Military Engineer Services-MES has published Provision Of Smoke Detector Fire Alarm System In Repair Labs And Stores Under Ge Af Borjhar 2Nd Call. Submission Date for this Tender is 23-08-2021. Smoke Detectors Tenders in Borjhar Assam. Bidders can get complete Tender details and download the document.




Tender Notice

27972831
Corrigendum : Provision Of Smoke Detector Fire Alarm System In Repair Labs And Stores Under Ge Af Borjhar 2Nd Call
Open Tender
Indian
Assam
Borjhar
23-08-2021

Tender Details

Provision Of Smoke Detector Fire Alarm System In Repair Labs And Stores Under Ge Af Borjhar 2Nd Call

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 14-Jun-2021 Corrigendum to dates1 Date 07-07-2021
2 30-Jun-2021 Corrigendum to dates2 Date 22-07-2021
3 15-Jul-2021 Corrigendum to dates3 Date 07-08-2021
4 28-Jul-2021 Corrigendum to BOQ BOQ 07-08-2021
5 28-Jul-2021 Amendment in Tender documents Other 07-08-2021
6 29-Jul-2021 Corrigendum to dates4 Date 16-08-2021
7 16-Aug-2021 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 23-08-2021

Key Value

Document Fees
INR 1000 /-
EMD
INR 119500.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: PROVN OF SMOKE DETECTOR & FIRE ALARM SYSTEM IN REPAIR LABS AND STORES UNDER GE (AF) BORJHAR(2ND CALL)
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply, install, commissioning and testing fire alarm control panel complying with BS EN 54 single loop panel of capacity from 99 detectors & 99 modules upto 200 detector and modules with non expandable, 2 x 16 character LCD Display, Inbuilt Fire relay & Fault relay complete all as specified and as directed. 6 Each
2 2 Supply, install, commissioning and testing indoor detector complying with and type certified to EN-45 Addressable type smoke detector photoelectric/optical with base with self built intelegence as per IS-2175 Addressable type multi censor detector heat & smoke combination complete all as specified and as directed. 224 Each
3 3 Supply, install, commissioning and testing Addressable Manual call point resettable type complete all as specified and as directed. 18 Each
4 4 Supply, install, commissioning and testing annunciating device remote response indicator complete all as specified and as directed. 45 Each
5 5 Supply, install, commissioning and testing fire alarm sounder/siren electrinic type horizontal single stage continuous normal operation for atleast 50mm with sound level 65 db to 129 db measured at 1.5 m with sound with sound output variation of +5 db 1000 m range complete all as specified and as directed. 18 Each
6 6 Supply, install, commissioning and testing submain wiring single core 1.5 Sqmm (Nominal area) multistranded FRLS PVC insulated unsheathed copper conductor cable 1100 volts grade, drawn through in and including surface rigid steel Conduit of size 20mm (ISI Marked) complete all as specified and as directed.\nNote: Two runs of 1.5 Sqmm cable shall be measured as one run length and conduit will be measured and paid separately. 1610 RM
7 7 Supply and fix PVC insulated unarmoured copper cable of size 1.5 sqmm 2 core complete all as specified and as directed. 1200 RM
8 8 Supply and fix GI pipe light grade, 20 mm dia including necessary fittings, fixing clamp to wall, for protection of cable for passing through walls, road crossing etc. complete all as specified and as directed. 30 RM
9 9 Supply and fix Steel rigid conduit, welded of size 20 mm dia, fixed to wall, roof with all accessories such as tees, bends, elbows, reducer, bell mouth tube ends and fixing accessories complete all as specified and as directed. 1610 RM
10 10 Supply, install, commissioning and testing indoor detector complying with and type certified to EN-45 Addressable type flame detectors with UV/IR detection capacity (add up cost of module to be a complete set, the type of module shall be relay type module) with self built intelegence as per IS-11360 complete all as specified and as directed. 6 Each
11 11 Supply, install, commissioning and testing fire alarm monitoring control panel complying with character LCD display, inbuilt fire relay & fault relay complete with all accessories complete all as specified and as directed. 1 Each
12 12 Supply, install, commissioning and testing amplifieres suitable for 100 Watts, 230 VAC, 50 HZ complete all as specified and as directed. Make : Ahuja/Piyano/Philips 6 Each
13 13 Supply, fixing and testing MCB DB , SPN 4 way, double door with 200 Amp rated bus bar, horizontal type IP-43 including earth and neutral link ,complete with fixing accessories complete all as specified and as directed.\n 8 Each
14 14 Supply and fixing MCB SPN, 240 Volts, 'C' series, breaking capacity 10 KA of rating 6-40 Amps complete all as specified and as directed. 8 Each
15 15 Supply and fixing MCB SP 240 Volts, 'C' series, breaking capacity 10 KA of rating 6-40 Amps complete all as specified and as directed. 8 Each
16 16 Boring of holes under road, pavement, hard standing by trenchless tecnology using ultra sounding technique with suitable machine including providing HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and as directed.. 60 RM
17 17 Excavation in trenches n.exc. 1.5 m wide and n.exc. 1.5m in depth for foundation etc or for shafts, wells, manholes, pier holes, etc. n exc 10 sqm on plan and getting out in in soft/loose soil complete all as specified and directed 50 Cum
18 18 Material and Labour for dry sand cushioning with coarse sand in trenches for protection of underground electric cable 8cm deep before laying the cable and 15cm thick after laying & stretching of cable complete all as specified and as directed. (Note:- Only punned thickness shall be measured and paid). 30 Cum
19 19 Material and labour for sub class 'B' bricks well burnt old size 230x115x75mm laid dry flat for protection of cable complete all as specified and as directed by Engr-in-charge. 2000 Each
20 20 Removing surplus excavated material (soil) to a distance not exc. 50 m and depositing where directed at a level n.exc. 1.5 m above the starting point complete all as specified and directed. 32 Cum
21 21 Returning, filling in, including spreading, leveling, watering and well ramming in layers n.exc 25 cm thick in soils complete all as specified and directed. 18 Cum
22 22 Supply, laying, jointing and testing XLPE insulated, PVC bedded, Galvanized steel strip or wire armoured underground heavy duty electric power cable with stranded aluminum conductor 1100 volts grade, laid in trenches / duct / on pole including all necessary fixing arrangement such as lugs, glands end termination etc of cross sectional area 6 Sqmm 3 core complete all as specified and as directed. 300 RM
23 23 Supply, fixing, commissioning and testing loud speaker 10 Watt, 230 Volt, 50 HZ of study design weather proof type with re-entrant horn type for operating under rough condition complete all as specified and as directed. Make : Ahuja/Piyano/Philips 6 Each
24 24 Earthing complete with copper earth plate electrode of size 30cm x 30cm x 3mm buried directly in ground vertically at a depth not less than 2.25 m below normal ground level with top edge of earth plate at a depth not less than 1.5 m below normal ground level, sourrounded from all sides by 15 cm thick packed layer of charcoal dust and common salt filled in alternate layers etc and connected to and including 25 x 3 mm copper strip upto 7.5 m by means of bolts, nuts, check nuts and washers made of galvanised iron and protected by light grade 40 mm bore GI pipe connected to main control board and GI pipe medium grade 15 mm bore for watering and including funnel, wire mesh etc including providing RCC pit cover flush to earth pit 50 mm thick reinforced with 8 mm TMT bar 100 mm C/C and PCC chamber pit with PCC (1:3:6) type C1 (using 20 mm graded crushed stone aggregate) including excavation and earthwork, disposal of surplus soil to a distance not exceeding 50 m and testing after completion all as specified and shown on plate No 3 of SSR Part-I complete all as specified and directed. 6 Each