Essential Repair And Renewal Of Ht Cts 22 Kv , Indoor , Outdoor Breakers , Ht Mocbs , Vcbs , Rmus And Repair And Maintenance Of Transformer , Dehydration , Filtration Of Transformer Oil And Other Misc Works At Naval Station Karanja, NAVAL STATION KARANJA-Maharashtra

Military Engineer Services-MES has published Essential Repair And Renewal Of Ht Cts 22 Kv , Indoor , Outdoor Breakers , Ht Mocbs , Vcbs , Rmus And Repair And Maintenance Of Transformer , Dehydration , Filtration Of Transformer Oil And Other Misc Works At Naval Station Karanja. Submission Date for this Tender is 17-07-2021. Transformer Oil Tenders in NAVAL STATION KARANJA Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

28240204
Corrigendum : Essential Repair And Renewal Of Ht Cts 22 Kv , Indoor , Outdoor Breakers , Ht Mocbs , Vcbs , Rmus And Repair And Maintenance Of Transformer , Dehydration , Filtration Of Transformer Oil And Other Misc Works At Naval Station Karanja
Open Tender
Indian
Maharashtra
NAVAL STATION KARANJA
17-07-2021

Tender Details

Essential Repair And Renewal Of Ht Cts 22 Kv , Indoor , Outdoor Breakers , Ht Mocbs , Vcbs , Rmus And Repair And Maintenance Of Transformer , Dehydration , Filtration Of Transformer Oil And Other Misc Works At Naval Station Karanja

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 01-Jul-2021 Date Corrigendum Date 10-07-2021
2 01-Jul-2021 BOQ corrigendum BOQ 17-07-2021
3 10-Jul-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 17-07-2021

Key Value

Document Fees
INR 500 /-
EMD
INR 90000.0 /-
Tender Value
Refer document

BOQ Items

NAME OF WORK : ESSENTIAL REPAIR/ RENEWAL OF HT CT's 22 KV, INDOOR/ OUTDOOR BREAKERS, HT MOCB's, VCBs, RMUs AND REPAIR/ MAINTENANCE OF TRANSFORMER, DEHYDRATION/ FILTRATION OF TRANSFORMER OIL AND OTHER MISC WORKS AT NAVAL STATION KARANJA
Sl. No. Description of Item of Work Item Code / Make Quantity Unit
1 1 Periodical checking / preventive maintenance of HT MOCB 22 KV 800 Amps, 50 Hz 700 MVA yearly 3 times are as under complete all as specified and as directed by Engr-in-charge.\n(a) Checking the closing and opening operation of MOCB and functional checks and repair/ replacement of the defective components.\n(b) Overhauling and Calibration of relays (secondary injection/Primary injection on each multiple setting of relays).\n(c) Setting and coordination of relays.\n(d) Checking and recording of IR value of MOCB trolley and panel.\n(e) Checking/repairing/rectification of the control wiring.\n(f) Replacement of panel heater 80 watt.\n(g) Replacement of worn out bushing PT/Busbar support insulators\n(h) Replacement of worn out bushing PT/Busbar support insulators\n(j) Replacement of unserviceable and Open circuit CT's. 3 Each Job Per Breaker
2 1.01 (k) Checking fibre plates, gaskets, transformer oil and applying multi grease to the mechanical parts and dry graphite conductive sealant to contacts of PT etc., and re-assembling the same and commissioning complete to entire satisfaction of Engr-in-charge.\n(l) Testing of polarities of CT's.\n(m) High voltage testing with high voltage tester of CT and Breaker pole to withstand working pressure of HT 22 KV to ascertain servicieability and spare parts found defective to be replaced for smooth functioning.\n(n) Labour only for Opening the busbar chamber of HT 22KV MOCB panel board cleaning the bus bar chamber, inspect the CT's wiring, spout insulator and bus-bar joints and tightening if required and heating up with hot air blower to remove moisture, meggering, HV testing applying TRTPPEX(B) supplied to bus bar and commissioning.
3 1.02 Notes: (i) All spares required for replacement shall be measured and paid separately under respective item of schedule here-in-after as supply only.\n(ii) Machine grease, oil, liquid sealant and any minor item costing upto Rs 250 will be included in the unit rate of above item and for satisfactory function of the breakers and no extra cost will be allowed. Decision of accepting officer in this regard will remain final and binding.\n(iii) The overhauling of HT breakers to be carried out either through OEM's service Engineer/authorised dealer/San and Engg consultant /Triotech consultant/ those who posses HT handling license.
4 2 Periodical checking /preventive maintenance of HT VCBs/ RMUs Panel etc., of 630 Amps /800 Amps rating indoor and outdoor type detailed are as under complete all as specified and as directed by Engr-in-charge.\nMake: ABB/ Arriva/ C&G / Schineder\n(a) Servicing (i.e light primary terminals) and repair/ replacement of defective components.\n(b) Functional checks\n(c) Mechanisum servicing and lubrication\n(d) Protection checks\n(e) Control wiring tightness\n(f) Power connection tightness\n(g) Insulation measurement of main circuit\n(h) Contact resistance of main circuit\n(j) Checking the operation of VCB/RMUs panel\n(k) Overhauling and Calibration of relays\n(l) Setting and coordination of relays 10 Each Job Per Breaker
5 2.01 (m) Checking and recording of IR value of breaker trolley\n(n) Checking/repairing/rectification of the control wiring\n(o) Checking the panel heater and replacement of faulty space heater\n(p) Replacement of the unserviceable / open circuit CT's\n(q) Testing of PT and PT circuits\n(r) Cleaning the breaker externally and internally thoroughly with lint free cloth\n(s) High voltage testing with high voltage tester to withstand working pressure HT 22 KV to ascertain servicieability, spare parts found defective to be replaced for smooth functioning\nNotes: (i) All spares required for replacement shall be measured and paid separately under respective items of schedule 'A' here-in-after as supply only.\n(ii) The overhauling of HT breakers to be carried out either through OEM's service Engineer/ authorised dealer/ San and Engg consultant / Triotech consultant/ those who posses HT handling license.
6 3 Supply only following spare parts required for ser item No.1 here-in-bofore suitable for MOCB of 800 Amps, 700 MVA all as per sample complete all as specified and as directed by Engr-in-charge.\nNote: The element of fixing of spare is already included in respective Sl Item No. 1 here-in-before.
7 3.01 Spout insulator (Epoxy) 3 Each
8 3.02 TRTPPX (B) for HT 22 KV for breaker 3 Each
9 3.03 Current Transformer 22 KV single phase indoor Resin cast CT Ratio 30-15/5-5 Amps Class 1.0 insulation level 28 KV/75 KV as per IS 2075 3 Each
10 3.04 OLTF assembly suitable for MOCB, 22KV, 800Amps, indoor type 2 Each
11 3.05 Strip type heater 80 watt 3 Each
12 3.06 Closing coil 2 Each
13 3.07 Tripping coil 2 Each
14 3.08 PT Primary fuse 22 KV 23 Amps 3 Each
15 3.09 Control fuse 2 Amps with HRC fuse and fuse holder in existing\nMake: EE/ Standard/ Havells/ L&T 3 Each
16 3.1 Insulation Tape suitable for HT 22 KV 1.5" wide.\nMake: 3M or equivalent 20 RM
17 3.11 MOCB oil tank gasket suitable for MOCB 22KV 800 Amps indoor type 2 Each
18 3.12 Baffle pot assembly suitable for MOCB, 22 KV, 800 Amps, indoor type 3 Each
19 3.13 Main moving contact bolted/ threaded type suiatable for MOCB, 22KV, 800Amps, indoor type 3 Each
20 3.14 PT single phase indoor resin cast PT Ratio 22 KV/ R3/ 110V /R3 Class 1.0, 200VA. 3 Each
21 3.15 HT bushing with spindle 2 Each
22 3.16 Thermostat - 0-100 Deg. Celcius 3 Each
23 3.17 Moving contact rod 3 Each
24 3.18 Upper fix contact 2 Each
25 3.19 Lower fix contact 3 Each
26 3.2 Top and bottom male contact 3 Each
27 3.21 Female contact 3 Each
28 3.22 Support insulator 2 Each
29 3.23 Partition fiber plate 3 Each
30 3.24 Copper strip of 800 Amps (per Kg) 1 KG
31 4 Supply only following spare parts required for ser item No.2 here-in-before suitable for HT VCBs /RMUs panel 630 Amps /800 Amps 22 KV complete all as specified and as directed by Engr-in-charge.\nNote: The element of fixing of spares is already included in respective ser Item No. 2 here-in-before.
32 4.01 Current transformer resin cast single phase 22 KV - 200/ 100V, 5-A, Class-1.0, SP-10 6 Each
33 4.02 Potential transformer resin cast single phase 22 KV /R3 /110V /R3, 200 VA, class-I 6 Each
34 4.03 O/C and earth fault relay with IDMT and inst charatrostics MC 61 A.\nMake : L&T 30 Volt DC 3 Each
35 4.04 Master Trip relay 30v DC 3 NO + 1 NC.\nMake: Ashida 3 Each
36 4.05 Digital voltmeter (KV meter) 0 to 30 V (PTR 22 KV/ 110 V, AC with selector switch) 5 Each
37 4.06 Digital Amps meter class - 1.0, CTR ratio - 0 to 200/100-5-5A 5 Each
38 4.07 Numerical O/C & E/F Relay 1/5A (miccom P 111).\nMake : Areva 3 Each
39 4.08 Supervision relay 924 volt DC, VAX31248071BM Model 3 Each
40 4.09 ANNC 12 W facia Annunciator relay 3 Each
41 4.1 Digital Trivector meter - PTR/ CTR program (EM 6400) 3 Each
42 4.11 Breaker control switch 25 A non lockable\nMake: Kaycee 8 Each
43 4.12 Local remote switch lockable\nMake: Kaycee 8 Each
44 4.13 TNC switch\nMake: Kaycee 8 Each
45 4.14 Space heater 100 watt\nMake: Eltec 8 Each
46 4.15 Thermostate 30 to 100 Degree\nMake: Girish 6 Each
47 4.16 MCB 2 pole 10 A - 16 A.\nMake: Legrand 8 Each
48 4.17 Limit switch 1 NO+ 1 NC , 15 A 240 Volt.\nMake: Brisk 50 Each
49 4.18 22 KV HT insulator resin cast for busbar support 8 Each
50 4.19 22 KV HT, PT fuse primary 8 Each
51 4.2 HT insulation tape\nMake: 3M 30 RM
52 4.21 22 KV angle boots 8 Each Set
53 4.22 22 KV HT slive\nMake: 3M/ Reycem 15 RM
54 4.23 Indicator lamp LED type Red, Yellow, Green, Blue, White, Amber, Clear 100 Each
55 4.24 Current transformer terminal (CATD)\nMake: connect well/ Elmex 10 Each
56 4.25 AC & DC Terminal (CST/ CST10) 65 A, 415 Volt.\nMake: Connect well/ Elmex 10 Each
57 4.26 Control Terminal (CST/ CST 2.5) 36 A, 415 Volt.\nMake: Connect well /Elmex 25 Each
58 4.27 Spring charging motor 230 V AC 2 Each
59 4.28 Load manager digital 3 phase 4 wire, CL-I , CTR 200-100/ 5-5A, PTR- 22 KV/110V\nMake: Conzerv EM 6400 2 Each
60 5 Dismantling top cover alongwith conservator tank for filteration of transformer oil and after draining out transformer oil up to terminal level in situ by dismantling copper bus bars HT /LV bushing and earthing strips, replacement of LT /HT bushing and terminal rod of brass gasket, nuts, bolts and washers etc., refitting top cover and conservator tank after cleaning and filtration, removing the sludge, reconnecting HT/ LT cable/ conductor and earthing strips and filtration of tranformer oil including toping up of transformer oil by adding new transformer oil having 60 KV di-electric strength and charging /testing the transformer on load for transformer of rating upto 160 KVA capacity complete all as specified and as directed by Engr-in-charge.\nNotes: (i) Contractor should make his own arrangement of filtration plant at each transformer sites for filtration of transformer oil including provision of electric supply to the filteration.\n(ii) New transformer oil shall be measured and paid separately.\n(iii) Cost of HT /LT bushing and terminal rod wiil be measured and paid separately.\n(iv) Filtration of oil will be measured separately.\n(v) Contractor have to test di-electric strength breakdown voltage before and after filtration of oil and record of the same duly signed by Engr-in-charge and contractor to be kept on record. 3 Each Job
61 6 All as per item No.5 here-in-before but for transformer of rating 200 KVA. 3 Each Job
62 7 All as per item No.5 here-in-before but for transformer of rating 250 KVA. 3 Each Job
63 8 All as per item No.5 here-in-before but for transformer of rating 315 KVA. 3 Each Job
64 9 All as per item No.5 here-in-before but for transformer of rating 400 KVA. 2 Each Job
65 10 All as per item No.5 here-in-before but for transformer of rating 500 KVA. 3 Each Job
66 11 All as per item No.5 here-in-before but for transformer of rating 630 KVA. 2 Each Job
67 12 All as per item No.5 here-in-before but for transformer of rating 1000 KVA. 1 Each Job
68 13 Supply only the following spare parts of transfomer 22 /0.433 KV operated in ser item No. 5 to 12 complete all as specified and as directed by Engr-in-charge.
69 13.01 (a) HV Bushings
70 13.02 (i) 22 KV from up to 160 KVA 5 Each
71 13.03 (ii) 22 KV from 200 KVA to 630 KVA 3 Each
72 13.04 (iii) 22 KV 1000 KVA 1 Each
73 13.05 (b) HV terminal rod with nut bolts, caps etc
74 13.06 (i) 22 KV from up to 160 KVA 3 Each
75 13.07 (ii) 22 KV from 200 KVA to 630 KVA 4 Each
76 13.08 (iii) 22 KV 1000 KVA 1 Each
77 13.09 (c) LV Bushings
78 13.1 (i) 22 KV from up to 160 KVA 2 Each
79 13.11 (ii) 22 KV from 200 KVA to 630 KVA 4 Each
80 13.12 (iii) 22 KV 1000 KVA 1 Each
81 13.13 (d) LV terminal rod with nut bolts, caps etc
82 13.14 (i) 22 KV from up to 160 KVA 4 Each
83 13.15 (ii) 22 KV from 200 KVA to 630 KVA 5 Each
84 13.16 (iii) 22 KV 1000 KVA 1 Each
85 13.17 (e) LT Brass connectors
86 13.18 (i) 12mm 2 Each
87 13.19 (ii) 20mm 4 Each
88 13.2 (iii) 30mm 4 Each
89 13.21 (iv) 42mm 2 Each
90 14 Supply and filling new transformer oil having 60 KV di-electric strength and conforming to IS for replacement or topping up to oil level mark at the conservator complete all as specified and as directed by Engr-in-charge. 3000 Ltr
91 15 Filteration of transformer oil, in situ, to achieve di-electric strength of the oil not less than 50 KV complete all as specified and as directed by Engr-in-charge.\nNote: Contractor will submit before and after testing report of transformer oil. 14000 Ltr
92 16 Disconnecting HT /LT and earth termination connections from transformer, taking down the transformers from plinth /platform and loading into the vehicle; transporting the same to workshop for carrying out necessary repairs and back, reconnecting HT/ LT connections at site and charging the transformer on load, commissioning and testing including meggar test at site complete all as specified and as directed by Engr-in-charge. 1 Each Job
93 17 Material for rewinding of transformer core with same numbers /grade of copper enamelled conductor with same size of turns as per manufactures's specification and testing and commissioning transformers after repair complete all as specified and as directed by Engr-in-charge. 510 Kg
94 18 Material for reinsulation of copper windings (LT and HT), Class B, with electrical grade insulating kraft paper all confirming to IEC-60554-3-5 (1984) complete all as specified and as directed by Engr-in-charge. 42 Kg
95 19 Material and labour for replacement of burned or rusty core with 53 grade imported CRGO material complete all as specified and as directed by Engr-in-charge. 21 Kg
96 20 Draining out transformer oil, dismantling top cover alongwith conservator tank, taking out core assembly after disconnecting connections, rewinding with same size and type of copper conductor and number of turns and insulating material such as paper insulator sleeves, heating etc., Putting back the core assembly into the tank after removing sludge and replacement of HT and LT bushing complete with brass terminal, refixing top cover and conservator including replacement of gasket, nuts, bolts and washers filling new transformer oil having 60 KV di-electric strength and carring out type tests as per IS 2026 in presence of Engr-in-charge for the following capacity complete all as specified and as directed by Engr-in-charge.\nNotes: (i) New transformer oil and its filling shall be measured and paid separately under relevant items of schedule.\n(ii) Cost of rewinding material, insulation material and spares of transformer shall be measured and paid separately under relevant item of Schedule.\n(iii) Replacement of spares will be on required basis.
97 20.01 75 to 160 KVA 1 Each Job
98 20.02 200 to 315 KVA 1 Each Job
99 20.03 400 to 1000 KVA 1 Each Job
100 21 Disconnecting HT/ LT and earth termination connections from trolley mounted transformer (500 KVA capacity) and towing the same to a location, within 5 KMs including Material and labour for making of HT/ LT and earth termination connections of the trolley mounted transformer to the existing electric distribution system in indoor /outdoor substation complete all as specified and as directed by Engr-in-charge.\nNotes: (i) Trolley mounted transformer will be issued to contractor by MES however Contractor has to make his own arrangements of towing vehicle.\n(ii) The job also includes disconnecting of HT/ LT and earth termination connections of Trolley Mounted Transformer and towing the same to a location as directed by Engr-in-Charge. 1 Each Job
101 22 Testing of transformers of various capcities installed at various locations at Naval Station Karanja by performing following tests complete all as specified and as directed by Engr-in-charge.\n(a) IR Value on LV & HV side using 500 V and 5 KV megger respectively.\n(b) Ratio on all the taps.\n(c) Magnetic balance tests on LV & HV.\n(d) Vector group.\n(e) Magnetizing current.\n(f) Winding Resistance Test on HV & LV terminals.\nNotes: (i) Contractor should make his own arragement of testing equipments and electric supply so required.\n(ii) A detailed test report should be submitted to Engr-in-Charge. 25 Each
102 23 Excavation in trenches not exc 1.5m wide and not exc 1.5m depth and getting out in soft /loose soil including taking out faulty cable/ cable, cable covers and GI pipe complete all as specified and as directed by Engr-in-charge. 36.45 Cum
103 24 Returning filling in including spreading levelling watering and well ramming in layers not exc 25cms complete all as specified and as directed by Engr-in-charge. 21.51 Cum
104 25 Removing excavated materials not exc 50m and depositing where directed at a level not exc 1.5m above the starting point complete all as specified and as directed by Engr-in-charge. 14.94 Cum
105 26 Material and labour for dry river sand as sand cushioning for protection of UG cable including punning of sand in layers complete all as specified and as directed by Engr-in-charge.\nNote: Only punned thickness shall be measured for payment. 10.94 Cum
106 27 Supply and laying un-reinforced precast concrete cable cover class LV type 1, flat size 250x150x40mm complete all as specified and as directed by Engr-in-charge. 900 Each
107 28 Dismantling LT cable of following sizes from cable end box of transformer and main switch/ MCCB/ ACB of LT panel, taking out from trench/ duct complete all as specified and as directed by Engr-in-charge.
108 28.01 3.5 core 185 sqmm 150 RM
109 28.02 3.5 core 240/ 300 sqmm 150 RM
110 28.03 3.5 core 400 sqmm 150 RM
111 29 Supply and fixing, jointing, connecting and testing in trenches XLPE /PVC insulated PVC sheathed cable heavy duty 1100 volts grade, aluminium conductor in trenches/ ducts of following sizes complete all as specified and as directed by Engr-in-charge.
112 29.01 3.5 core 185 sqmm 150 RM
113 29.02 3.5 core 300 sqmm 150 RM
114 29.03 3.5 core 400 sqmm 150 RM
115 30 Supply and fix in repairs 1.1 KV straight through joint kit 3.5 core 150 sqmm to 185 sqmm complete all as specified and as directed by Engr-in-charge.\nMake: 3M/ M Seal/ Raychem 1 Each
116 31 Supply and fix in repairs 1.1 KV straight through joint kit 3.5 core 240 sqmm to 300 sqmm complete all as specified and as directed by Engr-in-charge.\nMake: 3M/ M Seal/ Raychem 1 Each
117 32 Supply and fix in repairs 1.1 KV straight through joint kit 3.5 core 400 sqmm complete all as specified and as directed by Engr-in-charge.\nMake: 3M/ M Seal/ Raychem 1 Each
118 33 Supply and fix in repairs heat shirnk right angled boots for XLPE 22 KV 120 sqmm cable including dismantling of HT cable from HT side of Transformer / HT breakers complete all as specified and as directed by Engr-in-charge. 6 Each set
119 34 Material and labour for heat shrinkable cable end termination joint including jointing kit outdoor type suitable for earthed 3 core 95 /120 sqmm HT 22 KV XLPE aluminium conductor cable and HV test after jointing and connecting up complete all as specified and as directed by Engr-in-charge.\nMake: Raychem/ XICON/ M-Seal/ Denson 2 Each
120 35 Material and labour for heat shrinkable straight through jointing kit with all necessary jointing material suitable for HT 22 KV XLPE 3 core 95/ 120 sqmm aluminium conductor cable complete all as specified and as directed by Engr-in-charge.\nMake: Raychem/ XICON/ M-Seal /Denson 2 Each
121 36 Supply and fix in repairs breather assembly with silica gel suitable in situ for transformer of any rating complete all as specified and as directed by Engr-in-charge. 20 Each
122 37 Supply and fix in repairs dial type temprature guage 100mm dia with dual calibration in degree celcius and degree fahrenheit, range 0 to 100 C and equivalent degree fahrenheit complete with capillary tube and sensor suitable for transformer of any rating complete all as specified and as directed by Engr-in-charge. 10 Each
123 38 Material and labour for replacement of self-indicating Orange to Green silica gel granules from transformer breather assembly complete all as specified and as directed by Engr-in-charge. 5 KG
124 39 Material and labour for preparation of old painted surfaces of 100 KVA transformer with scrapers, any number of coats, any width or girth and applying two coats of synthetic enamel paint by spray painting including writing 5mm /MES numbers complete all as specified and as directed by Engr-in-charge. 4 Each Job
125 40 All as per item No. 39 here-in-before but 160 KVA transformer 4 Each Job
126 41 All as per item No. 39 here-in-before but 200 /250 KVA transformer 4 Each Job
127 42 All as per item No. 39 here-in-before but 315 KVA transformer 4 Each Job
128 43 All as per item No. 39 here-in-before but 400 /500 KVA transformer 4 Each Job
129 44 All as per item No. 39 here-in-before but 630 KVA transformer 2 Each Job
130 45 All as per item No. 39 here-in-before but 1000 KVA transformer 1 Each Job
131 46 Supply and fix in repairs end termination box HV side with cover made of 3mm thick MS sheets including fibre board insulation sheets and including nuts, bolts and washer including painting of steel surfaces with two coats of red oxide zinc chrome primer complete all as specified and as directed by Engr-in-charge. 2 Each
132 47 All as per item No. 46 here-in-before but for LV side. 2 Each
133 48 Material and labour for earthing complete with GI earth plate electrode of size 600x600x6mm thick burried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below the normal ground level connected with GI strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanished iron steel including necessary excavation and earth work in any type of soil, removing surplus soil to a distance not exc 50m, with and including PCC chamber in PCC 1:2:4, type B1 (Using 20mm graded stone aggregate), mild steel angle iron frame made out of MS angle iron of size 40x40x6mm thick duly painted with two coats of synthetic enamel paint over one coat of red oxide zinc chrome primer hinged with and including 6mm thick CI cover with handle, watering arrangement with funnel internally secured with wire mesh with 40mm dia medium grade pipe for watering 40mm dia light grade, GI pipe for lead protection in and including alternate layers of charcoal dust and common salt complete all as shown in electrical plate No. 03 and connected to earthing test point and indicated including testing on completion including retrieving old GI earth plate, CI cover, GI pipes, angle iron frame from existing earthing complete all as specified and as directed by Engr-in-charge. 16 Each
134 49 Material and labour for replacement old rusted busbar of 3mm thick MS sheet to be used in cable ducts from transfomer to breaker switch complete all as specified and as directed by Engr-in-charge.\nLocation: MRF Sub station 470 Kg
135 50 Supply and fix for earth continuity conductor or main earthing lead fixed to wall on batten or fixed to pole GI strip 32x6mm complete all as specified and as directed by Engr-in-charge. 130 RM
Disclaimer :