| 1 | Section-I |
| 2 | Comprehensive preventive maintenance by technically qualified technician and rendering operationally 1 No x 200 CFM and 2 No x 225 CFM Air compressor including assemblies inspection to maintenance of nut, bolts, washer, split pins for proper tightness of V beltand safety including replacement of defective parts, and all other miscellaneous item & ensure safe operation of compressor. preventive maintenance of housing system assy comprising of inspection checking including topping of Gear box with water cool system. Cleaning up all greasy/clipping materials inspection servicing, setting and testing breaking limit system for its safe operation. Inspection, checking andsetting out. preventive maintenance of electrical control system comprising of following:-(a)Inspection checking decarbonising & tightning of electrical connection in total system including replacement of thimbles etc.(b)Inspection & checking of fuses, setting & tightning the same as per their capacity.(c)Inspection and setting of voltage system including replacement of fused indicating lamp etc.Notes:- (i) Spares for air compressor will be measured and paid seperately.(ii) Contractor will be carry out comprehensive maintenance once in a month and maintain the record of same.(iii) Contracor will ensure serviceability and safety of air compressor during his each visit by way of maintining job card duly signed by JE E/M, (iv) The contractor willalso send representative/Technician on call basis in case of any fault. Fault to be rectified within 8hrs of receipt of complaint failing which Rs 500/- per day will be deducted till rectification of defect.(v) Rates of all consumables such as lubricant, gear oil, nut bolt,split pins, bushes, gasket are deemed to be included in the rates. details of Qty : (a) No of compressor = 3 Nos (b) Comprehensive maint for 6 months = 3 x 6 = 18 |
| 3 | Section-II |
| 4 | S & F in repairs MCCB 3 pole, 415V AC, 125 Amp rating 25 kA rupturing capacity, thermal magnectic release, complete with any retrofit work, terminal links and copper thimbles complete all as specified and as directed. (Make Schnieder/ Siemens/L&T/Legrand). |
| 5 | S & F in repairsMCCB 3 pole, 415V AC, 100 Amp rating 25 kA rupturing capacity, thermal magnectic release, complete with any retrofit work, terminal links and copper thimbles complete all as specified and as directed. (Make Schneider/ Siemens/L&T/ABB/ Legrand). |
| 6 | S & F in repairs MCCB 3 pole, 415V AC, 160 Amp rating 36 kA rupturing capacity, thermal magnectic release, complete with any retrofit work, terminal links and copper thimbles complete all as specified and as directed. (Make Schnieder or equivalent to Siemens/L&T/Legrand). |
| 7 | S & F in repairs MCB 3 pole, 415V AC, 32 Amp rating 10 KA rupturing capacity, thermal magnectic release, complete with any retrofit work.complete all as specified and as directed. (Make Schneider/ Siemens/L&T/ABB/ Legrand). |
| 8 | S & F in repairs MCCB 4 pole, 415V AC, 400 Amp rating 50 kA rupturing capacity, thermal magnectic release, complete with any retrofit work, terminal links and copper thimbles complete all as specified and as directed. (Make Schnieder or equivalent to Siemens/L&T/Legrand). |
| 9 | S & F in repairs MCCB 4 pole, 415V AC, 250 Amp rating 36 kA rupturing capacity, thermal magnectic release, complete with any retrofit work, terminal links and copper thimbles complete all as specified and as directed. (Make Schnieder or equivalent to Siemens/L&T/Legrand). |
| 10 | S & F in repairs MCCB 4 pole, 415V AC, 125 Amp rating 25 kA rupturing capacity, thermal magnectic release, complete with any retrofit work, terminal links and copper thimbles complete all as specified and as directed. (Make Schnieder/ Siemens/L&T/Legrand). |
| 11 | S & F in repairs Thermal Over Load Relay70 Amps to 90 Amps complete all as specified and as directed. (Make Schneider/ Siemens/L&T/ABB/ Legrand). |
| 12 | S & F in repairs air break contactor 45 Amps, 415 volt AC with 2NO+2NC size 3 complete all as specified and as directed. (Make Schneider/ Siemens/L&T/ABB/ Legrand). |
| 13 | S & F in repairs air break contactor 70 Amps, 415 volt AC with 2NO+2NC size 3 complete all as specified and as directed. (Make Schneider/ Siemens/L&T/ABB/ Legrand). |
| 14 | S & F in repairs air break contactor 85 Amps, 415 volt AC with 2NO+2NC size 3 complete all as specified and as directed. (Make Schneider/ Siemens/L&T/ABB/ Legrand). |
| 15 | S & F in repairs air break contactor ML2, 32 Amps, AC3, 415 volt AC with 2NO+2NC complete all as specified and as directed. (Make Schneider/ Siemens/L&T/ABB/ Legrand). |
| 16 | M&L for overhauling ofScrew compressorcapacity 5665 LPM oil cooled type . Make K G Khosala. NOTE: The overhauling includes repair and replacement of all parts, major/ minor required to keep the equipment functional, excluding the under mentioned items. The maintenance will be carried outby qualified technicians from Kirloskar/ Kaesar/ K G Khosala and the authenticity to be verified to Engr-in-Charge. |
| 17 | --- ditto--- all as per Item No 2.13 above but of capacity 6371 LPM and water cooled type . |
| 18 | Supply and fixing in repairs of Solenoid Valve 220V type 302013-1.2, 2G, Size I complete all as directed by Engineer in Charge (Make-Rotex or equivalent ISI mark) . |
| 19 | Supply and fixing in repairs of 15 mm bore dia gun metal gate valve with iron wheel head screwed both ends for iron pipe complete all as specified. (Make:- KIRLOSKAR/ LEADER/ VENUS/ ZOLOTO/ AUDCO). |
| 20 | ---ditto---- all as per item No 2.16 above but 50mm bore dia complete all as specified. (Make:- KIRLOSKAR/ LEADER/ VENUS/ ZOLOTO/ AUDCO). |
| 21 | Supply and fixing in repairs gun metal swing check valve, 50mm bore dia class -I, IS-778, complete all as specified. (Make:- KIRLOSKAR/ LEADER/ VENUS/ ZOLOTO/ AUDCO). |
| 22 | Supply and fixing in repairs of 25mm bore dia ball brass valves, high pressure, with polyethylene float and fly nut complete screwed for iron pipe complete all as specified and as directed (MAKE:- LEADER/ ZOLOTO/ AUDCO/ KIRLOSKAR). |
| 23 | --- ditto---- all as per item No 2.19 above but 50mm bore dia complete all as specified and as directed (MAKE:- LEADER/ ZOLOTO/ AUDCO/ KIRLOSKAR). |
| 24 | Supply and fixing in repairs of air release valve assemblySES-200 complete all as specified and as directed.(Make:- KIRLOSKAR/ LEADER/ ZOLOTO / AUDCO) |
| 25 | Supply and fixing in repairs of Air oil separator element No 46020610 complete all as specified and as directed. (Make :- KIRLOSKAR/ LEADER/ ZOLOTO / AUDCO) |
| 26 | Supply & fixing in repairs of Safety valve No 37040080 complete all as specified and as directed. (Make :- KIRLOSKAR/ LEADER/ ZOLOTO / AUDCO) |
| 27 | Supply & fixing in repairs of moisture trapNo 4619403 complete all as specified and as directed.(Make :- KIRLOSKAR/ LEADER/ ZOLOTO / AUDCO) |
| 28 | Supply & fixing in repairs of secondryoil filterelement No 46188320 complete all as specified and as directed.(Make :- KIRLOSKAR/ LEADER/ ZOLOTO / AUDCO) |
| 29 | Supply & fixing in repairs of suction filter element secondary and primary complete all as specified and as directed. (Make :- KIRLOSKAR/ LEADER/ ZOLOTO / AUDCO) |
| 30 | Supply & fixing in repairs of blow out valve No 46064640 complete all as specified and as directed. (Make :- KIRLOSKAR/ LEADER/ ZOLOTO / AUDCO) |
| 31 | Supply & fix in replacementFlat fan beltheavy duty for screw type compressor200CFM size 2615mmx65mm complete all as specified and as directed (Make :- Fenner/ Kirloskar/ Continental) |
| 32 | Supply & filling in replacement of compressor oil Servo No 68 complete all as specified and as directed (Make : HP/Bharat petroleum /Servo) |
| 33 | Supply & fixing in repairs of Pneumatic pressure cut off valve with wiring for compressor 225 CFM complete all as specified and as directed(Make :- Trident/Danfoss/Rotex) |
| 34 | Supply & fixing in repairs of safety relief valve 15mm dia Bronze 1BR Clause 282(A) complete all as specified and as directed(Make:- LEADER/ ZOLOTO/ KIRLOSKAR/ AUDCO) |
| 35 | Supply & fixing in repairs of 6 Sqmm single core wire multi stranded copper conductor, PVC insulated, FRLS insulated, unsheathed cable 1100 volt grade including taking down old unserviceable one complete all as specified & directed (Make:- Finolex /Polycab/ Havells/ RR Kabel/ KEI Industries). |
| 36 | Supply & fixing in repairs of digital Amp meter 0-300 AC complete all as specified & as directed (Make:- AE/L&T/Siemens) |
| 37 | Supply & fixing in repairs of analog Volt meter 0-15 DC complete all as specified & as directed (Make:- AE/L&T/Siemens) |
| 38 | Supply & fixing in repairs of Double Pole MCB 20 Amp 10 K \"C\" curve 230 volts, complete all as specified & as directed (Make:- L&T/ Siemens/ Legrand/ ABB). |
| 39 | Supply & fixing in repairs of High Pressure Bearing Ring complete all as specified & as directed (Make: K.G.Khosla/ Kirloskar/V tech). |
| 40 | Supply & fixing in repairs of High Pressure Sealing Ring complete all as specified & as directed (Make: K.G.Khosla/ Kirloskar/V tech). |
| 41 | Supply & fixing in repairs of “O” ring For Valve complete all as specified & as directed (Make: K.G.Khosla/ Kirloskar/V tech) |
| 42 | Supply & fiixing in repairs of Copper Ring under Valve complete all as specified & as directed(Make: K.G.Khosla/ Kirloskar/V tech). |
| 43 | Supply & fixing in repairs of locking Nut for crank shaft complete all as specified & as directed (Make: Kirloskar / K.G Khosla/V tech) |
| 44 | Supply & fixing in repairs of High Pressure Gasket FE Cover complete all as specified & as directed (Make: Kirloskar / K.G Khosla/V tech). |
| 45 | Supply & fixing in repairs of High Pressure Suction Valve Assembly complete all as specified & as directed (Make: Kirloskar / K.G Khosla/V tech) |
| 46 | Supply & fixing in repairs of High Pressure Delivery Valve Assembly complete all as specified & as directed(Make: Kirloskar / K.G Khosla/V tech). |
| 47 | Supply & fixing in repairs of unloading tables and spring complete all as specified & as directed (Make: Kirloskar / K.G Khosla/V tech). |
| 48 | Supply & fixing in repairs of packing ring Set complete all as specified & as directed (Make: Kirloskar / K.G Khosla/V tech). |
| 49 | Supply & fixing in repairs ofRetaining ring complete all as specified & as directed(Make: Kirloskar / K.G Khosla/V tech) |
| 50 | Supply & fixing in repairs of spherical roller bearing 22216EC3 complete all as specified & as directed (Make:SKF/NBC/ZKL/FAG) |
| 51 | Supply & fixing in repairs of water sensor model KP35 code 060-113391 complete all as specified & as directed(Make-Danfoss or equivalent). |
| 52 | Supply & fixing in repairs ofAir Sensor model RT-200 Code 017-523766 complete all as specified & as directed (Make-Danfoss or equivalent). |
| 53 | Supply & fixing in repairs of Screw compressed oil Roto inject complete all as specified & as directed . |
| 54 | Supply & fixing in repairs of Pressure limiting valve Cat No. 46054100 complete all as specified & as directed (Make-K.G Khosla/Kirloskar/ V Tech) |
| 55 | Supply & fixing in repairs ofrewinding 5.5 KW 3 phase 415V AC SQ cage induction motor 900 RPM by super enamelled copper wire with class B insulation with suitable size ball bearing complete all as specified & as directed . |
| 56 | Supply & fixing in repairs ofGun metal foot valve 50mm IS 318LTB2 300Psig Hyd complete all as specified & as directed(Make-KIRLOSKAR/ LEADER/ ZOLOTO/ AUDCO). |
| 57 | Supply & fixing in repairs of 4 Sqmm single core wire multi stranded copper conductor, PVC insulated, FRLS insulated, unsheathed cable 1100 volt grade including taking down old unserviceable one complete all as specified & directed (Make:- Finolex /Polycab/ Havells/ RR Kabel/ KEI Industries). |
| 58 | S & F in repairsMCCB 4 pole, 415V AC, 63 Amp rating 25 kA rupturing capacity, thermal magnectic release, complete with any retrofit work, terminal links and copper thimbles complete all as specified and as directed. (Make Schneider/ Siemens/L&T/ABB/ Legrand). |
| 59 | Supply & fixing in repairs ofDOL starter 3 HP, three phase complete all as specified & as directed(Make Schneider/ Siemens/L&T/ABB/ Legrand). |
| 60 | M&L for overhauling ofBattery Charging silicon rectifier type of capacity 20 KW, three phase, 440 volts input supply and out put supply DC-15/110 volts on floor mounting complete all as specified and as directed .( Make ELVOC.) NOTE: The overhauling includes repair and replacement of all parts, major/ minor required to keep the equipment functional are deemed to be included with quoted rate. The maintenance will be carried outby qualified technicians to be verified to Engr-in-Charge. |
| 61 | M&L for overhauling ofBattery Charging silicon rectifier type of capacity 6.5 KW, three phase, 440 volts input supply and out put supply DC-15/200 volts on floor mounting complete all as specified and as directed .( Make ELVOC.) NOTE: The overhauling includes repair and replacement of all parts, major/ minor required to keep the equipment functional are deemed to be included with quoted rate. The maintenance will be carried outby qualified technicians to be verified to Engr-in-Charge. |
| 62 | Supply & fixing in repairs ofSDF 160 Amps, three phase with HRC fuse links HN typesuitable for SDF complete all as specified & as directed(Make Schneider/ Siemens/L&T/ABB/ Legrand). |
| 63 | M&L for overhauling ofsquirrel cage induction electric motor, three phase, 415 volts, 1455 RPM of capacity 60 HP with re-assemble and testingcomplete all as specified and as directed .( Make ELVOC.) NOTE: The overhauling includes repair and replacement of all parts, major/ minor, re-winding dismantling and assemble, lubrication, required to keep the equipment functional are deemed to be included with quoted rate. The maintenance will be carried outthrough authorize service team of the OEM (Kirloskar). by qualified technicians to be verified to Engr-in-Charge. |