand of F.M.2.5 to 3 including screening, shuttering, and mixing Cement concrete in mixer with admixture of integral water proofing and Placing in position, striking curing, taxes and royalty all complete as per Building specification and direction of E/I. Panels that has been left should Be casted next day. There should be 6 mm gap between panels .brand-Sika _ plastocrate plus, MYK proof WP 10, Fosroc- ConplastX 421 ic DrFixit Pidiproof LM+ |
| 53 | Providing and mixing liquid integral water proffing compound in conctrete of plaster as manufacturer specification and as per direction of engineer in charge. Brand. Sika plastocrate plus, MYK proff WP 10, Fosroc-Conplast x 4211C, Dr.Fixit, Pidiproff LW+ or Equivalent |
| 54 | Providing and filling of 6 mm thick Groove between 25 mm PCC Panels with Polysuiphide Sealant (Porin.g Grade)as per drawings and technical specificationsi6nd direction of E in Charge. (with 18% GST) B rand Sika Polysulphide, Fosrpc-Thioflex 600 Dr. Fixit Pidiseal PS(42P. MY K Seal PS or Euivalent. |
| 55 | Embankment Construction with Material Obtained from Borrow Pits (Construction ofembankment with approved material obtained from borrow pits with all lifts and leads, transporting to site, spreading, grading to required slope and compacting to meet requirement of table 300-2) Rolling with smooth wheeled roller |
| 56 | Granular Sub-base with Close Graded Material (Table:- 400-1) By Mix in Place Method (Construction of granular sub-base by providing close graded material, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at OMC, and compacting with vibratory roller toachieve the desired density, complete as per clause 401) for grading- IIMaterial |
| 57 | Wet Mix Macadam (Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC inmechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver in sub- base / base course on well prepared surface and compacting with vibratory rollerto achieve the desired density.) WITH SMOOTH 3 WHEELED STEEL ROLLER |
| 58 | Prime coat (Providing and applying primer coat with bitumen emulsion on prepared surface of granular Base including clearing of road surface and spraying primer at the rate of 0.60 kg/sqm using mechanical means.) |
| 59 | Tack coat Providing and applying tack coat with bitumen emulsion using emulsion pressure distributor at the rate of 0.20 kg per sqm on the prepared bituminous/granular surface cleaned withmechanical broom. |
| 60 | Dense Graded Bituminous Macadam (Providing and laying dense bituminous macadam with 100- 120 TPH batch type HMP producing an average output of 75 tonnes per hour using crushed aggregates of specified grading, premixed with bituminous binder @ 4.0 to 4.5% by weight of total mix of mix and filler, transporting the hot mix to work site, laying with a hydrostatic paver inisher with sensor control to the required grade, level and alignment, rolling with smoothwheeled, vibratory and tandem rollers to achieve the desired compaction as per MoRTH specification clause No. 507 complete in all respects.) with VG-30 Grade Bulk Bitumen.for GradingII(19 mm nominal size) |
| 61 | Bituminous Concrete (Providing and laying bituminous concrete with 100-120 TPH batch type hot mix plant producing an average output of 75 tonnes per hour using crushed aggregates of specified grading, premixed with bituminous binder @ 5.4 to 5.6 % of mix and filler, transporting the hot mix to work site, laying with a hydrostatic paver finisher with sensor control to the required grade, level and alignment, rolling with smooth wheeled, vibratory and tandem rollers to achieve the desired compaction as per MORTH specification clause No. 509 complete in all respects) for Grading-II(10 mm nominal size) |
| 62 | Road Marking with Hot Applied Thermoplastic Compound with Reflectorising Glass Beads on Bituminous Surface (Providing and laying of hot applied thermoplastic compound 2.5 mm thick including reflectorising glass beads @ 250 gms per sqm area, thickness of 2.5 mm is exclusive of surface applied glass beads as per IRC:35 .The finished surface to be level, uniform and free from streaks and holes.) |
| 63 | Retro- reflectorised Traffic signs (Providing and fixing of retro- reflectorised cautionary, mandatory and informatory sign as per IRC :67 made of encapsulated lens type reflective sheeting vide clause 801.3, fixed over aluminium sheeting, 1.5 mm thick supported on a mild steel angle iron post 75 mm x 75 mm x 6 mm firmly fixed to the ground by means of properlydesigned foundation with M15 grade cement concrete 45 cm x 45 cm x 60 cm, 60 cm below ground level as per approved drawing 80 mm x 60 mm rectangular ) |
| 64 | Earthwork in stripping by hydraulic M/C in grade A and B type soil inculding morrom soil, soil mixed with kankar, pebbles, boulders upto size 300 mm size and dispossal of the same same along with all organic materials in the country side beyond 1.0 km upto 2.0 km km in all by tipper including construction and maintenance of haul road etc. all complete as per specification and direction of engineer in charge. |
| 65 | Cost of Driling 200mm x 165mm x 125 mtr.deep bore well in all kind of Soil and rock in rural area for instalation of pump set with Hydrolic DTH Rig machine all complete including all materials, tools,driling rig,air compressureand equipmentsas well as fule, lubricantsand cost of transportation of rig machine annd other vehical up to Site. |
| 66 | (a) From 0.00 M to 50.00 M below G.L. |
| 67 | (b) From 51.0 M to125.00 M |
| 68 | (c) From126.0 M to150.00 M |
| 69 | Supplying submersible pump sets confirming to IS 8034 and motor confirming to IS 9283. Pump shall be suitable for various delivery head and discharge with stainless steel pump shaft and polypropylene/noryl impeller. Motor suitable for working on 415V + 10%, 3PH, 50 Hz, A.C. supply with cable guard, thurst carbon/fiber bearing to withstand entire hydraulic thurst, water proof winding shall be provided. The pump set shall be suitable for direct coupling. Pump shall have suitable outlet as per manufacturers design. Anti thurst stream lined non return valve shall be provided with pump, 3 metre submersible copper conductor cable in single/double run shall be provided with each pump.Submersible pump set 100mm dia (with Polypropylene/Noryl Impeller) up to 20 stages2 HP |
| 70 | Supplying fitting and fixing Flat flexible submersible cable with, copper conductor PVC insulated and PVC sheathed. 3 core 4 sq.mm |
| 71 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. Granite work |
| 72 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. |
| 73 | Providing and fixing factory made P.V.C. door frame of size 50x47 mm with awall thickness of 5 mm, made out of extruded 5mm rigid PVC foam sheet, mitred at corners and joined with 2 Nos of 150 mm long brackets of 15x15 mm M.S. square tube, the vertical door frame profiles to be reinforced with 19x19 mm M.S. square tube of 19 gauge, EPDM rubber gasket weather seal to be provided through out the frame. The door frame to be fixed to the wall using M.S. screws of 65/100 mm size, complete as per manufacturer’s specification and direction of Engineerin-Charge. |
| 74 | Providing and fixing factory made panel PVC door shutter consisting of frame made out of M.S. tubes of 19 gauge thickness and size of 19 mm x 19 mm for styles and 15x15 mm for top & bottom rails. M.S. frame shall have a coat of steel primers of approved make and manufacture. M.S. frame covered with 5 mm thick heat moulded PVC \"C\" channel of size 30 mm thickness, 70 mm width out of which 50 mm shall be flat and 20 mm shall be tapered in 45 degree angle on both side forming styles and 5 mm thick, 95 mm wide PVC sheet out of which 75mm shall be flat and 20 mm shall be tapered in 45 degree on the inner side to form top and bottom rail and 115 mm wide PVC sheet out of which 75 mm shall be flat and 20 mm shall be tapered on both sides to form lock rail. Top, bottom and lock rails shall be provided both side of the panel. 10 mm (5 mm x 2 ) thick, 20 mm wide cross PVC sheet be provided as gap insert for top rail & bottom rail, paneling of 5 mm thick both side PVC sheet to be fitted in the M.S. frame welded/ sealed to the styles & rails with 7 mm (5 mm+2 mm) thick x 15 mm wide PVC sheet beading on inner side, and joined together with solvent cement adhesive. An additional 5 mm thick PVC strip of 20 mm width is to be stuck on the interior side of the \"C\" Channel using PVC solvent adhesive etc. complete as per direction of Engineer-in-charge, manufacturer\"s specification & drawing. 30 mm thick pre laminated PVC door shutters |
| 75 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. |
| 76 | Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge: Profile C Fixing with adjustable lugs with split end tail to each jamb |
| 77 | Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing. |
| 78 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-incharge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.). |
| 79 | Chequerred precast cement concrete tiles 22 mm thick in footpath & courtyard, jointed with neat cement slurry mixed with pigment to match the shade of tiles, including rubbing and cleaning etc. complete, on 20 mm thick bed of cement mortar 1:4 (1 cement: 4 coarse sand).Light shade pigment using white cement |
| 80 | Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab, including rubbing and polishing complete with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) : 25 mm thick |
| 81 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. |
| 82 | Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqmincluding pointing the joints with white cement and matching pigments etc., complete. |
| 83 | Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes. |
| 84 | 75 mm diameter |
| 85 | 110 mm diameter |
| 86 | Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. |
| 87 | Bend 87.5° 110 mm bend |
| 88 | Shoe (Plain) 110 mm Shoe |
| 89 | Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete. |
| 90 | 75 mm |
| 91 | 110 mm |
| 92 | Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineerin-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. |
| 93 | Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete : |
| 94 | Gutter (600 mm over all girth) |
| 95 | Ridges plain (500 - 600mm) |
| 96 | Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade: New work (Two or more coats applied @ 1.43 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) |
| 97 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. |
| 98 | Supplying at site Angle iron post & strut of required size including bottom to be split and bent at right angle in opposite direction for 10 cm length and drilling holes upto 10 mm dia. etc. complete. |
| 99 | Providing and fixing concertina coil fencing with punched tape concertina coil 600 mm dia 10 metre openable length ( total length 90 m), having 50 nos rounds per 6 metre length, upto 3 m height of wall with existing angle iron \"Y\" shaped placed 2.4m or 3.00 m apart and with 9 horizontal R.B.T. reinforced barbed wire, stud tied with G.I. staples and G.I. clips to retain horizontal, including necessary bolts or G.I. barbed wire tied to angle iron, all complete as per direction of Engineer-in-charge, with reinforced barbed tape(R.B.T.) / Spring core (2.5mm thick) wire of high tensile strength of 165 kg/ sq.mm with tape (0.52 mm thick) and weight 43.478 gm/ metre (cost of M.S. angle, C.C. blocks shall be paid separately) |
| 100 | Providing and laying 60mm thick faciory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50mm thick compacted bed of coarse sand, filling the joints with line sand etc. all complete as per the direction of Engineer-in-charge. |
| 101 | Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge). |
| 102 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: White Vitreous China Wash basin size 630x450 mm with a single 15 mm C.P. brass pillar tap |
| 103 | Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS:13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : Kitchen sink with drain board 510x1040 mm bowl depth 178 mm |
| 104 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. Flexible pipe 32 mm dia |
| 105 | Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing : Circular shape 450 mm dia |
| 106 | Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings arrangement of approved quality and colour, weighing not less than 88 gms. |
| 107 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. |
| 108 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931 :15 mm nominal bore |
| 109 | Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms. 15 mm nominal bore |
| 110 | Providing and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931. 15 mm nominal bore |
| 111 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 15mm nominal bore |
| 112 | Providing and fixing PTMT grating of approved quality and colour. 125 mm nominal dia with 25 mm waste hole |
| 113 | Providing and fixing PTMT swivelling shower, 15 mm nominal bore, weighing not less than 40 gm |
| 114 | Providing and fixing PTMT soap Dish Holder having length of 138mm, breadth 102mm, height of 75mm with concealed fitting arrangements, weighing not less than 106 gms. |
| 115 | Providing and fixing unplasticised P.V.C. connection pipe with PTMT Nuts, collar and bush of approved quality and colour.15 mm nominal bore with 45 cm length |
| 116 | Providing and fixing PTMT extension nipple for water tank pipe, fittings of approved quality and colour. 15 mm nominal bore, weighing not less than 32 gms |
| 117 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer in Charge. Concealed work, including cutting chases and making good the walls etc |
| 118 | 15 mm nominal dia Pipes |
| 119 | 20 mm nominal dia Pipes |
| 120 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work |
| 121 | 25 mm nominal dia Pipes |
| 122 | 32 mm nominal dia Pipes |
| 123 | 40 mm nominal dia Pipes |
| 124 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : |
| 125 | 150 mm dia. R.C.C. pipe |
| 126 | 450 mm dia. R.C.C. pipe |
| 127 | Supplying and fixing C.I. cover without frame for manholes : 500 mm diameter C.I. cover (medium duty) the weight of the cover to be not less than 58 kg |
| 128 | Making soak pit 2.5 m diameter 3.0 metre deep with 45 x 45 cm dry brick honey comb shaft with bricks and S.W. drain pipe 100 mm diameter, 1.8 m long complete as per standard design. With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 |
| 129 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fastenersto be paid for separately) : For fixed portion Powder coated aluminium (minimum thickness of powder coating 50 micron) |
| 130 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item): With float glass panes of 4.0 mm thickness (weight not less than 10kg/sqm) |
| 131 | Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : (a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. This layer will be allowed to air cure for 4 hours. (b) Second layer of slurry of cement @ 0.242 kg/sqm mixed with water proofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. |
| 132 | Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well casing (CM) pipe of required dia, conforming to IS: 12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer -in-charge.200 mm nominal size dia |
| 133 | Supplying, assembling, lowering and fixing in vertical position in bore well unplasticized PVC medium well screen (RMS) pipes with ribs, conforming to IS: 12818, including hire & labour charges, fittings & accessories etc. all complete, for all depths, as per direction of Engineer-in-charge. 100 mm nominal size dia |
| 134 | Supplying, filling, spreading & leveling stone boulders of size range 5 cm to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 135 | Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over the existing layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge. |
| 136 | Development of tube well in accordance with IS : 2800 (part I) and IS: 11189, to establish maximum rate of usable water yield without sand content (beyond permissible limit), with required capacity air compressor, running the compressor for required time till well is fully developed, measuring yield of well by \"V\" notch method or any other approved method, measuring static level & draw down etc. by step draw down method, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, all complete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirement and direction of Engineer-in-charge. |
| 137 | Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore well housing/ casing pipe, removable as per requirement, all complete for borewell of: 200 mm dia |
| 138 | Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts & nuts of required size complete.200 mm clamp |
| 139 | Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as required and specified, comprising of an outer heat strengthened float glass 6mm thick, of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an inner Heat strengthned clear float glass 6mm thick, spacer tube 12mm wide, dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor. (Payment for fixing of IGU Panels in the curtain glazing is included in cost of item No.25.2) For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm. (i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/ m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement. |
| 140 | Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including:(a) Structural analysis & design and preparation of shop drawings forthe specified design loads conforming to IS 875 part III (the systemmust passed the proof test at 1.5 times design wind pressure withoutany failure), including functional design of the aluminum sections forfixing glazing panels of various thicknesses, aluminium cleats, sleevesand splice plates etc. gaskets, screws, toggles, nuts, bolts, clampsetc., structural and weather silicone sealants, flashings, fire stop(barrier)cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including:(b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections andprofiles etc. to accommodate 3 Dimentional movement for achievingperfect verticality and fixing structural glazing system rigidly to theRCC/ masonry/structural steel framework of building structure usingstainless steel anchor fasteners/ bolts, nylon seperator to preventbimetallic contacts with nuts and washers etc. of stainless steelgrade 316, of the required capacity and in required numbers.(c) Providing and filling, two part pump filled, structural silicone sealantand one part weather silicone sealant compatible with the structuralsilicone sealant of required bite size in a clean and controlled factory/ work shop environment, including double sided spacer tape, settingblocks and backer rod, all of approved grade, brand and manufacture,as per the approved sealant design, within and all around theperimeter for holding glass. |
| 141 | Providing and fixing Sink Cock with Swinging casted spout |
| 142 | Carriage of materials from source to site work including loading & unloading all complete job as per specification and direction of E/I |
| 143 | Sand |
| 144 | Aggregate |
| 145 | Stone Metal |
| 146 | Brick |
| 147 | Fly Ash Brick |
| 148 | Tar/Bitmen |
| 149 | Wiring for Light point/fan point/exaust fan point/call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface/recessed PVC conduit, with modular type switch , Modular plate, suitable G.I boxes etc as required.Group-C |
| 150 | Wiring for light/power plug with 2x4 sqmm FR PVC insulated copper conductor single core cable in surface/recessed PVC conduit along with 1 No. 4 sq. mm FR PVC insulated copper conductor single core cable for loop earthing etc as required. |
| 151 | Wiring for circuit / sub-main wiringalong with earth wire with thefollowing sizes of PVC insulated, copper conductor, single core cable in surface/recessed PVC conduit as required. |
| 152 | 2 x 1.5 sq.mm + 1 x 1.5 sq. mm earth wire |
| 153 | 2 x 2.5 sq.mm + 1 x 2.5 sq. mm earth wire |
| 154 | 2 x 6.0 sq.mm + 1 x 6.0 sq. mm earth wire |
| 155 | 4 x 6.0 sq.mm + 2 x 6.0 sq. mm earth wire |
| 156 | Supplying and fixing of following sizes ofPVC Conduit along with accesseories in surface/recess including cutting the wall and making good the same in core recessed conduit etc. as required. 25mm |
| 157 | Supplying and fixing following modular Switch / socket on the existing modular plate and switch box including connections butexcluding modular plate etc as required. |
| 158 | 5/6 amps, one way switch |
| 159 | 5/6 amps, 3 pin socket outlet |
| 160 | Supplying and fixing following size / modules, GI box along with moduler base and cover plate for moduler switches in recess etc as required. 1 or 2 module (78mm x 78mm x 45mm) |
| 161 | Supplying and fixing suitable size GI box with modular plate and cover in front on surface or recess including providingand fixing 3 pin 5/6 amps moduler socket outlet and 5/6 amps modular switch. connection, painting etc as required. |
| 162 | Supplying and fixing suitable size GI box with modular plate & cover in front on surface or in recess including providing and fixing 6 pin 15/16amps moduler socket outlet and 15/16 amp modular switch.connection, painting etc as required. |
| 163 | Supplying and fixing 2 pin,5 amp ceiling rose on existing junction box/wooden block including connection etc as required. |
| 164 | Supplying and fixing batten/angle holder including connection etc. as required. |
| 165 | Installation testing and commissioning of Pre - wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube etc, directly on ceiling / wall, including connection with 1.5 Sq. mm. FR PVC insulated, copper conductor. |
| 166 | Installation testing and commissioning of Pre - wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube etc.including supplying and fixing ball and socket arrangement , 2 nos down rods of 20mm diax 1.6 mm thick steel conduit upto 30cm length. painting and wiring the down and connection with 1.5 sq. mm PVC insulated, copper conductor, single core cable and eartning etc. as required |
| 167 | Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (Up to 30 cm) with 1.5 sq. mm. FR PVC insulated,copper conductor, single core cable etc, as required. |
| 168 | Installation of exhaust fan upto 450 mm sweep in the existing opening, including making the hole to suit the size of the above fan, making good the damage, connection, testing, commissioningetc as required. |
| 169 | Installation of exhaust fan upto 510 mm sweep in the existing opening, including making the hole to cut the size of the above fan, making good the damage,including connection, testing, commissioningetc as required. |
| 170 | Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (but wiithout MCB/RCCB/Isolator)8 way, Double door |
| 171 | Supplying and fixingthe follwing wayhorizontal type three pole and neutral sheet steel, MCB Distribution board, 415 volts on surface/ recess, completed with tinned copper busbar, neutral bus bar, earth bus bar, din bar, interconnections, powder painted including earthing as required. (but wiithout MCB/RCCB/Isolator) 8 way Double door 4 way(4+12) Double door, Horizontal type |
| 172 | Supplying and fixing 6 amps to 32 ampsrating, 240 volts, \"C\" curve, miniature circuit breaker suitable for inductive loads of following poles in the existing MCB DB complete with connections, testing and commissioning etc, as required. |
| 173 | 6/32 amps, Single pole |
| 174 | 40 amps, SPN |
| 175 | 40 amps, TPN |
| 176 | GI Earth Pipe Electrode: Earthing with G.I. earth pipe 4.5 mtr long , 40mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. With charcoal and salt as required. |
| 177 | Earthing with copper plate 600mmx 600mmx 3mm thick including acessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe etcwith charcoal or cock and salt complete etc. as required. (with charcoal or coke and salt) |
| 178 | Providing & fixing of 25mmX 6mm GI Strip in 40 mm dia G.I. Pipe from eart electrode including connection eith G.I. Nut, bolt, spring, washer excavation and re-filling etc. as required. |
| 179 | Supplying and laying25mm x 5mm GI earth stripat 0.50 metre below ground as strip earth electrode, including connection / terminating with G.I. Nut, bolt, spring, washer, etc as required (Jointing shall be done by overlaping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mmsoldering etc as required) |
| 180 | Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. Pipe from earth electrode, as requirted. |
| 181 | Providing and Fixing G.I. Lightning Conductor Finial : P/F of lighting conductor finial, made of 25mm dia 300mm long copper tube, having single prong at top, with 85mm dia 3mm thick copper base plate including holes etc. complete as required. |
| 182 | providing and fixing G.I. Tape 20mm x 3mm thick on parapet or surface of wall for lightninf conductor complete as required. (for Horizontal run) |
| 183 | providing and fixing G.I. Tape 20mm x 3mm thick on parapet or surface of wall for lightninf conductor complete as required. (for Vertical run) |
| 184 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of size exceeding 35 sq mm but not exceeding 95 sq mmdirect in ground including excavation, sand cushioning, protective covering and re filling the trench etc as required. |
| 185 | S.I.T.C. Of following rating LED Flood lighting luminarie with pressure die cast housing and toughened glass cover (IP 66 protection) in Existing Pole / Pipe for Supply voltage 100-270V AC, 50 Hz. Luminarie shell be confirm to IS:10322 part-5 / section -5 and shall be complete with all neccssary accessories as required. 90/100W LED Flood light |
| 186 | Supply, Installation, testing and commissioning of following size ceiling fan 3 blades confirming to IS 374:2019 including wiring the down rods of standard length (upto m cm) with 1.5 Sq. Mm FR PVC insulated, copper wire suitable for 230 V 50 Hz, Single phase supplt etc. complete as required. 1200 mm (48\") Ceiling Fan |
| 187 | Supplying installation testing and commissioning following ration surface mounted LED tube light fittings suitable for 230V 50Hz. Single phase supply etc. complete as required. 20/22 W LED Tube Light |
| 188 | S.I.T.C. Of following rating reccess/surface mounted led round / squre shape down light luminaries with pressure die cast housing for single phase supply voltage. Luminaries shall be confirm to IS : 10322 part-5 / section -2 or IEC ; 62722 with all neccssary accessories as required15/16W LED Round Down Light |
| 189 | Supplying, fitting and fixing 40 mm high viterous white glazed earthen ware E.W.C. with \"p\" trap of Parry Hindustan or any other I.S.S. make including supplying & fixing 15 litres C.I. mosquito proof low down flushing cistern of approved make with complete fittings with C.I. handle and R.S. or bracket with telescopic flush pipe with brass coupling and plumbers joints spindle stop cock of approved quality weight not less than 450 grms. , 15 mm P.V.C. alkathene pipe 45 cm long with brass coupling at both ends and white/ black plastic solid state seal and lead of commander/ cuckoo or other I.S.S. make with hinges or screw etc. painting pipe and cistern etc. with 2 coats of approved paint over a coat of red oxide primer etc. all complete as per specification and direction of E/l.(A) With \"P\" trap (a)10.0 lit. low level PVC cistern |
| 190 | Supplying, fitting and fixing viterous white glazed earthen ware I.W.C. of Parry Hindustan or any other I.S.S. approved make with 100 mm H.C.I., \"p\" trap 15 litres C.I.. or C. pull and let go flushing cistern of names or other I.S.S. equivalent make, complete with all fittings, C.I. or C.C. brackets 32 mm alkathene/P.V.C. telescopic flush, pipe about 2 M long with one brass coupling and clamps G.I. chain and pull including supplying and fixing a pair of viterous white glazed earthenware where footrest to be fixed in floor 15 mm C.I. body brass spindle stop cock of weight not less than 50 grms. 15 mm P.V.C. connection pipe 450 mm long and the exposed pipe and cistern with two coats of approved paint over a coat of red oxide primer etc. all complete as per specification and direction of E/l.(A) 580 mm long (c) with 10.0 lit. low level P.V.C. cistern |
| 191 | Supplying, fitting and fixing flat back or angular, lipped front viterous white glazed earthenware urinal of \"Hindustan\" \" Parry\" or any other approved I.S.S. make with all fittings with C.I. or R.S. brackets, standard size G.I. flush pipe with fitting clamps, 15 mm C.I. body brass spindle stop cock of approved quality weight not less than 400 grms. , 15 mm P.V.C. alkathene pipe 450 mm long with brass coupling at both ends and doing plumber joints including painting of exposed part with 2 coats of approved paint over a priming coat of red oxide, cutting wall and floor, making good the same etc. all complete as per specification and direction of E/l. Flat back or standing corner (600mmx x350mm) |
| 192 | Supplying fitting fixing the following items Complete with all material as per specification and direction of E/IC.P. brass towel rail 20mmX600mm with bracket container |
| 193 | Supplying, materrials and labour for constructing inspection chamber of designation class 75B brick size 750mm deep, 600X450mm internal dimension having 250mm wall thickness in cement mortar (1:6) including 12mm cement plaster (1:4) with punning on inside and cement plaster (1:6) with 600X475mm G.I. cover with frame (weight not less than 35kg) alongwith earth work in excavation and 80mm thick PCC (1:3:6) in foundation and refilling all complete as per specification and direction of E/I. |
| 194 | Supply of followingPVC/XLPE insulated PVC sheathed, heavy duty , armouredelectrical cable with aluminium conductor for working voltage upto and including1.1 kV grade( Confirms to IS :1554, part-1). |
| 195 | 10 sq.mm, 4 core |
| 196 | 35 sq.mm, 3.5 core |
| 197 | 95 sq.mm, 3.5 core |
| 198 | Supply of Exhaust metalFan: Supply and fitting of 230mm, 230V ACmetal exhaust fan in the existing opening including making good the damage, connection testing, commissioning etc as required. Make :- Polar/Bajaj/Crompton Greaves / Havells / Orient/ Philips |
| 199 | Supply of Metal Exhaust Fan 15\"(380mm)(for Kitchen): Supply of15\"(380mm), 230V ACmetal exhaust fan in the existing opening including making good the damage, connection testing, commissioning etc as required.Make :- Polar/Bajaj/Crompton Greaves / Havells / Orient/ Philips |
| 200 | LED Bulb 9W/10W : Supplying and fixingofLED 9W /10W bulb and accessories as required. ( Make -Bajaj / Havells/ Philips) |
| 201 | SITC of 10 kVA, 415V, 3phinput & 3 ph output ON-LINE UPS system and all accessories as required of reputed. Make:- Numric / Luminous / Microtek, System parameter :-Rating-10KVA/10kw (3in-3out), Technology-IGBT based Double conversion PWM based online UPS, Parallel mode-4 (N+1), Isolation transformer-At input side, Installation mode-Tower, Input:- Rated voltage-400VAC 3-phase,4-wire, Volatge Range-Three phase 305VAC -498VAC at 100% load,180VAC -498VAC at 50% load, Rated Frequency-50Hz/60Hz, Frequency Range- 40Hz ~ 70Hz, Thdi-<5%, Power factor-0.99 at full load, Input phase reversal correction-Optional, Isolation Transformer-Inbuilt Isolation transformer. Output:- Rated power-10 kVA/10 kW, Voltage-Three Phase 380/400/415 Vac, Frequency synchronization range-Rated frequency±3Hz. Configurable range: ±0.5Hz ~ ±5Hz, Waveform-Pure sine waveform, Rated Power Factor-Unity,Crest Factor-3:1, Voltage harmonic distortion-< 2% (linear load) Voltage Regulation-1%, Dynamic response recovery time-40ms, Inverter Overload Capability on utility mode,At 25°C : 105% ~125%-10min,125%~150%-1min; 150% -more than 200ms,Inverter Overload Capability on battery mode-At 25°C :105% ~125%-60~ 30 s; >125%- more than 200ms |
| 202 | Sealed Maintenance free SMF Batteries for 10 kVA UPS for 20 Mins. backup with open type cabinate for installation of batteries and their respective battery leads copper cables / buslinks between batteries, copper cables between UPS & batteries, DC MCCB Box, with 24 months replacement guranty asper IS: 1651-1991 Make :- Luminus / Exide / Microtek |
| 203 | HT Cable : 3 core 50 sq.mm, HT XLPE cable, aluminium conductor, conductor screen with extruded semi conducting compund, XLPE insulated, insulation screening with extruded semi conducting compund in combination with copper tape, cores laid up, innersheathof PVC tape, glavinised flat steel strip armoured and overall PVC sheathed cable confirming to IS7098. Make-Polycab |
| 204 | Transformer 100kVA, 11kV/433V: Supply of continuous rating 100 kVA, 11/0.433KV, Off Circuit, oil cooled, copper wound, transformer andwith all accessories as per IS:2026, air filled cable box suitable for 11KV 1 Run, 3 Core 50 Sq mm XLPE Al. Ar. Cable and LV termination box shall have suitable arrangement for 1.1 KV, 2 Run, 3.5 Core, 95 Sq mm XLPE Al. Ar. Cable, HV and LV Side :- Bare bushing / XLPE Cable Box / Air Insulated Cable Box / Bus Duct (Kits and Bolts) etc as required.with making plateform or pole all comple with labor and material (Make:-GTB/Kirloskar / Crompton ) |
| 205 | Supply of JAKSON or equivalant make 20 kVA, 415 Volts DG Set comprising of Cummins make engine model X2.7TG1 developing 27.5 BHP and 20 kVAStamford make alternatormounted on a common base , complete with: Make-Jakson JAKSON or equivalanta) Fuel tank. b) Battery with leads. c) Manual Control Panel. d) Residential Silencer e) First fill of lube oil f) AVM Pad g) Acoustic EnclosurePSO 500 |
| 206 | Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required.2 run of cable |
| 207 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. |
| 208 | 3½ X 35 sq. mm (32mm) |
| 209 | 3½ X 95 sq. mm (45mm) |
| 210 | Supplying, installation, testing & commissioningof intelligent analog addressable photothermal detector complete with mounting base complete as required. |
| 211 | Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required. |
| 212 | Supplying, installation, testing & commissioning of addressable manual call point complete as required. |
| 213 | Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system (which is part of the schedule of work under SH: PA System)and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. Two Loop Panel. |
| 214 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump)(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body& bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-\"F\" insulation, conforming to IS-325. (c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required. (d) Suitable cement concrete foundation duly plastered and with anti vibration pads.900 lpm at 35 m Head |
| 215 | Supplying, fixing, testing and commissioning of butterfly valveof PN 1.6 rating with bronze/gunmetal seat dulyISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required : |
| 216 | 80 mm dia |
| 217 | 100 mm dia |
| 218 | Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required : |
| 219 | 80mm dia |
| 220 | 100mm dia |
| 221 | Providing, laying, testing & commissioning of \"C\" class heavy duty MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : |
| 222 | 25 mm dia |
| 223 | 80 mm dia |
| 224 | 100 mm dia |
| 225 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : |
| 226 | Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. 20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 1258520 mm nominal internal dia gun metal globe valve & nozzle. Drum and brackets for fixing the equipmets on wall. Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 40 m |
| 227 | Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :Gun Metal |
| 228 | Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :Gun metal |
| 229 | Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :4 way - 150 mm dia M.S. Pipe |
| 230 | Non schedule |
| 231 | Providing & injecting chemical emulsion for pre- construction Anti termite treatment and creating a chemical barrier under and all around the column pits wall treanched basement excavation top surface of plinth filling junction of wall and floor along the external perimeter of building with apporoved chemical as per IS coad as per specification and direction of E/I |
| 232 | Providing and fixing PVC Pipe fittings with all accessories (Supreme, Prince, Astral or Equivalent ) |
| 233 | i) 110 mm Door Tee (Supreme, Prince, Astral or Equivalent ) P.V.C. |
| 234 | ii) 110 mm Plain Bend (Supreme, Prince, Astral or Equivalent ) P.V.C. |
| 235 | iii) 110 mm Door Bend (Supreme, Prince, Astral or Equivalent )P.V.C. |
| 236 | iv) 110 mm 45 degree offset(Supreme, Prince, Astral or Equivalent ) P.V.C. |
| 237 | v) 110 mm Cowel (Supreme, Prince, Astral or Equivalent ) P.V.C. |
| 238 | vi) 110 mm Plain Trap (Supreme, Prince, Astral or Equivalent ) P.V.C. |
| 239 | i) 75 mm Door Tee (Supreme, Prince, Astral or Equivalent ) P.V.C. |
| 240 | ii) 75 mm Plain Bend (Supreme, Prince, Astral or Equivalent ) P.V.C. |
| 241 | iii) 75 mm Door Bend (Supreme, Prince, Astral or Equivalent )P.V.C. |
| 242 | iv) 75mm 45 degree offset(Supreme, Prince, Astral or Equivalent ) P.V.C. |
| 243 | vi) 75 mm Plain Trap (Supreme, Prince, Astral or Equivalent ) P.V.C. |
| 244 | Providing and fixing ball valve (full brass, KEC / APAR/ ZOLLOTO make or equivalent ) all complete . 32 MM DIA NOMINAL BORE |
| 245 | Supply fitting and fixing of standered make starter pannel Board with arrangement of all necsssury protection including all taxes ,royalty etcall complete job as per direction of E/I. |
| 246 | Supply fitting and fixing lowering 50 mm dia G.L. collumn pipe - do - do - all complete job as per direction of E/I. |
| 247 | Flame proof non-integral wellglass luminaire: Supply, installation and commissioning of Flame proofnon-integral wellglass luminaire,suitable for 15LED, epoxy finish LM6 aluminium alloy housing with resistant and toughened glass cover, painted MS wire guard and eye bolt. Model - Bajaj-BJISW80W MV HPMV80) |
| 248 | Supplying and fixing 32 Amp DP Switch fitting complete with connections, testing and commissioning etc. as required. |
| 249 | Power CuCable( for battery bank to MCCB) : 1 core 25 sq.mm, copper conductor, conductor screen with extruded semi conducting compund, XLPE insulated, PVC tape, inersheath for multicore cables. |
| 250 | 24 Port POE Access Level Switch : Switch ports of 24 x 10/100/1000 Base T with additional 4x SFP ports for uplink, 1x Out Of band port for IP based management, 1X Console port with Min PoE power budget should be 370 watt .Follow the annexure for detailed specification Preffered Make : Cisco/Extreme |
| 251 | Patch Panel -24 Port Fully Loaded : Supply, installation and commissioning of Patch Panel-24 Port fully loaded. Preffered Make-MOLEX/Schenider/DLINK |
| 252 | LAN Patch Cord 1.0 mtr : Preffered Make-Legrand/MOLEX/Schenider/DLINK |
| 253 | I/O Faceplate : Supply , installation and termination of white modular plate type Single front plate for 1 Nos. RJ 45 Dataoutlet(Make:- Legrand / ABB / Schneider/Dlink) |
| 254 | RJ45 Data Module : Supply , installation and termination ofRJ 45 Data Module to be fixed on face plate (Make:- Legrand / ABB / Schneider/Dlink) |
| 255 | Supply , installation and termination Gang Box to fix the faceplate and I/O Modules RJ45 |
| 256 | Supply, Installation & Commisioning of Wall Mount 15U Network Rack500(H) Width (mm)-600, Depth (mm)Approx.Net Wt (kg) - 20, Glass - 4mm Toughened Tinted Glass Door,Accessories:, Cooling Fan (230V A/C 90 CFM) - 2 Nos, PDU 230VAC - 1 No, Cable Manager- 1 No, Mounting Hardware (20 sets of M6 screws,washer,cage nuts (nickel coated)) - 1 No, Wall Screws (4 sets of 2\"\" screws, washer,rubber grommet (nickel coated)) - 1 No, Door Lock - 1 No, Front Metal Band -1 No. In the rack there must be maintained 1 U = 1.75 inches space. Preffered Make: Dlink/APC/Legrand/Any Standard |
| 257 | Supplying, designing, manufacturing, installation, testing and commissioning of UPS Panel of 14 SWG CRCA sheet (2 mm) steel IP-54wallmounted cubical typesuitable for operation on 415V, 50Hz, 3 Ph. AC supply and fault level 50kA arrangement for fixingMCCB as incomer and suitable nos. of outgoing are as follows: ( Make-of MCCB/MCB-Schnieder /Legrand/L&T/ Siemens)) Incomer : 1 no-MCCB-63A , 4P, 16kA-make -Legrand/ Schnider/L&T/Siemens. Ourgoings:MCB 10A, SP-HPL Make-2 nos, MCB 40A, TPN-ABB, Make-3 nos, Analogue type Ammetesr (0-400A) of 96 sq.mm.With selector switch . Make :- AUE / Universal / L&T / Esma., Analogue type voltmeter (0-500V) of 96 sq.mm.- 1 no ,with selector switch.Make :- AUE / Universal / L&T / Esma., LED indicatore (RYB) of 220V. 1 Set of 3 nosMake :- ESSEN / L&T - ESBEE / Binay / Teknik,14 SWG CRCA sheet (2 mm) steeland channel and bus bar of suitable size. |
| 258 | Box with MCCB Supplying, designing, manufacturing, installation, testing and commissioning ofwallmounted MCCB box with 63A MCCB, 4P suitable for operation on 415V, 50Hz, 3 Ph. AC supplyto beused in UPS server room forpower supply to UPS and battery bank: ( Make-/Legrand/L&T/ABB/ C&S/ Schnider) |
| 259 | IR Bullet Camera : ALCON AL-5001-MPC-HD4M-BULLET POE, 4MP, QUAD HD(2560x1440p), IP Bullet Camera,H.265 support, Fixed Lens, 20m IR, POE supported, IP-66 Housing. Preffered Make-Alcon |
| 260 | PTZ camera : ALCON: AL-5003-MPC-HD220XIR, 2.0MP, FULL-HD IP HIGH SPEED PTZ, 20X OPTICAL AND 16X DIGITAL ZOOM, 150m IR, INTEGRATED WIPER, INTEGRATED LIGHTNING PROTECTION, IP-66 HOUSING. |
| 261 | 40 Channel NVR : ALCON AL-NVR5040-4D, 40 Channel ULTRA HD NVR, H.265 HEVC, Support 4HDDx6TB(Hard Disk Not Included) |
| 262 | Hard Disk : 4TB WD Surveillance Hard Disk storage |
| 263 | 40\" LED Panel : LG 55SM5KB 40 inch Full HD LED Panel, LG Make -LG/ Samsung |
| 264 | Fabrication, Supplying, Installation, Testing & Commissioning of electrical control panel of cubical construction, wall mounted type, fabricated out of 2mm. thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection, and accessories mounting and internal wiring, earth terminals, numbering etc. complete in all respects, suitable for operation on 415 V,3 phase 50 HZ AC supply with enclosure protection class IP 42. |
| 265 | Supplying fitting fixing Pressure Gauge Assemble with Gate/Ball Valveall complete as per engineer in charge. |
| 266 | Supplying fitting fixing PAir release Valve all complete as per engineer in charge. |
| 267 | Providing and fixing 25 mm nominal gun metal gate valve class I with CI wheel of approved quality with union (Screwed end) |
| 268 | Supplying and fixing of hose cabinet of size 450mm x 450mm x 250mm made of 2mm thick M.S. sheet with 6mm thick glazed glass door including necessary locking arrangment suitable to accomodate 1 nos. 15 mtr. long hose pipe, 1 no. branch pipe mounted on wall or raised brick platform and duly painted with post office red externally and white internally with synthetic enamel paint complete in all respect. |
| 269 | Providing , fixing Dry Chemical Powder(Stored Pressure Type) Mono Ammonium Phosphate 50% powder confirming to ‘IS 14609’ , Nitrogen Pressurized, Controllable Discharge Mechanism, Pressure Gauge, Discharge Hose & Nozzle Epoxy Polyester PowderCoated As per ‘IS 15683’ ISI mark Fire Extinguishers. Operating Temperature: - (-) 20oC to (+) 55oC Suitable for ‘A’ ‘B’ ‘C’ Class of FIRE complete in all respects(4 Kg Capacity) |
| 270 | Carbon Di-oxide Type , Gas Confirming to IS ‘15222’ , Cylinder Confirming to ‘IS 7285’ & PESO approved ,Controllable Discharge Mechanism, Discharge Hose & Horn As per ‘IS 15683’ & ‘IS 2878’ ISI mark Fire Extinguishers (Wheel Type or Squeeze Grip Type). Operating Temperature :- (-)20oC to (+)55oC Suitable for‘B’ ‘C’ Class of FIRE (3 Kg Capacity) |
| 271 | Providing , fixing Modular type Fire Extinguishers for electrical rooms (Stored Pressure Type) Mono Ammonium Phosphate 50% powder confirming to ‘IS 14609’ , Nitrogen Pressurized, Controllable Discharge Mechanism, Pressure Gauge, Discharge Hose & Nozzle Epoxy Polyester PowderCoated As per ‘IS 15683’ ISI mark Fire Extinguishers. Operating Temperature: - (-) 10oC to (+) 55oC Suitable for ‘A’ ‘B’ ‘C’ Class of FIRE complete in all respects(5 Kg Capacity) |
| 272 | Main Panel(Power Distribution ): Power Distribution Board (PDB at GL) - Supplying, designing, manufacturing, installation, testing, fitting, fixing and commissioning in correct alignment position, effecting proper connection of all incomers and outgoing of PDB panel of 14 SWG CRCA Sheet (2mm) steil IP-54 floor mounting cubical type LT Panel suitable for operation on 415V, 50Hz, 3Ph, AC supply and fault level 35kA. Apporexmate size (Shall be given at the time of work order ) with front operated construction including seperate fabrication arrangement for fixing of switchgears and meters. The sheet steel under go minimum seven tanks treatement followed by finishing poder coating of minimum 60 microns thickness duly compart mentalized with locking arrangement duly fixed on base channel size 100mm X 75mm X 6mm having accessories mounted inside cubicale panel, earthing with 2 Nos. of earth studs. All opening shall be covered by soft rubber gaskit,enclosure shall be galvanished. Panel shall have suitable cable entry from top and bottom and suitable arrangement for multiruns aluminium cables for MCCB.Incomers-200A, 35 kA FP MCCB - 1 no, with front rotary handle with thermo magnetic release.- for JSEB. (Make-L&T/ Legrand/ Schneider/Siemens), 63A, 16 kA FP MCCB- 1 no with front rotary handle with thermo magnetic release.- for DG supply.( make-L&T/ Siemens/Schneider/ Legrand) ,Change Over Switch : 63A,FP ON/OFF load changeover- 1 no. , Outgoings-3-nos-63A , 16kA FP MCCB with front rotary handle with thermo magnetic release .- for UPS+spare, 5 nos-40A ,10kA FP MCB - forfloors MCBlighting DBs+Spare, Analogue type Ammetesr (0-400A) of 96 sq.mm.With selector switch . Analogue type voltmeter (0-500V) of 96 sq.mm.- 1 no ,with selector switch.Make :- AUE / Universal / L&T / Esma.LED indicatore (RYB) of 220V. 1 Set of 3 nosMake :- ESSEN / L&T - ESBEE / Binay / Teknik, Bakalite Fuse base with HRC Fuse 20A. 1 Set of 3 nos.Make :- Legrand / L&T / Schinder. CT 600/5VA -5 class one Epoxy resin cast CT 1 Set.300A Bus Bar(cu) |
| 273 | Add 12 % GST |
| 274 | Add 1% Labour Cess |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy