Annual Rate Of Electric Works For Various Buildings Under (R&B) Division, Navsari (Sub-Division, Navsari & Chikhli)-Gujarat

Road And Building Department-RBD has published Annual Rate Of Electric Works For Various Buildings Under (R&B) Division, Navsari (Sub-Division, Navsari & Chikhli). Submission Date for this Tender is 27-09-2021. Retaining Hardware Tenders in Gujarat. Bidders can get complete Tender details and download the document.




Tender Notice

29193993
Annual Rate Of Electric Works For Various Buildings Under (R&B) Division, Navsari (Sub-Division, Navsari & Chikhli)
Open Tender
Indian
Gujarat
27-09-2021

Tender Details

Annual Rate Of Electric Works For Various Buildings Under (R&B) Division, Navsari (Sub-Division, Navsari & Chikhli) 1. Point Wiring For Light / Fan/ Bell/ Primary Point With 2-1.5 Sq. Mm & Earth Wire Of 1.5 Sq. Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto Max Length Of 10 Mt, In Below Type Of Pipe Erected With 6A Tissino Type Isi Marked Flush Type Switch / Bell Push And Accessories Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) /Acrylic/Laminated Sheet. With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (A) With Medium Class Rigid Pvc Pipe And Accessories Erected Flushed On Wall/Ceiling Complete 2. Point Wiring For Light / Fan/ Bell/ Primary Point With 2-1.5 Sq. Mm & Earth Wire Of 1.5 Sq. Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto Max Length Of 10 Mt, In Below Type Of Pipe Erected With 6A Tissino Type Isi Marked Flush Type Switch / Bell Push And Accessories Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) /Acrylic/Laminated Sheet. With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (B) With 16 Swg(1.6 Mm Thick) Hgs Metal Conduit Pipe And Accessories Painted Black Erected Flushed On Wall/Ceiling Complete 3. Point Wiring For Light / Fan/ Bell/ Primary Point With 2-1.5 Sq. Mm & Earth Wire Of 1.5 Sq. Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto Max Length Of 10 Mt, In Below Type Of Pipe Erected With 6A Tissino Type Isi Marked Flush Type Switch / Bell Push And Accessories Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) /Acrylic/Laminated Sheet. With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. ( C) With Oval Conduit /Pvc Casing Capping Double Lock Type Erected Flushed On Wall/Ceiling Complete 4. Point Wiring For Light / Fan/ Bell/ Primary Point With 2-1.5 Sq. Mm & Earth Wire Of 1.5 Sq. Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto Max Length Of 10 Mt, In Below Type Of Pipe Erected With 6A Tissino Type Isi Marked Flush Type Switch / Bell Push And Accessories Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) /Acrylic/Laminated Sheet. With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping Erected Flushed On Wall/Ceiling Complete 5. Point Wiring For Light / Fan/ Bell/ Primary Point With 2-1.5 Sq. Mm & Earth Wire Of 1.5 Sq. Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto Max Length Of 10 Mt, In Below Type Of Pipe Erected With 6A Tissino Type Isi Marked Flush Type Switch / Bell Push And Accessories Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) /Acrylic/Laminated Sheet. With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (E) In Existing Pipe Erected Flushed On Wall/Ceiling Complete 6. Point Wiring For Light / Fan/ Bell/ Primary Point With 2-1.5 Sq. Mm & Earth Wire Of 1.5 Sq. Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto Max Length Of 10 Mt, In Below Type Of Pipe Erected With 6A Tissino Type Isi Marked Flush Type Switch / Bell Push And Accessories Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) /Acrylic/Laminated Sheet. With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (F) With Medium Class Rigid Pvc Pipe And Accessories Erected Concealed In Wall/Ceiling Complete 7. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [A] For 6 Amp Plug And 6 Amp Switch With 2-1.5 Sq. Mm Cu. Mains From Near By Switchboard/Db Board Upto 6 Mt. (A) With Medium Class Rigid Pvc Pipe And Accessories Erected Flushed On Wall/Ceiling Complete 8. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [A] For 6 Amp Plug And 6 Amp Switch With 2-1.5 Sq. Mm Cu. Mains From Near By Switchboard/Db Board Upto 6 Mt. (B) With 16 Swg(1.6 Mm Thick) Hgs Metal Conduit Pipe And Accessories Painted Black Erected Flushed On Wall/Ceiling Complete 9. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [A] For 6 Amp Plug And 6 Amp Switch With 2-1.5 Sq. Mm Cu. Mains From Near By Switchboard/Db Board Upto 6 Mt. ( C) With Oval Conduit /Pvc Casing Capping Double Lock Type Erected Flushed On Wall/Ceiling Complete 10. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [A] For 6 Amp Plug And 6 Amp Switch With 2-1.5 Sq. Mm Cu. Mains From Near By Switchboard/Db Board Upto 6 Mt. (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping Erected Flushed On Wall/Ceiling Complete 11. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [A] For 6 Amp Plug And 6 Amp Switch With 2-1.5 Sq. Mm Cu. Mains From Near By Switchboard/Db Board Upto 6 Mt. (E) In Existing Pipe Erected Flushed On Wall/Ceiling Complete 12. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [A] For 6 Amp Plug And 6 Amp Switch With 2-1.5 Sq. Mm Cu. Mains From Near By Switchboard/Db Board Upto 6 Mt. (F) With Medium Class Rigid Pvc Pipe And Accessories Erected Concealed In Wall/Ceiling Complete 13. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [B] 6/16A Plug And 16 Amp Switch With 2-2.5 Sq. Mm Cu. Mains From Mcb D B Boards. (A) With Medium Class Rigid Pvc Pipe And Accessories Erected Flushed On Wall/Ceiling Complete 14. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [B] 6/16A Plug And 16 Amp Switch With 2-2.5 Sq. Mm Cu. Mains From Mcb D B Boards. (B) With 16 Swg(1.6 Mm Thick) Hgs Metal Conduit Pipe And Accessories Painted Black Erected Flushed On Wall/Ceiling Complete 15. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [B] 6/16A Plug And 16 Amp Switch With 2-2.5 Sq. Mm Cu. Mains From Mcb D B Boards. ( C) With Oval Conduit /Pvc Casing Capping Double Lock Type Erected Flushed On Wall/Ceiling Complete 16. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [B] 6/16A Plug And 16 Amp Switch With 2-2.5 Sq. Mm Cu. Mains From Mcb D B Boards. (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping Erected Flushed On Wall/Ceiling Complete 17. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [B] 6/16A Plug And 16 Amp Switch With 2-2.5 Sq. Mm Cu. Mains From Mcb D B Boards. (E) In Existing Pipe Erected Flushed On Wall/Ceiling Complete 18. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [B] 6/16A Plug And 16 Amp Switch With 2-2.5 Sq. Mm Cu. Mains From Mcb D B Boards. (F) With Medium Class Rigid Pvc Pipe And Accessories Erected Concealed In Wall/Ceiling Complete 19. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [C] 6/16A Plug And 16 A Switch With 2-4 Sq.Mm Cu. Mains With 2.5 Sq.Mm ( Green) Earthing Wire (A) With Medium Class Rigid Pvc Pipe And Accessories Erected Flushed On Wall/Ceiling Complete 20. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [C] 6/16A Plug And 16 A Switch With 2-4 Sq.Mm Cu. Mains With 2.5 Sq.Mm ( Green) Earthing Wire (B) With 16 Swg(1.6 Mm Thick) Hgs Metal Conduit Pipe And Accessories Painted Black Erected Flushed On Wall/Ceiling Complete 21. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [C] 6/16A Plug And 16 A Switch With 2-4 Sq.Mm Cu. Mains With 2.5 Sq.Mm ( Green) Earthing Wire ( C) With Oval Conduit /Pvc Casing Capping Double Lock Type Erected Flushed On Wall/Ceiling Complete 22. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [C] 6/16A Plug And 16 A Switch With 2-4 Sq.Mm Cu. Mains With 2.5 Sq.Mm ( Green) Earthing Wire (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping Erected Flushed On Wall/Ceiling Complete 23. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [C] 6/16A Plug And 16 A Switch With 2-4 Sq.Mm Cu. Mains With 2.5 Sq.Mm ( Green) Earthing Wire (E) In Existing Pipe Erected Flushed On Wall/Ceiling Complete 24. Point Wiring For Independent Plug With Following Size Mains Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Upto 10 Mt Length, In Following Below Of Pipe Erected Complete With Isi Marked 3 / 5 Pin Socket And Tissino Type Switch Erected With Earth Continuity Connection Erected On Metal / Pvc/Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic/Laminated Sheet. [C] 6/16A Plug And 16 A Switch With 2-4 Sq.Mm Cu. Mains With 2.5 Sq.Mm ( Green) Earthing Wire (F) With Medium Class Rigid Pvc Pipe And Accessories Erected Concealed In Wall/Ceiling Complete 25. Point Wiring For On Board Looped Plug With Tissino Type Single Pole Isi Marked Switch And Socket Erected With Necessary Connections Erected On Wooden /Metal/ Pvc Box Covered With 3 Mm Thick Pc(Polycarbonate) /Acrylic Sheet For Open / Concealed Wiring For Following Size. [A] For 6 Amp. 26. Point Wiring For On Board Looped Plug With Tissino Type Single Pole Isi Marked Switch And Socket Erected With Necessary Connections Erected On Wooden /Metal/ Pvc Box Covered With 3 Mm Thick Pc(Polycarbonate) /Acrylic Sheet For Open / Concealed Wiring For Following Size. [B] For 16 Amp. 27. Point Wiring For Two Way Controlled Light Point With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Following Type Of Pipe To Be Erected Concealed In / Flushed On Wall / Ceiling Complete With 6A Tissino Type Isi Marked Accessories With Earth Continuity Erected On Metal/Pvc//Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic Sheet. With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (A) With Medium Class Rigid Pvc Pipe And Accessories Erected Flushed On Wall/Ceiling Complete 28. Point Wiring For Two Way Controlled Light Point With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Following Type Of Pipe To Be Erected Concealed In / Flushed On Wall / Ceiling Complete With 6A Tissino Type Isi Marked Accessories With Earth Continuity Erected On Metal/Pvc//Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic Sheet. With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (B) With 16 Swg(1.6 Mm Thick) Hgs Metal Conduit Pipe And Accessories Painted Black Erected Flushed On Wall/Ceiling Complete 29. Point Wiring For Two Way Controlled Light Point With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Following Type Of Pipe To Be Erected Concealed In / Flushed On Wall / Ceiling Complete With 6A Tissino Type Isi Marked Accessories With Earth Continuity Erected On Metal/Pvc//Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic Sheet. With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. ( C) With Oval Conduit /Pvc Casing Capping Double Lock Type Erected Flushed On Wall/Ceiling Complete 30. Point Wiring For Two Way Controlled Light Point With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Following Type Of Pipe To Be Erected Concealed In / Flushed On Wall / Ceiling Complete With 6A Tissino Type Isi Marked Accessories With Earth Continuity Erected On Metal/Pvc//Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic Sheet. With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping Erected Flushed On Wall/Ceiling Complete 31. Point Wiring For Two Way Controlled Light Point With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Following Type Of Pipe To Be Erected Concealed In / Flushed On Wall / Ceiling Complete With 6A Tissino Type Isi Marked Accessories With Earth Continuity Erected On Metal/Pvc//Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic Sheet. With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (E) In Existing Pipe Erected Flushed On Wall/Ceiling Complete 32. Point Wiring For Two Way Controlled Light Point With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Following Type Of Pipe To Be Erected Concealed In / Flushed On Wall / Ceiling Complete With 6A Tissino Type Isi Marked Accessories With Earth Continuity Erected On Metal/Pvc//Wooden Box Covered With 3 Mm Thick Pc(Polycarbonate) / Acrylic Sheet. With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (F) With Medium Class Rigid Pvc Pipe And Accessories Erected Concealed In Wall/Ceiling Complete 33. Point Wiring For Light / Bell With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length , In Below Type Of Pipe Erected With 6A Modular Type Switch / Bell Push & Accessories And Earth Continuity Of Following Type, Erected On Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured/Metallic/White Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected, With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (A) With Medium Class Rigid Pvc Pipe And Accessories Erected Flushed On Wall/Ceiling Complete Cat. Ii 34. Point Wiring For Light / Bell With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length , In Below Type Of Pipe Erected With 6A Modular Type Switch / Bell Push & Accessories And Earth Continuity Of Following Type, Erected On Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured/Metallic/White Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected, With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (B) With 16 Swg Hgs Metal Conduit Pipe And Accessories Painted Black Erected Flushed On Wall/Ceiling Complete Cat. Ii 35. Point Wiring For Light / Bell With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length , In Below Type Of Pipe Erected With 6A Modular Type Switch / Bell Push & Accessories And Earth Continuity Of Following Type, Erected On Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured/Metallic/White Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected, With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. ( C) With Oval Conduit /Pvc Casing Capping Double Lock Type Erected Flushed On Wall/Ceiling Complete Cat. Ii 36. Point Wiring For Light / Bell With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length , In Below Type Of Pipe Erected With 6A Modular Type Switch / Bell Push & Accessories And Earth Continuity Of Following Type, Erected On Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured/Metallic/White Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected, With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed. (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping Erected Flushed On Wall/Ceiling Complete Cat. Ii 37. Point Wiring For Light / Bell With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length , In Below Type Of Pipe Erected With 6A Modular Type Switch / Bell Push & Accessories And Earth Continuity Of Following Type, Erected On Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured/Metallic/White Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected, With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed.(E) In Existing Pipe Erected Flushed On Wall/Ceiling Complete Cat. Ii 38. Point Wiring For Light / Bell With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length , In Below Type Of Pipe Erected With 6A Modular Type Switch / Bell Push & Accessories And Earth Continuity Of Following Type, Erected On Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured/Metallic/White Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected, With Necessary Lamp Holder/Ceiling Rose / H.D.Connector As Directed.(F) With Medium Class Rigid Pvc Pipe And Accessories Erected Concealed In Wall/Ceiling Complete Cat. Ii 39. Point Wiring For Fan With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of .Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected With 6A Modular Type Switch And Hum Free Eme Four Or More Step Type Electronic Fan Regulator With Separately Mounted And Accessories With Earth Continuity Of Following Type Erected On Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured/Metallic/White Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected. With Necessary Ceiling Rose / H.D.Connector As Directed. (A) With Medium Class Rigid Pvc Pipe And Accessories Erected Flushed On Wall/Ceiling Complete Cat. Ii 40. Point Wiring For Fan With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of .Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected With 6A Modular Type Switch And Hum Free Eme Four Or More Step Type Electronic Fan Regulator With Separately Mounted And Accessories With Earth Continuity Of Following Type Erected On Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured/Metallic/White Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected. With Necessary Ceiling Rose / H.D.Connector As Directed. (B) With 16 Swg Hgs Metal Conduit Pipe And Accessories Painted Black Erected Flushed On Wall/Ceiling Complete Cat. Ii 41. Point Wiring For Fan With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of .Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected With 6A Modular Type Switch And Hum Free Eme Four Or More Step Type Electronic Fan Regulator With Separately Mounted And Accessories With Earth Continuity Of Following Type Erected On Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured/Metallic/White Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected. With Necessary Ceiling Rose / H.D.Connector As Directed. ( C) With Oval Conduit /Pvc Casing Capping Double Lock Type Erected Flushed On Wall/Ceiling Complete Cat. Ii 42. Point Wiring For Fan With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of .Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected With 6A Modular Type Switch And Hum Free Eme Four Or More Step Type Electronic Fan Regulator With Separately Mounted And Accessories With Earth Continuity Of Following Type Erected On Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured/Metallic/White Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected. With Necessary Ceiling Rose / H.D.Connector As Directed. (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping Erected Flushed On Wall/Ceiling Complete Cat. Ii 43. Point Wiring For Fan With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of .Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected With 6A Modular Type Switch And Hum Free Eme Four Or More Step Type Electronic Fan Regulator With Separately Mounted And Accessories With Earth Continuity Of Following Type Erected On Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured/Metallic/White Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected. With Necessary Ceiling Rose / H.D.Connector As Directed. (E) In Existing Pipe Erected Flushed On Wall/Ceiling Complete Cat. Ii 44. Point Wiring For Fan With 2-1.5 Sq.Mm & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of .Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected With 6A Modular Type Switch And Hum Free Eme Four Or More Step Type Electronic Fan Regulator With Separately Mounted And Accessories With Earth Continuity Of Following Type Erected On Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured/Metallic/White Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected. With Necessary Ceiling Rose / H.D.Connector As Directed. (F) With Medium Class Rigid Pvc Pipe And Accessories Erected Concealed In Wall/Ceiling Complete Cat. Ii 45. Point Wiring For Individual Plug With & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected Complete With Modular Type Switch & 5 Pin Plug Erected On Pvc / Metallic/Wooden Box Covered With Appropriate Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected With Following Type Of Accessories. [I] For 6A Plug And 6 A Switch With 2-1.5 Sq.Mm Cu. Wire From Nearby Switchboard/Mcb Db Board (A) With Medium Class Rigid Pvc Pipe And Accessories Erected Flushed On Wall/Ceiling Complete Cat. Ii 46. Point Wiring For Individual Plug With & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected Complete With Modular Type Switch & 5 Pin Plug Erected On Pvc / Metallic/Wooden Box Covered With Appropriate Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected With Following Type Of Accessories. [I] For 6A Plug And 6 A Switch With 2-1.5 Sq.Mm Cu. Wire From Nearby Switchboard/Mcb Db Board (B) With 16 Swg Hgs Metal Conduit Pipe And Accessories Painted Black Erected Flushed On Wall/Ceiling Complete Cat. Ii 47. Point Wiring For Individual Plug With & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected Complete With Modular Type Switch & 5 Pin Plug Erected On Pvc / Metallic/Wooden Box Covered With Appropriate Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected With Following Type Of Accessories. [I] For 6A Plug And 6 A Switch With 2-1.5 Sq.Mm Cu. Wire From Nearby Switchboard/Mcb Db Board ( C) With Oval Conduit /Pvc Casing Capping Double Lock Type Erected Flushed On Wall/Ceiling Complete Cat. Ii 48. Point Wiring For Individual Plug With & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected Complete With Modular Type Switch & 5 Pin Plug Erected On Pvc / Metallic/Wooden Box Covered With Appropriate Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected With Following Type Of Accessories. [I] For 6A Plug And 6 A Switch With 2-1.5 Sq.Mm Cu. Wire From Nearby Switchboard/Mcb Db Board (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping Erected Flushed On Wall/Ceiling Complete Cat. Ii 49. Point Wiring For Individual Plug With & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected Complete With Modular Type Switch & 5 Pin Plug Erected On Pvc / Metallic/Wooden Box Covered With Appropriate Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected With Following Type Of Accessories. [I] For 6A Plug And 6 A Switch With 2-1.5 Sq.Mm Cu. Wire From Nearby Switchboard/Mcb Db Board (E) In Existing Pipe Erected Flushed On Wall/Ceiling Complete Cat. Ii 50. Point Wiring For Individual Plug With & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected Complete With Modular Type Switch & 5 Pin Plug Erected On Pvc / Metallic/Wooden Box Covered With Appropriate Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected With Following Type Of Accessories. [I] For 6A Plug And 6 A Switch With 2-1.5 Sq.Mm Cu. Wire From Nearby Switchboard/Mcb Db Board (F) With Medium Class Rigid Pvc Pipe And Accessories Erected Concealed In Wall/Ceiling Complete Cat. Ii 51. Point Wiring For Individual Plug With & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected Complete With Modular Type Switch & 5 Pin Plug Erected On Pvc / Metallic/Wooden Box Covered With Appropriate Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected With Following Type Of Accessories. [Ii] For 16A Plug And 16 Amp Switch With 2-2.5 Sq.Mm Cu. Wire From Mcb Db Board. (A) With Medium Class Rigid Pvc Pipe And Accessories Erected Flushed On Wall/Ceiling Complete Cat. Ii 52. Point Wiring For Individual Plug With & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected Complete With Modular Type Switch & 5 Pin Plug Erected On Pvc / Metallic/Wooden Box Covered With Appropriate Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected With Following Type Of Accessories. [Ii] For 16A Plug And 16 Amp Switch With 2-2.5 Sq.Mm Cu. Wire From Mcb Db Board. (B) With 16 Swg Hgs Metal Conduit Pipe And Accessories Painted Black Erected Flushed On Wall/Ceiling Complete Cat. Ii 53. Point Wiring For Individual Plug With & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected Complete With Modular Type Switch & 5 Pin Plug Erected On Pvc / Metallic/Wooden Box Covered With Appropriate Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected With Following Type Of Accessories. [Ii] For 16A Plug And 16 Amp Switch With 2-2.5 Sq.Mm Cu. Wire From Mcb Db Board. ( C) With Oval Conduit /Pvc Casing Capping Double Lock Type Erected Flushed On Wall/Ceiling Complete Cat. Ii 54. Point Wiring For Individual Plug With & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected Complete With Modular Type Switch & 5 Pin Plug Erected On Pvc / Metallic/Wooden Box Covered With Appropriate Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected With Following Type Of Accessories. [Ii] For 16A Plug And 16 Amp Switch With 2-2.5 Sq.Mm Cu. Wire From Mcb Db Board. (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping Erected Flushed On Wall/Ceiling Complete Cat. Ii 55. Point Wiring For Individual Plug With & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected Complete With Modular Type Switch & 5 Pin Plug Erected On Pvc / Metallic/Wooden Box Covered With Appropriate Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected With Following Type Of Accessories. [Ii] For 16A Plug And 16 Amp Switch With 2-2.5 Sq.Mm Cu. Wire From Mcb Db Board. (E) In Existing Pipe Erected Flushed On Wall/Ceiling Complete Cat. Ii 56. Point Wiring For Individual Plug With & Earth Wire Of 1.5 Sq.Mm (Green) Both Are Of Isi Marked 1.1 Kv Grade Frls Pvc Insulated Multi Strand Copper Wires Up To 10 Mtr Length, In Below Type Of Pipe Erected Complete With Modular Type Switch & 5 Pin Plug Erected On Pvc / Metallic/Wooden Box Covered With Appropriate Front Plate Modules Erected On / In Wall / Ceiling As Per Pipe Erected With Following Type Of Accessories. [Ii] For 16A Plug And 16 Amp Switch With 2-2.5 Sq.Mm Cu. Wire From Mcb Db Board. (F) With Medium Class Rigid Pvc Pipe And Accessories Erected Concealed In Wall/Ceiling Complete Cat. Ii 57. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (1) One No. Sp 6 Amp. Cat.Ii 58. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (2) One No 5 Pin Plug Cat.Ii 59. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (3) Two Pin/Rj-11 Telephone Socket [A] For One Gang Cat.Ii 60. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (3) Two Pin/Rj-11 Telephone Socket [B] For Two Gang Cat.Ii 61. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (4) Tv Co-Axial Socket Outlet Cat.Ii 62. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (5) Electronic Hum Free Four Or More Steps Eme Fan Regulator Cat.Ii 63. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (6) Fuse Units 10Amp. Or 16 Amp. Cat.Ii 64. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (7) Blank Plate Single Cat.Ii 65. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (8) Computer Rj-45 Socket Cat.Ii 66. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (9) 16 Amp. Sp One Way Switch Cat.Ii 67. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (10) 6/16Amp. Universal Socket Cat.Ii 68. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (11) 6 Amps. Bell Push Cat.Ii 69. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (12) 6Amp. / 16 Amp. Two Way Switch Cat.Ii 70. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (13) 6A/10A/16A/20A/25A/32A Single Pole Modular Mcb Switch Cat.Ii 71. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (14) 6A/ 10A/ 16A/ 20A/ 25A/ 32A Double Pole Modular Mcb Switch Cat.Ii 72. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (15) 32 Amps. Dp Switch With Indicator Cat.Ii 73. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (16) 32 Amp. Dp Main Switch Operating With Energy Key Tag Cat.Ii 74. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (17-A) For 400W / 450 Watt One Module Electronic Dimmer Cat.Ii 75. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (17-B) For 600 / 650 Watt Two Module Electronic Dimmer Dimmer Cat.Ii 76. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (17-C) For 1000 Watt Two Module Electronic Dimmer Cat.Ii 77. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (18) 13 Amp. International Modular Socket Cat.Ii 78. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (20) Modular Buzzer Cat.Ii 79. Providing Following Type Of Modular Type Accessories Mounted With Pvc / Metallic/Wooden Box, Single Mounting Base Frame Covered With Textured / Metallic/White Front Plate , Modules Erected With Necessary Connections As Per Site Situation Directed By Engineer In Charge. (22) 16/20/25 Amp. Modular Starter For Motor / A.C. Unit Complete Cat.Ii 80. Providing And Erecting Isi Mark Medium Class Rigid Pvc Pipes Of Following Size Complete To Be Erected On/In Wall Or Ceiling Erected With Necessary Pvc Fittings & Junction Boxes Fixed With Adhesive Solution & Clamps With Following Dia Of Pipes, In Approved Manner As Directed (A)20 Mm 81. Providing And Erecting Isi Mark Medium Class Rigid Pvc Pipes Of Following Size Complete To Be Erected On/In Wall Or Ceiling Erected With Necessary Pvc Fittings & Junction Boxes Fixed With Adhesive Solution & Clamps With Following Dia Of Pipes, In Approved Manner As Directed (B) 25 Mm 82. Providing And Erecting Isi Mark Medium Class Rigid Pvc Pipes Of Following Size Complete To Be Erected On/In Wall Or Ceiling Erected With Necessary Pvc Fittings & Junction Boxes Fixed With Adhesive Solution & Clamps With Following Dia Of Pipes, In Approved Manner As Directed (C) 32 Mm 83. Providing & Erecting Approved Make Oval Conduit With Necessary Fittings Fixed With Adhesive Solution And Suitable Clamps Erected On Wall / Ceiling Of Following Size. (1) 20 Mm 84. Providing & Erecting Approved Make Oval Conduit With Necessary Fittings Fixed With Adhesive Solution And Suitable Clamps Erected On Wall / Ceiling Of Following Size. (2) 25Mm 85. Supplying & Erecting Upvc Mini Trunking (Pvc Casing-N-Capping) Having Double-Locking Arrangement With Grooves, Trunking Of Size Not Below 12.5 Mm In Height As Per Is With Accessories Of Pvc/Resin Polypropylene Not Below 1.8 Mm Thick Duly Sealed In Joint & Erected On Wall / Ceiling Of Following Size . (1) 20 Mm 86. Supplying & Erecting Upvc Mini Trunking (Pvc Casing-N-Capping) Having Double-Locking Arrangement With Grooves, Trunking Of Size Not Below 12.5 Mm In Height As Per Is With Accessories Of Pvc/Resin Polypropylene Not Below 1.8 Mm Thick Duly Sealed In Joint & Erected On Wall / Ceiling Of Following Size . (2) 25 Mm 87. Supplying & Erecting Upvc Mini Trunking (Pvc Casing-N-Capping) Having Double-Locking Arrangement With Grooves, Trunking Of Size Not Below 12.5 Mm In Height As Per Is With Accessories Of Pvc/Resin Polypropylene Not Below 1.8 Mm Thick Duly Sealed In Joint & Erected On Wall / Ceiling Of Following Size . (3) 32 Mm 88. Supplying And Laying Upvc Cable Trunking System Comprising Unplasticised Polyvinyl, Chloride Rigid Material With Ignition Free And Flame Proof Confirming Bs With Necessary End Caps Internal And External Bend, Flat Bends, Coupler, Tee Etc..All Necessary Accessories And Measuring Of Following Sizes (1) 75 Mm X 50 Mm Trunking 89. Supplying And Laying Upvc Cable Trunking System Comprising Unplasticised Polyvinyl, Chloride Rigid Material With Ignition Free And Flame Proof Confirming Bs With Necessary End Caps Internal And External Bend, Flat Bends, Coupler, Tee Etc..All Necessary Accessories And Measuring Of Following Sizes (2) 100 Mm X 50 Mm Trunking 90. Supply & Installation Of Modular Type Accessories For U Pvc Snap-On Adaptable Trunking/Pop Up Box With Required Items Erected With Necessary Connection. As Desired By Engineer In Charge I) 6 A Sp 1 Way Switch Cat-Iii 91. Supply & Installation Of Modular Type Accessories For U Pvc Snap-On Adaptable Trunking/Pop Up Box With Required Items Erected With Necessary Connection. As Desired By Engineer In Charge Ii) 16A Sp 1 Way Switch Cat-Iii 92. Supply & Installation Of Modular Type Accessories For U Pvc Snap-On Adaptable Trunking/Pop Up Box With Required Items Erected With Necessary Connection. As Desired By Engineer In Charge Iii) Bell Push 6 A Sp 1 Way Cat-Iii 93. Supply & Installation Of Modular Type Accessories For U Pvc Snap-On Adaptable Trunking/Pop Up Box With Required Items Erected With Necessary Connection. As Desired By Engineer In Charge Iv) 6A Universal Socket Shuttered Cat-Iii 94. Supply & Installation Of Modular Type Accessories For U Pvc Snap-On Adaptable Trunking/Pop Up Box With Required Items Erected With Necessary Connection. As Desired By Engineer In Charge Iv) 6/16 A Universal Socket Shuttered Cat-Iii 95. Supply & Installation Of Modular Type Accessories For U Pvc Snap-On Adaptable Trunking/Pop Up Box With Required Items Erected With Necessary Connection. As Desired By Engineer In Charge V) Rj-11 Telephone Socket Cat-Iii 96. Supply & Installation Of Modular Type Accessories For U Pvc Snap-On Adaptable Trunking/Pop Up Box With Required Items Erected With Necessary Connection. As Desired By Engineer In Charge Vi) Cat-6 Lan Socket Cat-Iii 97. Providing & Erecting 16 Gauge Hgs Conduit Pipe (As Per Is) Painted Black Surface/Concealed Of Following Size Complete To Be Erected On/In Wall Or Ceiling With Erected With Necessary Saddles, Screws, Bends, Junction Boxes Etc. With Following (Nominal Bore) Dia Of Pipes, In Approved Manner As Directed (1) 19/20 Mm 98. Providing & Erecting 16 Gauge Hgs Conduit Pipe (As Per Is) Painted Black Surface/Concealed Of Following Size Complete To Be Erected On/In Wall Or Ceiling With Erected With Necessary Saddles, Screws, Bends, Junction Boxes Etc. With Following (Nominal Bore) Dia Of Pipes, In Approved Manner As Directed (2) 25 Mm 99. Providing & Erecting 16 Gauge Hgs Conduit Pipe (As Per Is) Painted Black Surface/Concealed Of Following Size Complete To Be Erected On/In Wall Or Ceiling With Erected With Necessary Saddles, Screws, Bends, Junction Boxes Etc. With Following (Nominal Bore) Dia Of Pipes, In Approved Manner As Directed (3) 32 Mm 100. Providing & Erecting 16 Gauge Hgs Conduit Pipe (As Per Is) Painted Black Surface/Concealed Of Following Size Complete To Be Erected On/In Wall Or Ceiling With Erected With Necessary Saddles, Screws, Bends, Junction Boxes Etc. With Following (Nominal Bore) Dia Of Pipes, In Approved Manner As Directed (4) 38/40 Mm 101. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (A) 2 Wire 1.5 Sq. Mm 102. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (B) 2 Wire 2.5 Sq. Mm 103. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (C) 3 Wire 1.5 Sq. Mm 104. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (D) 3 Wire 2.5 Sq. Mm 105. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (E) 4 Wire 1.5 Sq. Mm 106. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (F) 4 Wire 2.5 Sq. Mm 107. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (G) 6 Wire 2.5 Sq. Mm 108. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (A) 2 Wire 1.5 Sq. Mm 109. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (B) 2 Wire 2.5 Sq. Mm 110. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (C) 3 Wire 1.5 Sq. Mm 111. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (D) 3 Wire 2.5 Sq. Mm 112. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (E) 4 Wire 1.5 Sq. Mm 113. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (F) 4 Wire 2.5 Sq. Mm 114. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (G) 6 Wire 2.5 Sq. Mm 115. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping (A) 2 Wire 1.5 Sq. Mm 116. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping (B) 2 Wire 2.5 Sq. Mm 117. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping (C) 3 Wire 1.5 Sq. Mm 118. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping (D) 3 Wire 2.5 Sq. Mm 119. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping (E) 4 Wire 1.5 Sq. Mm 120. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping (F) 4 Wire 2.5 Sq. Mm 121. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected Concealed In /Flushed On Wall/Ceiling, With 1.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (D) Partial Pvc Pipe And Drops In Oval Conduit / Pvc Casing Capping (G) 6 Wire 2.5 Sq. Mm 122. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (A) 2 Wire 4 Sq. Mm 123. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (B) 2 Wire 6 Sq. Mm 124. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (C) 2 Wire 10 Sq. Mm 125. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (D) 3 Wire 4 Sq. Mm 126. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (E) 3 Wire 6 Sq. Mm 127. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (F) 3 Wire 10 Sq. Mm(Use Earth Wire Of 4 Sq.Mm ) 128. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (G) 4 Wire 4 Sq. Mm 129. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (H) 4 Wire 6 Sq. Mm 130. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (A) With Medium Class Rigid Pvc Pipe And Accessories (I) 4 Wire 10 Sq. Mm (Use Earth Wire Of 4 Sq.Mm ) 131. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (A) 2 Wire 4 Sq. Mm 132. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (B) 2 Wire 6 Sq. Mm 133. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (C) 2 Wire 10 Sq. Mm 134. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (D) 3 Wire 4 Sq. Mm 135. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (E) 3 Wire 6 Sq. Mm 136. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (F) 3 Wire 10 Sq. Mm(Use Earth Wire Of 4 Sq.Mm ) 137. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (G) 4 Wire 4 Sq. Mm 138. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (H) 4 Wire 6 Sq. Mm 139. Providing And Erecting Mains With 1.1 Kv Grade Frls Pvc Insulated Isi Marked Stranded Copper Conductor Wire In Following Type Of Pipe To Be Erected In / On Wall / Ceiling With 2.5 Sq. Mm Copper Conductor Frls Pvc Insulated Stranded Wire Of Green Colour For Earth Continuity Of Following Size (C) With Oval Conduit /Pvc Casing Capping Double Lock Type (I) 4 Wire 10 Sq. Mm (Use Earth Wire Of 4 Sq.Mm ) 140. Supplying And Erecting Flexible Pvc Insulated Multi Strand Multi Core 1.1 Kv Grade Isi Marked Copper Wires Of Following Size To Be Erected As Directed. A) 0.75 Sq.Mm Twin Twisted 141. Supplying And Erecting Flexible Pvc Insulated Multi Strand Multi Core 1.1 Kv Grade Isi Marked Copper Wires Of Following Size To Be Erected As Directed. B) 1.00 Sq.Mm Twin Twisted 142. Supplying And Erecting Flexible Pvc Insulated Multi Strand Multi Core 1.1 Kv Grade Isi Marked Copper Wires Of Following Size To Be Erected As Directed. C) 1.00 Sq.Mm 2 Core Round/ Flat Pvc Sheathed 143. Supplying And Erecting Flexible Pvc Insulated Multi Strand Multi Core 1.1 Kv Grade Isi Marked Copper Wires Of Following Size To Be Erected As Directed. D) 1.50 Sq.Mm 2 Core Round Pvc Sheathed 144. Supplying And Erecting Flexible Pvc Insulated Multi Strand Multi Core 1.1 Kv Grade Isi Marked Copper Wires Of Following Size To Be Erected As Directed. E) 1.50 Sq.Mm 3 Core Round Pvc Sheathed 145. Supplying And Erecting Flexible Pvc Insulated Multi Strand Multi Core 1.1 Kv Grade Isi Marked Copper Wires Of Following Size To Be Erected As Directed. F) 1.50 Sq.Mm 4 Core Round Pvc Sheathed 146. Supplying And Erecting Flexible Pvc Insulated Multi Strand Multi Core 1.1 Kv Grade Isi Marked Copper Wires Of Following Size To Be Erected As Directed. G) 2.50 Sq.Mm 2 Core Round Pvc Sheathed 147. Supplying And Erecting Flexible Pvc Insulated Multi Strand Multi Core 1.1 Kv Grade Isi Marked Copper Wires Of Following Size To Be Erected As Directed. H) 2.50 Sq.Mm 3 Core Round Pvc Sheathed 148. Supplying And Erecting Flexible Pvc Insulated Multi Strand Multi Core 1.1 Kv Grade Isi Marked Copper Wires Of Following Size To Be Erected As Directed. I) 2.50 Sq.Mm 4 Core Round Pvc Sheathed 149. Supplying And Erecting Flexible Pvc Insulated Multi Strand Multi Core 1.1 Kv Grade Isi Marked Copper Wires Of Following Size To Be Erected As Directed. J) 4.00 Sq.Mm 3 Core Round Pvc Sheathed 150. Supplying And Erecting Flexible Pvc Insulated Multi Strand Multi Core 1.1 Kv Grade Isi Marked Copper Wires Of Following Size To Be Erected As Directed. K) 4.00Sq.Mm 4 Core Round Pvc Sheathed 151. Supplying & Erecting Approved Make Telephone Cable Electrolytic Copper Conductor Pe Insulation Twisted In Two Pairs, & Wrapped With Frls Pvc Tape & Sheathed With Frls Pvc Or Hffr Outer Jacket Suitable For Telephone Wiring & Confirming To C-Dot Erected In Existing Pipe. Of Following Size Of Conductors & Nos.Of Pairs. With Necessary Connections. [A] Conductor Size 0.5 Mm (A) Unarmoured 1) One Pair 152. Supplying & Erecting Approved Make Telephone Cable Electrolytic Copper Conductor Pe Insulation Twisted In Two Pairs, & Wrapped With Frls Pvc Tape & Sheathed With Frls Pvc Or Hffr Outer Jacket Suitable For Telephone Wiring & Confirming To C-Dot Erected In Existing Pipe. Of Following Size Of Conductors & Nos.Of Pairs. With Necessary Connections. [A] Conductor Size 0.5 Mm (A) Unarmoured 2) Two Pairs 153. Supplying & Erecting Approved Make Telephone Cable Electrolytic Copper Conductor Pe Insulation Twisted In Two Pairs, & Wrapped With Frls Pvc Tape & Sheathed With Frls Pvc Or Hffr Outer Jacket Suitable For Telephone Wiring & Confirming To C-Dot Erected In Existing Pipe. Of Following Size Of Conductors & Nos.Of Pairs. With Necessary Connections. [A] Conductor Size 0.5 Mm (A) Unarmoured 3) Three Pairs 154. Supplying & Erecting Approved Make Telephone Cable Electrolytic Copper Conductor Pe Insulation Twisted In Two Pairs, & Wrapped With Frls Pvc Tape & Sheathed With Frls Pvc Or Hffr Outer Jacket Suitable For Telephone Wiring & Confirming To C-Dot Erected In Existing Pipe. Of Following Size Of Conductors & Nos.Of Pairs. With Necessary Connections. [A] Conductor Size 0.5 Mm (A) Unarmoured 4) Five Pairs 155. Supplying & Erecting Approved Make Telephone Cable Electrolytic Copper Conductor Pe Insulation Twisted In Two Pairs, & Wrapped With Frls Pvc Tape & Sheathed With Frls Pvc Or Hffr Outer Jacket Suitable For Telephone Wiring & Confirming To C-Dot Erected In Existing Pipe. Of Following Size Of Conductors & Nos.Of Pairs. With Necessary Connections. [A] Conductor Size 0.5 Mm (A) Unarmoured 5) Ten Pairs 156. Supplying & Erecting Approved Make Telephone Cable Electrolytic Copper Conductor Pe Insulation Twisted In Two Pairs, & Wrapped With Frls Pvc Tape & Sheathed With Frls Pvc Or Hffr Outer Jacket Suitable For Telephone Wiring & Confirming To C-Dot Erected In Existing Pipe. Of Following Size Of Conductors & Nos.Of Pairs. With Necessary Connections. [A] Conductor Size 0.5 Mm (A) Unarmoured 6) Twenty Pairs 157. Supplying & Erecting Approved Make Lan Cable Of Following Size In Existing Pipe As Per Direction [C] Cat - 6 158. Providing & Erecting Switch Board For Computer Or Electric Apparatus Consisting Of Following Modular Type Accessories Mounted With Pvc / Metallic Concealed/Open Box With Single Mounting Base Frame Covered With Textured/Metallic /White Front Plate,Modules Erected With Necessary Connections As Directed1 No. 6A/16A Universal Plug-Switch Combined.3 Nos. 6A Switch3 Nos. 6A 5 Pin Plug For Modular Type Accessories Cat. Ii 159. Approved Make High Pressure Sodium Vapour Lamp, Tubular/Elliptical Type 70W. 230/240/250V. Erected, If Required. Cat.Ii 160. Approved Make High Pressure Sodium Vapour Lamp, Tubular/Elliptical Type 150W, 230/240/250V, Erected , If Required Cat.Ii 161. Approved Make Cfl Retrofit 5 / 7 / 9 /11 Watt, Erected If Required Cat.Ii 162. Approved Make C.F.L. Retrofit 13/15/18 Watt Erected If Required Cat.Ii 163. Approved Make C.F.L.Retrofit 20 / 23 / 25 / 26 Watt. Erected If Required Cat.Ii 164. Approved Make C.F.L.Retrofit Of Following Size Erected If Required [A] 35/36 Watt Cat.Ii 165. Approved Make C.F.L.Retrofit Of Following Size Erected If Required [B] 40/45 Watt Cat.Ii 166. Approved Make C.F.L.Retrofit Of Following Size Erected If Required [C] 55/65/85 Watt Cat.Ii 167. Providing And Erecting Decorative Wall Bracket Fittings Complete With Led Lamp And Rust Free Fittings Components Mounted In Chrome Finish Housing With Holder ,Clear/Opaque Glass Diffuser Complete Erected With Lead Wires With Minimum 15 Wattage Capacity As Per Instruction Engineer Incharge/Architect/Authority .Cat-Iii 168. Supplying And Erecting Approved Make Of Tube Fitting With One No T-5 Tube 24/ 28 W With Electronic Ballast With Each Tube Separately Thd Less Than 10 & Built In Adaptors, Gi / Pvc Housing & Mirror Optic Reflector, Suitable To Work On 120V - 300V, A.C. Supply With Connector And Adapter If Required. [Make Of Fitting & Tube May Be Differ& Fitting Shall Be Providing With Tube] Cat Ii 169. Supplying & Erecting Energy Saving Energy Efficient E+ (1 - 4 Ft) 28 Watt Retrofit Tube Fitting With One No 28Watt T-5 Tube Complete With E.G.P. Wings Reflector / Clear Acrylic Guard Cover & Tube And Electronic Inbuilt Circuit Ballast Of Rating 130 To 325 V A.C. The Fittings Should Be Able To Fit In Any Conventional Existing T - 8 Tube Fittings Complete Erected In An Approved Manner. 170. Outdoor Street Light Fitting Side Entry With Clear Acrylic /Plastic / Polystyrene Cover Complete With Starter, Polyester Choke Copper Wound Complete Erected With 40/36 Watt Tube Holders. With Lead Wire And Connections. (B) With 2 Tube 40 Watt.120 Cms. Cat.Ii 171. Providing And Erecting Approved Make C.F.L Out Door Type Street Light Fitting Side Entry With Clear Acrylic / Plastic Cover Electronic Ballast High Circuit P.F. Weather Proof Design (Ip 65) Thd Less Than 10% Rust Free Fitting Components Mounted In Powder Coated Crca / Al. Housing With Lead Wire & With Non Retrofit Cfl Tube Complete. [A] With One Cfl Tube 9 / 11/ 13 / 18 Watt Non Retrofit With Ballast & Holder Cat.Ii 172. Providing And Erecting Approved Make C.F.L Out Door Type Street Light Fitting Side Entry With Clear Acrylic / Plastic Cover Electronic Ballast High Circuit P.F. Weather Proof Design (Ip 65) Thd Less Than 10% Rust Free Fitting Components Mounted In Powder Coated Crca / Al. Housing With Lead Wire & With Non Retrofit Cfl Tube Complete.[B] With Two Cfl Tube 9 / 11/ 13 / 18 Watt Non Retrofit With Ballast & Holder Cat.Ii 173. Providing And Erecting Approved Make C.F.L Out Door Type Street Light Fitting Side Entry With Clear Acrylic / Plastic Cover Electronic Ballast High Circuit P.F. Weather Proof Design (Ip 65) Thd Less Than 10% Rust Free Fitting Components Mounted In Powder Coated Crca / Al. Housing With Lead Wire & With Non Retrofit Cfl Tube Complete.[C] With One Cfl Tube 36 Watt Retrofit Or Non Retrofit With Ballast & Holder Cat.Ii 174. Supply & Fixing Decorative Hanging Light With Glass Having Cylindrical Or Square Shape Having Length Not Less Than 10 & Width Not Less 3.5 With Holder, Lead Wire As Per Required Length But Not More Than 1Mm & Base Plate For Fixing The Fitting With Ceiling.[A] Suitable For Led Lamp Cat-Ii 175. Providing And Erecting Approved Make Street Light Luminaire With One No Suitable For- Hpsv / Mh Lamp Complete With Control Gear And Accessories , Single Piece Deep Drawn Aluminium Housing With Two Compartments Duly Stove Enameled Painted Side Reflector Protective Acrylic Cover, Synthetic Felt Gasket, Necessary Hardware. The Fitting Should Be Suitable For Side Entry Having Suitable Socket Bore For Clamping Complete Erected. (A) With 70 Watt Svl. /Metal Halide Lamp Cat.Ii 176. Providing And Erecting Approved Make Street Light Luminaire With One No Suitable For- Hpsv / Mh Lamp Complete With Control Gear And Accessories , Single Piece Deep Drawn Aluminium Housing With Two Compartments Duly Stove Enameled Painted Side Reflector Protective Acrylic Cover, Synthetic Felt Gasket, Necessary Hardware. The Fitting Should Be Suitable For Side Entry Having Suitable Socket Bore For Clamping Complete Erected. (B) With 150 Watt Svl. /Metal Halide Lamp Cat.Ii 177. Providing And Erecting Approved Make Street Light Luminaire With One No Suitable For- Hpsv / Mh Lamp Complete With Control Gear And Accessories , Single Piece Deep Drawn Aluminium Housing With Two Compartments Duly Stove Enameled Painted Side Reflector Protective Acrylic Cover, Synthetic Felt Gasket, Necessary Hardware. The Fitting Should Be Suitable For Side Entry Having Suitable Socket Bore For Clamping Complete Erected.(C) With 250 Watt Svl. /Metal Halide Lamp Cat.Ii 178. Supplying & Erecting Control Gear Box, Weather Proof Made Of Cast Aluminium With Heavy Duty Copper Polyester Choke, Condenser, Mcb, Connector Block & Earthing Terminal Complete Erected With Necessary Screws, Nuts & Bolts Clamps Suitable For (A) For Hpsv/Mh Lamp With Ignitor For One No. Lamp. (I) 7Ow Cat-Ll 179. Supplying & Erecting Control Gear Box, Weather Proof Made Of Cast Aluminium With Heavy Duty Copper Polyester Choke, Condenser, Mcb, Connector Block & Earthing Terminal Complete Erected With Necessary Screws, Nuts & Bolts Clamps Suitable For (A) For Hpsv/Mh Lamp With Ignitor For One No. Lamp. (Ii)150 W Cat-Ll 180. Supplying & Erecting Control Gear Box, Weather Proof Made Of Cast Aluminium With Heavy Duty Copper Polyester Choke, Condenser, Mcb, Connector Block & Earthing Terminal Complete Erected With Necessary Screws, Nuts & Bolts Clamps Suitable For (A) For Hpsv/Mh Lamp With Ignitor For One No. Lamp. (Iii)250 W Cat-Ll 181. Supplying & Erecting Control Gear Box, Weather Proof Made Of Cast Aluminium With Heavy Duty Copper Polyester Choke, Condenser, Mcb, Connector Block & Earthing Terminal Complete Erected With Necessary Screws, Nuts & Bolts Clamps Suitable For (A) For Hpsv/Mh Lamp With Ignitor For One No. Lamp. (Iv)40Ow Cat-Ll 182. Supplying And Erecting Led Indoor Fittings With Leds Of Wattage 0.2 Watt To 0.5 Watt Assembled On Single Mcpcb, With Housing Used As A Heat Sink Shall Be Made Of Thick Sheet Steel Conforming To Is: 513/Crca/ Aluminium Die Cast Powder Coated And High U.V. & Corrosion Resistance With Diffuser With Company Mark/Name 120 To 300 V,Power Factor More Than 0.9, Thd < 10 %,Cct 3000 K To 6500K, Luminaire Efficacy> 85 Lumens/Watt ,Led Efficiency-110 Lumens/Wattled Driver Efficiency > 85 %Cree / Osram / Philips Lumileds / Nichia / Seoul/Bridgelux Make Led Used For Luminaire. ( Fitting Required Lm-79 & Lm-80 Certificates)(Note: Below Description Have Shown Ranges Of Wattage Capacity Of Led Fittings.The Engineer Incharge May Select Any Wattage Capacity Between The Ranges Shown.) (A) Tube Light With Integral Driver (A) 5-9 Watts, Surge-2 Kv, Ip-20,2 Feet Cat-Ll 183. Supplying And Erecting Led Indoor Fittings With Leds Of Wattage 0.2 Watt To 0.5 Watt Assembled On Single Mcpcb, With Housing Used As A Heat Sink Shall Be Made Of Thick Sheet Steel Conforming To Is: 513/Crca/ Aluminium Die Cast Powder Coated And High U.V. & Corrosion Resistance With Diffuser With Company Mark/Name 120 To 300 V,Power Factor More Than 0.9, Thd < 10 %,Cct 3000 K To 6500K, Luminaire Efficacy> 85 Lumens/Watt ,Led Efficiency-110 Lumens/Wattled Driver Efficiency > 85 %Cree / Osram / Philips Lumileds / Nichia / Seoul/Bridgelux Make Led Used For Luminaire. ( Fitting Required Lm-79 & Lm-80 Certificates)(Note: Below Description Have Shown Ranges Of Wattage Capacity Of Led Fittings.The Engineer Incharge May Select Any Wattage Capacity Between The Ranges Shown.) (A) Tube Light With Integral Driver (B) 12-14 Watts, Surge-2 Kv, Ip-20, 4 Feet Cat-Ll 184. Supplying And Erecting Led Indoor Fittings With Leds Of Wattage 0.2 Watt To 0.5 Watt Assembled On Single Mcpcb, With Housing Used As A Heat Sink Shall Be Made Of Thick Sheet Steel Conforming To Is: 513/Crca/ Aluminium Die Cast Powder Coated And High U.V. & Corrosion Resistance With Diffuser With Company Mark/Name 120 To 300 V,Power Factor More Than 0.9, Thd < 10 %,Cct 3000 K To 6500K, Luminaire Efficacy> 85 Lumens/Watt ,Led Efficiency-110 Lumens/Wattled Driver Efficiency > 85 %Cree / Osram / Philips Lumileds / Nichia / Seoul/Bridgelux Make Led Used For Luminaire. ( Fitting Required Lm-79 & Lm-80 Certificates)(Note: Below Description Have Shown Ranges Of Wattage Capacity Of Led Fittings.The Engineer Incharge May Select Any Wattage Capacity Between The Ranges Shown.) (A) Tube Light With Integral Driver (C) 16-20 Watts, Surge - 2Kv,Ip-20, 4 Feet Cat-Ll 185. Supplying And Erecting Led Indoor Fittings With Leds Of Wattage 0.2 Watt To 0.5 Watt Assembled On Single Mcpcb, With Housing Used As A Heat Sink Shall Be Made Of Thick Sheet Steel Conforming To Is: 513/Crca/ Aluminium Die Cast Powder Coated And High U.V. & Corrosion Resistance With Diffuser With Company Mark/Name 120 To 300 V,Power Factor More Than 0.9, Thd < 10 %,Cct 3000 K To 6500K, Luminaire Efficacy> 85 Lumens/Watt ,Led Efficiency-110 Lumens/Wattled Driver Efficiency > 85 %Cree / Osram / Philips Lumileds / Nichia / Seoul/Bridgelux Make Led Used For Luminaire. ( Fitting Required Lm-79 & Lm-80 Certificates)(Note: Below Description Have Shown Ranges Of Wattage Capacity Of Led Fittings.The Engineer Incharge May Select Any Wattage Capacity Between The Ranges Shown.) (A) Tube Light With Integral Driver (D) 22-24 Watts, Surge - 2Kv,Ip-20, 4 Feet Cat-Ll 186. Supplying And Erecting Led Indoor Fittings With Leds Of Wattage 0.2 Watt To 0.5 Watt Assembled On Single Mcpcb, With Housing Used As A Heat Sink Shall Be Made Of Thick Sheet Steel Conforming To Is: 513/Crca/ Aluminium Die Cast Powder Coated And High U.V. & Corrosion Resistance With Diffuser With Company Mark/Name 120 To 300 V,Power Factor More Than 0.9, Thd < 10 %,Cct 3000 K To 6500K, Luminaire Efficacy> 85 Lumens/Watt ,Led Efficiency-110 Lumens/Wattled Driver Efficiency > 85 %Cree / Osram / Philips Lumileds / Nichia / Seoul/Bridgelux Make Led Used For Luminaire. ( Fitting Required Lm-79 & Lm-80 Certificates)(Note: Below Description Have Shown Ranges Of Wattage Capacity Of Led Fittings.The Engineer Incharge May Select Any Wattage Capacity Between The Ranges Shown.) (A) Tube Light With Integral Driver (E) 36 Watts, Surge-2 Kv, Ip-20, 4 Feet Cat-Ll 187. Supplying And Erecting Led Street Light / Flood Light Fittings With High Power White Leds Wattage Of 1Watt And Above Assembled On Single Mcpcb, Efficiency More Than 130 Lm/W And Corrosion Free High Pressure Die Cast Aluminum Housing With Smooth Finish Powder Coated And Heat Sink Extruded Aluminium With Diffuser And Polycarbonate Optics/ Lenses With Company Mark/Name Engraved Or Embossed 120 To 300 V,Power Factor More Than 0.95, Thd < 10 %, Cct 3000 K To 5700K,Uniformity Ratio >0.45, Luminaire Efficacy> 100 Lumens/Watt . Led Driver Efficiency > 85 %.Cree / Osram / Philips Lumileds / Nichia / Seoul/ Bridgelux (U.S.A.) Make Led Used For Luminaire. ( Fittings Required Lm-79 & Lm-80 Certificates)(Note: Below Description Have Shown Ranges Of Wattage Capacity Of Led Fittings.The Engineer Incharge May Select Any Wattage Capacity Between The Ranges Shown.) (A) Street Light (Ip-65), Surge Protection -4Kv Integral And 10 Kv Non Integral ,Light Must Have 440Vac Line Supply Protection. It Should Withstand 48 Hours For 440Vac Line Supply. (A) 10 To 12 Watts Cat-Ll 188. Supplying And Erecting Led Street Light / Flood Light Fittings With High Power White Leds Wattage Of 1Watt And Above Assembled On Single Mcpcb, Efficiency More Than 130 Lm/W And Corrosion Free High Pressure Die Cast Aluminum Housing With Smooth Finish Powder Coated And Heat Sink Extruded Aluminium With Diffuser And Polycarbonate Optics/ Lenses With Company Mark/Name Engraved Or Embossed 120 To 300 V,Power Factor More Than 0.95, Thd < 10 %, Cct 3000 K To 5700K,Uniformity Ratio >0.45, Luminaire Efficacy> 100 Lumens/Watt . Led Driver Efficiency > 85 %.Cree / Osram / Philips Lumileds / Nichia / Seoul/ Bridgelux (U.S.A.) Make Led Used For Luminaire. ( Fittings Required Lm-79 & Lm-80 Certificates)(Note: Below Description Have Shown Ranges Of Wattage Capacity Of Led Fittings.The Engineer Incharge May Select Any Wattage Capacity Between The Ranges Shown.) (A) Street Light (Ip-65), Surge Protection -4Kv Integral And 10 Kv Non Integral ,Light Must Have 440Vac Line Supply Protection. It Should Withstand 48 Hours For 440Vac Line Supply. (B) 15 To 24 Watts Cat-Ll 189. Supplying And Erecting Led Street Light / Flood Light Fittings With High Power White Leds Wattage Of 1Watt And Above Assembled On Single Mcpcb, Efficiency More Than 130 Lm/W And Corrosion Free High Pressure Die Cast Aluminum Housing With Smooth Finish Powder Coated And Heat Sink Extruded Aluminium With Diffuser And Polycarbonate Optics/ Lenses With Company Mark/Name Engraved Or Embossed 120 To 300 V,Power Factor More Than 0.95, Thd < 10 %, Cct 3000 K To 5700K,Uniformity Ratio >0.45, Luminaire Efficacy> 100 Lumens/Watt . Led Driver Efficiency > 85 %.Cree / Osram / Philips Lumileds / Nichia / Seoul/ Bridgelux (U.S.A.) Make Led Used For Luminaire. ( Fittings Required Lm-79 & Lm-80 Certificates)(Note: Below Description Have Shown Ranges Of Wattage Capacity Of Led Fittings.The Engineer Incharge May Select Any Wattage Capacity Between The Ranges Shown.) (A) Street Light (Ip-65), Surge Protection -4Kv Integral And 10 Kv Non Integral ,Light Must Have 440Vac Line Supply Protection. It Should Withstand 48 Hours For 440Vac Line Supply. (C) Above 24 To 36 Watts Cat-Ll 190. Supplying And Erecting Led Street Light / Flood Light Fittings With High Power White Leds Wattage Of 1Watt And Above Assembled On Single Mcpcb, Efficiency More Than 130 Lm/W And Corrosion Free High Pressure Die Cast Aluminum Housing With Smooth Finish Powder Coated And Heat Sink Extruded Aluminium With Diffuser And Polycarbonate Optics/ Lenses With Company Mark/Name Engraved Or Embossed 120 To 300 V,Power Factor More Than 0.95, Thd < 10 %, Cct 3000 K To 5700K,Uniformity Ratio >0.45, Luminaire Efficacy> 100 Lumens/Watt . Led Driver Efficiency > 85 %.Cree / Osram / Philips Lumileds / Nichia / Seoul/ Bridgelux (U.S.A.) Make Led Used For Luminaire. ( Fittings Required Lm-79 & Lm-80 Certificates)(Note: Below Description Have Shown Ranges Of Wattage Capacity Of Led Fittings.The Engineer Incharge May Select Any Wattage Capacity Between The Ranges Shown.) (A) Street Light (Ip-65), Surge Protection -4Kv Integral And 10 Kv Non Integral ,Light Must Have 440Vac Line Supply Protection. It Should Withstand 48 Hours For 440Vac Line Supply. (D) Above 36 To 48 Watts Cat-Ll 191. Supplying And Erecting Led Street Light / Flood Light Fittings With High Power White Leds Wattage Of 1Watt And Above Assembled On Single Mcpcb, Efficiency More Than 130 Lm/W And Corrosion Free High Pressure Die Cast Aluminum Housing With Smooth Finish Powder Coated And Heat Sink Extruded Aluminium With Diffuser And Polycarbonate Optics/ Lenses With Company Mark/Name Engraved Or Embossed 120 To 300 V,Power Factor More Than 0.95, Thd < 10 %, Cct 3000 K To 5700K,Uniformity Ratio >0.45, Luminaire Efficacy> 100 Lumens/Watt . Led Driver Efficiency > 85 %.Cree / Osram / Philips Lumileds / Nichia / Seoul/ Bridgelux (U.S.A.) Make Led Used For Luminaire. ( Fittings Required Lm-79 & Lm-80 Certificates)(Note: Below Description Have Shown Ranges Of Wattage Capacity Of Led Fittings.The Engineer Incharge May Select Any Wattage Capacity Between The Ranges Shown.) (B) Flood Light (Ip-65), Surge -4Kv,Light Must Have 440Vac Line Supply Protection. It Should Withstand 48 Hours For 440Vac Line Supply (A) Above 40 To 48 Watts Cat-Ll 192. Supplying And Erecting Led Street Light / Flood Light Fittings With High Power White Leds Wattage Of 1Watt And Above Assembled On Single Mcpcb, Efficiency More Than 130 Lm/W And Corrosion Free High Pressure Die Cast Aluminum Housing With Smooth Finish Powder Coated And Heat Sink Extruded Aluminium With Diffuser And Polycarbonate Optics/ Lenses With Company Mark/Name Engraved Or Embossed 120 To 300 V,Power Factor More Than 0.95, Thd < 10 %, Cct 3000 K To 5700K,Uniformity Ratio >0.45, Luminaire Efficacy> 100 Lumens/Watt . Led Driver Efficiency > 85 %.Cree / Osram / Philips Lumileds / Nichia / Seoul/ Bridgelux (U.S.A.) Make Led Used For Luminaire. ( Fittings Required Lm-79 & Lm-80 Certificates)(Note: Below Description Have Shown Ranges Of Wattage Capacity Of Led Fittings.The Engineer Incharge May Select Any Wattage Capacity Between The Ranges Shown.) (B) Flood Light (Ip-65), Surge -4Kv,Light Must Have 440Vac Line Supply Protection. It Should Withstand 48 Hours For 440Vac Line Supply (B) Above 48 To 60 Watts Cat-Ll 193. Providing And Erecting Approved Make Double Pole Plastic Switch And Fuse 250V., 30A Confirming To Is Erected On Polished Wooden Block As Directed. 194. Providing Approved Make Double Pole Cast Iron Clad Switch & Rewirable Fuse 240 / 250 V Confirming To Is. (A)16A. Cat.Ii 195. Providing Approved Make Double Pole Cast Iron Clad Switch & Rewirable Fuse 240 / 250 V Confirming To Is. (B)32 A. Cat.Ii 196. Providing Approved Make Triple Pole Cast Iron Clad Switch & Rewirable Fuse With Neutral Link 415/500 V Confirming To Is (A)16 A Cat.Ii 197. Providing Approved Make Triple Pole Cast Iron Clad Switch & Rewirable Fuse With Neutral Link 415/500 V Confirming To Is (B) 32 A Cat.Ii 198. Providing Approved Make Triple Pole Metal / Iron Clad Switch & Fuse With Neutral Link 415/500 V Confirming To Is (A)63A Cat.Ii 199. Providing Approved Make Triple Pole Metal / Iron Clad Switch & Fuse With Neutral Link 415/500 V Confirming To Is (B) 100 A Cat.Ii 200. Providing And Erecting Approved Make Panel Mounting Front Fixing Rotary Switch (Cam Switch) With Face Plate With Double Pair Of Contacts With Two Fix And A Moving Contacts, Operated By Means Of Slide, Rest On Disk With Grooves For Sequential Operation Rotated By Switch Handle, Square Shaft And Knob For Two Way With Off (I)Two Pole (A) 16/25A - 240 V 201. Providing And Erecting Approved Make Panel Mounting Front Fixing Rotary Switch (Cam Switch) With Face Plate With Double Pair Of Contacts With Two Fix And A Moving Contacts, Operated By Means Of Slide, Rest On Disk With Grooves For Sequential Operation Rotated By Switch Handle, Square Shaft And Knob For Two Way With Off (I)Two Pole (B) 32A - 240V 202. Providing And Erecting Approved Make Panel Mounting Front Fixing Rotary Switch (Cam Switch) With Face Plate With Double Pair Of Contacts With Two Fix And A Moving Contacts, Operated By Means Of Slide, Rest On Disk With Grooves For Sequential Operation Rotated By Switch Handle, Square Shaft And Knob For Two Way With Off (Ii) Four Pole (A) 16/25A - 440V 203. Providing And Erecting Approved Make Panel Mounting Front Fixing Rotary Switch (Cam Switch) With Face Plate With Double Pair Of Contacts With Two Fix And A Moving Contacts, Operated By Means Of Slide, Rest On Disk With Grooves For Sequential Operation Rotated By Switch Handle, Square Shaft And Knob For Two Way With Off (Ii) Four Pole (B) 32A- 440V 204. Providing And Erecting Approved Make Panel Mounting Front Fixing Rotary Switch (Cam Switch) With Face Plate With Double Pair Of Contacts With Two Fix And A Moving Contacts, Operated By Means Of Slide, Rest On Disk With Grooves For Sequential Operation Rotated By Switch Handle, Square Shaft And Knob For Two Way With Off (Ii) Four Pole (C) 40A - 440V 205. Providing And Erecting Approved Make Panel Mounting Front Fixing Rotary Switch (Cam Switch) With Face Plate With Double Pair Of Contacts With Two Fix And A Moving Contacts, Operated By Means Of Slide, Rest On Disk With Grooves For Sequential Operation Rotated By Switch Handle, Square Shaft And Knob For Two Way With Off (Ii) Four Pole (D) 63A- 440V 206. Providing And Erecting Following Additional Parts For Panel Mounting Mccbs (A)Extended Operating Rotary Handle With Pad Lock With Three Position Trip,Off,On Suitable For 25A To 250 A Panel Mounting Cat-Iii 207. Providing And Erecting Following Additional Parts For Panel Mounting Mccbs (B)Extended Operating Rotary Handle With Pad Lock With Three Position Trip,Off,On Suitable For 400A To 630 A Panel Mounting Cat-Iii 208. Supply Of Approved Make Iron Clad Or Metal Clad Four Pole Change Over Switch 415V. Confirming To Is Of Following Capacity (A) 16A Cat. Ii 209. Supply Of Approved Make Iron Clad Or Metal Clad Four Pole Change Over Switch 415V. Confirming To Is Of Following Capacity (B) 32A Cat. Ii 210. Supplying & Erecting Approved Make Four Pole 415V Change Over Switch Interior For Panel Mounting With Operating Mechanism A.C.23 Duty Confirming To Is For (A)32-40A Cat-Ll 211. Supplying & Erecting Approved Make Four Pole 415V Change Over Switch Interior For Panel Mounting With Operating Mechanism A.C.23 Duty Confirming To Is For (B)63 A Cat-Ll 212. Providing And Erecting Miniature Circuit Breaker Single Pole 6A To 25A Suitable To Operate On 240 V A.C. System And Having Breaking Capacity 10 Ka To Be Erected In Existing Box. Confirming To Is 8828/1996 With Isi Mark Cat.Ii 213. Providing & Erecting 240 V Mcb Double Pole Switch For Motor & Inductive Load (C Curve) Having 10 Ka Breaking Capacity & Confirms To Is : 8828 In Existing Box Having Following Capacity (A) 6 To 32 Amp.Cat.Ii 214. Providing & Erecting 240 V Mcb Double Pole Switch For Motor & Inductive Load (C Curve) Having 10 Ka Breaking Capacity & Confirms To Is : 8828 In Existing Box Having Following Capacity (B) 40 Amp. Cat.Ii 215. Providing & Erecting 240 V Mcb Double Pole Switch For Lighting Load (B Curve) Having 10 Ka Breaking Capacity & Confirms To Is : 8828 In Existing Box Having Following Capacity (A) 6 To 32 Amp. Cat.Ii 216. Providing & Erecting 240 V Mcb Double Pole Switch For Lighting Load (B Curve) Having 10 Ka Breaking Capacity & Confirms To Is : 8828 In Existing Box Having Following Capacity (B) 40 Amp. Cat.Ii 217. Providing & Erecting 415V Mcb Four Pole Switch For Lighting Load (B Curve) Having 10Ka Breaking Capacity & Confirms To Is :8828 In Existing Box Having Following Capacity (A) 6 To 32 Amp.Cat.Ii 218. Providing & Erecting 415V Mcb Four Pole Switch For Lighting Load (B Curve) Having 10Ka Breaking Capacity & Confirms To Is :8828 In Existing Box Having Following Capacity (B)40 Amp.Cat.Ii 219. Providing And Erecting Three Pole Miniature Isolator A.C. 22 Duty Confirms To Is 13947-3 In Existing Box. (A) For 40 Amp. Cat.Ii 220. Providing And Erecting Three Pole Miniature Isolator A.C. 22 Duty Confirms To Is 13947-3 In Existing Box. (B) For 63 Amp. Cat.Ii 221. Providing And Erecting Three Pole Miniature Isolator A.C. 22 Duty Confirms To Is 13947-3 In Existing Box. (C) For 100 Amp. Cat.Ii 222. Providing And Erecting Two Way Centre Off Four Pole Mcb Change Over Switch (Is 13947-3 / Iec 60947-3) In Existing Box. (A) For 25 Amp. Cat.Ii 223. Providing And Erecting Two Way Centre Off Four Pole Mcb Change Over Switch (Is 13947-3 / Iec 60947-3) In Existing Box. (B) For 40 Amp. Cat.Ii 224. Providing And Erecting Sheet Steel Powder Coated Mcb Distribution Board - Flush / Surface Mounted Fitted With Busbar, Neutral Link, Earth Bar And Din Rail, Conforms To Is 8623-1 & 3, Iec 61439-1 & 3 Without Mcb To House Appropriate Nos. Of Mcbs.(The Dbs Should Be Used Of Same Company Of Mcb To Be Used) Suitable For (B) Sheet Steel Double Door (Ip-43) (I)4 Way 225. Providing And Erecting Sheet Steel Powder Coated Mcb Distribution Board - Flush / Surface Mounted Fitted With Busbar, Neutral Link, Earth Bar And Din Rail, Conforms To Is 8623-1 & 3, Iec 61439-1 & 3 Without Mcb To House Appropriate Nos. Of Mcbs.(The Dbs Should Be Used Of Same Company Of Mcb To Be Used) Suitable For (B) Sheet Steel Double Door (Ip-43) (Ii)6 Way 226. Providing And Erecting Sheet Steel Powder Coated Mcb Distribution Board - Flush / Surface Mounted Fitted With Busbar, Neutral Link, Earth Bar And Din Rail, Conforms To Is 8623-1 & 3, Iec 61439-1 & 3 Without Mcb To House Appropriate Nos. Of Mcbs.(The Dbs Should Be Used Of Same Company Of Mcb To Be Used) Suitable For (B) Sheet Steel Double Door (Ip-43) (Iii)8 Way 227. Providing And Erecting Sheet Steel Powder Coated Mcb Distribution Board - Flush / Surface Mounted Fitted With Busbar, Neutral Link, Earth Bar And Din Rail, Conforms To Is 8623-1 & 3, Iec 61439-1 & 3 Without Mcb To House Appropriate Nos. Of Mcbs.(The Dbs Should Be Used Of Same Company Of Mcb To Be Used) Suitable For (B) Sheet Steel Double Door (Ip-43) (Iv)12 Way 228. Providing And Erecting Sheet Steel Powder Coated Mcb Distribution Board - Flush / Surface Mounted Fitted With Busbar, Neutral Link, Earth Bar And Din Rail, Conforms To Is 8623-1 & 3, Iec 61439-1 & 3 Without Mcb To House Appropriate Nos. Of Mcbs.(The Dbs Should Be Used Of Same Company Of Mcb To Be Used) Suitable For (B) Sheet Steel Double Door (Ip-43) (V) 16 Way 229. Providing And Erecting Approved Make Elcbs / Rccbs Conforming To Is: 12640 And Having Sensitivity Of 30 Ma And Short Circuit Withstand Capacity Of 10 Ka And Suitable For Operation On Single Phase 240 V,50Hz. Having Characteristic Of Quick Action & Tripping With All Advance Feature & Do Not Incorporate Any Electronic Component. For Following Max. Rating Erected As Directed (I) 25 Amps.Dp Cat. Ii 230. Providing And Erecting Approved Make Elcbs / Rccbs Conforming To Is: 12640 And Having Sensitivity Of 30 Ma And Short Circuit Withstand Capacity Of 10 Ka And Suitable For Operation On Single Phase 240 V,50Hz. Having Characteristic Of Quick Action & Tripping With All Advance Feature & Do Not Incorporate Any Electronic Component. For Following Max. Rating Erected As Directed (Ii) 40Amps. Dp Cat. Ii 231. Providing And Erecting Approved Make Elcbs / Rccbs Conforming To Is: 12640 And Having Sensitivity Of 30 Ma And Short Circuit Withstand Capacity Of 10 Ka And Suitable For Operation On Single Phase 240 V,50Hz. Having Characteristic Of Quick Action & Tripping With All Advance Feature & Do Not Incorporate Any Electronic Component. For Following Max. Rating Erected As Directed (Iii) 63 Amps. Dp Cat. Ii 232. Providing And Erecting Approved Make Elcbs / Rccbs Conforming To Is: 12640 And Having Sensitivity Of 30 Ma And Short Circuit Withstand Capacity Of 10 Ka And Suitable For Operation On 3 Phase And Neutral 415V,50Hz. Having Characteristic Of Quick Action & Tripping With All Advance Feature & Do Not Incorporate Any Electronic Component For Following Max. Rating Erected As Directed. (I) 25 Amps.Fp Cat. Ii 233. Providing And Erecting Approved Make Elcbs / Rccbs Conforming To Is: 12640 And Having Sensitivity Of 30 Ma And Short Circuit Withstand Capacity Of 10 Ka And Suitable For Operation On 3 Phase And Neutral 415V,50Hz. Having Characteristic Of Quick Action & Tripping With All Advance Feature & Do Not Incorporate Any Electronic Component For Following Max. Rating Erected As Directed. (Ii) 40Amps. Fp Cat. Ii 234. Providing And Erecting Approved Make Elcbs / Rccbs Conforming To Is: 12640 And Having Sensitivity Of 30 Ma And Short Circuit Withstand Capacity Of 10 Ka And Suitable For Operation On 3 Phase And Neutral 415V,50Hz. Having Characteristic Of Quick Action & Tripping With All Advance Feature & Do Not Incorporate Any Electronic Component For Following Max. Rating Erected As Directed. (Iii) 63 Amps. Fp Cat. Ii 235. Supplying & Erecting Xlpe(Is:7098) (I)-88 Isi Unarmoured Aluminium Cable 1.1 Kv.Grade To Be Erected As Directed Of Following Size. (A) 2 Core 2.5 Sq. Mm 236. Supplying & Erecting Xlpe(Is:7098) (I)-88 Isi Unarmoured Aluminium Cable 1.1 Kv.Grade To Be Erected As Directed Of Following Size. (B) 2 Core 4 Sq. Mm 237. Supplying & Erecting Xlpe(Is:7098) (I)-88 Isi Unarmoured Aluminium Cable 1.1 Kv.Grade To Be Erected As Directed Of Following Size. (C) 2 Core 6 Sq. Mm 238. Supplying & Erecting Xlpe(Is:7098) (I)-88 Isi Unarmoured Aluminium Cable 1.1 Kv.Grade To Be Erected As Directed Of Following Size. (D) 2 Core 10 Sq. Mm 239. Supplying & Erecting Xlpe(Is:7098) (I)-88 Isi Unarmoured Aluminium Cable 1.1 Kv.Grade To Be Erected As Directed Of Following Size. (A)4 Core 2.5 Sq. Mm 240. Supplying & Erecting Xlpe(Is:7098) (I)-88 Isi Unarmoured Aluminium Cable 1.1 Kv.Grade To Be Erected As Directed Of Following Size. (B)4 Core 4 Sq. Mm 241. Supplying & Erecting Xlpe(Is:7098) (I)-88 Isi Unarmoured Aluminium Cable 1.1 Kv.Grade To Be Erected As Directed Of Following Size. (C)4 Core 6 Sq. Mm 242. Supplying & Erecting Xlpe(Is:7098) (I)-88 Isi Unarmoured Aluminium Cable 1.1 Kv.Grade To Be Erected As Directed Of Following Size. (D)4 Core 10 Sq. Mm 243. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (A) 2 Core 2.5 Sq. Mm 244. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (B) 2 Core 4 Sq.Mm 245. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. ( C) 2 Core 6 Sq. Mm 246. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (D) 2 Core 10 Sq. Mm 247. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (E) 3 Core 2.5 Sq. Mm 248. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (F) 3 Core 4 Sq. Mm 249. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (G) 3 Core 6 Sq. Mm 250. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (H) 3 Core 10 Sq. Mm 251. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (I) 3 Core 16 Sq. Mm 252. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (J) 4 Core 2.5 Sq. Mm 253. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (K) 4 Core 4 Sq. Mm 254. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (L) 4 Core 6 Sq. Mm 255. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (M) 4 Core 10 Sq. Mm 256. Supplying & Erecting Xlpe(Is:7098)(I)-88 Isi Unarmoured Copper Cable 1.1 Kv Grade To Be Erected As Directed Of Following Size. (N) 4 Core 16 Sq. Mm 257. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables. (A) 3 Core 2.5 Sq. Mm 258. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables. (B) 3 Core 4 Sq. Mm 259. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables. (C) 3 Core 6 Sq. Mm 260. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables. (D) 3 Core 10 Sq. Mm 261. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables. (E) 3 Core 16 Sq. Mm 262. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables. (F) 3 Core 25 Sq. Mm 263. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables. (G) 3 Core 35 Sq. Mm 264. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables. (H) 3 Core 50 Sq. Mm 265. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables. (I) 3 Core 70 Sq. Mm 266. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables. (J) 3 Core 95 Sq. Mm 267. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables. (K) 3 Core 120 Sq. Mm 268. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (A) 3 1/2 Core 25 Sq. Mm ( 16 Sq. Mm 1/2 Core) 269. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (A-1) 3 1/2 Core 35 Sq. Mm ( 16 Sq. Mm 1/2 Core) 270. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (B) 3 1/2 Core 50 Sq. Mm ( 25 Sq.1/2 Mm Core) 271. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (C) 3 1/2 Core 70 Sq. Mm ( 35 Sq. Mm 1/2 Core) 272. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (D) 3 1/2 Core 95 Sq. Mm ( 50 Sq. Mm 1/2 Core) 273. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (E) 3 1/2 Core 120 Sq. Mm ( 70 Sq. Mm 1/2 Core) 274. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (F) 3 1/2 Core 150 Sq. Mm ( 70 Sq. Mm 1/2 Core) 275. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (G) 3 1/2 Core 185 Sq. Mm ( 95 Sq. Mm 1/2 Core 276. Providing And Erecting Xlpe (Is:7098)(I)-88 Isi Armoured Cable Multistrand / Solid Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (A) 4 Core 4 Sq. Mm 277. Providing And Erecting Xlpe (Is:7098)(I)-88 Isi Armoured Cable Multistrand / Solid Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (B) 4 Core 6 Sq. Mm 278. Providing And Erecting Xlpe (Is:7098)(I)-88 Isi Armoured Cable Multistrand / Solid Aluminium Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (C) 4 Core 10 Sq. Mm 279. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Copper Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (A) 2 Core 2.5 Sq. Mm 280. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Copper Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (A-1) 2 Core 4 Sq. Mm 281. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Copper Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (B) 2 Core 6 Sq. Mm 282. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand Copper Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe Of Following Size Of Cables (C) 2 Core 10 Sq. Mm 283. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand / Solid Copper Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe At Road Crossing Or Floor Of Following Size Of Cables. (A) 4 Core 2.5 Sq. Mm 284. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand / Solid Copper Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe At Road Crossing Or Floor Of Following Size Of Cables. (A-1) 4 Core 4 Sq. Mm 285. Providing And Erecting Xlpe(Is:7098)(I)-88 Isi Armoured Cable Multistrand / Solid Copper Conductor For 1.1 Kv. To Be Laid On Wall With Necessary Clamps Or In Existing Trench / Pipe At Road Crossing Or Floor Of Following Size Of Cables. (B) 4 Core 6 Sq. Mm 286. Providing And Erecting Approved Make Ceiling Fan With Double Ball Bearing Isi Mark With Condenser A.C. 23Ov.50 C/S.1200 Mm. Sweep Complete, Canopy Erected On Existing Hook Or Clamp With Earthing. [Make Shall Be Approved By Engineer In Charge] 287. Providing & Erecting Approved Make Ceiling Fan With Double Ball Bearing Isi Mark With Condenser A.C.230V 50C/S. 1400 Mm. Sweep Complete, Canopy Erected On Existing Hook Or Clamp With Earthing [ Make Shall Be Approved By Engineer In Charge] 288. Providing & Erecting Approved Make Ceiling Fan With Double Ball Bearing Isi Mark With Condenser 230 Volt A.C.50 Hz 1200 Mm Sweep Complete Having 3 Blades Aluminium Body And Blade Sets Having Ornamental Design Shanks , Canopy Erected With Earthing. [ Make Shall Be Approved By Engineer In Charge] 289. Providing & Erecting Approved Make Ceiling Fan With Double Ball Bearing Isi Mark With Condenser 230 Volt A.C.50 Hz. 1200 Mm Sweep Complete Having 4 Blades Aluminium Body And Blade Sets Having Ornamental Design Shanks, Canopy Erected With Earthing [ Make Shall Be Approved By Engineer In Charge] 290. Providing & Erecting Approved Make Ceiling Fan With Double Ball Bearing With Condenser 230 Volt A.C.50 Hz. 900 Mm Sweep Complete Having 3 Aluminium Blades, Canopy Erected Complete. [ Make Shall Be Approved By Engineer In Charge] 291. Supply, Installation, Testing And Commissioning Of Suitable Sweep, Bee 5 Star Rated, Ceiling Fan With Brush Less Direct Current (Bldc) Permanent Ferrite Magnet Motor, Class Of Insulation: B, Rust Free 3 Nos.Aluminium Blades, 2 Nos. Canopies, Shackle Kit With Earthing Provision, 22 Gauge Copper Winding, Power Factor Not < 0.9, Service Value (Cmm/W) Minimum 6.85, Air Delivery Minimum 215 Cmm, 350 Rpm,230V (Tolerance As Per Is : 374-2019), Thd < 10%, Remote Or Electronic Regulator Unit For Speed Control And All Remaining Accessories Including Safety Pin, Nut Bolts, Washers, Temperature Rise = 75 Degree C (Max.), Suitable For 140 To 285 Voltage And Rectifier Circuit With Surge, Over Current And Overload Protection , 50 Hz, Single Phase Ac Supply, Earthing Etc. Complete As Required.[ Make Shall Be Approved By Engineer In Charge] A)900 Mm Sweep (A)900Mmsweep (36) 292. Supply, Installation, Testing And Commissioning Of Suitable Sweep, Bee 5 Star Rated, Ceiling Fan With Brush Less Direct Current (Bldc) Permanent Ferrite Magnet Motor, Class Of Insulation: B, Rust Free 3 Nos.Aluminium Blades, 2 Nos. Canopies, Shackle Kit With Earthing Provision, 22 Gauge Copper Winding, Power Factor Not < 0.9, Service Value (Cmm/W) Minimum 6.85, Air Delivery Minimum 215 Cmm, 350 Rpm,230V (Tolerance As Per Is : 374-2019), Thd < 10%, Remote Or Electronic Regulator Unit For Speed Control And All Remaining Accessories Including Safety Pin, Nut Bolts, Washers, Temperature Rise = 75 Degree C (Max.), Suitable For 140 To 285 Voltage And Rectifier Circuit With Surge, Over Current And Overload Protection , 50 Hz, Single Phase Ac Supply, Earthing Etc. Complete As Required.[ Make Shall Be Approved By Engineer In Charge] A)900 Mm Sweep (A) 1200 Mm Sweep (48) 293. Supply, Installation, Testing And Commissioning Of Suitable Sweep, Bee 5 Star Rated, Ceiling Fan With Brush Less Direct Current (Bldc) Permanent Ferrite Magnet Motor, Class Of Insulation: B, Rust Free 3 Nos.Aluminium Blades, 2 Nos. Canopies, Shackle Kit With Earthing Provision, 22 Gauge Copper Winding, Power Factor Not < 0.9, Service Value (Cmm/W) Minimum 6.85, Air Delivery Minimum 215 Cmm, 350 Rpm,230V (Tolerance As Per Is : 374-2019), Thd < 10%, Remote Or Electronic Regulator Unit For Speed Control And All Remaining Accessories Including Safety Pin, Nut Bolts, Washers, Temperature Rise = 75 Degree C (Max.), Suitable For 140 To 285 Voltage And Rectifier Circuit With Surge, Over Current And Overload Protection , 50 Hz, Single Phase Ac Supply, Earthing Etc. Complete As Required.[ Make Shall Be Approved By Engineer In Charge] A)900 Mm Sweep (B) 1400 Mm Sweep (56) 294. Supplying & Erecting Single Phase Approved Make Industrial Exhaust Fan Suitable For Medium Duty Ring Mounted Low Noise Operation Suitable For Medium Duty Having Following Dia Size And Maximum Speed In Rpm [A] 305 Mm Dia 900 Rpm Cat.Ii 295. Supplying & Erecting Single Phase Approved Make Industrial Exhaust Fan Suitable For Medium Duty Ring Mounted Low Noise Operation Suitable For Medium Duty Having Following Dia Size And Maximum Speed In Rpm [B] 380 Mm Dia 900 Rpm Cat.Ii 296. Supplying & Erecting Single Phase Approved Make Industrial Exhaust Fan Suitable For Medium Duty Ring Mounted Low Noise Operation Suitable For Medium Duty Having Following Dia Size And Maximum Speed In Rpm [C] 380 Mm Dia 1400 Rpm Cat.Ii 297. Supplying & Erecting Single Phase Approved Make Industrial Exhaust Fan Suitable For Medium Duty Ring Mounted Low Noise Operation Suitable For Medium Duty Having Following Dia Size And Maximum Speed In Rpm[D] 450 Mm Dia 900 Rpm Cat.Ii 298. Supplying & Erecting Single Phase Approved Make Industrial Exhaust Fan Suitable For Medium Duty Ring Mounted Low Noise Operation Suitable For Medium Duty Having Following Dia Size And Maximum Speed In Rpm [E] 450 Mm Dia 1400 Rpm Cat.Ii 299. Supplying And Erecting Approved Make Bracket Fan Of 230 Volt, A.C. 50 Cy/S., 400/450 Mm Sweep Complete Erected On Wall Or With Lead Cores And Connections Complete. Cat.Ii 300. Supplying And Erecting Approved Make Window Type Air-Conditioning Machine Comprising Of Hermetically Sealed Rotary Compressor, Condensing & Evaporating Unit, Fan/Blower Motor, Thermostat, Relay, Remote Hand Sets Etc Suitable For (A) For 3 Star Rated Ac Machine (A) 1 Ton Capacity 301. Supplying And Erecting Approved Make Window Type Air-Conditioning Machine Comprising Of Hermetically Sealed Rotary Compressor, Condensing & Evaporating Unit, Fan/Blower Motor, Thermostat, Relay, Remote Hand Sets Etc Suitable For (A) For 3 Star Rated Ac Machine (B) 1.5 Ton Capacity 302. Installation Charges For Window Type Air-Conditioning Machine By Making Modification To The Window, If Necessary By Providing Wooden Frame Made Of Solid Wood Of Good Quality Polished For Proper Support Of The Unit Blocking The Side Opening If Any, Around The Unit, But Within The Window Frame By Asbestos Cement Sheet Or Hard Wood From Inside And Outside Placing The Unit Inside The Frame And Starting The Unit Complete With Necessary Painting. 303. Installation Charges For Wt Ac In Existing Window Opening With Minor Civil Work Covering Of Opening. 304. Providing And Erecting Approved Make Split Air-Conditioning Unit Consisting Of Copper Condensing Unit With Fan Motor, Hermetically Sealed Rotary Compressor With Accessories Etc. Duly Connected Separately Erected Evaporating Unit And Blower Motor With Its Accessories By Means Of Extra Supplied Proper Insulated Copper Tubing,Drain Pvc Pipes Suitable For ( Cost Includes Powder Coated Stand, Eco Friendly Green Gas Charging, 15A Plug Top & Remote Control) With Necessary Core Cutting. For 3 Star Rating Of Current Year [A] For 1 Ton Capacity 305. Extra Charges For The Refrigerant Piping, Cabling & Drain Piping Beyond Standard Length.For Ductable A.C. Machine 18 Gauge Hard Drawn Copper Pipe Including Necessary Fittings I.E. Elbows, Couplings, Reducers Etc. Without Insulation For Liquid Line.. [A] For 5.5 Tr -5/8 Outdoor Copper Pipe 306. Extra Charges For The Refrigerant Piping, Cabling & Drain Piping Beyond Standard Length.For Ductable A.C. Machine 18 Gauge Hard Drawn Copper Pipe Including Necessary Fittings I.E. Elbows, Couplings, Reducers Etc. Without Insulation For Liquid Line.. [B] For 8.5 Tr - 7/8 Outdoor Copper Pipe 307. Extra Charges For The Refrigerant Piping, Cabling & Drain Piping Beyond Standard Length.For Ductable A.C. Machine 18 Gauge Hard Drawn Copper Pipe Including Necessary Fittings I.E. Elbows, Couplings, Reducers Etc. Without Insulation For Liquid Line.. [C] For 11.Tr - 1.1/8 Outdoor Copper Pipe 308. Replacing Fan Motor Capacitor 6 Mfd By New For A.C.Machine 309. Replacing Unserviceable Thermostat Switch By New Denfoss Or Approved Make Thermostat Switch Having Temp. Range 15 To 30 C. For A.C.Machine. 310. Replacing Starting Capacitor Of 80 To 120 Mfd For 2.5 H.P. Compressor Motor For A.C.Machine. 311. Replacing Unserviceable Starting Capacitor Of 100 To 120 Mfd For 2.5 H.P. Compressor Motor For A.C.Machine. 312. Replacing Unserviceable Running Capacitor Of 36 Mfd For 2.5 H.P. Compressor Motor For A.C.Machine. 313. Replacing The Overlode Protector For Compressor Motor Winding If Temp. Exceeds 240 F With A Time Lag Of 10 Sec. Suitable For 1.5 Ton A.C.Machine 314. Replacing Compressor Starting Relay By New On Having Pick-Up Voltage Suitable For 1.5 Ton A.C.Machine. 315. Replacing Copper Capillary Tube Of 0.064€

Key Value

Document Fees
INR 900 /-
EMD
INR 15000.0 /-
Tender Value
Refer document

BOQ Items

S.NOTenderItemIDItem NoItem DescriptionUnit
1 . 11Point wiring for Light / Fan/ Bell/ Primary Point with 2-1.5 sq. mm & earth wire of 1.5 sq. mm (green) both are of ISI marked 1.1 kv grade FRLS PVC insulated multi strand copper wires upto max length of 10 mt, in below type of pipe erected with 6A Tissino Type ISI marked flush type switch / bell push and accessories erected on Metal / PVC/Wooden Box covered with 3 mm thick PC(Polycarbonate) /Acrylic/Laminated sheet. with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling completePt
2 . 22Point wiring for Light / Fan/ Bell/ Primary Point with 2-1.5 sq. mm & earth wire of 1.5 sq. mm (green) both are of ISI marked 1.1 kv grade FRLS PVC insulated multi strand copper wires upto max length of 10 mt, in below type of pipe erected with 6A Tissino Type ISI marked flush type switch / bell push and accessories erected on Metal / PVC/Wooden Box covered with 3 mm thick PC(Polycarbonate) /Acrylic/Laminated sheet. with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (b) with 16 swg(1.6 mm thick) HGS metal conduit pipe and accessories painted black erected flushed on wall/ceiling completePt.
3 . 33Point wiring for Light / Fan/ Bell/ Primary Point with 2-1.5 sq. mm & earth wire of 1.5 sq. mm (green) both are of ISI marked 1.1 kv grade FRLS PVC insulated multi strand copper wires upto max length of 10 mt, in below type of pipe erected with 6A Tissino Type ISI marked flush type switch / bell push and accessories erected on Metal / PVC/Wooden Box covered with 3 mm thick PC(Polycarbonate) /Acrylic/Laminated sheet. with necessary Lamp holder/ceiling rose / H.D.Connector as directed. ( c) with oval conduit /PVC casing capping double lock type erected flushed on wall/ceiling completePt.
4 . 44Point wiring for Light / Fan/ Bell/ Primary Point with 2-1.5 sq. mm & earth wire of 1.5 sq. mm (green) both are of ISI marked 1.1 kv grade FRLS PVC insulated multi strand copper wires upto max length of 10 mt, in below type of pipe erected with 6A Tissino Type ISI marked flush type switch / bell push and accessories erected on Metal / PVC/Wooden Box covered with 3 mm thick PC(Polycarbonate) /Acrylic/Laminated sheet. with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (d) partial PVC pipe and drops in oval conduit / PVC casing capping erected flushed on wall/ceiling completePt.
5 . 55Point wiring for Light / Fan/ Bell/ Primary Point with 2-1.5 sq. mm & earth wire of 1.5 sq. mm (green) both are of ISI marked 1.1 kv grade FRLS PVC insulated multi strand copper wires upto max length of 10 mt, in below type of pipe erected with 6A Tissino Type ISI marked flush type switch / bell push and accessories erected on Metal / PVC/Wooden Box covered with 3 mm thick PC(Polycarbonate) /Acrylic/Laminated sheet. with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (e) in existing pipe erected flushed on wall/ceiling completePt
6 . 66Point wiring for Light / Fan/ Bell/ Primary Point with 2-1.5 sq. mm & earth wire of 1.5 sq. mm (green) both are of ISI marked 1.1 kv grade FRLS PVC insulated multi strand copper wires upto max length of 10 mt, in below type of pipe erected with 6A Tissino Type ISI marked flush type switch / bell push and accessories erected on Metal / PVC/Wooden Box covered with 3 mm thick PC(Polycarbonate) /Acrylic/Laminated sheet. with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling completePt
7 . 77Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [A] For 6 amp plug and 6 amp switch with 2-1.5 sq. mm Cu. Mains from near by switchboard/db board upto 6 mt. (a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling completePt.
8 . 88Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [A] For 6 amp plug and 6 amp switch with 2-1.5 sq. mm Cu. Mains from near by switchboard/db board upto 6 mt. (b) with 16 swg(1.6 mm thick) HGS metal conduit pipe and accessories painted black erected flushed on wall/ceiling completePt.
9 . 99Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [A] For 6 amp plug and 6 amp switch with 2-1.5 sq. mm Cu. Mains from near by switchboard/db board upto 6 mt. ( c) with oval conduit /PVC casing capping double lock type erected flushed on wall/ceiling completePt.
10 . 1010Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [A] For 6 amp plug and 6 amp switch with 2-1.5 sq. mm Cu. Mains from near by switchboard/db board upto 6 mt. (d) partial PVC pipe and drops in oval conduit / PVC casing capping erected flushed on wall/ceiling completePt.
11 . 1111Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [A] For 6 amp plug and 6 amp switch with 2-1.5 sq. mm Cu. Mains from near by switchboard/db board upto 6 mt. (e) in existing pipe erected flushed on wall/ceiling completePt.
12 . 1212Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [A] For 6 amp plug and 6 amp switch with 2-1.5 sq. mm Cu. Mains from near by switchboard/db board upto 6 mt. (f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling completePt.
13 . 1313Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [B] 6/16A Plug and 16 amp switch with 2-2.5 sq. mm Cu. Mains from mcb d b boards. (a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling completePt.
14 . 1414Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [B] 6/16A Plug and 16 amp switch with 2-2.5 sq. mm Cu. Mains from mcb d b boards. (b) with 16 swg(1.6 mm thick) HGS metal conduit pipe and accessories painted black erected flushed on wall/ceiling completePt.
15 . 1515Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [B] 6/16A Plug and 16 amp switch with 2-2.5 sq. mm Cu. Mains from mcb d b boards. ( c) with oval conduit /PVC casing capping double lock type erected flushed on wall/ceiling completePt.
16 . 1616Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [B] 6/16A Plug and 16 amp switch with 2-2.5 sq. mm Cu. Mains from mcb d b boards. (d) partial PVC pipe and drops in oval conduit / PVC casing capping erected flushed on wall/ceiling completePt.
17 . 1717Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [B] 6/16A Plug and 16 amp switch with 2-2.5 sq. mm Cu. Mains from mcb d b boards. (e) in existing pipe erected flushed on wall/ceiling completePt.
18 . 1818Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [B] 6/16A Plug and 16 amp switch with 2-2.5 sq. mm Cu. Mains from mcb d b boards. (f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling completePt.
19 . 1919Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [C] 6/16A Plug and 16 A switch with 2-4 sq.mm Cu. Mains with 2.5 sq.mm ( green) earthing wire (a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling completePt.
20 . 2020Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [C] 6/16A Plug and 16 A switch with 2-4 sq.mm Cu. Mains with 2.5 sq.mm ( green) earthing wire (b) with 16 swg(1.6 mm thick) HGS metal conduit pipe and accessories painted black erected flushed on wall/ceiling completePt.
21 . 2121Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [C] 6/16A Plug and 16 A switch with 2-4 sq.mm Cu. Mains with 2.5 sq.mm ( green) earthing wire ( c) with oval conduit /PVC casing capping double lock type erected flushed on wall/ceiling completePt.
22 . 2222Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [C] 6/16A Plug and 16 A switch with 2-4 sq.mm Cu. Mains with 2.5 sq.mm ( green) earthing wire (d) partial PVC pipe and drops in oval conduit / PVC casing capping erected flushed on wall/ceiling completePt.
23 . 2323Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [C] 6/16A Plug and 16 A switch with 2-4 sq.mm Cu. Mains with 2.5 sq.mm ( green) earthing wire (e) in existing pipe erected flushed on wall/ceiling completePt.
24 . 2424Point wiring for independent PLUG with following size mains earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires upto 10 mt length, in following below of pipe erected complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with earth continuity connection erected on Metal / PVC/Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic/Laminated sheet. [C] 6/16A Plug and 16 A switch with 2-4 sq.mm Cu. Mains with 2.5 sq.mm ( green) earthing wire (f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling completePt.
25 . 2525Point wiring for on board looped PLUG with tissino type single pole ISI marked Switch and Socket erected with necessary connections erected on wooden /Metal/ PVC Box covered with 3 mm thick PC(Polycarbonate) /Acrylic sheet for open / concealed wiring for following size. [A] For 6 Amp.Pt.
26 . 2626Point wiring for on board looped PLUG with tissino type single pole ISI marked Switch and Socket erected with necessary connections erected on wooden /Metal/ PVC Box covered with 3 mm thick PC(Polycarbonate) /Acrylic sheet for open / concealed wiring for following size. [B] For 16 Amp.Pt.
27 . 2727Point wiring for Two Way Controlled Light Point with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in following type of pipe to be erected concealed in / flushed on wall / ceiling complete with 6A Tissino Type ISI marked accessories with earth continuity erected on Metal/PVC//Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic sheet. with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling completePt.
28 . 2828Point wiring for Two Way Controlled Light Point with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in following type of pipe to be erected concealed in / flushed on wall / ceiling complete with 6A Tissino Type ISI marked accessories with earth continuity erected on Metal/PVC//Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic sheet. with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (b) with 16 swg(1.6 mm thick) HGS metal conduit pipe and accessories painted black erected flushed on wall/ceiling completePt.
29 . 2929Point wiring for Two Way Controlled Light Point with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in following type of pipe to be erected concealed in / flushed on wall / ceiling complete with 6A Tissino Type ISI marked accessories with earth continuity erected on Metal/PVC//Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic sheet. with necessary Lamp holder/ceiling rose / H.D.Connector as directed. ( c) with oval conduit /PVC casing capping double lock type erected flushed on wall/ceiling completePt.
30 . 3030Point wiring for Two Way Controlled Light Point with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in following type of pipe to be erected concealed in / flushed on wall / ceiling complete with 6A Tissino Type ISI marked accessories with earth continuity erected on Metal/PVC//Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic sheet. with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (d) partial PVC pipe and drops in oval conduit / PVC casing capping erected flushed on wall/ceiling completePt.
31 . 3131Point wiring for Two Way Controlled Light Point with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in following type of pipe to be erected concealed in / flushed on wall / ceiling complete with 6A Tissino Type ISI marked accessories with earth continuity erected on Metal/PVC//Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic sheet. with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (e) in existing pipe erected flushed on wall/ceiling completePt.
32 . 3232Point wiring for Two Way Controlled Light Point with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in following type of pipe to be erected concealed in / flushed on wall / ceiling complete with 6A Tissino Type ISI marked accessories with earth continuity erected on Metal/PVC//Wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic sheet. with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling completePt.
33 . 3333Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length , in below type of pipe erected with 6A Modular type switch / bell push & accessories and earth continuity of following type, erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected, with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling complete Cat. IIPt.
34 . 3434Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length , in below type of pipe erected with 6A Modular type switch / bell push & accessories and earth continuity of following type, erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected, with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (b) with 16 swg HGS metal conduit pipe and accessories painted black erected flushed on wall/ceiling complete Cat. IIPt.
35 . 3535Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length , in below type of pipe erected with 6A Modular type switch / bell push & accessories and earth continuity of following type, erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected, with necessary Lamp holder/ceiling rose / H.D.Connector as directed. ( c) with oval conduit /PVC casing capping double lock type erected flushed on wall/ceiling complete Cat. IIPt.
36 . 3636Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length , in below type of pipe erected with 6A Modular type switch / bell push & accessories and earth continuity of following type, erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected, with necessary Lamp holder/ceiling rose / H.D.Connector as directed. (d) partial PVC pipe and drops in oval conduit / PVC casing capping erected flushed on wall/ceiling complete Cat. IIPt.
37 . 3737Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length , in below type of pipe erected with 6A Modular type switch / bell push & accessories and earth continuity of following type, erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected, with necessary Lamp holder/ceiling rose / H.D.Connector as directed.(e) in existing pipe erected flushed on wall/ceiling complete Cat. IIPt.
38 . 3838Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length , in below type of pipe erected with 6A Modular type switch / bell push & accessories and earth continuity of following type, erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected, with necessary Lamp holder/ceiling rose / H.D.Connector as directed.(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete Cat. IIPt.
39 . 3939Point wiring for FAN with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of .ISI marked 1.1 KV Grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected with 6A Modular type switch and hum free EME four or more step type electronic fan regulator with separately mounted and accessories with earth continuity of following type erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected. with necessary ceiling rose / H.D.Connector as directed. (a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling complete Cat. IIPt.
40 . 4040Point wiring for FAN with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of .ISI marked 1.1 KV Grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected with 6A Modular type switch and hum free EME four or more step type electronic fan regulator with separately mounted and accessories with earth continuity of following type erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected. with necessary ceiling rose / H.D.Connector as directed. (b) with 16 swg HGS metal conduit pipe and accessories painted black erected flushed on wall/ceiling complete Cat. IIPt.
41 . 4141Point wiring for FAN with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of .ISI marked 1.1 KV Grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected with 6A Modular type switch and hum free EME four or more step type electronic fan regulator with separately mounted and accessories with earth continuity of following type erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected. with necessary ceiling rose / H.D.Connector as directed. ( c) with oval conduit /PVC casing capping double lock type erected flushed on wall/ceiling complete Cat. IIPt.
42 . 4242Point wiring for FAN with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of .ISI marked 1.1 KV Grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected with 6A Modular type switch and hum free EME four or more step type electronic fan regulator with separately mounted and accessories with earth continuity of following type erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected. with necessary ceiling rose / H.D.Connector as directed. (d) partial PVC pipe and drops in oval conduit / PVC casing capping erected flushed on wall/ceiling complete Cat. IIPt.
43 . 4343Point wiring for FAN with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of .ISI marked 1.1 KV Grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected with 6A Modular type switch and hum free EME four or more step type electronic fan regulator with separately mounted and accessories with earth continuity of following type erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected. with necessary ceiling rose / H.D.Connector as directed. (e) in existing pipe erected flushed on wall/ceiling complete Cat. IIPt.
44 . 4444Point wiring for FAN with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of .ISI marked 1.1 KV Grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected with 6A Modular type switch and hum free EME four or more step type electronic fan regulator with separately mounted and accessories with earth continuity of following type erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe erected. with necessary ceiling rose / H.D.Connector as directed. (f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete Cat. IIPt.
45 . 4545Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories. [I] For 6A Plug and 6 a switch with 2-1.5 sq.mm Cu. Wire from nearby switchboard/mcb db board (a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling complete Cat. IIPt.
46 . 4646Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories. [I] For 6A Plug and 6 a switch with 2-1.5 sq.mm Cu. Wire from nearby switchboard/mcb db board (b) with 16 swg HGS metal conduit pipe and accessories painted black erected flushed on wall/ceiling complete Cat. IIPt.
47 . 4747Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories. [I] For 6A Plug and 6 a switch with 2-1.5 sq.mm Cu. Wire from nearby switchboard/mcb db board ( c) with oval conduit /PVC casing capping double lock type erected flushed on wall/ceiling complete Cat. IIPt.
48 . 4848Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories. [I] For 6A Plug and 6 a switch with 2-1.5 sq.mm Cu. Wire from nearby switchboard/mcb db board (d) partial PVC pipe and drops in oval conduit / PVC casing capping erected flushed on wall/ceiling complete Cat. IIPt.
49 . 4949Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories. [I] For 6A Plug and 6 a switch with 2-1.5 sq.mm Cu. Wire from nearby switchboard/mcb db board (e) in existing pipe erected flushed on wall/ceiling complete Cat. IIPt.
50 . 5050Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories. [I] For 6A Plug and 6 a switch with 2-1.5 sq.mm Cu. Wire from nearby switchboard/mcb db board (f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete Cat. IIPt.
S.NOTenderItemIDItem NoItem DescriptionUnit
1 . 5151Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories. [II] For 16A Plug and 16 amp switch with 2-2.5 sq.mm Cu. Wire from mcb db board. (a) with medium class Rigid PVC pipe and accessories erected flushed on wall/ceiling complete Cat. IIPt.
2 . 5252Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories. [II] For 16A Plug and 16 amp switch with 2-2.5 sq.mm Cu. Wire from mcb db board. (b) with 16 swg HGS metal conduit pipe and accessories painted black erected flushed on wall/ceiling complete Cat. IIPt.
3 . 5353Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories. [II] For 16A Plug and 16 amp switch with 2-2.5 sq.mm Cu. Wire from mcb db board. ( c) with oval conduit /PVC casing capping double lock type erected flushed on wall/ceiling complete Cat. IIPt.
4 . 5454Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories. [II] For 16A Plug and 16 amp switch with 2-2.5 sq.mm Cu. Wire from mcb db board. (d) partial PVC pipe and drops in oval conduit / PVC casing capping erected flushed on wall/ceiling complete Cat. IIPt.
5 . 5555Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories. [II] For 16A Plug and 16 amp switch with 2-2.5 sq.mm Cu. Wire from mcb db board. (e) in existing pipe erected flushed on wall/ceiling complete Cat. IIPt.
6 . 5656Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand copper wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories. [II] For 16A Plug and 16 amp switch with 2-2.5 sq.mm Cu. Wire from mcb db board. (f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete Cat. IIPt.
7 . 5757Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (1) One No. SP 6 Amp. Cat.IIEa.
8 . 5858Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (2) One No 5 pin plug Cat.IIEa.
9 . 5959Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (3) Two Pin/RJ-11 Telephone Socket [A] For One Gang Cat.IIEa.
10 . 6060Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (3) Two Pin/RJ-11 Telephone Socket [B] For Two Gang Cat.IIEa.
11 . 6161Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (4) TV Co-axial Socket outlet Cat.IIEa.
12 . 6262Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (5) Electronic hum Free four or more steps EME Fan regulator Cat.IIEa.
13 . 6363Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (6) Fuse units 10Amp. or 16 Amp. Cat.IIEa.
14 . 6464Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (7) Blank Plate Single Cat.IIEa.
15 . 6565Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (8) Computer RJ-45 socket Cat.IIEa.
16 . 6666Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (9) 16 Amp. SP one way switch Cat.IIEa.
17 . 6767Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (10) 6/16Amp. Universal socket Cat.IIEa.
18 . 6868Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (11) 6 Amps. Bell Push Cat.IIEa.
19 . 6969Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (12) 6Amp. / 16 Amp. Two Way switch Cat.IIEa.
20 . 7070Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (13) 6A/10A/16A/20A/25A/32A Single pole Modular MCB Switch Cat.IIEa.
21 . 7171Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (14) 6A/ 10A/ 16A/ 20A/ 25A/ 32A Double Pole Modular MCB Switch Cat.IIEa.
22 . 7272Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (15) 32 Amps. DP switch with Indicator Cat.IIEa.
23 . 7373Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (16) 32 Amp. DP Main Switch Operating with Energy Key Tag Cat.IIEa.
24 . 7474Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (17-a) For 400W / 450 watt One Module Electronic Dimmer Cat.IIEa.
25 . 7575Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (17-b) For 600 / 650 watt Two module Electronic Dimmer Dimmer Cat.IIEa.
26 . 7676Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (17-c) For 1000 watt two module Electronic Dimmer Cat.IIEa.
27 . 7777Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (18) 13 Amp. International Modular Socket Cat.IIEa.
28 . 7878Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (20) Modular Buzzer Cat.IIEa.
29 . 7979Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. (22) 16/20/25 Amp. Modular Starter for Motor / A.C. Unit Complete Cat.IIEa.
30 . 8080Providing and erecting ISI mark Medium class RIGID PVC PIPES of following size complete to be erected on/in wall or ceiling erected with necessary PVC fittings & Junction boxes fixed with adhesive solution & Clamps with following dia of pipes, in approved manner as directed (a)20 mmMtr.
31 . 8181Providing and erecting ISI mark Medium class RIGID PVC PIPES of following size complete to be erected on/in wall or ceiling erected with necessary PVC fittings & Junction boxes fixed with adhesive solution & Clamps with following dia of pipes, in approved manner as directed (b) 25 mmMtr.
32 . 8282Providing and erecting ISI mark Medium class RIGID PVC PIPES of following size complete to be erected on/in wall or ceiling erected with necessary PVC fittings & Junction boxes fixed with adhesive solution & Clamps with following dia of pipes, in approved manner as directed (c) 32 mmMtr.
33 . 8383Providing & erecting approved make OVAL CONDUIT with necessary fittings fixed with adhesive solution and suitable clamps erected on wall / ceiling of following size. (1) 20 mmMtr.
34 . 8484Providing & erecting approved make OVAL CONDUIT with necessary fittings fixed with adhesive solution and suitable clamps erected on wall / ceiling of following size. (2) 25mmMtr.
35 . 8585Supplying & erecting UPVC Mini trunking (PVC Casing-n-Capping) having double-locking arrangement with grooves, trunking of size not below 12.5 mm in height as per IS with accessories of PVC/Resin polypropylene not below 1.8 mm thick duly sealed in joint & erected on wall / ceiling of following size . (1) 20 mmMtr.
36 . 8686Supplying & erecting UPVC Mini trunking (PVC Casing-n-Capping) having double-locking arrangement with grooves, trunking of size not below 12.5 mm in height as per IS with accessories of PVC/Resin polypropylene not below 1.8 mm thick duly sealed in joint & erected on wall / ceiling of following size . (2) 25 mmMtr.
37 . 8787Supplying & erecting UPVC Mini trunking (PVC Casing-n-Capping) having double-locking arrangement with grooves, trunking of size not below 12.5 mm in height as per IS with accessories of PVC/Resin polypropylene not below 1.8 mm thick duly sealed in joint & erected on wall / ceiling of following size . (3) 32 mmMtr.
38 . 8888Supplying and laying UPVC cable trunking system comprising unplasticised polyvinyl, chloride rigid material with ignition free and flame proof confirming BS with necessary end caps Internal and external bend, flat bends, coupler, tee etc..All necessary accessories and measuring of following sizes (1) 75 mm x 50 mm trunkingMtr.
39 . 8989Supplying and laying UPVC cable trunking system comprising unplasticised polyvinyl, chloride rigid material with ignition free and flame proof confirming BS with necessary end caps Internal and external bend, flat bends, coupler, tee etc..All necessary accessories and measuring of following sizes (2) 100 mm x 50 mm trunkingMtr.
40 . 9090Supply & installation of modular type accessories for U PVC snap-on adaptable trunking/Pop up Box with required items erected with necessary connection. As desired by Engineer In charge i) 6 A SP 1 Way Switch cat-IIIEa.
41 . 9191Supply & installation of modular type accessories for U PVC snap-on adaptable trunking/Pop up Box with required items erected with necessary connection. As desired by Engineer In charge ii) 16A SP 1 Way Switch cat-IIIEa.
42 . 9292Supply & installation of modular type accessories for U PVC snap-on adaptable trunking/Pop up Box with required items erected with necessary connection. As desired by Engineer In charge iii) Bell Push 6 A SP 1 Way cat-IIIEa.
43 . 9393Supply & installation of modular type accessories for U PVC snap-on adaptable trunking/Pop up Box with required items erected with necessary connection. As desired by Engineer In charge iv) 6A universal socket shuttered cat-IIIEa.
44 . 9494Supply & installation of modular type accessories for U PVC snap-on adaptable trunking/Pop up Box with required items erected with necessary connection. As desired by Engineer In charge iv) 6/16 A universal socket shuttered cat-IIIEa.
45 . 9595Supply & installation of modular type accessories for U PVC snap-on adaptable trunking/Pop up Box with required items erected with necessary connection. As desired by Engineer In charge v) RJ-11 Telephone socket cat-IIIEa.
46 . 9696Supply & installation of modular type accessories for U PVC snap-on adaptable trunking/Pop up Box with required items erected with necessary connection. As desired by Engineer In charge vi) Cat-6 LAN Socket cat-IIIEa.
47 . 9797Providing & erecting 16 gauge HGS conduit pipe (as per IS) painted black surface/concealed of following size complete to be erected on/in wall or ceiling with erected with necessary saddles, screws, bends, junction boxes etc. with following (Nominal Bore) dia of pipes, in approved manner as directed (1) 19/20 mmMtr.
48 . 9898Providing & erecting 16 gauge HGS conduit pipe (as per IS) painted black surface/concealed of following size complete to be erected on/in wall or ceiling with erected with necessary saddles, screws, bends, junction boxes etc. with following (Nominal Bore) dia of pipes, in approved manner as directed (2) 25 mmMtr.
49 . 9999Providing & erecting 16 gauge HGS conduit pipe (as per IS) painted black surface/concealed of following size complete to be erected on/in wall or ceiling with erected with necessary saddles, screws, bends, junction boxes etc. with following (Nominal Bore) dia of pipes, in approved manner as directed (3) 32 mmMtr.
50 . 100100Providing & erecting 16 gauge HGS conduit pipe (as per IS) painted black surface/concealed of following size complete to be erected on/in wall or ceiling with erected with necessary saddles, screws, bends, junction boxes etc. with following (Nominal Bore) dia of pipes, in approved manner as directed (4) 38/40 mmMtr.
S.NOTenderItemIDItem NoItem DescriptionUnit
1 . 101101Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (a) 2 wire 1.5 sq. mmMtr.
2 . 102102Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (b) 2 wire 2.5 sq. mmMtr.
3 . 103103Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (c) 3 wire 1.5 sq. mmMtr.
4 . 104104Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (d) 3 wire 2.5 sq. mmMtr.
5 . 105105Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (e) 4 wire 1.5 sq. mmMtr.
6 . 106106Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (f) 4 wire 2.5 sq. mmMtr.
7 . 107107Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (g) 6 wire 2.5 sq. mmMtr.
8 . 108108Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (a) 2 wire 1.5 sq. mmMtr.
9 . 109109Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (b) 2 wire 2.5 sq. mmMtr.
10 . 110110Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (c) 3 wire 1.5 sq. mmMtr.
11 . 111111Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (d) 3 wire 2.5 sq. mmMtr.
12 . 112112Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (e) 4 wire 1.5 sq. mmMtr.
13 . 113113Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (f) 4 wire 2.5 sq. mmMtr.
14 . 114114Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (g) 6 wire 2.5 sq. mmMtr.
15 . 115115Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (D) partial PVC pipe and drops in oval conduit / PVC casing capping (a) 2 wire 1.5 sq. mmMtr.
16 . 116116Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (D) partial PVC pipe and drops in oval conduit / PVC casing capping (b) 2 wire 2.5 sq. mmMtr.
17 . 117117Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (D) partial PVC pipe and drops in oval conduit / PVC casing capping (c) 3 wire 1.5 sq. mmMtr.
18 . 118118Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (D) partial PVC pipe and drops in oval conduit / PVC casing capping (d) 3 wire 2.5 sq. mmMtr.
19 . 119119Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (D) partial PVC pipe and drops in oval conduit / PVC casing capping (e) 4 wire 1.5 sq. mmMtr.
20 . 120120Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (D) partial PVC pipe and drops in oval conduit / PVC casing capping (f) 4 wire 2.5 sq. mmMtr.
21 . 121121Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (D) partial PVC pipe and drops in oval conduit / PVC casing capping (g) 6 wire 2.5 sq. mmMtr.
22 . 122122providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (a) 2 wire 4 sq. mmMtr.
23 . 123123providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (b) 2 wire 6 sq. mmMtr.
24 . 124124providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (c) 2 wire 10 sq. mmMtr.
25 . 125125providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (d) 3 wire 4 sq. mmMtr.
26 . 126126providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (e) 3 wire 6 sq. mmMtr.
27 . 127127providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (f) 3 wire 10 sq. mm(use earth wire of 4 sq.mm )Mtr.
28 . 128128providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (g) 4 wire 4 sq. mmMtr.
29 . 129129providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (h) 4 wire 6 sq. mmMtr.
30 . 130130providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (A) with medium class Rigid PVC pipe and accessories (i) 4 wire 10 sq. mm (use earth wire of 4 sq.mm )Mtr.
31 . 131131providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (a) 2 wire 4 sq. mmMtr.
32 . 132132providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (b) 2 wire 6 sq. mmMtr.
33 . 133133providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (c) 2 wire 10 sq. mmMtr.
34 . 134134providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (d) 3 wire 4 sq. mmMtr.
35 . 135135providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (e) 3 wire 6 sq. mmMtr.
36 . 136136providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (f) 3 wire 10 sq. mm(use earth wire of 4 sq.mm )Mtr.
37 . 137137providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (g) 4 wire 4 sq. mmMtr.
38 . 138138providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (h) 4 wire 6 sq. mmMtr.
39 . 139139providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size (C) with oval conduit /PVC casing capping double lock type (i) 4 wire 10 sq. mm (use earth wire of 4 sq.mm )Mtr.
40 . 140140Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of following size to be erected as directed. a) 0.75 Sq.mm twin twistedMtr.
41 . 141141Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of following size to be erected as directed. b) 1.00 Sq.mm twin twistedMtr.
42 . 142142Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of following size to be erected as directed. c) 1.00 Sq.mm 2 core round/ flat PVC sheathedMtr.
43 . 143143Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of following size to be erected as directed. d) 1.50 Sq.mm 2 core round PVC sheathedMtr.
44 . 144144Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of following size to be erected as directed. e) 1.50 Sq.mm 3 core round PVC sheathedMtr.
45 . 145145Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of following size to be erected as directed. f) 1.50 Sq.mm 4 core round PVC sheathedMtr.
46 . 146146Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of following size to be erected as directed. g) 2.50 Sq.mm 2 core round PVC sheathedMtr.
47 . 147147Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of following size to be erected as directed. h) 2.50 Sq.mm 3 core round PVC sheathedMtr.
48 . 148148Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of following size to be erected as directed. i) 2.50 Sq.mm 4 core round PVC sheathedMtr.
49 . 149149Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of following size to be erected as directed. j) 4.00 Sq.mm 3 core round PVC sheathedMtr.
50 . 150150Supplying and erecting Flexible PVC insulated multi strand multi core 1.1 kv grade ISI marked copper wires of following size to be erected as directed. k) 4.00Sq.mm 4 core round PVC sheathedMtr.
S.NOTenderItemIDItem NoItem DescriptionUnit
1 . 151151Supplying & erecting approved make Telephone Cable electrolytic copper conductor PE insulation twisted in two pairs, & wrapped with FRLS PVC tape & sheathed with FRLS PVC or HFFR outer Jacket suitable for telephone wiring & confirming to C-DOT erected in existing pipe. of following size of conductors & nos.of pairs. With necessary connections. [A] Conductor Size 0.5 mm (a) Unarmoured 1) One PairMtr.
2 . 152152Supplying & erecting approved make Telephone Cable electrolytic copper conductor PE insulation twisted in two pairs, & wrapped with FRLS PVC tape & sheathed with FRLS PVC or HFFR outer Jacket suitable for telephone wiring & confirming to C-DOT erected in existing pipe. of following size of conductors & nos.of pairs. With necessary connections. [A] Conductor Size 0.5 mm (a) Unarmoured 2) Two PairsMtr.
3 . 153153Supplying & erecting approved make Telephone Cable electrolytic copper conductor PE insulation twisted in two pairs, & wrapped with FRLS PVC tape & sheathed with FRLS PVC or HFFR outer Jacket suitable for telephone wiring & confirming to C-DOT erected in existing pipe. of following size of conductors & nos.of pairs. With necessary connections. [A] Conductor Size 0.5 mm (a) Unarmoured 3) Three PairsMtr.
4 . 154154Supplying & erecting approved make Telephone Cable electrolytic copper conductor PE insulation twisted in two pairs, & wrapped with FRLS PVC tape & sheathed with FRLS PVC or HFFR outer Jacket suitable for telephone wiring & confirming to C-DOT erected in existing pipe. of following size of conductors & nos.of pairs. With necessary connections. [A] Conductor Size 0.5 mm (a) Unarmoured 4) Five PairsMtr.
5 . 155155Supplying & erecting approved make Telephone Cable electrolytic copper conductor PE insulation twisted in two pairs, & wrapped with FRLS PVC tape & sheathed with FRLS PVC or HFFR outer Jacket suitable for telephone wiring & confirming to C-DOT erected in existing pipe. of following size of conductors & nos.of pairs. With necessary connections. [A] Conductor Size 0.5 mm (a) Unarmoured 5) Ten PairsMtr.
6 . 156156Supplying & erecting approved make Telephone Cable electrolytic copper conductor PE insulation twisted in two pairs, & wrapped with FRLS PVC tape & sheathed with FRLS PVC or HFFR outer Jacket suitable for telephone wiring & confirming to C-DOT erected in existing pipe. of following size of conductors & nos.of pairs. With necessary connections. [A] Conductor Size 0.5 mm (a) Unarmoured 6) Twenty PairsMtr.
7 . 157157Supplying & erecting approved make LAN cable of following size in existing pipe as per direction [C] CAT - 6Mtr
8 . 158158Providing & erecting Switch board for Computer or electric apparatus consisting of following modular type accessories mounted with PVC / Metallic concealed/open box with single mounting base frame covered with textured/metallic /white front plate,modules erected with necessary connections as directed1 no. 6A/16A universal plug-switch combined.3 nos. 6A Switch3 nos. 6A 5 pin Plug For Modular Type Accessories Cat. IIEa.
9 . 159159Approved make High pressure sodium vapour lamp, Tubular/Elliptical type 70W. 230/240/250V. erected, if required. Cat.IIEa.
10 . 160160Approved make High pressure sodium vapour lamp, Tubular/Elliptical type 150W, 230/240/250V, erected , if required Cat.IIEa.
11 . 161161Approved make CFL Retrofit 5 / 7 / 9 /11 Watt, erected if required Cat.IIEa.
12 . 162162Approved make C.F.L. Retrofit 13/15/18 Watt erected if required Cat.IIEa.
13 . 163163Approved make C.F.L.Retrofit 20 / 23 / 25 / 26 Watt. erected if required Cat.IIEa.
14 . 164164Approved make C.F.L.Retrofit of following size erected if required [A] 35/36 Watt Cat.IIEa.
15 . 165165Approved make C.F.L.Retrofit of following size erected if required [B] 40/45 Watt Cat.IIEa.
16 . 166166Approved make C.F.L.Retrofit of following size erected if required [C] 55/65/85 Watt Cat.IIEa.
17 . 167167Providing and erecting decorative wall bracket fittings complete with LED lamp and rust free fittings components mounted in chrome finish housing with holder ,clear/opaque glass diffuser complete erected with lead wires with minimum 15 wattage capacity as per instruction engineer incharge/architect/authority .cat-IIIEa.
18 . 168168Supplying and erecting approved make of tube fitting with One no T-5 tube 24/ 28 W with Electronic ballast with each tube separately THD less than 10 & built in adaptors, GI / PVC housing & mirror optic reflector, suitable to work on 120V - 300V, A.C. supply with connector and adapter if required. [Make of fitting & tube may be differ& fitting shall be providing with tube] Cat IIEa.
19 . 169169Supplying & erecting energy saving Energy Efficient E+ (1 - 4 ft) 28 watt retrofit tube fitting with one no 28watt T-5 tube complete with E.G.P. wings reflector / clear acrylic guard cover & tube and electronic inbuilt circuit ballast of rating 130 to 325 V A.C. The fittings should be able to fit in any conventional existing T - 8 tube fittings complete erected in an approved manner.Ea.
20 . 170170Outdoor street light fitting side entry with clear acrylic /plastic / polystyrene cover complete with starter, polyester choke copper wound complete erected with 40/36 watt tube holders. with lead wire and connections. (b) with 2 tube 40 watt.120 cms. Cat.IIEa.
21 . 171171Providing and erecting approved make C.F.L out door type street light fitting side entry with clear acrylic / plastic cover electronic ballast high circuit P.F. weather proof design (IP 65) THD less than 10% rust free fitting components mounted in powder coated CRCA / Al. housing with lead wire & with Non Retrofit CFL tube complete. [a] With One CFL tube 9 / 11/ 13 / 18 watt Non Retrofit with ballast & Holder Cat.IIEa.
22 . 172172Providing and erecting approved make C.F.L out door type street light fitting side entry with clear acrylic / plastic cover electronic ballast high circuit P.F. weather proof design (IP 65) THD less than 10% rust free fitting components mounted in powder coated CRCA / Al. housing with lead wire & with Non Retrofit CFL tube complete.[b] With Two CFL tube 9 / 11/ 13 / 18 watt Non Retrofit with ballast & Holder Cat.IIEa.
23 . 173173Providing and erecting approved make C.F.L out door type street light fitting side entry with clear acrylic / plastic cover electronic ballast high circuit P.F. weather proof design (IP 65) THD less than 10% rust free fitting components mounted in powder coated CRCA / Al. housing with lead wire & with Non Retrofit CFL tube complete.[c] With One CFL tube 36 watt Retrofit or Non Retrofit with ballast & Holder Cat.IIEa.
24 . 174174Supply & fixing decorative Hanging light with glass having cylindrical or square shape having length not less than 10" & width not less 3.5" with holder, lead wire as per required length but not more than 1mm & base plate for fixing the fitting with ceiling.[a] suitable for led lamp cat-IIEa.
25 . 175175providing and erecting Approved make street light luminaire with one no suitable for- HPSV / MH lamp complete with control gear and accessories , Single piece Deep drawn Aluminium housing with two compartments duly stove enameled painted side reflector protective acrylic cover, synthetic felt gasket, necessary hardware. The fitting should be suitable for side entry having suitable socket bore for clamping complete erected. (A) With 70 watt SVL. /Metal Halide lamp Cat.IIEa.
26 . 176176providing and erecting Approved make street light luminaire with one no suitable for- HPSV / MH lamp complete with control gear and accessories , Single piece Deep drawn Aluminium housing with two compartments duly stove enameled painted side reflector protective acrylic cover, synthetic felt gasket, necessary hardware. The fitting should be suitable for side entry having suitable socket bore for clamping complete erected. (B) With 150 watt SVL. /Metal Halide lamp Cat.IIEa.
27 . 177177providing and erecting Approved make street light luminaire with one no suitable for- HPSV / MH lamp complete with control gear and accessories , Single piece Deep drawn Aluminium housing with two compartments duly stove enameled painted side reflector protective acrylic cover, synthetic felt gasket, necessary hardware. The fitting should be suitable for side entry having suitable socket bore for clamping complete erected.(C) With 250 watt SVL. /Metal Halide lamp Cat.IIEa.
28 . 178178Supplying & erecting control gear box, weather proof made of Cast aluminium with heavy duty copper polyester choke, condenser, MCB, connector block & earthing terminal complete erected with necessary screws, nuts & bolts clamps suitable for (A) For HPSV/MH Lamp with ignitor For One No. Lamp. (i) 7OW Cat-llEa
29 . 179179Supplying & erecting control gear box, weather proof made of Cast aluminium with heavy duty copper polyester choke, condenser, MCB, connector block & earthing terminal complete erected with necessary screws, nuts & bolts clamps suitable for (A) For HPSV/MH Lamp with ignitor For One No. Lamp. (ii)150 W Cat-llEa
30 . 180180Supplying & erecting control gear box, weather proof made of Cast aluminium with heavy duty copper polyester choke, condenser, MCB, connector block & earthing terminal complete erected with necessary screws, nuts & bolts clamps suitable for (A) For HPSV/MH Lamp with ignitor For One No. Lamp. (iii)250 W Cat-llEa
31 . 181181Supplying & erecting control gear box, weather proof made of Cast aluminium with heavy duty copper polyester choke, condenser, MCB, connector block & earthing terminal complete erected with necessary screws, nuts & bolts clamps suitable for (A) For HPSV/MH Lamp with ignitor For One No. Lamp. (iv)40OW Cat-llEa
32 . 182182Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with housing used as a heat sink shall be made of thick sheet Steel conforming to IS: 513/CRCA/ aluminium die cast powder coated and high U.V. & corrosion resistance with diffuser with company mark/name 120 to 300 V,Power Factor more than 0.9, THD < 10 %,CCT 3000 K to 6500K, Luminaire efficacy> 85 lumens/watt ,LED efficiency-110 lumens/wattLED driver efficiency > 85 %CREE / OSRAM / PHILIPS Lumileds / NICHIA / SEOUL/Bridgelux make LED used for luminaire. ( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) (A) Tube Light with integral driver (a) 5-9 Watts, Surge-2 KV, IP-20,2 feet Cat-llEach
33 . 183183Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with housing used as a heat sink shall be made of thick sheet Steel conforming to IS: 513/CRCA/ aluminium die cast powder coated and high U.V. & corrosion resistance with diffuser with company mark/name 120 to 300 V,Power Factor more than 0.9, THD < 10 %,CCT 3000 K to 6500K, Luminaire efficacy> 85 lumens/watt ,LED efficiency-110 lumens/wattLED driver efficiency > 85 %CREE / OSRAM / PHILIPS Lumileds / NICHIA / SEOUL/Bridgelux make LED used for luminaire. ( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) (A) Tube Light with integral driver (b) 12-14 Watts, Surge-2 KV, IP-20, 4 feet Cat-llEach
34 . 184184Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with housing used as a heat sink shall be made of thick sheet Steel conforming to IS: 513/CRCA/ aluminium die cast powder coated and high U.V. & corrosion resistance with diffuser with company mark/name 120 to 300 V,Power Factor more than 0.9, THD < 10 %,CCT 3000 K to 6500K, Luminaire efficacy> 85 lumens/watt ,LED efficiency-110 lumens/wattLED driver efficiency > 85 %CREE / OSRAM / PHILIPS Lumileds / NICHIA / SEOUL/Bridgelux make LED used for luminaire. ( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) (A) Tube Light with integral driver (c) 16-20 Watts, Surge - 2KV,IP-20, 4 feet Cat-llEach
35 . 185185Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with housing used as a heat sink shall be made of thick sheet Steel conforming to IS: 513/CRCA/ aluminium die cast powder coated and high U.V. & corrosion resistance with diffuser with company mark/name 120 to 300 V,Power Factor more than 0.9, THD < 10 %,CCT 3000 K to 6500K, Luminaire efficacy> 85 lumens/watt ,LED efficiency-110 lumens/wattLED driver efficiency > 85 %CREE / OSRAM / PHILIPS Lumileds / NICHIA / SEOUL/Bridgelux make LED used for luminaire. ( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) (A) Tube Light with integral driver (d) 22-24 Watts, Surge - 2KV,IP-20, 4 feet Cat-llEach
36 . 186186Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with housing used as a heat sink shall be made of thick sheet Steel conforming to IS: 513/CRCA/ aluminium die cast powder coated and high U.V. & corrosion resistance with diffuser with company mark/name 120 to 300 V,Power Factor more than 0.9, THD < 10 %,CCT 3000 K to 6500K, Luminaire efficacy> 85 lumens/watt ,LED efficiency-110 lumens/wattLED driver efficiency > 85 %CREE / OSRAM / PHILIPS Lumileds / NICHIA / SEOUL/Bridgelux make LED used for luminaire. ( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) (A) Tube Light with integral driver (e) 36 Watts, Surge-2 KV, IP-20, 4 feet Cat-llEach
37 . 187187Supplying and erecting LED street light / Flood light fittings with High power White LEDs wattage of 1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/ lenses with company mark/name engraved or embossed 120 to 300 V,Power Factor more than 0.95, THD < 10 %, CCT 3000 K to 5700K,Uniformity ratio >0.45, Luminaire efficacy> 100 lumens/watt . LED driver efficiency > 85 %.CREE / OSRAM / PHILIPS Lumileds / NICHIA / SEOUL/ BridgeLux (U.S.A.) make LED used for luminaire. ( fittings required LM-79 & LM-80 certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) (A) Street Light (IP-65), Surge protection -4KV integral and 10 kv non integral ,Light must have 440VAC line supply protection. It should withstand 48 hours for 440VAC line supply. (a) 10 to 12 Watts Cat-llEach
38 . 188188Supplying and erecting LED street light / Flood light fittings with High power White LEDs wattage of 1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/ lenses with company mark/name engraved or embossed 120 to 300 V,Power Factor more than 0.95, THD < 10 %, CCT 3000 K to 5700K,Uniformity ratio >0.45, Luminaire efficacy> 100 lumens/watt . LED driver efficiency > 85 %.CREE / OSRAM / PHILIPS Lumileds / NICHIA / SEOUL/ BridgeLux (U.S.A.) make LED used for luminaire. ( fittings required LM-79 & LM-80 certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) (A) Street Light (IP-65), Surge protection -4KV integral and 10 kv non integral ,Light must have 440VAC line supply protection. It should withstand 48 hours for 440VAC line supply. (b) 15 to 24 Watts Cat-llEach
39 . 189189Supplying and erecting LED street light / Flood light fittings with High power White LEDs wattage of 1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/ lenses with company mark/name engraved or embossed 120 to 300 V,Power Factor more than 0.95, THD < 10 %, CCT 3000 K to 5700K,Uniformity ratio >0.45, Luminaire efficacy> 100 lumens/watt . LED driver efficiency > 85 %.CREE / OSRAM / PHILIPS Lumileds / NICHIA / SEOUL/ BridgeLux (U.S.A.) make LED used for luminaire. ( fittings required LM-79 & LM-80 certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) (A) Street Light (IP-65), Surge protection -4KV integral and 10 kv non integral ,Light must have 440VAC line supply protection. It should withstand 48 hours for 440VAC line supply. (c) above 24 to 36 watts Cat-llEach
40 . 190190Supplying and erecting LED street light / Flood light fittings with High power White LEDs wattage of 1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/ lenses with company mark/name engraved or embossed 120 to 300 V,Power Factor more than 0.95, THD < 10 %, CCT 3000 K to 5700K,Uniformity ratio >0.45, Luminaire efficacy> 100 lumens/watt . LED driver efficiency > 85 %.CREE / OSRAM / PHILIPS Lumileds / NICHIA / SEOUL/ BridgeLux (U.S.A.) make LED used for luminaire. ( fittings required LM-79 & LM-80 certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) (A) Street Light (IP-65), Surge protection -4KV integral and 10 kv non integral ,Light must have 440VAC line supply protection. It should withstand 48 hours for 440VAC line supply. (d) above 36 to 48 watts Cat-llEach
41 . 191191Supplying and erecting LED street light / Flood light fittings with High power White LEDs wattage of 1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/ lenses with company mark/name engraved or embossed 120 to 300 V,Power Factor more than 0.95, THD < 10 %, CCT 3000 K to 5700K,Uniformity ratio >0.45, Luminaire efficacy> 100 lumens/watt . LED driver efficiency > 85 %.CREE / OSRAM / PHILIPS Lumileds / NICHIA / SEOUL/ BridgeLux (U.S.A.) make LED used for luminaire. ( fittings required LM-79 & LM-80 certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) (B) Flood Light (IP-65), Surge -4KV,Light must have 440VAC line supply protection. It should withstand 48 hours for 440VAC line supply (a) above 40 to 48 watts Cat-llEach
42 . 192192Supplying and erecting LED street light / Flood light fittings with High power White LEDs wattage of 1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/ lenses with company mark/name engraved or embossed 120 to 300 V,Power Factor more than 0.95, THD < 10 %, CCT 3000 K to 5700K,Uniformity ratio >0.45, Luminaire efficacy> 100 lumens/watt . LED driver efficiency > 85 %.CREE / OSRAM / PHILIPS Lumileds / NICHIA / SEOUL/ BridgeLux (U.S.A.) make LED used for luminaire. ( fittings required LM-79 & LM-80 certificates)(NOTE: Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) (B) Flood Light (IP-65), Surge -4KV,Light must have 440VAC line supply protection. It should withstand 48 hours for 440VAC line supply (b) above 48 to 60 Watts Cat-llEach
43 . 193193providing and erecting Approved make Double Pole Plastic Switch and fuse 250V., 30A confirming to IS erected on Polished wooden block as directed.Ea.
44 . 194194Providing Approved make Double Pole Cast Iron Clad Switch & rewirable Fuse 240 / 250 V confirming to IS. (a)16A. Cat.IIEa.
45 . 195195Providing Approved make Double Pole Cast Iron Clad Switch & rewirable Fuse 240 / 250 V confirming to IS. (b)32 A. Cat.IIEa.
46 . 196196Providing Approved make Triple Pole Cast Iron Clad Switch & rewirable Fuse with neutral link 415/500 V confirming to IS (a)16 A Cat.IIEa.
47 . 197197Providing Approved make Triple Pole Cast Iron Clad Switch & rewirable Fuse with neutral link 415/500 V confirming to IS (b) 32 A Cat.IIEa.
48 . 198198Providing Approved make Triple Pole Metal / Iron Clad Switch & Fuse with neutral link 415/500 V confirming to IS (a)63A Cat.IIEa.
49 . 199199Providing Approved make Triple Pole Metal / Iron Clad Switch & Fuse with neutral link 415/500 V confirming to IS (b) 100 A Cat.IIEa.
50 . 200200Providing and erecting Approved make panel mounting front fixing rotary switch (CAM Switch) with face plate with double pair of contacts with two fix and a moving contacts, operated by means of slide, rest on disk with grooves for sequential operation rotated by switch handle, square shaft and knob for Two way with off (i)Two pole (a) 16/25A - 240 VEa.
S.NOTenderItemIDItem NoItem DescriptionUnit
1 . 201201Providing and erecting Approved make panel mounting front fixing rotary switch (CAM Switch) with face plate with double pair of contacts with two fix and a moving contacts, operated by means of slide, rest on disk with grooves for sequential operation rotated by switch handle, square shaft and knob for Two way with off (i)Two pole (b) 32A - 240VEa.
2 . 202202Providing and erecting Approved make panel mounting front fixing rotary switch (CAM Switch) with face plate with double pair of contacts with two fix and a moving contacts, operated by means of slide, rest on disk with grooves for sequential operation rotated by switch handle, square shaft and knob for Two way with off (ii) Four pole (a) 16/25A - 440VEa.
3 . 203203Providing and erecting Approved make panel mounting front fixing rotary switch (CAM Switch) with face plate with double pair of contacts with two fix and a moving contacts, operated by means of slide, rest on disk with grooves for sequential operation rotated by switch handle, square shaft and knob for Two way with off (ii) Four pole (b) 32A- 440VEa.
4 . 204204Providing and erecting Approved make panel mounting front fixing rotary switch (CAM Switch) with face plate with double pair of contacts with two fix and a moving contacts, operated by means of slide, rest on disk with grooves for sequential operation rotated by switch handle, square shaft and knob for Two way with off (ii) Four pole (c) 40A - 440VEa.
5 . 205205Providing and erecting Approved make panel mounting front fixing rotary switch (CAM Switch) with face plate with double pair of contacts with two fix and a moving contacts, operated by means of slide, rest on disk with grooves for sequential operation rotated by switch handle, square shaft and knob for Two way with off (ii) Four pole (d) 63A- 440VEa.
6 . 206206providing and erecting following additional parts for panel mounting MCCBs (A)Extended operating rotary handle with pad lock with three position trip,off,on suitable for 25A to 250 A panel mounting cat-IIIea.
7 . 207207providing and erecting following additional parts for panel mounting MCCBs (B)Extended operating rotary handle with pad lock with three position trip,off,on suitable for 400A to 630 A panel mounting cat-IIIEa.
8 . 208208supply of Approved make Iron Clad or metal clad four pole change over switch 415V. confirming to IS of following capacity (A) 16A Cat. IIEa.
9 . 209209supply of Approved make Iron Clad or metal clad four pole change over switch 415V. confirming to IS of following capacity (B) 32A Cat. IIEa.
10 . 210210Supplying & erecting approved make Four Pole 415V change over switch interior for panel mounting with operating mechanism A.C.23 duty confirming to IS for (A)32-40A Cat-llEa.
11 . 211211Supplying & erecting approved make Four Pole 415V change over switch interior for panel mounting with operating mechanism A.C.23 duty confirming to IS for (B)63 A Cat-llEa.
12 . 212212providing and erecting Miniature circuit breaker single pole 6A to 25A suitable to operate on 240 V A.C. system and having breaking capacity 10 KA to be erected in existing box. confirming to IS 8828/1996 with ISI Mark Cat.IIEa.
13 . 213213Providing & erecting 240 V MCB double pole switch for motor & inductive load (C Curve) having 10 KA breaking capacity & confirms to IS : 8828 in existing box having following capacity (A) 6 to 32 Amp.Cat.IIEa.
14 . 214214Providing & erecting 240 V MCB double pole switch for motor & inductive load (C Curve) having 10 KA breaking capacity & confirms to IS : 8828 in existing box having following capacity (B) 40 Amp. Cat.IIEa.
15 . 215215Providing & erecting 240 V MCB double pole switch for lighting Load (B Curve) having 10 KA breaking capacity & confirms to IS : 8828 in existing box having following capacity (A) 6 to 32 Amp. Cat.IIEa.
16 . 216216Providing & erecting 240 V MCB double pole switch for lighting Load (B Curve) having 10 KA breaking capacity & confirms to IS : 8828 in existing box having following capacity (B) 40 Amp. Cat.IIEa.
17 . 217217Providing & erecting 415V MCB Four Pole Switch for Lighting Load (B curve) having 10KA breaking capacity & confirms to IS :8828 in existing box having following capacity (a) 6 to 32 Amp.Cat.IIEa.
18 . 218218Providing & erecting 415V MCB Four Pole Switch for Lighting Load (B curve) having 10KA breaking capacity & confirms to IS :8828 in existing box having following capacity (b)40 Amp.Cat.IIEa.
19 . 219219Providing and erecting Three pole Miniature isolator A.C. 22 duty confirms to IS 13947-3 in existing box. (a) for 40 Amp. Cat.IIEa.
20 . 220220Providing and erecting Three pole Miniature isolator A.C. 22 duty confirms to IS 13947-3 in existing box. (b) for 63 Amp. Cat.IIEa.
21 . 221221Providing and erecting Three pole Miniature isolator A.C. 22 duty confirms to IS 13947-3 in existing box. (c) for 100 Amp. Cat.IIEa.
22 . 222222Providing and erecting Two way Centre off Four pole MCB Change Over Switch (IS 13947-3 / IEC 60947-3) in existing box. (a) for 25 Amp. Cat.IIEa.
23 . 223223Providing and erecting Two way Centre off Four pole MCB Change Over Switch (IS 13947-3 / IEC 60947-3) in existing box. (b) for 40 Amp. Cat.IIEa.
24 . 224224Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for (b) sheet steel double door (IP-43) (i)4 wayEa.
25 . 225225Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for (b) sheet steel double door (IP-43) (ii)6 wayEa.
26 . 226226Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for (b) sheet steel double door (IP-43) (iii)8 wayEa.
27 . 227227Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for (b) sheet steel double door (IP-43) (iv)12 wayEa.
28 . 228228Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for (b) sheet steel double door (IP-43) (v) 16 wayEa.
29 . 229229providing and erecting Approved make ELCBs / RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short Circuit withstand capacity of 10 KA and suitable for operation on single phase 240 V,50Hz. having characteristic of quick action & tripping with all advance feature & do not incorporate any electronic component. for following Max. rating erected as directed (i) 25 Amps.DP Cat. IIEa.
30 . 230230providing and erecting Approved make ELCBs / RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short Circuit withstand capacity of 10 KA and suitable for operation on single phase 240 V,50Hz. having characteristic of quick action & tripping with all advance feature & do not incorporate any electronic component. for following Max. rating erected as directed (ii) 40Amps. DP Cat. IIEa.
31 . 231231providing and erecting Approved make ELCBs / RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short Circuit withstand capacity of 10 KA and suitable for operation on single phase 240 V,50Hz. having characteristic of quick action & tripping with all advance feature & do not incorporate any electronic component. for following Max. rating erected as directed (iii) 63 Amps. DP Cat. IIEa.
32 . 232232providing and erecting Approved make ELCBs / RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short Circuit withstand capacity of 10 KA and suitable for operation on 3 phase and neutral 415V,50Hz. having characteristic of quick action & tripping with all advance feature & do not incorporate any electronic component for following Max. rating erected as directed. (i) 25 Amps.FP Cat. IIEa.
33 . 233233providing and erecting Approved make ELCBs / RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short Circuit withstand capacity of 10 KA and suitable for operation on 3 phase and neutral 415V,50Hz. having characteristic of quick action & tripping with all advance feature & do not incorporate any electronic component for following Max. rating erected as directed. (ii) 40Amps. FP Cat. IIEa.
34 . 234234providing and erecting Approved make ELCBs / RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short Circuit withstand capacity of 10 KA and suitable for operation on 3 phase and neutral 415V,50Hz. having characteristic of quick action & tripping with all advance feature & do not incorporate any electronic component for following Max. rating erected as directed. (iii) 63 Amps. FP Cat. IIEa.
35 . 235235Supplying & erecting XLPE(IS:7098) (I)-88 ISI unarmoured Aluminium cable 1.1 KV.grade to be erected as directed of following size. (a) 2 core 2.5 Sq. mmMtr.
36 . 236236Supplying & erecting XLPE(IS:7098) (I)-88 ISI unarmoured Aluminium cable 1.1 KV.grade to be erected as directed of following size. (b) 2 core 4 Sq. mmMtr.
37 . 237237Supplying & erecting XLPE(IS:7098) (I)-88 ISI unarmoured Aluminium cable 1.1 KV.grade to be erected as directed of following size. (c) 2 core 6 Sq. mmMtr.
38 . 238238Supplying & erecting XLPE(IS:7098) (I)-88 ISI unarmoured Aluminium cable 1.1 KV.grade to be erected as directed of following size. (d) 2 core 10 Sq. mmMtr.
39 . 239239Supplying & erecting XLPE(IS:7098) (I)-88 ISI unarmoured Aluminium cable 1.1 KV.grade to be erected as directed of following size. (a)4 core 2.5 Sq. mmMtr.
40 . 240240Supplying & erecting XLPE(IS:7098) (I)-88 ISI unarmoured Aluminium cable 1.1 KV.grade to be erected as directed of following size. (b)4 core 4 Sq. mmMtr.
41 . 241241Supplying & erecting XLPE(IS:7098) (I)-88 ISI unarmoured Aluminium cable 1.1 KV.grade to be erected as directed of following size. (c)4 core 6 Sq. mmMtr.
42 . 242242Supplying & erecting XLPE(IS:7098) (I)-88 ISI unarmoured Aluminium cable 1.1 KV.grade to be erected as directed of following size. (d)4 core 10 Sq. mmMtr.
43 . 243243Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (A) 2 core 2.5 Sq. mmMtr.
44 . 244244Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (B) 2 core 4 sq.mmMtr.
45 . 245245Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. ( C) 2 core 6 Sq. mmMtr.
46 . 246246Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (D) 2 core 10 Sq. mmMtr.
47 . 247247Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (E) 3 core 2.5 Sq. mmMtr.
48 . 248248Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (F) 3 core 4 Sq. mmMtr.
49 . 249249Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (G) 3 core 6 Sq. mmMtr.
50 . 250250Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (H) 3 core 10 Sq. mmMtr.
S.NOTenderItemIDItem NoItem DescriptionUnit
1 . 251251Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (I) 3 core 16 Sq. mmMtr.
2 . 252252Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (J) 4 core 2.5 Sq. mmMtr.
3 . 253253Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (K) 4 core 4 Sq. mmMtr.
4 . 254254Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (L) 4 core 6 Sq. mmMtr.
5 . 255255Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (M) 4 core 10 Sq. mmMtr.
6 . 256256Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size. (N) 4 core 16 Sq. mmMtr.
7 . 257257Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables. (A) 3 core 2.5 Sq. mmMtr.
8 . 258258Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables. (B) 3 core 4 Sq. mmMtr.
9 . 259259Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables. (C) 3 core 6 Sq. mmMtr.
10 . 260260Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables. (D) 3 core 10 Sq. mmMtr.
11 . 261261Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables. (E) 3 core 16 Sq. mmMtr.
12 . 262262Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables. (F) 3 core 25 Sq. mmMtr.
13 . 263263Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables. (G) 3 core 35 Sq. mmMtr.
14 . 264264Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables. (H) 3 core 50 Sq. mmMtr.
15 . 265265Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables. (I) 3 core 70 Sq. mmMtr.
16 . 266266Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables. (j) 3 core 95 Sq. mmMtr.
17 . 267267Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables. (k) 3 core 120 Sq. mmMtr.
18 . 268268Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (A) 3 1/2 core 25 Sq. mm ( 16 Sq. mm 1/2 core)Mtr.
19 . 269269Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (A-1) 3 1/2 core 35 Sq. mm ( 16 Sq. mm 1/2 core)Mtr.
20 . 270270Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (B) 3 1/2 core 50 Sq. mm ( 25 Sq.1/2 mm core)Mtr.
21 . 271271Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (C) 3 1/2 core 70 Sq. mm ( 35 Sq. mm 1/2 core)Mtr.
22 . 272272Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (D) 3 1/2 core 95 Sq. mm ( 50 Sq. mm 1/2 core)Mtr.
23 . 273273Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (E) 3 1/2 core 120 Sq. mm ( 70 Sq. mm 1/2 core)Mtr.
24 . 274274Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (F) 3 1/2 core 150 Sq. mm ( 70 Sq. mm 1/2 core)Mtr.
25 . 275275Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (G) 3 1/2 core 185 Sq. mm ( 95 Sq. mm 1/2 coreMtr.
26 . 276276Providing and erecting XLPE (IS:7098)(I)-88 ISI armoured cable multistrand / Solid Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (a) 4 core 4 Sq. mmMtr.
27 . 277277Providing and erecting XLPE (IS:7098)(I)-88 ISI armoured cable multistrand / Solid Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (b) 4 core 6 Sq. mmMtr.
28 . 278278Providing and erecting XLPE (IS:7098)(I)-88 ISI armoured cable multistrand / Solid Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (c) 4 core 10 Sq. mmMtr.
29 . 279279Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (a) 2 core 2.5 Sq. mmMtr.
30 . 280280Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (a-1) 2 core 4 Sq. mmMtr.
31 . 281281Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (b) 2 core 6 Sq. mmMtr.
32 . 282282Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables (c) 2 core 10 Sq. mmMtr.
33 . 283283Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand / Solid Copper conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cables. (A) 4 core 2.5 Sq. mmMtr.
34 . 284284Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand / Solid Copper conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cables. (A-1) 4 core 4 Sq. mmMtr.
35 . 285285Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand / Solid Copper conductor for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cables. (B) 4 core 6 Sq. mmMtr.
36 . 286286Providing and erecting Approved make Ceiling fan with double ball bearing ISI mark with condenser A.C. 23OV.50 c/s.1200 mm. sweep complete, canopy erected on existing hook or clamp with earthing. [Make shall be approved by Engineer in charge]Ea.
37 . 287287Providing & erecting Approved make Ceiling Fan with double ball bearing ISI mark with condenser A.C.230V 50c/s. 1400 mm. sweep complete, canopy erected on existing hook or clamp with earthing [ Make shall be approved by Engineer in Charge]Ea.
38 . 288288Providing & erecting Approved make Ceiling Fan with double ball bearing ISI mark with Condenser 230 volt A.C.50 Hz 1200 mm sweep complete having 3 blades aluminium body and blade sets having ornamental design shanks , canopy erected with earthing. [ Make shall be approved by Engineer in Charge]Ea.
39 . 289289Providing & erecting Approved make Ceiling Fan with double ball bearing ISI mark with Condenser 230 volt A.C.50 Hz. 1200 mm sweep complete having 4 blades Aluminium body and blade sets having ornamental design shanks, canopy erected with earthing [ Make shall be approved by Engineer in Charge]Ea.
40 . 290290Providing & erecting Approved make Ceiling Fan with double ball bearing with Condenser 230 volt A.C.50 Hz. 900 mm sweep complete having 3 Aluminium blades, canopy erected complete. [ Make shall be approved by Engineer in Charge]Ea.
41 . 291291Supply, Installation, Testing and Commissioning of suitable sweep, BEE 5 Star rated, Ceiling fan with Brush Less Direct Current (BLDC) permanent ferrite magnet Motor, class of insulation: B, Rust free 3 nos.Aluminium blades, 2 nos. canopies, shackle kit with earthing provision, 22 gauge copper winding, Power factor not < 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM,230v (tolerance as per IS : 374-2019), THD < 10%, remote or electronic regulator unit for Speed Control and all remaining accessories including safety pin, nut bolts, washers, temperature rise = 75 degree C (Max.), suitable for 140 to 285 Voltage and rectifier circuit with surge, over current and overload protection , 50 Hz, Single phase AC Supply, earthing etc. Complete as required.[ Make shall be approved by Engineer in Charge] A)900 mm sweep (A)900mmsweep (36")Ea.
42 . 292292Supply, Installation, Testing and Commissioning of suitable sweep, BEE 5 Star rated, Ceiling fan with Brush Less Direct Current (BLDC) permanent ferrite magnet Motor, class of insulation: B, Rust free 3 nos.Aluminium blades, 2 nos. canopies, shackle kit with earthing provision, 22 gauge copper winding, Power factor not < 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM,230v (tolerance as per IS : 374-2019), THD < 10%, remote or electronic regulator unit for Speed Control and all remaining accessories including safety pin, nut bolts, washers, temperature rise = 75 degree C (Max.), suitable for 140 to 285 Voltage and rectifier circuit with surge, over current and overload protection , 50 Hz, Single phase AC Supply, earthing etc. Complete as required.[ Make shall be approved by Engineer in Charge] A)900 mm sweep (A) 1200 mm Sweep (48")Ea.
43 . 293293Supply, Installation, Testing and Commissioning of suitable sweep, BEE 5 Star rated, Ceiling fan with Brush Less Direct Current (BLDC) permanent ferrite magnet Motor, class of insulation: B, Rust free 3 nos.Aluminium blades, 2 nos. canopies, shackle kit with earthing provision, 22 gauge copper winding, Power factor not < 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM,230v (tolerance as per IS : 374-2019), THD < 10%, remote or electronic regulator unit for Speed Control and all remaining accessories including safety pin, nut bolts, washers, temperature rise = 75 degree C (Max.), suitable for 140 to 285 Voltage and rectifier circuit with surge, over current and overload protection , 50 Hz, Single phase AC Supply, earthing etc. Complete as required.[ Make shall be approved by Engineer in Charge] A)900 mm sweep (B) 1400 mm Sweep (56")Ea.
44 . 294294Supplying & erecting single phase approved make industrial exhaust fan suitable for medium duty ring mounted low noise operation suitable for medium duty having following dia size and maximum speed in RPM [A] 305 mm dia 900 RPM Cat.IIEa.
45 . 295295Supplying & erecting single phase approved make industrial exhaust fan suitable for medium duty ring mounted low noise operation suitable for medium duty having following dia size and maximum speed in RPM [B] 380 mm dia 900 RPM Cat.IIEa.
46 . 296296Supplying & erecting single phase approved make industrial exhaust fan suitable for medium duty ring mounted low noise operation suitable for medium duty having following dia size and maximum speed in RPM [C] 380 mm dia 1400 RPM Cat.IIEa.
47 . 297297Supplying & erecting single phase approved make industrial exhaust fan suitable for medium duty ring mounted low noise operation suitable for medium duty having following dia size and maximum speed in RPM[D] 450 mm dia 900 RPM Cat.IIEa.
48 . 298298Supplying & erecting single phase approved make industrial exhaust fan suitable for medium duty ring mounted low noise operation suitable for medium duty having following dia size and maximum speed in RPM [E] 450 mm dia 1400 RPM Cat.IIEa.
49 . 299299Supplying and erecting approved make Bracket fan of 230 volt, A.C. 50 Cy/s., 400/450 mm sweep complete erected on wall or with lead Cores and connections complete. Cat.IIEa.
50 . 300300Supplying and erecting approved make window type Air-Conditioning machine comprising of hermetically sealed rotary compressor, condensing & evaporating unit, fan/blower motor, thermostat, relay, remote hand sets etc suitable for (A) For 3 star rated AC machine (a) 1 Ton CapacityNos.
S.NOTenderItemIDItem NoItem DescriptionUnit
1 . 301301Supplying and erecting approved make window type Air-Conditioning machine comprising of hermetically sealed rotary compressor, condensing & evaporating unit, fan/blower motor, thermostat, relay, remote hand sets etc suitable for (A) For 3 star rated AC machine (b) 1.5 Ton CapacityNos.
2 . 302302Installation charges for window type air-conditioning machine by making modification to the window, if necessary by providing wooden frame made of solid wood of good quality polished for proper support of the unit blocking the side opening if any, around the unit, but within the window frame by asbestos cement sheet or hard wood from inside and outside placing the unit inside the frame and starting the unit complete with necessary painting.Job
3 . 303303Installation charges for WT AC in existing window opening with minor civil work covering of opening.Nos.
4 . 304304Providing and erecting approved make split air-conditioning unit consisting of copper condensing unit with fan motor, hermetically sealed rotary compressor with accessories etc. duly connected separately erected evaporating unit and blower motor with its accessories by means of extra supplied proper insulated copper tubing,drain PVC pipes suitable for ( cost includes powder coated Stand, Eco Friendly green gas charging, 15A plug top & Remote Control) with necessary core cutting. For 3 Star Rating of current year [a] For 1 Ton CapacityNos.
5 . 305305Extra charges for the refrigerant piping, cabling & drain piping beyond standard length.For ductable A.C. Machine 18 Gauge hard drawn copper pipe including necessary fittings i.e. elbows, couplings, reducers etc. without insulation for liquid line.. [A] For 5.5 TR -5/8" Outdoor Copper PipeRMT
6 . 306306Extra charges for the refrigerant piping, cabling & drain piping beyond standard length.For ductable A.C. Machine 18 Gauge hard drawn copper pipe including necessary fittings i.e. elbows, couplings, reducers etc. without insulation for liquid line.. [B] For 8.5 TR - 7/8" Outdoor Copper PipeRMT
7 . 307307Extra charges for the refrigerant piping, cabling & drain piping beyond standard length.For ductable A.C. Machine 18 Gauge hard drawn copper pipe including necessary fittings i.e. elbows, couplings, reducers etc. without insulation for liquid line.. [C] For 11.TR - 1.1/8" Outdoor Copper PipeRMT
8 . 308308Replacing fan motor capacitor 6 mfd by new for A.C.MachineNo
9 . 309309Replacing unserviceable thermostat switch by new denfoss or approved make thermostat switch having temp. range 15 to 30 C. for A.C.Machine.No
10 . 310310Replacing starting capacitor of 80 to 120 MFD for 2.5 H.P. Compressor motor for A.C.Machine.No
11 . 311311Replacing Unserviceable starting capacitor of 100 to 120 MFD for 2.5 H.P. Compressor motor for A.C.Machine.No
12 . 312312Replacing Unserviceable running capacitor of 36 MFD for 2.5 H.P. Compressor motor for A.C.Machine.No
13 . 313313Replacing the overlode protector for compressor motor winding if temp. Exceeds 240 F with a time lag of 10 sec. suitable for 1.5 Ton A.C.machineNo
14 . 314314Replacing compressor starting relay by new on having pick-up voltage suitable for 1.5 Ton A.C.machine.No
15 . 315315Replacing copper capillary tube of 0.064â€