Supply And Installation Of Electrical Materials, NAD Aluva-Kerala

Kerala State Electronics Development Corporation Limited-KELTRON has published Supply And Installation Of Electrical Materials. Submission Date for this Tender is 14-05-2021. Electrical Products Tenders in NAD Aluva Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

27796021
Supply And Installation Of Electrical Materials
Open Tender
Indian
Kerala
NAD Aluva
14-05-2021

Tender Details

Supply And Installation Of Electrical Materials.- 2 1.01 Charges Towards Supply Of Material Required For Installation, Testing And Commissioning Of 1250Kva Solar Inverter Duty Transformer , Including All Item Etc, All As Per The Direction Of Engineer In Charge & Iec Standards.Installation As Per Latest Cea / Cei / Mes Guidelines.Supply Of ( Transformers Under The Scope Of Keltron ) Cost Inclusive Of Providing Fencing Etc Extra As Required. Item1 2 Nos 3 1.02 Charges Towards Supply Of Material Required For Installation , Testing And Commissioning Of 100Kva Stepdown Transformer , Including All Item Etc, All As Per The Direction Of Engineer In Charge & Iec Standards.Installation As Per Latest Cea / Cei / Mes Guidelines.Supply Of ( Transformers Under The Scope Of Keltron ) Cost Inclusive Of Providing Fencing Etc Extra As Required. Item2 1 No 4 1.03 Charges Towards Supply Of Material Required For Laying , Termination And Commissioning Of 3 Core X 240Sq Mm Xlpe Insulated, Screened Pvc Bedded Galvanised Steel Strip Or Wire Armoured Heavy Duty With Alumininum Conductor , 11 Kv ( E ) Ht Cable As Per Is 7098 ( Part Ii ) 1985. For Connecting Ht Transformer To Ht Panel To Meter Panel To Kseb Grid Including Supply Of Cable.Cost Inclusive Of Materials For Termination Of Cable, Checking Tightness Of Cable, Testing Sample Of Cable And Whole Length , Coordinating Mes With Sample Evaluavation And Testing As Per Mes Standards Etc As Applicable .Sand Cushioning With Dry River Sand Complete All As Specified And As Directed By Mes. Item3 350 Rmeter 5 1.04 Charges Towards Supply Of Material Required For Laying , Termination And Commissioning Of 3 Core X 95Sq Mm Xlpe Insulated, Screened Pvc Bedded Galvanised Steel Strip Or Wire Aemoured Heavy Duty With Alumininum Conductor , 11 Kv ( E ) Ht Cable As Per Is 7098 ( Part Ii ) 1985. For Connecting Ht Transformer To Ht Panel Including Supply Of Cable.Cost Inclusive Of Materials Required For Termination Of Cable. ( Min 2 Nos Of Ht Kit ) .Checking Tightness Of Cable, Testing Sample Of Cable And Whole Length , Coordinating Mes With Sample Evaluavation And Testing As Per Mes Standards Etc As Applicable .Sand Cushioning With Dry River Sand Complete All As Specified And As Directed By Mes. Item4 30 Rmeter 6 1.05 Charges Towards Supply Of Material Required For Sand Cushioning With Dry River Sand Complete All As Directed As Per Mes Standards Including Exacavation Work Required Lt Cable And Ht Cable Work. Item5 500 Cubic Nmeter 7 1.06 Charges Towards Supply Of Material Required For Installation Of Ht Interface Meter ( Abt ) Including Meter Installed In Totally Enclosed.Fully Interlock , Metal Clad Power Coated At Mes Sub Station-1 & Providing Suitable Capacity ( As Per Cmd ) Of Cts, Pts, Relay, Cable For Interconnection, Ht Insulater Etc All As Per The Specification & Site Condition. As Per Latest Norms Of Ksebl , Testing Of Cts, Pts And Abt Meter Inclusive, Cost Inclusive Of Any Additional Work Required For Completion Of This Work As Per Ksebl / Cei / Mes Direction. Item6 1 Set 8 1.07 Charges Towards Supply Of Ht 11Kv Grid Panel For Power Evacuation And Grid Interconnection Systems At Mrs Nad Gate Complete With Breakers, Cts, Pts, Vcb, Metering Panels Relays , Tod Meter ( Ht Check Meter ) Etc All As Per Design Parameter With Totally Enclosed Fully Interlocked Metal Clad Power Coated Enclosure Complete Modification / Extension Of Existing Ht Panel At Nad Shall Be Obtained From Prior To Install.Ct / Pt Of Metering Panel Shall Be Approved Make Of Ksebl And All As Per Guide Lines Given In The Kserc Notification Complete All As Per Specified And Charges Toward Materials Rquired For Imstallation Testing And Commisioning Of Above Panel As Per Mes / Cea / Cei / Ksebl Standards. Item7 1 Set 9 1.08 Charges Towards Supply Of Addressable Type Fire Alarm Control Panel Complying With Bs En 54 Single Loop Panel Of Capacity From 99 Detectors & 99 Modules Upto 200 Detector. Item8 1 Set 10 1.09 Charges Towards Supply Of Detectors Complying With And Type Certified To En-45 Addressable Type Multisensor Detector With Heat And Smoke Combination Photoelectric / Optical With Base With Self Built Intelligence As Per Is: 11360 Item9 10 Each 11 1.1 Charges Towards Supply Of Addressable Control Module Item10 3 Each 12 1.11 Charges Towards Supply Of Addressable Monitor Module Item11 3 Each 13 1.12 Charges Towards Supply Of Short Circuit Isolators Item12 3 Each 14 1.13 Charges Towards Supply Of Addressable Manual Call Point Resettable Type Item13 3 Each 15 1.14 Charges Towards Supply Of Addressable Electronic Sounder Cum Strobe Complete All As Specified And As Directed. Item14 2 Each 16 1.15 Charges Towards Supply Of Frls Armoured Copper Cable 2 Core 1.5 Sqmm Item15 250 Rmeter 17 1.16 Charges Towards Supply Of Battery Operated Led Display Lights ( Exit Signage ) Wall Mounted With Battery Backup Of 5 Hrs For Fire Exit All As Per Cat No : Lssr5w Of Cg Or Its Equivalent Make From List Of Makes. Item16 3 Each 18 1.17 Charges Towards Supply Of Duly Painted Ms Pedestal Stand For Suspending Fire Buckets As Per The Specification. Item17 1 Each 19 1.18 Charges Towards Supply Of Red Painted Ms Fire Bucket Of 13 Ltrs Capacity Of Fire Approved Quality, Filled With Sand As Per The Specification & Standards. Item18 2 Each 20 1.19 Charges Towards Supply Of Foam Type Extinguisher Hand 9 Kg All As Per The Specification & Standards Item19 2 Each 21 1.2 Charges Towards Supply Of Dcp Type ( Abc ) 10 Kg Designed / Tested Is 15683 With Safety Release Valve, Nrv And Ce Approved Valve.Dry Powder Is 14609 With Its Standard Accessories As Per Specification & Standards Item20 3 Each 22 1.21 Charges Towards Supply Of Co2 Type Hand 9 Kg With Wheel As Per Is 2878 Complete With Hose, Screw Valve, Co2 Gas Is 1522, Cylinder Is 7285, Valve Is 3224.Tested At 250Kg / Cm2 All As Per The Specification & Standards. Item21 2 Each 23 1.22 Charges Towards Supply Of Material Required For Earthing Complete With Galvanised Earth Plate Electrode 600X600x6 Mm Thick Buried Directly In Ground Vertically ( Earth Pit Not Less Than 2.25 Mtr Deep Below Normal Ground Level ) With Top Edge Of Plate Note Less Than 1.5Mtr Below Ground Level Connected To Including Gi Strip 32X6mm Size Protected With G I Medium Grade Pipe 40Mm Dia For Earth Electrode Up To Test Point Or Nup To 7.5 Mtr Whichever Is Less By Means Of Gi Nuts, Bolts, Check Nuts And Washer. Funnel, With Necessary Charcoal, Salt Etc And Material Required For Pcc Pit And Rcc Cover ( 1:2:4 Type B1 ) And Funnel With Necessary Charcoal, Salt Etc, Complete All As Per Electrical Plate No.3 Of Ssr Part-1 Including Testing For Required Value. Item22 21 Each 24 1.23 Charges Towards Supply Of 32 X 6 Mm Thick Gi Strip As Per The Specification & Standards. Item23 150 Rmeter 25 1.24 Earthing Complete With Copper Earth Plate Electrode 600X600x3.15 Mm Thick Buried Directly In Ground Vertically ( Earth Pit Not Less Than 2.25 Mtr Deep Below Normal Ground Level ) With Top Edge Of Plate Not Less Than 1.5 Mtr Below Normal Ground Level Connected To And Including Copper Strip 20X3 Mm Size Protected With G I Medium Grade Pipe 40Mm Dia For Earth Electrode Up To Test Point Or Up To 7.5 Mtr Whichever Is Less By Means Of Copper Nuts, Bolts, Check Nuts And Washers Including Earth Work, Excavation, Pcc Pit And Rcc Cover ( 1:2:4 Type B1 ) And Funnel, With Necessary Charcoal, Salt Etc;Complete All As Per Electrical Plate No.3 Of Ssr Part - I Including Testing For Required Value Complete All As Specified And Directed ( For Scada System ) Item24 4 Each 26 1.25 Charges Towards Supply Of Test Terminal Point Block Made Of Gun Metal Or Phosporous Bronze Of Size 75X75x25 Mm Including 3 Nos Of 8 Mm Dia Screws As Per The Specification & Standards. Item25 10 Nos 27 1.26 Charges Towards Supply Of Danger Notice Plate Of 1.6Mm Thick Mild Steel, Vitreous Enaneled White With Letters, Figures And Conventional Skull And Bones In Signal Red Colour And Fixed With Ms Clamps, Bolts And Nuts Of Approved Size For Ht , 25X20cm Complete All As Per The Specification & Standards Item26 10 Nos 28 1.27 Charges Towards Supply Of Synthetic Rubber Mat Of 2Mx1mx10mm For 420V As Per The Specification & Cea / Cei / Ksebl / Mes Standards. Item27 3 Each 29 1.28 Charges Towards Supply Of Synthetic Rubber Mat Of 2Mx1mx19mm For 11Kv As Per The Specification & Cea / Cei / Ksebl / Mes Standards. Item28 4 Each 30 1.29 Charges Towards Supply Of Cable Joining Kit For 11Kv ( Earthed ) Grade Cable For Indoor Termination Heat Shrink Type Joint Complete With Joining Material And Accessories Suitable For 3 Core Xlpe Armoured Aluminium Conductor Cable Of Size 240 Sqmm To 300 Sqmm Complete All As Per The Specification & Ksei Standards. Item29 6 Nos 31 1.3 Charges Towards Supply Of Cable Joining Kit For 11Kv ( Earthed ) Grade Cable For Indoor Termination Heat Shrink Type Joint Complete With Joining Material And Accessories Suitable For 3 Core Xlpe Armoured Aluminium Conductor Cable Of Size 70 Sqmm To 95 Sqmm Complete All As Per The Specification & Ksei Standards. Item30 8 Each 32 1.31 Charges Towards Supply Of Cable Joining Kit For 11 Kv ( Earthed ) Grade Cable For Indoor End Termination Heat Shrink Type Joint Complete With Joining Material And Accessories Suitable For 3 Core Xlpe Armoured Aluminium Conductor Cable Of Size 70 Sqmm To 95 Sqmm Item31 2 Each 33 1.32 Charges Towards Supply Of Non Pressure Np-2 Class Rcc Hume Pipe 150Mm Dia With Collar Jointed With Stiff Mixture Of Cm In 1:2 Including Excavation In Earth Work, Pcc Item32 30 Rmeter 34 1.33 Charges Towards Supply Of Non Pressure Np-2 Class Rcc Hume Pipe 100Mm Dia With Collar Jointed With Stiff Mixture Of Cm In 1:2 Including Excavation In Earth Work, Pcc Item33 50 Rmeter 35 1.34 Charges Towards Supply Of 100 Mm Dia Gi Pipe Light Grade For Cable Protection As Per N The Specification & Standards. Item34 50 Rmeter 36 1.35 Charges Towards Supply Of 50 Mm Dia Gi Pipe Light Grade For Cable Protection As Per N The Specification & Standards. Item35 50 Rmeter 37 1.36 Charges Towards Supply Of Digital Earth Resistance Tester Cambridge Instruments Det-2000 Item36 1 Each 38 1.37 Charges Towards Supply Of Digital Multimeter ( Make Shall Be Of Any Isi Marked ) Item37 1 Each 39 1.38 Charges Towards Supply Of Ac-Dc Clamp Meter Amp Range 1000Dc, 800Ac ( Make Shall Be Of Any Isi Marked ) Item38 1 Each 40 1.39 Charges Towards Supply Of Digital Megger- Lv 500 V ( Make Shall Be Of Any Isi Marked ) Item39 2 Each 41 1.4 Charges Towards Supply Of Digital Thermometer ( Wall Hanging ) ( Make Shall Be Of Any Isi Marked ) Item40 2 Each 42 1.41 Charges Towards Supply Of Digital Megger – Hv 10Kv ( Make Shall Be Of Any Isi Marked ) Item41 1 Each 43 1.42 Charges Towards Supply Of Crimping Tool With Dye Range 50-400Sq-Mm Cable, Mechanical Gear & Hydraulic Operated Power, Hand Operated ( Make Shall Be Of Any Isi Marked ) Item42 1 Each 44 1.43 Charges Towards Supply Of Crimping Tool Up To 6 Sq-Mm Cable ( Make Shall Be Of Any Isi Marked ) Item43 1 Each 45 1.44 Charges Towards Supply Of Pcc Cable Covers Class Hv, Type 1, Flat, Size 300Mm X 180Mm X 40Mm Item44 5000 Each 46 1.45 Charges Towards Supply Of Pcc Cable Covers Class Lv, Type 1, Flat, Size 250Mm X 150Mm X 40Mm Item45 700 Each 47 1.46 Charges Towards Supply Of Cable Route Indicator 15Cm Dia Made Out Of Cast Aluminium Duly Marked With Size And Type Of Cable Fixed On Isa 40X40x6mm Angle Iron Support Embedded Including In Pcc 1:2:4 Type B1 ( 300X300x400mm ) And Steel Surface Painted With Two Coats Of Anti Corrosive Paint Over A Coat Of Red Oxide Primer Including Necessary Earth Work Item46 40 Each 48 1.47 Charges Towards Supply Of Outdoor Ms Base Frame Mounted Cubical Type Factory Made Lt Panel Board Suitable For 415V 3 Phase 4 Wire, 50Hz Non-Metalic Kiosk Double Door With The Required Provision For 3 Switch Gears And Control Gears Along With The Approved Make. Enclosed In A Modular / Combinable Thermoplastic Polycarbonate Panel Enclosure Which Should Be Shock Proof, Ip65 ( Weather Proof ) , Rust Proof, Dust Proof, Water Proof, Corrosion Proof Having Internally Embadded Gasket On The Lid And Cable Entry Knockouts On All Sides Or Using Cable Entry Flanges Of Size 300 X 450 X 170Mm Required Of The Lt Panel Complete Fabrication Shall Be Painted As Per Specification. Lt Panel Board Shall Be Complete With All Standard Accessories Including Selector Switches, Phase Indicating Lamps Control Fuse Unit, Mv Danger Notice Plate Numbered / Lettered And With Comprising The Following. Make: Hensel Or Equivalent Make In List Of Manufactures Item47 1 Job 49 1.48 Sl.Item No.1.47 Contd / .. Incoming: Mccb 160 A, 4 Pole, 25Ka-1 No. Including Cts, Digital Ammeter, Ass, Digital Volt Meter, Vss, Phase Indicating Lamps & Control Fuses / Mcbs Etc.. Nbus Bar: One Set Of Tp&N 300A, Aluminium Bus Bar E 91 Grade, 1100 V, Grade Duly Covered With Heat Shrinkable Sleeves Colour Coded Duly Fixed On Moulded Brackets-1 Set. Noutgoing: Separate Cubical Chamber With A Cable Alley Not Less Than 300 Mm Width For Installation / Connecting The Following Switch Gear: N ( I ) Mccb 63A, 4 Pole, 25Ka - 1 Nos N ( Ii ) Mcb Tp&N 32A, 16Ka - 2 Nos N ( Iii ) Mcb Spn 32A, 16 Ka - 3 Nos Item48 1 Job 50 1.49 Charges Towards Supply Of Materials For Artistic Painting In Black Letters With Yellow Background For Solar Array Structures, Smbs, Dc Cable In / Out, Earth Chambers, Pcus, Transformers, Ups, Dbs Etc. Item49 1 Job 51 1.5 Charges Towards Supply Of Materials For Lightening Protection System Item50 1 Job 52 1.51 Charges Towards Supply Of Materials For Soakage Pit Of Size 1.2M Dia , 3.0M Item51 3 Each 53 2 Labour Charges For Installation Of Materials For 02Mw Solar Power Plant Project At Nad, Aluva Item52 1 Each 54 2.01 Labour Charges Towards Installation, Testing And Commissioning Of 1250Kva Solar Inverter Duty Transformer , Including All Item Etc, All As Per The Direction Of Engineer In Charge & Iec Standards.Installation As Per Latest Cea / Cei / Mes Guidelines.Supply Of ( Transformers Under The Scope Of Keltron ) Cost Inclusive Of Providing Fencing Etc Extra As Required. Item53 2 Each 55 2.02 Labour Charges Towards Installation, Testing And Commissioning Of 100Kva Stepdown Transformer , Including All Item Etc, All As Per The Direction Of Engineer In Charge & Iec Standards.Installation As Per Latest Cea / Cei / Mes Guidelines.Supply Of ( Transformers Under The Scope Of Keltron ) Cost Inclusive Of Providing Fencing Etc Extra As Required. Item54 1 No 56 2.03 Labour Charges Towards Installation, Termination And Commissioning Of 3 Core X 240Sq Mm Xlpe Insulated, Screened Pvc Bedded Galvanised Steel Strip Or Wire Armoured Heavy Duty With Alumininum Conductor , 11 Kv ( E ) Ht Cable As Per Is 7098 ( Part Ii ) 1985. For Connecting Ht Transformer To Ht Panel To Meter Panel To Kseb Grid Including Supply Of Cable.Cost Inclusive Of Materials For Termination Of Cable, Checking Tightness Of Cable, Testing Sample Of Cable And Whole Length , Coordinating Mes With Sample Evaluavation And Testing As Per Mes Standards Etc As Applicable .Sand Cushioning With Dry River Sand Complete All As Specified And As Directed By Mes. Item55 350 Rmeter 57 2.04 Labour Charges Towards Installation, Termination And Commissioning Of 3 Core X 95Sq Mm Xlpe Insulated, Screened Pvc Bedded Galvanised Steel Strip Or Wire Aemoured Heavy Duty With Alumininum Conductor , 11 Kv ( E ) Ht Cable As Per Is 7098 ( Part Ii ) 1985. For Connecting Ht Transformer To Ht Panel Including Supply Of Cable.Cost Inclusive Of Materials Required For Termination Of Cable. ( Min 2 Nos Of Ht Kit ) .Checking Tightness Of Cable, Testing Sample Of Cable And Whole Length , Coordinating Mes With Sample Evaluavation And Testing As Per Mes Standards Etc As Applicable .Sand Cushioning With Dry River Sand Complete All As Specified And As Directed By Mes. Item56 30 Rmeter 58 2.05 Labour Charges Towards Sand Cushioning With Dry River Sand Complete All As Directed As Per Mes Standards Including Exacavation Work Required Lt Cable And Ht Cable Work. Item57 500 Cubic Nmeter 59 2.06 Labour Charges Towards Installation Of Ht Interface Meter ( Abt ) Including Meter Installed In Totally Enclosed.Fully Interlock , Metal Clad Power Coated At Mes Sub Station-1 & Providing Suitable Capacity ( As Per Cmd ) Of Cts, Pts, Relay, Cable For Interconnection, Ht Insulater Etc All As Per The Specification & Site Condition. As Per Latest Norms Of Ksebl , Testing Of Cts, Pts And Abt Meter Inclusive, Cost Inclusive Of Any Additional Work Required For Completion Of This Work As Per Ksebl / Cei / Mes Direction. Item58 1 Set 60 2.07 Labour Charges Towards Installation Of Ht 11Kv Grid Panel For Power Evacuation And Grid Interconnection Systems At Mrs Nad Gate Complete With Breakers, Cts, Pts, Vcb, Metering Panels Relays , Tod Meter ( Ht Check Meter ) Etc All As Per Design Parameter With Totally Enclosed Fully Interlocked Metal Clad Power Coated Enclosure Complete Modification / Extension Of Existing Ht Panel At Nad Shall Be Obtained From Prior To Install.Ct / Pt Of Metering Panel Shall Be Approved Make Of Ksebl And All As Per Guide Lines Given In The Kserc Notification Complete All As Per Specified And Charges Toward Materials Rquired For Imstallation Testing And Commisioning Of Above Panel As Per Mes / Cea / Cei / Ksebl Standards. Item59 1 Set 61 2.08 Labour Charges Towards Installation Of Addressable Type Fire Alarm Control Panel Complying With Bs En 54 Single Loop Panel Of Capacity From 99 Detectors & 99 Modules Upto 200 Detector. Item60 1 Set 62 2.09 Labour Charges Towards Installation Of Detectors Complying With And Type Certified To En-45 Addressable Type Multisensor Detector With Heat And Smoke Combination Photoelectric / Optical With Base With Self Built Intelligence As Per Is: 11360 Item61 10 Each 63 2.1 Labour Charges Towards Installation Of Addressable Control Module Item62 3 Each 64 2.11 Labour Charges Towards Installation Of Addressable Monitor Module Item63 3 Each 65 2.12 Labour Charges Towards Installation Of Short Circuit Isolators Item64 3 Each 66 2.13 Labour Charges Towards Installation Of Addressable Manual Call Point Resettable Type Item65 3 Each 67 2.14 Labour Charges Towards Installation Of Addressable Electronic Sounder Cum Strobe Complete All As Specified And As Directed. Item66 2 Each 68 2.15 Labour Charges Towards Installation Of Frls Armoured Copper Cable 2 Core 1.5 Sqmm Item67 250 Rmeter 69 2.16 Labour Charges Towards Installation Of Battery Operated Led Display Lights ( Exit Signage ) Wall Mounted With Battery Backup Of 5 Hrs For Fire Exit All As Per Cat No : Lssr5w Of Cg Or Its Equivalent Make From List Of Makes. Item68 3 Each 70 2.17 Labour Charges Towards Installation Of Duly Painted Ms Pedestal Stand For Suspending Fire Buckets As Per The Specification. Item69 1 Each 71 2.18 Labour Charges Towards Installation Of Red Painted Ms Fire Bucket Of 13 Ltrs Capacity Of Fire Approved Quality, Filled With Sand As Per The Specification & Standards. Item70 2 Each 72 2.19 Labour Charges Towards Installation Of Foam Type Extinguisher Hand 9 Kg All As Per The Specification & Standards Item71 2 Each 73 2.2 Labour Charges Towards Installation Of Dcp Type ( Abc ) 10 Kg Designed / Tested Is 15683 With Safety Release Valve, Nrv And Ce Approved Valve.Dry Powder Is 14609 With Its Standard Accessories As Per Specification & Standards Item72 3 Each 74 2.21 Labour Charges Towards Installation Of Co2 Type Hand 9 Kg With Wheel As Per Is 2878 Complete With Hose, Screw Valve, Co2 Gas Is 1522, Cylinder Is 7285, Valve Is 3224.Tested At 250Kg / Cm2 All As Per The Specification & Standards. Item73 2 Each 75 2.22 Labour Charges Towards Installation Of Material Required For Earthing Complete With Galvanised Earth Plate Electrode 600X600x6 Mm Thick Buried Directly In Ground Vertically ( Earth Pit Not Less Than 2.25 Mtr Deep Below Normal Ground Level ) With Top Edge Of Plate Note Less Than 1.5Mtr Below Ground Level Connected To Including Gi Strip 32X6mm Size Protected With G I Medium Grade Pipe 40Mm Dia For Earth Electrode Up To Test Point Or Up To 7.5 Mtr Whichever Is Less By Means Of Gi Nuts, Bolts, Check Nuts And Washer. Funnel, With Necessary Charcoal, Salt Etc And Material Required For Pcc Pit And Rcc Cover ( 1:2:4 Type B1 ) And Funnel With Necessary Charcoal, Salt Etc, Complete All As Per Electrical Plate No.3 Of Ssr Part-1 Including Testing For Required Value. Item74 21 Each 76 2.23 Labour Charges Towards Installation Of 32 X 6 Mm Thick Gi Strip As Per The Specification & Standards. Item75 150 Rmeter 77 2.24 Labour Charge Towards Installation Of Materials Required For Earthing Complete With Copper Earth Plate Electrode 600X600x3.15 Mm Thick Buried Directly In Ground Vertically ( Earth Pit Not Less Than 2.25 Mtr Deep Below Normal Ground Level ) With Top Edge Of Plate Not Less Than 1.5 Mtr Below Normal Ground Level Connected To And Including Copper Strip 20X3 Mm Size Protected With G I Medium Grade Pipe 40Mm Dia For Earth Electrode Up To Test Point Or Up To 7.5 Mtr Whichever Is Less By Means Of Copper Nuts, Bolts, Check Nuts And Washers Including Earth Work, Excavation, Pcc Pit And Rcc Cover ( 1:2:4 Type B1 ) And Funnel, With Necessary Charcoal, Salt Etc;Complete All As Per Electrical Plate No.3 Of Ssr Part - I Including Testing For Required Value Complete All As Specified And Directed ( For Scada System ) Item76 4 Each 78 2.25 Labour Charges Towards Installation Of Test Terminal Point Block Made Of Gun Metal Or Phosporous Bronze Of Size 75X75x25 Mm Including 3 Nos Of 8 Mm Dia Screws As Per The Specification & Standards. Item77 10 Each 79 2.26 Labour Charges Towards Installation Of Danger Notice Plate Of 1.6Mm Thick Mild Steel, Vitreous Enaneled White With Letters, Figures And Conventional Skull And Bones In Signal Red Colour And Fixed With Ms Clamps, Bolts And Nuts Of Approved Size For Ht , 25X20cm Complete All As Per The Specification & Standards Item78 10 Each 80 2.27 Labour Charges Towards Installation Of Synthetic Rubber Mat Of 2Mx1mx10mm For 420V As Per The Specification & Cea / Cei / Ksebl / Mes Standards. Item79 3 Each 81 2.28 Labour Charges Towards Installation Of Synthetic Rubber Mat Of 2Mx1mx19mm For 11Kv As Per The Specification & Cea / Cei / Ksebl / Mes Standards. Item80 4 Each 82 2.29 Labour Charges Towards Installation Of Cable Joining Kit For 11Kv ( Earthed ) Grade Cable For Indoor Termination Heat Shrink Type Joint Complete With Joining Material And Accessories Suitable For 3 Core Xlpe Armoured Aluminium Conductor Cable Of Size 240 Sqmm To 300 Sqmm Complete All As Per The Specification & Ksei Standards. Item81 6 Each 83 2.3 Labour Charges Towards Installation Of Cable Joining Kit For 11Kv ( Earthed ) Grade Cable For Indoor Termination Heat Shrink Type Joint Complete With Joining Material And Accessories Suitable For 3 Core Xlpe Armoured Aluminium Conductor Cable Of Size 70 Sqmm To 95 Sqmm Complete All As Per The Specification & Ksei Standards. Item82 8 Each 84 2.31 Labour Charges Towards Installation Of Cable Joining Kit For 11 Kv ( Earthed ) Grade Cable For Indoor End Termination Heat Shrink Type Joint Complete With Joining Material And Accessories Suitable For 3 Core Xlpe Armoured Aluminium Conductor Cable Of Size 70 Sqmm To 95 Sqmm Item83 2 Each 85 2.32 Labour Charges Towards Installation Of Non Pressure Np-2 Class Rcc Hume Pipe 150Mm Dia With Collar Jointed With Stiff Mixture Of Cm In 1:2 Including Excavation In Earth Work, Pcc Item84 30 Rmeter 86 2.33 Labour Charges Towards Installation Of Non Pressure Np-2 Class Rcc Hume Pipe 100Mm Dia With Collar Jointed With Stiff Mixture Of Cm In 1:2 Including Excavation In Earth Work, Pcc Item85 50 Rmeter 87 2.34 Labour Charges Towards Installation Of 100 Mm Dia Gi Pipe Light Grade For Cable Protection As Per N The Specification & Standards. Item86 50 Rmeter 88 2.35 Labour Charges Towards Installation Of 50 Mm Dia Gi Pipe Light Grade For Cable Protection As Per N The Specification & Standards. Item87 50 Rmeter 89 2.36 Labour Charges Towards Installation Of Pcc Cable Covers Class Hv, Type 1, Flat, Size 300Mm X 180Mm X 40Mm Item88 5000 Each 90 2.37 Labour Charges Towards Installation Of Pcc Cable Covers Class Lv, Type 1, Flat, Size 250Mm X 150Mm X 40Mm Item89 700 Each 91 2.38 Labour Charges Towards Installation Of Cable Route Indicator 15Cm Dia Made Out Of Cast Aluminium Duly Marked With Size And Type Of Cable Fixed On Isa 40X40x6mm Angle Iron Support Embedded Including In Pcc 1:2:4 Type B1 ( 300X300x400mm ) And Steel Surface Painted With Two Coats Of Anti Corrosive Paint Over A Coat Of Red Oxide Primer Including Necessary Earth Work Item90 40 Each 92 2.39 Labour Charges Towards Installation Of Outdoor Ms Base Frame Mounted Cubical Type Factory Made Lt Panel Board Suitable For 415V 3 Phase 4 Wire, 50Hz Non-Metalic Kiosk Double Door With The Required Provision For 3 Switch Gears And Control Gears Along With The Approved Make. Enclosed In A Modular / Combinable Thermoplastic Polycarbonate Panel Enclosure Which Should Be Shock Proof, Ip65 ( Weather Proof ) , Rust Proof, Dust Proof, Water Proof, Corrosion Proof Having Internally Embadded Gasket On The Lid And Cable Entry Knockouts On All Sides Or Using Cable Entry Flanges Of Size 300 X 450 X 170Mm Required Of The Lt Panel Complete Fabrication Shall Be Painted As Per Specification. Lt Panel Board Shall Be Complete With All Standard Accessories Including Selector Switches, Phase Indicating Lamps Control Fuse Unit, Mv Danger Notice Plate Numbered / Lettered And With Comprising The Following. Make: Hensel Or Equivalent Make In List Of Manufactures Item91 1 Job 93 2.4 Sl.Item No.1.47 Contd / .. Incoming: Mccb 160 A, 4 Pole, 25Ka-1 No. Including Cts, Digital Ammeter, Ass, Digital Volt Meter, Vss, Phase Indicating Lamps & Control Fuses / Mcbs Etc.. Nbus Bar: One Set Of Tp&N 300A, Aluminium Bus Bar E 91 Grade, 1100 V, Grade Duly Covered With Heat Shrinkable Sleeves Colour Coded Duly Fixed On Moulded Brackets-1 Set. Noutgoing: Separate Cubical Chamber With A Cable Alley Not Less Than 300 Mm Width For Installation / Connecting The Following Switch Gear: N ( I ) Mccb 63A, 4 Pole, 25Ka - 1 Nos N ( Ii ) Mcb Tp&N 32A, 16Ka - 2 Nos N ( Iii ) Mcb Spn 32A, 16 Ka - 3 Nos Item92 1 Job 94 2.41 Labour Charges Towards Installation Of Materials For Artistic Painting In Black Letters With Yellow Background For Solar Array Structures, Smbs, Dc Cable In / Out, Earth Chambers, Pcus, Transformers, Ups, Dbs Etc. Item93 1 Job 95 2.42 Labour Charges Towards Installation Of Lightning Protection System Item94 1 Job 96 2.43 Labour Charges Towards Excavation And Getting Out Hard / Loose Soil / Disintegrated Rock And Refilling Item95 500 Cumtr 97 2.44 Labour Charges Towards Soakage Pit Of Size 1.2M Dia , 3.0M Effective Depth Including Necessary Earthwork Item96 3 Each 98 2.45 Charges Towards Testing Of Energy Meter, Netmeter, Ct, Pt Etc Item97 1 Job 99 2.46 Charges Towards Obtaining Scheme Approval, Energisation Order Etc Of 2Mw Grid Tied Solar Power Plant At Nad, Aluva From Cei / Ksei Including Statuatory Fees Item98 1 Job 100 2.47 Charges Towards Any Other Item Required For Completing Above Work As Per Mes / Cea / Cei / Kseb / Ksei Standards Item99 1 Set

Key Value

Document Fees
INR 2000 /-
EMD
INR 43000.0 /-
Tender Value
INR 43 Lakhs /-

BOQ Items

Name of Work: Supply and installation of Electrical materials for 2 MW Soalr Power Plant at NAD
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply of Electrical Materials for 02MW Solar Power Plant Project at NAD, Aluva
2 1.01 Charges towards Supply of material required for installation,testing and commissioning of 1250KVA Solar Inverter duty transformer ,including all item etc,all as per the direction of Engineer in charge & IEC standards.Installation as per latest CEA/CEI/MES guidelines.Supply of (Transformers under the scope of Keltron) Cost inclusive of providing fencing etc extra as required. item1 2 Nos
3 1.02 Charges towards Supply of material required for installation ,testing and commissioning of 100KVA stepdown transformer ,including all item etc, all as per the direction of Engineer in charge & IEC standards.Installation as per latest CEA/CEI/MES guidelines.Supply of (Transformers under the scope of Keltron) Cost inclusive of providing fencing etc extra as required. item2 1 No
4 1.03 Charges towards Supply of material required for laying ,termination and commissioning of 3 core x 240sq mm XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured heavy duty with alumininum conductor ,11 KV (E) HT cable as per IS 7098 (part II)1985. for connecting HT Transformer to HT Panel to Meter panel to KSEB Grid including supply of cable.Cost inclusive of materials for Termination of cable,checking tightness of cable,testing sample of cable and whole length ,coordinating MES with sample evaluavation and testing as per MES standards etc as applicable .sand cushioning with dry river sand complete all as specified and as directed by MES. item3 350 RMeter
5 1.04 Charges towards Supply of material required for laying ,termination and commissioning of 3 core x 95sq mm XLPE insulated,screened PVC bedded galvanised steel strip or wire aemoured heavy duty with alumininum conductor ,11 KV (E) HT cable as per IS 7098 (part II)1985. for connecting HT Transformer to HT Panel including supply of cable.Cost inclusive of materials required for Termination of cable.(Min 2 nos of HT kit).checking tightness of cable,testing sample of cable and whole length ,coordinating MES with sample evaluavation and testing as per MES standards etc as applicable .sand cushioning with dry river sand complete all as specified and as directed by MES. item4 30 RMeter
6 1.05 Charges towards Supply of material required for sand cushioning with dry river sand complete all as directed as per MES standards including exacavation work required LT Cable and HT Cable work. item5 500 Cubic\nMeter
7 1.06 Charges towards Supply of material required for installation of HT Interface Meter (ABT) including Meter installed in totally enclosed.fully interlock ,metal clad power coated at MES sub station-1 & Providing suitable capacity (as per CMD) of CTs,PTs,relay,cable for interconnection,HT insulater etc all as per the specification & site condition. As per latest norms of KSEBL , Testing of Cts, PTS and ABt meter inclusive, cost inclusive of any additional work required for completion of this work as per KSEBL/CEI/MES direction. item6 1 Set
8 1.07 Charges towards Supply of HT 11KV Grid panel for Power evacuation and Grid interconnection systems at MRS NAD gate complete with breakers, CTs,PTS,VCB, metering panels relays ,TOD meter (HT Check meter) etc all as per design parameter with totally enclosed fully interlocked metal clad power coated enclosure complete modification/extension of existing HT panel at NAD shall be obtained from prior to install.CT/PT of metering panel shall be approved make of KSEBL and all as per guide lines given in the KSERC notification complete all as per specified and charges toward materials rquired for imstallation testing and commisioning of above panel as per MES/CEA/CEI/KSEBL standards. item7 1 Set
9 1.08 Charges towards supply of Addressable type fire alarm control panel complying with BS EN 54 Single loop panel of capacity from 99 detectors & 99 modules upto 200 detector. item8 1 Set
10 1.09 Charges towards supply of Detectors Complying with and type certified to EN-45 Addressable type multisensor detector with heat and smoke combination Photoelectric / Optical with base with self built intelligence as per IS: 11360 item9 10 Each
11 1.1 Charges towards supply of Addressable control module item10 3 Each
12 1.11 Charges towards supply of Addressable monitor module item11 3 Each
13 1.12 Charges towards supply of Short circuit isolators item12 3 Each
14 1.13 Charges towards supply of Addressable manual call point resettable type item13 3 Each
15 1.14 Charges towards supply of Addressable electronic sounder cum strobe complete all as specified and as directed. item14 2 Each
16 1.15 Charges towards supply of FRLS armoured copper cable 2 core 1.5 sqmm item15 250 RMeter
17 1.16 Charges towards supply of Battery operated LED display Lights (Exit signage) wall mounted with battery backup of 5 Hrs for Fire exit all as per Cat No : LSSR5W of CG or its equivalent make from list of makes. item16 3 Each
18 1.17 Charges towards Supply of duly painted MS pedestal stand for suspending fire buckets as per the specification. item17 1 Each
19 1.18 Charges towards Supply of Red painted MS fire bucket of 13 ltrs capacity of fire approved quality, filled with sand as per the specification & standards. item18 2 Each
20 1.19 Charges towards Supply of Foam Type Extinguisher Hand 9 kg all as per the Specification & standards item19 2 Each
21 1.2 Charges towards Supply of DCP type (ABC) 10 Kg designed/tested IS 15683 with Safety release valve, NRV and CE approved valve.Dry powder IS 14609 with its standard accessories as per specification & standards item20 3 Each
22 1.21 Charges towards Supply of CO2 type Hand 9 Kg with wheel as per IS 2878 complete with hose, screw valve, CO2 gas IS 1522, cylinder IS 7285,valve IS 3224.Tested at 250Kg/cm2 all as per the Specification & standards. item21 2 Each
23 1.22 Charges towards Supply of material required for Earthing complete with galvanised earth plate electrode 600x600x6 mm thick buried directly in ground vertically (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate note less than 1.5mtr below ground level connected to including GI strip 32x6mm size protected with G I medium grade pipe 40mm dia for earth electrode up to test point or \nup to 7.5 mtr whichever is less by means of GI nuts, bolts, check nuts and washer. funnel, with necessary charcoal, salt etc and material required for PCC pit and RCC cover ( 1:2:4 type B1) and funnel with necessary charcoal,salt etc, complete all as per electrical plate no.3 of SSR part-1 including testing for required value. item22 21 Each
24 1.23 Charges towards Supply of 32 x 6 mm thick GI Strip as per the specification & standards. item23 150 Rmeter
25 1.24 Earthing complete with copper earth plate electrode 600x600x3.15 mm thick buried directly in ground vertically (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground level connected to and including copper strip 20x3 mm size protected with G I medium grade pipe 40mm dia for earth electrode up to test point or up to 7.5 mtr whichever is less by means of copper nuts, bolts, check nuts and washers including earth work, excavation, PCC pit and RCC cover ( 1:2:4 type B1) and funnel, with necessary charcoal, salt etc;complete all as per electrical plate No.3 of SSR Part - I including testing for required value complete all as specified and directed (For SCADA system) item24 4 Each
26 1.25 Charges towards Supply of Test Terminal point block made of gun metal or phosporous bronze of size 75x75x25 mm including 3 nos of 8 mm dia screws as per the specification & standards. item25 10 Nos
27 1.26 Charges towards Supply of Danger notice plate of 1.6mm thick mild steel, vitreous enaneled white with letters,figures and conventional skull and bones in signal red colour and fixed with MS clamps,bolts and nuts of approved size for HT , 25x20cm complete all as per the specification & standards item26 10 Nos
28 1.27 Charges towards Supply of synthetic rubber mat of 2mx1mx10mm for 420V as per the specification & CEA/CEI/KSEBL/MES standards. item27 3 Each
29 1.28 Charges towards Supply of synthetic rubber mat of 2mx1mx19mm for 11KV as per the specification & CEA/CEI/KSEBL/MES standards. item28 4 Each
30 1.29 Charges towards Supply of Cable joining kit for 11KV (Earthed) grade cable for indoor termination Heat shrink type joint complete with joining material and accessories suitable for 3 Core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm complete all as per the specification & KSEI standards. item29 6 Nos
31 1.3 Charges towards Supply of Cable joining kit for 11KV (Earthed) grade cable for indoor termination Heat shrink type joint complete with joining material and accessories suitable for 3 Core XLPE armoured aluminium conductor cable of size 70 sqmm to 95 sqmm complete all as per the specification & KSEI standards. item30 8 Each
32 1.31 Charges towards Supply of Cable joining kit for 11 KV (Earthed) grade cable for indoor end termination Heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 sqmm to 95 sqmm item31 2 Each
33 1.32 Charges towards Supply of Non pressure NP-2 class RCC hume pipe 150mm dia with collar jointed with stiff mixture of CM in 1:2 including excavation in earth work, PCC item32 30 RMeter
34 1.33 Charges towards Supply of Non pressure NP-2 class RCC hume pipe 100mm dia with collar jointed with stiff mixture of CM in 1:2 including excavation in earth work, PCC item33 50 RMeter
35 1.34 Charges towards Supply of 100 mm dia GI Pipe Light grade for cable protection as per\n the specification & standards. item34 50 RMeter
36 1.35 Charges towards Supply of 50 mm dia GI Pipe Light grade for cable protection as per\n the specification & standards. item35 50 RMeter
37 1.36 Charges towards Supply of Digital Earth Resistance Tester Cambridge Instruments DET-2000 item36 1 Each
38 1.37 Charges towards Supply of Digital multimeter ( Make shall be of any ISI marked) item37 1 Each
39 1.38 Charges towards Supply of AC-DC Clamp Meter Amp range 1000DC, 800AC ( Make shall be of any ISI marked) item38 1 Each
40 1.39 Charges towards Supply of Digital megger- LV 500 v ( Make shall be of any ISI marked) item39 2 Each
41 1.4 Charges towards Supply of Digital thermometer (wall hanging) ( Make shall be of any ISI marked) item40 2 Each
42 1.41 Charges towards Supply of Digital megger – HV 10KV( Make shall be of any ISI marked) item41 1 Each
43 1.42 Charges towards Supply of Crimping tool with Dye range 50-400sq-mm cable, mechanical gear & hydraulic operated power, hand operated ( Make shall be of any ISI marked) item42 1 Each
44 1.43 Charges towards Supply of Crimping tool up to 6 sq-mm cable ( Make shall be of any ISI marked) item43 1 Each
45 1.44 Charges towards Supply of PCC Cable covers class HV, Type 1, flat, size 300mm x 180mm x 40mm item44 5000 Each
46 1.45 Charges towards Supply of PCC Cable covers Class LV, Type 1, flat, size 250mm x 150mm x 40mm item45 700 Each
47 1.46 Charges towards Supply of Cable route indicator 15cm dia made out of cast aluminium duly marked with size and type of cable fixed on ISA 40x40x6mm angle iron support embedded including in PCC 1:2:4 type B1 (300x300x400mm) and steel surface painted with two coats of anti corrosive paint over a coat of red oxide primer including necessary earth work item46 40 Each
48 1.47 Charges towards Supply of Outdoor MS base frame mounted cubical type factory made LT panel board suitable for 415V 3 phase 4 wire, 50HZ non-metalic kiosk double door with the required provision for 3 switch gears and control gears along with the approved make. Enclosed in a modular/combinable thermoplastic polycarbonate panel enclosure which should be shock proof, IP65 (weather proof), rust proof, dust proof, water proof, corrosion proof having internally embadded gasket on the lid and cable entry knockouts on all sides or using cable entry flanges of size 300 x 450 x 170mm required of the LT panel complete fabrication shall be painted as per specification. LT panel board shall be complete with all standard accessories including selector switches, phase indicating lamps control fuse unit, MV danger notice plate numbered/lettered and with comprising the following. Make: HENSEL or equivalent make in list of manufactures item47 1 Job
49 1.48 Sl.item No.1.47 Contd/.. Incoming: MCCB 160 A, 4 pole, 25KA-1 No. including CTs, Digital Ammeter, ASS, Digital Volt meter, VSS, Phase indicating lamps & control fuses/MCBs etc.. \nBus Bar: One set of TP&N 300A, aluminium bus bar E 91 grade, 1100 V, grade duly covered with heat shrinkable sleeves colour coded duly fixed on moulded brackets-1 Set.\nOutgoing: Separate cubical chamber with a cable alley not less than 300 mm width for installation/connecting the following switch gear:\n(i) MCCB 63A, 4 Pole, 25KA - 1 Nos\n(ii) MCB TP&N 32A, 16KA - 2 Nos\n(iii) MCB SPN 32A, 16 KA - 3 Nos item48 1 job
50 1.49 Charges towards Supply of materials for Artistic painting in black letters with yellow background for Solar array structures, SMB's, DC Cable In/out, Earth chambers, PCU's, Transformers, UPS, DB's etc. item49 1 Job
51 1.5 Charges towards Supply of materials for Lightening Protection System item50 1 Job
52 1.51 Charges towards Supply of materials for Soakage pit of size 1.2m dia , 3.0M item51 3 Each
53 2 Labour charges for Installation of materials for 02MW Solar Power Plant Project at NAD, Aluva item52 1 Each
54 2.01 Labour charges towards installation,testing and commissioning of 1250KVA Solar Inverter duty transformer ,including all item etc,all as per the direction of Engineer in charge & IEC standards.Installation as per latest CEA/CEI/MES guidelines.Supply of (Transformers under the scope of Keltron) Cost inclusive of providing fencing etc extra as required. item53 2 Each
55 2.02 Labour charges towards installation,testing and commissioning of 100KVA stepdown transformer ,including all item etc, all as per the direction of Engineer in charge & IEC standards.Installation as per latest CEA/CEI/MES guidelines.Supply of (Transformers under the scope of Keltron) Cost inclusive of providing fencing etc extra as required. item54 1 No
56 2.03 Labour charges towards installation,termination and commissioning of 3 core x 240sq mm XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured heavy duty with alumininum conductor ,11 KV (E) HT cable as per IS 7098 (part II)1985. for connecting HT Transformer to HT Panel to Meter panel to KSEB Grid including supply of cable.Cost inclusive of materials for Termination of cable,checking tightness of cable,testing sample of cable and whole length ,coordinating MES with sample evaluavation and testing as per MES standards etc as applicable .sand cushioning with dry river sand complete all as specified and as directed by MES. item55 350 RMeter
57 2.04 Labour charges towards installation,termination and commissioning of 3 core x 95sq mm XLPE insulated,screened PVC bedded galvanised steel strip or wire aemoured heavy duty with alumininum conductor ,11 KV (E) HT cable as per IS 7098 (part II)1985. for connecting HT Transformer to HT Panel including supply of cable.Cost inclusive of materials required for Termination of cable.(Min 2 nos of HT kit).checking tightness of cable,testing sample of cable and whole length ,coordinating MES with sample evaluavation and testing as per MES standards etc as applicable .sand cushioning with dry river sand complete all as specified and as directed by MES. item56 30 RMeter
58 2.05 Labour charges towards sand cushioning with dry river sand complete all as directed as per MES standards including exacavation work required LT Cable and HT Cable work. item57 500 Cubic\nMeter
59 2.06 Labour charges towards installation of HT Interface Meter (ABT) including Meter installed in totally enclosed.fully interlock ,metal clad power coated at MES sub station-1 & Providing suitable capacity (as per CMD) of CTs,PTs,relay,cable for interconnection,HT insulater etc all as per the specification & site condition. As per latest norms of KSEBL , Testing of Cts, PTS and ABt meter inclusive, cost inclusive of any additional work required for completion of this work as per KSEBL/CEI/MES direction. item58 1 Set
60 2.07 Labour charges towards installation of HT 11KV Grid panel for Power evacuation and Grid interconnection systems at MRS NAD gate complete with breakers, CTs,PTS,VCB, metering panels relays ,TOD meter (HT Check meter) etc all as per design parameter with totally enclosed fully interlocked metal clad power coated enclosure complete modification/extension of existing HT panel at NAD shall be obtained from prior to install.CT/PT of metering panel shall be approved make of KSEBL and all as per guide lines given in the KSERC notification complete all as per specified and charges toward materials rquired for imstallation testing and commisioning of above panel as per MES/CEA/CEI/KSEBL standards. item59 1 Set
61 2.08 Labour charges towards installation of Addressable type fire alarm control panel complying with BS EN 54 Single loop panel of capacity from 99 detectors & 99 modules upto 200 detector. item60 1 Set
62 2.09 Labour charges towards installation of Detectors Complying with and type certified to EN-45 Addressable type multisensor detector with heat and smoke combination Photoelectric / Optical with base with self built intelligence as per IS: 11360 item61 10 Each
63 2.1 Labour charges towards installation of Addressable control module item62 3 Each
64 2.11 Labour charges towards installation of Addressable monitor module item63 3 Each
65 2.12 Labour charges towards installation of Short circuit isolators item64 3 Each
66 2.13 Labour charges towards installation of Addressable manual call point resettable type item65 3 Each
67 2.14 Labour charges towards installation of Addressable electronic sounder cum strobe complete all as specified and as directed. item66 2 Each
68 2.15 Labour charges towards installation of FRLS armoured copper cable 2 core 1.5 sqmm item67 250 RMeter
69 2.16 Labour charges towards installation of Battery operated LED display Lights (Exit signage) wall mounted with battery backup of 5 Hrs for Fire exit all as per Cat No : LSSR5W of CG or its equivalent make from list of makes. item68 3 Each
70 2.17 Labour charges towards installation of duly painted MS pedestal stand for suspending fire buckets as per the specification. item69 1 Each
71 2.18 Labour charges towards installation of Red painted MS fire bucket of 13 ltrs capacity of fire approved quality, filled with sand as per the specification & standards. item70 2 Each
72 2.19 Labour charges towards installation of Foam Type Extinguisher Hand 9 kg all as per the Specification & standards item71 2 Each
73 2.2 Labour charges towards installation of DCP type (ABC) 10 Kg designed/tested IS 15683 with Safety release valve, NRV and CE approved valve.Dry powder IS 14609 with its standard accessories as per specification & standards item72 3 Each
74 2.21 Labour charges towards installation of CO2 type Hand 9 Kg with wheel as per IS 2878 complete with hose, screw valve, CO2 gas IS 1522, cylinder IS 7285,valve IS 3224.Tested at 250Kg/cm2 all as per the Specification & standards. item73 2 Each
75 2.22 Labour charges towards installation of material required for Earthing complete with galvanised earth plate electrode 600x600x6 mm thick buried directly in ground vertically (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate note less than 1.5mtr below ground level connected to including GI strip 32x6mm size protected with G I medium grade pipe 40mm dia for earth electrode up to test point or up to 7.5 mtr whichever is less by means of GI nuts, bolts, check nuts and washer. funnel, with necessary charcoal, salt etc and material required for PCC pit and RCC cover ( 1:2:4 type B1) and funnel with necessary charcoal,salt etc, complete all as per electrical plate no.3 of SSR part-1 including testing for required value. item74 21 Each
76 2.23 Labour charges towards installation of 32 x 6 mm thick GI Strip as per the specification & standards. item75 150 Rmeter
77 2.24 Labour charge towards installation of materials required for Earthing complete with copper earth plate electrode 600x600x3.15 mm thick buried directly in ground vertically (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground level connected to and including copper strip 20x3 mm size protected with G I medium grade pipe 40mm dia for earth electrode up to test point or up to 7.5 mtr whichever is less by means of copper nuts, bolts, check nuts and washers including earth work, excavation, PCC pit and RCC cover ( 1:2:4 type B1) and funnel, with necessary charcoal, salt etc;complete all as per electrical plate No.3 of SSR Part - I including testing for required value complete all as specified and directed (For SCADA system) item76 4 Each
78 2.25 Labour charges towards installation of Test Terminal point block made of gun metal or phosporous bronze of size 75x75x25 mm including 3 nos of 8 mm dia screws as per the specification & standards. item77 10 Each
79 2.26 Labour charges towards installation of Danger notice plate of 1.6mm thick mild steel, vitreous enaneled white with letters,figures and conventional skull and bones in signal red colour and fixed with MS clamps,bolts and nuts of approved size for HT , 25x20cm complete all as per the specification & standards item78 10 Each
80 2.27 Labour charges towards installation of synthetic rubber mat of 2mx1mx10mm for 420V as per the specification & CEA/CEI/KSEBL/MES standards. item79 3 Each
81 2.28 Labour charges towards installation of synthetic rubber mat of 2mx1mx19mm for 11KV as per the specification & CEA/CEI/KSEBL/MES standards. item80 4 Each
82 2.29 Labour charges towards installation of Cable joining kit for 11KV (Earthed) grade cable for indoor termination Heat shrink type joint complete with joining material and accessories suitable for 3 Core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm complete all as per the specification & KSEI standards. item81 6 Each
83 2.3 Labour charges towards installation of Cable joining kit for 11KV (Earthed) grade cable for indoor termination Heat shrink type joint complete with joining material and accessories suitable for 3 Core XLPE armoured aluminium conductor cable of size 70 sqmm to 95 sqmm complete all as per the specification & KSEI standards. item82 8 Each
84 2.31 Labour charges towards installation of Cable joining kit for 11 KV (Earthed) grade cable for indoor end termination Heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 sqmm to 95 sqmm item83 2 Each
85 2.32 Labour charges towards installation of Non pressure NP-2 class RCC hume pipe 150mm dia with collar jointed with stiff mixture of CM in 1:2 including excavation in earth work, PCC item84 30 Rmeter
86 2.33 Labour charges towards installation of Non pressure NP-2 class RCC hume pipe 100mm dia with collar jointed with stiff mixture of CM in 1:2 including excavation in earth work, PCC item85 50 Rmeter
87 2.34 Labour charges towards installation of 100 mm dia GI Pipe Light grade for cable protection as per\n the specification & standards. item86 50 Rmeter
88 2.35 Labour charges towards installation of 50 mm dia GI Pipe Light grade for cable protection as per\n the specification & standards. item87 50 Rmeter
89 2.36 Labour charges towards installation of PCC Cable covers class HV, Type 1, flat, size 300mm x 180mm x 40mm item88 5000 Each
90 2.37 Labour charges towards installation of PCC Cable covers Class LV, Type 1, flat, size 250mm x 150mm x 40mm item89 700 Each
91 2.38 Labour charges towards installation of Cable route indicator 15cm dia made out of cast aluminium duly marked with size and type of cable fixed on ISA 40x40x6mm angle iron support embedded including in PCC 1:2:4 type B1 (300x300x400mm) and steel surface painted with two coats of anti corrosive paint over a coat of red oxide primer including necessary earth work item90 40 Each
92 2.39 Labour charges towards installation of Outdoor MS base frame mounted cubical type factory made LT panel board suitable for 415V 3 phase 4 wire, 50HZ non-metalic kiosk double door with the required provision for 3 switch gears and control gears along with the approved make. Enclosed in a modular/combinable thermoplastic polycarbonate panel enclosure which should be shock proof, IP65 (weather proof), rust proof, dust proof, water proof, corrosion proof having internally embadded gasket on the lid and cable entry knockouts on all sides or using cable entry flanges of size 300 x 450 x 170mm required of the LT panel complete fabrication shall be painted as per specification. LT panel board shall be complete with all standard accessories including selector switches, phase indicating lamps control fuse unit, MV danger notice plate numbered/lettered and with comprising the following. Make: HENSEL or equivalent make in list of manufactures item91 1 Job
93 2.4 Sl.item No.1.47 Contd/.. Incoming: MCCB 160 A, 4 pole, 25KA-1 No. including CTs, Digital Ammeter, ASS, Digital Volt meter, VSS, Phase indicating lamps & control fuses/MCBs etc.. \nBus Bar: One set of TP&N 300A, aluminium bus bar E 91 grade, 1100 V, grade duly covered with heat shrinkable sleeves colour coded duly fixed on moulded brackets-1 Set.\nOutgoing: Separate cubical chamber with a cable alley not less than 300 mm width for installation/connecting the following switch gear:\n(i) MCCB 63A, 4 Pole, 25KA - 1 Nos\n(ii) MCB TP&N 32A, 16KA - 2 Nos\n(iii) MCB SPN 32A, 16 KA - 3 Nos item92 1 job
94 2.41 Labour charges towards installation of materials for Artistic painting in black letters with yellow background for Solar array structures, SMB's, DC Cable In/out, Earth chambers, PCU's, Transformers, UPS, DB's etc. item93 1 Job
95 2.42 Labour charges towards Installation of Lightning protection system item94 1 Job
96 2.43 Labour charges towards Excavation and getting out hard/loose soil/disintegrated rock and refilling item95 500 CuMtr
97 2.44 Labour charges towards Soakage pit of size 1.2m dia , 3.0M effective depth including necessary earthwork item96 3 Each
98 2.45 Charges towards Testing of Energy Meter, NetMeter, CT, PT etc item97 1 Job
99 2.46 Charges towards obtaining Scheme approval, Energisation order etc of 2MW Grid Tied Solar Power Plant at NAD, Aluva from CEI/KSEI including statuatory fees item98 1 Job
100 2.47 Charges towards any other item required for completing above work as per MES/CEA/CEI/KSEB/KSEI standards item99 1 Set
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy