Military Engineer Services-MES has published Completion Of Incomplete Work Of Special Repair For Replacement/Upgradation Of Old Vintage Transformers And Water Supply Pumping Sets At Various Location Under Ge ( 859 ) Ews. Submission Date for this Tender is 26-04-2021. Transformer Supply Tenders in TENGA VALLEY Arunachal Pradesh. Bidders can get complete Tender details and download the document.
Nature of Work : Completion of incomplete work of Special repair for replacement/upgradation of old vintage Transformers and water supply pumping sets at various locations under GE 859 EWS. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Taking down old transformer of any size, make & capacity from site including disconnecting HT cable from two pole structure, HV side terminal /LT cable from LT panel, LV side terminal incl removing earthings form body and terminals complete and the same will be deposited to MES store yard complete all as directed. | 4 | JOB | |
2 | 2 | Disconnecting existing serviceable transformer 500 KVA capacity complete and shifting to new location within 500 mtr distance including re-installation, connecting, testing and commissioning as directed.\nNote :- Necessary T&P for shifting of transformer including dehydration of oil and top up of transformer oil are deemed to be included in the item rate. | 1 | EACH JOB | |
3 | 3 | Supply , installation, testing and commissioning of step down transformer, out door type, mounted on PCC platform of height 1.5m, copper wound, HT-11 KV 3 phase, LT 433 volts 3 phase 4 wire of capacity 400 KVA, with off load tap changing arrangement on HT side to vary secondary voltage up to (+) 5 % to \n(-)10% in steps 2.5 % variation in HV and with standard fittings such as dial type temparature gauge for reading maximum temperatur, conservator oil level indicator, drain out valve, silica gel breather, explosion vent diaphragm, all as per IS:1180 (Part-I) : 2014, confirming to energy efficiency level 3, including filling of new transformer oil, having dielectric strength not less than 40 KV (RMS) with gap of 2.5 mm, conforming to IS :335-1993 and including necessary fixing of foundation bolts, nuts, washers etc complete all as specified and directed. (Note :-PCC work for the mounting platform will be measured and paid under respective item of schedule) | 2 | EACH | |
4 | 4 | Supply , installation, testing and commissioning of step down transformer, out door type, mounted on PCC platform of height 1.5m, copper wound, HT-11 KV 3 phase, LT 433 volts 3 phase 4 wire of capacity 500 KVA, with off load tap changing arrangement on HT side to vary secondary voltage up to (+) 5 % to (-)10% in steps 2.5 % variation in HV and with standard fittings such as dial type temparature gauge for reading maximum temperatur, conservator oil level indicator, drain out valve, silica gel breather, explosion vent diaphragm, all as per IS:1180 (Part-I) : 2014, confirming to energy efficiency level 3, including filling of new transformer oil, having dielectric strength not less than 40 KV (RMS) with gap of 2.5 mm, conforming to IS :335-1993 and including necessary fixing of foundation bolts, nuts, washers etc complete all as specified and directed. (Note :-PCC work for the mounting platform will be measured and paid under respective item of schedule) | 2 | EACH | |
5 | 5 | Supply , installation, testing and commissioning of step down transformer, out door type, mounted on PCC platform of height 1.5m, copper wound, HT-11 KV 3 phase, LT 433 volts 3 phase 4 wire of capacity 750 KVA, with off load tap changing arrangement on HT side to vary secondary voltage up to (+) 5 % to (-)15% in steps 2.5 % of HV and with standard fittings such as dial type temparature gauge for reading maximum temperatur, conservator oil level indicator, drain out valve, silica gel breather, explosion vent diaphragm, all as per IS:1180 (Part-I) : 2014, confirming to energy efficiency level 3, including filling of new transformer oil, having dielectric strength not less than 40 KV (RMS) with gap of 2.5 mm, conforming to IS :335-1993 and including necessary fixing of foundation bolts, nuts, washers etc complete all as specified and directed. | 1 | EACH | |
6 | 6 | Disconnecting /taking out existing unserviceable /damaged HT underground cable of any size, any type from trenches/ ducts or from pole etc., complete all as directed. | 211 | RM | |
7 | 7 | Excavation in trenches not exceeding 1.5m wide and not exc 1.5 m depth in hard /dense soil and getting out complete all as directed. | 46.45 | CUM | |
8 | 8 | Returning filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm thick in hard/dense soil complete all as specified and directed. | 28.2 | CUM | |
9 | 9 | Removing excavated surplus material not exc 50 mtrs and deposited where directed at a level not exc 1.5 mtrs above the starting point complete all as specified and directed. | 14.3 | CUM | |
10 | 10 | Material and labour for sand cushioning for cable protection using clean dry sand complete all as specified and directed. | 14.7 | CUM | |
11 | 11 | M&L for unreinforced precast concrete cable covers class HV, type 1 of size 300mmx 180mm x40mm thick complete all as specified and directed. | 814 | EACH | |
12 | 12 | Supply and fixing GI pipe light grade 80 mm dia, ISI marked of required length for protection of cables laid in trenches or fixed along with the pole complete including necessary MS clamps, nuts bolts and washers etc all as specified & as directed. | 56 | RM | |
13 | 13 | Supply, laying ,testing , jointing and commissioning XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty), with stranded aluminum conductor, 11000 volts grade, suitable for earthed system, of cross sectional area 120 sqmm 3 core, laid in pipe, trenches/ducts, on pole etc complete all as specified and directed. \n | 240 | RM | |
14 | 14 | Supply, laying, testing and commissioning cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor,11000 volts grade, cross sectional area 185 Sqmm x 3 core. laid in pipe, trenches/ducts, on pole etc complete all as specified and directed. | 35 | RM | |
15 | 15 | M&L Cable jointing kit for 11 KV grade cable for indoor termination cold shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 SQ MM to 185 SQMM and testing after jointing all as specified and directed. \nMake :- 3M/Raychem RPG/Densons | 5 | EACH | |
16 | 16 | M&L Cable jointing kit for 11 KV grade cable for outdoor termination cold shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 SQ MM to 185 SQMM and testing after jointing all as specified and directed. \nMake :- 3M/Raychem RPG/Densons | 5 | EACH | |
17 | 17 | Supply, installation, commissioning and testing LT Panel board factory made CPRI approved of suitable size as approved by GE for 3 phase 4 wire, 415 Volts AC Supply, indoor cubical type, dust and vermin proof, floor block mounting , made out of 2.00 mm thick CRCA sheet with using 50mmx50mmx6 mm angle iron frame in base as legs and supports and length of legs not less than 450 mm, powder coated paint of approved colour all over steel surfaces complete with separate compartment of suitable shape and size with shutter and push type locking arrangement, cable alleys with and including locking key for each switch gear, including PCC 1:2:4 type B-1 work for fixing panel legs as per instruction of Engineer-in- Charge and 1200 Amps aluminium bus bar 3 Phase and neutral supported with DMC insulators, colour coded with heat shrinkable sleeve and including the following accessories :- \nNote \n(i) Making of electrical connections with existing LT cables by providing necessary cromium plated glands, Aluminium lugs as per the requirement at site is deemed to be included in the item rate\n(ii) Layout sketch of the Panel board shall be submitted by the contractor and get approved from GE before placing the order to the firm.\n(iii) Opening for natural ventilation shall be provided in the panel.\n(i) Incoming :- (a) ACB 800 Amps, 4 pole, 415 Volts, 50 HZ, 50 KA breaking capacity, manual drawout type micro processor release, overload and short circuit protection complete -01 No. Make :- Legrand/ABB/Siemens\n(b) Ammeter digital electronic type size of 96 mmx96 mm, rating 0f 0-800 Amps, and inbuilt selector switch and current transformers of 800/05 -03 Nos and control wiring with PVC insulated unsheathed stranded copper conductor cable of size 2.5 Sqmm.\n(c ) Indicating lamps LED type for three phases -one set of 3 Nos\n(d) Voltmeter (0-500V) range digital electronic type with inbuilt selector switch -01 No. \n(ii) Outgoing :-\n(a) MCCB 400 Amps, 4 pole, 415 Volts thermo magnetic adjustable type with breaking capacity Icu= 35 KA -01 No. Make :- Legrand/ABB/Siemens\n(b ) MCCB 250 Amps, 4 pole, 415 Volts thermo magnetic adjustable type with breaking capacity Icu=35 KA -01 No. Make :- Legrand/ABB/Siemens\n(b ) MCCB 200 Amps, 4 pole, 415 Volts thermo magnetic adjustable type with breaking capacity Icu=35 KA -03 Nos Make :- Legrand/ABB/Siemens. | 1 | JOB | |
18 | 18 | Supply, installation, commissioning and testing LT Panel board factory made CPRI approved of suitable size as approved by GE for 3 phase 4 wire, 415 Volts AC Supply, indoor cubical type, dust and vermin proof, floor block mounting , made out of 2.00 mm thick CRCA sheet with using 50mmx50mmx6 mm angle iron frame in base as legs and supports and length of legs not less than 450 mm, powder coated paint of approved colour all over steel surfaces complete with separate compartment of suitable shape and size with shutter and push type locking arrangement, cable alleys with and including locking key for each switch gear, including PCC 1:2:4 type B-1 work for fixing panel legs as per instruction of Engineer-in- Charge and \n800 Amps aluminium bus bar 3 Phase and neutral supported with DMC insulators, colour coaded with heat shrinkable sleeve and including the following accessories :- \nNote \n(i) Making of electrical connections with existing LT cables by providing necessary cromium plated glands, Aluminium lugs as per the requirement at site is deemed to be included in the item rate\n(ii) Layout sketch of the Panel board shall be submitted by the contractor and get approved from GE before placing the order to the firm.\n(i) Incoming :- (a) MCCB 500 Amps, 4 pole, 415 Volts, 50 HZ, 50 KA breaking capacity, thermo magnetic adjustable type including extended terminals -01 No. \n(b) Ammeter digital electronic type size of 96 mmx96 mm, rating 0f 0-500 Amps, and inbuilt selector switch and current transformers of 500/05 -03 Nos and control wiring with PVC insulated unsheathed stranded copper conductor cable of size 2.5 Sqmm.\n(c ) Indicating lamps LED type for three phases -one set of 3 Nos\n(d) Voltmeter (0-500V) range digital electronic type with inbuilt selector switch -01 No. \n(ii) Outgoing :-\n(a ) MCCB 250 Amps, 4 pole, 415 Volts thermo magnetic adjustable type with breaking capacity Icu=35 KA -01 No.\n(b ) MCCB 200 Amps, 4 pole, 415 Volts thermo magnetic adjustable type with breaking capacity Icu=35 KA -01 No\n(c) Blank compartment for fixing of MCCBs -02 Nos | 2 | JOB | |
19 | 19 | Supply, installation, commissioning and testing LT Panel board factory made CPRI approved of suitable size as approved by GE for 3 phase 4 wire, 415 Volts AC Supply, outdoor cubical type, dust with vermin proof, floor block mounting, made out of 3.15mm thick CRCA sheet with using 50mmx50mmx6 mm angle iron frame in base as legs and supports and length of legs not less than 450 mm, powder coated paint of approved colour all over steel surfaces complete with separate compartment of suitable shape and size with shutter and push type locking arrangement, cable alleys with and including locking key for each switch gear, including PCC 1:2:4 type B-1 work for fixing panel legs as per instruction of Engineer-in- Charge and \n1800 Amps copper bus bar 3 Phase and neutral supported with DMC insulators, colour coaded with heat shrinkable sleeve and including the following accessories :- \nNote \n(i) Making of electrical connections with existing LT cables by providing necessary cromium plated glands, Aluminium lugs as per the requirement at site is deemed to be included in the item rate\n(ii) Layout sketch of the Panel board shall be submitted by the contractor and get approved from GE before placing the order to the firm.\n(iii) Opening for natural ventilation shall be provided in the panel.\n(i) Incoming :- (a) ACB 1250 Amps, 4 pole, 415 Volts, 50 HZ, 50 KA breaking capacity, manual drawout type micro processor release, overload and short circuit protection complete -01 No. Make :- Legrand/ABB/Siemens\n(b) Ammeter digital electronic type size of 96 mmx96 mm, rating 0f 0-1250 Amps, and inbuilt selector switch and current transformers of 1250/05 -03 Nos and control wiring with PVC insulated unsheathed stranded copper conductor cable of size 2.5 Sqmm.\n(c ) Indicating lamps LED type for three phases -one set of 3 Nos\n(d) Voltmeter (0-500V) range digital electronic type with inbuilt selector switch -01 No. \n(ii) Outgoing :-\n(a) MCCB 400 Amps, 4 pole, 415 Volts thermo magnetic adjustable type with breaking capacity Icu= 35 KA -05 No.s Make :- Legrand/ABB/Siemens\n(b ) Blank compartment suitable for fixing of MCCB -01 No | 1 | JOB | |
20 | 20 | Supply, installation, commissioning and testing LT Panel board factory made CPRI approved of suitable size as approved by GE for 3 phase 4 wire, 415 Volts AC Supply, outdoor cubical type, dust with vermin proof, floor block mounting, made out of 3.15mm thick CRCA sheet with using 50mmx50mmx6 mm angle iron frame in base as legs and supports and length of legs not less than 450 mm, powder coated paint of approved colour all over steel surfaces complete with separate compartment of suitable shape and size with shutter and push type locking arrangement, cable alleys with and including locking key for each switch gear, including PCC 1:2:4 type B-1 work for fixing panel legs as per instruction of Engineer-in- Charge and 1200 Amps aluminium bus bar 3 Phase and neutral supported with DMC insulators, colour coded with heat shrinkable sleeve and including the following accessories :- \nNote (i) Making of electrical connections with existing LT cables by providing necessary cromium plated glands, Aluminium lugs as per the requirement at site is deemed to be included in the item rate\n(ii) Layout sketch of the Panel board shall be submitted by the contractor and get approved from GE before placing the order to the firm.\n(iii) Opening for natural ventilation shall be provided in the panel.\n(i) Incoming :- (a) ACB 800 Amps, 4 pole, 415 Volts, 50 HZ, 50 KA breaking capacity, manual drawout type micro processor release, overload and short circuit protection complete -01 No. Make :- Legrand/ABB/Siemens\n(b) Ammeter digital electronic type size of 96 mmx96 mm, rating 0f 0-800 Amps, and inbuilt selector switch and current transformers of 800/05 -03 Nos and control wiring with PVC insulated unsheathed stranded copper conductor cable of size 2.5 Sqmm.\n(c ) Indicating lamps LED type for three phases -one set of 3 Nos\n(d) Voltmeter (0-500V) range digital electronic type with inbuilt selector switch -01 No. \n(ii) Outgoing :-\n(a) MCCB 315/320 Amps, 4 pole, 415 Volts thermo magnetic adjustable type with breaking capacity Icu= 35 KA -03 No.s Make :- Legrand/ABB/Siemens\n(b ) MCCB 160 Amps, 4 pole, 415 Volts thermo magnetic adjustable type with breaking capacity Icu= 35 KA -01 No. Make :- Legrand/ABB/Siemens\n | 1 | JOB | |
21 | 21 | Supply, installation, commissioning and testing LT Panel board factory made CPRI approved of suitable size as approved by GE for 3 phase 4 wire, 415 Volts AC Supply, indoor cubical type, dust and vermin proof, floor block mounting , made out of 2.00 mm thick CRCA sheet with using 50mmx50mmx6 mm angle iron frame in base as legs and supports and length of legs not less than 450 mm, powder coated paint of approved colour all over steel surfaces complete with separate compartment of suitable shape and size with shutter and push type locking arrangement, cable alleys with and including locking key for each switch gear, including PCC 1:2:4 type B-1 work for fixing panel legs as per instruction of Engineer-in- Charge and 1200 Amps aluminium bus bar 3 Phase and neutral supported with DMC insulators, colour coded with heat shrinkable sleeve and including the following accessories :- \nNote (i) Making of electrical connections with existing LT cables by providing necessary cromium plated glands, Aluminium lugs as per the requirement at site is deemed to be included in the item rate\n(ii) Layout sketch of the Panel board shall be submitted by the contractor and get approved from GE before placing the order to the firm.\n(iii) Opening for natural ventilation shall be provided in the panel.\n(i) Incoming :- (a) ACB 800 Amps, 4 pole, 415 Volts, 50 HZ, 50 KA breaking capacity, manual drawout type micro processor release, overload and short circuit protection complete -01 No. Make :- Legrand/ABB/Siemens\n(b) Ammeter digital electronic type size of 96 mmx96 mm, rating 0f 0-800 Amps, and inbuilt selector switch and current transformers of 800/05 -03 Nos and control wiring with PVC insulated unsheathed stranded copper conductor cable of size 2.5 Sqmm.\n(c ) Indicating lamps LED type for three phases -one set of 3 Nos\n(d) Voltmeter (0-500V) range digital electronic type with inbuilt selector switch -01 No. \n(ii) Outgoing :-\n(a) MCCB 350 Amps, 4 pole, 415 Volts thermo magnetic adjustable type with breaking capacity Icu= 35 KA -02 No.s Make :- Legrand/ABB/Siemens\n(b ) MCCB 200 Amps, 4 pole, 415 Volts thermo magnetic adjustable type with breaking capacity Icu= 35 KA -01 No. Make :- Legrand/ABB/Siemens\n(c) Blank compartment suitable for fixing of MCCB-01 No\n | 1 | JOB | |
22 | 22 | Taking down & disconnecting old UNSV LT panels from existing position of different capacity including all accessories from panels complete including making good to the disturbed surfaces all as specified and directed. | 2 | EACH | |
23 | 23 | Material & labour for earthing complete with Galvanised Steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground vertically to depth not less than 2.25 m below the ground level with top edge of earth plate at a depth not less than 1.5 m below the ground level connected to galvanised Steel Earth strip of 32x6 mm earth lead by means of bolts, nuts check nuts and washers made of galvanised steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) Type C1, precast RCC (1:2:4) Type B-1 cover slab 54x54x55 CM reinforced with 8 mm dia TMT bars @ 150mm C/C both ways with one handle for lifting, made out of 8mm dia MS bar embedded in pre-cast cover slab, funnel ,wire mesh, 20 mm bore galvanised or steel pipe(medium grade) for watering, charcoal and salt in alternate layers 40mm bore galvanised steel tubing light grade for protection to earth lead connection, test point, necessary exavation and earth work in any type of soil and including necessary testing complete all as shown on electrical plate No 3 of SSR Part-I (2009).\nNote :- Main earthing lead from earth electrode to test point up to 7.5 metre included in the item rate. | 32 | Each Job | |
24 | 24 | Dismantling carefully cylinder head, piston assembly, cylinder liner, radiator inlet & exhaust manifold, turbo charger, silencer and other accessories for Engine of capacity 25 BHP to 40 BHP Make - Kirloskar by authorised service centre complete all as directed .\nNote :- 1. Necessary transportation from site to agency and back is deemed to be included in the item rate.\n2. Replacement of unserviceable parts shall be paid separately as 'Supply only' under relevant item of schedule.\n3. Before dismantling of engine a Board of Officer shall be convened by the accepting officer to ascertain the unserviceable parts. | 6 | EACH JOB | |
25 | 25 | Top overhualing of Diesel engine 25 BHP to 40 BHP Make : Kirloskar as per manufacturer's instruction including replacement of all defective parts required for making smooth functional of the Engine by authorised service centre complete all as specified and directed.\nNote :- Replacement of unserviceable parts shall be paid separately as 'Supply only' under relevant item of schedule. | 6 | EACH JOB | |
26 | 26 | Overhauling and calibration of fuel pump by authorised service centre including replacement of injector nozzle including worn out parts i.e delivery valve, pump plunger, nozzle spring adjustment screws etc all as specified and directed .\nNote :- Replacement of unserviceable parts shall be paid separately as 'Supply only' under relevant item of schedule. | 6 | EACH JOB | |
27 | 27 | Repair and calibration of injector assembly including replacement of nozzle, spring, barrel plunger, injector cup complete and refitting to original position duly changing the worn out nut, bolts/studs etc complete by authorised service centre , all as specified and directed .\nNote :- Replacement of unserviceable parts shall be paid separately as 'Supply only' under relevant item of schedule. | 6 | EACH JOB | |
28 | 28 | Opening of dynamo assembly by authorised service centre , replacement of wornout armature, carbon brushes and bushes complete and refixing all the components in it's original position with necessary screws, nuts & bolts all as directed .\nNote :- Replacement of unserviceable parts shall be paid separately as 'Supply only' under relevant item of schedule. | 6 | EACH JOB | |
29 | 29 | Repairs to cylinder head of Diesel engine 25 BHP to 40 BHP Make : Kirloskar by authorised service centre , shifting of clyinder head to workshop for machine work including grinding of inlet exhaust valve,fitting of valve guide,valve seat,facing,turning,polishing etc.\nNote :- Replacement of unserviceable parts shall be paid separately as 'Supply only' under relevant item of schedule. | 6 | SET | |
30 | 30 | Supply only the following parts/components for overhauling of Diesel Engine Make : Kirloskar \n(a) Cylinder head Gasket Pt No 4H.007.09.0.00 | 6 | SET | |
31 | 31 | (b) Valve guide for inlet & exhaust Pt No 4H.007.02.0.00 | 80 | EACH | |
32 | 32 | (c) Valve inlet Pt No 4H.007.05.0.00 | 48 | EACH | |
33 | 33 | (d) Valve Exhaust Pt No 02.022.13.0.00 . | 48 | EACH | |
34 | 34 | (e) Valve spring Pt No 02.022.13.0.00 . | 80 | EACH | |
35 | 35 | (f) Valve seat Pt No 06.631.02.0.00 | 80 | EACH | |
36 | 36 | (g) Cylinder linear Pt No 2H.008.01.0.00 | 24 | EACH | |
37 | 37 | (h) Piston ring set (standard) Pt No, 2H.009.30.0.00 | 24 | EACH | |
38 | 38 | (i) Gasket set complete | 6 | EACH | |
39 | 39 | (j) Set of 'O' ring Pt No 4H.087.07.0.00 | 6 | EACH | |
40 | 40 | (k) Thrust bearing | 6 | EACH | |
41 | 41 | (l) Set of oil seal Pt No 47.160.12.0.00 | 6 | EACH | |
42 | 42 | (m) Push rod Pt No 02.024.70.0.00 | 80 | EACH | |
43 | 43 | (n) CR bush bearing | 6 | SET | |
44 | 44 | (o) Battery with maintenance free 12 Volts, 180AH. Make :- Exide/Amaron (Amararaja)/AMCO | 2 | EACH | |
45 | 45 | (p) Belt 'V' Pt No 4H.069.01.0.00 | 12 | EACH | |
46 | 46 | (q) Piston Pt No 4H.180.10.0.00 | 24 | EACH | |
47 | 47 | (r) Valve solenoid Pt No 4H.150.10.0.00 | 6 | EACH | |
48 | 48 | Material and Labour for preparation of old painted body surface of alternator and engine by scraping and applying two coats of synthetic enamel paint including writing of SM No. and MES No. complete all as specified and directed. | 4 | EACH JOB | |
49 | 49 | Dismantling carefully by authorised service centre of complete cylinder head, piston assembly, cylinder liner, radiator inlet and exhaust manifold, turbo charger, silencer and other accessories for Diesel Engine of capacity 127 BHP Make - KIRLOSKAR complete all as specified and directed. \nNote :- 1. Necessary transportation from site to agency and back is deemed to be included in the item rate.\n2. Replacement of unserviceable parts shall be paid separately as 'Supply only' under relevant item of schedule. | 1 | EACH JOB | |
50 | 50 | Top overhualing of Diesel engine 127 BHP Make : Kirloskar as per manufacturer's instruction by authorised service centre including replacement of all defective parts required for making smooth functional of the DG set Engine complete all as specified and directed \nNote :- Replacement of unserviceable parts shall be paid separately as 'Supply only' under relevant item of schedule. | 1 | EACH JOB | |
51 | 51 | Overhauling and calibration of fuel pump of Diesel engine 127 BHP Make : Kirloskar by authorised service centre including replacement of injector nozzle including worn out parts i.e delivery valve, pump plunger, nozzle spring adjustment screws etc complete all as specified and directed . | 1 | EACH JOB | |
52 | 52 | Repair and calibration of injector assembly of Diesel engine 127 BHP Make : Kirloskar by authorised service centre including replacement of nozzle, spring, barrel plunger, injector cup complete and refitting to its original position duly changing the worn out nut, bolts/studs etc complete all as specified and directed .Note :- Replacement of unserviceable parts shall be paid separately as 'Supply only' under relevant item of schedule. | 6 | EACH JOB | |
53 | 53 | Opening of dynamo assembly of Diesel engine 127 BHP Make : Kirloskar by authorised service centre including replacement of wornout armature, carbon brushes and bushes complete and refixing all the components in it's original position with necessary screws, nuts & bolts complete all as directed .\nNote :- Replacement of unserviceable parts shall be paid separately as 'Supply only' under relevant item of schedule. | 1 | EACH JOB | |
54 | 54 | Repairs to cylinder head of Diesel engine 127 BHP Make : Kirloskar by authorised service centre , shifting of clyinder head to workshop for machine work including grinding of inlet exhaust valve,fitting of valve guide,valve seat,facing,turning,polishing etc.\nNote :- Replacement of unserviceable parts shall be paid separately as 'Supply only' under relevant item of schedule. | 1 | EACH JOB | |
55 | 55 | Takiing down carefully Radiator assembly from existing diesel engine 127 BHP Make: Kirloskar Transportation to authorised service centre of manufacture if directed by Engr-in-charge for repairs to fins,circulation ducts,upper and lower tank by brazing weilding for making leak proofing incl descaling internally the upper and lower tanks and incl transportation of repaired radiator from service centre to site and refixing the same in original position and testing complete of Diesel engine 127 all as specified and directed. | 1 | EACH JOB | |
56 | 56 | Supply only the following parts/components for overhauling of DG set of 127 BHP Make : Kirloskar :- \n(a) Cylinder head Gasket Pt No 6H.007.06.0.00 Make : Kirloskar | 1 | SET | |
57 | 57 | (b) Valve guide for inlet & exhaust Pt No 4H.007.02.0.00 | 12 | EACH | |
58 | 58 | (c) Valve inlet Pt No 4H.007.05.0.00 | 6 | EACH | |
59 | 59 | (d) Valve Exhaust Pt No 4H.007.06.0.00 | 6 | EACH | |
60 | 60 | (e) Valve spring Pt No 02.022.13.0.00 . | 12 | EACH | |
61 | 61 | (f) Valve Seal Pt No 06.631.02.0.00 | 12 | EACH | |
62 | 62 | (g) Turbo charger Pt No 6H.029.10.0.00 Make : Kirloskar | 1 | EACH | |
63 | 63 | (h) Cylinder liner Pt No 2H.008.01.0.00 | 6 | EACH | |
64 | 64 | (i) Piston ring set (standard) Pt No, 2H.009.30.0.00 Make : Kirloskar | 6 | EACH | |
65 | 65 | (j) Gasket set complete | 1 | EACH | |
66 | 66 | (k) Set of 'O' ring Pt No 3H.009.11.0.00 | 6 | EACH | |
67 | 67 | (l) Liner joint ring Pt No 2H.008.07.0.00 | 18 | EACH | |
68 | 68 | (m) Small end bush Pt No 4H.182.02.0.00 | 1 | EACH | |
69 | 70 | (n) Push rod Pt No 02.024.70.0.00 | 12 | EACH | |
70 | 71 | (o) High pressure pipe complete set Pt No 6H.009.70.0.00 | 4 | EACH | |
71 | 72 | (p) Large end bearing pair Pt No 6H.015.03.0.00 | 1 | SET | |
72 | 73 | (q) Belt 'V' (XPA 1250) cogged Pt No 4H.069.01.0.00 | 2 | EACH | |
73 | 74 | (r) Gear pump Pt No 2H.011.01.0.00 | 1 | EACH | |
74 | 75 | (s) Water pump assy Pt No 4H.052.20.0.00 | 1 | EACH | |
75 | 76 | (t) Piston Pt No 4H.180.10.0.00 | 6 | EACH | |
76 | 77 | (u) Stop solenoid assembly, 12V Pt No 4H.150.10.0.00 | 1 | EACH | |
77 | 78 | (v) Alternator assy 12V, 35A. Make - Lucas | 1 | EACH | |
78 | 79 | (w) Leak off pipe assembly Pt No 6H.023.01.0.00 | 1 | EACH | |
79 | 80 | (x) Fuel filter (1.1 liter) Pt No 48.117.10.0.00 | 4 | EACH | |
80 | 81 | (y) Gasket for exhaust manifold Pt No 4H.035.02.0.00 | 6 | EACH | |
81 | 82 | (z) Stud Pt No 50010/10x025 | 4 | EACH | |
82 | 83 | (aa) Socket head screw Pt No 50011/08x075 | 8 | EACH | |
83 | 84 | (ab) Flex Exhaust pipe(4" ID) Pt No F6.503.02.0.00 | 2 | EACH | |
84 | 85 | (ac) Lub oil inlet pipe Pt No 6H.034.04.0.00 | 1 | EACH | |
85 | 86 | (ad) Antivibration mounting Pt No F6.509.04.0.00 | 4 | EACH | |
86 | 87 | (ae) Main bearing 0.10 under size | 6 | PAIR | |
87 | 88 | (af) Big end bearing | 6 | PAIR | |
88 | 89 | Supply and laying anti vibration pad to base frame of 127 BHP Engine complete all as specified and directed. | 8 | EACH |