| 1 | Providing, installation testing and commissioning of VRV/VRF outdoor units (hot and cold) complete with all accessories like compressors, condenser coil, PCB, fan etc and fixtures for resting of the outdoor units. The outdoor units combination shall be provided with individual remote control alongwith centrally controlled remote controller having touch screen panel capable fo monitoring operation of outdoor unitsm. The Hot an cold out door units combination shall have following specifications.14HPHeating capacity 45KW.Cooling capacity 40KW.The equipment design shall be compatible to maintain desired inside temperature of 240C+ 20C during winter session and 22.50C+ 20C during summer session. The job includes the providing and fixing of the refrigerant pipes/Drain pipes duly insulated with nitrile rubber (25mm thick) of requisite size and the control cabling from indoor to the out door units as per the site requirement. The job includes pressure testing of the refrigerant pipes after proper vacumization for a period of 24hrs and charging the machines with required quantity of refrigerant as per OEMs recommendation. The job also includes providing and fitting of any other equipment for successful commissioning also includes providing and fitting of any other equipment for successful commissioning of VRV machines. The outdoor units shall be provided with power scanner, L-shaped exhaust duct with bird screen and proper earthing as recommended by OEM. |
| 2 | Supply, installation, testing and commissioning of ductable type indoor units with pre-high efficiency fine filter at terminal compatable with without unit combination of 12HPThe Detailed specifications and requirements as under specifications.Cooling capacity:-20KW or moreEarthing capacity:-20KW or more.Air flow rate:-2000CFMPower supply:- Single phase.Static pressure:-100-150paDrain pipe: Drain pipe is fabricated from 20SWG stainless steel sheet having uniform slope from all sides for zero water retention and entire assembly is mounted on isulated bottom panel. The job includes requisite control cables and electric panels complete in all respects as per the codes/norms in this regard. |
| 3 | Supply, installation, testing and commissioning of sheet metal ducts(G.I) complete with all the accessories like flanges, gaskets for connection of the ducts, supports for hanging of ducts and shall also conform to the SMACNA specifications including manufacturers standard accessories |
| 4 | 24 gauge for ducts. |
| 5 | 22 gauge for plenum |
| 6 | Supply of fixing of external thermal insulation (19mm thick nitrile rubber) over ducting. |
| 7 | Supply, installation, testing and commissioning of multiple of louver system type G.I. damper for branches to be provided with suitable links, levers and quadrants for manual control of volume of air flow in supply and return duct. |
| 8 | Supply, installation, testing and commissioning of powder coated extruded Al. supply air girls/diffusers with G.I. volume control damper (Key operated). |
| 9 | Supply, installation, testing and commissioning of powder coated extruded Al. return air frills/diffusers (without VCD) |
| 10 | Providing and fitting of fresh air inlet multiple louver type damper with air pre filter and bird screen in the machine room. |
| 11 | Supply, installation, testing and commissioning of flexible double canvas connection of fire treated material at required joints of ducting. |
| 12 | Supply, installation, testing and commissioning of 25mm PVC (flexible) pipe for draining of condensed water from the evaporator coil (Brackets clips etc included). |
| 13 | Supply, installation, testing and commissioning of main cubical panel (to accommodate the above mentioned machines including the outdoor unit and indoor units) free standing type, dust and vermin proof fabricated out of 16SWG MS sheet to be laid over MS angle frame internally wired. The panel shall have modular construction with incoming and outgoing MCCB’s housed in an enclosure forming the basic module. All the internal wiring used shall be of suitable rating for individual component of the panel.Aluminum bus bars, with requisite Amps, TPNs mounted on insulators. the bus bars shall be provided with heat shrinkable type PVC sleeves duly color coated. The job also includes the providing and fixing of control cabling for connections of indoor and outdoor units and connections of main panel to the sub panels fo the machines as per the size and type recommended by OEM of the machine. |
| 14 | Providing and laying of RCC foundation (1:2:4 mix) for 1No outdoor units as per the recommendations. |
| 15 | Providing fabrication, fixing of supports for indoor units/outdoor units and ducting at machine room. The supports be fabricated out of ISA 40x40x5/MS plates 5mm as per site requirement. |
| 16 | Providing and fitting of 3.5mm thick HEPA filter of 1000cfm size 24”x24” (Mecro glass fiber paper with aluminum spacer in aluminum anodized box. Having efficiency of 99.9%) for the Orthopaedic and Opthmology theaters. |
| 17 | Supply, installation, testing and commissioning of high wall mounted split type hot and cold air donctioning units of 2.2TR capacity with inverter technology each complete with indoor unit and outdoor unit comprising of compressor, condenser etc. including providing and fixing of copper refrigerant pipeing of suitable dia insulated with nitrile rubber of recommended thickness, interconnecting of copper conductor power cables 3core 4mm2 between the indoor unit and outdoor unit through 5KVA voltage stabilizer, MCB of required capacity, plugs and sockets, solid condensate pipe and M.S stand for mounting of outdoor unit. The job also includes pressure testing, vacuum testing and charging of refrigerant for rated performance of air conditioning machine.a. Cooling capacity: 24000Btu/hr) 7800 (min)-29000 (max)Btu/hr. b. Heating capacity: (28000Btu/hr) 7900 (min)-34100 (Max) Btu/Hr |