| 1 | Excavation in trenches n. exc. 1.5 mtr in wide and n. exc. 1.5 mtr in depth for laying of underground cable and getting out in Hard/dense soil complete all as specified and directed. |
| 2 | Excavation in trenches not exc. 1.5 m wide and exc. 1.5m in depth for foundation of poles, stay assembly etc and getting out in hard/ dense soil complete all as specified and directed. |
| 3 | Returning, filling in surplus spoilincluding spreading, leveling, watering and well rammingin layers n. exc. 25 cm thick complete all as specified and directed. |
| 4 | Removing of excavted soil to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed. |
| 5 | M&L for Sand cushioning to under ground cable providing with a layer of Sand 08 cm thick before laying of cable and 15 cm after laying of cable in trenches, hand punning complete all as specified and directed by Engr-in-charge(Note : Punning thickness of 18 cm will be measured for payment purpose) |
| 6 | M&L for Burnt bricks locally available, sub class \"B\",laid flat for protection of under ground cable complete all as specified and directed at site. |
| 7 | Supply, laying , jointing and testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade withstranded aluminum conductor of size 185 sqmm 3.5core, laid in trenches/ducts or fixed to poles/walls or laid under roads/paths/drains/culvertsincluding cable gland of suitable sizesand aluminium lugs for connection, fixed as in repairs complete all as specified and directed. Make: Finolex / KEI Industries Pvt Ltd / Polycab / Gloster / Universal Cables.Note: Excavation, earthwork, sand cushioning, brick protection shall be measured & paid for separately. |
| 8 | All as per Item No 7 above but size 3.5 core 120 sqmm complete all as specified and directed. |
| 9 | All as per Item No 7 above but size 3.5 core 95 sqmm complete all as specified and directed. |
| 10 | All as per Item No 7 above but size 3.5 core 70 sqmm complete all as specified and directed. |
| 11 | All as per Item No 7 above but size 3.5 core 50 sqmm complete all as specified and directed. |
| 12 | All as per Item No 7 above but size 3.5 core 35 sqmm complete all as specified and directed. |
| 13 | All as per Item No 7 above but size 4 core 25 sqmm complete all as specified and directed. |
| 14 | All as per Item No 7 above but size 4 core 16 Sqmm complete all as specified and directed. |
| 15 | All as per Item No 7 above but size 4 core 10 sqmm complete all as specified and directed. |
| 16 | Supplying, installation and errection in true vertical position steel tubular swaged weldedpole, 9.0 metre long,conforming to IS-2713 part-II, type 410 SP-31, complete with cast iron/MS base plate 6mm thick and of size 300x300mm,finial taper, pole cap, bolts, nuts, washers & screws etc., pole made out of ERW Mild steel tubing tubing including holes of required Nos and size for fixing of cross arms, paintingwith one coat of red oxide primer and two coats of aluminium paint on exposed surfacesand two coats of black bituminous paint for portion embedded in concrete, painting three signal red colour bands at lower portion of exposed pole starting from plinth block , each band of 300mm height at 300mm spacing, painting pole No with black paint by stenciled letters/figures of 8cm height, fixed as in repairs complete all as specified and directed.Make : QUALITY STEEL / SURJIT STEEL INDUSTRIES / SOHAN LAL & SONS / ANIL ENGG CORPORATION / ZAIN INDUSTRIES SRINAGAR / ADVANCE TUBE JAMMUNote:Excavation, earth work and PCC in foundation of poles, coping etc shall be measured and paid separately in respected items. |
| 17 | Dismantling of cross arms, bracings, supports, clamps etc of MS fabricated complete with all accessories viz nut, bolts, washer etc. complete all as specified and directed. |
| 18 | M&L for Cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts,bolts,washers, welding , bending cold or hot, drilling holes for bolts,in any shape or sizes as indicated or directed and inclusive of one primer coat and two coats of alluminium paint complete all as specified and directed. |
| 19 | S&F in repair Pin type insulator Porcelain, vitreous white/brown/green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, 100 mm height, 65 mm dia for 1100 volt grade, complete all as specified and directed.Make: PACTIL/BHEL/JAIPURIA |
| 20 | Shackle type porcelain , vitreous white, brown or green insulator including galvanised mild steel straps, wahsers, insulator bolts, wahsers and nuts, asworking pressure 1100 volts height in 100 mm maximum dia 115 mmsection of straps in 31 x 5 mm dia of bolts 14 mm fixed as in repairs complete all as specified and directed.Make: PACTIL/BHEL/JAIPURIA |
| 21 | Stay assembly comprising of MS stay plate of size 30cmx30cmx6mm thick, stay rod with nuts 215cm long, 20mm dia, MS/GI stay bow 40 cm length with 2 Nos GI thimbles, galvanized stay wire standard size 7/4mm, loop insulation size 90mmx140mm clearance of hole 25.5 mm & other accessories all as per SSR Part-1, Plate No.1including necessary MS clamps, excavation earth work & PCC work fixed as in repairs complete all as specified and directed. |
| 22 | Supply and fixing in repair galvonised stay strand, size 7/3.15 mm for connecting stay assembly with MS clamps on poles complete all as specified and directed. |
| 23 | Supply and fixing in repairs loop insulator Porcelain, vitreous white/brown/green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, large size with overall dimensions 90mmx 140mm, clearance of hole 25.5 mm, Complete all as specified and directed. Make: PACTIL/BHEL/JAIPURIA |
| 24 | Cradle hexagonal , rectangular fabricated with GI wire 3.15 / 4 mm dia on existing OH line, fixed as in repairs complete all as specified and directed. |
| 25 | M&L for dismantling of ACSR conductors and removing from the site complete all as specified and directed. |
| 26 | Supply, stringing, streaching and binding with insulator, ACSR conductor of adequate size (Weasel /ferret/Mink) on LT Poles including providing of necessary jumpers, connecting all existing incoming and out going connections, trimming of trees approximately 2 mtr around conductor etc complete all as specified and directed.Make: ICC/NICCO/JAIPURIA/ALIND |
| 27 | M&L for Trimming tree branches coming in proximity to LT over head lines and involved with over head lines where detected , over head lines to be cleared of tree branches atleast 2.5 Mtrs apart from ACSR conductor from all sides complete all as specified and directed.Note: Contactor is supposed to manage long wooden ladder atleast 32 feet height, rope and handsaw machine to clear the lines from tree branches having girth upto 6\" dia at his own arrangement and cost. |
| 28 | Re-streching of loose over head ACSR conductor of any type including GI wire and repair of the broken conductors andaddingnew length( if required) in placeof old and burnt conductor of any size on existing poles with proper sagging including winding with winding wire complete all as specified and directed.Note: Old conductor shall be reused where required for repairing broken length of conductor as directed by Engr-in-charge. Note: Five lines together will bemeasured as one span from pole to pole. |
| 29 | M&L for Painting to steel poles including cross arms, \"V\" brackets, \"D\" clamps, nuts, bolts,complete including painting with five strips of 30cm each black and white paint in alternate strips from the base of pole upto 1.5mtr height complete, spray painting with two coat of synthetic enamel paint of first quality silver paint over a coat of red oxide primer after and including complete removal of old paint by scratching, rubbing complete all as specified and directed. |
| 30 | S&F in repair Earthing complete with galvanized steel plate electrode 600 mm x 600 mm x 6.0 mm thick, burried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron strip 32 x 6 mm size by means of GI bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 40 mm bore (light grade) connected to main switch board or any other electrical equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and includingnecessary excavation and earth work in any type of soil, 20 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 8 mm dia TMT bars @ 15cm c/c both way for cover and MS frame etc., complete all as specified and directed.NOTE: The unit rate includes earth strip and protection pipe upto (maximum 7.5 metre from earth plate) earth point/test point. |
| 31 | S&F in repair Earthing complete with galvanized steel plate electrode 600 mm x 600 mm x 6.0 mm thick, burried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron wire 4 mm dia by means of GI bolts, nuts, check nuts and washers, earth wire protected by galvanized iron pipe 15 mm bore (light grade) connected to main switch board or any other electrical equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and includingnecessary excavation and earth work in any type of soil, 20 mm bore medium grade GI pipe for watering, funnel with wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 8 mm dia TMT bars @ 15cm c/c both way for cover and MS frame etc., complete all as specified and directed.NOTE: The unit rate includes earth wire and protection pipe upto (maximum 7.5 metre from earth plate) earth point/test point. |
| 32 | S&F in repair Single pointed air termination Aluminium rod 12mm dia, 300 mm long complete all as specified and directed. |
| 33 | S&F in repair Test point terminal block made of gun metal or phosphorous bronze of size 75x75 x 25mm drilled and screwed including 3 Nos 8mm dia 25mm long hexagonal head brass screws including box of size 90 x 90 x 90mm made of 1.6mm plain sheet and screwed to GI pipe/ wall for protection of test point complete all as specified and directed. |
| 34 | S&F in repair Tubing \"lightgrade\" galvanised iron with all fittings and fixed to poles, walls etc. with flat iron clamps/bolts/nuts/washers or laid in floors/under roads complete of size 50 mm bore, complete all as specified and directed.Make: Jindal Pipes / TATA / BST / Prakash Surya |
| 35 | S&F in repair Tubing \"lightgrade\" galvanised iron with all fittings and fixed to poles, walls etc. with flat iron clamps/bolts/nuts/washers or laid in floors/under roads complete of size 80 mm bore, complete all as specified and directed.Make: Jindal Pipes / TATA / BST / Prakash Surya |
| 36 | S&F in repair Tubing \"lightgrade\" galvanised iron with all fittings and fixed to poles, walls etc. with flat iron clamps/bolts/nuts/washers or laid in floors/under roads complete of size 40 mm bore,complete all as specified and directed.Make: Jindal Pipes / TATA / BST / Prakash Surya |
| 37 | S&F in repair Aluminium strip 25 x 3.15mm with saddles and fixing screws, insulators rawl plugs etc forconductor for roof and fixed on wall upto test point, complete all as specified and directed. |
| 38 | S&F in repair Galvanized iron strip 32 x 6mm fixed with saddles & fixing screws, PVC dash fastners, insulators fixed from test point to earth on walls or burried in ground / drawn into hume pipe, complete all as specified and directed.NOTE : Excavation & earth work shall be measured and paid for seperately under relevant item of schedule. |
| 39 | M&L for Painting of LT panel including preparation of old surfaces by scrapping old paint completely and applying two coats of super enameled paint over a coat of red oxide primer complete all as specified and directed. |
| 40 | S&F in repair MCCB, 3 pole,63 Amps, 415 voltswith breaking capacity 16 KA Ics=75% Icu, complete all as specified and directed.Make: Legrand/Schneider/ABB/SIEMENS/L&T/C&S |
| 41 | S&F in repair MCCB, 4 pole, 160 Amps, 415 voltswith breaking capacity 25 KAIcs=100% Icu, complete all as specified and directed.Make: Legrand/Schneider/ABB/SIEMENS/L&T/C&S |
| 42 | S&F in repair MCCB, 4 pole, 200 Amps, 415 voltswith breaking capacity 36 KAIcs=100% Icu, complete all as specified and directed.Make: Legrand/Schneider/ABB/SIEMENS/L&T/C&S |
| 43 | S&F in repair MCCB, 4 pole, 250 Amps, 415 voltswith breaking capacity 36 KAIcs=100% Icu, complete all as specified and directed.Make: Legrand/Schneider/ABB/SIEMENS/L&T/C&S |
| 44 | S&F in repair MCCB, 4 pole, 400 Amps, 415 voltswith breaking capacity 36 KAIcs=100% Icu, complete all as specified and directed.Make: Legrand/Schneider/ABB/SIEMENS/L&T/C&S |
| 45 | S&F in repair Aluminiumthimble suitable for LT XLPE cable 185 sqmm size, complete all as specified and directed. |
| 46 | S&F in repair Aluminiumthimble suitable for LT XLPE cable 120 sqmm size, complete all as specified and directed. |
| 47 | S&F in repair Aluminiumthimble suitable for LT XLPE cable 95 sqmm size, complete all as specified and directed. |
| 48 | S&F in repair Aluminiumthimble suitable for LT XLPE cable 70 sqmm size, complete all as specified and directed. |
| 49 | S&F in repair Aluminiumthimble suitable for LT XLPE cable 50 sqmm size, complete all as specified and directed. |
| 50 | S&F in repair Aluminiumthimble suitable for LT XLPE cable 35 sqmm size, complete all as specified and directed. |
| 51 | S&F in repair Aluminiumthimble suitable for LT XLPE cable 25 sqmm size, complete all as specified and directed. |
| 52 | M&L for Plain cement concrete 1:3:6 (nominal mix) type C-2(using 40mm graded crushed stone aggregates) as in foundation, filling and mass concrete complete all as specified and directed. |
| 53 | M&L for Plain cement concrete (1:4:8) Type D-2(using 40mm graded crushed stone aggregates) as in foundation for steel tubular polesincluding necessary form work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed. |
| 54 | M&L for Plain cement concrete (1:2:4) Type B-1 using 20 mm graded crushed stone aggregates, as in coping of steel tubular poles foundation for steel tubular polesincluding necessary form work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed. |
| 55 | S&F in repair Rubber insulating mat of size 2mx1mx12mm thick, ISI marked, complete all as specified and directed. |
| 56 | S&F in repair 1100 Volts grade heavy duty cable PVC insulated aluminum solidconductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm suspension wire, one twin core cable flat or circular, size of aluminum conductor 10 sq mm, complete all as specified and directed.Make : Finolex / KEI Industries Pvt Ltd / Polycab / Gloster / Universal Cables. |
| 57 | S&F in repair PVC spiral line spacer for LT over head line on 9.0 mtrs pole suitable for 2/3/4 wire, complete all as specified and directed. |
| 58 | Supply, fixing, testing & commissioning of LT weather proof panel board powder coated, outdoor type, double door shutter, made out of CRCA sheet 3 mm thickouter and 1.6 mm thick for inner door, confirming to IS 8623 with angle iron 50x50x6 mm, outdoor, floor mounting type with closed bus bar chamber and with Aluminiumbus barwith necessary insulator suitable for 3 phase, 4 wire 50 Hz AC supplyas per CPRI approved including provn of digital ammeter 0-500A,digital voltmeter 0-500 Volts, CT\"s of suitable ratio,indicator lamps R-Y-B,selector switches and internal wiring including PCC work, 0.6 Mtr above ground level, grouting etc including provision of suitable size of cable glands, cable lugs,nut, bolts,washers etc. (The bottom portion of enclosure shall be minimum 60 cm above ground level of legs of angle iron), including taking down old panel board, complete all as specified and directed and comprising of the followings:- |
| 59 | INCOMING(a) MCCB TPN 36 KA, 400 Amps- 1 Nos(I/C) Make- Havells: IHLLSEBF0400/ Crompton/ Legrand/ ScheneiderOUTGOING(a) MCCB TPN 25KA,200 Amps - 02 Nos Make- Havells: IHLLSEBF0400/Crompton/ Legrand/ Scheneider(b) MCCB TPN16 KA, 63Amps - 03 Nos Make- Havells: IHLLSEBF0400/Crompton/ Legrand/ Scheneider(c) Aluminium bus bar capacity 400 Amps for Phase-R-Y-B-3 Nos & 300 Amps for neutral -1 No(d) Digital Ammeter flush pattern type square dial 96 x 96 mm alongwith selector switch - 01 No and suitable CT ratio 0-300 Amps.Make: Havells / MECO / C&S Electric(e) Digital Voltmeter flush pattern type square dial 96 x 96 mm alongwithselector switch - 01 No 0-500 V.Make: Havells / MECO / C&S Electric(f) complete control panel wiring withstranded copper conductor of suitable size along with one set indicator lamp for R,Y & B for each incoming and outgoing feeder.(g) On Load Changeover Switch 415 Volts, 200 Amp 4 pole -01 No. Make:- Havells:IHCNFO0200/Crompton/ GE Power |
| 60 | Cutting through existing bituminous road /PCC/floor/approx size width 50cm X 60cmdepth along cross section of the road for laying of GI tubing/RCC pipe for encasing of cable and repairing the road to match with the original finish complete all as specified and directed. |
| 61 | S&F LT AB cable of size 3x35 sqmmtwisted alround the bar messenger of 1x25 sqmm , made out of aluminium stranded circular compacted conductor, XLPE insulatedall as per IS: 14255, IS 398 part-IV 7098 part-I including suspension clamp with eye hook at every 35 to 40 mtr span mounted on pole by means of MS clamp, fixed as in repairs, complete all as specified & directed. Make: Finolex / KEI/ POLYCAB/ GLOSTER |