Fixing Of Rate Contract For Repairs / Replacement To Electrical Equipment Installed At Different Wsss Of Phe Mechanical Sub-Division Qazigund Fixing Of Rate Contract For Repairs / Replacement To Electrical Equipment Installed At Different Ws, Qazigund-Jammu And Kashmir

Public Health Engineering Department-PHED has published Fixing Of Rate Contract For Repairs / Replacement To Electrical Equipment Installed At Different Wsss Of Phe Mechanical Sub-Division Qazigund Fixing Of Rate Contract For Repairs / Replacement To Electrical Equipment Installed At Different Ws. Submission Date for this Tender is 26-08-2021. Bolts Tenders in Qazigund Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

28755766
Fixing Of Rate Contract For Repairs / Replacement To Electrical Equipment Installed At Different Wsss Of Phe Mechanical Sub-Division Qazigund Fixing Of Rate Contract For Repairs / Replacement To Electrical Equipment Installed At Different Ws
Open Tender
Indian
Jammu And Kashmir
Qazigund
26-08-2021

Tender Details

Fixing Of Rate Contract For Repairs / Replacement To Electrical Equipment Installed At Different Wsss Of Phe Mechanical Sub-Division Qazigund Fixing Of Rate Contract For Repairs / Replacement To Electrical Equipment Installed At Different Wsss Of Phe Mechanical Sub-Division Qazigund - 1 Providing, Fitting And Testing Of Copper Thimbles At Site 2 1. 10 Sq. Mm 3 2. 16 Sq. Mm 4 3. 25 Sq. Mm 5 4. 50 Sq. Mm 6 5. 70 Sq. Mm 7 5. 90 Sq. Mm 8 6. 120 Sq. Mm 9 7. 150 Sq. Mm 10 Providing, Fitting And Testing Of Aluminum Thimbles At Site 11 1. 10 Sq. Mm 12 2. 16 Sq. Mm 13 3. 25 Sq. Mm 14 4. 50 Sq. Mm 15 5. 70 Sq. Mm 16 5. 90 Sq. Mm 17 6. 120 Sq. Mm 18 7. 150 Sq. Mm 19 Providing, Fitting Of Below Mentioned Item For Repairs To 50Kva Voltage Stabilizer Including Extraction Of Damaged Items, Transportation, Loading, Unloading, Shifting Back And Then Fitting And Successful Testing On No And Full Load At Site. 20 Copper Wire Of Specific Gauge For Fabrication Of Primary / Secondary Coil 21 Bush Rod With Porcelain Insulator And Packing 22 Rewinding / Re-Taping / Re-Insulation Of Coils 23 T-Oil 24 Copper Strip 25 Filtration / Dehydration Of T-Oil 26 Cost Of Scrap Copper Dismattled Windings 27 Cost Of Damaged Lamination 28 Providing, Fitting Of Below Mentioned Item For Repairs To 75Kva Voltage Stabilizer Including Extraction Of Damaged Items, Transportation, Loading, Unloading, Shifting Back And Then Fitting And Successful Testing On No And Full Load At Site. 29 Copper Wire Of Specific Gauge For Fabrication Of Primary / Secondary Coil 30 Bush Rod With Porcelain Insulator And Packing 31 Rewinding / Re-Taping / Re-Insulation Of Coils 32 T-Oil 33 Copper Strip 34 Filtration / Dehydration Of T-Oil 35 Cost Of Scrap Copper Dismattled Windings 36 Cost Of Damaged Lamination 37 Providing, Fitting Of Below Mentioned Item For Repairs To 100Kva Voltage Stabilizer Including Extraction Of Damaged Items, Transportation, Loading, Unloading, Shifting Back And Then Fitting And Successful Testing On No And Full Load At Site. 38 Copper Wire Of Specific Gauge For Fabrication Of Primary / Secondary Coil 39 Bush Rod With Porcelain Insulator And Packing 40 Rewinding / Re-Taping / Re-Insulation Of Coils 41 T-Oil 42 Copper Strip 43 Filtration / Dehydration Of T-Oil 44 Cost Of Scrap Copper Dismattled Windings 45 Cost Of Damaged Lamination 46 Providing, Fitting Of Below Mentioned Item For Repairs To Voltage Regulator ( Plate Type Switch ) Including Extraction Of Damaged Items, Transportation, Loading, Unloading, Shifting Back And Then Fitting And Successful Testing On No And Full Load At Site. 47 1. 150Mmx150mm 48 2. 225Mm X 225Mm 49 3. 200Mm X 200Mm 50 4. 250Mm X 250Mm 51 5.300Mm X 300Mm 52 6. 375Mm X 375Mm 53 7.450Mm X 450Mm 54 Providing, Fitting Of Below Mentioned Item For Repairs To Voltage Regulator ( Drum Type Switch ) Including Extraction Of Damaged Items, Transportation, Loading, Unloading, Shifting Back And Then Fitting And Successful Testing On No And Full Load At Site. 55 1. 32A 56 2. 63A 57 3. 100A 58 4. 200A 59 Providing, Fitting And Testing Of Voltmeters At Site 60 0-200V 61 0-500V 62 Providing, Fitting And Testing Ofthree Phase Digital Type Led Voltmeters Class 1At Site - Make L&T / Rishab 63 0-500V 64 Providing, Fitting And Testing Of Ammeters At Site 65 1. 0-50A With Ct Ratio Of 5 / 50 66 2. 0-100A With Ct Ratio Of 5 / 100 67 3. 0-150A With Ct Ratio Of 5 / 150 68 4. 0-200A With Ct Ratio Of 5 / 200 69 Providing, Fitting And Testing Of 96 Sq Mm Three Phase Digital Led Ammeters Class1at Site - Make L&T / Rishab 70 Providing, Fitting And Testing Of 96 Sq Mm Three Phaseled Frequency Meter Class0.2 At Site - Make L&T / Rishab 71 Providing, Fitting And Testing Of Three Phase Analogus Type 0-50Hz Frequency Meter At Site - Make L&T / Rishab / Ae 72 Providing, Fitting And Testing Of Post Type Drop Out Set Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 73 Suitable For 25Kva Ss 74 Suitable For 63Kva Ss 75 Suitable For 100Kva Ss 76 Suitable For 250Kva Ss 77 Providing, Fitting And Testing Of Link Set Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 78 Suitable For 25Kva Ss 79 Suitable For 63Kva Ss 80 Suitable For 100Kva Ss 81 Suitable For 250Kva Ss 82 Providing, Fitting And Testing Of 11Kva Disc Set Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 83 Providing, Fitting And Testing Of 11Kva Pin Insulators Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 84 Providing, Fitting And Testing Of Submersible Copper Cables Of Below Mentioned Specifications Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 85 1. 10 Sq Mm 86 2. 16 Sq Mm 87 3. 25 Sq Mm 88 Providing, Fitting And Testing Of Copper Cables Of Below Mentioned Specifications Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 89 19 / 0.0064 90 19 / 0.044 91 7 / 16.00 92 Providing, Fitting And Testing Of 3.5 Core Xlpe Aluminum Conductor Of Below Mentioned Specifications Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 93 1. 35 Sq. Mm 94 2. 50 Sq. Mm 95 3. 70 Sq. Mm 96 3. 95 Sq. Mm 97 4. 120 Sq. Mm 98 5. 185 Sq. Mm 99 Providing, Fitting And Testing Of 11Kvaxlpe Aerial Bunched Cable ( Ht ) Of Below Mentioned Specifications Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 100 1. 35 Sq. Mm 101 2. 50 Sq. Mm 102 Providing, Fitting And Testing Of 11Kvacable Termination / Jointing Kit Set Below Mentioned Specifications Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 103 1. 35 Sq. Mm 104 2. 50 Sq. Mm 105 Providing, Fitting And Testing Of 11Kv Post Type Lightening Arrestor Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 106 Providing, Fitting And Testing Of G.O.D Set Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 107 Providing, Fitting And Testing Of Cross Arms Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 108 1. Channels 75X40 109 2. Channels 100 X 50 110 3. Angle Iron Support 111 4. F-Top 112 5. U Clamps 113 6. Guy-Wire With Turn Buckle 114 7. Guy-Insulator 115 Providing, Fitting And Testing Of Acsr Conductor Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 116 1. 0.03 117 2. 0.05 118 Providing, Fitting And Testing Of Mccbs ( 04 Pole ) Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 119 63 Amps 120 100 Amps 121 125 Amps 122 160 Amps 123 200 Amps 124 250 Amps 125 320 Amps 126 400 Amps 127 Providing, Fitting And Testing Of Mccbs ( 03 Pole ) Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 128 63Amps 129 100Amps 130 125Amps 131 160Amps 132 200Amps 133 250Amps 134 Providing, Fitting And Testing Of Change Over Switch Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. 135 63 A 136 100 A 137 200 A 138 630 A 139 Providing, Fitting And Testing Of On Load Change Over Switch Front Operated On Load 4 Pole Including Extraction Of Damaged Ones, Transportation, Loading, Unloading, Fitting And Successful Testing On No And Full Load At Site. Make - L& T 140 100 Amp 141 200Amp 142 Providing, Fitting And Testing Of Combined Volt-Ammeter For Mu-G Starters 143 30A 144 60A 145 75A 146 100A 147 125A 148 Providing, Fitting And Testing Of 415V Indicating Lamps 149 Red 150 Yellow 151 Green 152 Providing, Fitting And Testing Of 415V Single Phase Preventor ( Mu G10 To Mu G75 ) 153 Providing, Fitting And Testing Of Terminal Block With Start / Stop Button 154 30A-5 Way 155 60A-3Way 156 60A-6 Way 157 100A-3 Way 158 120A-3 Way 159 Providing, Fitting And Testing Of Power Contactor For Mu-G Starters 160 Mu-G10 161 Mu-G15 162 Mu-G20 163 Mu-G30 164 Mu-G40 165 Mu-G50 166 Mu-G75 167 Providing, Fitting And Testing Of Overload Relay / Under Voltage Relay / Single Phase Preventer / Timer For Mu-G Starters 168 Mu-G10 169 Mu-G15 170 Mu-G20 171 Mu-G30 172 Mu-G40 173 Mu-G50 174 Mu-G75 175 Providing And Fitting Of Gsm Based Remote Access Motor Control Module Complete Replacement 176 Providing And Fitting Of Multi-Function Meter Square Dial Type 177 Providing, Fitting Of Below Mentioned Item For Repairs To 40Kva To 100 Kva Voltage Stabilizer Including Extraction Of Damaged Items, Transportation, Loading, Unloading, Shifting Back And Then Fitting And Successful Testing On No And Full Load At Site. 178 Copper Wire Of Specific Gauge For Fabrication Of Primary / Secondary Coil 179 Bush Rod With Porcelain Insulator And Packing 180 Rewinding / Re-Taping / Re-Insulation Of Coils 181 T-Oil 182 Copper Strip 183 Filtration / Dehydration Of T-Oil 184 Cost Of Scrap Copper Dismattled Windings 185 Cost Of Damaged Lamination 186 Nuts And Bolts Of Different Size 187 Providing Fitting Ammeter / Voltmeter / Selector Switch 188 Providing, Fitting Of Below Mentioned Item For Repairs To 10Kva To 50Kva Servo Stabilizer Including Extraction Of Damaged Items, Transportation, Loading, Unloading, Shifting Back And Then Fitting And Successful Testing On No And Full Load At Site. 189 Replacement Of Digital Micro Controlled Processor Based Control Card 190 Replacement Of Ac Syncronous Servo Motor 191 Replacement Of Copper Wound Motorized Auto Transformer 192 Replacement Of Buck And Boost Series Transformer 193 Repairs To Led Lights At Site By Way Of Replacing Strips 194 25Watt 195 45Watt 196 48Watt 197 50Watt 198 60Watt 199 90Watt 200 100Watt 201 120Watt 202 Erection Of Ms Tubular 9M / 11M Tilted Pole By Way Of Excavation Of New Trench And Concrete Bottoming Including Re-Fitting / Fixing Of Acsr Conductor On The Insulators 203 Repairs To Horizontal Motor With Rating From 5Hp To 50Hpdismantling Of The Horizontal Motor At Site, Shifting To The Workshop, Repairing, Shifting Back To Site, Re-Fitting And Successfull Testing On Full Load. Job Includes Repairing / Fabrication And Providing / Replacement Of Following Items. 204 Copper Wire Used In Rewinding The Motor. 205 Rewinding, Skilled Labor, Insulated Paper And Sleeves Used During Rewinding And Testing Of Motor At Site. 206 Cost On Account Of Associated / Consumable Items Like Crimpled Paper, Sleeves, Pvc Paper, Bamboo Sticks, Thread, Varnish Etc 207 Cost Of Scrap Copper Dismanttled Windings 208 Repairs To Submersible Motor With Rating From 5Hp To 50Hpdismantling Of The Submersible Motor At Site, Shifting To The Workshop, Repairing, Shifting Back To Site, Re-Fitting And Successfull Testing On Full Load. Job Includes Repairing / Fabrication And Providing / Replacement Of Following Items. 209 Copper Wire Used In Rewinding The Motor. 210 Rewinding, Skilled Labor, Tapping And Sleeves Used During Rewinding And Testing Of Motor At Site. 211 Cost On Account Of Associated / Consumable Items Like Crimpled Paper, Sleeves, Pvc Paper, Bamboo Sticks, Thread, Etc 212 Replacement Of Motor Shaft 213 Cost Of Scrap Copper Dismanttled Windings 214 Replacing Of Damages Illumination Single Core Multistranded Copper Wiring 215 1 Sq Mm 216 1.5 Sq Mm 217 2 Sq Mm 218 2.5 Sq Mm 219 4 Sq Mm 220 Replacement Of Damaged Electrification And Electrification Of Pump House Including Cost Of Channels / Conduits, Fitting Charges, Transportation And Testing On Load At Site 221 Lighting Points In 1.0Mm2 Copper Wire Including 5W Led Lamp 222 Heating Points In 2.5 Mm2 Copper Wire Including 16Amp Ss Combined 223 Providing Of 5W / 7W Led Lamp 224 Replacement Of Damaged Led Street Light 48W ( Havells Make ) 225 Providing, Fitting Racer Plate To Submersible Motor From 05Hp To 50Hp Including Extraction Of Damaged Items, Transportation, Loading, Unloading, Shifting Back And Then Fitting And Successful Testing On No And Full Load At Site 226 Providing / Fitting Of Steel Coupling For Submersible Motors From 05Hp To 50 Hp Including Cotter 227 Providing / Fitting Of Connection Platefor Horizontal Motors From 05Hp To 50 Hp 228 Repairs To The Rotor / Body Of Submersible Motor 229 Repairs To The Rotor / Body, Fan, Shield Of Horizontal Motor 230 Providing / Fitting Of M S Coupling For Horizontal Motors From 05Hp To 50 Hp Including Cotter And Boring 231 Providing / Fitting Of Gun Metalbush ( Finished ) To The Submersible Motor From 05Hp To 50Hp As Per Sample 232 Repair Works On Dg Set 25 Kva - 62.5 Kva 233 Repairs To Self / Dynamo Of Dg Set 234 Providing / Fitting Of Avr To Dg Set As Per Sample ( 25 Kva To 62.5Kva ) 235 Repair And Rewinding Of Dg Set Cooling Fan 236 Minor Overhauling Of Dg Set Including Repair To Radiator 237 Providing / Fitting Of Battery Connection Leads With Copper Connectors 238 Replacement Of M-Oil 239 Replacement Of Air Hose Pipe 240 Replacement Of Fuel Pipe 241 Providing / Fitting Of Battery Connection Leads With Copper Connectors 242 Providing And Fitting Of Side Thrust Bearing For Different Capacity Open Well Submersible Pumping Units ( Horizontal Type ) Compatible For 243 7.5Hp 244 10Hp 245 12.5Hp 246 15Hp 247 Providing And Fitting Of Bush Bearing ( De & Nde ) For Different Capacity Open Well Submersible Horizontal Type Pumping Units Compatible For 248 7.5Hp 249 10Hp 250 12.5Hp 251 15Hp 252 Providing And Fitting Of Ball / Thrust Bearing ( De & Nde ) For Different Capacity Motors And Pumps Compatible For 253 No. 6308 254 No. 6309 255 No. 6312 256 No. 6306 257 No. 6208 258 No. 6211 259 No. 6311 260 No. 6310 261 No. 6212 262 Providing And Fitting Of Thrust Bearings For Deep Well Submersible Pumping Units Compatible For 263 Thrust Base V4 264 Thrust Base V6 265 Thrust Base V8 266 Thrust Pad V4 267 Thrust Pad V6 268 Thrust Pad V8

Key Value

Document Fees
INR 500 /-
EMD
Refer document
Tender Value
Refer document

BOQ Items

Name of Work: Fixing of rate contract for repairs/ replacement to electrical equipment installed at different WSSs of PHE Mechanical Sub-Division QAZIGUND (District Anantnag and Kulgam) for the financial year 2021-22
Sl. No. Item Description
1Providing, fitting and testing of Copper thimbles at site
21.     10 Sq. mm
32.     16 Sq. mm
43.     25 Sq. mm
54.     50 Sq. mm
65.     70 Sq. mm
75.     90 Sq. mm
86.     120 Sq. mm
97.     150 Sq. mm
10Providing, fitting and testing of Aluminum thimbles at site
111.     10 Sq. mm
122.     16 Sq. mm
133.     25 Sq. mm
144.     50 Sq. mm
155.     70 Sq. mm
165.     90 Sq. mm
176.     120 Sq. mm
187.     150 Sq. mm
19Providing, fitting of below mentioned item for repairs to 50KVA Voltage Stabilizer including extraction of damaged items, transportation, loading, unloading, shifting back and then fitting and successful testing on no and full load at site.
20Copper wire of specific gauge for fabrication of primary / secondary coil
21Bush rod with porcelain insulator and packing
22Rewinding/Re-taping /re-insulation of coils
23T-Oil
24Copper strip
25Filtration / dehydration of T-oil
26Cost of scrap copper dismattled windings
27Cost of damaged lamination
28Providing, fitting of below mentioned item for repairs to 75KVA Voltage Stabilizer including extraction of damaged items, transportation, loading, unloading, shifting back and then fitting and successful testing on no and full load at site.
29Copper wire of specific gauge for fabrication of primary / secondary coil
30Bush rod with porcelain insulator and packing
31Rewinding/Re-taping /re-insulation of coils
32T-Oil
33Copper strip
34Filtration / dehydration of T-oil
35Cost of scrap copper dismattled windings
36Cost of damaged lamination
37Providing, fitting of below mentioned item for repairs to 100KVA Voltage Stabilizer including extraction of damaged items, transportation, loading, unloading, shifting back and then fitting and successful testing on no and full load at site.
38Copper wire of specific gauge for fabrication of primary / secondary coil
39Bush rod with porcelain insulator and packing
40Rewinding/Re-taping /re-insulation of coils
41T-Oil
42Copper strip
43Filtration / dehydration of T-oil
44Cost of scrap copper dismattled windings
45Cost of damaged lamination
46Providing, fitting of below mentioned item for repairs to Voltage regulator (plate type switch) including extraction of damaged items, transportation, loading, unloading, shifting back and then fitting and successful testing on no and full load at site.
471.     150mmx150mm
482.     225mm x 225mm
493.     200mm x 200mm
504.     250mm x 250mm
515.300mm x 300mm
526. 375mm x 375mm
537.450mm x 450mm
54Providing, fitting of below mentioned item for repairs to Voltage regulator (drum type switch) including extraction of damaged items, transportation, loading, unloading, shifting back and then fitting and successful testing on no and full load at site.
551.     32A
562.     63A
573.     100A
584.     200A
59Providing, fitting and testing of Voltmeters at site
600-200V
610-500V
62Providing, fitting and testing ofThree phase digital type LED voltmeters class 1at site - Make L&T/Rishab
630-500V
64Providing, fitting and testing of Ammeters at site
651.     0-50A with CT ratio of 5/50
662.     0-100A with CT ratio of 5/100
673.     0-150A with CT ratio of 5/150
684.     0-200A with CT ratio of 5/200
69Providing, fitting and testing of 96 sq mm Three phase digital LED Ammeters class1at site - Make L&T/Rishab
70Providing, fitting and testing of 96 sq mm Three phaseLED Frequency meter class0.2 at site - Make L&T/Rishab
71Providing, fitting and testing of Three phase Analogus type 0-50HZ frequency meter at site - Make L&T/Rishab/AE
72Providing, fitting and testing of post type drop out set including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
73Suitable for 25KVA SS
74Suitable for 63KVA SS
75Suitable for 100KVA SS
76Suitable for 250KVA SS
77Providing, fitting and testing of link set including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
78Suitable for 25KVA SS
79Suitable for 63KVA SS
80Suitable for 100KVA SS
81Suitable for 250KVA SS
82Providing, fitting and testing of 11KVA Disc set including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
83Providing, fitting and testing of 11KVA pin insulators including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
84Providing, fitting and testing of submersible copper cables of below mentioned specifications including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
851.    10 sq mm
862.    16 sq mm
873.    25 sq mm
88Providing, fitting and testing of copper cables of below mentioned specifications including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
8919/0.0064
9019/0.044
917/16.00
92Providing, fitting and testing of 3.5 core XLPE aluminum conductor of below mentioned specifications including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
931.    35 Sq. mm
942.    50 Sq. mm
953.    70 Sq. mm
963.    95 Sq. mm
974.    120 Sq. mm
985.    185 Sq. mm
99Providing, fitting and testing of 11KVAXLPE aerial Bunched cable(HT)of below mentioned specifications including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
1001.    35 Sq. mm
1012.    50 Sq. mm
102Providing, fitting and testing of 11KVAcable termination/Jointing kit set below mentioned specifications including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
1031.    35 Sq. mm
1042.    50 Sq. mm
105Providing, fitting and testing of 11KV post type lightening arrestor including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
106Providing, fitting and testing of G.O.D set including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
107Providing, fitting and testing of Cross arms including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
1081.    Channels 75x40
1092. Channels 100 x 50
1103.    Angle iron support
1114.    F-top
1125.    U Clamps
1136.    Guy-wire with turn buckle
1147.    Guy-Insulator
115Providing, fitting and testing of ACSR Conductor including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
1161.    0.03
1172.    0.05
118Providing, fitting and testing of MCCBs (04 Pole) including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
11963 Amps
120100 Amps
121125 Amps
122160 Amps
123200 Amps
124250 Amps
125320 Amps
126400 Amps
127Providing, fitting and testing of MCCBs (03 Pole) including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
12863amps
129100amps
130125amps
131160amps
132200Amps
133250amps
134Providing, fitting and testing of Change over switch including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site.
13563 A
136100 A
137200 A
138630 A
139Providing, fitting and testing of on load Change over switch Front operated on load 4 pole including extraction of damaged ones, transportation, loading, unloading, fitting and successful testing on no and full load at site. Make - L& T
140100 Amp
141200Amp
142Providing, fitting and testing of Combined volt-ammeter for MU-G starters
14330A
14460A
14575A
146100A
147125A
148Providing, fitting and testing of 415V Indicating lamps
149Red
150Yellow
151Green
152Providing, fitting and testing of 415V Single phase preventor (MU G10 to MU G75)
153Providing, fitting and testing of Terminal block with start/stop button
15430A-5 way
15560A-3way
15660A-6 way
157100A-3 way
158120A-3 way
159Providing, fitting and testing of Power contactor for MU-G starters
160MU-G10
161MU-G15
162MU-G20
163MU-G30
164MU-G40
165MU-G50
166MU-G75
167Providing, fitting and testing of Overload relay/under voltage relay/single phase preventer/Timer for MU-G starters
168MU-G10
169MU-G15
170MU-G20
171MU-G30
172MU-G40
173MU-G50
174MU-G75
175Providing and fitting of GSM based remote access motor control module complete replacement
176Providing and fitting of Multi-Function Meter Square Dial type
177Providing, fitting of below mentioned item for repairs to 40KVA to 100 KVA Voltage Stabilizer including extraction of damaged items, transportation, loading, unloading, shifting back and then fitting and successful testing on no and full load at site.
178Copper wire of specific gauge for fabrication of primary / secondary coil
179Bush rod with porcelain insulator and packing
180Rewinding/Re-taping /re-insulation of coils
181T-Oil
182Copper strip
183Filtration / dehydration of T-oil
184Cost of scrap copper dismattled windings
185Cost of damaged lamination
186Nuts and bolts of different size
187Providing Fitting Ammeter /Voltmeter/Selector Switch
188Providing, fitting of below mentioned item for repairs to 10KVA to 50KVA Servo Stabilizer including extraction of damaged items, transportation, loading, unloading, shifting back and then fitting and successful testing on no and full load at site.
189Replacement of digital micro controlled processor based control card
190Replacement of AC syncronous servo motor
191Replacement of copper wound motorized auto transformer
192Replacement of buck and boost series transformer
193Repairs to LED lights at site by way of replacing strips
19425Watt
19545Watt
19648Watt
19750Watt
19860Watt
19990Watt
200100Watt
201120Watt
202Erection of MS tubular 9m/11m tilted pole by way of excavation of new trench and concrete bottoming including re-fitting/fixing of ACSR conductor on the insulators
203Repairs to horizontal Motor with rating from 5HP to 50HP Dismantling of the horizontal motor at site, shifting to the workshop, repairing, shifting back to site, re-fitting and successfull testing on full load. Job includes repairing / fabrication and providing / replacement of following items.
204Copper wire used in rewinding the motor.
205Rewinding,Skilled labor, insulated paper and sleeves used during rewinding and testing of motor at site.
206Cost on account of associated/consumable items like crimpled paper, sleeves, PVC paper, bamboo sticks, thread, varnish etc
207Cost of scrap copper dismanttled windings
208Repairs to submersible Motor with rating from 5HP to 50HP Dismantling of the submersible motor at site, shifting to the workshop, repairing, shifting back to site, re-fitting and successfull testing on full load. Job includes repairing / fabrication and providing / replacement of following items.
209Copper wire used in rewinding the motor.
210Rewinding, Skilled labor, tapping and sleeves used during rewinding and testing of motor at site.
211Cost on account of associated/consumable items like crimpled paper, sleeves, PVC paper, bamboo sticks, thread, etc
212Replacement of motor shaft
213Cost of scrap copper dismanttled windings
214Replacing of damages illumination single core multistranded copper wiring
2151 Sq mm
2161.5 Sq mm
2172 Sq mm
2182.5 Sq mm
2194 Sq mm
220Replacement of damaged electrification and electrification of pump house including cost of channels/conduits, fitting charges, transportation and testing on load at site
221Lighting points in 1.0mm2 copper wire including 5W LED lamp
222Heating points in 2.5 mm2 copper wire including 16Amp SS combined
223Providing of 5W/7W LED lamp
224Replacement of damaged LED street light 48W (Havells make)
225Providing, fitting Racer plate to submersible motor from 05HP to 50HP including extraction of damaged items, transportation, loading, unloading, shifting back and then fitting and successful testing on no and full load at site
226Providing/fitting of Steel coupling for submersible motors from 05HP to 50 HP including cotter
227Providing/fitting of connection platefor Horizontal motors from 05HP to 50 HP
228Repairs to the rotor/body of submersible motor
229Repairs to the rotor/body, fan, shield of Horizontal motor
230Providing/fitting of M S coupling for Horizontal motors from 05HP to 50 HP including cotter and boring
231Providing/fitting of Gun metalbush (finished) to the submersible motor from 05HP to 50HP as per sample
232Repair works on DG Set 25 KVA - 62.5 KVA
233Repairs to self / Dynamo of DG set
234Providing/fitting of AVR to DG set as per sample (25 KVA to 62.5KVA)
235Repair and rewinding of DG set cooling fan
236Minor overhauling of DG set including repair to radiator
237Providing/fitting of Battery connection leads with copper connectors
238Replacement of M-Oil
239Replacement of Air Hose Pipe
240Replacement of Fuel Pipe
241Providing/fitting of Battery connection leads with copper connectors
242Providing and fitting of Side thrust bearing for different capacity open well submersible pumping units (horizontal type) compatible for
2437.5HP
24410HP
24512.5HP
24615HP
247Providing and fitting of Bush bearing (DE & NDE) for different capacity open well submersible horizontal type pumping units compatible for
2487.5HP
24910HP
25012.5HP
25115HP
252Providing and fitting of Ball/Thrust bearing (DE & NDE) for different capacity motors and pumps compatible for
253No. 6308
254No. 6309
255No. 6312
256No. 6306
257No. 6208
258No. 6211
259No. 6311
260No. 6310
261No. 6212
262Providing and fitting of thrust bearings for deep well submersible pumping units compatible for
263Thrust base V4
264Thrust base V6
265Thrust base V8
266Thrust pad V4
267Thrust pad V6
268Thrust pad V8
269Note: The Scrap Value mentioned above shall be deducted from the total valve of BOQ to arrive at value without scrap. The value thus attained shall be again deducted by total scrap value to get the effective amount on BOQ for ascertainingoverall L1. Unless specified, the old material shall be returned to divisional/sub divisional store