| 1 | Handling and carriage from ECSD Pampora / Divisional Store to siteandITC of 10 MVA 33/11KV, ONAN, Copper wound, Out-door Type, conventional Power Transformer, Oil Filled with OLTC and all accessories including HT and LT Terminal connections( within Receiving Station) |
| 2 | SITC of 33 kV Post Insulator Polymer 36kV,35kV Impulse, creepage distance 1224m |
| 3 | SITC of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 KV Grade, ISI, FRLS. |
| 4 | Supply, Installation testing and commissioningof11 kV VCB Panel Board (12 kV, 1250A, 25 KA, indoor) with O/C, E/F relays (IEC61850, mimic diagram, volt meter, ammeter, annunciation windows with annunciation relay, 3 phase triovecto meter-5Amp, Dlms compliant with RS-485 port (1 Incomer)of make Schneider / Crompton / ABB /Eason Reyrole ( job includes extension of bus from existing panel set with the new panels enclosed within bus extension chamber made ofsame Quality of panel material in use) |
| 5 | SITC of 11 KV 630mm2single- Core XLPE cable (with one spare length) armoured, FRLS |
| 6 | SITC of 11 kV Outdoor Heat Shrinkable Cable Termination Kits for single core incoming cable outdoor type630 mm sq ( 3NO) |
| 7 | SITC of 11 kV Outdoor Heat Shrinkable Cable Termination Kits for single core incoming cable indoor type630 mm sq ( 3NO) |
| 8 | SITC of Galvanised iron of sorts |
| 9 | Chemical Earthing in 33 KV yard using electrodes of 3mtre long 3 No and connection of same with earthing mesh & New power transformer complete Job including transformer neutral. |
| 10 | SITC of 800 ampere Aluminium Bus with suitable Tclamps for connection withPower cable |
| 11 | Supply and layingof Cement concrete to channel Iron Galvanized for support structure to 11KV Bus on LV side of Transformer in1:2:4 mix as per REC standards complete job |
| 12 | SITC of 33 kV C&R Panel with numerical Relays ( IEC 61850) |
| 13 | Supply and laying ofRubber Mat 1mx2m 19mm thick |
| 14 | Supply of Earthing rod (set of 3 rods) (with telescopic rod of 5 Mtr detachable) |
| 15 | Supply ofHV Detectors all voltages (50 hV with telescopic rod of 5 Mtr detachable) |
| 16 | SITC of a). Battery Bank 36 V,180 AH , of 18 No. cells of 2 V each, sealed maintenance free VRLA type, High impact Polyprophelene copolymer container, flame etardant.b). 36v,180 AH , Float-Cum-Boost Charger With Full waverectification for 220 V, 1Phase, 50 HZ AC Input Supply . |
| 17 | Lifting of Old Transformer from site & transportation carriage of same from site to Divisional Store or any Rec station with aducate space for stocking within District Baramulla (25 % Appreciationon quoted rate if stocked outside district .( job include insurance of the transformer during transit )( any item dismantled during transit need to be installed backand kept transformer in its earlier state) |